Design and Implementation of Smart Electrical Power Meter System


Mofeed Turky Rashid
Electrical Engineering Department, Engineering College,
University of Basrah, Basrah, Iraq.
mofid76@yahoo.com, mofeed.t.rashid@ieee.org

ABSTRACT
In recent years, increased importance of Smart Grid, which includes monitoring and
control the consumption of customers of electric power. In this paper, Wireless Smart
Electrical Power Meter has been designed and implemented which ZigBee wireless
sensor network (WSN) will be used for wireless electrical power meter
communication supported by PIC microcontroller which used for power unit
measurements. PIC microcontroller will be used for evaluating all electric power
parameters at costumer side like Vrms, Irms, KWh, and PF, and then all these
parameters will be send to base station through wireless network in order to be
calibrated and monitored.

Keywords: Electrical power meter, PIC Microcontroller, Wireless communications,


ZigBee.

‫نظام السلكي ذكي لقياس القدرة الكهربائية المستهلكة‬


‫مفيد تركي رشيد‬
،‫ كلية الهندسة‬،‫قسم الهندسة الكهربائية‬
.‫ العراق‬،‫ البصرة‬،‫جامعة البصرة‬
Mofid76@yahoo.com, mofeed.t.rashid@ieee.org

‫الملخص‬

‫ التي تشمل رصد ومراقبة استهالك العمالء للطاقة‬،"‫ زادت أهمية "الشبكة الذكية‬،‫في السنوات األخيرة‬
‫ تم تصميم وبناء نظام ال سلكي ذكي لقياس استهالك الطاقة الكهربائية حيث يستخدم‬،‫ في هذ ا البحث‬.‫الكهربائية‬
‫ ثم ارسال هذه القيم ال سلكيا الى المحطة‬Vrms, Irms, KWh, and PF ‫ لقياس‬PIC microcontroller
‫ حيث يتم معالجة البيانات ومراقبتها في‬ZigBee wireless sensor network (WSN) ‫الرئيسية باستخدام‬
.‫المحطة الرئيسية‬

I. Introduction power, and one of the most important


In fact, after the 1991 Gulf War, reasons and influencing is a distribution
electrical power has been severely network damaged and irregular
damaged in Iraq, where the destroying consumption of electric power. Now an
in the power plants exceeds 90% since urgent need for a comprehensive change
that time, Iraq is suffering from a real in the electrical distribution network
crisis in providing demand for electric and especially controlling the

1
Iraq J. Electrical and Electronic Engineering ‫اﻟﻤﺠﻠﺔ اﻟﻌﺮاﻗﻴﺔ ﻟﻠﻬﻨﺪﺳﺔ اﻟﻜﻬﺮﺑﺎﺋﻴﺔ واﻻﻟﻜﺘﺮوﻧﻴﺔ‬
Vol.10 No.1 , 2014 2014 ، 1 ‫ اﻟﻌﺪد‬، 10 ‫ﻡﺠﻠﺪ‬

consumption of customers of electrical  Manual meter reading: it is the


power and control must rely on an oldest method and it is weak because;
efficient and reliable system for for each house there is its own meter,
accurate readings which this reduces the this method required employers which
cost of measurements, in addition to taking readings of metrics manually,
providing an environment to monitor high cost of measurements because it
power factor which is an important needs a large number of staff, low
factor that increasing consumption or accuracy of readings, and difficult to
pressure on the network. Change in the monitor gauges that these devices
national distribution network must vulnerable to abuses. This method is
include providing a safe environment still used in Iraq so far.
for measurements and calculations, cost  IC card prepaid meter: it is used
which this matter will increase network pay-before use therefore it does not
efficiency and reduce consumption as need employers to reading meters on
well as to increase the value of the site. It has partially solved the problem
financial benefits. of manual meter reading because of no
The present system of energy metering need to be on site and less
as well as billing in Iraq, which uses measurements cost. But some problems
electromechanical energy meter is error exist in the actual operation process: IC
prone and it consumes more time and card meter is easily damaged due to its
labor. The conventional direct contact with users and no real-
electromechanical meters are being time monitoring. It also fails to avoid
replaced by new electronic meters to theft, damage, and the fault of a meter.
improve accuracy in meter reading.  Wire-line metering control system:
Still, the Iraqi power sector faces a in this method, the problem of
serious problem of revenue collection measurements in real time has been
for the actual electric energy supplied solved, so all meters can be monitored
owing to energy thefts and network and controlled in real time, also this
losses. One of the prime reasons is the type of meters can be connected to the
traditional billing system which is main station through telephone lines,
inaccurate many times, slow, costly, and power line, TV network, etc. therefore it
lack of flexibility as well as reliability has low measurements cost. But it has
[1]. In recent years, the developments in problems of long construction period,
electric power meter seem to provide high installation cost and maintenance
opportunities in implementing energy cost, expansion of the system upgrade
efficient metering technologies that are and compatibility with other network.
more precise, accurate, error free, etc.  Wireless meter reading system: it
[2-5]. is a process that the meter data is read
There are many methods for measuring and processed automatically via special
electrical power at home are manual equipment using wireless
meter, IC Card prepaid meter, wire-line communication and computer network
and wireless meter reading system: [6] technology. In this type of meters all

2
Iraq J. Electrical and Electronic Engineering ‫اﻟﻤﺠﻠﺔ اﻟﻌﺮاﻗﻴﺔ ﻟﻠﻬﻨﺪﺳﺔ اﻟﻜﻬﺮﺑﺎﺋﻴﺔ واﻻﻟﻜﺘﺮوﻧﻴﺔ‬
Vol.10 No.1 , 2014 2014 ، 1 ‫ اﻟﻌﺪد‬، 10 ‫ﻡﺠﻠﺪ‬

problems of real time measurement, meter has been used for each customer.
monitoring and control has been solved. These meters have been used to
Compared with the traditional meter measure the instantaneous electrical
reading, it not only effectively saves power per hour (KWh) and power factor
human resources, but also save the (PF) by using Microcontroller circuit
wiring cost and helps the management which sends the values of (KWh and
department find problems in time and PF) to the base station through ZigBee
take appropriate measures to deal with. wireless network technology.
Also, it has easy and low cost Normally base station located far away
installation, easy to extend, and more from costumers, in this case routing
secure than other methods [7][8]. device based on ZigBee wireless
In this paper, design and standard have been used in order to
implementation of Wireless Smart arrive the measurements of electrical
Electric Power Meter will be achieved power meter to the base station. The
which PIC microcontroller will be used final stage of the system is located at the
as the main part for evaluation base station, which the server based on
consumed electric power and PF. The ZigBee standard has been used to
rms value of voltage and current, receive all measurements of costumers
consumed electric power, and PF will and store these data in database for
be monitored through LCD at home and managing and analyzing.
also send these parameters through a
ZigBee wireless network to the base
In this paper, automatic electric power
station in order to monitor electric
meter has been designed in order to
power demand and evaluate consumed
measure instantaneous voltage and
electrical power fees.
current. The consumed power and PF
The outline of the paper is as follows.
has been calculated by PIC
The comprehensive structure of a
microcontroller which consumer
wireless meter system is described in
monitors these values at home by LCD
section II. The design and
while the same values sends to a base
implementation of the electrical power
station for monitoring and calculating
meter are explained in details in section
the consumed electric power. Xbee kit
III. System software is described in
has been used for ZigBee wireless
section IV. Result discussion in section
communication. The XBee/XBee-PRO
V, while conclusions are summarized in
RF Modules are designed to operate
section VI.
within the ZigBee protocol and support
II. The comprehensive structure of the unique needs of low-cost, low-
wireless meter system power wireless sensor networks. The
The comprehensive structure of wireless modules require minimal power and
electric power meter system is shown in provide reliable delivery of data
Fig. 1. The wireless electric power between remote devices.

3
Iraq J. Electrical and Electronic Engineering ‫اﻟﻤﺠﻠﺔ اﻟﻌﺮاﻗﻴﺔ ﻟﻠﻬﻨﺪﺳﺔ اﻟﻜﻬﺮﺑﺎﺋﻴﺔ واﻻﻟﻜﺘﺮوﻧﻴﺔ‬
Vol.10 No.1 , 2014 2014 ، 1 ‫ اﻟﻌﺪد‬، 10 ‫ﻡﺠﻠﺪ‬

House For alternating current, average power


can be calculated by V*I*cos(θ)، where
Router Wireless
Power Meter V and I are average rms voltage and
Server
House
current، and θ is the phase angle
Base station

Wireless
between the V and I. Instantaneous
Power Meter
sampling does not directly use power
Figure 1: Comprehensive structure of factor; the value of the phase angle is
smart wireless electrical power meter. essentially embedded in the
instantaneous current measurement.
III. Design of the electric power
Recovering the actual phase angle for
meter
the purpose of calculating and
In this section, the implementation of a
displaying the power factor can be done
basic watt hour meter using
separately and is very calculation
microcontroller circuit has been
intensive.
achieved. In the process, ADC with a
It is difficult for a microcontroller to
sample-and-hold circuit can effectively
make direct measurements when the
measure both voltage and load current.
supply voltage is 230V at up to 50A.
KWh and PF have been calculated by
This makes it necessary to indirectly
PIC microcontroller which sends to
measure line voltage and current at a
XBee kit through RS232 serial
level consistent with a microcontroller،
connection. The design discussed here
and then rescale these measurements to
uses the PIC24FJ128GA010 and
arrive at the original value. Measuring
Current Transformer (CT) for current
current here is essentially the same as
sensing.
measuring voltage which transducer has
been used to generate a voltage
A. Principles of measurement proportional to the load current. The
Basically, a watt hour meter is designed actual voltage and current readings can
to measure energy or power consumed then be derived.
over time. In simple terms، electrical For this application, the derived voltage
power is the product of voltage and reading, Vd, is related to the actual
current. If measurements of both instantaneous line voltage Vi by the
instantaneous voltage and current, or Vi expression, Vd = Vi *Kd/Kv or Vi = Vd
and Ii has been repeated for N times, the *Kv/Kd, where Kd is the digitization
average power (watt) is. constant for the ADC in this application
and Kv is the voltage proportionality
constant for the circuit design.
Similarly, the derived current reading,
The total energy consumed during Id, is related to Ii by the expression, Id =
specific time can be calculated by Ii *Kd/Ki or Ii = Id *Ki/Kd, where Ki is
multiplying the average power by time. the current proportionality constant
specific to this design; it is calculated
by dividing the CT turn ratio by the

4
Iraq J. Electrical and Electronic Engineering ‫اﻟﻤﺠﻠﺔ اﻟﻌﺮاﻗﻴﺔ ﻟﻠﻬﻨﺪﺳﺔ اﻟﻜﻬﺮﺑﺎﺋﻴﺔ واﻻﻟﻜﺘﺮوﻧﻴﺔ‬
Vol.10 No.1 , 2014 2014 ، 1 ‫ اﻟﻌﺪد‬، 10 ‫ﻡﺠﻠﺪ‬

product of the current amplifier gain The principle is graphically represented


and the input burden resistance. in Fig. 2.
By substituting the values of Vd and Id In this paper, the sampling time t has
into Equation 2, the total consumed been taken in order to measure voltage
power of indirect voltage and current and current. The procedure has been
measurements will as follow. achieved to calculate the voltage for a
particular current measurement:
1. Measure the first voltage sample at
time t0.
2. After an interval of t, measure the
It is more practical to accumulate up to current (time t1).
some fixed amount, and then increment 3. After another interval of t, measure
a counter to indicate energy the voltage again (time t2).
consumption. In this paper, for each 4. Calculate the voltage at t1 as (Vdt0 +
accumulating 1000 Wh (1 KWh) the Vdt1)/2.
counter will be incremental. This value
represents the resolution limit of the
meter. It is equivalent to 3,600,000 watt
seconds (1000 W x 60 x 60). The
resolution limit D can be calculated by
Equation 3.

Figure 2: Interpolating voltage for a


Any time that the accumulated sum of current sample.
the voltage and current products equals
or exceeds D, the counter will be C. Hardware Design
increment the KWh. Also, any The conceptual design of the energy
remainder in excess of D will be saved meter is shown in Fig. 3; a more
to be used in the next round of detailed schematic is presented in Fig.4.
accumulation. This design was prototyped using the
PIC24FJ128GA010.
B. Sampling Voltage and Current As shown in Fig.4, line voltage and
Calculating power assumes that the current are sampled sequentially at
voltage and current are sampled exactly regular intervals, with voltage and
the same time. By using a single ADC current being presented to different
with one sample-and-hold circuit makes analog input channels. To measure
this impossible. By using an voltage, the AC line is sampled across a
interpolated voltage value that very potential divider, R1 and R2, which
closely approximates what the voltage divides the input voltage by about 280.
would be when the current is sampled. For current measurement, a current

5
Iraq J. Electrical and Electronic Engineering ‫اﻟﻤﺠﻠﺔ اﻟﻌﺮاﻗﻴﺔ ﻟﻠﻬﻨﺪﺳﺔ اﻟﻜﻬﺮﺑﺎﺋﻴﺔ واﻻﻟﻜﺘﺮوﻧﻴﺔ‬
Vol.10 No.1 , 2014 2014 ، 1 ‫ اﻟﻌﺪد‬، 10 ‫ﻡﺠﻠﺪ‬

transformer creates voltage signal resistors, these determine the value of


across burden resistors (R5 and R6) that the current proportionality constant, Ki.
are proportional to the load current. As
the core design of the energy meter will
accommodate different types of
transducers, the CT is not shown on the While the voltage proportional constant
schematic. Kv is
A fixed offset of approximately 1.5 V is
added to both the current and voltage
signals. This maintains the signal well
above VSS, which is an operating Information of energy consumption is
requirement of the microcontroller’s sent over an 8-wire interface to an
ADC. By itself, the ADC does not have external LCD. The current version of
the dynamic range or resolution to the application firmware displays
perform the necessary measurements. cumulative energy use to date, as well
For the current signal, an amplifier with as several other parameters, in a
two selectable gain stages follows the continuous rollover fashion.
analog switches; it is used to The core hardware design also includes
compensate for the wider dynamic a serial RS-232 interface for data
range of the current sample. Single communication. The data lines are
stage gain is set by the values of R7 and electrically isolated from the rest of the
R8; together with the turn ratio of the meter circuitry to reduce the risk of
CT and the value of the burden damage to external equipment.

Measurement PIC24FJ128GA010
AC Falt
Selectable
Gain LCD
Attenuation Amplifier
Voltage

ADC
Line
Current Communication / Control
CT Attenuation Selectable
Gain
Amplifier

ZigBee Based
UART RS232
Wireless Kit

Figure 3: Conceptual block diagram of the energy meter.

6
Iraq J. Electrical and Electronic Engineering ‫اﻟﻤﺠﻠﺔ اﻟﻌﺮاﻗﻴﺔ ﻟﻠﻬﻨﺪﺳﺔ اﻟﻜﻬﺮﺑﺎﺋﻴﺔ واﻻﻟﻜﺘﺮوﻧﻴﺔ‬
Vol.10 No.1 , 2014 2014 ، 1 ‫ اﻟﻌﺪد‬، 10 ‫ﻡﺠﻠﺪ‬

Figure 4: Schematic diagram of electrical power meter.

D. System Firmware: the required procedures for ADC and


A high-level overview of the energy serial data transmission protocol
metering firmware is shown in Fig. 5. UART while the second step is to
The first step of firmware is initialized select all suitable value for evaluating

7
Iraq J. Electrical and Electronic Engineering ‫اﻟﻤﺠﻠﺔ اﻟﻌﺮاﻗﻴﺔ ﻟﻠﻬﻨﺪﺳﺔ اﻟﻜﻬﺮﺑﺎﺋﻴﺔ واﻻﻟﻜﺘﺮوﻧﻴﺔ‬
Vol.10 No.1 , 2014 2014 ، 1 ‫ اﻟﻌﺪد‬، 10 ‫ﻡﺠﻠﺪ‬

consumed KWh. The main loop is accumulated energy will always be


responsible for updating the KWh positive, even across a PF range from
counter and maintaining the visual 0.5 lag to 0.8 lead. Nevertheless، a
display shown on the LCD. The KWh reverse-current condition, where
counter is incremented on the basis of voltage and current are 180° out of
a status flag, set in an interrupt driven phase, will still produce a negative
power measurement routine. A accumulated energy result. If this
separate display timer is used to happens, a flag is set to permit the
determine how long each measured energy algorithm to produce a correct
value is displayed before rolling over (positive) result from the next cycle
to the next value. onward. Finally KWh will be send to
Voltage and current measurement are LCD for monitoring, and to base
performed during an interrupt service station through ZigBee wireless
routine triggered by the Timer0 communication standard.
interrupt. Measurements are performed
in a specific sequence, with the entire E. Wireless Communication System
sequence being repeated every (Ts = Since wireless communication links
T/N ms). Interleaving samples of can be quickly built, engineering cycle
voltage and current are taken, with the significantly shortened, and has better
simultaneous voltage values for the scalability compared to a wire-line
current measurements being system [9-12]. If a fault occurs, only
interpolated by the application. For check wireless data module for causes
each instantaneous voltage and current, quickly, and then restores the system
the consumed power has been back to normal operation. Wireless
evaluated and repeated for each full network system has been used to
time cycle T. The consumed power has transfer data to the base station. In this
been accumulated. When accumulate project, ZigBee wireless standard has
consumed power exceeding the value been used for wireless network.
of D, the value of KWh counter will be
ZigBee technology is a bidirectional
increments.
wireless communication technology
Also included in the measurement
mainly works on 868 MHz or 4.2 GHz
routine is logic to handle reverse-
ISM band with 20 ~ 250 kbit/s data
current conditions. Although the
rate, 100 m ~ 40 km maximum
energy calculations involve signed
transmission range, and a typical 100
operations, the result of the calculation
m distance [13-15]. The technical
after 2½ cycles should always be
features include security, reliability,
positive. This assumes that the current
low cost, power saving, high network
sensors are connected to produce
capacity, and short delays which
voltage and current signals in phase (or
enhanced communication delays for
nearly so) at unity power factor (UPF).
delay-sensitive applications.
If this is properly done، the

8
Iraq J. Electrical and Electronic Engineering ‫اﻟﻤﺠﻠﺔ اﻟﻌﺮاﻗﻴﺔ ﻟﻠﻬﻨﺪﺳﺔ اﻟﻜﻬﺮﺑﺎﺋﻴﺔ واﻻﻟﻜﺘﺮوﻧﻴﺔ‬
Vol.10 No.1 , 2014 2014 ، 1 ‫ اﻟﻌﺪد‬، 10 ‫ﻡﺠﻠﺪ‬

Start

Initialize System

Initialize ADC and UART

Select T, N, R1, R2, R3,


R4, R5, R6, R7, R8

Evaluate Ts=T/N, Ki, Kv, Kd, D, and Fs

Start = UART

Is No
Start?

Yes

No
i <= N*Ts

Yes

V1 = ADC No
Consumed
Power > D

Wait t0 Yes

Increment KWh counter


Current = ADC

Send KWh value to LCD


Wait t0

Send KWh value to base station


V2 = ADC

Accumulate consumed power = 0


Volt = (V1+V2)/2

i=0
Evaluate accumulate consumed power

i = i+Ts

Figure 5: Energy meter firmware.

9
Iraq J. Electrical and Electronic Engineering ‫اﻟﻤﺠﻠﺔ اﻟﻌﺮاﻗﻴﺔ ﻟﻠﻬﻨﺪﺳﺔ اﻟﻜﻬﺮﺑﺎﺋﻴﺔ واﻻﻟﻜﺘﺮوﻧﻴﺔ‬
Vol.10 No.1 , 2014 2014 ، 1 ‫ اﻟﻌﺪد‬، 10 ‫ﻡﺠﻠﺪ‬

XBee/XBee-PRO OEM RF module to retransmit messages for long


has been used for support ZigBee distance communication.
wireless network. For the applications 3. XBee has been configured as
where robust mesh networking Coordinator device in base station side
topologies are preferred, XBee/XBee- which connected to PC server through
PRO OEM RF modules provide RS232 in order to receive messages of
developers with both ZigBee mesh and all END devices.
the soon-to-be-released proprietary ZigBee END device reads energy
DigiMesh™ topologies. These measurement information in
networks allow devices to harness the multifunction electric meter by UART,
entire network of RF modules to and transmits them to the network
effectively extend range beyond that of Coordinator via Zigbee wireless
a single module, and create a more network, thus it can realize the wireless
stable and reliable network. Employing meter reading of the network
dynamic self-healing, self-discovery coordinator. Therefore, the END
functionality for reliable device must be able to communicate
communications, XBee/XBee-PRO with the electric power meter and
OEM RF modules make mesh Coordinator. The Coordinator also has
networking simple and easy to deploy to know which END node that sends
[16]. The XBee module is very easy to the data so the data can be read
use, and the interface is based on a accurately. Each of ZigBee modules
simple dialogue with a serial port, has a unique 64-bit permanent address,
which can be easily handled by a so the addressing won’t be much
microcontroller or a PC as shown in difficult.
Fig. 6.

IV. Power meter software design

Instantaneous voltage and current have


been measured by electric power meter
based on PIC microcontroller which
rms value of voltage and current,
power factor, and KWh have been
Figure 6: XBee/XBee-PRO OEM RF
evaluated by microcontroller. These
module [16].
information have been sent to the base
In this project X-CTU software has
station through ZigBee wireless
been used to configure XBee module
network. In base station side the
as:
information has been stored in PC
1. END device which connected to
server for management and
power meter through RS232 to
monitoring.
received measurement parameters that
At the base station the Graphical User
will be send to base station.
Interface (GUI) of smart electrical
2. Router device which used to routing
power meter is shown in Fig. 7.
messages to destination also it is used

10
Iraq J. Electrical and Electronic Engineering ‫اﻟﻤﺠﻠﺔ اﻟﻌﺮاﻗﻴﺔ ﻟﻠﻬﻨﺪﺳﺔ اﻟﻜﻬﺮﺑﺎﺋﻴﺔ واﻻﻟﻜﺘﺮوﻧﻴﺔ‬
Vol.10 No.1 , 2014 2014 ، 1 ‫ اﻟﻌﺪد‬، 10 ‫ﻡﺠﻠﺪ‬

Figure 7: Power meter software at base station side.

System software has been designed to current has been attenuated by CT of


manage and monitor the electric power 100/5 transformation ratio which
parameter and personal information of reduces (15 to 0.75 A) peak load
customers. For this reason, database current. The load current converted to
has been designed by using Visual voltage by using R6 as shown in Fig. 4
Basic Dot Net. For each customer there which selected as (1 Ω) to evaluate
are (ID, Name, Address, City, Phone 0.75 V. Next step is modifying the
No., Email, Vrms, Irms, PF, KWh, and instantaneous values of input voltage
KWh Cost). The information of KWh and load current by non-inverting Op-
and KWh cost has been updated during Amp amplifier which amplifier output
period time. Also the information of has been converted to digital value by
KWh cost will be sends to customers 8 bit - ADC. In microcontroller the
through email or mobile phone consumed power has been evaluated
messages for cost payment. which KWh counter will be increment
when consumed power exceeds the
V. Experiments results value of D.
Several experiments have been R3, R4, R7, and R8 have been selected
achieved in order to emulate the as (647 Ω, 5 KΩ, 5 KΩ, and 3.33 KΩ
operation of wireless power system respectively) while Fs have been
which the performance of this system selected as (400/50). The value of D
depends on the comprehensive has been evaluated as (115, 302) by
performance of all parts compounds using equations 4, 5 and 6. The
the system. The prototype of practical comparison between practical and
wireless electrical power meter circuit theoretical values is shown in Table 1.
is shown in Fig. 8. The server is connected to XBee Kit
The measurements starting through which is sets as Coordinator Device
potential divider step which the AC with ID=5000 and exchange data with
voltage supply damping to low level base station through RS232. Also the
voltage by using potential divider as electrical power meter of customers is
shown in Fig. 4 which R1 and R2 has connected to XBee Kits which set as
been selected as (210 KΩ and 750 Ω END Device with ID=5001, 5002, etc.
respectively) to attenuate (304 to 1.08 and exchange data with
V) peak supply voltage. The load microcontroller through RS232.

11
Iraq J. Electrical and Electronic Engineering ‫اﻟﻤﺠﻠﺔ اﻟﻌﺮاﻗﻴﺔ ﻟﻠﻬﻨﺪﺳﺔ اﻟﻜﻬﺮﺑﺎﺋﻴﺔ واﻻﻟﻜﺘﺮوﻧﻴﺔ‬
Vol.10 No.1 , 2014 2014 ، 1 ‫ اﻟﻌﺪد‬، 10 ‫ﻡﺠﻠﺪ‬

Figure 8: The prototype of practical wireless electrical power meter circuit.


Table 1: Comparison between practical and theoretical results.
Consumed Power
Vi Ii Vi/Kv Ii/Ki KWh
Vd Id
(V) (A) (V) (A) (1 hour)

Theoretical 304 15 1.22 1.25 134 136 3.6*106 31.5


Practical 304 15 1.2 1.26 136 137 3.7*106 32

SMS or email. The report of customer


At the base station, the information has
is shown in Fig. 9.
been received and stored in database
depending on ID of each customer. In
this project the ID of customer has
been selected same as XBee Kit ID
which is represents the source address
of XBee Kit.
The measurement information has
been sent from END devices to
coordinator by frames includes source
address. The electric power
measurement information has been
analyzed and can be printed or sends to
Figure 9: Email and SMS report of
costumers as report through cell phone
Customer.

13
Iraq J. Electrical and Electronic Engineering ‫اﻟﻤﺠﻠﺔ اﻟﻌﺮاﻗﻴﺔ ﻟﻠﻬﻨﺪﺳﺔ اﻟﻜﻬﺮﺑﺎﺋﻴﺔ واﻻﻟﻜﺘﺮوﻧﻴﺔ‬
Vol.10 No.1 , 2014 2014 ، 1 ‫ اﻟﻌﺪد‬، 10 ‫ﻡﺠﻠﺪ‬

VI. Conclusions Conference on Sensor


The design of the Wireless Smart Technologies and Applications
Power Meter System described in this (SENSORCOMM), pp.637-640,
2010.
paper is based on the microcontroller
[2] Shoeb S. Sheikh, et al., “Design
and high performance, extremely low and Implementation of Wireless
power consumption، high level of Automatic Meter Reading
integration, and low price of ZigBee System", International Journal of
technology. Wireless Smart Electric Engineering Science and
Power Meter prototype has been Technology, Vol. 3, No. 3, pp.
implemented and successfully tested 2329-2334, March 2011.
[3] Terry Chandler, “The Technology
for demand of 304 V and 15 A (peak
Development of Automatic
value). By using this system, the Metering and Monitoring
problem of the demand for electricity Systems”, The 7th International
in Iraq can be reduced, where the cost Power Engineering Conference,
of the electric power meter is a few pp. 147-150, Nov. 2005.
compared to the cost of the device [4] Ingeborg Graabak, Ove S. Grande,
available in the market because it Jussi Ikaheimo and Seppo
Karkkainen, “Establishment of
consists of a low-cost electronic items.
Automatic Meter Reading and
Also this system reduces the cost of Load Management, Experiences
measurement which needs less and Cost/Benefit”, 2004
measurement staff. The complete International Conference on Power
system setup and upgrade take a little System Technology, pp. 1333-
time, requires low cost and the setup is 1338, Nov. 2004.
[5] P. Corral, B. Coronado, A.C. De
very safe. Certainly rely on this system
Castro Lima, and O. Ludwig,
increases the accuracy of KWh, PF "Design of Automatic Meter
readings and monitor the amount of Reading based on Zigbee", Latin
real demand for energy in addition to America Transactions, IEEE
increasing security and not be (Revista IEEE America Latina),
manipulated by the customers and vol. 10 , Issue 1, pp. 1150–1155,
uncover abuses. The cost of the 2012.
amount of power factor can be added if [6] https://en.wikipedia.org/wiki/Elect
the customer doesn't improve the ricity_meter.
power factor conditions. As well as to [7] Duan Qichang, and Dong Ping,
increase the performance of “Network Data Transmission and
programing operation of the electric Information Exchange of the
Wireless Meter Reading System”,
power distribution system by controls
Techniques of Automation and
the energy consumption of customers. Application, vol.28, pp.39-41,
March 2009.
References
[8] Das V. V., “Wireless
[1] R. Devidas, M. V. Ramesh, Communication System for
“Wireless Smart Grid Design for Energy Meter Reading,” Advances
Monitoring and Optimizing in Recent Technologies in
Electric Transmission in India”, Communication and Computing,
2010 Fourth International 2009., pp.896-898, October 2009.

13
Iraq J. Electrical and Electronic Engineering ‫اﻟﻤﺠﻠﺔ اﻟﻌﺮاﻗﻴﺔ ﻟﻠﻬﻨﺪﺳﺔ اﻟﻜﻬﺮﺑﺎﺋﻴﺔ واﻻﻟﻜﺘﺮوﻧﻴﺔ‬
Vol.10 No.1 , 2014 2014 ، 1 ‫ اﻟﻌﺪد‬، 10 ‫ﻡﺠﻠﺪ‬

[9] R. Tahboub and V. Lazarescu, [12] Tatsiopoulos, A. Ktena, "A Smart


“Novel Approach for Remoter ZIGBEE Based Wireless Sensor
Energy Metering Reading using Meter System", 16th International
Mobile Agents”, 3rd International Conference on Systems, Signals
Conference on Information and Image Processing (IWSSIP),
Technology, New Generation, pp. Chalkida, Greece, pp. 1-4, 2009.
84-89, Apr. 2006. [13] Safaric S. and Malaric K., "ZigBee
[10] B.S. Koay, S.S. Cheah, Y. H. Sng, Wireless Standard", Proc. of the
P. H. J. Chong, P. Shum, Y. C. 48th International Symposium
Tong, X. Y. Wang, Y. X. Zuo and ELMAR-2006, Zadar Croatia, pp.
H. W. Kuek, “Design and 259-2621, 2006.
Implementation of Bluetooth
[14] http://www.digi.com.
Energy Meter”, Proceedings of the
2003 Joint Conference of the 4th [15] J. D. Lee, K. Y. Nam, S. H. Jeong,
International Conference on S. B. Choi, H. S. Ryoo and D. K.
Information, Communications and Kim, "Development of ZigBee
Signal Processing, 2003 Pacific Based Street Light Control
Rim Conference on Multimedia, System", Proc. of the Power
pp. 1474-1477, Dec. 2003. System Conference and
[11] H. Primicanta, M.Y. Nayan and Exposition, Atlanta GA, pp. 2236-