DIgSILENT Project:

PowerFactory
15.1.2 Date: 7/11/2018

Fault Locations with Feeders


Short-Circuit Calculation / Method : IEC 60909 Single Phase to Ground / Max. Short-Circuit Currents
Asynchronous Motors Grid Identification Short-Circuit Duration
Always Considered Automatic Break Time 0,10 s
Fault Clearing Time (Ith) 1,00 s
Conductor Temperature c-Voltage Factor
User Defined No User Defined No

Grid: Grid System Stage: Grid Annex: / 1


rtd.V. Voltage c- Sk" Ik" ip Ib Sb EFF
[kV] [kV] [deg] Factor [MVA/MVA] [kA/kA] [deg] [kA/kA] [kA] [MVA] [-]

Terminal(4) A 220,00 0,27 0,88 1,10 342,95 MVA 2,70 kA -89,12 7,28 kA 2,70 342,95 0,00
B 116,37 -105,37 0,00 MVA 0,00 kA 0,00 0,00 kA 0,00 0,00 0,90
C 116,37 107,12 0,00 MVA 0,00 kA 0,00 0,00 kA 0,00 0,00 0,89
L3 Terminal(1 A 134,48 MVA 1,06 kA 90,88 2,86 kA
B 4,33 MVA 0,03 kA -89,12 0,09 kA
C 4,33 MVA 0,03 kA -89,13 0,09 kA
Line(1) Terminal(3 A 208,47 MVA 1,64 kA 90,88 4,43 kA
B 4,33 MVA 0,03 kA 90,88 0,09 kA
C 4,33 MVA 0,03 kA 90,87 0,09 kA