CPS Gas Release Control Panel User Manual

CPS Gas Release Control Panel


Standard : MS1745 - Part2 : 2004
Brand : CPS

(User Manual)

Filename : CPS GRCP-User Manual-October 2008 INDUSTRONICS BERHAD


Page : 1 of 18
CPS Gas Release Control Panel User Manual

1.0 INTRODUCTION

The CPS Gas Release Control Panel is designed & fabricated to comply the
Malaysian Standard MS1745 – Part 2 : 2004 (equivalent to European Standard EN54-
2 : 1997). This is a multi-zone fully transistorized automatic fire detection system. It
is housed in a signal red coloured mild steel panel. The panel housing can be
fabricated based on different IP Standard to suit special requirement.

The alarm indication is both audible (bell ringing) and visible (Zone Fire red LED
indicators flashing). Fault and other indications are also both audible (buzzer beeps)
and visible (LED indicators ON), except the Disablements are indicating visibly only.

The standard models for the CPS Gas Release Control Panel are
i). MG-0200 (2 Zone Gas Release Control Panel-Normal Type);
ii). MG-0200/W (2 Zone Gas Release Control Panel-Weatherproof Type);

The CPS Gas Release Control Panel possesses the following features:
i). the control circuit with double lock system, ie., the output activated only if both
tie up zones are in alarm condition;
ii). the time delayed output to release / discharge the gas only after the pre-set delay
period of 28-32 seconds.
iii). the Gas Release Keyswitch contact input to immediately release the gas
regardless the status of both tie up zones.
iv). the Abort Switch contact input to stop the gas release process (prior to the
gas discharge started) by press & hold the switch. The gas release
process will be re-activated 8-10 seconds later after the switch has been released.

Filename : CPS GRCP-User Manual-October 2008 INDUSTRONICS BERHAD


Page : 2 of 18
CPS Gas Release Control Panel User Manual

2.0 OPERATION

Normal Condition
Set all the toggle switches in zoning to Normal (NOR) position. Switch on Mains
Supply and connect the standby battery. On normal condition, only two green LED
indicators are ON, ie. “MAINS ON” and “CHARGER ON”. All other LED indicators
should be OFF.

Alarm Condition
When a sensor or detector of any zone detects a hazard, both the particular Zone Fire
red LED indicators will flash, General Fire red LED indicator will ON, Master Bell
rings, pre-defined bells & outputs will be activated accordingly based on the pre-
defined alarm mapping. All the audible, visible & output activation remain if the
hazard and the Gas Release Control Panel are not attended to.

ACTION DURING ALARM CONDITION


(i) Set toggle switch on the particular zone to Disable (DIS) position. By doing
this, the activated devices will be turned OFF, the Zone Fire LED indicators
will ON steadily, the General Fire LED indicator remains ON.

(ii) Check and inspect the hazard zone and clear the hazard immediately.

(iii) Fight the hazard by means which you can and available (eg. Fire extinguisher
or hose reel).

(iv) After the hazard has been cleared and the sensing device replaced or reset, set
the toggle switch back to Normal (NOR) position. Reset the Gas Release
Control Panel to normalize the system by depressing the Alarm Reset Button
(ALARM RESET).

Filename : CPS GRCP-User Manual-October 2008 INDUSTRONICS BERHAD


Page : 3 of 18
CPS Gas Release Control Panel User Manual

IMPORTANT NOTES

(i) If the hazard is not cleared or the sensor is not replaced or reset, the Zone & General
Fire LED indicators cannot be reset, Master Bell & other pre-defined output devices
will be re-activated even though the toggle switch is set to Normal (NOR) position.

(ii) When zoning is in alarm condition, it is always recommended to disable that


particular alarm zone by switching the zone toggle switch to Disable (DIS) position.

(iii) By activating the Gas Release Keyswitch, the gas will immediately discharge even
though the system did not detect any alarm.

(iv) By activating the “GAS ISOLATE” Switch (prior the release of gas started), the gas
will not be discharged even though the system enters the discharge mode.

(v) By press & hold the externally installed Abort Switch, the release of gas will be
Temporary hold even though after the delay of 28-32 seconds. The discharge
action will continue back 8-10 seconds later after the switch has been released.

(vi) If the gas has been discharged, DO NOT enter the gas released room
WITHOUT equipped with proper breathing apparatus.

Filename : CPS GRCP-User Manual-October 2008 INDUSTRONICS BERHAD


Page : 4 of 18
CPS Gas Release Control Panel User Manual

3.0 SPECIFICATIONS
AC Input Voltage = 240Vac ± 10%, 50Hz, Single Phase

DC Output Voltage = 21 – 26 Vdc

Standby Battery = 24Vdc Rechargeable Type

Charger Output Voltage = 23 - 30Vdc Adjustable

Max Charging Current = 1.5A

End-of-line Resistor = 22K ohm ,1/4W, 5%, carbon film type


(for Alarm zone)

End-of-line Resistor = 4.7K ohm ,1/4W, 5%, carbon film type


(for bell output)

Bell / Tripping / Output = 21 – 26 Vdc

Standby Current per zone = 1.03mA

Input / Output contacts = Normally open voltage free contact

Chassis Colour / Material = Epoxy Signal Red /


1.5mm thick mild steel (16 Gauge)

Curtain Trip = Trips the curtain once both zones in alarm

Bell Intermittent = Any single zone in alarm, rings intermittently


Both zones in alarm, rings continuously

Flashing Light (Red) = Red Flash when any or both zones in alarm
Red ON once gas release started
Green ON when normal, OFF otherwise

Gas Discharge / Release = ON after 28-32 sec. after both zones in alarm
Output

Abort Switch = Pressed & hold to stop gas release process, the
release process will be re-activated 8-10 seconds
later after the release of this switch

Notes : a). Chassis Colour / Material might varies to suit the standard & requirement
specified by the relevant authority.
b). Cable requirements :
i). Zone / Contact Point – 2 cores x 1.5mm square cable
ii). Bell / Output / Actuate / Tripping Point – 2 cores x 2.5mm square cable

Filename : CPS GRCP-User Manual-October 2008 INDUSTRONICS BERHAD


Page : 5 of 18
CPS Gas Release Control Panel User Manual

4.0 MAIN CONTROL FACIAL DESCRIPTION

MAINS ON / = When the “MAINS ON” Switch is ON, the green LED
CHARGER ON indicator for “MAINS ON” will light up to indicate the
AC Mains is supplied to the system. The green Led
indicator for “CHARGER ON” will ON to indicate the
charger circuitry work, the Led indicator OFF if there is
no charger output. These 2 LED indicators will OFF
during the failure of AC supply.

DC ON = This green LED indicator light is ON & buzzer beeps


whenever the system is backup by batteries during the
failure of AC supply.

MAINS FAIL / = Both “MAINS FAIL” & “CHARGER FAIL” yellow


CHARGER FAIL LED indicators will ON and the buzzer beeps when
either one of the following conditions exists:-
(i) The AC Supply is switch OFF.
(ii) AC Fuse has been removed.

BATTERY FAIL = The “BATTERY FAIL” yellow LED indicator will ON


and the buzzer beeps when the batteries or Battery Fuse
is removed from the system.

BELL LINE OPEN = When the bell is removed or faulty, the


(Master Bell Line) “BELL LINE OPEN” yellow LED indicator will ON
and the buzzer beeps to show bell line in trouble.

TEST LED = By switch ON the “TEST LED ON” Switch, all the
LED indicators for Main Control & Zoning Facial will
ON and buzzer beeps. All LED indicators will restore
back to previous state by turn OFF this switch.

Filename : CPS GRCP-User Manual-October 2008 INDUSTRONICS BERHAD


Page : 6 of 18
CPS Gas Release Control Panel User Manual

BELL SILENCE = The “BELL SILENCE” yellow LED indicator ON once


the Bell Silence Switch is ON. The buzzer beeps
& all the bells stop ringing. Remember to OFF this
switch to resume the bells back in operation.

BUZZER SILENCE = The “BUZZER SILENCE” yellow LED indicator ON


once the Buzzer Silence Switch is ON to silence
the buzzer. Remember to OFF this switch to
resume the buzzer back in operation.

EARTH FAULT = The “EARTH FAULT” yellow LED indicator ON


whenever there is a short circuit between the Earth
portion with any cable / part within the system. The
buzzer beeps for audible annunciation.

FIRE (General) = General Fire red LED indicator ON whenever any zone
in alarm condition either activated from field or
manually by Test Zone Alarm Switch (T/A). This
indicator can only OFF by system reset.

FAULT (General) = General Fault yellow LED indicator ON whenever any


zone in fault condition either activated from field or
manually by Test Zone Fault Switch (T/F).

DISABLE (General) = General Disable yellow LED indicator ON whenever


any zone in disable condition activated by Zone Disable
Toggle Switch (DIS).

ALARM RESET = The alarm reset push-button switch is incorporated to


reset the alarm condition and set the system back to
normal.

VOLTAGE = The Voltmeter indicates the system’s voltage.

Filename : CPS GRCP-User Manual-October 2008 INDUSTRONICS BERHAD


Page : 7 of 18
CPS Gas Release Control Panel User Manual

CURRENT = The Ammeter indicates the system’s current


consumption.

GAS ISOLATE = This switch is incorporated to cut off supply to the


external gas release actuator. Once the switch is ON, the
yellow LED indicator will ON & the buzzer beeps. The
Gas Release Output will then not actuate.

MFAP ISOLATE = This switch is incorporated to prevent the gas release


contact signal to be sent to Master Fire Alarm Panel.
Once the switch is ON, the yellow LED indicator will
ON & the buzzer beeps. The contact signal will then be
isolated.

ACTUATED = The two “ACTUATED” red LED indicators ON once


the Gas Release Output activated.

ABORT = The two “ABORT” yellow LED indicators ON once the


input contact for externally installed Abort Switch is
pressed & hold. The gas release process will then
cancelled & the buzzer beeps. The function works only
prior the release of gas started.

Filename : CPS GRCP-User Manual-October 2008 INDUSTRONICS BERHAD


Page : 8 of 18
CPS Gas Release Control Panel User Manual

5.0 ZONING FACIAL DESCRIPTION

FIRE = When an alarm signal from sensors is received, the


two Zone Fire red LED indicators for that particular
zone will flash, Master Bell rings & the pre-defined
outputs triggered. The further alarm activation for
other zone will not affect the functionality of this
alarm zone. Since the signal is latched, the indication
will remain until the signal is cleared and after the
panel has been reset.

FAULT = When the external zone detector wiring is open /


faulty or the end-of-line resistor is removed, the two
Zone Fault yellow LED indicators for that particular
zone will ON and buzzer beeps. The Zone Fault LED
indicators will automatically clear when the fault
condition is cleared.

DISABLE = The two Zone Disable LED indicators for any zone
will light up when the toggle switch is set to Disable
(DIS) position for that particular zone. All the outputs
previously triggered by this alarm zone will then be
turned off. If the zone was previously in Zone Fault
condition, the buzzer sound triggered by this zone
fault will also be silenced once it had been disabled.

TEST FAULT (T/F) = When the black coloured non-latched (T/F) push-
button for any zone is depressed, it simulates an open
circuit on the detector line for that particular zone.
The system will response & acting exactly as “Zone
Fault”. The “Zone Fault” will automatically clear
when the “T/F” push-button is released.

Filename : CPS GRCP-User Manual-October 2008 INDUSTRONICS BERHAD


Page : 9 of 18
CPS Gas Release Control Panel User Manual

TEST ALARM (T/A) = Alarm condition can be tested from the panel by
depressing the red coloured (T/A) push-button & hold
for a short moment. The system will response & acting
exactly as “Zone Fire”. The Zone Fire LED indicators
will flash and it will remain flashing until the system is
reset by pushing the “ALARM RESET” switch.

Note : When doing Test Alarm , unless permission has been given, always
isolate the Gas Release Switch before activate any alarm to avoid
accidentally discharging the gas.

Disable (DIS) = When zoning switch is set to Disable (DIS) position, the
Zone Disable LED indicators will ON indicating that
particular zone is being disabled so that the alarm
condition cannot be initiated from that zone’s sensors.

Normal (NOR) = All zone toggle switches should always be in this


position when the system is on. When in this position,
none of the zoning LED indicators shall ON. Any
short-circuit in the external zone wire will cause an
alarm condition. Any open-circuit will cause a fault
condition.

Filename : CPS GRCP-User Manual-October 2008 INDUSTRONICS BERHAD


Page : 10 of 18
CPS Gas Release Control Panel User Manual

6.0 POWER SUPPLY UNIT

The power supply unit is operated on an 240Vac, 50 Hz, Single Phase mains
supply. It delivers

(i) 23-30Vdc adjustable regulated float charging output (max. 1.5A) to


charge the batteries.

(ii) 21-26Vdc adjustable regulated output (3A or 6A depends on the system


power consumption) to supply the system electronics, buzzer, bells, other
outputs & remote devices (detectors).

Automatic Earth Fault Detection circuit is incorporated for monitoring purpose.

The built- in status monitoring signals are available for monitoring purpose. These
signals are

(i) AC ON

(ii) CHARGER ON

(iii) BATTERY FAIL

(iv) EARTH FAULT

Filename : CPS GRCP-User Manual-October 2008 INDUSTRONICS BERHAD


Page : 11 of 18
CPS Gas Release Control Panel User Manual

7.0 WIRING INSTRUCTION

MAIN INPUT = The Mains Input is connected as follows:-

MAINS 240V

N E L
NEUTRAL EARTH LIVE

Make sure that the Mains Supply is AC 240V (±10%) 50Hz.

BATTERY INPUT = The Battery’s positive and negative terminals are


connected to the connectors marked.
BATTERY
+ -

-
24V
+ Standby
Battery

DETECTOR LINE = Two terminals are provided for each zone. At the
(ZONE x / NEG) last detector of each zone, an end-of-line resistor of
22K ohm, 1/4W, 5% carbon film type.

24V (POS / NEG) = DC24V supply output

MASTER BELL = This is the output for Master Bell. An end-of-line


resistor of 4.7K Ohm, 1/4W, 5% carbon film type
is connected at the bell.

GAS RELEASE = contact input to release the gas immediately


KEYSWITCH regardless the status of both zones.

Filename : CPS GRCP-User Manual-October 2008 INDUSTRONICS BERHAD


Page : 12 of 18
CPS Gas Release Control Panel User Manual

GAS DISCHARGE = This is the output to discharge / release the gas.

ABORT SWITCH = This is the contact input from Abort Switch.

FLASHING LIGHT = This is the 24V DC outputs respectively to the


(RED & GREEN) external red & green indicating lights.

EX.FAN TRIP = This is the output to trip the Exhaust Fan.

ASB.CURTAIN SOL. = This is the output to activate the curtain.

INTERMITTENT BELL = This is the output for Intermittent Bell. An end-of


line resistor of 4.7K Ohm, 1/4W, 5% carbon film
type is connected at the bell.
Any single zone in alarm, rings intermittently.
Both zones in alarm, rings continuously.

SIGNAL TO MFAP = This is the gas release contact signal to MFAP.

COMMON ALARM = This is a voltage free contact from the Gas Release
Control Panel for common alarm signal (optional).

COMMON FAULT = This is a voltage free contact from the Gas Release
Control Panel for common fault signal (optional).

Caution:
(A) Do not attempt to adjust the variable resistors on the printed circuit boards
as they are factory calibrated.

(B) When inserting the printed circuit boards, make sure that they are plugged in
properly in the correct place.

Filename : CPS GRCP-User Manual-October 2008 INDUSTRONICS BERHAD


Page : 13 of 18
CPS Gas Release Control Panel User Manual

8.0 MAINTENANCE & RECOMMENDATION OF PARTS REPLACEMENT

A) ELECTRONIC COMPONENTS

All electronics circuitries in the panel are designed according to the


specification and within the allowable maximum rating of the discrete or
integrated electronics components.

Although all parts (except battery) are warranty for 12 months against
manufacturing defect, the life span for these parts is very long i.e.
approximately 100,000 hours. The life span would be shortened depending on
the condition of operating temperature, supply voltage and other
environmental effects.

Note : The repair of the electronic cards is strictly prohibited & all
faulty cards shall be returned to the manufacturer for repairing.

B) BATTERY

A float charge (constant voltage) method is use for the battery charging.
Depending on the battery installed, please check from each battery
manufacturer’s data for the service life under its charging category. A 2.5
years of service life is recommended for Sealed lead acid battery.

Note : The battery size shall be determined based on the total hours
required by the relevant authority to backup the system in
standby mode. Nickel Cadmium type of batteries is also usable if
specified by the authority.

Filename : CPS GRCP-User Manual-October 2008 INDUSTRONICS BERHAD


Page : 14 of 18
CPS Gas Release Control Panel User Manual

9.0 CUSTOMIZATION

A) CHASSIS

The environment & location to install the Gas release Control panel
determines the chassis to be fabricated as indoor or outdoor type plus the IP
categories. As such, the manufacturer would only fabricate the size & type of
panel housing subject to the approval from the relevant authority involved.

All electronics supplied for customized chassis has no different to the one that
used for the standard models by only cascading each of the standard
module/part in order to comply the system with the Malaysian Standard
MS1745-Part2:2004.

B) CHARGER POWER SUPPLY UNIT

The Charger Power Supply Unit can be modified to increase the power
capacity by increasing the transformer to 6A or 10A for the output part. The
Charger & other monitoring circuitries remain same to the standard unit in
order to comply the Malaysia Standard MS1745 - Part 2 : 2004.

Filename : CPS GRCP-User Manual-October 2008 INDUSTRONICS BERHAD


Page : 15 of 18
CPS Gas Release Control Panel User Manual

Filename : CPS GRCP-User Manual-October 2008 INDUSTRONICS BERHAD


Page : 16 of 18
CPS Gas Release Control Panel User Manual

Filename : CPS GRCP-User Manual-October 2008 INDUSTRONICS BERHAD


Page : 17 of 18
CPS Gas Release Control Panel User Manual

Filename : CPS GRCP-User Manual-October 2008 INDUSTRONICS BERHAD


Page : 18 of 18