You are on page 1of 2

4007ES CPU and Display Board

4007ES NAC PSU (Hybrid)

Jumper Purpose Connector Purpose


Used to transfer files to or upload reports from the 4007ES using the Ethernet port on your laptop.
J1 Ethernet Port P2 Serial Interface port is used for connection to remote services.
This operation requires you to enable the Ethernet port by installing Service Mode Jumper J3..
Card Power and Communications connectors.
J2 USB Port Used to transfer files to or upload reports from the 4007ES. P3 & P4
Caution: Locking tabs are located up, on the top of the connectors.

LED Purpose
1 Ethernet connection LED (ON when connected, blinks with activity)
J3 Service Mode This jumper is normally positioned on only one of J3’s two pins. When installed, shorting the two pins, the Ethernet
2 Flashes once a second to show the CPU is processing
Jumper Port connection is enabled and a “SERVICE MODE JUMPER INSTALLED” trouble is generated.
3 Flashes once per polling cycle
4&5 Not used
6 Reset

SW1 Reset Switch – Cold Start. Clears Disables, Manual Overrides, and Logs
U11 - Contains the panel Serial Number and MAC address

© 2015 Tyco Fire Protection Products. All rights reserved. 579-1212


All specifications and other information shown were current as of document revision date and are subject to change without notice.
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited.
Rev. A
4007ES CPU and Display Board
4007ES NAC PSU (Hybrid)
Terminal Blocks on the 4007ES NAC PSU BOARD
TB Terminal(s) Purpose
1-4 IDNet
1 5&6 Aux/SNAC
7-10 RUI
2 1-8 NAC 1 & 2 (Class A operation is software selectable.
Class B operation has six software selectable EOLs).
3 1-8 NAC 3 & 4 (Class A operation is software selectable.
Class B operation has six software selectable EOLs).
4 1&2 Battery connection terminals

LEDS on the 4007ES NAC PSU BOARD


LED Color Behavior
LED 1 Aux/SNAC Y Aux Power is Default, 24 volt non-resettable output
SNAC operation depends on the selected Point Type
LED 2 RUI Trouble Y ON for Class A RUI trouble, otherwise OFF
LED 3 Comm Y ON when offline with Master, otherwise OFF
LED 4 General Power Y ON for AC Power Loss, Earth Fault, Overcurrent Trouble
LED 5 NAC 1 Y ON for OverCurrent, Short, Open
LED 6 RUI OC Y Fast blink on short (OverCurrent)
LED 7 NAC 2 Y ON for OverCurrent, Short, Open
LED 8 NAC 3 Y ON for OverCurrent, Short, Open
LED 9 NAC 4 Y ON for OverCurrent, Short, Open
LED 10 AC Status G OFF on AC Fail, otherwise ON
LED 11 IDNet Loop III Y A and/or B terminal short, or Class A open trouble
LED 12 IDNet Loop II Y A and/or B terminal short, or Class A open trouble
LED 13 IDNet Loop I Y A and/or B terminal short, or Class A open trouble
LED 14 IDNet Earth - Y Negative Earth Fault
LED 15 IDNet Earth + Y Positive Earth Fault
LED 16 IDNet Y IDNet Channel Fail
LED 17 IDNet Comm Y ON when offline with MAster, otherwise OFF

P Connectors on the 4007ES NAC PSU BOARD


P Purpose
1 RUI Class Selector. Default is Class A. For Class B operation, move the two jumpers to short the
top two pins.
2 IDNet+ Loop A Class. Default is Class A. For Class B operation, move the two jumpers to short
the top two pins.
10 AC power input connector
11 Connector for ribbon harness to optional city card or optional relay card

J Connectors on the 4007ES NAC PSU BOARD


Associated
J Purpose
with P
5 Communications and Power for Zone/Relay card(s)
7 Connector for IDNet Loop B card (first expansion IDNet card)
8 Connector for IDNet Loop C card (second expansion IDNet card)
9 4 Default - NAC Power Supply Online
Jumper removed NAC Power Supply Offline
11 6 Battery Depleted Jumper - * Canadian operation is not the default jumper setting
12 8 Default 1-2 IDNet Online
Jumper removed IDNET Offline
13 9 25V Regulator Jumpers 1-2, 3-4 default.
Remove Jumpers and plug in 25V Regulator Harness
when using the 25V Regulator Module
14 9 25V Regulator Jumpers 1-2, 3-4 default.
Remove Jumpers when using the 25V Regulator Module
15 Communications and Power for Zone/Relay card(s)
16 Communications and Power for the retainer mounted CPU card
17 Communications and Power for an option card

579-1212
Rev. A

You might also like