Building HGB BAROOM YARD No.

of floors YARD, WHARE HOUSE, WORK SHOP


Department/Faculty HSE SGB BAROOM
Inspection date 15-03-2018 Date of report 15-03-2018
Mr.Abdullah & Muhammad
Inspection team Ramzan

Immediate action Comments Priority Status Target date


Observations Hazards
needed
Green
Red

1 Air compressor hose is not in High


good condition. Any time, it prioirty
can blast with explosion. Personal
injury,
(air compressor) Need to be fixed;
Property cut the 18 inch
damage, hose then fix it
Fire hazard, tightly.
Dust hazard

2 Air compressor hose is not in High


good condition. Any time, it prioirty
can blast with explosion.
(air receiver) Personal
injury,
Need to be fixed;
Property cut the 18 inch
damage, hose then fix it
Fire hazard, tightly.
Dust hazard
3 Acetylene cylinder has less High
gap between wielding area priority
and storage area of cylinder .
Fire hazard Change the
location away
Explosion from the
hazard wielding area

4 Grinding cable is not good Medium


condition , it is in damaged prioirty
condition, fabricated
insulation .
Shock hazard It should be
Electric hazard changed.
5 Flying objects are Medium
everywhere. Dust is all around Skin priority
especially in sandblasting irritation
area.
Dermatitis Keep the mesh
hazards net and put the
Suffocation signage
and cough
Dust hazards

6 Fabricated tools are found . Medium


that are not allowed for hand Hand injury, priority
safety. No proper Use right tools
grip, for right job.
Only authorized
No durability ,
and approved
Slippery tools, tools must be
Struck to any used.
body

7 Mesh net is found damaged Medium


and expired. priority
Flying objects
will scatter all It should be
around. Skin replaced with
irritation. new one.
Dust hazards
8 Acetylene cylinder is stored in high
the direct sun light. It is prioirty
unsafe condition.
Explosion To be stored in
hazard, fence/net with
Leakage of gas chain along with
hazards 6.1m distance.

9 Fire extinguisher is found high


Gauge is not
damaged and ineffective in prioirty
working Fire extinguisher
the fork lift.
properly. should be
Fire hazards changed.