You are on page 1of 9

1 2 3 4 5 6 7 8 9

THIS DOCUMENT REMAINS THE EXCLUSIVE PROPERTY OF ASIAPHIL MANUFACTURING IND., INC. REPRODUCTION OR ANY USE NOT IN CONFORMITY WITH THE INTENDED APPLICATION IS NOT PERMISSIBLE.
A
CARCON LINE 1 CARCON LINE 2
3 X PT-4 , DRY TYPE
3 X PT-3 , DRY TYPE
34.5 KV/1.732 : 115/1.732 VOLTS
34.5 KV/1.732 : 115/1.732 VOLTS
RATIO : 300:1
RATIO : 300:1
3 X LA 3 X LA

3 X PT-8 , DRY TYPE


34.5 KV/1.732 : 115/1.732 VOLTS
CI 23: 2000 AMPS CH 23: 2000 AMPS RATIO : 300:1
34.5 KV BUS B
4000 AMPS

CJ 3B : 4000 AMPS CI 3B : 4000 AMPS CH 3B : 4000 AMPS

3 3 3
2 2 2
B 1 1 1

CJ 3 : 3000 AMPS CI 3 : 2000 AMPS CH 3 : 2000 AMPS


1 1 1
3 X PT-1 , DRY TYPE 2 2 2
34.5 KV/1.732 : 115/1.732 VOLTS
RATIO : 300:1 3 3 3

CJ 3A : 4000 AMPS CI 3A : 4000 AMPS CH 3A : 4000 AMPS


SIGPIT LINE 2 CJ 23
CJ 2B : 4000 AMPS CI 2B : 4000 AMPS CH 2B : 4000 AMPS

3 3 3
3 X LA-1
2 2 2
1 1 1

CJ 2 : 3000 AMPS CI 2 : 2000 AMPS CH 2 : 2000 AMPS

1 1 1
C 3 X PT-2 , DRY TYPE
34.5 KV/1.732 : 115/1.732 VOLTS
2 2 2
3 3 3
RATIO : 300:1
CJ 2A : 4000 AMPS
CI 2A : 4000 AMPS CH 2A : 4000 AMPS
SIGPIT LINE 1 CJ 12
CJ 1B : 4000 AMPS CI 1B : 4000 AMPS CH 1B : 4000 AMPS
3 3 3
3 X LA
2 2 2
1 1 1
CJ 1 : 3000 AMPS CI 1 : 2000 AMPS CH 1 : 2000 AMPS

1 1 1
2 2 2
3 3 3

3 X PT-5 , DRY TYPE


CJ 1A : 4000 AMPS CI 1A : 4000 AMPS CH 1A : 4000 AMPS 34.5 KV/1.732 : 115/1.732 VOLTS
RATIO : 300:1
34.5 KV BUS A
D 4000 AMPS

CI 12: 2000 AMPS CH 12: 2000 AMPS

BY OTHERS EXISTING 3 X LA 3 X LA
3 X PT-6 , DRY TYPE 3 X PT-7 , DRY TYPE
34.5 KV/1.732 : 115/1.732 VOLTS 34.5 KV/1.732 : 115/1.732 VOLTS
RATIO : 300:1 RATIO : 300:1

DASCON LINE 1 DASCON LINE 2

SINGLE LINE DIAGRAM : CARCON


DRAWING SUBMITTED TO/FOR: DATE REMARKS CONTRACTOR DESIGNER: OWNER : PROJECT : DRAWN : FILE NO. SHEET NO.
WRB
TENDERING: 0 1-6-2016
TOLEDO CARCON POWER STATION CHECKED : AJB 1
ENG-FM-004-1

FOR APPROVAL:
REVISION

1 DRAWING NO.
EFF: 8-1-15

FOR CONSTRUCTION: 2 APPROVED : GOC 19911 - E01


ASIAPHIL MANUFACTURING INDS., INC. PROJECT LOCATION: SHEET CONTENT: OF
AS BUILT: 3
SCALE : NTS FEEDER NO.
4 CEBU PLAN LAYOUT 9
RECEIVED BY:
5 1150 PRES. QUIRINO AVE. EXTN. PACO, MANILA DATE : 12/26/2015
1 2 3 4 5 6 7 8 9

THIS DOCUMENT REMAINS THE EXCLUSIVE PROPERTY OF ASIAPHIL MANUFACTURING IND., INC. REPRODUCTION OR ANY USE NOT IN CONFORMITY WITH THE INTENDED APPLICATION IS NOT PERMISSIBLE.
A
CARCON LINE 1 CARCON LINE 2
3 X PT-4 , DRY TYPE
3 X PT-3 , DRY TYPE
34.5 KV/1.732 : 115/1.732 VOLTS
34.5 KV/1.732 : 115/1.732 VOLTS
RATIO : 300:1
3 X LA RATIO : 300:1 3 X LA

A Wh V A Wh V 3 X PT , DRY TYPE
CI 23 VA VAR W CH 23 VA VAR W 34.5 KV/1.732 : 115/1.732 VOLTS
RATIO : 300:1
34.5 KV BUS B
IED METER(CRP) IED METER(CRP)
4000 AMPS

CJ 3B

A Wh V 3 3 CI 3B 3 CH 3B
VA VAR W 2 2 2
B IED METER(CRP)
1 1 1

CJ 3 CI 3 CH 3
1 1 1

3 X PT-1 , DRY TYPE 2 2 2


34.5 KV/1.732 : 115/1.732 VOLTS 3 3 3
RATIO : 300:1 CI 3A CH 3A
CJ 3A
SIGPIT LINE 2 CJ 23
CJ 2B
CI 2B CH 2B
3 3 3
3 X LA
2 2 2
A Wh V 1 1 1
VA VAR W CJ 2 CI 2 CH 2
IED METER(CRP)
1 1 1

C 3 X PT-2 , DRY TYPE 2 2 2


34.5 KV/1.732 : 115/1.732 VOLTS 3 3 3
CJ 2A CI 2A CH 2A
RATIO : 300:1

SIGPIT LINE 1 CJ 12
CJ 1B CI 1B CH 1B
3 3 3
3 X LA
2 2 2
1 1 1
CJ 1 CI 1 CH 1

1 1 1
2 2 2
3 CJ 1A 3 CI 1A 3 CH 1A

3 X PT-5 , DRY TYPE


34.5 KV/1.732 : 115/1.732 VOLTS
34.5 KV BUS A RATIO : 300:1
4000 AMPS
D

CI 12 A Wh V CH 12 A Wh V
VA VAR W VA VAR W
IED METER(CRP) IED METER(CRP)

BY OTHERS EXISTING 3 X LA 3 X LA

3 X PT-6 , DRY TYPE 3 X PT-7 , DRY TYPE


34.5 KV/1.732 : 115/1.732 VOLTS 34.5 KV/1.732 : 115/1.732 VOLTS
RATIO : 300:1 RATIO : 300:1

DASCON LINE 1 DASCON LINE 2

METERING SYSTEM : CARCON


DRAWING SUBMITTED TO/FOR: DATE REMARKS CONTRACTOR DESIGNER: OWNER : PROJECT : DRAWN : FILE NO. SHEET NO.
WRB
TENDERING: 0 1-6-2016
TOLEDO CARCON POWER STATION CHECKED : AJB 2
ENG-FM-004-1

FOR APPROVAL:
REVISION

1 DRAWING NO.
EFF: 8-1-15

FOR CONSTRUCTION: 2 APPROVED : GOC 19911 - E01


ASIAPHIL MANUFACTURING INDS., INC. PROJECT LOCATION: SHEET CONTENT: OF
AS BUILT: 3
SCALE : NTS FEEDER NO.
4 CEBU PLAN LAYOUT 9
RECEIVED BY:
5 1150 PRES. QUIRINO AVE. EXTN. PACO, MANILA DATE : 12/26/2015
1 2 3 4 5 6 7 8 9

THIS DOCUMENT REMAINS THE EXCLUSIVE PROPERTY OF ASIAPHIL MANUFACTURING IND., INC. REPRODUCTION OR ANY USE NOT IN CONFORMITY WITH THE INTENDED APPLICATION IS NOT PERMISSIBLE.
DEVICE NUMBER LEGEND

79 AUTO RECLOSE
A 30 ALARM / ANNUNCIATOR
50 PHASE INSTANTANEOUS OVERCURRENT CARCON LINE 1 CARCON LINE 2
51 PHASE TIME OVERCURRENT
3 X PT-4 , DRY TYPE
94 AUXILLIARY TRIP RELAY 3 X PT-3 , DRY TYPE
34.5 KV/1.732 : 115/1.732 VOLTS
34.5 KV/1.732 : 115/1.732 VOLTS
50N NEUTRAL INSTANTANEOUS OVERCURRENT RATIO : 300:1
RATIO : 300:1

51N NEUTRAL TIME OVERCURRENT 3 X LA 3 X LA

27 UNDERVOLTAGE
59 OVERVOLTAGE
87B BUS BAR DIFFERENTIAL 3 X PT , DRY TYPE
34.5 KV/1.732 : 115/1.732 VOLTS
50BF BREAKER FAILURE
CI 23 CH 23 RATIO : 300:1
67 PHASE DIRECTIONAL OVERCURRENT 34.5 KV BUS B
67G GROUND DIRECTIONAL OVERCURRENT 4000 AMPS
25 SYNCHROCHECK

CJ 3B

3 3 CI 3B 3 CH 3B
2 2 2

B 1 1 1

CJ 3 CI 3 CH 3
1 1 1
3 X PT-1 , DRY TYPE 2
79 50/51 50N/
51N
27/59
2
79 50/51 50N/
51N
27/59
2
79 50/51 50N/
51N
27/59
34.5 KV/1.732 : 115/1.732 VOLTS
RATIO : 300:1 3 30 94 67 67G 3 30 94 67 67G 3 30 94 67 67G
CI 3A CH 3A
CJ 3A SEL 351 (CRP) SEL 351 (CRP) SEL 351 (CRP)

TRIPS CJ3 TRIPS CI3


SIGPIT LINE 2 CJ 23 TRIPS CJ2 TRIPS CI2
TRIPS CH3
TRIPS CH2
CJ 2B
CI 2B CH 2B
3 3 3
3 X LA
2 2 2
1 1 1

CJ 2 CI 2 CH 2

1 1 1
3 X PT-2 , DRY TYPE
C 34.5 KV/1.732 : 115/1.732 VOLTS
2 2 2
3 3 3
RATIO : 300:1 CJ 2A CI 2A CH 2A
50N/ 50N/ 50N/
79 50/51
51N
27/59 79 50/51
51N
27/59 79 50/51
51N
27/59

SIGPIT LINE 1 CJ 12
30 94 67 67G 30 94 67 67G 30 94 67 67G
SEL 351 (CRP) SEL 351 (CRP) SEL 351 (CRP)
CJ 1B TRIPS CJ1 CI 1B TRIPS CI1 CH 1B
TRIPS CH1
3 3 3
3 X LA TRIPS CJ2 TRIPS CI2 TRIPS CH2
2 2 2
1 1 1
CJ 1 CI 1 CH 1

1 1 1
2 2 2
3 CJ 1A 3 CI 1A 3 CH 1A
3 X PT-5 , DRY TYPE
34.5 KV/1.732 : 115/1.732 VOLTS
RATIO : 300:1
34.5 KV BUS A
4000 AMPS
D

CI 12 CH 12

BY OTHERS EXISTING 3 X LA 3 X LA
3 X PT-6 , DRY TYPE 3 X PT-7 , DRY TYPE
34.5 KV/1.732 : 115/1.732 VOLTS 34.5 KV/1.732 : 115/1.732 VOLTS
RATIO : 300:1 RATIO : 300:1

DASCON LINE 1 DASCON LINE 2

FEEDER PROTECTION SYSTEM : CARCON


DRAWING SUBMITTED TO/FOR: DATE REMARKS CONTRACTOR DESIGNER: OWNER : PROJECT : DRAWN : FILE NO. SHEET NO.
WRB
TENDERING: 0 1-6-2016
TOLEDO CARCON POWER STATION CHECKED : AJB 3
ENG-FM-004-1

FOR APPROVAL:
REVISION

1 DRAWING NO.
EFF: 8-1-15

FOR CONSTRUCTION: 2 APPROVED : GOC 19911 - E01


ASIAPHIL MANUFACTURING INDS., INC. PROJECT LOCATION: SHEET CONTENT: OF
AS BUILT: 3
SCALE : NTS FEEDER NO.
4 CEBU PLAN LAYOUT 79
RECEIVED BY:
5 1150 PRES. QUIRINO AVE. EXTN. PACO, MANILA DATE : 12/26/2015
1 2 3 4 5 6 7 8 9

THIS DOCUMENT REMAINS THE EXCLUSIVE PROPERTY OF ASIAPHIL MANUFACTURING IND., INC. REPRODUCTION OR ANY USE NOT IN CONFORMITY WITH THE INTENDED APPLICATION IS NOT PERMISSIBLE.
DEVICE NUMBER LEGEND

79 AUTO RECLOSE
A 30 ALARM / ANNUNCIATOR
50 PHASE INSTANTANEOUS OVERCURRENT CARCON LINE 1 CARCON LINE 2
51 PHASE TIME OVERCURRENT
3 X PT-4 , DRY TYPE
94 AUXILLIARY TRIP RELAY 3 X PT-3 , DRY TYPE
34.5 KV/1.732 : 115/1.732 VOLTS
34.5 KV/1.732 : 115/1.732 VOLTS
50N NEUTRAL INSTANTANEOUS OVERCURRENT RATIO : 300:1
RATIO : 300:1

51N NEUTRAL TIME OVERCURRENT 3 X LA 3 X LA

27 UNDERVOLTAGE
59 OVERVOLTAGE
87B BUS BAR DIFFERENTIAL 3 X PT , DRY TYPE
34.5 KV/1.732 : 115/1.732 VOLTS
50BF BREAKER FAILURE
CI 23 CH 23 RATIO : 300:1
67 PHASE DIRECTIONAL OVERCURRENT 34.5 KV BUS B
67G GROUND DIRECTIONAL OVERCURRENT 4000 AMPS
25 SYNCHROCHECK

CJ 3B CI 3B CH 3B

3 3 3 79 50/51 50N/ 27/59


51N
2 2 2
30 94 87B
B 1 1 1
SEL 487B (CRP)
CJ 3 CI 3 CH 3 TRIPS CJ3
1 1 1 TRIPS CI3
3 X PT-1 , DRY TYPE
34.5 KV/1.732 : 115/1.732 VOLTS
2 2 2 TRIPS CH3
RATIO : 300:1 3 3 3

CJ 3A CI 3A CH 3A
SIGPIT LINE 2 CJ 23
CJ 2B CI 2B CH 2B

3 3 3
3 X LA
2 2 2
1 1 1

CJ 2 CI 2 CH 2

1 1 1
C 3 X PT-2 , DRY TYPE
34.5 KV/1.732 : 115/1.732 VOLTS
2 2 2
3 3 3
RATIO : 300:1 CJ 2A CI 2A CH 2A

SIGPIT LINE 1 CJ 12 79 50/51 50N/ 27/59


51N

CJ 1B CI 1B CH 1B 30 94 87B

3 3 3 SEL 487B (CRP)


3 X LA
2 2 2
1 1 1 TRIPS CJ1
CJ 1 CI 1 CH 1 TRIPS CI1
TRIPS CH1
1 1 1
2 2 2
3 3 3

3 X PT-5 , DRY TYPE


CH 1A 34.5 KV/1.732 : 115/1.732 VOLTS
CJ 1A CI 1A RATIO : 300:1
34.5 KV BUS A
D 4000 AMPS

CI 12 CH 12

BY OTHERS EXISTING 3 X LA 3 X LA
3 X PT-6 , DRY TYPE 3 X PT-7 , DRY TYPE
34.5 KV/1.732 : 115/1.732 VOLTS 34.5 KV/1.732 : 115/1.732 VOLTS
RATIO : 300:1 RATIO : 300:1

DASCON LINE 1 DASCON LINE 2

BUS / BREAKER PROTECTION SYSTEM : CARCON


DRAWING SUBMITTED TO/FOR: DATE REMARKS CONTRACTOR DESIGNER: OWNER : PROJECT : DRAWN : FILE NO. SHEET NO.
WRB
TENDERING: 0 1-6-2016
TOLEDO CARCON POWER STATION CHECKED : AJB 4
ENG-FM-004-1

FOR APPROVAL:
REVISION

1 DRAWING NO.
EFF: 8-1-15

FOR CONSTRUCTION: 2 APPROVED : GOC 19911 - E01


ASIAPHIL MANUFACTURING INDS., INC. PROJECT LOCATION: SHEET CONTENT: OF
AS BUILT: 3
SCALE : NTS FEEDER NO.
4 CEBU PLAN LAYOUT 79
RECEIVED BY:
5 1150 PRES. QUIRINO AVE. EXTN. PACO, MANILA DATE : 12/26/2015
1 2 3 4 5 6 7 8 9

THIS DOCUMENT REMAINS THE EXCLUSIVE PROPERTY OF ASIAPHIL MANUFACTURING IND., INC. REPRODUCTION OR ANY USE NOT IN CONFORMITY WITH THE INTENDED APPLICATION IS NOT PERMISSIBLE.
DEVICE NUMBER LEGEND

A 79 AUTO RECLOSE
30
50
ALARM / ANNUNCIATOR
PHASE INSTANTANEOUS OVERCURRENT CARCON LINE 1 CARCON LINE 2
51 PHASE TIME OVERCURRENT 3 X PT-4 , DRY TYPE
3 X PT-3 , DRY TYPE
94 AUXILLIARY TRIP RELAY 34.5 KV/1.732 : 115/1.732 VOLTS
34.5 KV/1.732 : 115/1.732 VOLTS
RATIO : 300:1
50N NEUTRAL INSTANTANEOUS OVERCURRENT RATIO : 300:1
3 X LA 3 X LA
51N NEUTRAL TIME OVERCURRENT
27 UNDERVOLTAGE
59 OVERVOLTAGE
3 X PT , DRY TYPE
87B BUS BAR DIFFERENTIAL 34.5 KV/1.732 : 115/1.732 VOLTS
50BF BREAKER FAILURE CI 23 CH 23 RATIO : 300:1
34.5 KV BUS B
67 PHASE DIRECTIONAL OVERCURRENT
4000 AMPS
67G GROUND DIRECTIONAL OVERCURRENT

25 SYNCHROCHECK

CJ 3B

3 3 CI 3B 3 CH 3B
2 2 2
B 1 1 1

CJ 3 25/27 CI 3 25/27 CH 3 25/27


1 1 1
3 X PT-1 , DRY TYPE 2 2 2
34.5 KV/1.732 : 115/1.732 VOLTS
RATIO : 300:1 3 3 3
CI 3A CH 3A
CJ 3A
SIGPIT LINE 2 CJ 23
CJ 2B
CI 2B CH 2B
3 3 3
3 X LA
2 2 2
1 1 1

CJ 2 CI 2 CH 2
25/27 25/27 25/27
1 1 1
C 3 X PT-2 , DRY TYPE
34.5 KV/1.732 : 115/1.732 VOLTS
2 2 2
3 3 3
RATIO : 300:1 CJ 2A CI 2A CH 2A

SIGPIT LINE 1 CJ 12
CJ 1B CI 1B CH 1B
3 3 3
3 X LA
2 2 2
1 1 1
CJ 1 CI 1 CH 1
25/27 25/27 25/27
1 1 1
2 2 2
3 CJ 1A 3 CI 1A 3 CH 1A
3 X PT-5 , DRY TYPE
34.5 KV/1.732 : 115/1.732 VOLTS
RATIO : 300:1

D
34.5 KV BUS A
4000 AMPS CI 12 CH 12

BY OTHERS EXISTING 3 X LA 3 X LA
3 X PT-6 , DRY TYPE 3 X PT-7 , DRY TYPE
34.5 KV/1.732 : 115/1.732 VOLTS 34.5 KV/1.732 : 115/1.732 VOLTS
RATIO : 300:1 RATIO : 300:1

DASCON LINE 1 DASCON LINE 2

SYNCHRONIZING SYSTEM : CARCON


DRAWING SUBMITTED TO/FOR: DATE REMARKS CONTRACTOR DESIGNER: OWNER : PROJECT : DRAWN : FILE NO. SHEET NO.
WRB
TENDERING: 0 1-6-2016
TOLEDO CARCON POWER STATION CHECKED : AJB 5
ENG-FM-004-1

FOR APPROVAL:
REVISION

1 DRAWING NO.
EFF: 8-1-15

FOR CONSTRUCTION: 2 APPROVED : GOC 19911 - E01


ASIAPHIL MANUFACTURING INDS., INC. PROJECT LOCATION: SHEET CONTENT: OF
AS BUILT: 3
SCALE : NTS FEEDER NO.
4 CEBU PLAN LAYOUT 9
RECEIVED BY:
5 1150 PRES. QUIRINO AVE. EXTN. PACO, MANILA DATE : 12/26/2015
1 2 3 4 5 6 7 8 9

THIS DOCUMENT REMAINS THE EXCLUSIVE PROPERTY OF ASIAPHIL MANUFACTURING IND., INC. REPRODUCTION OR ANY USE NOT IN CONFORMITY WITH THE INTENDED APPLICATION IS NOT PERMISSIBLE.
3000 950 4850 950 4850 950 4850 950 4850 950 3000
A

3000
PT PT PT PT PT PT PT PT PT PT PT PT

950
6 5 6 5 6 5

4850
4 3 4 3 4 3

B 2 1 2 1 2 1

950

6 5 6 5 6 5
PT
PT
4850

4 3 4 3 4 3

PT
2 1 2 1 2 1
PT
C
PT
PT
950

4000 AMPS 4000 AMPS


TUBULAR BUS TUBULAR BUS

6 5 6 5 6 5

PT
4850

4 3 4 3 4 3

2 1 2 1 2 1
PT

D PT
950

NGCP AREA
E

CARCON SUBSTATION PLAN LAYOUT


DRAWING SUBMITTED TO/FOR: DATE REMARKS CONTRACTOR DESIGNER: OWNER : PROJECT : DRAWN : FILE NO. SHEET NO.
WRB
TENDERING: 0 1-6-2016
TOLEDO CARCON POWER STATION CHECKED : AJB 6
ENG-FM-004-1

FOR APPROVAL:
REVISION

1 DRAWING NO.
EFF: 8-1-15

FOR CONSTRUCTION: 2 APPROVED : GOC 19911 - E01


ASIAPHIL MANUFACTURING INDS., INC. PROJECT LOCATION: SHEET CONTENT: OF
AS BUILT: 3
SCALE : NTS FEEDER NO.
4 CEBU PLAN LAYOUT 9
RECEIVED BY:
5 1150 PRES. QUIRINO AVE. EXTN. PACO, MANILA DATE : 12/26/2015
1 2 3 4 5 6 7 8 9

THIS DOCUMENT REMAINS THE EXCLUSIVE PROPERTY OF ASIAPHIL MANUFACTURING IND., INC. REPRODUCTION OR ANY USE NOT IN CONFORMITY WITH THE INTENDED APPLICATION IS NOT PERMISSIBLE.
LA LA
A

950
4000 AMPS 4000 AMPS

2700
TUBULAR BUS TUBULAR BUS
PT PT

950
900
950
900 450
B

FENCE

900
450 900

3000 950 4850 950 4850 950 4850 950 4850 950 3000

C
FRONT ELEVATION SECTION "A-A"

4000 AMPS
TUBULAR BUS

D
900 451

900

FENCE
900
900

900
450 900

900

950 4850 950 4850 950 4850 950 1500 1500


E

SIDE ELEVATION SECTION "B-B"


DRAWING SUBMITTED TO/FOR: DATE REMARKS CONTRACTOR DESIGNER: OWNER : PROJECT : DRAWN : FILE NO. SHEET NO.
WRB
TENDERING: 0 1-6-2016
TOLEDO CARCON POWER STATION CHECKED : AJB 7
ENG-FM-004-1

FOR APPROVAL:
REVISION

1 DRAWING NO.
EFF: 8-1-15

FOR CONSTRUCTION: 2 APPROVED : GOC 19911 - E01


ASIAPHIL MANUFACTURING INDS., INC. PROJECT LOCATION: SHEET CONTENT: OF
AS BUILT: 3
SCALE : NTS FEEDER NO.
4 CEBU PLAN LAYOUT 9
RECEIVED BY:
5 1150 PRES. QUIRINO AVE. EXTN. PACO, MANILA DATE : 12/26/2015
1 2 3 4 5 6 7 8 9

THIS DOCUMENT REMAINS THE EXCLUSIVE PROPERTY OF ASIAPHIL MANUFACTURING IND., INC. REPRODUCTION OR ANY USE NOT IN CONFORMITY WITH THE INTENDED APPLICATION IS NOT PERMISSIBLE.
A 3475 5800 5800 5800 5800 3475

3475

3475
1250

1250

2900
B
5800

2900
2900
5800

2900
2900
5800

2900
D
1886

1876
2850 1250 4550 1250 4550 1250 4550 1250 4550 1250 2830

E
CARCON SUBSTATION FOUNDATION LAYOUT

DRAWING SUBMITTED TO/FOR: DATE REMARKS CONTRACTOR DESIGNER: OWNER : PROJECT : DRAWN : FILE NO. SHEET NO.
WRB
TENDERING: 0 1-6-2016
TOLEDO CARCON POWER STATION CHECKED : AJB 7
ENG-FM-004-1

FOR APPROVAL:
REVISION

1 DRAWING NO.
EFF: 8-1-15

FOR CONSTRUCTION: 2 APPROVED : GOC 19911 - E01


ASIAPHIL MANUFACTURING INDS., INC. PROJECT LOCATION: SHEET CONTENT: OF
AS BUILT: 3
SCALE : NTS FEEDER NO.
4 CEBU FOUNDATION PLAN LAYOUT 9
RECEIVED BY:
5 1150 PRES. QUIRINO AVE. EXTN. PACO, MANILA DATE : 12/26/2015
1 2 3 4 5 6 7 8 9

THIS DOCUMENT REMAINS THE EXCLUSIVE PROPERTY OF ASIAPHIL MANUFACTURING IND., INC. REPRODUCTION OR ANY USE NOT IN CONFORMITY WITH THE INTENDED APPLICATION IS NOT PERMISSIBLE.
A

TOP VIEW
2930

2380
NEW TOP VIEW
FOUNDATION 1029
BLACKOUT
2380

B
676 1029 676
BLACKOUT

A A

600
1470
2229

1029
670

110mm BOTHWAYS &

2229

1029
200mm O.C BOTHWAYS

600
B M20x300
FIXING ANCHOR 2229 GENERAL NOTES:
2380 NEW
C BOLT 1029 FOUNDATION
1029 1. COMPRESSIVE STRENGTH OF CONRETE AT 28-DAY PERIOD SHALL BE
100

670

100
2380 f'c = 4000psi FOR FOUNDATION AND
300

FGL. 100 f'c = 3000psi FOR LEAN CONCRETE RESPECTIVELY


300

FGL. 100
300

1029 @ 200mm O.C BOTHWAYS 2. ALL STEEL REINFORCEMENT SHALL CONFORM w/ ASTM A615 GRADED

100
100

100
f'y = 4000psi
1050

1050
FGL. 100 3. CONCRETE MINIMUM CONCRETE COVER

300
1400

750

1400

750

50mm = EXPOSED

100
75mm = BELOW GRADE LINE
4. PROVIDE NON-SHRINK GROUT BETWEEN STEEL STRUCTURE BASE
350

350

PLATE & CONCRETE PEDESTAL.


350

@ 110mm O.C BOTHWAYS

SECTION "A"
400 2130 400 EXISTING 400 670 400 EXISTING
2930 FOUNDATION FOUNDATION
1470

SECTION "A" SECTION "B"


D C1 PLINTH PAD REBAR DETAIL FOR DEAD TANK
1.1 SCALE NTS

C1 69kV DEAD TANK CB FOUNDATION DETAILS


1 SCALE NTS

DRAWING SUBMITTED TO/FOR: DATE REMARKS CONTRACTOR DESIGNER: OWNER : PROJECT : DRAWN : FILE NO. SHEET NO.
WRB
TENDERING: 0 1-6-2016
TOLEDO CARCON POWER STATION CHECKED : AJB 7
ENG-FM-004-1

FOR APPROVAL:
REVISION

1 DRAWING NO.
EFF: 8-1-15

FOR CONSTRUCTION: 2 APPROVED : GOC 19911 - E01


ASIAPHIL MANUFACTURING INDS., INC. PROJECT LOCATION: SHEET CONTENT: OF
AS BUILT: 3
SCALE : NTS FEEDER NO.
4 CEBU PCB FOUNDATION DETAILS 9
RECEIVED BY:
5 1150 PRES. QUIRINO AVE. EXTN. PACO, MANILA DATE : 12/26/2015

You might also like