Pro-MEC VCB/VI
Vacuum Circuit Breaker
Ratings H1-4
Constructional and operating characteristics H1-10
Control circuit diagram H1-11
7.2kV dimension H1-12
H1 Vacuum Interrupter
Features & Ordering information
Structure
Operating characteristics
Ratings and Specifications
Dimensions
H1-52
H1-53
H1-54
H1-55
H1-58
Vacuum Circuit Breaker
LS Pro-MEC VCB is user-friendly to give more convenience
and safety by providing high speed interrupting time (3cycles),
adopting the rapid auto-reclosing method, and having
wide range of accessories.
H1-2
VACUUM CIRCUIT BREAKER
H1-3
Vacuum Circuit Breaker
Ratings
Type �-20D
LVB-06� �-25D
LVB-06�
Rated voltage (kV) 7.2 7.2
Rated normal current (A) 630 1250 2000 630 1250 2000
Rated frequency (Hz) 50/60 50/60
Rated short-circuit breaking current (kA) 20 25
Rated short-circuit breaking capacity (MVA) 250 310
Rated short-time withstand current (kA/3sec) 20 25
Rated short-circuit making current (kAp) 52 65
Rated breaking time (Cycle) 3 3
Rated opening time (sec) ≤ 0.04 ≤ 0.04
No-load closing time (sec) ≤ 0.06 ≤ 0.06
Withstand Power frequency (kV/min) 20 20
voltage Impulse (kV/1.2×50㎲) 60 60
Rated operating sequence O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO
Mechanical M2 (10,000 times) M2 (10,000 times)
Type
Electrical E2 (List1) E2 (List1)
test
Capacitive current switching Note 1) C2 C2
Without maintenance (Time) 20000 20000
Mechanical
Maintenance (Time) 30000 30000
Lifetime
Without maintenance (Time) 20000 20000
Electrical
Maintenance (Time) 30000 30000
Auxiliary switch 4a4b, 10a10b 4a4b, 10a10b
Fixed Visible, Fixed Visible, Fixed Visible, Fixed Visible, Fixed
E-type Visible, Clip Visible, Tulip Visible, Clip Visible, Tulip
Installing F-type Visible, Clip Visible, Tulip Visible, Clip Visible, Tulip
Draw-out
method - Visible, Clip Visible, Tulip Visible, Clip Visible, Tulip
type G-type Note 2)
T Enclosed, Tulip Enclosed, Tulip Enclosed, Tulip Enclosed, Tulip
M-type Note 2) Enclosed, Tulip Enclosed, Tulip
E-type (kg) 94 99 134.5 94 99 134.5
VCB F-type (kg) 95 100 135.5 95 100 135.5
Weight G, M-type (kg) 95 (137) 100 (147) 135.5 (163.5) 95(137) 100(147) 135.5(163.5)
Note 3) E-type (kg) 37 39.5 60 37 39.5 60
Cradle F-type (kg) 39 41.5 62.5 39 41.5 62.5
G-type (kg) 39(103) 41.5(107) 62.5(117) 39(103) 41.5(107) 62.5(117)
Applied standard IEC 62271-100 IEC 62271-100
Test laboratory KERI Note 4) � �
Note 1) Applied cable-charging current switching test
2) In the event of ordering Enclosed Tulip type for G class VCB, please add “T” in the end of type name. (Ex: LVB-06G-20D/06-1A2B-T)
3) ( )* indicates the weight of Enclosed Tulip installing method VCB.
4) KERI: Korea Electrotechnology Research Institute.
▲ Visible VCB ▲ E-type cradle ▲ E-type cradle ▲ F -type cradle ▲ G-type cradle
(Draw-out type) (Visible, Clip contact) (Visible, Tulip contact) (Visible, Clip contact) (Visible, Tulip contact)
H1-4
Type �-32D
LVB-06� �-40D
LVB-06�
Rated voltage (kV) 7.2 7.2
Rated normal current (A) 1250 2000 3150 1250 2000 3150
Rated frequency (Hz) 50/60 50/60
Rated short-circuit breaking current (kA) 31.5 40
Rated short-circuit breaking capacity (MVA) 390 500
Rated short-time withstand current (kA/3sec) 31.5 40
Rated short-circuit making current (kAp) 82 104
Rated breaking time (Cycle) 3 3
Rated opening time (sec) ≤ 0.04 ≤ 0.04
No-load closing time (sec) ≤ 0.06 ≤ 0.06
Withstand Power frequency (kV/min) 20 20
voltage Impulse (kV/1.2×50㎲) 60 60
Rated operating sequence O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO
Mechanical M2 (10,000 times) M2 (10,000 times)
Type
Electrical E2 (List1) E2 (List1)
test
Capacitive current switching Note 1) C2 C2
Without maintenance (Time) 20000 20000
Mechanical
Maintenance (Time) 30000 30000
Lifetime
Without maintenance (Time) 20000 20000
Electrical
Maintenance (Time) 30000 30000
Auxiliary switch 4a4b, 10a10b 4a4b, 10a10b
Fixed Visible, Fixed Visible, Fixed Visible, Fixed Visible, Fixed
E-type Visible, Tulip Visible, Clip Visible, Tulip Visible, Tulip
Installing F-type Visible, Tulip Visible, Tulip Visible, Tulip Visible, Tulip
Draw-out
method - Visible, Tulip Visible, Tulip Visible, Tulip Visible, Tulip
type G-type Note 2)
T Enclosed, Tulip - Enclosed, Tulip -
M-type Enclosed, Tulip - Enclosed, Tulip -
E-type (kg) 131.5 134.5 210 135 138 210
VCB F-type (kg) 132.5 135.5 211 136 139 211
Weight G, M-type (kg) 132.5(159) 135.5(160) 220 136(162.5) 139(163.5) 220
Note 3) E-type (kg) 52 60 131 52 60 131
Cradle F-type (kg) 54.5 62.5 135 54.5 62.5 135
G-type (kg) 62.5(110) 135(117) 155 62.5(110) 135(117) 155
Applied standard IEC 62271-100 IEC 62271-100
Test laboratory KERI Note 4) � �
Note 1) Applied cable-charging current switching test
2) In the event of ordering Enclosed Tulip type for G class VCB, please add “T” in the end of type name. (Ex: LVB-06G-20D/06-1A2B-T)
3) ( )* indicates the weight of Enclosed Tulip installing method VCB.
4) KERI: Korea Electrotechnology Research Institute
▲ Enclosed VCB ▲ G-type Cradle ▲ Visible, Clip contact ▲ Visible, Tulip contact ▲ Enclosed, Tulip contact
(Draw-out type, G-type) (Enclosed, Tulip contact)
H1-5
Vacuum Circuit Breaker
Ratings
H1-6
Type �-25D/06, 12, 20, 25
LVB-17� �-40D/12, 20,30
LVB-17�
Rated voltage (kV) 17.5 17.5
Rated normal current (A) 630 1250 2000 2500 1250 2000 3150
Rated frequency (Hz) 50/60 60
Rated short-circuit breaking current (kA) 25 40
Rated short-circuit breaking capacity (MVA) 750 1200
Rated short-time withstand current (kA/3sec) 25 40
Rated short-circuit making current (kAp) 65 104
Rated breaking time (Cycle) 3
Rated opening time (sec) ≤0.04
No-load closing time (sec) ≤0.06
Withstand Power frequency (kV/min) 38
voltage Impulse (kV/1.2×50㎲) 95
Rated operating sequence O-0.3s-CO-3min-CO
Mechanical M2 (10,000 times)
Type
Electrical E2 (List1)
test
Capacitive current switching Note 1) C2
Without maintenance (Time) 20000
Mechanical
Maintenance (Time) 30000
Lifetime
Without maintenance (Time) 20000
Electrical
Maintenance (Time) 30000
Auxiliary switch 4a4b,10a10b
Fixed Visible, Fixed -
H1-7
Vacuum Circuit Breaker
Ratings
▲ Fixed type VCB ▲ E-type cradle ▲ F-type cradle ▲ G-type cradle ▲ G-type cradle
(Withdrawable by lever) (Withdrawable by screw)
H1-8
Motor
When the closing spring is charged, the control power of motor is turned off by the built-in limit s/w.
DC 48V 21 4 350 13
DC 110V 20 3 330 12
DC 125V 20 3 330 12
DC 220V 17 2.6 374 12
Note 1) Range of the normal operating voltage: 85~110%
2) DC 24V is the underdeveloped rating.
Rated voltage Rated current (A) Rated voltage Rated current (A)
DC 48V 6 DC 48V 6
DC 110V 3 DC 110V 3
DC 125V 3 DC 125V 3
DC 220V 2.5 DC 220V 2.5
Note 1) Range of the normal operating voltage: 85~110% Note 1) Range of the normal operating voltage: 70~110%
2) DC 24V is the underdeveloped rating. 2) DC 24V is the underdeveloped rating.
Auxiliary switch
Standard 4a4b / Optional 10a10b �Position of the Aux.contact switch
General Inductive Contact VCB “a” contact “b”contact
Classification
load (A) load (A) configuration ON ON OFF
250V 10 5 OFF OFF ON
AC
125V 10 5
4a4b
Contact Ratings 250V 10 5
10a10b
DC 125V 10 5
30V 10 5
Note) The contact capacity of the following accessories are the same with that of the Aux. switch. Position switch, Closing spring
contact, Charging complete indicating contact, Position switch of the earthing switch, Mechanically operated cell switch,
Truck operated cell switch.
Charged Discharged
Close position Open position
Counter
Mechanically counts the switching of the VCB by 5digits analog type counter (Standard option)
H1-9
Vacuum Circuit Breaker
Constructional and operating characteristics
① Charge Indicator
of the closing spring
② Close button
③ Key lock (Optional)
④ Trip button
① ⑤ ⑤ Manual charge hole
⑥ Position indicator
⑪ of the main contacts
②
⑦ Counter
③ ⑨ ⑧ Screw hole for draw-in
and draw-out
④ ⑨ Nameplate
⑩ Mounting hole
⑥ ⑪ Safety cover
Manual charge
Insert the charge handle into the manual charge hole in the front of a
VCB, and rotate it to clockwise over 40times and the charge
complete with a metal sound.
Motor charge
If you apply the control power to a VCB, the closing spring will be
charged automatically by a motor and then the control power will be
turned off by the built-in limit s/w. Please use the same control
voltage for motor, Closing coil, Trip coil.
H1-10
Control circuit diagram
∅: External terminal of VCB 52b: Auxiliary switch (NC) Connecting terminal arrangement
52: Vacuum circuit breaker LS1: Closing interlock limit switch (only withdrawable type)
M: Spring charging motor LS2: Motor stopping, closing spring charged indication A Type B Type
TC: Trip coil LS3: Anti-closing, anti-pumping limit switch
TC1: Secondary Trip coil LCS1: Opening latch checking switch(preventing closing
C: Closing coil unless the trip latch is properly reset)
Y: Anti-pump relay LS4, LS5: Position s/w (close in test position)
52a: Auxiliary switch (NO) LS6, LS7: Position s/w (close in run position)
H1-11
※ Above circuit diagram is based on ‘OFF’ status of VCB. and closing spring is charged.
Vacuum Circuit Breaker
7.2kV dimension (VCB)
H1-12
LVB-06E, F, G-20D, 25D, 32D, 40D E, F, G class - (630/1250/2000A)
(Unit: mm)
<Terminal conductor>
�Top
H1-13
Vacuum Circuit Breaker
7.2kV dimension (VCB)
H1-14
LVB-06G-32D, 40D G class (Visible, Tulip contact) - (3150A)
(Unit: mm)
�Front �Side
�Top
H1-15
Vacuum Circuit Breaker
7.2kV dimension (Cradle)
�Front �Side
�Top
H1-16
LCL-06E-20D, 25D, 32D, 40D E class (Visible, Tulip contact)
(Unit: mm)
�Front �Side
Rating 1250A 2000A
A 10 20
�Top
<Terminal conductor>
H1-17
Vacuum Circuit Breaker
7.2kV dimension (Cradle)
�Front �Side
<Terminal conductor>
�Top
H1-18
LCL-06F-32D, 40D F class (Visible, Tulip contact) - (1250/2000A)
(Unit: mm)
�Front �Side
Rating 1250A 2000A
A 10 20
<Terminal conductor>
�Top
�Top
H1-19
Vacuum Circuit Breaker
7.2kV dimension (Cradle)
�Top
<Terminal conductor>
H1-20
LCL-06G-20D/T, 25D/T, 32D/T, 40D/T G class (Enclosed, Tulip contact) - (630/1250/2000A)
(Unit: mm)
�Front �Side
�Top
<Terminal conductor>
20/25kA 31.5/40kA
Rating
630A 1250A 2000A 1250A 2000A
A 6 12 25 12 25
B ∅29 ∅48 ∅48
H1-21
Vacuum Circuit Breaker
7.2kV dimension (Cradle)
�Side
�Top
<Terminal conductor>
H1-22
12kV dimension (VCB)
�Front �Side
668
69
355
549 438
H1-23
Vacuum Circuit Breaker
12kV dimension (VCB)
�Front �Side
360
806.6
348.5
714 290
10
747 502
�Top
210 210
676
H1-24
12kV dimension (Cradle)
�Front �Side
�Top
<Terminal conductor>
25kA 31.5kA
Rating
630A 1250A 2000A 1250A 2000A
A 12 25 12 25
B ∅29 ∅48
H1-25
Vacuum Circuit Breaker
12kV dimension (Cradle)
�Front �Side
1250A:12t
2000A:25t
295
1235
630
731.5
946
<Terminal conductor>
�Top 150 150
60
26
26
83
RUN
150
600
560
150
100 662
H1-26
LCL-12G-32D/LCL-12G-40D G class (Enclosed, Tulip contact) - (3150A)
(Unit: mm)
�Front �Side
12 12
360
1100
439
764
1014
<Terminal conductor>
�Top
230 230
120
70
35
145
210
760
800
210
100 724
H1-27
Vacuum Circuit Breaker
17.5kV dimension (VCB)
�Front �Side
Rating 630A 1250A/2000A
A 6 20
�Top
<Terminal conductor>
H1-28
LVB-17E, F-25D E, F class (Visible, Tulip contact) - (630/1250/2000A)
(Unit: mm)
�Front �Side
H1-29
Vacuum Circuit Breaker
17.5kV dimension (VCB)
�Front �Side
�Top
<Terminal conductor>
H1-30
LVB-17G-40D G class (Visible, Tulip contact) - (1250/2000A)
(Unit: mm)
H1-31
Vacuum Circuit Breaker
17.5kV dimension (Cradle)
�Front �Side
�Top
<Terminal conductor>
H1-32
LCL-17E-25D E class (Visible, Tulip contact) - (2500A)
(Unit: mm)
�Front �Side
�Top
<Terminal conductor>
H1-33
Vacuum Circuit Breaker
17.5kV dimension (Cradle)
�Front �Side
Rating 630A 1250A 2000A
A 6 10 20
�Top
<Terminal conductor>
H1-34
LCL-17F-25D F class (Visible, Tulip contact) - (2500A)
(Unit: mm)
�Front �Side
�Top
<Terminal conductor>
H1-35
Vacuum Circuit Breaker
17.5kV dimension (Cradle)
�Front �Side
�Top
<Terminal conductor>
H1-36
LCL-17G-25D G class (Visible, Tulip contact) - (2500A)
(Unit: mm)
�Front �Side
�Top
<Terminal conductor>
H1-37
Vacuum Circuit Breaker
17.5kV dimension (Cradle)
�Side
�Top
<Terminal conductor>
H1-38
LCL-17G-40D G class (Visible, Tulip contact) - (3150A)
(Unit: mm)
�Side
�Top
<Terminal conductor>
H1-39
Vacuum Circuit Breaker
24kV dimension (VCB)
�Front �Side
<Terminal conductor>
Note ) In case of 12.5kA & 16kA 630A, the dimension shown in parenthesis should be applied.
H1-40
LVB-20G-13D, 16D, 25D G class (Visible, Tulip contact) - (630/1250A)
(Unit: mm)
�Front �Side
�Front �Side
H1-41
Vacuum Circuit Breaker
24kV dimension (Cradle)
�Front �Side
Rating A B T
630, 1250A 768 190.5 10
2000A 778 185.5 20
<Terminal conductor>
�Top
Note) Insulation barrirer is not used for rating 12.5kA 630A and 16kA 630A
H1-42
LCL-20E-13D/T, 16D/T, 25D/T E class (Enclosed, Tulip contact) - (630/1250/2000A)
(Unit: mm)
�Front �Side
Rating A B T
630, 1250A 768 190.5 10
2000A 778 185.5 20
10(630/1250A)
20(2000A)
265 265 15
340
1033
115
404.5
280
∅6.5
730 947.5 97.5
960 1120
972 1167
42
660
40.5
ST: 260 25
300
265
80
80
40
40
40
40 20 40 20 40 20
210.5
265
202
245
300
7-∅14
100
40
90
Note) Insulation barrirer is not used for rating 12.5kA 630A and 16kA 630A
H1-43
Vacuum Circuit Breaker
24kV dimension (Cradle)
�Front �Side
Rating A B T
630, 1250A 768 190.5 10
2000A 778 185.5 20
<Terminal conductor>
�Top
Note) Insulation barrirer is not used for rating 12.5kA 630A and 16kA 630A
H1-44
LCL-20F-13D/T, 16D/T, 25D/T F class(Enclosed, Tulip contact) - (630/1250/2000A)
(Unit: mm)
�Front �Side
Rating A B T
630, 1250A 768 190.5 10
2000A 778 185.5 20
<Terminal conductor>
�Top
Note) Insulation barrirer is not used for rating 12.5kA 630A and 16kA 630A
H1-45
Vacuum Circuit Breaker
24kV dimension (Cradle)
�Front �Side
�Top
<Terminal conductor>
H1-46
LCL-20G-13D/T, 16D/T, 25D/T G class (Enclosed, Tulip contact) - (630/1250/2000A)
(Unit: mm)
�Front �Side
�Top
<Terminal conductor>
210mm
�Earthing Switch
H1-47
Vacuum Circuit Breaker
Accessories
Button padlock
Button padlock protects 'ON' or 'OFF' button when accident is occurred
by operation at discretion.
It is available to operate after release button padlock.
Button cover
Button cover protects 'ON' of 'OFF' button when accident is
occurred by operation at discretion. It is available to operate by push
bar.
<Push bar>
<G class>
H1-48
Accessories
Charge indicator
Remotely indicates the charging is completed.
(Standard Feature)
- Terminal No.: 9, 10
Position padlock
The hole to prevent the draw-in and out of a VCB from the present
position.('Run' or 'Test')
Standard option in the interlock lever of the E, F class draw-out type
VCB. (Hole size = ∅ 8)
H1-49
Vacuum Circuit Breaker
Accessories
H1-50
Accessories for Cradle
Shutter padlock
The hole to lock the shutters (load and line side) in close position, to
increase the safety during the maintenance of a VCB draw-out
position.
(Hole size = ∅8)
Padlock
To prevent the insert draw-in/out handle to a screw hole by operating
G class VCB temporarily
H1-51
Vacuum Circuit Breaker
Accessories
Optional accessories
Capacitor trip device (CTD) �Dimension
When the control power is off, the
CTD supply the power for tripping
a VCB.
Ratings Specification
Type CB-T1 CB-T2
Rated input voltage AC100/110V AC200/220V
Freguency (Hz) 50/60 50/60 �Connection diagram �CDT
Charging volt(V) 140/155 280/310
Charging time Within 10 Sec. after the AC power off
Tripping time Within 30 Sec. after the AC power off
Allowable Input
85% ~ 100% 85% ~ 110%
voltage range
Capacitor rating(μF) 1000 560
Rectifier �Dimension
When the DC power is not available, rectify the AC power and
get the DC power for closing coil.
Type AC Input voltage Output current Rating time
150
100
1∅ 100/110V
VCB-X 40A DC 10 sec.
1∅ 200/220V
70
29.5
25
80 40
�Connection diagram
+
- ~ ~
Standard tool
E, F class G class
H1-52
Types and ordering information
LVB 20 G 13 D 06 1A 2B B, C, D
Cradle
LCL 20 G 13 D 06 A, B, C
LS Cradle Installation method Breaking current Note1) Revision No. Rated current Accessories
E E class draw-out type 8 8kA A Conventional 04 400A Note3) A MOS(3a4b)+ TOC(3a4b)
F F class draw-out type 13 12.5kA D Pro-MEC 06 630A Note3) B Earthing Switch
G G class draw-out type 16 16kA Pro-MEC 12 1250A Earthing Switch Position Switch+
Rated voltage Note2) E Note3) C
20 20kA (Minimized type) 20 2000A Earthing Switch Locking coil
06 7.2kV
25 25kA 30 3150A T Enclosed type, Tulip contact
20 24kV
32 31.5kA Position S/W Block
PS
40 40kA (24kV E/F class only)
H1-53
Vacuum Circuit Breaker
Types and ordering information
12kV
LVB 12 G 25 D 06 1A 2B B, C1, D1
Cradle
LCL 12 G 25 D 06 A, B, C
LS Cradle Installation method Breaking current Revision No. Rated current Accessories
G class 25 25kA D Pro-MEC 06 630A T Enclosed type, Tulip contact
G
draw-out type 32 31.5kA 12 1250A
40 40kA 20 2000A
Rated voltage
30 3000A
12 12kV
H1-54
Vacuum Circuit Breaker
Types and ordering information
17.5kV
LVB 17 G 25 D 06 1A 2B B, C1, D1
Cradle
LCL 17 G 25 D 06 A, B, C
LS Cradle Installation method Breaking current Revision No. Rated current Accessories
E E class draw-out type 25 25kA D Pro-MEC 06 630A A MOC (3a4b) + TOC (3a4b)
F F class draw-out type 40 40kA 12 1250A Note) ‘A’ is for ‘G’ class only
G G class draw-out type 20 2000A
Rated voltage
25 2500A
17 17.5kV
30 3150A
H1-55
Vacuum Interrupter
Features & Ordering information
Features
�Small Size and Light Weight
�High performance, reliability, and
long life are assured.
�Maintains High Vacuum
�High-alumina ceramics provide
superior mechanical strength and
easy degassing.
�High speed interruption and short
arcing time.
�The LS Vacuum Interrupter can
meet all IEC, ANSI and NEMA
performance standards.
Ordering Information
LV 07 08 0 A
Rated short
Basic type Rated voltage Ampere Revision No.
circuit current
L LS 07 7.2kV 04 4.5kA Below
0
V Vacuum / 12kV 08 8kA 630A
10 15kV 12 12.5kA 1 1250A
24 24kV 16 16kA 2 2000A
20 20kA 3 3150A
25 25kA
31 31.5kA
40 40kA
50 50kA
H1-56
Structure
Movable Electrode
Bellows
Bellows Shield
Ceramic
Arc Shield
Contacts
End Shield
Fixed Electrode
H1-57
Vacuum Interrupter
Operating characteristics
Fault
current
Voltage Phenomena
(ⅰ) Arc reignition
(ⅱ) Restrikes
(ⅲ) B. I. L
(ⅳ) AC voltage
withstand
Recovery
voltage
H1-58
Ratings and Specifications
Outer view
b 78 92 92 123
c 62 62 62 79
Opening speed, average 0 to 75% of full stroke (m/s) 0.6 0.7~1.0 0.7~1.0 0.7~1.0
Closing speed, average last 33% of full stroke (m/s) 0.3 0.7~1.0 0.7~1.0 0.7~1.0
H1-59
Vacuum Interrupter
Ratings and Specifications
Outer view
Rated short circuit making current (kA, peak) 65 52 65/81.9 81.9 104
Opening speed, average 0 to 75% of full stroke (m/s) 1.0~1.3 0.7~1.0 1.0~1.3 1.2~1.6 0.7~1.0 1.0 1.2
Closing speed, average last 33% of full stroke (m/s) 0.7~1.0 0.7~1.0 0.7~1.0 0.7~1.0
Added force from atmospheric pressure (kg�f) 227 154 227/306 306 367
H1-60
LV-24120 LV-24121A LV-24252A LV-24403 LV-12503 LV-25000
50 50 50 70 20 50 70 19 48 60
3 3 3 3 3 1
15 15 17 17 10 9.5
3 3 3 3 2 2.54
1 1 1 1 2 1
1) Only with additional external insulation
H1-61
Vacuum Interrupter
Dimensions
Note)
H1-62
LV-12503 LV-24120 LV-24121A
49.5
H1-63
Pro-MEC MCSG VCB
Vacuum Circuit Breaker for MCSG
Features and Structure H2-2
Control circuit diagram H2-4
Dimensions H2-5
Contents
H2
Vacuum Circuit Breaker for MCSG
Features and Structure
Features
�Module type VCB
�Convenient especially for fabricating MCSG
- Housing is designed like VCB compartment style
- MCSG panel can be easily constructed if combined with Low voltage compartment, Busbar
compartment and Cable compartment.
�Main functions
- Breaker : draw- in or out electrically or manually
- Compartment : 3-positions
�Standard
- IEC 62271-100
① Name plate
② Manual closing button
③ Keylock
④ Manual trip button
⑤ Manual charging hole
⑥ Contact position
indicator
⑦ Closing spring
⑦
charge indicator
②
⑤ ⑧ Operation counter
③
⑨ Insertion &
④
⑥ Draw-out screw
① ⑩ Geared Mechanism
⑧
Electrical
drive unit
H2-2
Ratings
Type ‐25□
LVB‐ □-25□
□/06 ‐25□
LVB‐ □-25□
□/20
Rated voltage (kV) 25.8
Rated normal current (A) 630 2000
Rated frequency (Hz) 60
Rated short-circuit breaking current (kA) 25
Rated short-circuit breaking capacity (MVA) 1100
Rated short-time withstand current (kA) 25/3s
Rated short-circuit making current (kA) 65
Rated breaking time (Cycles) 3
Withstand Power frequency (kV) 50/1min
voltage Impulse (kV/1.2××50㎲ ) 125
TRV rising rate (kV/㎲ ) 0.47
TRV max. (kV) 41
Rated operating sequence O-0.3s-CO-3min-CO
Mechanical lifetime 10,000operations
Electrical lifetime 10,000operations
Rated control voltage (V) DC 110V
Rated trip voltage( V) DC 110V
Standard auxiliary switch 4a4b, 8a8b
Rated opening time (s) ≤ 0.04
No-load closing time (s) ≤ 0.06
Rated charging motor current (A) ≤7
Rated closing coil current (A) ≤5
Rated trip coil current (A) ≤5
Closing spring charging time (s) ≤ 12
Draw-in/out motor voltage (V) DC 110V
Draw-in/out motor current (A) ≤5
Distance between phases (mm) 265
breaker 205 236.5
Weight (kg)
compartment 281 293
Installing G
Applied standard IEC 62271-100
�Breaker
LVB 25 G 25 I 06 1A 2B B,C,D
LS VCB Installation method Version Control voltage Accessories
G Gclass draw-out 1A DC110V B Position Switch
1B DC220V C1 Button Padlock(ON)
Rated voltage Rated current 1C DC48V C2 Button Padlock(OFF)
25 25.8kV 06 630A 1E DC125V C3 Button Padlock(ON/OFF)
20 2000A 1F AC220(M), DC110(TC) D1 Button Cover(ON)
Breaking current 1H AC220(M), DC220(TC) D2 Button Cover(OFF)
25 25kA 1T AC110(M), DC110(TC) D3 Button Cover(ON/OFF)
E Button Padlock(ON)+Button Cover(OFF)
Auxiliary switch F Button Padlock(OFF)+Button Cover(ON)
2G 4a4b(B type connector) G Key Lock
2H 8a8b(B type connector) H Secondary Trip Coil
�Cradle(Compartment)
LCL 25 C 13 D 06 A,B,C
LS VCB Rated voltage Installation method Breaking current Version Rated current Accessories
25 25.8kV C Bushing 25 25kA 06 630A B Earthing Switch
20 2000A E Door
H2-3
3
H2-4
Auxiliary switch
8a 8b
P P P P
4a 4b Position S/W
CW CCW
CS CS (인입) (인출) Test Run
A1 9 A3 A5 13 14 15 16 17 22 24 26 28 40 42 44 46 36 38 50 52 54 56 58 70 1 3
43 43
89X 89Y 13 13
44 44 89X 89Y
LS2 3 LS3 4
1 1 3 14 14
Ya 1 1
4 2 2 4 LS6 LS5
6
1 2 2 1
Yb 21 21
5 89M
5 6 89Y 89X 22 24 26 28 40 42 44 46 36 38 50 52 54 56 58 70 1 3
30 52a 22 22 2
M 52b PS1 PS2
31 8 8
6 3 7 6' 23 25 27 29 41 43 45 47 37 39 51 53 55 57 59 71 2 4
89X 89Y 33 33
C Y 9 9 89Y 89X
A2 10 A4 A6 23 25 27 29 41 43 45 47 37 39 51 53 55 57 59 71 2 4
Control circuit diagram
N N N
Indication for closing spring "charged" is available.
C : Closing coil
C 50 51 52 53 C Y : Anti-pump relay
B 13 14 15 16 17 36 37 38 39 B 52a : Auxiliary switch (NO)
A A1 A2 A3 A4 A5 A6 22 23 24 25 26 27 28 29 A 52b : Auxiliary switch (NC)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 LS1 : Closing interlock limit switch(only withdrawable type)
( 4a 4b ) LS2 : Motor stopping, closing spring charged indication
LS3 : Anti-closing, Anti-pumping limit switch
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 LS5 : "Off" at Test Position
D 1 2 3 4 9 10 D LS6 : "Off" at Run Position
C 50 51 52 53 54 55 56 57 58 59 70 71 C PS1 : Position S/W("On" at Test Position)
PS2 : Position S/W("On" at Run Position)
B 13 14 15 16 17 42 43 44 45 46 47 36 37 38 39 B
89X : Auxiliary Relay for Inserting
A A1 A2 A3 A4 A5 A6 22 23 24 25 26 27 28 29 40 41 A 89Y : Auxiliary Relay for withdrawing
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 89M : Motor for withdrawing and Inserting
( 8a 8b )
SECONDARY DISCONNECT WIRING
( TOP VIEW )
Dimensions
45
70 103 75
C 10 60 2-∅13
372.6
st:310
30
425
86
190
26.8 3-∅10
340
340
1365
1365
425
86
1082
30
60
265 265 265 265
652.4
175
425
B B (Earthing)
(212.4)
∅6.5
(183.4)
183.4
15.4
TEST RUN
95
95
1
45
35
A
53 894 53 410 553 1 Earthing 968
1000 963 1000
128 50
265
175
700
700
630A
265 265 445
2000A
340
445
1013
340
608
860 350 50
886 481
912 785
H2-5
Vacuum Circuit Breaker for MCSG
Dimensions
45
125
25t(2000A)
10t(630/1250A)
398.6
415
st:310
Test Run
500
Test
190
74
(Door)
340
**Option 3-∅10
415
1750
500
265 265
User Bus
415
767.4 175
(Earthing)
36 ∅6.5
M12 TAP
500
Test B (DP:24)
415
454
244
265 265
(Earthing S/W)
125
**Option
45
A 35
1000 39 963 320.9 968
17
26
9-∅11Mounting Hole
83
700
950
26
26
25
60
100 763 100
70
50 340 40 483 50
H2-6
Power Plants VCB
Vacuum Circuit Breaker for Power Plants
Ratings H3-4
Ratings of Accessories H3-5
Accessories H3-6
Control circuit diagram H3-8
Contents Dimensions
Types and ordering information
H3-9
H3-14
H3
Vacuum Circuit Breaker
Power Plants
A product developed for water and thermal power plants due
to the revision and application of Kepco’s standard (ES150)
followed by the IEC standard revision. It has completed the
high capacity (40~50kA) VCB series for power plants by
securing higher breaking capacity, safety and reliability.
H3-2
Vacuum Circuit Breakers
for Power Plants
H3-3
Vacuum Circuit Breaker for Power Plants
Ratings
Rated normal current (A) 1200 2000 3000 1250 2000 2500 3150 1250 2000 3150
Type Mechanical M2
Weight Breaker G-type (kg) 200 260 200 260 200 260
H3-4
Ratings and auxiliary devices
Motor
When the closing spring is charged, the control power of motor is turned off by the built-in limit s/w.
DC 110V 20 3 330 12
DC 125V 20 3 330 12
Note) Range of the normal operating voltage: 85~110% of rated voltage
Rated voltage Rated current (A) Rated voltage Rated current (A)
DC 110V 3 DC 110V 3
DC 125V 3 DC 125V 3
Note) Range of the normal operating voltage: 75~125% of rated voltage Note) Range of the normal operating voltage: 60~125% of rated voltage
Auxiliary switch
Standard configuration : 3a3b1b of early-b contact function exists inside Position of the Auxiliary switch
Resistive Inductive Contact Switch Mechanism MOC TOC
Classification
load (A) load (A) configuration
Breaker a b a b a b
110V 10 5
Contact Ratings DC 3a3b CLOSE ON OFF ON OFF ON OFF
125V 10 5 RUN
Note) The contact ratings of Mechanical Operated Cell Switch(MOC) OPEN OFF ON OFF ON OFF ON
are the same with that of the Aux. switch.
CLOSE ON OFF ON * OFF * ON OFF
TEST
Truck Operated Cell Switch(TOC) OPEN OFF ON OFF * ON * OFF ON
Note) * applied in the VCB of which MOC is operable at the TEST position.
Resistive Inductive Contact
Classification
load (A) load (A) configuration
110V 10 5
Contact Ratings DC 3a3b
125V 10 5
Charged Discharged
Close position Open position
Counter
Mechanically counts the operation of the VCB by 5digits
H3-5
Vacuum Circuit Breaker for Power Plants
Accessories
�Position padlock
It is located at the screw hole to prevent the draw-in and out of a breaker
from the present position(Disconnected, Test or Connected)
�Position interlock
The breaker is locked in each position-Disconnected, Test or Connected,
thus it is necessory to release the lock before draw-in or out of a breaker
from the present position.
�Auto connection
When the breaker is moved to Test position from Disconnected position
the connector for control powers is automatically connected. In case of
reverse moving of the breaker the connector is automatically
disconnected.
�Code plate
When the breaker is inserted to the cradle, if the ratings does not match
with the cradle, it mechanically prevents the breaker from being inserted
into the cradle.
H3-6
Accessories for breakers
H3-7
H3-8
<TOC> Cell switch in service position
15 16 17
25 26 27
A
12 13 14
22 23 24
<MOC>
15 16 17 30 34 36 38 50 52
P P P
Auxiliary switch
25 26 27 31 35 37 39 51 53 CS CS 3a 3b
B A1 A3 A5 22 24 26 54 56 58
12 13 14 6 22 24 26 28 40
22 23 24 7 23 25 27 29 41
LS2 LS3
4
3 1 3
Ya
Control circuit diagram
4 2 4 6
1
Yb
5 6 22 24 26 54 56 58
52b 30 52a
31
5 3 7 7 23 25 27 55 57 59
M C Y 1
A1 A3 A5 54
A2 A4 A6 55
Note) Diagram shows the circuit breaker in position“OFF”with closing spring“Charged”
22 24 26 56 58
23 25 27 57 59
∅ : External terminal of VCB
52 : Vacuum circuit breaker A B
(12P TAP PLUG)
Vacuum Circuit Breaker for Power Plants
LVB-06G-40H, 40J G class (Visible, Tulip contact)-(1200, 1250, 2000A) (unit : mm)
�Front �Side
54(male conductor)
722 336
360
815.2
130
351.3
368.2
60
10
696 686.2
717
�Top
254 254
<Conductor>
685.2
532
584
1200/1250/2000A
745
H3-9
Vacuum Circuit Breaker for Power Plants
Dimensions - Breakers
LVB-06G-40H, 40J G class (Visible, Tulip contact)-(2500, 3000, 3150A) (unit : mm)
�Front �Side
79(male conductor)
722 336
Heat sink
(only for 3150A)
360
815.2
130
349.8
368.2
60
10
696 686.2
717
�Top
<Conductor>
254 254
685.2
532
584
2500/3000/3150A
745
H3-10
LVB-06G-50J G class (Visible, Tulip contact)-(1250, 2000A) (unit : mm)
�Front �Side
54(male conductor)
722
115.5 336
140
360
130
815.7
403.8
341.3
368.2
60
696 677.2 10
717
�Top
254 254
676.2
532
584
745
H3-11
Vacuum Circuit Breaker for Power Plants
Dimensions - Breakers
�Front �Side
79(male conductor)
722
336
115.5 140
360
107
130
815.7
136.5
358.7
341.8
267.8
150.2
445.8
696 541
10
677.2
717
�Top
254 254
676.2
532
584
H3-12
Cradles (unit : mm)
4-M12
252 374
DP20 1134
50 35 240
150 500 361
∅14
∅218
∅148
∅79
310
(Earthing)
50
254
140 123
175
2500/3000/3150A
816
776
103.5
254
DP20 35 240
235.5
∅218
∅148
310
∅54
36
338
360
1035
61(레일폭)
449.5
644
59
61
151.5
75.8
T.O.C(6a6b) 1038.5
H3-13
Vacuum Circuit Breaker for Power Plants
Types and ordering information
Breaker
LVB 06 G 40 J 12 1A 2L P3,Q,R
Cradle
LCL 06 G 40 J 12 A1, A2
H3-14
Nuclear Power Plants VCB
Vacuum Circuit Breaker for Nuclear Power Plants
Ratings H4-4
Ratings of Accessories H4-5
Accessories H4-6
Control circuit diagram H4-8
Contents Dimensions
Types and ordering information
H4-9
H4-11
H4
Vacuum Circuit Breaker
Nuclear Power Plants
It was developed for KEPCO nuclear power stations. This breaker
satisfies quality, safety measures (secure from earthquake and
other environments), and surge protection class complies with
“1E-CLASS” ±provisions. It is featured with high breaking
technologies, safety, and reliability by applying our own vacuum
interrupters (50KA) approved by ANSI standard tests.
H4-2
Vacuum Circuit Breakers
for Nuclear Power Plants
1200 1200
3000 -
H4-4
Ratings of Accessories
Motor
When the closing spring is charged, the control power of motor is turned off by the built-in limit s/w.
Auxiliary switch
Standard configuration : Reversible 8C(5a3b)
and 2c(2b) with early-b contact function Position of the Auxiliary switch
30V 10 5
Charged Discharged
Close position Open position
Counter
Mechanically counts the operation of the VCB by 5digits
H4-5
Vacuum Circuit Breaker for Nuclear Power Plants
Accessories
�Auto connection
When the breaker is moved to Test position from Disconnected position the
connector for control powers is automatically connected.
In case of reverse moving of the breaker the connector is automatically
disconnected.
�Reversible contact
10 auxiliary switches are provided. 8 of them consist of reversible 8c which
can be changed from a(b) to b(a). Factory composition is 5a3b. And the
other 2 switches are supplied as 2b with early-b contact function
�Code plate
When the breaker is inserted to the cradle, if the ratings does not match
with the cradle, it mechanically prevents the breaker from being inserted
into the cradle.
�Auto discharge
In case the breaker is drawn-out when the closing spring is charged in the
position-Disconnected, Test or Connected, or the breaker is moved to
Disconnected position from Test position the closing spring shall be
automatically released.
H4-6
Accessories for cradles
�Mechanically operated cell switch (MOC)
This 6a6b switch indicates the 'ON' or 'OFF' condition of a VCB and is
operated in the positions of 'Run' and 'Test"..
H4-7
H4-8
P P P
Auxiliary switch
CS CS
5a 3b
A1 A3 A5 22 24 26 28 40 54 56 58
LS2 3 LS3 1 3 4
Ya
4 2 4 6
1
Yb
5 22 35 24 37 26 39 28 51 40 53 43 54 45 56 47 58
5 30 6
52b 52a
M
31
Control circuit diagram
6 6’ 23 34 25 36 27 38 29 50 41 52 42 55 44 57 46 59
3 7
N N N early b
Breaker
722
254 254
722
745
<Front view>
360
817
816
369
3000A
86.5
109.5 442.5
713
1200/2000A
<Side view>
H4-9
Vacuum Circuit Breaker for Nuclear Power Plants
Dimensions
Cradle
936
254 254
644
850
<Front view>
343 137
100
252
213
310
203
36
360
4-M12 DP18
1070
2-M12 DP24
1200/2000A
449
50
157
2-M12 DP24
3000A
195 630
1020
<Side view>
H4-10
Types and ordering information
Breaker
LVB 05 G 40 B 20 1A 2K 1
Cradle
LCL 05 G 40 B 20 1
2 Non 1E class
H4-11
Memo
H4-12
� For your safety, please read user's manual thoroughly before operating.
� Contact the nearest authorized service facility for examination, repair, or adjustment.
� Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions � Any maintenance and inspection shall be performed by the personnel having expertise concerned.
www.lsis.biz
2009. 02 Vacuum Circuit Breakers/Vacuum Interrupter(E) 2008. 11/(02) 2009. 02 Printed in Korea STAFF