BATCH CONTROLLER

WITH ONE STAGE CONTROL


DATASHEET F030 - BATCH CONTROLLER

Advantages Signal output


• Robust IP67 (NEMA Type4X) field enclosure. • One control output for one-stage batching.
It is so rugged, you can even stand on it!
• Intrinsically Safe available - ATEX, IECEx, FM and Signal input
CSA approval for gas and dust applications. Flow
• Programming can be done by your own crew, with • Ability to process all types of flowmeter signals:
the sensible menu-driven structure, saving cost Reed-switch, NAMUR, NPN/PNP pulse, Sine wave
and irritation. Know one, know them all! (coil), Active pulse signals, (0)4 - 20mA.
• Very diverse mounting possibilities: walls, pipes,
panels or directly onto outdoor sensors! Applications
• The F-Series is your first and safest choice for field
Features mount indicators in safe and hazardous area
• Large display shows preset value and running applications. Especially in harsh weather
batch value simultaneously. conditions like rain, snow, salty atmospheres and
• Self-learning overrun correction. temperatures between -40°C up to +80°C
• Easy operation to enter a batch value and to (-40°F up to 176°F).
control the process. • For batching small up to very large quantities.
• Count-up and count-down function available. Single or repeating batches. Alternative more
• Selectable on-screen engineering units; volumetric sophisticated models: F130 - F131, F136 and
or mass. 300-Series or the D-Series DIN panel mount
• Explosion/flame proof available. indicators and controllers.
• Loop or battery powered, 8 - 24V AC/DC or
115 - 230V AC power supply.
• Sensor supply 3.2 / 8.2 / 12 / 24V DC.
1
General information Signal input
Introduction The F030 accepts most pulse and analog input
The F030 is a straight forward but basic Batch signals for volumetric flow or mass flow
Controller. The operator can enter a batch quantity measurement. The input signal type can be
easily or execute repeating batches. During the selected by the user in the configuration menu
batch, the preset value is displayed as well as the without having to adjust any sensitive mechanical
batched (or remaining) quantity and the units of dip-switches, jumpers or trimmers. The analog
measurement. The automatic self-learning overrun input is available with lineair and square root cal-
correction will ensure an accurate result each batch culation and even as 4 - 20mA input loop powered.
again. A wide selection of options further enhances
the capabilities of this model, including Intrinsic Power requirements
Safety. Several power supply options are available to
power the F030 and sensor. A battery powered
Display version with a long life lithium battery which will
The display has large 17mm (0.67”) and 8mm last up to five years. For analog sensors, a 4 -
(0.31”) digits which are used to display the 20mA loop powered version is available as well. A
batched quantity and the preset value real sensor supply is offered with the 24V AC / DC
simultaneously. On-screen engineering units are or 115 - 230V AC power requirement options.
easily configured from a comprehensive menu.
A seven digit resettable "day total" is available as Hazardous area
well as an eleven digit non-resettable accumulated For hazardous area applications, this model has
total. All are backed-up in EEPROM memory every been ATEX, IECEx, FM and CSA certified
minute. A smart display update function achieves a Intrinsically Safe for gas and dust applications,
readable display even at -40°C / -40°F. with an allowed ambient temperature of
-40°C to +70°C (-40°F to +158°F). A flame proof
Backlight Ex d enclosure with ATEX certification is also
For those applications where readability during available.
day and night is an issue, a white backlight is
available. The intensity can be adjusted from the Enclosures
keyboard. The display is a transflective type, Various types of enclosures can be selected, all
which means that a high contrast reading is guaran- ATEX, IECEx, FM and CSA approved. As standard
teed in full sunlight as well as during the night. the F030 is supplied in an GRP panel mount
This backlight option is available Intrinsically Safe. enclosure. Most popular is our aluminum field
mount enclosure with IP67 / NEMA Type4X rating.
Configuration Both European or U.S. cable gland entry threads
All configuration settings are accessed via a are available.
simple operator menu which can be password
protected. Each setting is clearly indicated with an Overview application F030
alphanumerical description, which avoids
confusing abbreviations. Once familiar with one
F-series product, you will be able to program all
models in the series without a manual. All settings
are safely stored in EEPROM memory in the event
of sudden power failure.

Control output Control output


One output is available for one stage control of Flowmeter
smaller batchvolumes. The output signal can be a input
passive NPN or an active PNP transistor, or an
isolated electro-mechanical relay.

2 F030
Dimensions enclosures Terminal connections
Aluminum & GRP panel mount enclosure PB/PC - PD - PL - PX
FLOWMETER INPUT POWER REQUIREMENTS CONTROL OUTPUT BACKLIGHT
31 mm 29 mm
(1.22") (1.14") 130 mm (5.12")

02 04 05 06 07 08 09 10
120 mm (4.72")

115 (4.53") 01 03

98 (3.86")
P: coil PD: 16 - 30V DC OT: passive trans. ZB: 20 - 30V DC

+ + + +
P: reed switch / NPN Sensor supply:
For pulse input
+ (type P): 8.2V DC
HB & HC enclosures panel cut-out
P: active signal

+
Aluminum & GRP field / wall mount enclosures
P: PNP

130 mm (5.12") Ø 7mm (0.27") Ø 7mm (0.27") - +


P: namur
-
120 mm (4.72")

60 mm (2.36")

A: (0)4 - 20mA For analog input


(type A): voltage as
I+ connected to terminal 5.

75 mm (2.95") 112 mm (4.40") A - PL: 4 - 20mA PL: input loop powered.

I+
Aluminum GRP
30mm 30mm PX: 8 - 30V DC
22,50mm

+
HA HD
PG9 M20 x 1,5 PG9
PB / PC: battery powered
(PX is also available: if an external supply is connected,
1.18" 1.18" 30mm 30mm the battery supply will be switched off / on automatically.)
22,50mm
0.9"

HL HE
/ "NPT
1 2 /2"NPT
1
Ø16 Ø20 Ø16
22,50mm (0.9")

30mm 30mm
22,50mm

HM HF Terminal connections PF - PM
M16 x 1,5 M20 x 1,5 M16 x 1,5 Ø22 ( 7/8")

25mm 25mm
22,50mm
22,50mm

HN HG POWER REQUIREMENTS CONTROL OUTPUT FLOWMETER INPUT

M20 x 1,5 Ø20 Ø20

12mm 12mm
25mm 25mm
17mm

00 01 02 03 04 05 06 07
22,50mm

HO HH PF: 24V AC OA: active 24V DC P: coil


14mm

+
M20 x 1,5 M20 x 1,5 24mm 24mm Ø12
36mm 36mm
12mm 12mm
22,50mm (0.9")

30mm (1.18") 30mm (1.18") PF: 24V DC OT: passive trans. P: reed switch / NPN
17mm

- + + +
HP HJ
14mm

24mm 24mm 6 x M12 PM: 115 - 230V AC OR: mech. relay P: PNP
Ø22 ( 7/8") Ø22 ( 7/8") Ø22 ( 7/8")
36mm 36mm
= = - +
0.9"

P: namur
HT HK - +
/ "NPT
1 2 Flat bottom, no holes available.
P: active signal
1.18" 1.18"
+
0.9"

HU A: (0)4 - 20mA
/ "NPT
1 2 1
/2"NPT
/ "NPT
+
1 2
+
15mm 15mm
15mm

HV
16mm

38mm 4 x M20 x 1.5

HZ

F030 3
Typical wiring diagram F030-P-OT-PB-(PX)-(ZB) Typical wiring diagram F030-A-OT-PX-ZB

Type PB: Type PX:


TERMINAL CONNECTORS BATTERY POWERED TERMINAL CONNECTORS BASIC 8 - 30V DC POWER REQUIREMENTS
F0 - series F0 - series
(STANDARD)
10

10
Backlight supply Backlight option: type ZB Backlight supply Backlight option: type ZB
(not used in this example) 20 - 30V DC
Common ground Common ground
09

09
e.g. relay e.g. relay
+
08

08
8 - 30V DC
Common ground Common ground
07

07
Control output type OT: - Control output type OT:
passive transistor passive transistor

+
Power supply type PX:
05

05
Main supply Main supply Power supply type PX: 8 - 30V DC
8 - 30V DC
8 - 30V DC
(not used in this example)
Common ground Common ground
04

04
-

Supply *
Circuit depends on

Circuit depends on
Flowmeter input type A:
type of signal

type of signal
03

(0)4 - 20mA
Signal Flowmeter input Signal
type P:
02

02
pulse
01

01
Common ground Common ground

* Sensor supply voltage for pulse flowmeter type P: * Sensor supply voltage for pulse flowmeter type P:
Terminal 3: 1.2 / 3.2V DC. Terminal 3: 1.2 / 3.2 V DC.

* Sensor supply voltage for analog flowmeter type A: * Sensor supply voltage for analog flowmeter type A:
Termina 3: not available. Termina 3: not available.

Typical wiring diagram F030-A-OT-PL-(ZB) Typical wiring diagram F030-P-OT-PD-ZB


Type PL: Type PD:
TERMINAL CONNECTORS INPUT LOOP POWERED TERMINAL CONNECTORS 16 - 30V DC POWER REQUIREMENTS
F0 - series F0 - series

Backlight option: type ZB


20 - 30V DC
Backlight option: type ZB
10

10

Backlight supply (not used in this example) Backlight supply

Common ground Common ground


09

09

e.g. relay e.g. relay


+
08

08

8 - 30V DC
Common ground Common ground Control output type OT:
07

07

Control output type OT: -


passive transistor
passive transistor
Supply *
06

Sensor supply type PD: +


16 - 30V DC
05

Main supply 16 - 30V DC

Common ground
04

Flowmeter input type A - PL: Supply *


Circuit depends on

Circuit depends on
type of signal

type of signal

03

Input loop powered 4 - 20mA


Signal
+
Signal Flowmeter input
type P:
02

02

pulse
8 - 30V DC
01

01

Common ground - Common ground

Sensor supply: sensor is externally powered. * Sensor supply voltage for pulse flowmeter type P:
Terminal 3: 1.2 / 3.2V DC. Terminal 6 with type PD: 8.2V DC.

* Sensor supply voltage for analog flowmeter type A:


Termina 3: not available.
Terminal 6 with type PD: voltage as connected to terminal 5 (internally linked).

4 F030
Typical wiring diagram F030-P-OA-PF-ZB Typical wiring diagram F030-A-OR-PF-ZB

Type PF: Type PF:


TERMINAL CONNECTORS 24V AC / DC POWER REQUIREMENTS TERMINAL CONNECTORS 24V AC / DC POWER REQUIREMENTS
F0 - series F0 - series

Backlight option: type ZB Backlight option: type ZB


Internally powered. Internally powered.

Supply * Supply *
Circuit depends on

Circuit depends on
type of signal

type of signal
07

07
Flowmeter input type A:
Signal Flowmeter input Signal (0)4 - 20mA
type P:
06

06
pulse

Common ground Common ground


05

05
Control output type OR:
+
mechanic relay
04

04
Control output type OA:
- e.g. relay active 24V DC signal e.g. relay
03

03
02

02
Main supply Power supply type PF: 24V AC Main supply +
8 - 24V AC / DC
01

01
Power supply type PF: 24V DC
8 - 24V AC / DC
Common ground Common ground
00

00
-

* Sensor supply voltage for pulse flowmeter type P: * Sensor supply voltage for pulse flowmeter type P:
Terminal 7: 1.2 / 3.2 / 8.2 / 12 / 24V DC. Terminal 7: 1.2 / 3.2 / 8.2 / 12 / 24V DC.

* Sensor supply voltage for analog flowmeter type A: * Sensor supply voltage for analog flowmeter type A:
Terminal 7: 8.2 / 12 / 24V DC. Terminal 7: 8.2 / 12 / 24V DC.

Typical wiring diagram F030-A-OA-PM-ZB Typical wiring diagram F030-P-OR-PM-ZB


Type PM: Type PM:
TERMINAL CONNECTORS 115 - 230V AC POWER REQUIREMENTS TERMINAL CONNECTORS 115 - 230V AC POWER REQUIREMENTS
F0 - series F0 - series

Backlight option: type ZB Backlight option: type ZB


Internally powered. Internally powered.

Supply * Supply *
Circuit depends on

Circuit depends on
type of signal

type of signal
07

07

Flowmeter input type A:


Signal (0)4 - 20mA Signal Flowmeter input
type P:
06

06

pulse

Common ground Common ground


05

05

+
04

04

Control output type OA: Control output type OR:


- e.g. relay active 24V DC signal e.g. relay mechanic relay
03

03

N N
02

02

Main supply Power supply type PM: Main supply Power supply type PM:
115 - 230V AC 115 - 230V AC
L1 L1
01

01

Common ground Common ground


00

00

* Sensor supply voltage for pulse flowmeter type P: * Sensor supply voltage for pulse flowmeter type P:
Terminal 7: 1.2 / 3.2 / 8.2 / 12 / 24V DC. Terminal 7: 1.2 / 3.2 / 8.2 / 12 / 24V DC.

* Sensor supply voltage for analog flowmeter type A: * Sensor supply voltage for analog flowmeter type A:
Terminal 7: 8.2 / 12 / 24V DC. Terminal 7: 8.2 / 12 / 24V DC.

F030 5
Hazardous area applications The F030-PD-XI offers a 8.2V DC sensor supply
The F030-XI has been certified according ATEX to power e.g. a Namur sensor or the input
and IECEx by KEMA and according CSA c-us and voltage to power an analog sensor.
FM for use in Intrinsically Safe applications with An ATEX approved flame proof Ex d enclosure is
an ambient temperature of -40°C to +70°C available as well. Please contact your supplier
(-40°F to +158°F). for further details.
• The ATEX markings for gas and dust
applications are: Certificate of conformity KEMA 05ATEX1168 X
II 1 G Ex ia IIC T4 Ga • IECEx KEM 08.0006X • CSA.08.2059461 X
II 1 D Ex ia IIIC T100 °C Da.
• The IECEx markings for gas and dust
applications are: Ex ia IIC T4 Ga and CERTIFICATE OF CONFORMITY

Ex ia IIIC T100 °C Da. 1.


2.
3.
HAZARDOUS (CLASSIFIED) LOCATION ELECTRICAL EQUIPMENT PER US REQUIREMENTS
Certificate No:
Equipment:
FM16US0177X
F0 Series General Purpose Indicators

• The CSA c-us markings are: Class I/II/III,


(Type Reference and Name)

4. Name of Listing Company: Fluidwell BV

5. Address of Listing Company: Voltaweg 23

Division 1, Groups A, B, C, D, E, F, G,
5466 AZ Veghel
Netherlands

6. The examination and test results are recorded in confidential report number:

3033306 dated 25 June 2009

Temperature class T4 and Class I, Zone 0, 7. FM Approvals LLC, certifies that the equipment described has been found to comply with the following Approval
standards and other documents:

FM Class 3600:2011, FM Class 3610:2015, FM Class 3810:2005,

AEx ia IIC T4.


ANSI/UL 60079-0:2013, ANSI/UL 60079-11:2014, ANSI/IEC 60529:2004

8. If the sign ‘X’ is placed after the certificate number, it indicates that the equipment is subject to specific
conditions of use specified in the schedule to this certificate.

9. This certificate relates to the design, examination and testing of the products specified herein. The FM

• The FM markings are: Class I/II/III, Division 10.


Approvals surveillance audit program has further determined that the manufacturing processes and quality
control procedures in place are satisfactory to manufacture the product as examined, tested and Approved.

Equipment Ratings:

1, Groups A, B, C, D, E, F, G, Temperature
Intrinsically Safe for use in Class I / II / III, Division 1, Groups A, B, C, D, E, F and G
Class I, Zone 0, Group IIC, Hazardous (Classfied) Locations

class T4 and Class I, Zone 0, AEx ia IIC T4. Certificate issued by:

It is allowed to connect up to three I.S. power J. E. Marquedant


20 September 2016
Date
Manager, Electrical Systems

supplies to power the unit, sensor and back- To verify the availability of the Approved product, please refer to www.approvalguide.com

THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE

light. Consult the certificate for the maximum FM Approvals LLC. 1151 Boston-Providence Turnpike, Norwood, MA 02062 USA
T: +1 (1) 781 762 4300 F: +1 (1) 781 762 9375 E-mail: information@fmapprovals.com www.fmapprovals.com

F 347 (Mar 16) Page 1 of 3

input and output values of the circuits.

Configuration example IIA - IIB and IIC - F030-P-OT-PC-(PX)-XI-(ZB) - Battery powered unit

HAZARDOUS AREA SAFE AREA


TERMINAL CONNECTORS
F0 - series

Supply backlight Backlight option: type ZB


10

(not used in this example).


Common ground
09

Intrinsically Safe apparatus


Power supply or
+
Uo = max. 30V
switch interface
08

Io = max. 200mA For example


- Po = max. 1,2W MTL 5525
Common ground MTL 5511
07

Control output type OT: passive transistor e.g. relay

Basic power supply type PX:


8 - 30V DC
05

Main supply (not used in this example).

Common ground
04
Circuit depends on
type of signal

Supply *
03

I.S. flow meter


input type: P
Signal
02

pulse

Common ground
01

* Sensor supply voltage for pulse flowmeter type P : Terminal 3: 1.2 / 3.2V DC.
Please note: type PX may be used in combination with the battery (type PC). PX will power the unit; the battery will be disabled automatically till power is disconnected.

6 F030
Configuration example IIA - IIB and IIC - F030-P-OT-PX-XI-(ZB) - Basic power requirement 8 - 30V DC

HAZARDOUS AREA SAFE AREA


TERMINAL CONNECTORS
F0 - series

Supply backlight Backlight option: type ZB


10

(not used in this example).


Common ground
09

Intrinsically Safe apparatus


Power supply or
+
Uo = max. 30V
switch interface
08

Io = max. 200mA For example


- Po = max. 1,2W MTL 5525
Common ground MTL 5511
07

Control output type OT: passive transistor e.g. relay

+
Uo = max. 30V Power supply
05

Main supply Io = max. 200mA


Power supply type PX: 8 - 30V DC
For example
- Po = max. 1,2W MTL 5525
Common ground
04
Circuit depends on
type of signal

Supply *
03

I.S. flow meter


input type: P
Signal
02

pulse

Common ground
01

Note: above values are safety values.


Consult the technical specification for operational values.
* Sensor supply voltage for pulse type P: Terminal 3: 1.2V / 3.2V DC.
Please note: type PX may be used in combination with the battery (type PC). PX will power the unit; the battery will be disabled automatically till power is disconnected.

Configuration example IIA - IIB and IIC - F030-P-OT-PX-XI-ZB - Basic power requirement 8 - 30V DC

HAZARDOUS AREA SAFE AREA


TERMINAL CONNECTORS
F0 - series
+
Uo = max. 30V Power supply
Supply backlight
10

Backlight option: type ZB Io = max. 200mA


For example
- Po = max. 0,75W MTL 5525
Common ground
09

Intrinsically Safe apparatus


Power supply or
+
Uo = max. 30V
switch interface
08

Io = max. 200mA For example


- Po = max. 1,2W MTL 5525
Common ground MTL 5511
07

Control output type OT: passive transistor e.g. relay

+
Uo = max. 30V Power supply
05

Main supply Io = max. 200mA


Power supply type PX: 8 - 30V DC
For example
- Po = max. 1,2W MTL 5525
Common ground
04
Circuit depends on
type of signal

Supply *
03

+
Uo = max. 30V Power supply
I.S. flow meter
Signal
02

input type: P Io = max. 150mA


For example
pulse Po = max. 0,92W
- MTL 5525
Common ground
01

Note: above values are safety values.


Consult the technical specification for operational values.
* Sensor supply voltage for pulse type P: Terminal 3: 1.2V / 3.2V DC.
Please note: type PX may be used in combination with the battery (type PC). PX will power the unit; the battery will be disabled automatically till power is disconnected.

F030 7
Configuration example IIA - IIB and IIC - F030-P-OT-PD-XI-ZB - Power requirement 16 - 30V DC

HAZARDOUS AREA SAFE AREA


TERMINAL CONNECTORS
F0 - series
+
Uo = max. 30V Power supply
Supply backlight
10

Backlight option: type ZB Io = max. 200mA


For example
- Po = max. 0,75W MTL 5525
Common ground
09

Intrinsically Safe apparatus


Power supply or
+
Uo = max. 30V
switch interface
08

Io = max. 200mA For example


- Po = max. 1,2W MTL 5525
Common ground MTL 5511
07

Control output type OT: passive transistor e.g. relay

Supply *
06

+
Uo = max. 30V Power supply
05

Main supply Io = max. 200mA


Power supply type PD: 16 - 30V DC
For example
- Po = max. 1,2W MTL 5525
Common ground
04
Circuit depends on
type of signal

Supply *
03

I.S. flow meter


input type: P
Signal
02

pulse

Common ground
01

Note: above values are safety values.


Consult the technical specification for operational values.
* Sensor supply voltage for pulse type P: Terminal 3: 1.2V / 3.2V DC. Terminal 6: 8.2V DC.
Please note: type PD may be used in combination with the battery (type PC). PD will power the unit; the battery will be disabled automatically till power is disconnected.

Configuration example IIA - IIB and IIC - F030-A-OT-PD-XI-ZB - Power requirement 16 - 30V DC

HAZARDOUS AREA SAFE AREA


TERMINAL CONNECTORS
F0 - series
+
Uo = max. 30V Power supply
Supply backlight
10

Backlight option: type ZB Io = max. 200mA


For example
- Po = max. 0,75W MTL 5525
Common ground
09

Intrinsically Safe apparatus


Power supply or
+
Uo = max. 30V
switch interface
08

Io = max. 200mA For example


- Po = max. 1,2W MTL 5525
Common ground MTL 5511
07

Control output type OT: passive transistor e.g. relay

Supply *
06

+
Uo = max. 30V Power supply
05

Main supply Io = max. 200mA


Power supply type PD: 16 - 30V DC
For example
- Po = max. 1,2W MTL 5525
Common ground
04
Circuit depends on
type of signal

I.S. flow meter input - type A: (0)4 - 20mA

Signal
02

Common ground
01

Note: above values are safety values.


Consult the technical specification for operational values.
* Sensor supply voltage for analog flow meter type A: Terminal 6: as input voltage terminal 5 (internally linked).
Please note: type PD may be used in combination with the battery (type PC). PD will power the unit; the battery will be disabled automatically till power is disconnected.

8 F030
Configuration example IIA - IIB and IIC - F030-A-OT-PL-XI-ZB - Input loop powered

HAZARDOUS AREA SAFE AREA


TERMINAL CONNECTORS
F0 - series
+
Uo = max. 30V Power supply
Supply backlight
10

Backlight option: type ZB Io = max. 200mA


For example
- Po = max. 0,75W MTL 5525
Common ground
09

Intrinsically Safe apparatus


Power supply or
+
Uo = max. 30V
switch interface
08

Io = max. 200mA For example


- Po = max. 1,2W MTL 5525
Common ground MTL 5511
07

Control output type OT: passive transistor e.g. relay


Circuit depends on
type of signal

I.S. flow meter input - type A-PL: 4 - 20mA input loop powered.
+
Uo = max. 30V Power supply
Signal
02

Io = max. 93mA
For example
- Po = max. 0,92W MTL 5525
Common ground
01

Note: above values are safety values.


Consult the technical specification for operational values.
Sensor supply is not available: unit is input loop powered (type PL).
Please note: type PL may be used in combination with the battery (type PC). PL will power the unit; the battery will be disabled automatically till power is disconnected.

Configuration example IIA - IIB and IIC - F030-A-OT-PX-XI-ZB - Basic power requirement 8 - 30V DC

HAZARDOUS AREA SAFE AREA


TERMINAL CONNECTORS
F0 - series
+
Uo = max. 30V Power supply
Supply backlight
10

Backlight option: type ZB Io = max. 200mA


For example
- Po = max. 0,75W MTL 5525
Common ground
09

Intrinsically Safe apparatus


Power supply or
+
Uo = max. 30V
switch interface
08

Io = max. 200mA For example


- Po = max. 1,2W MTL 5525
Common ground MTL 5511
07

Control output type OT: passive transistor e.g. relay

+
Uo = max. 30V Power supply
05

Main supply Io = max. 200mA


Power supply type PX: 8 - 30V DC
For example
- Po = max. 1,2W MTL 5525
Common ground
04
Circuit depends on
type of signal

I.S. flow meter input - type A: (0)4 - 20mA


+
Uo = max. 30V Power supply
Signal
02

Io = max. 150mA
For example
- Po = max. 0,92W MTL 5525
Common ground
01

Note: above values are safety values.


Consult the technical specification for operational values.
* Sensor supply voltage for analog flow meter type A: not available in this example.
Please note: type PX may be used in combination with the battery (type PC). PX will power the unit; the battery will be disabled automatically till power is disconnected.

F030 9
Technical specification Directives & Standards
EMC Directive 2014/30/EU, FCC 47 CFR part 15.
General Low voltage Directive 2014/35/EU.
Display RoHS Directive 2011/65/EU.
Type High intensity reflective numeric and ATEX / IECEx Directive 2014/34/EU, IEC 60079-0, IEC 60079-11,
alphanumeric LCD, UV-resistant. IEC 60079-26.
Dimensions 90 x 40mm (3.5" x 1.6"). FM FM Class No. 3600, FM Class No. 3610.
Digits Seven 17mm (0.67") and eleven 8mm (0.31") digits. CSA CSA 22.2 No. 157-92.
Various symbols and measuring units. IP & NEMA EN 60529 & NEMA 250.
Refresh rate User definable: fast, 1sec , 3sec, 15sec, 30sec, off.
Option ZB Transflective LCD with white LED-backlight.
Intensitiy can be adjusted in the configuration menu. Enclosure
Good readings in full sunlight and darkness. General
Also available Intrinsically Safe. Window Polycarbonate window.
Sealing Silicone.
Control keys Three industrial micro-switch keys. UV-resistant
Ambient temperature
silicone keypad.
Safe areas -40°C to +80°C (-40°F to +176°F).
Intrinsically Safe -40°C to +70°C (-40°F to +158°F).
Aluminum wall / field mount enclosures
General Die-cast aluminum wall/field mount enclosure IP67 /
Power requirements
NEMA Type4X with 2-component UV-resistant coating.
Type PB Long life Lithium battery - life-time depends upon
Dimensions 130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D.
settings and configuration - up to 5 years.
Weight 1100 gr.
(requires PD, PL or PX)
Type HA Cable entry: 2 x PG9 and 1 x M20.
Type PC Intrinsically Safe long life lithium battery - life-time
Type HL Cable entry: 2 x 1/2" NPT.
depends upon settings and configuration - up to 5
Type HM Cable entry: 2 x M16 and 1 x M20.
years. (requires XI, and PD, PL or PX)
Type HN Cable entry: 1 x M20.
Type PD 16 - 30V DC. Power consumption max. 1 Watt.
Type HO Cable entry: 2 x M20.
Type PF 24V AC / DC ± 10%. Power consumption max. 15 Watt.
Type HP Cable entry: 6 x M12.
Type PL Input loop powered from sensor signal 4 - 20mA
Type HT Cable entry: 1 x 1/2" NPT.
(type A).
Type HU Cable entry: 3 x 1/2" NPT.
Type PM 115 - 230V AC ± 10%. Power consumption max. 15 Watt.
Type HV Cable entry: 4 x M20.
Type PX 8 - 30V DC. Power consumption max. 0.3 Watt.
Type HZ Cable entry: no holes.
Type ZB 20 - 30V DC. Power consumption max. 1 Watt.
With type PF / PM: internally powered.
Note PB/PF/PM Not available Intrinsically Safe. GRP wall / field mount enclosures
Note PF/PM The total consumption of the sensor, active output General GRP wall/field mount enclosure IP67 / NEMA Type4X,
type OA and backlight type ZB may not exceed UV-resistant and flame retardant.
400mA @ 24V DC. Dimensions 130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D.
Note For Intrinsically Safe applications, consult the safety Weight 600 gr.
values in the certificate. Type HD Cable entry: no holes.
Type HE Cable entry: 2 x Ø 16mm and 1 x Ø 20mm.
Sensor excitation Type HF Cable entry: 1 x Ø 22mm (7/8").
Type PB/PC/PX 3.2V DC for pulse signals and 1.2V DC for coil G
Type H Cable entry: 2 x Ø 20mm.
pick-up. Type HH Cable entry: 6 x Ø 12mm.
Note This is not a real sensor supply. Only suitable for Type HJ Cable entry: 3 x Ø 22mm (7/8").
sensors with a very low power consumption like coils Type HK Flat bottom, cable entry: no holes.
(sine wave) and reed-switches.
Type PD for pulse signals: 1.2 / 3.2 / 8.2V DC - max. Panel mount enclosures
5mA@8.2V DC. For analog signals, the sensor supply Dimensions 130 x 120 x 60mm (5.12" x 4.72" x 2.36") - W x H x D.
voltage is according to the power supply voltage Panel cut-out 115 x 98mm (4.53" x 3.86") L x H.
connected. Type HB Die-cast aluminum panel mount enclosure IP65 /
Type PF / PM With pulse input: 1.2 / 3.2 / 8.2 / 12 / 24V DC - NEMA Type4X.
max. 400mA @ 24V DC. Weight 600 gr.
With analog input: 8.2 / 12 / 24V DC - Type HC GRP panel mount enclosure IP65 / NEMA Type4X,
max. 400mA @ 24V DC. UV-resistant and flame retardant.
Weight 450 gr.
Terminal connections
Type Removable plug-in terminal strip.
Wire max. 1.5mm2 and 2.5mm2.

Data protection
Type EEPROM backup of all settings. Backup of running
totals every minute. Data retention at least 10 years.
Password Configuration settings can be password protected.

10 F030
Hazardous area Operational
Explosion proof Operator functions
ATEX certification II 2 G / Ex d IIB T5 Gb. Displayed • Preset value - can be entered by the operator.
II 2 D / Ex t IIIB T100 °C Db. functions • Batched quantity or remaining quantity.
Type XF Dimensions of enclosure: 300 x 250 x 200mm • Total and accumulated total.
(11.8" x 9.9" x 7.9") L x H x D. • Total can be reset to zero by pressing the STOP-key
Weight Appr. 15kg. twice.
Note IECEx available on request.
Preset and total
Intrinsically Safe Digits 7 digits.
ATEX II 1 G Ex ia IIC T4 Ga. Units L, m3, GAL, USGAL, kg, lb, bbl, no unit.
certification II 1 D Ex ia IIIC T100 °C Da. Decimals 0 - 1 - 2 or 3.
IECEx Ex ia IIC T4 Ga. Note Total can be reset to zero.
certification Ex ia IIIC T100 °C Da.
CSA c-us Intrinsically Safe for Class I/II/III, Div. 1, Accumulated total
certification Groups A, B, C, D, E, F, G, Temp. class T4 Digits 11 digits.
and Class I, Zone 0, AEx ia IIC T4. Units / decimals According to selection for total.
FM certification Intrinsically Safe for Class I/II/III, Div. 1, Note Can not be reset to zero.
Groups A, B, C, D, E, F, G, Temp. class T4
and Class I, Zone 0, AEx ia IIC T4.
Intrinsically Safe isolators
Ambient Ta -40°C to +70°C (-40°F to +158°F).
ACG01 MTL5511 - One channel pulse or switch output
transfer from hazardous area to safe area.
Signal input ACG02 MTL5525 - One channel power supply from safe area
Flowmeter sensor to hazardous area (e.g. to power the unit with PD or
Type P Coil / sine wave (HI: 20mVpp or LO: 80mVpp - to power a switching or analog device in hazardous
sensitivity selectable), NPN/PNP, open collector, reed- area).
switch, Namur, active pulse signals 8 - 12 and 24V DC. ACG03 MTL5541 - One channel 4 - 20mA repeater from
Frequency Minimum 0Hz - maximum 7kHz for total and flow rate. hazardous area to safe area.
Maximum frequency depends on signal type and ACG04 MTL 5051 - Bi-direction serial-data-isolator
internal low-pass filter. E.g. reed switch with (for Modbus communication).
low-pass filter: max. frequency 120Hz. ACG05 MTL5516C - Two channel pulse or switch output
K-Factor 0.000010 - 9,999,999 with variable decimal position. transfer from hazardous area to safe area.
Low-pass filter Available for all pulse signals. ACG06 MTL5513 - One channel pulse or switch output
Option ZF coil sensitivity 10mVpp. transfer from hazardous area to safe area.
Option ZG coil sensitivity 5mVpp. ACG07 MTL5546Y - One channel isolated driver bringing
Type A (0)4 - 20mA. Analog input signal can be scaled to any 4 - 20mA from safe area to hazardous area, HART
desired range within 0 - 20mA. transparent, OCD.
Type U 0 - 10V DC. Contact factory.
Accuracy Resolution: 16 bit. Error < 0.01mA / ± 0.05% FS. Display example - 90 x 40mm (3.5" x 1.6")
Low level cut-off programmable.
Span 0.001 / 999,999 with variable decimal position.
Update time Four times per second.
Voltage drop Type A: max. 1V DC @ 20mA.
Voltage drop Type A - PL (loop powered): max. 2.6V DC @ 20mA.
Relationship Linear and square root calculation.
Note For signal type A: external power to sensor is
required; e.g. type PD.

Signal output
Digital output
Function Control output according the batch process.
Type OA One active 24V DC transistor output (PNP);
load max. 400mA (requires PF or PM).
Type OR One electro-mechanical relay output - isolated;
max. switch power 230V AC (N.O.) - 0.5A
(requires PF or PM).
Type OT One passive transistor output (NPN) - not isolated.
Max. 50V DC - 300mA per output.

F030 11
Ordering information
Standard configuration: F030-P-HC-OT-PX-XX-ZX.
ordering information: F030 -_ -H _ -O _ -P _ -X _ -Z _
Flowmeter input signal
A (0)4 - 20mA input.
P Pulse input: coil, npn, pnp, namur, reed-switch.
Panel mount enclosures - IP65 / NEMA Type4X
HB Aluminum enclosure.
HC GRP enclosure.
GRP field / wall mount enclosures - IP67 / NEMA Type4X
HD Cable entry: no holes.
HE Cable entry: 2 x Ø 16mm & 1 x Ø 20mm.
HF Cable entry: 1 x Ø 22mm (7/8”).
GH Cable entry: 2 x Ø 20mm.
HH Cable entry: 6 x Ø 12mm.
HJ Cable entry: 3 x Ø 22mm (7/8”).
HK Flat bottom, cable entry: no holes.
Aluminum field / wall mount enclosures - IP67 / NEMA Type4X
HA Cable entry: 2 x PG9 + 1 x M20.
HL Cable entry: 2 x 1/2”NPT.
HM Cable entry: 2 x M16 + 1 x M20.
HN Cable entry: 1 x M20.
HO Cable entry: 2 x M20.
HP Cable entry: 6 x M12.
HT Cable entry: 1 x 1/2”NPT.
HU Cable entry: 3 x 1/2”NPT.
HV Cable entry: 4 x M20.
HZ Cable entry: no holes.
Digital output signal
OA One active transistor output - requires PF or PM.
OR One mechanical relay output - requires PF or PM.
OT One passive transistor output - standard configuration.
Power requirements
PD 16 - 30V DC + sensor supply.
PF 24V AC / DC + sensor supply.
PL Input loop powered from sensor signal type “A”.
PM 115 - 230V AC + sensor supply.
PX Basic power supply 8 - 30V DC (no real sensor supply).
Additional battery supply (optional)
PB Lithium battery powered - requires PD, PL or PX.
PC Lithium battery powered - Intrinsically Safe - requires XI, and PD, PL or PX.
Hazardous area
XI Intrinsically Safe, according ATEX, IECEx, CSA c-us and FM.
XF Ex d enclosure - 3 keys according ATEX.
XX Safe area only.
Other options
ZB Backlight.
ZF Coil input 10mVpp.
GZ Coil input 5mVpp.
ZX No options.
The bold marked text contains the standard configuration.
Available Intrinsically Safe.
Copyright: Fluidwell bv - 2017 - F030-DATA-EN-V1727