Professional Documents
Culture Documents
Bulk amount of power supply is only possible if the following two conditions meet
satisfactorily:
In practice, the system should not be operated at the limit. It must have margin to
cater for the minor changes in load and other minor disturbances. This point is
categorized under the dynamic stability of the Power System.
Another aspect is that of the stability under major disturbances and contingencies.
This is dealt under the category of transient state stability.
Voltages must be kept near to their rated values.
2. Frequency stability
[short-term and long-term]
3. Voltage stability
[small disturbance and large disturbance]
Time scale Generator driven Load driven
Rotor angle stability
Short-term Short term voltage stability
Small signal Large signal
Long term Frequency stability Long term voltage stability
Classification of power system stability
Normal: All parameters in limit.
Alert: May lead to collapse due to
disturbance but still in limit (less
margin).
Restorative: Increase in reserve if
succeed then normal otherwise in alert.
Emergency: If severe event hits the
system while in alert situation but still
intact with system extreme limits.
In Extremis: Cascaded tripping and
outages.
Power System Stability Analogy
Due to transient
Stator with three phase
windings
LAGGING
CURRENT
BNET
BR LOAD ANGLE
‘δ’
WR
BS
Data:
Similarly draw the phasor diagrams for the unity and leading power factor
condition.
Equilibrium/Synchronism
Disturbance in the electrical torque of the machine can be split into two ways:
1. Synchronizing torque.
2. Damping Torque.
The nature of the system response to
the small disturbance depends upon
the operating conditions, excitation
control and transmission system
strength.
• Local Modes.
• Inter-area Modes.
• Control Modes.(poor tuning)
• Torsional Modes.(T-G shaft system
components.
First Swing
case of
instability
Post fault
condition
is small
signal
unstable
Inertia constant is defined as:
H=Stored energy at rated speed in MW/MVA Important terms:
rating
Type of generating unit H J: Moment of inertia
Thermal unit Jw=M=angular
3600 rpm 4.0-7.0 momentum
1800 rpm 6.0-9.0
H:Stored K.E (MJ)/MVA
Hydal unit 2.0-4.0
rating
In general form:
𝑬𝑽
𝑷𝒆 = 𝐬𝐢𝐧 𝜹
𝑿
Where;
Pe= Electrical power
E = Generated voltage
V = Terminal voltage
𝜹 = Load angle
δo
The ability of the synchronous machine to maintain its synchronism after being
subjected to small or large disturbance is referred as the rotor angle stability
A2
Pm2
A1
Pm1
∂max ∂
This method also gives the maximum input power which
can be applied while stability is maintained.
If both the areas are not equal then accelerating
momentum can never be overcome.
The stability limit occurs when ∂max is at the intersection
of line Pm and the power-angle for 900 < ∂ <1800.
APPLICATION TO SUDDEN INCREASE IN INPUT
Pe POWER
Pm2
Pm1
∂o ∂1 ∂max ∂
APPLICATION TO SUDDEN INCREASE IN INPUT
Pe POWER
Pm2
Pm1
∂o ∂1 ∂max ∂
Application of equal area criterion to
various cases
Pm
∂
∂o ∂c ∂max
APPLICATION TO THREE PHASE-FAULT
During fault(fault
Pm on circuit 2 at some
distance)
∂o ∂c ∂max
∂
Pe
Pm
∂o ∂c ∂max
∂
Question:
The single-line diagram of through parallel transmission lines to a large
metropolitan system considered as an infinite bus. The machine is delivering 1.0
p.u and both the terminal and infinite bus voltages are 1.0. The generator
reactance is 0.2 p.u. Draw the power angle curve.
Question:
Calculate the critical clearing angle and time when the system is subjected to
three phase fault at point P on the short transmission line. The initial conditions
are same. H= 5 MJ/MVA.
The most practically available method today for transient stability analysis of complex
interconnected system is time domain simulation which uses non-linear differential
equations solved by step by step numerical integration techniques.
SOLUTION OF THE SWING
EQUATION
In this method we make use of the equation that was derived in
the Equal Area Criteria.
= =
Now the graph between time and load angle will be the swing curve as
shown below:
Using pre-calculated swing curves:
The simplest way to find out the critical clearing time is the use of sets of
pre-determined SWING CURVES.
Each curve in the curve family is responding to the constant value of Sin∂o with a
particular value of Power (p) as shown below:
REMARKS:
Lower
Speed To Turbine
Fly ball
Governor
High pressure
oil
Hydraulic
WR
Amplifier
Steam from Boiler
Speed
Lower
Changer
To Turbine
Main Valve
Raise
Fixed
Pivot
Fly ball
Governor
High
pressure oil Hydraulic
WR Amplifier
Fly-Ball/ Transducer and
Comparator Governor
Gain/Levers and
Linkages
Servo-motor/Hydraulic
Amplifier
Limits
Double
Cross-over
Power Fractions Flow LPT
HPT
Steam Chest
LPT
IPT
To Re-heater