You are on page 1of 6

International Journal of Advanced Computer Research (ISSN (print): 2249-7277 ISSN (online): 2277-7970)

Volume-2 Number-4 Issue-6 December-2012

Design of Earthing System for a Substation : A Case Study


O.P. Rahi1, Abhas Kumar Singh2, Shashi Kant Gupta3, Shilpa Goyal4
Electrical Engineering Department, National Institute of Technology, Hamirpur, India1,2,3,4

Abstract proper caution, the method described here is also


applicable to indoor portion of such substation. By
This paper presents the design of earthing system using proper conductor and electrode size, earthing
for 132 KV substations and simulation for system may be able to overcome lightening effects.
calculation of required parameters. This paper is to
provide information pertinent to safe earthing 2. Earthing system for a substation
practices in ac substation design and to establish the
safe limits of potential difference under normal and A. Components of earthing system
fault conditions. The grounding grid system of a An effective substation earthing system typically
practical 220 kV substation is calculated by consists of earth rods, connecting cables from buried
MATLAB program. The supporting data has been earthing grid to metallic parts of structures and
obtained from actual field tested at the substation. equipments, connections to earthed system neutrals,
Standard equations are used in the design of and the earth surface insulating covering material
earthing system to get desired parameters such as briefly discussed in [1,3]. Current flowing into the
touch and step voltage criteria for safety, earth earthing grid from lightening arrester operation
resistance, grid resistance, maximum grid current, impulse or switching surge flashover of insulators and
minimum conductor size and electrode size, line to ground fault current from the bus or connected
maximum fault current level and resistivity of soil. transmission lines all cause potential differences
By selection the proper horizontal conductor size, between earthed points in the substation. Without a
vertical electrode size and soil resistivity, the best properly designed earthing system, large potential
choice of the project for safety is performed. This differences can exist between different points within
paper mentions the calculation of the desired the substation itself. Under normal circumstances, it is
parameters which are simulated by MATLAB the current constitutes the main threat to personal.
program. Some simulated results are evaluated.
B. Data needed for design of earthing
Keywords  Substation grid area
 Soil resistivity at the site
component; Safe earthing system, Grounding, resistivity ,  Fault clearing time
AC substation, MATLAB program, Flowchart.  Maximum grid current
 Resistivity of soil at surface
1. Introduction
C. Factors on which design of earthmat
In substation earthing system is essential not only to depends
provide the protection of people working in the  Materials used for earth electrodes and
vicinity of earthed facilities and equipments against conductors must be chosen carefully taking
danger of electric shock but to maintain proper into account physical, chemical and
function of electrical system. Reliability and security economical constraints. Ground conductor
are to be taken in considerations as well as adherence must be adequate for fault current
to statutory obligations (IEEE and Indian standards on (considering corrosion). Basic requirements
electrical safety [1-2] and environmental aspects). are thoroughly studied in paper [4].
Earthing system thus design must be easily  Conductor sizing depends on fault current
maintained and future expansion must be taken into and conductivity as well as mechanical
account while designing the dimensions of earth mat. strength of material used.
 Resistivity of soil and surface layer
This paper is concerned with earthing practices and determines the STEP and TOUCH
design for outdoor AC substation for power frequency potentials, which determine safe values of
in the range of 50 Hz. DC substation GIS and operation as described in reference [1, 5-9].
lightening effects are not covered in this paper. With Also the multilayer resistivity has been a
228
International Journal of Advanced Computer Research (ISSN (print): 2249-7277 ISSN (online): 2277-7970)
Volume-2 Number-4 Issue-6 December-2012

subject of continuous attention by the F. Selection of Electrode material


researchers [10-13]. The material for grounding grid should have good
 A good grounding system provides a low conductivity, be mechanically rugged and resist
resistance in order to minimize GPR (ground fusing and deterioration of joints.
potential rise)[14]. Copper was very commonly used in the past. It has
 Grid geometry is a major factor in high conductivity and is resistant to underground
determining the step, touch and mesh corrosion. However, a grid of copper forms a
potential contours and current distribution in galvanic cell with other buried structure and pipes
grid. The limitations on the physical and is likely to hasten the corrosion of the latter.
parameters of a ground grid are based on Aluminium is not used because of corrosion problem.
economics and the physical limitations of the
installation of the grid. 3. Mathematical Description
D. Fault Clearing Time G. Safe limits and values of potentials
The faults clearing time is governed by system The safety of a person depends on preventing the
stability consideration and depend on protection and critical amount of shock energy from being absorbed.
switchgear equipment. Generally a value of 0.5 The maximum driving voltage of any accidental
seconds is assumed. circuit should not exceed the limits defined as
The size of the conductor is based on a time of 1 follows.
second. The tolerable step voltage criteria is

E. Determination of Maximum Grid Current


A single line to ground fault is more common and
causes more fault current as compared to a double
line to ground fault. Therefore , the design is based
on single line to ground fault current. For calculation The tolerable touch voltage criteria is
of this current grid resistance and fault resistance are
assumed to be zero. Then
Ig=SfIf
Where
Ig= symmetrical grid current , Amp
If= rms value of symmetrical ground fault
current, Where
Amp Cs = 1 for no protective surface layer
Sf= current division factor relating the ρs= the resistivity of the surface material in A-m
magnitude of fault current to that of its portion ts = duration of shock circuit in seconds
flowing in the earthing grid. The minimum conductor size formula is mentioned
Only a part of the total fault current flows through the below-
grid. The remaining current flows through the
overhead ground wires and other ground return paths.
The factor Sf gives this current division and can be
calculated, if the system data is known, from the
value of Ig the design value of grid current is found as
I=GfDfIg 3)
Where
I= maximum grid current
Gf= A factor to account for increase in fault Where
current due to system growth during life span of grid. Ko = 1/ αo or 1/ αo - Tr
Df= Decrement factor to account for tc = time of current flow in sec
asymmetry of the fault current wave. TCAP = thermal capacity factor
Typical values of Gf assumed in design, lie in the
range of 1.2 to 1.5 depending on the rate of growth of For grounding resistance, the following formula is
the system. used

229
International Journal of Advanced Computer Research (ISSN (print): 2249-7277 ISSN (online): 2277-7970)
Volume-2 Number-4 Issue-6 December-2012

D = spacing between conductor of the grid


d = diameter of grid conductor
Km = spacing factor for mesh voltage
Kii = 1 for grids with rods along perimeter
Kh = Corrective weighting factor for grid depth
Where
ρ = soil resistivity
Lt = total length of grid conductor
A = total area enclosed by earth grid
h = depth of earth grid conductor

For calculation of grid current, equation (5) is used Where


D = spacing between conductor of the grid
h = depth of burial grid conductor
n = number of parallel conductor in one direction
The length required to keep mesh voltage within safe
Where limits, can be calculated by
Ig = maximum grid current
3Io = symmetrical fault current in substation for
Conductor
sizing in A (11)
Sf = current diversity factor
Equation (6) is expressed for grid potential rise If the length of conductor in the Preliminary design is
(GPR) less than that given eqn. (11) a revision in design is
necessary.

H. Design procedure
Maximum attainable step and touch voltages are Values of maximum attainable touch voltages are
given by: calculated. If the GPR of the preliminary design is
Formula for c-alculation of mesh and step voltage are below the tolerable touch voltage, no further analysis
is necessary. Only additional conductor required to
provide access to equipment grounds is necessary.
If the computed mesh voltage is below the tolerable
touch voltage, the design may be complete. If the
computed mesh voltage is greater than the tolerable
touch voltage, the preliminary design should be
revised. If both the computed touch and step voltages
are below the tolerable voltages, the design needs only
the refinements required to provide access to
Where equipment grounds. If not, the preliminary design
ρ = soil resistivity, ohms-m must be revised.
Em = mesh voltage at the center of corner mesh
Es = step voltage between point Further for the safe design we need to compare the
Km = spacing factor for mesh voltage length of the electrode in the preliminary design to the
Ks = spacing factor of step voltage length of the electrode required to keep mesh voltage
Ki = correct factor for grid geometry within safe limits

If either the step or touch tolerable limits are


exceeded, revision of the grid design is required.
These revisions may include smaller conductor
spacing, additional ground rods, and use of closer
spacing of conductor. In case the length given by eqn.
(11) is too small to allow for connections to all
Where
equipments, more conductor may be required even
230
International Journal of Advanced Computer Research (ISSN (print): 2249-7277 ISSN (online): 2277-7970)
Volume-2 Number-4 Issue-6 December-2012

though it is not necessary for safety ,etc as discussed


in reference [1]. Input Network topology
ρ,A
If the length of the conductor in the preliminary
design is less than the length required to keep mesh Compute of Network Conductor
3Io , tc , d
voltage within safe limits. , then the design needs to
be revised by entering more number of electrodes or
Compute of Touch and Step Voltage
by decreasing spacing between the conductors, Etouch , Estep
otherwise the design is accurate. Further, if the
Ground Potential Rise (R*Ig) is less than the Initial design
tolerable value of touch potential then the design of D, n, L, h
the electrical grid is considered to be safe otherwise
we need to guard personnel and other communication Grid Resistance
Modify design
equipment against transferred potential. Rg, Lc, Lr
D,n, Lc,h

Grid current
Checking of step Potential:- IG, tf
The tolerable step potential and actual step potential
can be calculated from eqn (1) and eqn (8). If actual YES
step potential is more than tolerable, a revision in IG.Rg <Etouch
design is necessary. The final step in design includes
provision of closer meshes in the area frequently
visited by operating personnel, additional ground
rods for surge arrester leads, etc., and provision of Compute of Real Network voltages
Em, Es, Km, Ks, Ki, Kii, Kh
risers for connection to equipments.
NO
Impulse behaviour of earthing system:
The degree of protection provided by an earthing Em< ETouch
system under lightning discharge conditions depends
on its impulse impedance (i.e.,impedance under
NO
impulse conditions) and not the power frequency
resistance. The impulse impedance is different from Em < EStep
the power frequency resistance due to effect of 1 st
soil ionization 2nd electrode inductance.
Investigate of Design and its Details
When the magnitude of impulse current is high, the
Studies
soil in the vicinity of electrode may break-down
causing a decrease in resistance. When the length of Fig 1: Design procedure
electrode is large, its inductance may cause only a
part of the earthing system to be effective in Table I
dissipating current and, thus result in an increase in
impedance. Constant values for design calculations
Quantity Symbol Value
The relative contributions of these two factors depend
Ambient temperature Ta 40
on the type of earthing system. The effect of soil
Maximum allowable
ionization is very predominant in driven rods so that Tm 620
temperature
the impulse resistance of a driven rod is always less Fault duration time ts 1s
than its power frequency resistance. Thermal coefficient of
αr 0.0042
resistivity
The whole procedure can be shown by this flowchart: Resistivity of conductors ρr 15
Resistivity of substation soil ρ 220
Resistivity of surface
ρs 3300
material
Thermal capacity factor TCAP 3.7490
Depth of burial conductor h 0.6m

231
International Journal of Advanced Computer Research (ISSN (print): 2249-7277 ISSN (online): 2277-7970)
Volume-2 Number-4 Issue-6 December-2012

Constant values for design calculations


Quantity Symbol Value
Diameter of grid conductor d 25mm
Length of one earth rod Lr 3m

Table II

Output results for grid construction design


Quantity Symbol Value
Earth conductor size Ac 376.2573
Maximum grid current IG 15750
Ground resistance Rg 0.9646
Ground potential rise GPR 1512
Spacing factor for mesh
Km 0.2244
voltages
Spacing factor for step
Ks 0.4338
voltages Fig. 3: Grid Potential Rise with Different Values of
Touch voltage criteria Etouch 689.97
Resistivity of Soil
Step voltage criteria Estep 2267.72
Maximum attainable step
voltage
Es 1453.93 5. Significance and Touch Voltage
Maximum attainable mesh
Em 581.61 The step and touch voltages are dangerous for human
voltage
body. Human body may get electric shocks from step
4. Result and touch voltages. From the safety point of view it is
necessary to calculate step and touch voltage. When
These results are obtained by a MATLAB program. high voltage substations are designed step and touch
voltages should be calculated and must be in specified
standard. The expected shock current caused by touch
voltage can be effectively limited by applying
inexpensive insulating layers on the earth’s surface
.The limits of step and touch potentials varies in
different seasons because the resistivity of the soil
layer is affected by different seasons .The step and
touch voltage calculations are very significant while
designing substation.

6. Conclusion
This paper has a focus on designing of an AC
substation. The results for earthling system design are
obtained by MATLAB program for earthing
conductor and vertical earth electrode mild steel is
used.

Acknowledgement
The author wish to thank Er. O. P. Rahi for his
Fig. 2: Mesh Voltage with Different Values of guidance and moral support provided during this
Spacing between Conductors. research effort and Dr. M.G.Sharma for helping with
substation data.

232
International Journal of Advanced Computer Research (ISSN (print): 2249-7277 ISSN (online): 2277-7970)
Volume-2 Number-4 Issue-6 December-2012

References [16] F. P. Dawalibi and D. Mukhedkar, ―Optimum


design of substation grounding in two-layer earth
structure—Part I, Analytical study,‖ IEEE Trans.
[1] N.M. Tabatabaei, S.R. Mortezaeei; ―Design of on PAS, vol. 94, no. 2, pp. 252–261, Mar.–Apr.
Grounding System in 1975.
Substation by ETAP Intelligent Softwere‖,IJTPE [17] Xun Long; Ming Dung; Wilsun Xu ; Yun Weili,
Journal, March 2010, Page(s):45-49. ―Omline Monitoring of Substation Grounding
[2] Chae-Kyun Jung; Jong-kee choi; Ji-won Kang, Grid Conditions Using Touch and Step Voltage
―A study on effect of grounding system on Sensors‖, IEEE Journals, 2012, Page(s):761-769.
transient voltage in 154kV Substation‖, IEEE [18] Hernandez Martinez.G.; Venegas Rehollar, V.,
Conference Publications, 2009, Page(s): 1-6. ―Design and Simulation of a grounding grid for
[3] Ladanyi, J. ―Survey of the equivalent Substation GIS Substation‖ IEEE Journals, 2008, Page(s):
earth current and earth impedance for transformer 137-143.
Station‖, IEEE Conference Publications, 2011, [19] Dwarka Prasad, H.C. Sharma; ―Significance of
Page(s): 1-5. Step and Touch voltages‖, (IJSCE) Volume-1,
[4] Lee, C.H; Lin, S. D., ―Safety assesment of AC Issue-5, November 2011.
earthing system in a DC traction-supply
Substation, IEEE Journals, 2005, Page(s): 885-
893. Om Prakash Rahi was born in Kullu
(H.P.), India. He received the B.Tech.
[5] IEEE Std. 80-2000, ―IEEE Guide for Safety in
AC Substation Grounding‖, IEEE: Institute of degree from REC Hamirpur (HP),
Electrical and Electronic Engineers, Inc., New India, in 1992, and the M.E. degree in
York, 2000, Page(s) 1- 192. Electrical Power Systems from Punjab
[6] F. Gatta, S. Lauria, G. Parise, ― Common Engineering College, Chandigarh, in
grounding system in urban areas‖ (in italian), 1997. He joined Government
Conference on ―Safety in complex system‖-Bari Polytechnic, Sundernagar (HP) as
(Italy) 16-17 October 2003. Lecturer in 1997. Since 2000, he has been working as
[7] K. M. Bhatia and B. K. Jain, ―Standardization in Lecturer in the Electrical Engineering Department,
the Field of Electrical Safety‖. National Institute of Technology, Hamirpur, H.P., and
[8] IEEE Std. 142-2007, ―IEEE Recommended India. He has published a number of research papers. His
Practice for Grounding of Industrial and research interests are in the area of Condition Monitoring
Commercial Power System‖, IEEE: Institute of of Power Transformers, Deregulation of Power and Hydro
Electrical and Electronic Engineers, Inc., New
York, 2007. Page(s): 1-215. Power Development.
[9] Brian Allport, ―Practical considerations Abhas Kumar Singh was born in
(substation earthing)‖, VA TECH Reyrolle Ambikapur (Surguja) C.G., India. He
Transmission. received the 3 year Diploma in
[10] H.B. Dwight, "Calculations of Resistances to Electrical Engg. from Govt. Polytechnic
Ground", AIEE Transactions, December 1936, College Ambikapur India, in 2007 and
pp.1319-1328. the B.Tech. degree in Electrical and
[11] J. Nohman and S. Skuletich, "Irregularity Electronics Engineering from Shri
Correction Factors for Mesh and Step Voltages of Shankaracharya College of Engg. & Tech. Bhilai, India, in
Grounding Grids", IEEE Transactions on Power 2010.He is currently pursuing the M.Tech. degree in Power
Apparatus and Systems, vol. PAS-99, No. 1, System from National Institute of Technology, Hamirpur.
1980,pp 174-180.
[12] Thapar, B., Gerez, V., Balakrishnan, A., and Shashi Kant Gupta was born in Obra
Blank, D., Simplified equations for mesh and (Uttar Pradesh), India. He received the
step voltages in an AC substation, IEEE Trans. B.Tech. degree in Electrical and
Power Delivery, 6, 601–607, 1991. Electronics Engineering from
[13] R. J. Heppe, ―Computation of potential at surface S.R.M.S.C.E.T. Bareilly (UP), India, in
above an energized grid or other electrode, 2010. He is currently pursuing the
allowing for nonuniform current distribution,‖ M.Tech. degree in Power System from
IEEE Trans. on PAS, vol. 98, no. 6, pp. 1978–
1989, Nov.–Dec. 1979. National Institute of Technology, Hamirpur.
[14] Marlar Thein oo, Ei Ei Cho,Design of earthing Shilpa goyal was born in Chandigarh.
system for new substation project , Myanmar. She received the B.Tech. degree in
[15] S. J. Schwartz, "Analytical Expression for Electrical and Electronics Engineering
Resistance of Grounding Systems", AIEE from NIT Hamirpur in 2010. She is
Transactions, vol. 73, Part 111-B, 1954, pp. currently working in Infosys.
1011-1016.

233

You might also like