Alarms In NOKIA FLEXI BTS

BY : Preetam Kumar Jangid

1.) 7401 Alarm


Syntex Mains Failure
Type N/C
Severity Major
Colour Green & Green/White
Pin 7, 25
Root
PIU DDF BTS

Root cause Alarm occurs when there is no AC power supply on site


Cause 1. AC gets failure due to regular AC cut.
2. AC gets failure due to any s/c.
3. AC gets failure due to any o/c.
Verification  To check the alarm Switch off the mains MCB from
PIU.
 To remove alarm turn on the mains mcb.

2.) 7402 Alarm


Syntex Rectifier Fail
Type N/O
Severity Minor
Colour Blue & Blue /White
Pin 8, 26
Root
Alarm panel
Of P.P. DDF BTS
Root cause Alarm occurs when any one of the SMPS gets failure.
Cause 1. Any SMPS gets failure.
2. Due to failure of MCB.
3. Due to any s/c.
Verification  To check the alarm firstly remove the rectifier from
the SMPS or switch off the MCB of rectifier from
SMPS.
 To remove alarm switch on the.MCB of the
rectifier moduleor insert the new rectifier module.

3.) 7403 Alarm


Syntex Low Battery Voltage
Type N/O
Severity Criticle
Colour Violet & Violet /White
Pin 9, 27
Root
Alarm panel
Of P.P. DDF BTS

Root cause Alarm occurs when Battery voltage reaches 46V/47V.


Cause 1. When AC gets failure and D.G. is not working & site
on battery from last 3-4 hrs.
2. When Battery is not fully charged and load on
battery.
Verification  To check the alarm set the o/p load vtg of battery
less then 48V & switch off the MCB & D.G..
 To remove alarm switch on the.MCB (mains) or
switch on the D.G. if AC is not available.

4.) 7404 Alarm


Syntex Site On Battery
Type N/O
Severity Major
Colour Gray & Gray /White
Pin 10, 28
Root
Alarm panel
Of P.P. DDF BTS

Root cause Alarm occurs when all SMPS & Rectifiers gets failure.
Cause 1. When AC gets failure and D.G. does not start.
2. AC gets fail DG is off.
3. DG is not working properly.
4. AC gets failure & DG is not available at site.
5. All SMPS & rectifires gets failure.
Verification  To check the alarm switch off the mains MCB from
PIU & switch off DG also.
 To remove alarm switch on the mains MCB or DG
(if mains is not available).

5.) 7405 Alarm


Syntex Site On DG
Type N/O
Severity Minor
Colour Pink & Pink /White
Pin 11, 29
Root
PIU DDF BTS

Root cause Alarm occurs when load of site on DG.


Cause 1. When AC gets failure due to cutting time.
2. AC gets fail due to s/c.
3. MCB gets failure.
Verification  To check the alarm switch off the mains MCB from
PIU & switch on the DG (if it is not in auto mode).
 To remove alarm switch on the mains MCB (if
mains is available).

6.) 7406 Alarm


Syntex DG LLOP
Type N/O
Severity Criticle
Colour Light Green & Black /Green
Pin 12, 30
Root
LLOP Sensor PIU DDF BTS

Root cause Alarm occurs when lube oil pressure gets below then
specified level.
Cause 1. Due to leakage of lubricant.
2. Due to overflow of lubricant.
3. Due to no service on time.
4. Due to no oil change on the time.
Verification  To check the alarm switch off the mains MCB from
PIU & switch off the DG also.
 To remove alarm maintain the lubricant oil
pressure till specified level.

7.) 7407 Alarm


Syntex Low Fuel Level
Type N/O
Severity Minor
Colour Light Blue & Black /Blue
Pin 13, 31
Root
Fuel Sensor PIU DDF BTS

Root cause Alarm occurs when fuel level goes below then 40% of the
capacity.
Cause 1. When site on DG from long time.
2. When fuel tank is not fully filled.
3. Tank have leakage.
Verification  To check the alarm see if the desired fuel level of DG
is set on 40% or not.
 To remove alarm fill the tank of DG.

8.) 7408 Alarm


Syntex DG Fails To Start
Type N/O
Severity Major
Colour White & Black /White
Pin 13, 31
Root
PIU DDF BTS

Root cause Alarm occurs when PIU is not able to start DG in 3


attempts.
Cause 1. Due to problem in self.
2. Self battery is not charge.
3. No fuel in DG.
4. No connection b/w PIU & Self.
Verification  To check the alarm switch off the mains mcb from
PIU and check dg set is not in auto mode or remove
the connection b/w PIU and Self.
 To remove alarm start DG in manual mode.
9.) 7409 Alarm
Syntex AC Failure
Type N/O
Severity Major
Colour Light Gray & Black /light gray
Pin 15, 33
Root
µC DDF BTS

Root cause Alarm occurs when both AC gets failure.


Cause 1. Due to problem in µC.
2. Site on battery.
3. Level of gas in AC goes below then the
specified level.
4. Switching problem.
Verification  To check the alarm switch off the AC’s.
 To remove alarm switch on/repair/replace AC’s.

10.) 7410 Alarm


Syntex Door Open
Type N/C
Severity Minor/Major/Criticle (Accd. to condition)
Colour Red/ Black & Red/Blue
Pin 16, 34
Root
Door Sensor PIU DDF BTS

Root cause Alarm occurs when Door is open.


Cause 1. Unauthorisd person is in the shelter.
2. Work on progress inside the shelter.
3. Someone (may be technician, engineer or guard)
forget to close the door.
4. Sealing of door is not proper.
5. Lock of door is not correct.
Verification  To check the alarm open the door.
 To remove alarm close and seal proper the door.

11.) 7411 Alarm


Syntex High Room Temp.
Type N/O
Severity Major
Colour Orange/Red & orange/Light gray
Pin 16, 34
Root
Temp.Sensor µc of AC DDF BTS

Root cause Alarm occurs when Temp reaches 35° c.


Cause 1. AC is not working.
2. Door of shelter is open.
3. Site on battery.
Verification  To check the alarm rub thermister in b/w hands .
 To remove alarm switch on the AC & set AC temp
on desired value.

12.) 7412 Alarm


Syntex Fire & Smoke.
Type N/O
Severity Criticle
Colour Orange/Black & Orange/Green
Pin 18, 36
Root
F& S sensor PIU DDF BTS
Root cause Alarm occurs when Fire & Smoke at site.
Cause 1. Fire & Smoke at site.
2. Due to any inflammable object at site.
Verification  To check the alarm create a small fire by paper or
jute.
 To remove alarm Reset smoke & fire sensor and
clean the smoke from the sensor.