ELECTRICAL CIRCU

CABLE ROUTE LOAD


Supply
SN. Connected Power Demand Load Demand
FROM TO Voltage
Load (W) Factor (VA) Load (A)

1 ALP-1 ALP-1/1 1,500 0.85 1,765 2.55 400

2 ALP-1 ALP-1/2 2,400 0.85 2,824 4.08 400

3 ALP-1 ALP-1/3 2,400 0.85 2,824 4.08 400

4 ALP-1 ALP-1/4 2,400 0.85 2,824 4.08 400

5 ALP-1 ALP-1/5 2,400 0.85 2,824 12.28 230

6 ALP-1 ALP-1/6 2,400 0.9 2,667 3.85 400

7 ALP-1 ALP-1/7 2,400 0.9 2,667 3.85 400

8 ALP-1 ALP-1/8 2,400 0.9 2,667 3.85 400

9 ALP-1 ALP-1/9 2,400 0.9 2,667 11.59 230

40
ELECTRICAL CIRCUITING VOLTAGE DROP CLACULATIONS
CABLES
No of CKT No of
Phases Breaker Luminaires Cable size Type R X Grounding
(Sq.mm) (Sq.mm)

3 25 6 10 Cu.XLPE.Mult 2.33 0.1111 10

3 25 24 10 Cu.XLPE.Mult 2.33 0.1111 10

3 25 24 10 Cu.XLPE.Mult 2.33 0.1111 10

3 25 24 10 Cu.XLPE.Mult 2.33 0.1111 10

1 25 24 10 Cu.XLPE.Single 2.33 0.137 10

3 25 24 10 Cu.XLPE.Mult 2.33 0.1111 10

3 25 24 10 Cu.XLPE.Mult 2.33 0.1111 10

3 25 24 10 Cu.XLPE.Mult 2.33 0.1111 10

1 25 24 10 Cu.XLPE.Single 2.33 0.137 10


Voltage
Length to 1st Total Length drop (%)
Installation Luminaire (m) (m)

Direct burried 50 300 0.51%

Direct burried 50 1,200 2.43%

Direct burried 100 1,250 2.61%

Direct burried 20 1,170 2.32%

Direct burried 50 1,200 26.29%

Direct burried 50 1,200 2.41%

Direct burried 100 1,250 2.59%

Direct burried 20 1,170 2.31%

Direct burried 50 1,200 26.09%