H V A C S y s t e m s M o n i t o r i n g

4-Wire Low-Flow
Duct Smoke Detector
Model
DH100ACDCLP 4-Wire Photoelectric
Duct Smoke Detector
with Low-Flow
Technology

Product Overview
Air velocity rating from The System Sensor Innovair™ DH100ACDCLP is a 4-wire photoelectric air
100 to 4000 feet per minute duct smoke detector capable of sensing smoke in air velocities from 100 to
(0.5 to 20.32 m/sec.) 4,000 feet per minute (0.5 to 20.32 m/sec). This Innovair features Low-Flow
Patented interconnect ability for multi-fan technology that enables duct smoke detection throughout a broad range of
shutdown (up to ten air handlers) airflow environments. Many difficult to solve HVAC applications occur in low
Patented telescopic sampling tube airflow duct applications where reliable smoke detection is critical. Innovair
Patented cover tamper trouble signal with Low-Flow technology can detect smoke at air speed velocities of 100 feet
per minute or greater, while continuing the same reliable performance to 4,000
24 VAC/DC or 120/240 VAC operation
feet per minute.
High-Low voltage barrier
The two available form C relay contacts provide reliable performance for
Equipped with two DPDT Form C relay
the management of fans, blowers and air conditioning systems. These HVAC
contacts
devices can be configured to prevent the spread of toxic smoke and fire gasses
Built-in reset button through a protected area
Outside mounting tabs
The Innovair family is designed for simplified installation and easy mainte-
Easy and quick mounting to round nance. The modular construction allows for easy cleaning and uncomplicated
or rectangular ducts from 1′–12′ field replacement of the UL recognized power and sensor boards. The patented
(0.3–3.7 meters) wide
cover missing feature insures the cover is securely tightened following routine
Easy to clean cleaning and maintenance. The patented interconnect feature allows
UL recognized field-replaceable power multiple Innovairs to communicate with each other. In the event smoke is
and sensor boards detected, the Innovair will signal the remaining interconnected detectors to
Remote test station option initiate their relays for smoke control.
Remote sounder option WARNING: Duct smoke detectors have specific limitations.
Transparent cover for convenient DUCT SMOKE DETECTORS ARE:
visual inspection NOT a substitute for an open area smoke detector,
UL 268A listed NOT a substitute for early warning detection, and
3-year warranty NOT a replacement for a building’s regular fire
detection system.
Refer to NFPA 72 and 90A for additional information about the proper
application of duct smoke detectors.
Architectural/Engineering Specifications
The air duct smoke detector shall be a System Sensor Model DH100ACDCLP Series Duct Smoke Detector. The detector hous-
ing shall be UL listed per UL 268A specifically for use in air handling systems. The detector shall operate at air velocities of
100 feet per minute to 4000 feet per minute (0.5 to 20.32 m/sec.). The unit shall be capable of controlling up to ten (10)
air handling systems when interconnected with other detectors. The detector shall be capable of providing a trouble signal
in the event that the front cover is removed. It shall be capable of local testing via magnetic switch or remote testing using
the SSK451 Multi-Signaling Accessor y or the RTS451KEY Remote Test Station. The unit shall be reset by local reset button
or remote test station. The duct smoke detector housing shall incorporate an air tight smoke chamber in compliance with UL
268A, Standard for Smoke Detectors for Duct Applications. The housing shall be capable of mounting to either rectangular or
round ducts without adapter brackets. An integral filter system shall be included to reduce dust and residue effects on detec-
tor and housing, thereby reducing maintenance and ser vicing. Sampling tubes shall either be telescoping or be easily installed
by passing through the duct housing after the housing is mounted to the duct. The unit shall provide a spacial separation of
no less than 1⁄4″ (6.4 mm) and/or a physical barrier between the high and low voltage terminals. The enclosure shall meet all
applicable NEC and NFPA standards regarding electrical junction boxes. Terminal connections shall be of the strip and clamp
method suitable for 12–18 AWG wiring.

Wiring Guide
System wiring diagram for 4-wire duct smoke detectors

AVAILABLE POWER INPUTS AVAILABLE POWER INPUTS CONNECT POWER SOURCE


POWER INPUTS ACCEPT TO APPROPRIATE TERMINALS
24 VDC, 24 VAC 50-60 HZ, 9 10 A B C 9 10 A B C
OF EACH DETECTOR. SEE
120 VAC 50-60 HZ, OR SPECIFICATIONS FOR
220/240 VAC 50-60 HZ. ADDITIONAL POWER SUPPLY
CONNECT POWER SOURCE INFORMATION.
TO APPROPRIATE TERMINALS 120 120
24V 24V VAC
OF EACH DETECTOR. VAC
220/240 220/240
VAC VAC

ALARM AUXILIARY CONTACTS ALARM AUXILIARY CONTACTS


FOR FAN SHUTDOWN, ETC. FOR FAN SHUTDOWN, ETC.
AUX. CONTACT RATINGS 16 6 17 7 18 8 16 6 17 7 18 8
10A @ 30 VDC RESISTIVE
10A @ 250 VAC FOR WIRING OF AUXILIARY
100mA MINIMUM @ 5 VDC N.C. C. N.O. N.O. C. N.C. N.C. C. N.O. N.O. C. N.C. DEVICES, REFER TO
NOT INTENDED FOR MANUFACTURER'S
CONNECTION TO CONTROL INSTALLATION INSTRUCTIONS
PANELS. OR CONTACT MANUFACTURER.

ALARM AUXILIARY CONTACTS SHOWN IN ALARM AUXILIARY CONTACTS SHOWN IN NOTE: THE SUPERVISORY RELAY NOW
STANDBY. CONTACTS TRANSFER DURING STANDBY. CONTACTS TRANSFER DURING PROVIDES A "FORM C" CONTACT FOR
ALARM AS INDICATED BY THE ARROWS. ALARM AS INDICATED BY THE ARROWS. CUSTOMIZED APPLICATIONS.
FOR STANDARD APPLICATIONS, ONLY
THE "NO" CONTACT IS USED
TROUBLE CONTACT RATING SUPERVISORY TROUBLE CONTACTS SUPERVISORY TROUBLE CONTACTS
2.0 A @ 30 VDC resistive
2.0 A @ 125 VAC resistive 14 3 14 3

TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY. TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY.
CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS
REMOVED OR WHEN TAMPER FEATURE TIMES OUT. OPEN REMOVED OR WHEN TAMPER FEATURE TIMES OUT. OPEN
CONTACTS SIGNAL TROUBLE CONDITION TO PANEL. CONTACTS SIGNAL TROUBLE CONDITION TO PANEL.

+
5 5

ALARM ALARM CONTACTS SHOWN ALARM CONTACTS SHOWN


INITIATION INITIATION OPEN IN STANDBY. INITIATION OPEN IN STANDBY.
LOOP CONTACTS CONTACTS CLOSE CONTACTS CONTACTS CLOSE
IN ALARM. IN ALARM.
4 4


EOL RESISTOR
UL LISTED 4-WIRE FIRST DETECTOR IN THE LOOP LAST DETECTOR IN THE LOOP SPECIFIED BY
CONTROL PANEL DH100ACDCLP DH100ACDCLP PANEL MANUFACTURER

Specifications
Size Storage Temperature Range
143⁄8″ (37 cm.) Length –22° to +158°F (–30° to +70°C)
51⁄2″ (14 cm.) Width
23⁄4″ (7 cm.) Depth Operating Humidity Range
10% to 93% relative humidity non-condensing
Shipping Weight
33⁄4 lbs. (1.7 kg.) Air Duct Velocity
100 to 4000 ft./min. (0.5 to 20.32 m/sec.)
Operating Temperature Range
32° to 131°F (0° to 55°C)
Electrical Ratings – DH100ACDCLP (Includes Detector)
Power supply voltage: 20-29 VDC 24 VAC 50-60-Hz 120 VAC 50-60 Hz 220/240 VAC 50-60 Hz
Input capacitance: 270 µF max. 270 µF max. N/A N/A
Reset voltage: 3.0 VDC min. 2.0 VAC min. 10 VAC min. 20 VAC min.
Reset time (with RTS451): .03 to 0.3 sec. .03 to 0.3 sec. .03 to 0.3 sec. .03 to 0.3 sec.
Reset time (by power down): 0.6 sec. max. 0.6 sec. max. 0.6 sec. max. 0.6 sec. max.
Power up time: 34 sec. max. 34 sec. max. 34 sec. max. 34 sec. max.
Alarm response time: 2 to 17 sec. 2 to 17 sec. 2 to 17 sec. 2 to 17 sec.
Sensitivity Test: See detector label See detector label See detector label See detector label

Power Supply Voltage 20 - 29 VDC 24 VAC 50 - 60 Hz 120 VAC 50 - 60 Hz 220/240 VAC 50 - 60 Hz

CURRENT REQUIREMENTS (USING NO ACCESSORIES)


Max. standby current 15 mA 35 mA RMS 25 mA RMS* 15 mA RMS*
Max. alarm current 70 mA 125 mA RMS 35 mA RMS* 25 mA RMS*

CONTACT RATINGS
Alarm initiation contacts (SPST) 2.0A @ 30 VAC/DC (0.6 power factor) ACCESSORY CURRENT LOADS AT 24 VDC
DEVICE STANDBY TROUBLE ALARM
Alarm auxiliary contacts (DPDT) 10A @ 30 VDC
APA451 12.5mA Max. n/a 30mA Max.
10A @ 250 VAC
Note: Alarm auxiliary contacts must switch 100mA minimum at 5VDC. Alarm auxiliary contacts shall not be PA400 0mA n/a 15mA Max.
connected to inititaing circuits of control panels. Use the alarm initiation contact for this purpose. RA400Z 0mA n/a 10mA Max.

Trouble contacts (SPDT) 2.0A @ 30 VDC (resistive) RTS451/RTS451KEY 12mA* n/a 7.5mA Max.
2.0A @ 125 VAC (resistive) SSK451 5mA Max. 9mA Max. 30mA Max.
*NOTE: When a unit is powered at the 120VAC or 220/240VAC input, any
combination of accessories may be used such that the given accessory loads are:
60 mA or less in the standby state; 110 mA or less in the alarm state.
Wiring diagram for DH100ACDCLP to APA451:
DH100ACDCLP APA451 Important Interconnect Notes
Alarm Signal 15 2 Alarm
(Red LED) • When using the interconnect feature, all interconnected units
Aux. Power + 19
must be powered with the same, independent supply.
Sup. N. O. 14 • Polarity must be maintained throughout the interconnect wiring.
Connect terminal 12 on unit 1 to terminal 12 on unit 2 and so
Sup. COM 3 3 Power
(Green LED) on. Similarly, connect terminal 1 on unit 1 to terminal 1 on unit
Aux. Power – 20 1 Common 2 and so on.
• Up to 10 units may be interconnected.
NOTE: Wiring diagram shown is for DH100ACDCLP 4-wire duct
smoke detector system equipped without a control panel.
NOTE: A trouble condition is indicated when the green LED
is not illuminated. Wiring diagram for DH100ACDCLP to SSK451:
FIELD INSTALLED
JUMPER FOR
Wiring diagram for the DH100ACDCLP to RTS451/ TEMPORAL PATTERN
RTS451KEY: SSK451 DH100ACDCLP
DH100ACDCLP RTS451/RTS451KEY
DH100ACDCLP RTS451/RTS451KEY
COMMON 3
Alarm Signal 15 1 (Red LED) Alarm
Alarm Signal 15 1 (Red LED) Alarm TEMPORAL SELECT 2
Aux. Power + 19 6 (Green LED) ** ALARM SIGNAL 1 15 ALARM SIGNAL
Aux. Power + 19
Sup. N. O. 14 *only without a
Power
For RTS451KEY SUPERVISORY SIGNAL 4 3
14
NO SUPERVISORY
CONTACT
Sup. N. O. 14 control panel.
Sup. COM RESET 7 2 RESET
3
Sup. COM 3 6 (Green LED) TEST 8 11 TEST
Aux. Power – 20 2 Power POWER (–) 6 20 AUX. POWER (–)
POWER (+) 5 19 AUX. POWER (+)
Aux. Power – 20 2
Reset 2 3

Reset
Test 211 Field
3
4 Installed
Jumper FIELD INSTALLED
Interconnect – 1 4 JUMPER
5
Test 11 5 Wiring diagrams for optional accessories:
Interconnect +
Unit 1 12
*NOTE: For RTS451KEY only
without a Control Panel. ALARM SIGNAL (+)
15 (+)
ALARM SIGNAL (+)
15 (+)

DH100ACDCLP RTS451 does not have a terminal 6.


UNIT 2 NOTE: Wiring diagram shown is for AUX POWER (–) AUX POWER (–) RED
DH100ACDCLP 4-wire duct 20 (–) 20 (–)
Interconnect – 1
smoke detector system equipped
without a control panel.
Interconnect + 12 NOTE: A trouble condition is indicated DUCT DETECTOR PA400 (OPTIONAL) DUCT DETECTOR RA400Z (OPTIONAL)
DH100ACDCLP AUDIBLE ALERT DH100ACDCLP REMOTE (LED)
when the green LED is not ANNUNCIATOR
illuminated.
Ordering Information
Part No. Description
DH100ACDCLP 4-wire photoelectric duct detector with low-flow technology
A5190 Replacement 4-wire photoelectric detector board
A5064 Replacement 4-wire power board

Accessories
ST-1.5 Metal sampling tube duct widths 1′–2′ (0.3–0.6 m) MOD400R Sensitivity test module
ST-3 Metal sampling tube duct widths 2′–4′ (0.6–1.2 m) RA400Z Remote annunciator alarm LED
ST-5 Metal sampling tube duct widths 4′–8′ (1.2–2.4 m) F36-09-11 Replacement air filters (two per package)
ST-10 Metal sampling tube duct widths 8′–12′ (2.4–3.7 m) M02-04-00 Test magnet
T80-71-00 Replacement telescoping sampling tube P48-21-00 End cap for metal sampling tubes
P48-55-00 Replacement end cap for T80-71-00 S08-39-01 Photo replacement screen
SSK451 Multi-Signaling accessor y PA400W Mini-Aler t sounder
RTS451KEY Remote test station with key lock PS24LOW Mini-Aler t add-on strobe
RTS451 Remote test station PS12/24SLENSW Wall-mount “SMOKE” lens
APA451 Remote annunciator with piezo alarm PS12/24SLENSC Ceiling-mount “SMOKE” lens

Accessories
System Sensor provides system flexibility with a variety of accessories, including two remote test stations, and several different
means of visible and audible system annunciation. As with our duct detectors, all duct smoke detector accessories are UL listed.

ALARM POWER
ALARM
F ALARM

I
R
ON
RESET TEST

E RESET

APA451 RTS451KEY PA400W RTS451 RA400Z


Piezo Annunciator Remote Test Station Mini-Aler t Sounder Remote Test Station Remote Annunciator
(UL S4011) with Key (UL S2522) (UL S3593) (UL S2522) (UL S2522)
shown with PS24LOW add-on
strobe (PS12/24SLENSW
smoke lens option available)

S
M
O SSK451
K Multi-Signaling Accessor y
SSK451
Multi-Signaling E (UL 268A)
shown with PS24LOW add-on
Accessor y strobe (PS12/24SLENSW
(UL 268A) smoke lens option available)

System Sensor Sales and Service


System Sensor Headquarters System Sensor Canada System Sensor in China System Sensor – Far East System Sensor – India
3825 Ohio Avenue Ph: 905.812.0767 Ph: 86.29.8832.0119 Ph: 85.22.191.9003 Ph: 91.124.637.1770 x.2700
St. Charles, IL 60174 Fx: 905.812.0771 Fx: 86.29.8832.5110 Fx: 85.22.736.6580 Fx: 91.124.637.3118
Ph: 800/SENSOR2 System Sensor Europe System Sensor in Singapore System Sensor – Australia System Sensor – Russia
Fx: 630/377-6495 Ph: 44.1403.276500 Ph: 65.6273.2230 Ph: 613.54.281.142 Ph: 70.95.937.7982
www.systemsensor.com Fx: 44.1403.276501 Fx: 65.6273.2610 Fx: 613.54.281.172 Fx: 70.95.937.7983

­© 2004 System Sensor. The company reserves the right to change product specifications without notice. A05-1044-006•10/05•#1433