Commissioning Check List E

Restricted
ANSI 59N/ 64G/ 67G
CL-E131 Stator Earth Fault
Protection 90%
Primary Injection Tests
Panama Colon PP BB001062
Power Plant Plant Code

System: Protection/ Synchronization and Metering (Generator)

Component: CHA10-U08-F01 – generator protection

Page: 1 of 2 Appendices:

No. Activity (Items not applicable to be marked N/A) Remarks Confirmed

1. Technical data: See device coversheet

Secondary injection checklist CL-E231 available 

2. Primary tests

2.1 Test with L1 grounded at generator bus duct.


- 1 phase short circuit to ground on the Generator terminal.
- Block diff protection and unbalanced load protection.
- Block the Generator Circuit Breaker for ON command.
- The Generator is in service with manual excitation.
- Increase the excitation until one of the two ground protection
trips the GCB and turbine.
- Block the stator ground protection that tripped and restart the
turbine. Increase the excitation until the other stator ground
protection trips the GCB and turbine.
- Remove 1-phase short circuit.

UL1-L2 [V]
UE [V]

- Unblock Relay

2.3 Measuring of displacement voltage at 100% of generator voltage, without


earth fault.

generator rated voltage


displacement voltage UE [V] UL1-L2 [V]
[%]

100

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization


of its content and communication thereof to others without express authorization are prohibited.
Project Site Execution Offenders will be held liable for payment of damages. All rights created by patent grant or
registration of a utility model or design patent are reserved.
CL-E131 Stator Earth Fault Protection 90%
Primary Injection Tests

Commissioning Checklist E System: Protection/ Synchronization and Metering (Generator)


Component: CHA10-U08-F01 – generator protection

Page: 2 of 2

No. Activity (Items not applicable to be marked N/A) Remarks Confirmed

3. Evaluation

Measured displacement voltages acceptable 

UEset = 11 [V]

4. Remarks:
.......................................................................................................................................................................................... 1

......................................................................................................................................................................................... 2

Department: ........................................................ Name: .......................................................................

Date:. ...................................................................... Signature: .............................................................

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization


of its content and communication thereof to others without express authorization are prohibited.
Project Site Execution Offenders will be held liable for payment of damages. All rights created by patent grant or
registration of a utility model or design patent are reserved.