Professional Documents
Culture Documents
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1
E 907 – 96 (2004)
controls to maintain the constant negative pressure at each test 8.2 Conduct tests when the temperature of the roof surface
pressure increment as required in 8.8. is in the range from 4 to 38°C (40 to 100°F). Temperatures
5.4 Dial Indicator, with a reset face graduated in at least outside this range will produce questionable results. For safety
0.05 mm (0.002 in.) units and having at least a 50 mm (2 in.) considerations, tests shall not be conducted when the wind
range, mounted at the center of a 50 by 50 by 1500 mm (2 by speed at the roof level is over 6.5 m/s (15 mph). When
2 by 59 in.) long aluminum bar or member of equivalent necessary to measure and record wind speed, a portable
stiffness. Feet on each end of the bar provide support and give anemometer shall be used.
a clear distance of 50 mm (2 in.) above the roof surface. This 8.3 Place the bar with attached dial indicator so that the tip
allows measurement of roof surface deflections in the test area of the dial indicator is in contact with the roof membrane near
(see Fig. 3). the center of the test area.
5.4.1 All persons not involved in the test shall be kept far
8.4 Place the assembled chamber over the roof test area so
enough away from the test area to ensure that the dial gage
that the deflection bar with attached dial indicator is centered
indicator is not affected by movement and influence the
within the chamber and is perpendicular to two sides of the
readings.
chamber. The edges of the chamber shall be sealed to the roof
6. Hazards surface. Orient the chamber on the roof so that the edges are
6.1 The manometer shall be designed to serve as a safety parallel with the direction of the structural framing of the
device to prevent negative pressures that will cause the plastic building.
dome to shatter. The design of the manometer or safety features 8.5 Install the pressure measuring device. If a manometer is
of other pressure sensing devices shall not be changed to used, fill it with water to zero calibration level.
increase negative pressures above the design or allowable 8.6 Connect the vacuum equipment to the hole provided for
values of the chamber. it in the chamber. Make sure that the bypass valve on the
6.2 Safety goggles or face shield shall be worn by persons vacuum equipment is open before starting the equipment, or if
operating the equipment or observing its operation as a a rheostat is used, that it is in the OFF position.
precaution against injury caused by a sudden failure of the test 8.7 Continuously observe the deflection and pressure mea-
chamber or roofing system. suring device throughout the period that vacuum is created for
7. Sampling sudden or variable rates of movement.
7.1 Perform testing in selected locations representative of 8.8 Regulate the negative pressure in the chamber to the
the perimeter and interior areas of the roof. specified level. Unless otherwise specified, conduct the test by
7.2 Select the number of tests in accordance with Table 1. raising the negative pressure in the chamber to 720 6 20 Pa (15
lbf/ft2) and holding this pressure for 1 min. Thereafter, raise the
8. Procedure pressure in increments not greater than 360 6 20 Pa (7.5
8.1 Measure and record air temperature with a thermometer, lbf/ft2) until the agreed upon pressure is reached. Hold the
and roof surface temperature with a surface thermometer. pressure at each increment for 1 min. Terminate the test when
2
E 907 – 96 (2004)
failure occurs or at the completion of 1 min at the agreed upon well adhered, the increase in deflection will be gradual and at
specified negative pressure. Roof assembly failure is described a relatively constant rate up to a point at or near failure. When
in Section 9. failure occurs due to lack of adhesive or cohesive resistance of
the roof system, there will be a sudden increase in the upward
9. Interpretation of Results deflection.
9.1 Most roof systems subjected to a negative pressure will 9.2 Failure is taken as uplifting of the roof covering as
exhibit an upward deflection that will increase as the negative indicated by a measured upward deflection of 25 mm (1 in.) or
pressure increases. Poorly adhered systems will exhibit rela- greater at the center unless a particular system exhibits greater
tively large increases in upward deflections with relatively limits of deflection without failure as determined by examina-
small increases in applied pressure. For roof systems that are tion or past test experience, or both. A sudden increase in
3
E 907 – 96 (2004)
FIG. 3 Bar with Attached Dial Indicator Used to Measure Roof Surface Deflections
TABLE 1 Number of Tests per Roof Area 10.2.4 Description of the test procedure giving the negative
Roof Area Number of Tests pressure increments, length of time pressure maintained at each
100–450 m2 or 10–50 squaresA 2 increment, and the maximum applied pressure.
450–1000 m2 or 50–100 squares 4
Over 1000 m2 or 100 squares 4 plus 1 additional test for each
10.2.5 Tabulation of results observed at each pressure in-
additional 1000 m2 (100 squares) or crement including visual observations and deflection. The
portion thereof deflection shall be measured and recorded at the start and end
A
A square is equal to 100 ft2(9.3 m2) of roof area. of each pressure increment.
10.2.6 If failure occurs during the tests, the complete record
shall include: (a) the negative pressure at which failure
deflection indicates a problem that requires further investiga- occurred, (b) observations obtained by thorough examination
tion to determine if adhesion or attachment of roofing system of the failed area including cuts through the membrane if
components is adequate. necessary (cuts in built-up membranes shall be made as shown
NOTE 2—Deflection due to negative pressure will potentially vary at in Fig. 4 to preserve the integrity of the test cut area), (c)
different locations because of varying stiffness of the roof system description of type of failure and its location within the roof
assembly. Stiffness of a roof system assembly including deck is influenced assembly, and (d) other observations of the roof assembly
by location of mechanical fasteners, the thickness of insulation, stiffness conditions that are attributed to the failure. The cut area of
of decking, and by the type, proximity, and rigidity of connections roofing shall be repaired after examination of the failed area.
between the decking and framing system.
10.2.7 Names, signatures, and affiliations of the persons
10. Report observing the tests.
10.1 Refer to Practice E 575 for general use in reporting
structural performance tests of building assemblies.
10.2 Report the following information:
10.2.1 Area, height, and plan view of the roof showing the
location of the test areas.
10.2.2 Complete detailed description of the roof assembly
construction being tested. Include the type of roof deck and
method of attachment, deck support spacing, vapor retarder
and adhesive, if any, types and thicknesses of insulation, if any,
methods of attachment, and the type of adhered roofing
including surfacing.
10.2.3 Dates of tests, air and roof surface temperatures, and
wind speed (if measured). The internal pressure of the building
shall be recorded before starting the uplift tests. FIG. 4 Cuts for Examination of Failed Insulated Bur Sections
4
E 907 – 96 (2004)
11. Precision and Bias 12. Keywords
11.1 When sufficient testing has been completed using this 12.1 bituminous roofing; built-up roofing; field testing;
test method, a precision and accuracy statement will be performance testing; roofing systems; steel deck insulation;
included. wind uplift resistance
ASTM International takes no position respecting the validity of any patent rights asserted in connection with any item mentioned
in this standard. Users of this standard are expressly advised that determination of the validity of any such patent rights, and the risk
of infringement of such rights, are entirely their own responsibility.
This standard is subject to revision at any time by the responsible technical committee and must be reviewed every five years and
if not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional standards
and should be addressed to ASTM International Headquarters. Your comments will receive careful consideration at a meeting of the
responsible technical committee, which you may attend. If you feel that your comments have not received a fair hearing you should
make your views known to the ASTM Committee on Standards, at the address shown below.
This standard is copyrighted by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959,
United States. Individual reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the above
address or at 610-832-9585 (phone), 610-832-9555 (fax), or service@astm.org (e-mail); or through the ASTM website
(www.astm.org).