A Why-Because Analysis
Bernd Sieker
Causalis Limited
May 2007
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 1 / 26
Overview
1 Introduction
2 Sequence of Events
3 The Why-Because-Graph
4 Observations
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 2 / 26
The European Blackout 4 November 2006
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 3 / 26
Sources
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 4 / 26
Sequence of Events
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 5 / 26
Sequence of Events II
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 6 / 26
Sequence of Events III
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 7 / 26
WB-Graph
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 8 / 26
WB-Graph — Blackout
Consumers have to be disconnected in a controlled manner in regions with
under-production
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 9 / 26
WB-Graph — Frequencies
The entire net has to be synchronized to work. Before any
resynchronisation can be done, the split parts have to be brought to
matching frequency.
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 10 / 26
Frequencies — Oscillation, Split, Drift
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 11 / 26
Frequencies — Oscillation, Split, Drift
Just after the split, frequencies quickly drift apart from the nominal 50Hz,
precluding a quick reconnection.
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 12 / 26
WB-Graph — Wind Power
Wind turbines are not centrally controlled
Disconnect automatically when parameters deviate too far
exacerbates underfrequency and underproduction problem
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 13 / 26
Wind Power — Infeed around the split time
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 14 / 26
WB-Graph — Busbar Coupling
E.ON did not perform load flow analyses
Erroneously assumed busbar coupling would reduce load
Coupling did increase load instead!
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 15 / 26
Busbar Coupling — Consequences
Overloaded line Landesbergen Wehrendorf trips
Other lines trip in an unstoppable cascade within seconds of each
other
First 14 lines tripped within 14 seconds
Total 33 lines tripped within 1 min 20s
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 16 / 26
WB-Graph — N Minus One
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 17 / 26
WB-Graph — N Minus One, Take 2
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 18 / 26
WB-Graph — N Minus One, Take 3
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 19 / 26
The N-1 Criterion
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 20 / 26
Checking for N-1 Safety
RWE
◮ has automated system that performs N-1 calculations every 15 minutes
automatically
◮ Personnel can easily trigger additional calculation runs
E.ON
◮ No automated system
◮ Personnel have to initiate calculations manually
◮ Left to Dispatchers’ discretion when to perform calculations
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 21 / 26
Interconnected European Power Grid
Unevenly distributed generation and consumption
High-cross-boundary flows of power
Use of AC requires frequency synchronisation
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 22 / 26
“Main Causes” in Official Reports
Main Causes
◮ Violation of N-1 criterion
◮ Insufficient inter-TSO co-ordination
Bundesnetzagentur and UCTE agree on these findings
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 23 / 26
UCTE recommendations
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 24 / 26
Correspondence to Findings in WB-Graph
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 25 / 26
Thank you very much for your Attention
The HV line Conneforde-Diele, which did not have to be switched off for the AIDA diva
Bundesnetzagentur:
Report on the disturbance in the German and European power system on the 4th of November 2006
Bernd Sieker (Causalis Limited) The Disruption in the European Power Gridon 4 November 2006 May 2007 26 / 26