The document provides a data point summary for a chiller plant manager, listing the total points for various plant components including air cooled chillers, condenser water pumps, chilled water pumps, and chiller diagnostic points. It includes descriptions of the points, quantities, and required field devices and signal types. A total of 246 points are required to monitor and control the chiller plant system.
The document provides a data point summary for a chiller plant manager, listing the total points for various plant components including air cooled chillers, condenser water pumps, chilled water pumps, and chiller diagnostic points. It includes descriptions of the points, quantities, and required field devices and signal types. A total of 246 points are required to monitor and control the chiller plant system.
The document provides a data point summary for a chiller plant manager, listing the total points for various plant components including air cooled chillers, condenser water pumps, chilled water pumps, and chiller diagnostic points. It includes descriptions of the points, quantities, and required field devices and signal types. A total of 246 points are required to monitor and control the chiller plant system.
DATA POINT SUMMARY FOR CHILLER PLANT MANAGER (CPM)
Sr. No Description Qty Total Points
DI DO AI AO SW A Chiller Plant (Air Cooled Chiller) 4
1 Chiller On/Off command 4
2 Chiller Run status 4 3 Chiller Fault/Alarm status 4 4 Chiller Outlet isolation valve Open/Close command 4 5 Chiller Outlet isolation valve Open/Close status 4 6 Common CHW supply header temperature 2 7 Common CHW return header temperature 2 8 Flow transmitter 2 9 BTU Meter (2 Sets) 8 10 Supply/return header Bypass valve cmd 2 2 11 Diff. pressure 4 12 Outside Air Temp/Humidity 2 # Total points for Chiller Plant 12 8 14 2 8
B Primary Constant Flow Pump 4 DI DO AI AO SW
1 Pump Auto/Manual status 4
2 Pump On/Off command 4 3 Pump run status 4 4 Pump trip status 4 5 Supply/ return Diff. pressure 4 # Total points for Condenser Water Pumps 12 4 4 0 0
C Secondary Variable Chilled Water Pumps 3 DI DO AI AO SW
1 Pump Auto/Manual status 3
2 Pump On/Off command 3 3 Pump run status 3 4 Pump trip status 3 5 Supply/ return Diff. pressure 3 6 Pump VFD control 3 7 Pump VFD feedbback 3 8 Pump VFD control 33 # Total points for Chilled Water Pumps 9 3 6 3 33
D Chiller Diagnostic Points (for both Air cooled Chillers) DI DO AI AO SW
1 Leaving chilled liquid - setpoint 4
2 Motor current limit -setpoint 4 3 Leaving chilled liquid - temperature 4 4 Entering chilled liquid - temperature 4 5 Leaving condensor liquid - temperature 4 6 Entering condensor liquid - temperature 4 7 Evaporator pressure 4 8 Condensor pressure 4 9 Oil – low differential pressure 4 10 Motor FLA current 4 11 Discharge pressure 4 12 Operating hours 4 13 Unit safety fault code 4 14 Unit cycling fault code 4 15 Opreation code 4 16 Evaporator – low pressure 4 17 Evaporator – low-pressure – smart freeze 4 18 Evaporator – transducer or leaving liquid probe 4 19 Condenser – high pressure 4 20 Condenser – pressure transducer out of range 4 22 Discharge – low temperature 4 23 Oil – high temperature 4 24 Oil – low differential pressure 4 26 Oil – clogged filter 4 27 Motor controller – loss of current 4 28 Oil – high pressure 4 29 Oil – separator – low level 4 30 Leaving chilled liquid - low temperature 4 31 Motor controller – loss of current 4 32 Sys Oil Temperature 4 33 Sys Oil Pressure 4 34 Sys Oil Filter Pressure 4 35 Slide Valve Position 4 36 Sys Discharge Temp 4 37 SYS.EVAPORATOR SATURATION TEMPERATURE 4 38 SYS.EVAPORATOR SUB TEMPERATURE 4 39 SYS.CONDENSER SATURATION TEMPERATURE 4 40 EVAPORATOR REFRIGERANT TEMPERATURE 4 41 EVAPORATOR SMALL TEMPERATURE DIFFERENCE 4 42 CONDENSER SMALL TEMPERATURE DIFFERENCE 4 43 SYS. START TIMES 4 Total diagnostic points 164
Total 33 15 24 5 205
20% Spare 40 18 29 6 246
Required signal/Field Devices
NO/NC Potential free contact to Chiller Microprocessor
NO/NC Potential free contact from Chiller Microprocessor NO/NC Potential free contact from Chiller Microprocessor NO/NC Relay Command to Valve NO/NC Potential free contact from Valve TE-632AM-1+WZ 1000-5 TE-632AM-1+WZ 1000-5 0-10 VDC or 4-20mA from Flow Meter 2 Nos BTU meter NO/NC Relay Command to Valve 0-10VDC from Pressure sensor(P499VAP-105K) 0-10VDC from RH cum temp sensor(HE-67N3-0N0BT)
NO/NC Potential free contact from MCC Panel/Pump VFD
NO/NC Potential free contact from MCC Panel/Pump VFD NO/NC Potential free contact from MCC Panel/Pump VFD NO/NC Potential free contact from MCC Panel/Pump VFD 0-10VDC from Pressure sensor(P499VAP-105K)
NO/NC Potential free contact from MCC Panel/Pump VFD
NO/NC Potential free contact from MCC Panel/Pump VFD NO/NC Potential free contact from MCC Panel/Pump VFD NO/NC Potential free contact from MCC Panel/Pump VFD 0-10VDC from Pressure sensor(P499VAP-105K) 0-10VDC or 4-20mA to Pump VFD 0-10VDC or 4-20mA from Pump VFD Soft Integration