TABLES (according to SAUDI cable Company

TABLE (A)

Rating factors for variation in air temperature

INSULATION AIR TEMPERATURE(C)


25C 30C 35C 40C 45C 50C 55C
LSF 1.14 1.10 1.05 1.00 0.95 0.89 0.84

TABLE (B)

Group rating factors for multicore cable in flat formation

number of cable spacing


Touching
in group 0.15 m 0.3 m 0.45 m
2 0.81 0.87 0.91 0.93
3 0.70 0.78 0.84 0.88
4 0.63 0.74 0.81 0.86
5 0.59 0.70 0.78 0.84
6 0.55 0.68 0.77 0.83

TABLE (C)
Ampacity of cable

ampacity of cable
cable mv/A/M
free air in duct
(4x4MM² XLPE/LSF) 38 31 8.7
(4x6MM² XLPE/LSF) 48 38 5.9
(4x10MM² XLPE/LSF) 67 52 3.5
(4x16MM² XLPE/LSF) 88 68 2.2
(4x25MM² XLPE/LSF) 118 90 1.5
(4x35MM² XLPE/LSF) 142 107 1.1
(4x50MM² XLPE/LSF) 175 129 0.81
(4x70MM² XLPE/LSF) 220 161 0.58
(4x95MM² XLPE/LSF) 272 196 0.44
(4x120MM² XLPE/LSF) 316 226 0.37
(4x150MM² XLPE/LSF) 363 258 0.31
(4x185MM² XLPE/LSF) 418 295 0.27
(4x240MM² XLPE/LSF) 496 346 0.23
(4x300MM² XLPE/LSF) 571 394 0.2
(1x4MM² XLPE/LSF) 38 32 8.8
(1x6MM² XLPE/LSF) 49 40 5.9
(1x10MM² XLPE/LSF) 66 54 3.6

TABLE (D)
(GE) COMPANY BUSAWY VOLTAGE DROP

BUSWAY VD VD
V / 100 FEET V/METER
1600A 3.13 0.094
2000A 2.88 0.086
2500A 2.81 0.084
3000A 3.11 0.093
4000A 2.92 0.088
5000A 2.77 0.083