Floor Beam FB05
TIMBER FLOOR BEAM V5.02 Demo User

Beam: (Floor Beam FB05) 240mm x 45mm F17 KD HW (Single span)


Bending: M(dl)* = 1.52kNm < øM(dl) = 8.79kNm, M* = 3.00kNm < øM = 12.34kNm OK (0.17,0.24)
Shear: V(dl)* = 1.69kN < øV(dl) = 12.56kN, V* = 3.34kN < øV = 17.63kN OK (0.13,0.19)
Deflection: δ(dl+Ψl*ll) = L/771 (5mm) , Ψs.δll = L/1493 (2mm), 1kN midspan δ =1.3mm Warning (vibr.)
Reactions: (Each end) Rdl = 0.5kN, Rll = 1.8kN, R* = 3.3kN

Geometry (For a primary building member)

Category = 2 (1) House, (2) Primary building elements, (3) Important


House = Y (Y)es,(N)o
Span (L) = 3600 mm Span type = S (S)ingle,(D)ouble
Centres (cts) = 450 mm Edge restrained = C (T)ension, (C)omp.
Lay (Top) 600 mm (Downward)
Loadings

Floor area (A) = 1.62 m² Live load type = N (N)ormal, (S)torage, (M)anual
Long term LL (Ψl) = 1.00 AS/NZS 1170.0 - Table 4.1
Uniform dead loads
Floor dead load (wdl) = 0.50 kPa * 450 mm + kN/m = 0.23 kN/m
Wall dead load (wdl) = kPa * 450 mm + kN/m = 0.00 kN/m
Other dead load (wdl) = kPa * mm + kN/m = 0.00 kN/m
Include S.Wt = Y (Y)es,(N)o S.Wt = 0.07 kN/m
Σwdl = 0.30 kN/m
Uniform live loads
Floor live load (wll) = 1.50 kPa * 450 mm + kN/m = 0.68 kN/m
Partitions (wll) = kPa * 450 mm + kN/m = 0.00 kN/m
Alternate point live load = 1.80 kN (critical) Distr. to 1 members Σwll = 1.00 kN/m

Point loads
Dead load (pdl) = kN Position = 1800 mm from LHS
Live load (pll) = kN Shear using PL at support = N (Y)es,(N)o

Short term LL factor (Ψsu) = 1.00 (Ψsp) = 1.00


Long term LL factor (Ψlu) = 0.40 (Ψlp) = 0.60
w(dl+Ψl.ll)* = 1.35*(wdl+Ψl*wll) = 0.94 kN/m M(dl+Ψl.ll)* = 1.52 kNm (Max at 1800mm)
w* = 1.2*wdl+1.5*wll = 1.85 kN/m M* = 3.00 kNm (Max at 1800mm)
p(dl+Ψl.ll)* = 1.35*(pdl+Ψl*pll) = 0.00 kN V(dl+Ψl.ll)* = 1.69 kN
p* = 1.2*pdl+1.5*pll = 0.00 kN V* = 3.34 kN
Bending and Shear Capacity - Cl 3.2.1 & Cl 3.2.5

Member = 240mm x 45mm F17 KD HW Area (A) = 10800 mm²


Description = F17k seasoned hardwood Section modulus (Zx) = 432 x10³ mm³
Design depth (dD) = 240 mm Stiffness (Ix) = 51.8 x10⁶ mm⁴
Design width (dW) = 45 mm Modulus of elasticity (E) = 14000 MPa - Table H2.1

S1=1.25*dD/dW*(Lay/dD)⁰·⁵ = 10.54 For comp. edge restrained - Cl 3.2.3.2


k12 = 1.000 for ρb*S < 10 - Cl 3.2.4 f'b = 42.0 MPa
Strength reduction factor (ø) = 0.85 Table 2.1 f's = 3.6 MPa
Material constant (ρb) = 0.92 (rb=0.81)
øM(dl) = ø*(k1=0.57)*k4*k6*k9*k12*f'b*Zx = 8.79 kNm Duration factor (k1) = 0.80
øM = ø*k1*k4*k6*k9*k12*f'b*Zx = 12.34 kNm Moisture factor (k4) = 1.00
Temp. factor (k6) = 1.00
øV(dl) = ø*(k1=0.57)*k4*k6*f's*(2/3*A) = 12.56 kN Sharing factor (k9) = 1.00
øV = ø*k1*k4*k6*f's*(2/3*A) = 17.63 kN Size modifer (mod.b) = 1.00
Deflections Size modifer (mod.s) = 1.00

Ireq'd DL+Ψl.LL (L/300) = 20.2 x10⁶ mm⁴ < Critical δDL+Ψl.LL= 4.7 mm Span / 771
Ireq'd Ψs.LL (12mm) = 10.4 x10⁶ mm⁴ Ψs.δLL = 2.4 mm Span / 1493

j2 = 2.0 1kN midspan δ = 1.3 mm

Deflection limits

Service class = N (1),(2),(3),(S)evere/Adverse,(N)ot applicable

δ(DL+Ψl.LL) lim. = Span/ 300 = 12mm or 16 mm δDL+Ψl.LL lim. = 12 mm


δLL lim. = Span/ 300 = 12mm or 12 mm δLL lim. = 12 mm
Notes:
Double members:
Double members are not considered laminated.
Refer to AS1684.2 Cl 2.3 for requirements of
vertical lamination.
Laminated = Y (Y)es,(N)o

Importance:
Category 1 House failure affecting < 25m², secondary building element
Category 2 Building, house failure affecting > 25m²
Category 3 Important

Double spans:
Moment taken critical at internal support.

Dead load descriptions:


Title =
Title =

Live load description:


Title = Partitions

Point load description:


Title =

Duration:
Intermediate (Manual) durations from Table 2.3
may be used with engineering judgement.
k4 factor:
Partial seasoning factor
Refer Cl 2.4.2.2 & 2.4.2.3 for more information.

k6 factor:
Refer Cl 2.4.3 if designing structures near coastal
regions of Queensland north of 25°S and all other
regions north of 16°S

Material constant:
Refer to Appendix E2
Load ratio = 0.81

Dead load deflection:


Dead Load in calculations includes the
portion of permanent live load (Ψl) as noted
in clause 2.4.1.2 Note 1 and AS1170.2 Table 4.1

Vibration:
Refer AS1170.0 Table C1 Note 10
Vibration warning = Y (Y)es,(N)o

Service class:
Service class defined in AS/NZS 1328.1 1998 Glued Laminated Structural Timber
1 - Domestic houses, Commerical Offices
2 - Open sheds, exposed beams under soffits, porches, laundries
3 - Marine structures, Bridges
S - Severe/Adverse requires specialist advice