You are on page 1of 16

EQUIPMENT: FIRERAY 2000

PUBLICATION: 01B-05-D1
ISSUE No. & DATE: 02 1/01

DOCUMENT CONTROL NUMBER /

FIRERAY 2000 OPTICAL BEAM SMOKE DETECTOR

PRODUCT APPLICATION AND SYSTEM DESIGN

LIST OF CONTENTS

1. GENERAL 3 6. CONSTRUCTION 16

2. SALIENT FEATURES 3 7. TECHNICAL SPECIFICATION 16

3. CONTROLS AND INDICATORS 3 8. ORDERING INFORMATION 16

4. OPERATION 3 9. ASSOCIATED PUBLICATIONS 16


4.1 PRINCIPLES OF OPERATION 3
4.2 SMOKE DETECTION 3
4.2.1 EXAMPLES OF THRESHOLD
SETTINGS 4
4.3 AUTO RESET 4
4.3.1 LINK SETTING FOR
AUTO RESET 4
4.4 AUTOMATIC GAIN CONTROL
(AGC) 4
4.4.1 LINK SETTING FOR (AGC
COMPENSATION) 4
4.5 FAULT INDICATION 4

5. DESIGN CONSIDERATIONS 4
5.1 GENERAL 4
5.2 LOOP POWERED OPERATION 4
5.3 RETRO-REFLECTIVE OPERATION 4
5.4 AREAS OF PROTECTION 5
5.4.1 BEAMS INSTALLED IN THE
APEX OF A PITCHED OR
NORTH LIGHT ROOF 5
5.4.2 BEAMS INSTALLED UNDER
A FLAT ROOF 5
5.5 CABLING 11
5.6 POWER SUPPLIES 11
5.7 ALIGNMENT AND TESTING 11
5.8 SETTING THE PCB LINKS 15

© 2001 Tyco Electronic Product Group PAGE 1 of 16


Registered Office: 19-21 Denmark Street, Wokingham, Berks RG40 2QE

«¥™š—˜¥³¸¾¯¼¸«¾³¹¸«¶¥¶¾® ¥­¹·º«¸Ã
FIRERAY 2000
01B-05-D1
02 1/01

THIS PAGE IS INTENTIONALLY LEFT BLANK

PAGE 2 of 16
EQUIPMENT: FIRERAY 2000
PUBLICATION: 01B-05-D1
ISSUE No. & DATE: 02 1/01

1. GENERAL 3. CONTROLS AND INDICATORS


The FIRERAY 2000 Optical Beam Smoke Detector is an The Control Box has a fire indicator (red LED) on the front
active infrared smoke detector. The system comprises a panel. No operator controls are fitted. Other presets and
Transmitter, a Receiver, and a Control Box. indicators are fitted inside the unit. The presets and status
indicators are accessible when the front panel of the unit is
A modulated infrared beam from Transmitter to Receiver is
opened. The presets and indicators mounted on the PCB
analysed by the Control Box to determine whether smoke is
give status indications as an aid to setting up and fault
present. A fire alarm signal is generated when the Control
finding.
Box determines that smoke is causing partial obscuration of
the infrared beam. The Transmitter Unit has a range adjustment preset, (used
when setting up) which is located beneath a removable
The system is designed for use in large open type interiors
grommet opposite the cable entry gland.
such as manufacturing plants, hangars and workshop areas,
power stations, shopping malls where the installation and The Receiver Unit has no controls, indicators, or presets.
servicing of point-type detectors would prove difficult or
impractical, or cable tunnels where access is only possible at
either end. 4. OPERATION
The system can be used with any Tyco Conventional or
Addressable Fire Controller. 4.1 PRINCIPLES OF OPERATION
The Transmitter Unit emits a beam of infrared light which is
pulse-modulated and collimated to produce a cone of
2. SALIENT FEATURES illumination of approximately 3 metres radius at 100 metres
range.
• Beam range 5 metres to 100 metres
The Receiver Unit senses the transmitted beam amplifies it
• Area of coverage 1400 square metres and feeds it to the Control Box.
• Selectable sensitivity The Control Box examines received the signal to determine
• Self-check and automatic compensation if the received signal strength has changed from the
calibrated alignment value. Any change in signal strength is
• Manual or automatic reset analysed to check if it is above or below a certain reference
• Suitable for use with both conventional and level, and is present for a required time. If the conditions are
met then the circuit responds by either adjusting the system
addressable controllers
gain or by signalling a fault or an alarm.
• Fault/Fire interface to MINERVA controller
• Alarm relay may be latching or non latching
4.2 SMOKE DETECTION
• Optional MINERVA loop-powered interface
module (LPBD520) When smoke is present in the beam, the signal received is
reduced to a level determined by the density of the
• Low current consumption smoke. In the event of the smoke reducing the signal
• Robust metal construction strength to a level between the specified alarm threshold and
93% obscuration for a period of between 5 to 10 seconds, the
• Flexible system design options fire alarm output is activated.
• Designed to conform to BS5839 Part 5 Three alarm thresholds can be selected.
i) 25% - 1.23 dB
ii) 35% - 1.87 dB
iii) 50% - 3.01 dB

Note:
1) The 25% threshold does not fully meet BS5839
r e q u i r e m e n t s fo r s t a b i l i t y ove r t h e f u l l
temperature range.
2) The 50% threshold is recommended for retro-
reflective operation.

© 2001 Tyco Electronic Product Group PAGE 3 of 16


Registered Office: 19-21 Denmark Street, Wokingham, Berks RG40 2QE

«¥™š—˜¥³¸¾¯¼¸«¾³¹¸«¶¥¶¾® ¥­¹·º«¸Ã
FIRERAY 2000
01B-05-D1
02 1/01

4.2.1 EXAMPLES OF THRESHOLD ii) The Fireray will, when at the last stage of
SETTINGS gain, signal a fault. This will inhibit the Fire
alarm.
If the threshold level for a conventional beam Tx to Rx, For option (ii) set the link marked ‘COMP’ to
end-to-end was set at 25%. Then the threshold level for a closed.
retro-reflective beam set up for a comparable response
would need to use the 35% setting.
Similarly, if the threshold level for a conventional beam Tx 4.5 FAULT INDICATION
to Rx end-to-end was set at 35%. Then the threshold level
for a retro-reflective beam set up for a comparable response A fault condition is signalled if the signal level is reduced
would need to use the 50% setting. by more than 93% for a period in excess of 5 seconds. The
reduction in signal level may be caused through power
failure at the transmitter or mechanical blockage of the
beam, or other malfunction.
4.3 AUTO RESET
The Auto-reset function automatically resets the receiver
five seconds after a fault condition has been indicated if the 5. DESIGN CONSIDERATIONS
fault is no longer present.
5.1 GENERAL
The beam can detect the presence of black or white smoke.
4.3.1 LINK SETTING FOR AUTO RESET The beam range is between 5 metres to 100 metres.
The fire alarm may be latching or non-latching: The beam between the Transmitter (Tx) and Receiver (Rx)
i) For latching operation set the link marked must be between 0.3m and 0.6m below and parallel to the
‘ALARM’ to closed. ceiling of the building in which the detectors are installed.
ii) For non-latching operation set the link to The transmitter and receiver must be mounted so that the
open. beam emitted from the round glass area of the transmitter is
in line-of-sight with the round glass area of the receiver.
For MINERVA application use the latching setting and also Each pair of detectors must be mounted on a firm structural
refer to publication 08A-02-D26. part of the building.

4.4 AUTOMATIC GAIN CONTROL (AGC) Note: Ensure that there is no source of infrared
(heat) near the detectors such as a heater, an
Long term degradation of signal strength by component incandescent light bulb or direct sunlight.
ageing or the accumulation of dirt on the optical surfaces
will not generate an alarm because of compensation
provided by the AGC circuit. The AGC circuit operates by The Control Box should be mounted at ground level, within
comparing the received signal against a standard at 100 metres cable run of the receiver.
predetermined time intervals. Differences of more than 7%
are corrected by the automatic selection of gain stages. The
AGC time is factory set to nominally 1.5 hours. 5.2 LOOP POWERED OPERATION
For details on loop powered operation and connections
4.4.1 LINK SETTING FOR (AGC refer to publication 08A-02-D26.
COMPENSATION)
There are two options available when the AGC runs out of 5.3 RETRO-REFLECTIVE OPERATION
compensation:
Where the beam path is less than 10 metres or access to the
i) The Fireray will, when at the last stage of opposing wall is restricted or wiring to one of the heads is
gain, signal a fault. difficult, the Fireray 2000 should be configured for retro-
In the event of further signal loss reducing the reflective operation.
signal to the alarm threshold, a Fire alarm will
be signalled. (This is to conform to BS5839
part 5). For option (i) set the link marked Note: For beam ranges of less than 10 metres, use
‘COMP’ to open. a retro-reflective configuration to avoid
receiver saturation.

PAGE 4 of 16
EQUIPMENT: FIRERAY 2000
PUBLICATION: 01B-05-D1
ISSUE No. & DATE: 02 1/01

For retro-reflective operation the two heads are mounted 5.5 CABLING
side by side as closely as possible and a reflector is mounted
on the opposing wall. The number of reflectors required Receiver Unit - The cable supplied with the receiver unit is
varies proportionally with the distance between heads and nominally one metre in length and unscreened, therefore it is
reflector. usually necessary to use a conduit box to connect between
the receiver unit cable and the cable to the Control
Range: 2 metres to 25 metres: 1 reflector Box. Mount the conduit box as close as practicably possible
Range: 25 metres to 35 metres: 4 reflectors (to form a to the receiver unit so that the cable between conduit box and
square) receiver is kept as short, to reduce the possibility of
electomagnetic interference. Use screened cables and
Range: 35 metres to 45 metres: 6 reflectors (to form a terminate the screen braid to the cable gland on the control
rectangle) box, refer to Fig. 17.
The maximum length of cable run between Rx unit and
When using reflectors the gain of the Transmitter must be set control box should not exceed 100 metres.
to full (max). Transmitter Unit - As with the receiver unit, the the cable
supplied with the transmitter unit is also nominally one
metre in length, and unscreened therefore use a conduit box
5.4 AREAS OF PROTECTION to connect between the transmitter unit cable and the
The areas of protection for different roof styles are detailed incoming power supply cable. Position the the conduit box
in this section, for examples see Fig. 1 to Fig. 5. as close as practicable to the transmitter unit. Use screened
cables and terminate the screen braid to the cable gland on
It is possible for the beam to pass through holes in wall but the control box. or power supply casing if a separate supply
the holes must be at least 20 cm diameter or the diameter of is used, refer to Fig. 17.
the beam at the point along the beam path.
The terminal blocks in the control box accept a maximum of
2.5mm2 cable.
5.4.1 BEAMS INSTALLED IN THE APEX The size for the cables from the detectors is 0.5mm2. Use fire
OF A PITCHED OR NORTH LIGHT resistant cable between the detectors and Control Box.
ROOF
Where beam detectors are installed in the apex of a pitched 5.5.1 RECOMMENDED CABLES
or north light roof, the width of the area protected by the
beam, can be increased. MICC ‘P y ro ’ type cable is recomme nded for all
applications, as it provides excellent EMC performance,
The beam width in flat areas is 14 metres and this dimension high strength and superb long term fire resistance, however,
can be increased by 1% (14 centimetres) for each degree of any good quality screened cable may be used. (Legislation
slope from the horizontal, up to a maximum increase of 25% and building/local regulations permitting).
of slope (equating to 3.5 metres).
The most important aspect in meeting the required EMC
performance is the method of screen termination. Pigtails
Note: This relaxation only applies to a beam mounted
are not sufficient. Good quality metal glands should be
in the apex.
used. The cable screens must be terminated at the gland and
have a 360 o connection to it. Also metal junction boxes
should be used where extensions are made to the supplied Tx
5.4.2 BEAMS INSTALLED UNDER A FLAT and Rx cables.
ROOF
The screens should be terminated at metal junction box
For areas under a flat horizontal ceiling (less than 3.5 glands, with the screen effectively passing through the metal
degrees from the horizontal) the maximum distance from box MICC ‘Pyro’ glands are suitable for use both with pyro
any adjacent parallel wall or partition must not exceed 8 cable and normal screened cable if the correct size is
metres when measured perpendicular to the beam on the chosen. The screen of the cable should be folded back over
plan view. the outer insulatiom of the cable and the gland olive should
In open areas the maximum permitted distance between be a push fit over this.
parallel beam smoke detectors is 14 metres when measured Whenever possible, avoid bunching the system cabling with
perpendicular to the beam on the plan view. other factory/ building services wiring.

© 2001 Tyco Electronic Product Group PAGE 5 of 16


Registered Office: 19-21 Denmark Street, Wokingham, Berks RG40 2QE

«¥™š—˜¥³¸¾¯¼¸«¾³¹¸«¶¥¶¾® ¥­¹·º«¸Ã
FIRERAY 2000
01B-05-D1
02 1/01

Fig. 1 Beam Divergence

Fig. 2 Area of Protection

PAGE 6 of 16
EQUIPMENT: FIRERAY 2000
PUBLICATION: 01B-05-D1
ISSUE No. & DATE: 02 1/01

Fig. 3 Flat Roofs

Fig. 4 Sloping Roofs

Fig. 5 Pitched and North Light Roofs

© 2001 Tyco Electronic Product Group PAGE 7 of 16


Registered Office: 19-21 Denmark Street, Wokingham, Berks RG40 2QE

«¥™š—˜¥³¸¾¯¼¸«¾³¹¸«¶¥¶¾® ¥­¹·º«¸Ã
FIRERAY 2000
01B-05-D1
02 1/01

Fig. 6 Control Box - Overall and Fixing Dimensions

PAGE 8 of 16
EQUIPMENT: FIRERAY 2000
PUBLICATION: 01B-05-D1
ISSUE No. & DATE: 02 1/01

Fig. 7 Transmitter and Receiver Unit - Overall Dimensions

Fig. 8 Transmitter/Receiver - Mounting Bracket

© 2001 Tyco Electronic Product Group PAGE 9 of 16


Registered Office: 19-21 Denmark Street, Wokingham, Berks RG40 2QE

«¥™š—˜¥³¸¾¯¼¸«¾³¹¸«¶¥¶¾® ¥­¹·º«¸Ã
FIRERAY 2000
01B-05-D1
02 1/01

Fig. 9 Ceiling Mounting

Fig. 10 Wall Mounting

PAGE 10 of 16
EQUIPMENT: FIRERAY 2000
PUBLICATION: 01B-05-D1
ISSUE No. & DATE: 02 1/01

5.6 POWER SUPPLIES 5.7 ALIGNMENT AND TESTING


The optical beam smoke detector can be powered from The detectors need to be aligned so that they work
either a 12 volt or 24 volt dc supply. correctly. An Alignment Aid (Fig. 12) which consists of a
small box with a light mounted on it, is used during
The Receiver unit derives its power from the Control Box. commissioning to facilitate optimum beam alignment.
The Transmitter unit may be powered from either the Supplied inside the Control Box is an acetate Test Card with
Control Box or from a separate 12 volt or 24 volt dc supply. black markings on it. The markings pattern provides partial
If the optical beam smoke detector is being used with a obscuration of the beam when testing the FIRE and FAULT
MINERVA addressable fire controller the power supply can functions.
be derived the loop via a LPBD520 module.
If the optical beam smoke detector is being used with a
conventional fire controller the power is drawn from a
suitable 12 volt or 24 volt dc power supply unit.

Fig. 11 Connections to Alignment Aid

Fig. 12 Alignment Aid

© 2001 Tyco Electronic Product Group PAGE 11 of 16


Registered Office: 19-21 Denmark Street, Wokingham, Berks RG40 2QE

«¥™š—˜¥³¸¾¯¼¸«¾³¹¸«¶¥¶¾® ¥­¹·º«¸Ã
FIRERAY 2000
01B-05-D1
02 1/01

Fig. 13 Detector Cabling - Single LPBD or Conventional Configuration

Fig. 14 Detector Cabling - Two LPBD520s on the Same Loop or Two Different Loops or
Conventional Configuration using Two Separate 24V Power Supplies

PAGE 12 of 16
EQUIPMENT: FIRERAY 2000
PUBLICATION: 01B-05-D1
ISSUE No. & DATE: 02 1/01

Fig. 15 Detector Cabling - Retro-reflective or Conventional Configuration

Fig. 16 Reflector - TKS 100x100

© 2001 Tyco Electronic Product Group PAGE 13 of 16


Registered Office: 19-21 Denmark Street, Wokingham, Berks RG40 2QE

«¥™š—˜¥³¸¾¯¼¸«¾³¹¸«¶¥¶¾® ¥­¹·º«¸Ã
FIRERAY 2000
01B-05-D1
02 1/01

Fig. 17 Cable Connections

PAGE 14 of 16
EQUIPMENT: FIRERAY 2000
PUBLICATION: 01B-05-D1
ISSUE No. & DATE: 02 1/01

Fig. 18 PCB Layout

5.8 SETTING PCB LINKS


Set the links on the PCB to the positions required. See Table 1 below:

LINK POSITION
OPTION REQUIRED
ALARM COMP 25% 35% 50%

ALARM Non-latching OPEN - - - -

ALARM Latching CLOSED - - - -

COMP - AGC compensation to signal FAULT and OPEN - - - -


ALARM

COMP - AGC compensation to signal FAULT and CLOSED - - - -


inhibit ALARM

25% Obscuration threshold - - CLOSED OPEN OPEN

35% Obscuration threshold - - OPEN CLOSED OPEN

50% Obscuration threshold - - OPEN OPEN CLOSED

Table 1: Link Settings

© 2001 Tyco Electronic Product Group PAGE 15 of 16


Registered Office: 19-21 Denmark Street, Wokingham, Berks RG40 2QE

«¥™š—˜¥³¸¾¯¼¸«¾³¹¸«¶¥¶¾® ¥­¹·º«¸Ã
FIRERAY 2000
01B-05-D1
02 1/01

6. CONSTRUCTION Current drawn:


The Control Box is pressed sheet steel and finished in white. Control Box, Receiver and Transmitter:
Quiescent current: less than 13mA
The Detector Heads are cast in Zinc alloy and also finished
in white to match the Control Box. Alarm current: less than 20mA
The detector brackets are steel, finished in white. Control Box and Receiver only:
Quiescent current: less than 13mA
7. TECHNICAL SPECIFICATION Alarm current: less than 20mA

OVERALL DIMENSIONS Transmitter only:


Control box Quiescent current: less than 13mA
Height: 260 Alarm current: less than 20mA
Width: 210
Optical wavelength: 880nm
Depth: 80
Weight: 2.25kg Electromagnetic Compatibility:

Transmitter/Receiver Unit heads EMC Equals or exceeds the


requirements of:
Height: 95 BS EN 50081-1 : 1992
Width: 80 BS EN 50082-1 : 1992
Depth: 115
Weight (with brackets): 0.4kg Note: The above standards fulfil the requirements of
the European Directive for EMC (89/336/EEC).
Colour: All units finished in white
to RAL9010 Tolerance to Beam Misalignment:
Transmitter: ± 0.5o
Environmental:
Receiver: ± 0.5o
Storage temperature: -20oC to +55oC
(Reflector TKS 100 x 100 Temp Range -20oC to +60oC)
Operating temperature: -20oC to +55oC
Humidity: up to 95% (non condensing)
Enclosure IP rating: IP54 8. ORDERING INFORMATION
Fireray 2000 complete: 516-015-006A
Electrical Charactristics: Fireray 2000 complete: 516-015-006T
Supply voltage: +11.5V to 28V dc LPBD520: 557-180-217
Retro-Reflector (TKS 100 x 100): 516-015-007
Alignment Aid: 516-015-008

9. ASSOCIATED PUBLICATIONS
15A-02-D1 ‘MINERVA’ RANGE OF ANALOGUE ADDRESSABLE CONTROLLERS -
PRODUCT APPLICATION AND SYSTEM DESIGN
20A-02-D1 T880 FIRE CONTROLLERS - PRODUCT APPLICATION AND SYSTEM DESIGN
20A-02-D1 T881 FIRE CONTROLLERS - PRODUCT APPLICATION AND SYSTEM DESIGN
08A-02-D26 LPBD520 LOOP POWERED BEAM DETECTOR INTERFACE MODULE -
PRODUCT APPLICATION AND SYSTEM DESIGN

CB/jm 12th January 2001


PAGE 16 of 16

You might also like