Product Data Sheet

FD2000
Beam smoke detector 10 - 100m

General

The FD2000 series products consists of an infrared transmitter,


a receiver and a control unit. They are designed to be used
where point smoke detectors are not applicable due to height or
inaccessibility. The control units have relay outputs for alarm
and fault and may therefore be monitored by all types of fire
panels.

Installer friendly

The control unit, which contains the threshold settings and test
meter output, may be conveniently mounted at ground level.
Wiring is restricted to a minimum as no connection is required
between transmitter and receiver. The low power consumption
of the units allows the powering of multiple sets from a single Standard Features
power supply without compromising the system's autonomy.
E Large area coverage up to 1500 m² per unit
A wireless alignment tool reduces installation time considerably. E Range from 10 to 100m
On difficult sites the receiver and transmitter may be used in E Up to ceiling heights of 25 m
reflective mode by mounting the transmitter and receiver next to E 12 to 24 VDC
each other and using passive reflectors. E Low current consumption
E Manual or automatic reset
E 3 selectable alarm thresholds
Reducing false alarms E Self check and automatic signal compensation
E Automatic discrimination between fire and fault
When smoke is present in the beam path, the received signal is E Retro operation through prisms
reduced by a level determined by the density of the smoke. In E Ground level electronics
the event of the smoke reducing the signal strength between E Easy wiring and alignment
the obscuration threshold and 93% for a period between 8 to 10 E Conforms to BS5839 part 5
seconds, the fire alarm output is activated. To optimise for every E VdS approved
environment, the units provide three selectable alarm E Atex flame-proof version
thresholds, each set for a different % obscuration.

An automatic gain control prevents nuisance alarms caused by


long term signal degradation, e.g. in the case of dirt build up.
Total obscuration (> 90%) will generate a fault and not an
alarm.
FD2000
Beam smoke detector 10 - 100m

Specifications Ordering Information


Supply Voltage 11.5 - 28 VDC Part No. Description
Current consumption FD2000 Beam smoke detector 10 - 100m
Quiscent less than 13 mA
Alarm less than 20 mA
Operating Temperature -20 to 55 °C
Size
Control Unit 210 x 160 x 80 mm
Heads 83 x 115 x 135 mm
IP Rating
Control Unit IP 50
Heads IP 50
Construction
Control Unit Double pressed steel sheet
Heads Zinc alloy
Colour
Control Unit White RAL 9010
Heads White RAL 9010
Certification VdS

As a company of innovation, UTC Fire & Security reserves the right to change product
specifications without notice. For the latest product specifications, visit UTC Fire & Security
online or contact your sales representative.
FD2000-2014-02-3 14:15:55 Released :29-AUG-11