Beam smoke detector 10 - 100m
General
Installer friendly
The control unit, which contains the threshold settings and test
meter output, may be conveniently mounted at ground level.
Wiring is restricted to a minimum as no connection is required
between transmitter and receiver. The low power consumption
of the units allows the powering of multiple sets from a single Standard Features
power supply without compromising the system's autonomy.
E Large area coverage up to 1500 m² per unit
A wireless alignment tool reduces installation time considerably. E Range from 10 to 100m
On difficult sites the receiver and transmitter may be used in E Up to ceiling heights of 25 m
reflective mode by mounting the transmitter and receiver next to E 12 to 24 VDC
each other and using passive reflectors. E Low current consumption
E Manual or automatic reset
E 3 selectable alarm thresholds
Reducing false alarms E Self check and automatic signal compensation
E Automatic discrimination between fire and fault
When smoke is present in the beam path, the received signal is E Retro operation through prisms
reduced by a level determined by the density of the smoke. In E Ground level electronics
the event of the smoke reducing the signal strength between E Easy wiring and alignment
the obscuration threshold and 93% for a period between 8 to 10 E Conforms to BS5839 part 5
seconds, the fire alarm output is activated. To optimise for every E VdS approved
environment, the units provide three selectable alarm E Atex flame-proof version
thresholds, each set for a different % obscuration.