Professional Documents
Culture Documents
LABORATORY: PROCESS 1
REVISION NO:
CONTROL
29 SEPT
EFFECTIVE DATE:
EXPERIMENT:GAS PRESSURE 2014
PROCESS CONTROL AMENDMENT
DATE:
INTRODUCTION: /5%
PROCEDURE: /5%
RESULTS& CALCULATIONS /15%
ANALYSIS /15%
DISTRIBUTION OF MARKS FOR DISCUSSIONS: /20%
LABORATORY REPORT: ADDITIONAL QUESTIONS /15%
CONCLUSION /10%
REFERENCES: /5%
TOTAL: /100%
I hereby declare that I have prepared this report with my own efforts. I also admit to
not accept or provide any assistance in preparing this report and anything
that is in it is true.
1.0 OBJECTIVES
a) To identify the important components of the air pressure control system and to
mark them in the P&I Diagram To study single loop flow control using PID
controller
b) To control the pressure in single capacity and two capacity processes using
PID controller.
c) To tune the PID controller using Ziegler Nichols closed-loop method.
5.0 PROCEDURE
5.1 STARTUP PROCEDURES
Go through these steps before starting any experiment.
1) Switch the "PANEL, SCADA/DDC" selector switch at the front of the
cubicle to the "PANEL, SCADA" position.
2) Switch ON the main power supply at the front of the cubicle. All the
panel instruments will lit up.
If the recorder chart drive is running, STOP it by pressing the `RCD'
pushbutton.
3) If any annunciator gets activated, press the ACKNOWLEDGE button
to silence the buzzer.
4) Set the instrument air supply regulator to the pressure indicated at
the air regulators at the pneumatic control valves PCV91 and PCV92.
Purge if there is any condensed water in the air regulators by opening
the bottom drain valves.
5) Make sure that the by-pass valves around the control valves PCV91
and PCV92 are shut fully and the pair of manual valves
upstream/downstream of these control valves are opened.
6) Check that the control valve positioner (PP) of PCV91 is connected
(ON) (i.e., not by-passed).
7) Make sure the compressed air is available at the pressure inlet air
regulator AR91.
8) Check that the vent valve (V) and bottom drain valve (D) of vessel T91
are shut.
9) SHUT fully the manual valves MV91B and MVIII.
10) SHUT fully the process inlet manual valve MV91.
11) Place the panel controller PIC91 in manual (M) mode and adjust its
MV = - 6.3% to open the control valve PCV91 fully.
12) Open fully the final discharge manual valve (VP). This valve is at
downstream of pressure control valve PCV91.
UniKL MICET EDITION: 1
LABORATORY: PROCESS 1
REVISION NO:
CONTROL
29 SEPT
EFFECTIVE DATE:
EXPERIMENT:GAS PRESSURE 2014
PROCESS CONTROL AMENDMENT
DATE:
13) From the process air supply, trace the two pipe lines PLI and PLII as
follows: Pipeline PLI: Single capacity process:
AR91-MV91-T91-PLI-B92- FI92 -P CV9 1 –VP
Two-capacity process
AR9 1 -MV9 1 -T91 -PLI-MVI-T92-MV92-FI92 -PCV 9 1 –VP
Pipeline II (PLII):
AR9 1 -MV9 1 -T91-PLII-MVII-PCV92-MV92A/MV92B-V
14) Open fully the pipelines PLI (Single capacity process) and PLII at their
various manual valves.
15) Make sure the manual by-pass valve B92 around vessel T92 is opened
and the manual valves at the inlet MVI and outlet MV92 of T92 are
shut.
16) The pipeline PLII has two discharge manual valves, MV92A (globe
valve) and MV92B (gate valve). SHUT both the valves MV92A and
MV92B.
17) Check and adjust the pressure at AR91 is approximately at the
pressure indicated at AR91. Check MV91 is fully shut.
18) Slowly open MV91 and regulate it until the flow rate at the variable
area flow meter FI92 reads 35 Nm3/Hr
19) Check the pressure and flow rate setting:
a. Shut fully PCV91 from PIC91 in manual (M) mode with
MV=106.3%. Read the pressure at vessel T91 at the PV reading
of PIC91. If the pressure is about 22 – 27 psig, the pressure is
correctly set.
b. Open fully PCV91 from PIC91 in manual (M) mode with MV=-
6.3%. Read the pressure at vessel T91 at the PV reading of
PIC91. If the pressure is not more than 10 psig and the flow
rate at FI92 also reads 35 Nm 3/Hr, the air flow rate is correctly
set.
c. Now the process air supply pressure and flow rate are set. DO
NOT readjust AR91 and MV91 hereafter.
UniKL MICET EDITION: 1
LABORATORY: PROCESS 1
REVISION NO:
CONTROL
29 SEPT
EFFECTIVE DATE:
EXPERIMENT:GAS PRESSURE 2014
PROCESS CONTROL AMENDMENT
DATE:
6) For single capacity operation, only vessel T91 is used. Vessel T92
is by-passed
a. Open by-pass valve B92 around T92
b. Shut the manual valves at the inlet, MVI, and at the outlet,
MV92, of T92.
c. Make sure the air flow path T91-PLI-FI92-PCV91-VP is
opened through B92.
7) Set the set point of PIC91 as SV = 15 psig.
8) Set the PID controller with the first (I) trial values: PB1 =
70%, T11 = 40 secs, TD1 = 0 sec.
9) Transfer the controller to Auto (A) mode and wait for the
response to become almost stable.
10) Switch PIC91 to Manual (M) mode, decrease MV by about 5 to
10%, switch back to Auto (A) mode and observe the response for
a few minutes.
DO NOT FORGET TO MARK THE PID VALUES AND THE
SETPOINT ON THE CHART PAPER WHENEVER THE VALUES
ARE CHANGED. ALSO MARK ON THE CHART THE BEGINNING
OF EACH PART OF THE EXPERIMENT
11) If the response is slow to return to the set point SV = 15 psig,
reduce
TI1 to 20 secs. and repeat the step (10) again.
12) Now set the PID controller with the second (II) trial values:
PB1 = 45%, TI1 = 30 secs, TD1 = 0 sec.
9.0 DISCUSSIONS
10.0 CONCLUSION
Conclusion is merely a summary of the important findings already reported in the
discussion section. It also relates to the objectives stated earlier.
12.0 REFERENCES
Minimum of at least 5 references (with 3 of them are paper/book/chapter base
CAMPUS : UniKL MICET EDITION: 1
LABORATORY: SECTION of 1
PROCESS CHEMICAL REVISION NO:
TECHNOLOGY
29 SEPT
EFFECTIVE DATE:
EXPERIMENT: LIQUID FLOW 2014
PROCESS CONTROL AMENDMENT
DATE: