Wall Properties
in the Wall
Type of Material Thermal Thickness, t, m
Conductivity, k, W/m-
cement
According to: Thermodynamics by V.M. Faires and C.M.Simmang, 6th Edition, Chapter 19,
Heat
Computation
A. Total Resistance
𝑚2 −𝐾
𝑅1 = 0.044 𝑊
Concrete Block
𝑡
𝑅2 = 𝑘
0.154𝑚
𝑅2 = 𝑊
.7786
𝑚−𝐾
𝑚2 −𝐾
𝑅2 = 0.1978 𝑊
Wallboard
𝑡
𝑅3 = 𝑘
0.070𝑚
𝑅3 = 𝑊
0.04902
𝑚−𝐾
𝑚2 −𝐾
𝑅3 = 1.4280 𝑊
Asbestos – cement
𝑡
𝑅4 = 𝑘
0.013𝑚
𝑅4 = 𝑊
.1247
𝑚−𝐾
𝑚2 −𝐾
𝑅4 = 0.1043 𝑊
White pine
𝑡
𝑅5 = 𝑘
0.013𝑚
𝑅5 = 𝑊
.1514
𝑚−𝐾
𝑚2 −𝐾
𝑅5 = 0.08587 𝑊
𝑚2 −𝐾
𝑅6 = 0.12 𝑊
Total Resistance, 𝑅𝑇 = 𝑅1 + 𝑅2 + 𝑅3 + 𝑅4 + 𝑅5 + 𝑅6
𝑚2 −𝐾
𝑅𝑇 = (0.044 + 0.1978 + 1.4280 + 0.1043 + 0.08587 + 0.12) 𝑊
𝒎𝟐 −𝑲
𝑹𝑻 = 1.97997 𝑾
B. Floor Composition
Floorboard 20 mm 𝑊
0.021𝑚−𝐾
Floor tiles 10 mm 𝑊
0.017𝑚−𝐾
Source: http://www.homestyler.com/designprofile/028a3fc3-56a3-4353-8181-
992b14d95e24
Concrete
𝐿 0.10 𝑚 𝑚2 −𝐾
R1 = 𝐾 = 𝑊 = 0.25
0.4 𝑊
𝑚−𝐾
Floorboard
𝐿 0.020 𝑚 𝑚2 −𝐾
R2 = 𝐾 = 𝑊 = 0.9524
0.021 𝑊
𝑚−𝐾
Floor tiles
𝐿 0.010 𝑚 𝑚2 −𝐾
R3 = 𝐾 = 𝑊 = 0.588
0.017 𝑊
𝑚−𝐾
𝑚2 −𝐾
R4=0.12
𝑊
𝑚2 −𝐾 𝑚2 −𝐾 𝑚2 −𝐾 𝑚2 −𝐾
= 0.25 +0.9524 +0.588 +0.12
𝑊 𝑊 𝑊 𝑊
𝒎𝟐 −𝑲
RT = 1.9104 𝑾
C. Ceiling Composition, T=40℃
Concrete, medium
𝐿 0.15 𝑚 𝑚2 −𝐾
R1 = 𝐾 = 𝑊 = 0.375
0.4 𝑊
𝑚−𝐾
Built- up Roofing
𝑚2 −𝐾
R2=0.6 𝑊
𝑚2 −𝐾
R5= 0.044 𝑊
Inside Air Film
𝑚2 −𝐾
R6=0.12 𝑊
𝑚2 −𝐾 𝑚2 −𝐾 𝑚2 −𝐾 𝑚2 −𝐾
=0.375 + 0.06 + 0.044 +0.12
𝑊 𝑊 𝑊 𝑊
𝒎𝟐 −𝑲
RT = 0.599 𝑾
A. Partition A ( Office @ 24℃)
For walls using conduction:
WallA1
𝐴∆𝑇
QA1 = 𝑅𝑇
Area of WallA1=21.6m2
𝐴∆𝑇
QA1 = 𝑅𝑇
21.6𝑚2 (45−24)𝐾
= 𝑚2 −𝐾
1.97997
𝑊
QA1 =230W
𝐴∆𝑇
QA2 = 𝑅𝑇
20.31𝑚2 (45−24)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QA2 =215W
For walls:
WallA3
𝐴∆𝑇
QA3 = 𝑅𝑇
𝐴∆𝑇
QA3.1 = 𝑅𝑇
18𝑚2 (27−24)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QA3 =27.27W
𝐴∆𝑇
QA3.2 = 𝑅𝑇
18𝑚2 (25−24)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QA3.2 =9.09W
WallA4
𝐴∆𝑇
QA4 = 𝑅𝑇
= 36m2 – [2(1x1.2m2]
𝐴∆𝑇
QA4 = 𝑅𝑇
33.6𝑚2 (45−24)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QA4 =27.27W
𝐴∆𝑇
QDD= 𝑅𝑇
3,690𝑚2 (45−24)
= 0.04445
0.17
QDD = 296.36W
For Windows using conduction:
QW=UA(T2-T1)
𝑚2 −𝑘
=5.9 x 1.2 m2 x (45-24)
𝑊
= 594.72W x 4 windows
QW =2378.88W
81𝑚2 (31−24)
QS= 𝒎𝟐 −𝑲
1.9104
𝑾
Qs=296.8W
81𝑚2 (40−24)
Qc= 𝒎𝟐 −𝑲
0.6
𝑾
Qc =2160W
For appliances:
QWA1+ QWA2+ QWA3.1+ QW3.2+ QWA4+ QD+ Qwind+ Qsoil+ Qceil +Qappliances
215+230+27.27+9.09+27.27+296.36+296.8+2160+2830+2378.88
QTA=8470.76W
B. Partition B ( Canteen @ 27℃)
WallB1
𝐴∆𝑇
QB1 = 𝑅𝑇
𝐴∆𝑇
QB1 = 𝑅𝑇
18𝑚2 (27−24)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QB1=27.27W
=32m2-[1.2m2+3.7m2]
=27.1 m2
𝐴∆𝑇
QB2 = 𝑅𝑇
27.1𝑚2 (45−27)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QB2 =246.37W
WallB3
𝐴∆𝑇
QB3 = 𝑅𝑇
Area of WallB3=28.955m2
𝐴∆𝑇
QB3 =
𝑅𝑇
28.955𝑚2 (45−27)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QB3 =136W
𝐴∆𝑇
QB4= 𝑅𝑇
32𝑚2 (27−25)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QB4=32.32W
For Doors using conduction:
𝐴∆𝑇
QDD= 𝑅𝑇
3,690𝑚2 (45−27)
= 0.04445
0.17
QDD = 254W
𝐴∆𝑇
QD= 𝑅𝑇
1.845𝑚2 (45−27)
= 0.04445
0.17
QD = 127W
QW=UA(T2-T1)
𝑚2 −𝑘
=5.9 x 1.2 m2 x(45-27)
𝑊
= 127.44 x 2 windows
QW =254.88W
36𝑚2 (31−27)
QS= 𝒎𝟐 −𝑲
Qs=75.38W
1.9104
𝑾
For ceiling@ 40C using conduction:
36𝑚2 (40−27)
Qc= 𝒎𝟐 −𝑲
0.6
𝑾
Qc =780W
For appliances:
Material Heat load (W) No. of items Total
Refrigerator 310 1 310
Stove 1930 2 3860
Water dispenser 350 1 350
Toaster 1600 1 1600
Blender 300 1 300
Coffee Maker 450 1 450
Oven 400 1 400
Food Warmer 950 1 950
Source:2001 ASHRAE Fundamental Handbook (SI)
Total heat load of appliances = 8220W
27.27+246.37+136+32.32+254+127+254.8+75.38+780+8220
QTB=10153.14W
C. Partition C ( Store @ 25℃)
WallC1
𝐴∆𝑇
QC1 = 𝑅𝑇
𝐴∆𝑇
QC1 = 𝑅𝑇
18𝑚2 (25−24)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QC1=9.09W
𝐴∆𝑇
QC2 = 𝑅𝑇
32𝑚2 (27−25)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QC2=32.32W
For walls:
WallC3
𝐴∆𝑇
QC3 = 𝑅𝑇
Area of WallC3=16.8m2
𝐴∆𝑇
QC3 = 𝑅𝑇
16.8𝑚2 (45−25)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QC3=170W
𝐴∆𝑇
QC4= 𝑅𝑇
27.11𝑚2 (45−25)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QC4=273.8W
For Doors using conduction:
𝐴∆𝑇
QDD= 𝑅𝑇
3,690𝑚2 (45−25)
= 0.04445
0.17
QDD = 282.25W
𝐴∆𝑇
QD= 𝑅𝑇
1.845𝑚2 (45−25)
= 0.04445
0.17
QD = 141.12W
QW=UA(T2-T1)
𝑚2 −𝑘
=5.9 x 1.2 m2 x (45-25)
𝑊
=141.6W x 2 windows
QW =283.2W
36(31−25)
QS= 𝒎𝟐 −𝑲
1.9104
𝑾
Qs=113W
For ceiling@ 40C using conduction:
36𝑚2 (40−25)
Qc= 𝒎𝟐 −𝑲
0.6
𝑾
Qc =900W
For appliances:
Material Heat load (W) No. of items Total
Refrigerator 310 1 310
Electric fan 50 2 100
Water dispenser 350 1 350
TV 220 1 220
Cash Register 48 2 96
Source:2001 ASHRAE Fundamental Handbook (SI)
Total heat load of appliances = 1076W
9.09+32.32+170+273.8+282.25+141.12+283.2+113+900+1076
QTC=3280.78W
D. Partition D( Store @ 20℃)
WallD1
𝐴∆𝑇
QD1 = 𝑅𝑇
𝐴∆𝑇
QD1 = 𝑅𝑇
24𝑚2 (45−20)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QD1 =303.03W
𝐴∆𝑇
QD2 = 𝑅𝑇
16.31𝑚2 (45−20)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QD2 =205.9W
For walls:
WallD3
𝐴∆𝑇
QD3 = 𝑅𝑇
𝐴∆𝑇
QD3 = 𝑅𝑇
24𝑚2 (20−18)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QD3 =24.24W
𝐴∆𝑇
QD4= 𝑅𝑇
22.155𝑚2 (45−20)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QD4=280W
For Doors:
𝐴∆𝑇
QDD= 𝑅𝑇
3,690𝑚2 (45−20)
= 0.04445
0.17
QDD = 352.8W
𝐴∆𝑇
QD= 𝑅𝑇
1.845𝑚2 (45−20)
= 0.04445
0.17
QD = 176.4W
A=36m2
36𝑚2 (31−20)
QS= 𝒎𝟐 −𝑲
1.9104
𝑾
Qs=172.7W
A=36m2
36𝑚2 (40−20)
Qc= 𝒎𝟐 −𝑲
0.6
𝑾
Qc =1000W
For appliances:
Material Heat load (W) No. of items Total (W)
Tissue culture 1146 1 1146
Centrifuge 730 3 2190
Electrochemical 84 1 84
analyzer
Chiller 310 1 310
Incubator 264 3 792
Oscilloscope 97 2 97
Source:2001 ASHRAE Fundamental Handbook (SI)
Total heat load of appliances = 4619W
303.03+205.9+24.24+280+352.8+176.4+172.2+1000+4619
QTD=7133.57W
E. Partition E( Store @ 18℃)
WallE1
𝐴∆𝑇
QE1 = 𝑅𝑇
𝐴∆𝑇
QE1 = 𝑅𝑇
24𝑚2 (20−18)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QE1 =24.24W
𝐴∆𝑇
QE2 = 𝑅𝑇
16.31𝑚2 (45−18)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QE2 =222.4W
WallE3
𝐴∆𝑇
QE3 = 𝑅𝑇
𝐴∆𝑇
QE3 =
𝑅𝑇
24𝑚2 (22−18)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QE3 =48.5W
𝐴∆𝑇
QE4= 𝑅𝑇
3.045𝑚2 (45−18)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QE4=41.52W
For Doors using conduction:
𝐴∆𝑇
QDD= 𝑅𝑇
3,690𝑚2 (45−18)
= 0.04445
0.17
QDD = 380.61W
𝐴∆𝑇
QD= 𝑅𝑇
1.845𝑚2 (45−18)
= 0.04445
0.17
QD = 190W
30𝑚2 (25−18)
QS= 𝒎𝟐 −𝑲
1.9104
𝑾
Qs=110W
30𝑚2 (34−18)
Qc= 𝒎𝟐 −𝑲
0.6
𝑾
Qc =800W
For Windows using conduction:
QW=UA(T2-T1)
𝑚2 −𝑘
=5.9 x 1.2 m2 x (45-18)
𝑊
QW = 191.16W
For appliances:
Material Heat load (W) No. of items Total (W)
Packaging machine 1000 2 2000
Chiller 350 3 1050
Electric Fan 250 3 750
Source:2001 ASHRAE Fundamental Handbook (SI)
Total heat load of appliances = 3800W
24.24+222.4+48.5+41.52+380.61+190+110+800+3800
QTE=5808.43W
F. Partition F( Store @ 22℃)
WallF1
𝐴∆𝑇
QF1 = 𝑅𝑇
𝐴∆𝑇
QF1 = 𝑅𝑇
24𝑚2 (22−18)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QF1 =48.48W
Area of WallF2=16.31 m2
𝐴∆𝑇
QF2 = 𝑅𝑇
16.31𝑚2 (45−22)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QF2 =190W
For walls:
WallF3
𝐴∆𝑇
QF3 = 𝑅𝑇
𝐴∆𝑇
QF3 = 𝑅𝑇
24𝑚2 (45−22)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QF3 =278.8W
Area of WallF4=18.155m2
𝐴∆𝑇
QF4= 𝑅𝑇
18.155𝑚2 (45−22)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QF4=210.9W
For Doors using conduction:
𝐴∆𝑇
QDD= 𝑅𝑇
3,690𝑚2 (45−22)
= 0.04445
0.17
QDD = 324.6W
𝐴∆𝑇
QD= 𝑅𝑇
1.845𝑚2 (45−22)
= 0.04445
0.17
QD = 162.3W
30𝑚2 (31−22)
QS= 𝒎𝟐 −𝑲
1.9104
𝑾
Qs=141.33W
30𝑚2 (40−22)
Qc= 𝒎𝟐 −𝑲
0.6
𝑾
Qc =900W
For Windows using conduction:
QW=UA(T2-T1)
𝑚2 −𝑘
=5.9 (1.2m2)(45-22)
𝑊
QW = 162.44W
For appliances:
Material Heat load (W) No. of items Total (W)
Incubator 479 6 2874
Electric Fan 250 3 750
Source:2001 ASHRAE Fundamental Handbook (SI)
Total heat load of appliances = 3624W
48.48+190+278.8+210.9+324.6+162.3+141.3+900+162.44+3624
QTF=5808.43W
G. Partition G( Employee’s Quarter for Girls @ 24℃)
WallG1
𝐴∆𝑇
QG1 = 𝑅𝑇
𝐴∆𝑇
QG1 = 𝑅𝑇
12𝑚2 (45−24)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QG1 =127.27W
Area of WallG2=10.155 m2
𝐴∆𝑇
QG2 = 𝑅𝑇
10.155𝑚2 (45−24)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QG2 =107.7W
For walls:
WallG3
𝐴∆𝑇
QG3 = 𝑅𝑇
𝐴∆𝑇
QG3 = 𝑅𝑇
24𝑚2 (27−24)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QG3 =36.36W
Area of WallG4=15.11m2
𝐴∆𝑇
QG4= 𝑅𝑇
15.11𝑚2 (45−24)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QG4=160.26W
For Doors using conduction:
𝐴∆𝑇
QDD= 𝑅𝑇
3,690𝑚2 (45−24)
= 0.04445
0.17
QDD = 296.03W
30𝑚2 (31−24)
QS= 𝒎𝟐 −𝑲
1.9104
𝑾
Qs=157W
30𝑚2 (40−24)
Qc= 𝒎𝟐 −𝑲
0.6
𝑾
Qc =800W
QW=UA(T2-T1)
𝑚2 −𝑘
=5.9 (1.2m2)(45-24)
𝑊
QW = 148.68W
For appliances:
Material Heat load (W) No. of items Total (W)
Heater 1200 1 1200
Electric Fan 250 3 750
Rice cooker 350 1 350
Toaster 1050 1 1050
Coffee maker 1050 1 1050
TV 420 1 420
Source:2001 ASHRAE Fundamental Handbook (SI)
Total heat load of appliances = 4820W
107.27+127.27+36.36+160.2+296.03+157+800+4820+(148.68x2)
QTG=6801.92W
H. Partition H( Employee’s Quarter for Boys @ 27℃)
WallH1
𝐴∆𝑇
QH1 = 𝑅𝑇
𝐴∆𝑇
QH1 = 𝑅𝑇
12𝑚2 (27−24)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QH1 =18.18W
𝐴∆𝑇
QH2 = 𝑅𝑇
10.2𝑚2 (45−27)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QH2 =92.73W
For walls:
WallH3
𝐴∆𝑇
QH3 = 𝑅𝑇
𝐴∆𝑇
QH3 = 𝑅𝑇
24𝑚2 (28−27)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QH3 =12.12W
Area of WallH4=15.11m2
𝐴∆𝑇
QH4= 𝑅𝑇
15.11𝑚2 (45−27)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QH4=137.36W
For Doors using conduction:
𝐴∆𝑇
QDD= 𝑅𝑇
3,690𝑚2 (45−27)
= 0.04445
0.17
QDD = 254W
30𝑚2 (31−27)
QS= 𝒎𝟐 −𝑲
1.9104
𝑾
Qs=63W
30𝑚2 (40−27)
Qc= 𝒎𝟐 −𝑲
0.6
𝑾
Qc =650W
QW=UA(T2-T1)
𝑚2 −𝑘
=5.9 (1.2m2)(45-27)
𝑊
QW = 127.44W
For appliances:
Material Heat load (W) No. of items Total (W)
Heater 1200 1 1200
Electric Fan 250 3 750
Rice cooker 350 1 350
Toaster 1050 1 1050
Coffee maker 1050 1 1050
TV 420 1 420
Source:2001 ASHRAE Fundamental Handbook (SI)
Total heat load of appliances = 4820W
18.18+92.73+12.12+137.36+254+63+650+127.44+4820
QTH=6174.83W
I. Partition I( Garage for Forklift @ 30℃)
WallI1
𝐴∆𝑇
QI1 = 𝑅𝑇
𝐴∆𝑇
QI1 = 𝑅𝑇
24𝑚2 (28−27)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QI1 =36.36W
𝐴∆𝑇
QI2 = 𝑅𝑇
17.6(45−30)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QI2 =181.11W
For walls:
WallH3
𝐴∆𝑇
QI3 = 𝑅𝑇
𝐴∆𝑇
QI3 = 𝑅𝑇
21.6𝑚2 (45−30)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QI3 =163.36W
= 20m2- [ 4m x 3m ]
𝐴∆𝑇
QI4= 𝑅𝑇
8(45−30)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QI4=60.60W
For flooring @ 31C using conduction:
30𝑚2 (31−30)
QS= 𝒎𝟐 −𝑲
1.9104
𝑾
Qs=15.7W
30𝑚2 (40−30)
Qc= 𝒎𝟐 −𝑲
0.6
𝑾
Qc =500W
QW=UA(T2-T1)
𝑚2 −𝑘
=5.9 (1.2m2)(45-30)
𝑊
QW = 212.4W x 4 windows
QW = 850 W
For Forklift:
Area of forklift = (2.5m x 1.150m)
Area of forklift = 2.875m2
𝐴𝑟𝑒𝑎 𝑜𝑓 𝐺𝑎𝑟𝑎𝑔𝑒
Number of Forklift = 𝐴𝑟𝑒𝑎 𝑜𝑓 𝐹𝑜𝑟𝑘𝑙𝑖𝑓𝑡
30𝑚2
Number of Forklift = 2.875𝑚2 = 10.43
For appliances:
Material Heat load (W) No. of items Total (W)
Forklift 1300* 6 7800
*Assuming that the forklift is parked right after operation
Source: https://www.scribd.com/doc/16676089/Heat-Load-Calculation-Cold-Storage-Plant
Total heat load of appliances = 7800W
36.36+181.11+163.36+60.60+15.7+500+850+7800
QTI=9607W
J. Partition J( Storage of Raw Materials @ 28℃)
WallJ1
𝐴∆𝑇
QJ1 = 𝑅𝑇
𝐴∆𝑇
QJ1 = 𝑅𝑇
26.155𝑚2 (45−28)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QJ1 =224.56W
Area of WallJ2= Area of wall – [(2 x Area of window) – Area of Double Door)
𝐴∆𝑇
QJ2 = 𝑅𝑇
29.91𝑚2 (45−28)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QJ2 =256.806W
For walls:
WallJ3
𝐴∆𝑇
QJ3 = 𝑅𝑇
𝐴∆𝑇
QJ3 = 𝑅𝑇
26.155𝑚2 (45−28)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QJ3 =224.56W
WallJ4
Area of WallJ4= ( 9m x 4m )
Area of WallJ4=36m2
𝐴∆𝑇
QJ4= 𝑅𝑇
36𝑚2 (45−28)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QJ4=309.09W
For Double Doors using conduction:
𝐴∆𝑇
QDD= 𝑅𝑇
3,690𝑚2 (45−28)
= 0.04445
0.17
QDD = 240W
𝐴∆𝑇
QD= 𝑅𝑇
1.845𝑚2 (45−28)
= 0.04445
0.17
QW=UA(T2-T1)
𝑚2 −𝑘
=5.9 𝑊
(1.2m2)(45-28)
QW = 120.36W x 2 windows
QW = 240 W
For flooring @ 31C using conduction:
63𝑚2 (31−28)
QS= 𝒎𝟐 −𝑲
1.9104
𝑾
Qs=99W
63𝑚2 (40−28)
Qc= 𝒎𝟐 −𝑲
0.6
𝑾
Qc =1260W
QWI1+ QWI2+ QWI3+ QWI4+ Qstraw + Qwind+ Qsoil+ Qceil + Qdoor + Qdoubledoor
(224.56+256.806+224.56+309.09+240+240+240+17203)W
QTJ=20300W
Properties of Wheat Straw according to “Heat and Mass Transfer Study During Wheat Straw
Solid Substrate Fermentation with P.ostreatus by C.I. Koncsag and K. Kirwan”
Q=Hc(A)(T2-T1)
𝑊
Q=51.22 𝑚2 −𝐾 x (0.06𝑚2 ) 𝑥 (28-20)C
Q= 24.6W
𝐴𝑟𝑒𝑎 𝑜𝑓 𝑅𝑜𝑜𝑚
Number of bags = 𝐴𝑟𝑒𝑎 𝑝𝑒𝑟 𝑏𝑎𝑔
63𝑚2
Number of bags = 0.06𝑚2 = 1050 bags
Assuming that there are 700 bags for convenience and allowance in the building.
WallK1
𝐴∆𝑇
QK1 = 𝑅𝑇
𝐴∆𝑇
QK1 = 𝑅𝑇
34.155𝑚2 (45−25)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QK1 =345W
WallK2
𝐴∆𝑇
QK2 = 𝑅𝑇
18𝑚2 (25− −1 )
= 𝒎𝟐 −𝑲
3.9
𝑾
QK2 =120W
WallK3
𝐴∆𝑇
QK3 = 𝑅𝑇
Area of WallK3 = 9m x 4m
𝐴∆𝑇
QK3 =
𝑅𝑇
36𝑚2 (30−25)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QK3 =91W
WallK4
Area of WallK4=14.31m2
𝐴∆𝑇
QK4= 𝑅𝑇
14.31𝑚2 (45−25)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QK4=144.5W
For Double Doors using conduction:
𝐴∆𝑇
QDD= 𝑅𝑇
3,690𝑚2 (45−25)
= 0.04445
0.17
QDD = 282.25W
𝐴∆𝑇
QD= 𝑅𝑇
1.845𝑚2 (45−25)
= 0.04445
0.17
QD = 141.12 W
40.5𝑚2 (31−25)
QS= 𝒎𝟐 −𝑲
1.9104
𝑾
Qs=127.2W
40.5𝑚2 (40−28)
Qc= 𝒎𝟐 −𝑲
Qc =1012.5W
0.6
𝑾
Properties of Wheat Straw according to “Heat and Mass Transfer Study During Wheat Straw
Solid Substrate Fermentation with P.ostreatus by C.I. Koncsag and K. Kirwan”
Q=Hc(A)(T2-T1)
𝑊
Q=51.22 𝑚2 −𝐾 x (0.06𝑚2 ) 𝑥 (25-20)C
Q= 15.366W
𝐴𝑟𝑒𝑎 𝑜𝑓 𝑅𝑜𝑜𝑚
Number of bags = 𝐴𝑟𝑒𝑎 𝑝𝑒𝑟 𝑏𝑎𝑔
40.5𝑚2
Number of bags = 0.06𝑚2 = 675 bags
Assuming that there are 350 bags for convenience and allowance in the building.
𝑃𝑜𝑤𝑒𝑟
𝑄= 𝑥 746 𝑥 3.41
𝐸𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦
3.7𝐻𝑝
𝑄= 𝑥 746 𝑥 3.41
0.9
Q = 10,458W
For Fan
𝑃𝑜𝑤𝑒𝑟
𝑄= 𝑥 746 𝑥 3.41
𝐸𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦
0.5𝐻𝑝
𝑄= 𝑥 746 𝑥 3.41
0.8
QWI1+ QWI2+ QWI3+ QWI4+ Qstraw + Qwind+ Qsoil+ Qceil+ Qhumidifier + Qfan
345W+120W+91W+144.5+282.25+141.12W+127.2W+1012.5W+5388W+10458W+3180W
QTK=21279.57W
L. Partition L( Incubation Room @ 30C)
WallL1
𝐴∆𝑇
QL1 = 𝑅𝑇
𝐴∆𝑇
QL1 = 𝑅𝑇
36𝑚2 (30−25)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QL1 =91W
WallL2
𝐴∆𝑇
QL2 = 𝑅𝑇
18𝑚2 (30− −1 )
= 𝒎𝟐 −𝑲
3.9
𝑾
QL2 =143.07W
WallL3
𝐴∆𝑇
QL3 = 𝑅𝑇
𝐴∆𝑇
Ql3 =
𝑅𝑇
34.155𝑚2 (45−30)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QK3 =258.754W
WallL4
Area of WallL4=14.31m2
𝐴∆𝑇
QL4= 𝑅𝑇
14.31𝑚2 (45−25)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QK4=144.5W
For Double Doors using conduction:
𝐴∆𝑇
QDD= 𝑅𝑇
3,690𝑚2 (45−30)
= 0.04445
0.17
QDD = 211.68W
𝐴∆𝑇
QD= 𝑅𝑇
1.845𝑚2 (45−30)
= 0.04445
0.17
QD = 105.84 W
40.5𝑚2 (31−30)
QS= 𝒎𝟐 −𝑲
1.9104
𝑾
Qs=21.2W
40.5𝑚2 (40−30)
Qc= 𝒎𝟐 −𝑲
Qc =675W
0.6
𝑾
Properties of Wheat Straw according to “Heat and Mass Transfer Study During Wheat Straw
Solid Substrate Fermentation with P.ostreatus by C.I. Koncsag and K. Kirwan”
Q=Hc(A)(T2-T1)
𝑊
Q=51.22 𝑚2 −𝐾 x (1.57𝑚2 ) 𝑥 (30-25)C
Q= 402W
𝐴𝑟𝑒𝑎 𝑜𝑓 𝑅𝑜𝑜𝑚
Number of bags = 𝐴𝑟𝑒𝑎 𝑝𝑒𝑟 𝑏𝑎𝑔
40.5𝑚2
Number of bags = 1.57𝑚2 = 25.8 bags
Assuming that there are 13 bags for convenience and allowance in the building.
Qburner=1930W T2=82C
𝐽
CpSteam = 1996𝐾𝑔−𝐾 T1=20C
𝑸 = 𝒎𝑪𝒑∆𝑻
𝑸
𝒎=
𝑪𝒑∆𝑻
𝟏𝟗𝟑𝟎𝑾
𝒎=
𝐽
1996 𝐾𝑔 − 𝐾 (𝟖𝟐 − 𝟐𝟎)
m = 0.0156 kg/s
Computing for the heat released by the steam:
𝐽
CpSteam = 1996𝐾𝑔−𝐾 T1=30C (Room Temperature)
𝑸 = 𝒎𝑪𝒑∆𝑻
𝐽
𝑸 =(0.0156 kg/s) (1996𝐾𝑔−𝐾)(82-30)C
Q = 1619W
QWL1+ QWL2+ QWL3+ QWL4+ Qstraw + Qwind+ Qsoil+ Qceil+ Qburner + QSteam + Q doubledoor+ Q door
91W+143.07W+258.754W+144.5+211.7+106W+21.2W+675W+5226W+1619W
QTL=8500W
M. Partition M (Greenhouse @ 15C)
Fiber Insulation 𝑚2 −𝐾
0.14 𝑊
Source: http://bwgreenhouse.ca/R-valueU-value.html
𝑚2 −𝐾 𝑚2 −𝐾
Rpolyethylene= 2 x 0.3 𝑊
= 0.6
𝑊
𝑚2 −𝐾 𝑚2 −𝐾 𝑚2 −𝐾
RT=0.14 𝑊
+ 0.6
𝑊
+ 0.44
𝑊
Floorboard 20 mm 𝑊
0.021𝑚−𝐾
Source: http://www.homestyler.com/designprofile/028a3fc3-56a3-4353-8181-992b14d95e24
0.1𝑚
Resistance of Concrete = 𝑊
0.4
𝑚−𝐾
𝒎𝟐 −𝑲
Resistance of Concrete = 0.25 𝑾
0.02𝑚
Resistance of Floorboard = 𝑊
0.021
𝑚−𝐾
𝒎𝟐 −𝑲
Resistance of Floorboard = 0.95 𝑾
0.005𝑚
Resistance of White plastic film = 𝑊
0.33
𝑚−𝐾
𝒎𝟐 −𝑲
Resistance of White Plastic Film = 0.015 𝑾
𝒎𝟐 −𝑲 𝒎𝟐 −𝑲 𝒎𝟐 −𝑲
RT = 0.25 + = 0.95 + 0.015
𝑾 𝑾 𝑾
𝒎𝟐 −𝑲
RT = 1.215 𝑾
Fiber Insulation 𝑚2 −𝐾
0.14 𝑊
Reflective Foil 𝑚2 −𝐾
0.625 𝑊
𝑚2 −𝐾 𝑚2 −𝐾 𝑚2 −𝐾
RT= (0.3 X 2) + 0.14 + 0.625
𝑊 𝑊 𝑊
𝒎𝟐 −𝑲
RT = 1.365 𝑾
For walls using conduction
WallM1
𝐴∆𝑇
QM1 = 𝑅𝑇
𝐴∆𝑇
QM1 = 𝑅𝑇
29.63𝑚2 (45−15)
= 𝒎𝟐 −𝑲
1.18
𝑾
QM1 =953.5W
WallM2
𝐴∆𝑇
QM2 = 𝑅𝑇
40𝑚2 (45− 15 )
= 𝒎𝟐 −𝑲
1.18
𝑾
QM2 =1016.95W
WallM3
𝐴∆𝑇
QM3 = 𝑅𝑇
𝐴∆𝑇
QM3 = 𝑅𝑇
33.32𝑚2 (45−15)
= 𝒎𝟐 −𝑲
1.18
𝑾
QM3 =847.12W
WallM4
Area of WallM4=40m2
𝐴∆𝑇
QM4= 𝑅𝑇
40𝑚2 (15−15)
= 𝒎𝟐 −𝑲
1.18
𝑾
QM4=0W
For Double Doors using conduction:
𝒎𝟐 −𝑲
RT = 0.564 , According to “http://greenhousegab.com/consider-the-r-value/”
𝑾
𝐴∆𝑇
QDD= 𝑅𝑇
3,690𝑚2 (45−15)
= 𝒎𝟐 −𝑲
𝟎.𝟓𝟔𝟒
𝑾
QDD = 196.2W
83.3(28−15)
QS= 𝒎𝟐 −𝑲
1.2
𝑾
Qs=902.24W
83.3𝑚2 (40−15)
Qc= 𝒎𝟐 −𝑲
1.365
𝑾
Qc =1525.64W
Properties of Wheat Straw according to “Heat and Mass Transfer Study During Wheat Straw
Solid Substrate Fermentation with P.ostreatus by C.I. Koncsag and K. Kirwan”
Q=Hc(A)(T2-T1)
𝑊
Q=51.22 𝑚2 −𝐾 x (0.06𝑚2 ) 𝑥 (20-15)C
Q= 15.366W
𝐴𝑟𝑒𝑎 𝑜𝑓 𝑅𝑜𝑜𝑚
Number of bags = 𝐴𝑟𝑒𝑎 𝑝𝑒𝑟 𝑏𝑎𝑔
83.3𝑚2
Number of bags = 0.06𝑚2 = 1390 bags
Assuming that there are 750 bags for convenience and allowance in the building.
𝑃𝑜𝑤𝑒𝑟
𝑄= 𝑥 746 𝑥 3.41
𝐸𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦
3.7𝐻𝑝
𝑄= 𝑥 746 𝑥 3.41
0.9
Q = 10,458W
For Fan
𝑃𝑜𝑤𝑒𝑟
𝑄= 𝑥 746 𝑥 3.41
𝐸𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦
0.5𝐻𝑝
𝑄= 𝑥 746 𝑥 3.41
0.8
953.5W+1016.95W+847.12W+0W+196.2W+902.24W+1525.64W+1152W+10458W+3180W
QTM=20231.65W
N. Partition N(Greenhouse @ 15C)
Fiber Insulation 𝑚2 −𝐾
0.14 𝑊
Source: http://bwgreenhouse.ca/R-valueU-value.html
𝑚2 −𝐾 𝑚2 −𝐾
Rpolyethylene= 2 x 0.3 𝑊
= 0.6
𝑊
𝑚2 −𝐾 𝑚2 −𝐾 𝑚2 −𝐾
RT=0.14 𝑊
+ 0.6
𝑊
+ 0.44
𝑊
Floorboard 20 mm 𝑊
0.021𝑚−𝐾
Source: http://www.homestyler.com/designprofile/028a3fc3-56a3-4353-8181-992b14d95e24
0.1𝑚
Resistance of Concrete = 𝑊
0.4
𝑚−𝐾
𝒎𝟐 −𝑲
Resistance of Concrete = 0.25 𝑾
0.02𝑚
Resistance of Floorboard = 𝑊
0.021
𝑚−𝐾
𝒎𝟐 −𝑲
Resistance of Floorboard = 0.95 𝑾
0.005𝑚
Resistance of White plastic film = 𝑊
0.33
𝑚−𝐾
𝒎𝟐 −𝑲
Resistance of White Plastic Film = 0.015 𝑾
𝒎𝟐 −𝑲 𝒎𝟐 −𝑲 𝒎𝟐 −𝑲
RT = 0.25 + = 0.95 + 0.015
𝑾 𝑾 𝑾
𝒎𝟐 −𝑲
RT = 1.215 𝑾
Fiber Insulation 𝑚2 −𝐾
0.14 𝑊
Reflective Foil 𝑚2 −𝐾
0.625 𝑊
𝑚2 −𝐾 𝑚2 −𝐾 𝑚2 −𝐾
RT= (0.3 X 2) + 0.14 + 0.625
𝑊 𝑊 𝑊
𝒎𝟐 −𝑲
RT = 1.365 𝑾
For walls using conduction
WallN1
𝐴∆𝑇
QN1 = 𝑅𝑇
𝐴∆𝑇
QN1 = 𝑅𝑇
29.63𝑚2 (45−15)
= 𝒎𝟐 −𝑲
1.18
𝑾
QN1 =953.5W
WallN2
𝐴∆𝑇
QN2 = 𝑅𝑇
40𝑚2 (15− 15 )
= 𝒎𝟐 −𝑲
1.18
𝑾
QN2 =0W
WallN3
𝐴∆𝑇
QN3 = 𝑅𝑇
𝐴∆𝑇
QN3 =
𝑅𝑇
33.32𝑚2 (45−15)
= 𝒎𝟐 −𝑲
1.18
𝑾
QN3 =847.12W
WallN4
Area of WallN4=40m2
𝐴∆𝑇
QN4= 𝑅𝑇
40𝑚2 (15−15)
= 𝒎𝟐 −𝑲
1.18
𝑾
QN4=0W
For Double Doors using conduction:
𝒎𝟐 −𝑲
RT = 0.564 , According to “http://greenhousegab.com/consider-the-r-value/”
𝑾
𝐴∆𝑇
QDD= 𝑅𝑇
3,690𝑚2 (45−15)
= 𝒎𝟐 −𝑲
𝟎.𝟓𝟔𝟒
𝑾
QDD = 196.2W
83.3(28−15)
QS= 𝒎𝟐 −𝑲
1.2
𝑾
Qs=902.24W
83.3𝑚2 (40−15)
Qc= 𝒎𝟐 −𝑲
1.365
𝑾
Qc =1525.64W
Properties of Wheat Straw according to “Heat and Mass Transfer Study During Wheat Straw
Solid Substrate Fermentation with P.ostreatus by C.I. Koncsag and K. Kirwan”
Q=Hc(A)(T2-T1)
𝑊
Q=51.22 𝑚2 −𝐾 x (0.06𝑚2 ) 𝑥 (20-15)C
Q= 15.366W
𝐴𝑟𝑒𝑎 𝑜𝑓 𝑅𝑜𝑜𝑚
Number of bags = 𝐴𝑟𝑒𝑎 𝑝𝑒𝑟 𝑏𝑎𝑔
83.3𝑚2
Number of bags = 0.06𝑚2 = 1390 bags
Assuming that there are 750 bags for convenience and allowance in the building.
𝑃𝑜𝑤𝑒𝑟
𝑄= 𝑥 746 𝑥 3.41
𝐸𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦
3.7𝐻𝑝
𝑄= 𝑥 746 𝑥 3.41
0.9
Q = 10,458W
For Fan
𝑃𝑜𝑤𝑒𝑟
𝑄= 𝑥 746 𝑥 3.41
𝐸𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦
0.5𝐻𝑝
𝑄= 𝑥 746 𝑥 3.41
0.8
953.5W+0W+847.12W+0W+196.2W+902.24W+1525.64W+1152W+10458W+3180W
QTN=19214.7W
O. Partition O (Greenhouse @ 15C)
Fiber Insulation 𝑚2 −𝐾
0.14 𝑊
Source: http://bwgreenhouse.ca/R-valueU-value.html
𝑚2 −𝐾 𝑚2 −𝐾
Rpolyethylene= 2 x 0.3 𝑊
= 0.6
𝑊
𝑚2 −𝐾 𝑚2 −𝐾 𝑚2 −𝐾
RT=0.14 𝑊
+ 0.6
𝑊
+ 0.44
𝑊
Floorboard 20 mm 𝑊
0.021𝑚−𝐾
Source: http://www.homestyler.com/designprofile/028a3fc3-56a3-4353-8181-992b14d95e24
0.1𝑚
Resistance of Concrete = 𝑊
0.4
𝑚−𝐾
𝒎𝟐 −𝑲
Resistance of Concrete = 0.25 𝑾
0.02𝑚
Resistance of Floorboard = 𝑊
0.021
𝑚−𝐾
𝒎𝟐 −𝑲
Resistance of Floorboard = 0.95 𝑾
0.005𝑚
Resistance of White plastic film = 𝑊
0.33
𝑚−𝐾
𝒎𝟐 −𝑲
Resistance of White Plastic Film = 0.015 𝑾
𝒎𝟐 −𝑲 𝒎𝟐 −𝑲 𝒎𝟐 −𝑲
RT = 0.25 + = 0.95 + 0.015
𝑾 𝑾 𝑾
𝒎𝟐 −𝑲
RT = 1.215 𝑾
Fiber Insulation 𝑚2 −𝐾
0.14 𝑊
Reflective Foil 𝑚2 −𝐾
0.625 𝑊
𝑚2 −𝐾 𝑚2 −𝐾 𝑚2 −𝐾
RT= (0.3 X 2) + 0.14 + 0.625
𝑊 𝑊 𝑊
𝒎𝟐 −𝑲
RT = 1.365 𝑾
For walls using conduction
WallO1
𝐴∆𝑇
QO1 = 𝑅𝑇
𝐴∆𝑇
QO1 = 𝑅𝑇
29.63𝑚2 (45−15)
= 𝒎𝟐 −𝑲
1.18
𝑾
QO1 =953.5W
WallO2
𝐴∆𝑇
QO2 = 𝑅𝑇
40𝑚2 (15− 15 )
= 𝒎𝟐 −𝑲
1.18
𝑾
QO2 =0W
WallO3
𝐴∆𝑇
QO3 = 𝑅𝑇
𝐴∆𝑇
QO3 = 𝑅𝑇
33.32𝑚2 (45−15)
= 𝒎𝟐 −𝑲
1.18
𝑾
QO3 =847.12W
WallO4
Area of WallO4=40m2
𝐴∆𝑇
QO4= 𝑅𝑇
40𝑚2 (45−15)
= 𝒎𝟐 −𝑲
1.18
𝑾
QO4=1016.9W
For Double Doors using conduction:
𝒎𝟐 −𝑲
RT = 0.564 , According to “http://greenhousegab.com/consider-the-r-value/”
𝑾
𝐴∆𝑇
QDD= 𝑅𝑇
3,690𝑚2 (45−15)
= 𝒎𝟐 −𝑲
𝟎.𝟓𝟔𝟒
𝑾
QDD = 196.2W
83.3(28−15)
QS= 𝒎𝟐 −𝑲
1.2
𝑾
Qs=902.24W
83.3𝑚2 (40−15)
Qc= 𝒎𝟐 −𝑲
1.365
𝑾
Qc =1525.64W
Properties of Wheat Straw according to “Heat and Mass Transfer Study During Wheat Straw
Solid Substrate Fermentation with P.ostreatus by C.I. Koncsag and K. Kirwan”
Q=Hc(A)(T2-T1)
𝑊
Q=51.22 𝑚2 −𝐾 x (0.06𝑚2 ) 𝑥 (20-15)C
Q= 15.366W
𝐴𝑟𝑒𝑎 𝑜𝑓 𝑅𝑜𝑜𝑚
Number of bags = 𝐴𝑟𝑒𝑎 𝑝𝑒𝑟 𝑏𝑎𝑔
83.3𝑚2
Number of bags = 0.06𝑚2 = 1390 bags
Assuming that there are 750 bags for convenience and allowance in the building.
𝑃𝑜𝑤𝑒𝑟
𝑄= 𝑥 746 𝑥 3.41
𝐸𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦
3.7𝐻𝑝
𝑄= 𝑥 746 𝑥 3.41
0.9
Q = 10,458W
For Fan
𝑃𝑜𝑤𝑒𝑟
𝑄= 𝑥 746 𝑥 3.41
𝐸𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦
0.5𝐻𝑝
𝑄= 𝑥 746 𝑥 3.41
0.8
953.5W+1016.95W+847.12W+0W+196.2W+902.24W+1525.64W+1152W+10458W+3180W
QTO=20231.65W
P. Partition P (Cold Storage @ -1C)
Image from“https://archive.lib.msu.edu/DMC/Ag.%20Ext.%202007-Chelsie/PDF/e1914-ND.pdf”
Concrete Block 𝑚2 −𝐾
0.195 𝑊
Polyutherane 𝑚2 −𝐾
3.3 𝑊
Gypsum 𝑚2 −𝐾
0.058 𝑊
https://archive.lib.msu.edu/DMC/Ag.%20Ext.%202007-Chelsie/PDF/e1914-ND.pdf
𝑚2 −𝐾 𝑚2 −𝐾 𝑚2 −𝐾 𝑚2 −𝐾 𝑚2 −𝐾
R T= 0.044 𝑊
+ 0.195𝑊
+ 3.3 𝑊
+ 0.058 𝑊
+ 0.3𝑊
𝒎𝟐 −𝑲
RT = 3.9 𝑾
Image from “https://archive.lib.msu.edu/DMC/Ag.%20Ext.%202007-Chelsie/PDF/e1914-ND.pdf”
Concrete Block 𝑚2 −𝐾
0.1016 𝑊
Subfloor Insulation 𝑚2 −𝐾
1.76 𝑊
Polyethylene 𝑚2 −𝐾
0.3 𝑊
https://archive.lib.msu.edu/DMC/Ag.%20Ext.%202007-Chelsie/PDF/e1914-ND.pdf
𝑚2 −𝐾 𝑚2 −𝐾 𝑚2 −𝐾 𝑚2 −𝐾
RT= 0.3 𝑊
+ 0.1016 𝑊
+ 1.76 𝑊
+ 0.3 𝑊
𝑚2 −𝐾
RT = 2.4616 𝑊
Cold Storage Ceiling Composition
Concrete Block 𝑚2 −𝐾
0.195 𝑊
Polyutherane 𝑚2 −𝐾
3.3 𝑊
Gypsum 𝑚2 −𝐾
0.058 𝑊
Polyethylene 𝑚2 −𝐾
0.3 𝑊
https://archive.lib.msu.edu/DMC/Ag.%20Ext.%202007-Chelsie/PDF/e1914-ND.pdf
𝑚2 −𝐾 𝑚2 −𝐾 𝑚2 −𝐾 𝑚2 −𝐾 𝑚2 −𝐾 𝑚2 −𝐾
RT = 0.044 𝑊
+ 0.195 + 3.3 + 0.058 + 0.3 + 0.3
𝑊 𝑊 𝑊 𝑊 𝑊
𝑚2 −𝐾
RT = 4.2 𝑊
For walls using conduction
WallP1
𝐴∆𝑇
QP1 = 𝑅𝑇
𝐴∆𝑇
QP1 = 𝑅𝑇
14𝑚2 (45−−1)
= 𝒎𝟐 −𝑲
3.9
𝑾
QP1 =165W
WallP2
𝐴∆𝑇
QP2 = 𝑅𝑇
36𝑚2 (45− −1 )
= 𝒎𝟐 −𝑲
3.9
𝑾
QP2 =424.6W
WallP3
𝐴∆𝑇
QP3 = 𝑅𝑇
𝐴∆𝑇
QP3 =
𝑅𝑇
14𝑚2 (45−−1)
= 𝒎𝟐 −𝑲
3.9
𝑾
QP3 =165.13W
WallP4.1
Area of WallP4.1=18m2
𝐴∆𝑇
QP4= 𝑅𝑇
18𝑚2 (30−−1)
= 𝒎𝟐 −𝑲
3.9
𝑾
QP4.1=143W
WallP4.2
Area of WallP4.2=18m2
𝐴∆𝑇
QP4.2= 𝑅𝑇
18𝑚2 (25−−1)
= 𝒎𝟐 −𝑲
3.9
𝑾
QP4.2=120W
Using double door Mark IV™ Bi-Parting Horizontal Sliding Manually Operated
Door R-28,
𝒎𝟐 −𝑲
RT = 28 , According to “http://greenhousegab.com/consider-the-r-value/”
𝑾
𝐴∆𝑇
QDD= 𝑅𝑇
10𝑚2 (45−−1)
= 𝒎𝟐 −𝑲
𝟓
𝑾
QDD = 92W
For flooring @ 20C using conduction:
54𝑚2 (20−−1)
QS= 𝒎𝟐 −𝑲
2.4616
𝑾
Qs=460.68W
54𝑚2 (30−−1)
Qc= 𝒎𝟐 −𝑲
4.2
𝑾
Qc =400W
165W+424.6W+165.13W+143W+120W+92W+460.68W+400W
Storage size 9m x 6m x 4m
𝐽 1𝑘𝐽
1970.41 x 𝑥 3600s x 24
𝑠 1000𝐽
=977012.4kJ/24hrs
Bin weight during loading x Specific heat of bin x TD x kJ factor for 24hrs
Bin weight (200 bins)(10.5kg/bin)
𝑘𝐽
(2100 kg) x (0.5𝑘𝑔−𝐾) x (20-5) x (4.186)
= 65929.5 kJ/24hr
During Second day [Temperature Difference (TD) = 5C-(-1C)]
Fruit weight during loading x Specific heat of mushroom x TD x kJ factor for 24hrs
Fruit weight = (200 bins) (20kg/bin)
𝑘𝐽
(4000kg) x (3.89 𝑘𝑔−𝐾) 𝑥 (5C--1C) x (4.186)
=390804.96kJ/24hrs
Bin weight during loading x Specific heat of bin x TD x kJ factor for 24hrs
Bin weight (200 bins)(10.5kg/bin)
𝑘𝐽
(2100 kg) x (0.5𝑘𝑔−𝐾) x (5C- -1C) x (4.186)
= 26371.8kJ/24hrs
Reference: https://www.scribd.com/doc/16676089/Heat-Load-Calculation-Cold-Storage-Plant
Q. Comfort Rooms
For Comfort Room A @ 25C
For walls using conduction:
WallA1
𝐴∆𝑇
QA1 = 𝑅𝑇
Area of WallA1=11.76m2
𝐴∆𝑇
QA1 = 𝑅𝑇
11.76𝑚2 (45−25)𝐾
= 𝑚2 −𝐾
1.97997
𝑊
QA1 =118.78W
Area of WallA2= 3m x 3m
𝐴∆𝑇
QA2 = 𝑅𝑇
12𝑚2 (45−25)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QA2 =121.21W
For walls:
WallA3
𝐴∆𝑇
QA3 = 𝑅𝑇
Area of WallA3.1= 4m x 3m
𝐴∆𝑇
QA3 = 𝑅𝑇
12𝑚2 (25−24)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QA3 =6.06W
WallA4
𝐴∆𝑇
QA4 = 𝑅𝑇
= 12m2 – [1.854m2]
𝐴∆𝑇
QA4 = 𝑅𝑇
10.155𝑚2 (25−24)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QA4 =5.13W
For Doors using conduction:
𝐴∆𝑇
QD= 𝑅𝑇
1.845𝑚2 (25−24)
= 0.04445
0.17
QD = 7.05W
QW=UA(T2-T1)
𝑚2 −𝑘
=5.9 x 0.24 m2 x (45-25)
𝑊
QW =28.32W
9𝑚2 (28−25)
QS= 𝒎𝟐 −𝑲
1.9104
𝑾
Qs=14.133W
9𝑚2 (35−25)
Qc= 𝒎𝟐 −𝑲
= 150W
0.6
𝑾
For Comfort Room G @ 25C
For walls using conduction:
WallG1
𝐴∆𝑇
QG1 = 𝑅𝑇
Area of WallG1=11.76m2
𝐴∆𝑇
QG1 = 𝑅𝑇
11.76𝑚2 (45−25)𝐾
= 𝑚2 −𝐾
1.97997
𝑊
QG1 =118.79W
Area of WallG2= 4m x 2m
Area of WallG2 =8 m2
𝐴∆𝑇
QG2 = 𝑅𝑇
8𝑚2 (45−25)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QG2 =80.80W
For walls:
WallG3
𝐴∆𝑇
QG3 = 𝑅𝑇
Area of WallG3= 4m x 3m
𝐴∆𝑇
QG3 = 𝑅𝑇
12𝑚2 (25−24)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QG3 =6.06W
WallG4
𝐴∆𝑇
QG4 = 𝑅𝑇
= 8m2 – [1.854m2]
𝐴∆𝑇
QG4 = 𝑅𝑇
6.155𝑚2 (25−24)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QG4 =3.13W
For Doors using conduction:
𝐴∆𝑇
QD= 𝑅𝑇
1.845𝑚2 (25−24)
= 0.04445
0.17
QD = 7.05W
QW=UA(T2-T1)
𝑚2 −𝑘
=5.9 x 0.24 m2 x (45-25)
𝑊
QW =28.32W
9𝑚2 (28−25)
QS= 𝒎𝟐 −𝑲
1.9104
𝑾
Qs=14.133W
9𝑚2 (35−25)
Qc= 𝒎𝟐 −𝑲
= 150W
0.6
𝑾
For Comfort Room H@ 25C
For walls using conduction:
WallH1
𝐴∆𝑇
QH1 = 𝑅𝑇
Area of WallH1=11.76m2
𝐴∆𝑇
QH1 = 𝑅𝑇
11.76𝑚2 (45−25)𝐾
= 𝑚2 −𝐾
1.97997
𝑊
QH1 =118.79W
Area of WallH2= 4m x 2m
Area of WallH2 =8 m2
𝐴∆𝑇
QH2 = 𝑅𝑇
8𝑚2 (45−25)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QH2 =80.80W
For walls:
WallH3
𝐴∆𝑇
QH3 = 𝑅𝑇
Area of WallH3= 4m x 3m
𝐴∆𝑇
QH3 = 𝑅𝑇
12𝑚2 (27−25)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QH3 =12.12W
WallH4
𝐴∆𝑇
QH4 = 𝑅𝑇
= 8m2 – [1.854m2]
𝐴∆𝑇
QH4 = 𝑅𝑇
6.155𝑚2 (27−25)
= 𝒎𝟐 −𝑲
1.97997
𝑾
QH4 =6.2W
For Doors using conduction:
𝐴∆𝑇
QD= 𝑅𝑇
1.845𝑚2 (27−25)
= 0.04445
0.17
QD = 14.11W
QW=UA(T2-T1)
𝑚2 −𝑘
=5.9 x 0.24 m2 x (45-25)
𝑊
QW =28.32W
9𝑚2 (28−25)
QS= 𝒎𝟐 −𝑲
1.9104
𝑾
Qs=14.133W
9𝑚2 (35−25)
Qc= 𝒎𝟐 −𝑲
= 150W
0.6
𝑾
Total Heat Load for Comfort Rooms:
R. Lighting
CLF = cooling load factor from Table 4-6 from Refrigeration and Air-conditioning by
Stoecker and Jones.
𝐿𝑢𝑚𝑒𝑛𝑠
Total Watt per Room =100 𝑙𝑢𝑚𝑒𝑛𝑠 𝑝𝑒𝑟 𝑤𝑎𝑡𝑡
For Room A
Lumens = 250 x 81 m2
20250
Total Watt per Room =100 𝑙𝑢𝑚𝑒𝑛𝑠 𝑝𝑒𝑟 𝑤𝑎𝑡𝑡
202.5𝑊
Number of lights = = 6 lights
32𝑊
For Room B
Lumens = 500 x 36 m2
18000𝑊
Total Watt per Room =100 𝑙𝑢𝑚𝑒𝑛𝑠 𝑝𝑒𝑟 𝑤𝑎𝑡𝑡
180𝑊
Number of lights = = 6 lights
32𝑊
For Room C
Lumens = 250 x 36 m2
9000
Total Watt per Room =100 𝑙𝑢𝑚𝑒𝑛𝑠 𝑝𝑒𝑟 𝑤𝑎𝑡𝑡
90𝑊
Number of lights = 32𝑊 = 3 lights
For Room D
Lumens = 1000 x 30 m2
30000
Total Watt per Room =100 𝑙𝑢𝑚𝑒𝑛𝑠 𝑝𝑒𝑟 𝑤𝑎𝑡𝑡
300𝑊
Number of lights = = 9 lights
32𝑊
Lumens = 500 x 30 m2
150000
Total Watt per Room =100 𝑙𝑢𝑚𝑒𝑛𝑠 𝑝𝑒𝑟 𝑤𝑎𝑡𝑡
150𝑊
Number of lights = = 5 lights x 2 = 10 lights
32𝑊
For Room G to I
Lumens = 250 x 30 m2
7500
Total Watt per Room =100 𝑙𝑢𝑚𝑒𝑛𝑠 𝑝𝑒𝑟 𝑤𝑎𝑡𝑡
75𝑊
Number of lights = 32𝑊 = 2 lights x 3= 6 lights
For Room J
Lumens = 150 x 63 m2
9450
Total Watt per Room =100 𝑙𝑢𝑚𝑒𝑛𝑠 𝑝𝑒𝑟 𝑤𝑎𝑡𝑡
94.5𝑊
Number of lights = = 3 lights
32𝑊
20250
Total Watt per Room =100 𝑙𝑢𝑚𝑒𝑛𝑠 𝑝𝑒𝑟 𝑤𝑎𝑡𝑡
202.5𝑊
Number of lights = = 6 lights x 2 = 12 lights
32𝑊
For Room M to O
12500
Total Watt per Room =100 𝑙𝑢𝑚𝑒𝑛𝑠 𝑝𝑒𝑟 𝑤𝑎𝑡𝑡
125𝑊
Number of lights = = 4 lights x 3 = 12 lights
32𝑊
For Room P
Lumens = 150 x 54 m2
8100
Total Watt per Room =100 𝑙𝑢𝑚𝑒𝑛𝑠 𝑝𝑒𝑟 𝑤𝑎𝑡𝑡
81𝑊
Number of lights = 32𝑊 = 3 lights
Total Number of lights = 6+6+3+9+10+6+3+12+12+3 = 70 lights
𝑸 = 𝟑𝟐𝑾 𝒙 𝟏. 𝟎 𝒙 𝟏. 𝟐 𝒙 𝟕𝟎
Qlights= 2688W
S. Occupancy
1000𝑚2
Total number of person: 15 𝑚2
Assuming that every person work and each occupies 15m2 and industrial working that has
450W of heat gain and 35% sensible heat gain Refrigeration and Air-conditioning by
Stoecker and Jones.
Total Heat Load for the 1000 m2 Oyster Mushroom Farm: 223,916.16W