You are on page 1of 33

Electrical Engineering Sizing Calculation PRE : SPS

S.NO A) Bill of quantity

1 Power Cable Qty Including different Sizes of cables in m,Gland,Lugs


Termination Kits,etc

2 Steel Qty Including Vertical & Horizontal Support,Base frame,etc

3 Tray Qty Including 2.5m length,2mm thick prefabricated 


trays for tray size wise

Tray types
a) Ladder type tray
b) Perforated tray (100,75mm)
c) Connection   -  Coupler Plate

Safe Load of Trays


250Kg/m  = 1000,750mm trays
200Kg/m  = 600,450,300mm trays
150Kg/m  = 100,75mm trays

3 Lighting Qty Including Lighting trafos, DB,Lighting fixture type


cables,Glands,Junction boxes,GI pipe,Conduit,etc

4 Earthing Qty Including Earth flats, earthing cables, earth pits 


and accessorie setc

5 Lightning Qty Including Lightening arrester spikes, down comer strip, 


clamps, test links, earthing rods, supports etc.

6 LPB Qty a) 7.5kw & above with Ammeter for DOL/HDOL/RDOL feeders


b) Below 7.5kW without Ammeter for DOL/HDOL/RDOL feeders

7 EPB Qty For Bucket elevator,Beltconveyors only

B) Documents

1 Feeder list HT,LT(PCC&MCC wise)


a) HT - Above 200kW for different Voltage levels
b) LT - 75KW to 200kW Considered for 415V PCC
c) LT - Up to 75KW Considered for 415V MCC

2 Power cable schedule HT,LT(PCC&MCC wise)


a) Considered above 75kW ,3Cx2.5sq.mm Space Heater cables
b) P & V Cables 3Cx2.5sq.mm for Centrifugal Fan,pump,
Top motors 
c) Considered Miscelenious cables for MCC to VFD Panel,
VFD Panel to Motor

3 Technical Spec. HT,LT Equipments,etc

4 Erection & Supply Tender Including all quantities,Panels,Transformers etc.

calculation.xls Electrical Cal 1 of 33
Electrical Engineering Sizing Calculation PRE : SPS

C) Sizing Calculation

1 Transformer Sizing Define


      Trafo is a static device,it transfers power from one ckt to 
another ckt with out changing frequency & with change
of voltage level.
Principle Faraday's law of electromagnetic induction.
Trafo Rating in KVA
Cu Loss of a trafo depends on current & Iron loss on voltage.
Hence total trafo loss on VA.That is trafo rating is KVA.

Data (Power& Distribution transformers)


Connected load (KW)   
Standards Load factor(LF)  (LF is a Average loading of Motor)
Diversity factor(DF) (DF is a Simultaneous running of Motor)
Power trafo - IS 2026(1977) PF & Efficiency
Dist.trafo - 1180(1974) a) Sizes = (KW x LF x DF) / (PF x Eff)
Trafo oil - IS 335 b) Adding 20% for future
CT - IS 2705
Bushing - IS 2099 Tests
Installation & maintanance - IS 1886 1 Oil test
Fitting & Accessory - IS 3639 2 Installation Resistance test
Loading of oil immersed - IS 6600 3 Polarity & Phasing out
On load tap changer - IS 8648
Core
1 Cold rolled grain oriented silicon steel.
Ideal Trafo: 2 This core gives very low specific power loss at
* No losses operating flux densities.
* No winding resistance
* No leakage flows Winding
Windings are made from paper insulated cu 
Parallel operation of Trafo: conductor.which are transposed at regular intervals
throuh out the winding for ensuring equal flux linkage
1ph Trafo and equal current distribution between strands.
* Plority must be same otherwise heavy short ckt occure in the ckt.
* Voltage ratio must be same.
* Impedence are per unit impedence must be same. Auto trafo
* Winding resistance to reactance are same. One wdg only used it is common to both
3Ph Trafo py & sy.In this trafo py & sy are not
* with includes above 1ph trafo points also electrically isolated from each other.
*  Phase sequence must be identical. uses:
* Same vector group & same type of trafo used. * control equipment for 1ph & 3ph 
electrical locomotives
* It gives upto 50 to 60% of full voltage
to an Induction Motor during starting.

2 Cable Sizing HT & LT Cable sizing

Cable selection is essential in order to select the Size of 
Standards Cable, which is used to carry the power without
interruption of service to consumers.Selection of the cables
IS 7098(Part 2) mainly depends on various current that may flow on the
IEC 60502 fault conditions. Cables are used to transfer the
BS 6622 power from one place to other place.

I) Technical requirements
Cable laying & Install 1) Factors to be considered for cable selection :
IS 1255(84) a) Maximum operating voltage (V),Current loading(I)
b) Type of load P(Trafos,motors,lightings etc) ,Power factor (PF)
PVC Al - IS 1554 c) Voltage drop or VoltageRegulation
XLPE Al - IS 7098 d) Ambient Temperature
e) Length of the cable (L) in Meter
f) Short circuit current
Cable types g) Derating factor (DF) (Cooling Effect) Heat disipating factor
A2XFY h) Physical and Chemical properties of soil
A - Al.Conductor
2X - XLPE insulation Cable Details
F - Flat strip Ar.steel No of Cores           : Single & Three
Y - PVC outer sheath Conductor Material   : Copper / Aluminium
Type of Insulation    : XLPE / PVC
AYFY(Al. PVC cable) Type of Inner sheath : PVC wraped / PVC extruded

calculation.xls Electrical Cal 2 of 33
Electrical Engineering Sizing Calculation PRE : SPS

A - Al.Conductor Type of Outer sheath : PVC / Flame retardent


Y - PVC insulation Zero Halagen(LSOH)
F - Flat strip Ar.steel Type of armour : Un armoured / wire armoured
Y - PVC outer sheath Strip armoured
Armour
YWY(cu PVC cable)   Armour Cables generally galvanized steel wire (or) Strip wire 
Y - Cu.Conductor armouring over the inner sheath in multicore cables &
W - Round wire Ar.steel over the insulation in single core cable.
Y - PVC outer sheath
2) Installation requirements
a) Duct,trays,in the air of tunnels
b) Direct burial under ground
c) Conduit banksunder ground banks or in air

3) Economic requirements
a) Splices
b) Tetminations & connectors

II) Operating conditions


a) Nominal voltage of the system(U)
b) Highest voltage of the system(Um)
c) System frequency
d) Type of earthing
e) Outdor terminals are specified,the altitude above sea level
f) Max rated current for continuous operation
g) Short ckt current and time

III) Cable selection process


a) Selection of cables based on planned application & installation
b) Selection of Conductor size based on ampacity.
c) If necessary,Increasing cable size based on Voltage regulation
d) If necessary,Increasing cable size based on fault currents
e) Selection of metallic shield size for cables based on ground 
fault currents

Calculation Steps
a) Full load current (I)              =  P / (1.732 x V x P.F) 
b) Current carriying capacity    = FLC / DF
c) To refer  cable catelouge choose the cable sizes
d) Selected cable sizes to take R,X Values, & Z = √R^2 + X^2
In Starting 15% e) Voltage drop  = (1.732 x 6 x I x Z x L)/1000 Starting
Voltage drop allowable f) Voltage drop  = (1.732 x I x Z x L)/1000 Running
f) %Voltage drop  = (Voltage drop / Voltage) x 100
In Running 3% g) Power loss(Kw)  = (3 x I^2 x R x L)/1000/1000
Voltage drop allowable h) % of Power loss  = (Power loss/Actual Power) x100

IV) Installation Data


Length and profile of route
Details of laying arrangements (flat or trefoil)

Tests 1) Underground cables


1)Routine test a) Details of installation such as direct burrial,in ducts etc.
Conductor Resistance test And type of armour, type of over all jacket such as 
Partial discharge test anti corrosion,flame retarding,anti terminate.
High voltage test b) Depth of laying
c) Thermal resistivity and soil
2)Type test d) Min , Max & average ground temp at depth of burial
High voltage test at  e) Other load carrying cables or other heat sources
        power frequency. f) Length of troughs,ducts or pipe lines
Test for armour wires f) No of ducts or pipes
Physical test for  g) Internal dia of ducts or pipes
                 insulation. h) Spacing bw individual ducts or pipes,if more than one
Dielectric PF Test i) Material of ducts or pipes
 (Applicable for 
6.6KV/11 KV & above) 2) Cables in Air
etc., a) Min , Max & average ambient air temp to be assumed
b) Details of ventillation for cables indoors or in tunnels
Star c) whether exposed to direct sunlight
Line voltage = 3ph volt
Line current = ph current Cables in Water
3) Individual installation require specific consideration.

calculation.xls Electrical Cal 3 of 33
Electrical Engineering Sizing Calculation PRE : SPS

Star
Line voltage = ph volt Power cable types & application
Line current = 3ph current a) In general,Single conductor cables are easy to handle,splices,
terminate and are supplied in longer lengths than 
three conductor cables.
b) Reactance is higher than three conductor cables and use of 
metallic sheath for mechanical protection would be more 
expensive and result in higher losses than 3 conductor cables.
c) Ampacity & voltage drop will be higher for three 1 conductor 
cables compared with a similar size of three conductor cable.

3 Earthing Cal.
Purposes
Standards The object of earthing is to limit the potential b/w the 
non current carrying parts of all electrical apparatus
IS 3043(1987) (or) The installation b/w these parts and earth to safe value 
Earthing trafo - 3151(1982) under all conditions of normal & abnormal system operation.
IEEE-80
Indu.Earthing IEEE-142 NGR
Indian Electricity Rules Sheet metal enclosure & shall be naturally ventilaed.
IS 1956 The resistor shall be of unbrakable ,Corrosion proof jointless,
Earthing Installation stainless steel grids.
no:6.51 - 84 The NGR shall be rated to withstand the fault current for 10Sec.
Firing Plate no:7-51-0103
Pipe electrode no:7-51-102 Step Potentional
The max value of the potential difference possible of being 
shunted by a human body b/w 2 accessible points on the
Types ground seperated by the distance of one pace which may be
System Earthing assumed to be 1m.
Equipment grounding
Touch Potentional
The max value of the potential difference b/w a point on the
ground and a point on an object likely to carry fault current 
such that the points can be touched by a person.

Objective
1 To design the Size of main earth grid conductor.
2 To design auxiliary earth conductor for HT/LT equipment.
3 To design the earthing conductor for transformer 
Body and Neutral.
To check whether net resistance of earthing system is 
less than one ohms.
5 To Calculate the No. Of Earth Pits Required.

Input Data
Soil Resistivety (r)
Length of the Electrode (L1)     
Diameter of the electrode (d)                 
Estimated Length Strip (L2)      
Width of the Buried Strip  (t)      
Depth of the Buried Strip (W)   
Fault current duration for conductor        : 1 Sec 

Sizing of Earth strip:


The Transformer body should withstand the highest fault  
current among the HT side or LT side.Considering the LT
earthing system should withstand  highest fault current
50KA for 1sec
The earthing conductor required S = I x √t / k
Where, 
S  = cross-section Area in Sq.mm
I    =  Fault current in Amps 
K  =  Factor dependent on material of protective 
        conductor and duration / sec.
K  =  80 for GI & 205 for CI

calculation.xls Electrical Cal 4 of 33
Electrical Engineering Sizing Calculation PRE : SPS

Calculation of net Resistance


a) Resistance for Earth Electrode  Re= 100r Log e (4L1/d)
                 2*3.14* L1

b) Resistance of the Buried Earth Strip 

RS  =   100p Log e (2L2^2/wt)) 
                  2*3.14* L2
Types of electrodes
GI Pipe electrode c) Net Resistance of earthing grid          RT  =    Re x RS
Pipe or Plate electrode                    Re + RS 
3
CI Pipe electrode Max Current density I  = 7.57 x 10 A / m2
√p x t
Earth Electrode t  = Duration of earth fault in Sec
A metal plate,pipe or other  p = Resistivity of soil in ohm metre
conductor or an array of  LT Motors
conductors electrically 
connected to the general a) AC motors of 110 kW and above            60mm x 10mm
mass of the earth. b) AC motors above 60kW up to 90 kW         50mm x 8mm
c) AC motors above 30kW upto 60 kW         40mm x 6mm 
Earth d) AC motors above 10kW Upto 30 kW        25mm x 4mm
A Connection to the  e) AC motor 10kw                                           8 SWG wire 
general mass of earth by  f) Control desk & control panel                          25mm x 3mm 
means of an earth electrode. g) LCS, Limit switches         
   6 sq. mm wire 
Junction boxes.    stranded 
Earthing Resistor h) TPN receptacles Welding outlets from   25mm x 4mm 
A resistor through which a 16A to 100A  
system is earthed & which i) Columns, structures & cable trays                                
50mm x 6mm
serves to limit the current j) Rail tracks, mobile equipment & other non 
flowing in the event of  current carrying metal parts  60mm x 10mm 
an earth fault. k)  Lighting fixtures, single phase  8 SWG wire
receptacles, lighting circuits    (4mm wire) 
l) Isolator up to 16 A                                                             
16 sq. mm wire stranded. 
m) Fractional Horse Power motor                                             
8 SWG wire(4mm wire) 

calculation.xls Electrical Cal 5 of 33
Electrical Engineering Sizing Calculation PRE : SPS

4 Lighting Cal. Input Data


Room Length,breath,Height
Standards COU,MF,Recommented Lux level
Lumens & no of lamps
IS 3646(1966) a) Room Index  = (L x B)/(L+B x H) COU catelouge
Indust.Light - IS 6665 b) No of fittings = (L x B x Lux)/(COU x MF x Lumens x no of lamps)
Street light pole:7-51-0107
COU
   Ratio of the total flux which reaches the working plane
Types to the total lamp flux. (or)
   The propertion of luminous flux emitted by the lamps which
Normal Lighting - 415/240V,3ph reaches the working plane directly or Indirectly.
Emergency Lighting - 415/240V,3ph
Critical Lighting - DC Supply Luminance
   It is the measure of the preceived brightness of an 
Critical Lighting Considered as illuminated surface.
Control Room
Substation Luminous flux
DG Set    Rate at which light is emitted by a light source.
Fire water pump house
Lux
   It is the ratio of Luminous flux to the area

MF = Lamp lumens MF x Fixture MF x Room surface MF

Lux Types Lumens Application


50 70W 5800 IP54 Cable cellor,Staircase
150-200 2 x 80W 2450 IP20 Panel rooms,office rooms
100-200 150W 13500 IP54 Equipment Building
250W 25000 Street light
250W FL 25000 PH Buildings - High temp
Low & high bay - Hight of building
HPSV Mill Area

Ingress Protection (IP).


st
Characters 1 Character(dust) 2nd Character(water)
0 No protection No protection(All are open)
1 50mm particle rain water vertical
2 20mm particle rain water 30deg inclaind
3 1mm particle All around rain water
4 Very fine dust Horse pipe
5 No dust entry High Pressure Horse pipe
6 Totally dust proof Imersion(no entry)

calculation.xls Electrical Cal 6 of 33
Electrical Engineering Sizing Calculation PRE : SPS

5 Battery sizing Cal All HT & LT Switchgear panels for breakers,Transducers 


a) Triping of all breaker at a time  0 - 1 min Eg: 2 hrs
Standards b) Closing of one breaker at a time 119 - 120 min
c) Normal Indication of breaker  0-1/1-119/119-120min
IS 1651 d) Trip circuit supervision 0-1/1-119/119-120min
IEEE 485 e) Transducers(KWT,KVAT,PFT) 0-1/1-119/119-120min

Tripping - 500W Battery Details


Closing - 500W Battery type : VRLA(MAINTENANCE FREE)
Indication/lamp - 7W (Valve Regulated Lead Acid)
Trip ckt sup. - 12W System DC voltage : 110
Transducer - 5W Battery nominal voltage :2
Float voltage : 2.25
Boost voltage : 2.3
End cell voltage 1.75
a) Highest permissible voltage 110V x 1.1= 121
b) Lowest permissible voltage 110V x 0.85 = 93.5
c)  Battery No. of cells =  Lowest permissible voltage
        End cell voltage
or
 Battery No. of cells =  Highest permissible voltage
        Float voltage

Estimation of Battery capacity


Required capacity for First Section S1 i.e. up to 1 min. 
S1 = A1 x K 1min.
Where 
K1min = [(C5 AH )/A] factor for end cell voltage 
of 1.75 V for 1min. discharge
A1  = Battery discharge current in Amperes 
at1min. based on Vendor’s performance 
data for K1 min. for 1min. at end cell 
voltage of 1.75V)

Battery Charger Sizing

INPUT DATA:

Battery nominal DC Voltage 110V DC
Battery AH capacity Cal values
Float charging voltage 1.4V
Float charging rate 2mA/AH
(As per Ni-Cd Battery catalogue of SABNIFE)
DC system continuous load current Cal value
(as per Fig.1 in Appendix-1)

Design criteria for Battery charger sizing:


The Battery charger is sized to meet maximum of the 
following charging current:
a Float charging current of Battery + continuous DC load current
(i.e. Float charging will be continuous during normal operation) 
b Boost charging current only
(Because in the DC battery charger scheme considered the 
load will be disconnected during boost charging)

calculation.xls Electrical Cal 7 of 33
Electrical Engineering Sizing Calculation PRE : SPS

Cal Steps
1 Float charging current of Battery   = Battery AH capacity x
     Float charging rate
2 Battery Charger rating  = Float charging current of Battery + 
     continuous DC load current

3 Boost charging current  =  (AH capacity) x F*
Total recharging time specified

*F= Factor based on  Battery charge
Battery discharge

6 Capacitor Sizing Cal Input Data


Load in KW  = P
Standards Existing PF = EPF
Desired PF  = DPF , Efficency
-1 -1
HT Cap - IS 13925(88) a) Capacitor KVAr  =  KW (tan cos (EPF) - tan cos (DPF)
Ser.Reactor - IS 5553 Efficiency
(Part 2) b) Reactor  = Actual capactor x 6%
Insulation.Material - IS 1271
Surge capacitor - IS 2834 Reactor Purpose = Current limiting & Harmonic suppression
Reactor Type      = Dry type

Shunt capacitor
It is used in all voltage levels & all sizes
a Reduction of line current
b Increased voltage level at the load
c Reduced system losses
d Increased PF of a source current
e Reduced loading on source generators & circuits.
f Reduced system investment per kw of load

V,f, ambient temp,Voltage & permissible variation = +/- 10%
Frequency variation = +/- 5%
Arrangement up to 500kvar   = Delta
                      above 500kvar  = Star

7 Soak pit Sizing Cal 5000lts and above considered soak pit


1 10 MVA Transformer-1
Quantity of Oil =  8000 Litres
Purposes (1000 Liters = 1 Cubic Meter)
            =  8.0 Cu.Mtrs
To collect & store  2 10 MVA Transformer-2
the transformers oil Quantity of Oil =  8000 Litres
            =  8.0 Cu.Mtrs
For 2 nos of 10 MVA Trafos 
Total oil capacity for the soak Pit = 8.0 x 2
= 16 CU.MTRS
Therefore 3M L x 3M W x 2M D Soak Pit is sufficient 
for these transformers.

calculation.xls Electrical Cal 8 of 33
Electrical Engineering Sizing Calculation PRE : SPS

8 NGR Sizing Cal Input Data


Transformer rated line voltage(V)
Transformer rated output (KVA)
Ratio of fault current and rated current(n)
Impedance in neutral connection in ohms (Zn)

2
a) Zn =          V ohms
         n x KVA x 1000
where,
n = trafo rated secondary current or Lower limit of fault current

9 Transformer Losses Input Data


Rate of Interest ( r )
Rate of Electrical Energy(EC)
Life of Transformer(n)
Transformer is in Service(350Days)
Cooling Aux.reamain in service(40%)
Annual Load Factor(LF)(60%)

a) Annual Loss Factor (LS)

Annual Loss Factor (LS)
LS = 0.2LF+0.8(LF)^2
Where,
LS   = Annual Loss Factor
LF   = Annual Load Factor

b) Step I: Capitalised cost of iron losses (IL)


IL= 350 x 24 x EC x (1+r)^n - 1
r(1+r)^n
c) Step II: Capitalised cost of Load losses (LL)
LL=             350 x 24 x EC x (1+r)^n - 1 x LS
r(1+r)^n

10 ACSR Conductor Sizing Input Data


Earth Fault Current (Isc)=31500A
Ambient temp (50 deg c) assumed
Tariff : Duration of fault current(t) = 1sec
The rate at which electrical Max operating temp of ACSR(To) = 85 deg c
energy is supplied to a Max S.C temp with stand capacity(Tm) = 200 deg c
consumer.
Area of conductor (A) is given by 

A =                  Isc x sqrt(t) in sq inch
14x104  (log10 (Tm+258)
       To+258

A = Ans x 645.16 sq.mm
or

A =                  Isc x sqrt(t) in sq .mm
217 x     (log10 (Tm+258)
       To+258
Ex: Aluminium area of Zebra ACSR = 427.5Sq.mm
Steel area of Panther ACSR = 55.4Sq.mm
Taking 30% rating for steel S.C Condition area considered
(ie) 55.4*30% = 16.62
Total area of Zebra ACSR for with standing S.C Current
=427.5+16.62 444.12Sq.mm

calculation.xls Electrical Cal 9 of 33
Electrical Engineering Sizing Calculation PRE : SPS

Conculsion:
a) Hence "Zebra" ACSR can with stand fault current of 
31.5kA for 1 sec.
b) Full load current carrying capacity of "Zebra" ACSR is 830A
for a rise of 35 deg.C over an ambient of 50 deg.C.
c) Hence "Zebra" ACSR has been selected.

11 Vk & Imag Cal


CALCULATION OF Vk for the REF Relay
Input Data
Trfo CT Ranges
Trfo % impedances
Cable resistance

VK > 2If (RCT + 2RL )


Where,
Vk   = Knee voltage
If     = Fault current in KA
RL   = Cable resistance in Ohm
RCT = CT resistance in Ohm
Eg:
2.5 MVA TRANSFORMER  (6.6KV /0.433KV) 3500A Sec CT
a) If =  Trafo cap x 100 in KA
% imp x 1.732 x voltage

If at Secondary side =       If in Amps


 Sec.CT rating

b) Rct = 2.5ohm per 1000turns
(I.e) Rct for 3500 turns = 2.5 x 3500 in Ohms
1000

c) RL for 1km  = 14.5 ohm (Assume 3C x 2.5 sq.mm)
(I.e) RL for 50m = 14.5 x 50 in Ohms
1000
Substitue all values in above formula
VK > Voltage (some value)
I mag < 30 mA at VK / 2

5 Lightning Cal.

Standards

IS 2309
IS 3070
IEC 99

8 Busbar Cal

calculation.xls Electrical Cal 10 of 33
Electrical Engineering Sizing Calculation PRE : SPS

11 Relay Co-ordination O/C,Earth fault etc

Standards Points to be considered during the Relay co ordination:


1 Relay pickup setting is to be considered in 110% of 
Elect.Relay for power sys.prot. full load current.
IS 3231 2 Relay operating time is to be considered in 0.35 Sec for each 
IEC 255 Co- ordination.
3 Relay time dial (K factor) is to be considered in down stream     
for 0.05 to 0.08.(In practical value k  factor is  0.08).
4 By using the formula relay operating time
t = (0.14/((If/Ips)^0.02)-1)*k is to find Out on k factor.
5 Where,
   If   = fault current in Amps in terms of CT secondary current.
   Ips = Pick up setting in Amps in terms of CT secondary    
                         Current.

Rating / Trafo sec Trafo pry Incomer Comments


Relay Loc Relay Relay Relay
Rating 1 MVA 1600KW
Voltage 0.415KV 6.6KV 6.6KV
CT Ratio 1600/1 A 100/1 A  200/1 A
Fault 25.66*(.415/6.6)= 
current 25.66KA 1.61KA     8.16KA 1.61kA
 (SC current on the LV side refer to 6.6kV)
FLC 1391.2A 87.47A 174.957
Relay
pick up
current 1530.2A 96.21A 192.45A
Ips in Sy 0.96 0.96 0.96
If in Sy 16.04 16.1 40.8
K factor 0.08 0.23 Calc 0.39 Calc In down stream only
Relay 0.53         
operating (0.18+0.3 0.7(0.35 
time 0.19 Calc 5) +0.35) top=0.35 calculated

Points to be considered during the Earth fault Protection:


1 In Earth fault Protection the Pick up Setting for all Stream is 
P=0.2 SEC.
2 In Earth fault Protection the Operating time is to be 
Considered 0.35 SEC for each Co-ordination.
3 In Fault level, the Secondary Side of Transformer does not 
affected the Primary Side.So we are neglecting the 
Secondary earth fault.
4 Same as above step 3,4,5 in O/C Setting

D) Drawings

1 Single line diagram Including Power transmission & Distribution for HT & LT


feeders for over all plant.

Input Data
a) Collect Drive list as per client

calculation.xls Electrical Cal 11 of 33
Electrical Engineering Sizing Calculation PRE : SPS

2 Load centre Drawing a) Including To proper location and arrangement of all HT & LT 


equipment panels(HT,PCC,MCCHT Capacitor ,APFC,
Fixed capacitors,thyrister,VFD,P&V,LRS,GRR,AC,
Where distribution of Magnetic seperator, LDB,PDB Panels),transformers,etc
electrical system takesplace
b) Instrumentation panels(I/O,UPS,Battery,SFM,Bin weigher,
Apron,Gas analyser Panels etc)

c) Cut out Details,Insert plate Details,panel elevation drawings,etc

d) for the above panel drawings for different Load centre & 
floor levels

LC Clearances
1 Front clearance = min 1m
switchgear arrangement 2 Rear clearance  =  min 750mm if there are rear entry cables
IS 5578 or rear doors or there is necessity to
work behind.
or less than 200mm if there is no such 
item to above.
3 Space between HT & LT  = min 2m
4 If 2 switch boards are erected facing each other,the clearance 
should be min 2m
5 If 2 switch boards are erected back to back,the clearance 
should be min 1.5m
6 If 2 switch boards are erected adjacent to each ,if the same line
the clearance b/w 2 switch boards should be eighter
less than 200mm or more than 750mm
7 If double fronted switchgboard / mcc panels are erected as 
sapce of not less than 1m shold be provided for the both
the front sides.

3 Cable Routing Drawing a) Including different tray sizes for Power,Control & Signal cables  


for over all Plant layout & Individual Buildings

b) Different Section drawings

c) Gantry,Trench & Buried details

d) The above cable routing drawing for possible to shortest 
routes considered 

e) The cable tray routings are possible to rise & drop along the 
Coloumn,Beam,Belt conveyor Structure, I Beam

4 Lighting Drawing a) Including Lighting boq,Lighting layout drawing for varieous 


equipment buildings

b) Power Distribution for Lighting (SLD)

5 Earthing Drawing a)  Earthing layout with calculation, earth electrode quantity, 


earthing conductor sizing etc.

b) Typical drawings for earth electrode installation, 
earthing of motors panels etc.

c) Earthing Details drawings

calculation.xls Electrical Cal 12 of 33
Electrical Engineering Sizing Calculation PRE : SPS

E) Protection
Relay No Relay Description
1 Transmission Lines & feeders
50 O/C ,Time delay
50N E/F ,Time delay
Senstive E/F
21 Distance
87 Differential protection(Longitudinal)
Phase Comparision
2 Bus bar Protection
50 O/C
50N E/F
Frame earth protection
21 Distance
Differential protection
Phase comparision protection
Direction locking protection
System Protection used to cover busbars
3 Generator Protection
50 Over current protection & Time delay
50N Stator Earth fault 
46 Phase Unbalanced loading
64F Rotor earth faults
32 Reverse power
87 Differential protection
Field failure impedence
59 Over Voltage
24 Over load
Rotor temperature
4 Trafo Protection
50 Over current protection & Time delay
87 Differential protection(Longitudinal)
Over Heating
50N Instanteneous Restricted E/F Current & Time delay
63 Buchholz

5 Trafo feeder Protection


50 Over current protection & Time delay
E/F current & Time delay
87 Differential protection(Longitudinal)
59N Neutral displacement
50N Instanteneous Restricted E/F Current & Time delay
Instanteneous high set O/C  & Time delay
21 Distance

6 Generator Trafo Protection


earthed Resistance Earthing trafo

Differential protection Differential protection
HV Restricted Earth Fault
HV Restricted Earth Fault
O/C time delayed O/C time delayed
LV Instatenious E/F
Phase unbalance or Negative sequence 
Phase unbalance or Negative sequence 
Over Voltage Over Voltage
Field failure impedenceField failure impedence
Rotor earth faults Rotor earth faults
Reverse power Reverse power
Winding temp Winding temp
Buchholz Buchholz

7 AC Motor & Synchronous Motors


49 Thermal Over load Protection
Start up Protection
Stall Protection or Locked Rotor 
46 Phase unbalance or Negative sequence 
50>> Short circuit current(High set overcurrent)
50N Instanteneous Earth fault
No of Stards per Period (Starts/Hr)
Time b/w Two starts Protection(in minute)
87 Differential protection

calculation.xls Electrical Cal 13 of 33
Electrical Engineering Sizing Calculation PRE : SPS

Soft starter
Functions of soft starters
1 To limit start current, thus to limit voltage drop on power system
a Excessive voltage drop may interfere with the normal power 
system function of the equipment connected to the same 
b Different countries have different voltage drop limits

2 To protect against mechanical impact on transmission gear and load
a Direct start results in high acceleration speed 
b High acceleration speed have great mechanical impact on transmission gear and load

3 To prolong life of motor
a  Direct start results in high start current and high acceleration speed
b Heat created by high start current may results in early aging of coils of motor
 

c High acceleration speed may shorten the life of bearings and rotors of motors
  

calculation.xls Electrical Cal 14 of 33
ELECTRICAL FUNDAMENDALS,LAW'S,MACHINES PRE : SPS

ELECTRICAL FUNDAMENDALS
Electric Current:
The flow of free electrons in a metal is called. (Or ) Movement of electric charge.

I = dq / dt   or Q / t = Charge / Time Unit : coloumb / sec

Electric Potential:
The ability of the charged body to do work.

V = W / Q = Work done / Charge Unit : Joules / Coloumb

Electric Field(E): E = F / q

Potential difference:
The difference in the potential of two charged bodies.

Resistance(R):
The opposition offered by a substance to the flow of electric current.
or  Property of a substance due to which it opposes the flow of current through it.

Electrical Resistivity(p):
R = pL / A ie  p = RA / L = ohm x m^2 / m Unit : ohm m

Conductance(G):
Reciprocal of resistance. Unit : mho or seimens

Conductivity :
Reciprocal of resistivity. Unit : mhos / m

Direct Current(DC) :
It is a current in which the flow of electric charges is unidirection.

Alternating Current(AC) :
It is a current in which the flow of electric charges Periodically reverse in direction.
Reason for the reversal of direction is that alternating voltage source reverses in polarity.

DC Voltage AC Voltage
* Fixed polarity * Reverses in polarity
* Steady or vary in magnitude * varies b/w reversals in polarity

Electrical Energy:
It is the ability to produce heat by causing charge to move from one location to another.
or It is the ability to do work. Unit : Joule

Electrical Power:
The rate of producing or using electrical energy as well as the rate of doing work.
P = W / t P = VI 1 HP =746W

Ground :
It is used in ac poer supply lines.
It one side of the line is neutralized by connecting a metal rod driven in to the ground.

Series ckt :
Various resistance are connected across a source in such a way.
There is only one path for the current flow.

Parallel ckt :
Various resistance are connected across a source in such a way.
There is more than one path for the current flow.

Open ckt :
When any part of the path is open or broken & there is no continuity in the 
conducting path.
 * Resistance of an open ckt is infinitaly high. R = Infinitely
 * There is no current in an open ckt  I = 0

calculation.xls Electrical law & machines 15 of  33
ELECTRICAL FUNDAMENDALS,LAW'S,MACHINES PRE : SPS

Short ckt :
When the voltage source has a closed path across its terminals.
 * Resistance of short ckt is zero result of this 
     there is no voltage drop across the hort ckt path. R = 0
 * Large flow of current through short ckt.  I = Isc

Resistor :
Resistor can conduct current in both the direction.
Purposes:
 * Controling the flow of electric current.
 * Providing desired amounts of voltage electric or electronics ckt.

Inductance :
It is the property of a coil which opposes change in current by means of 
energy storage in the form of magnetic field.

Inductor :
It is electrical component,which is manufactured with specified amount of inductance.
Uses :
 * To minimise alternating currents while permitting flow dc.

Capacitance :
Which opposes the change in voltage by means of energy storage in the form of 
electrostatic energy.

Capacitor :
Capacitor are the device which can store electric charge.

Transducer :
A transducer is a device which converts energy in one form to another form.
This energy may be electrical,mechanical,chemical,optical or thermal.

Capacitor : Stores electric field
Inductor : Stores magnetic field
Electric field : Charges at rest.
Magnetic field : Charges at motion

Magnetic Fields
Magnetic Flux(p):
The magnetic lines of force produced by a magnet.
8
Unit : weber 1weber = 10  Magnetic lines.

Magnetic Flux density(B):


Flux per unit area at right angles to the flux.
2      (
B = Φ / A Unit : weber / m 0r) Tesla

Magneto motive force (F) :


MMF is a producing flux in a magnetic ckt.
F = NI Unit : AT (Ampere turns)

Magnetic field intensity or magnetising force (H) :


It is defined as MMF / Unit length
H = NI / L Unit : Amp / m

Permeability ( μ):
Flux density(B) is proportional to Magnetising force(H)
B proportional H
B =μ H ie μ = B / H μ is constant proportionality.

Relative Permeability ( μr):


μr = Flux density in the medium
Flux density in vaccum

Reluctance(S) :
S = Magneto motive force Unit : Amp / weber

calculation.xls Electrical law & machines 16 of  33
ELECTRICAL FUNDAMENDALS,LAW'S,MACHINES PRE : SPS

Flux 

calculation.xls Electrical law & machines 17 of  33
ELECTRICAL FUNDAMENDALS,LAW'S,MACHINES PRE : SPS

Permeanance (p) :
Reciprocal of reluctance. Unit : weber / Amp

Leakage flux :
The flux which does not follow the desired path in magnetic ckt is known as.

Magnetic ckt:
It is the path followed by magnetic flux.
or Closed path for magnetic flux is known as.

Electric ckt: Closed path for electric current

Firing effect :
    in area of the air gap as a result      in flux density in the air gap.

Hall effect :
When a transverse magnetic field B is applied to a metal or a semiconductor carrying current I
an electric field E is induced in the direction of perpanticular to both I & B.
This Phenomenon is called.

Cycle : One complete set of +ve & -ve values of an alternating current.
I
Time period : Time taken by an alternating current to complete one cycle T
T = 1 / No of cycles
Cycle
Frequency : f = no of cycles / second f = 1 / T

Amplitude (Peak value): The max value of +ve or -ve half cycle of ac.

Peak to Peak value : Sum of  +ve & -ve peak value is called

Instateneous value(i) : The value of ac at any particular moment is called. i = Imax sinωt = Imax sinѲ

Phase : The fraction of a cycle or time period which has elapsed since an ac or voltage last passed a
given reference point.

Phase difference : The difference in phase b/w two ac or voltages of the same frequency is called.

BASIC LAWS
Ohm's Law :
It gives relationship b/w Voltage,Current & Resistance for good conductors. 
It states that " the electric current passing through the conductor is directly propotional to the 
poterntial difference applied across the conductor ".
I proportional V
= V/R R is proportionality constant ie V = IR

Kirchoff's Laws :
i) KCL
It states that " in any n/w the algebraic sum of current meeting at a point or junction is zero.
or The sum of current entering a junction is equal to the sum of current leaving the junction.

i) KVL
It states that "in any n/w the sum of all the voltages arround a closed path or loop is always zero.
ε IR + ε emf = 0
ε IR   = sum of voltage drop across resistor.
ε emf = sum of battery voltages
or The net emf round a ckt is equal to the sum of the pds round the loop.

Faraday's Law of Electromagnetic Induction :


It states that " electromagnetic force (emf) induced in ckt is equal to the rate of change of 
magnetic flux linking the ckt.
emf = -N(φ2 -φ1) / t ie) emf = dφ / dt emf = I v B

calculation.xls Electrical law & machines 18 of  33
ELECTRICAL FUNDAMENDALS,LAW'S,MACHINES PRE : SPS

Lenz Law :
It states that " any induced emf will circulate a current in such a direction so as to oppose the 
cause producing it".Lenz law gives the nature of induced emf's.
or  The direction of the induced emf is such that it tends to oppose the flux change causing it,
and does oppose it if induced current flows.
ε  = - N dφ / dt

Fleming's Left hand rule :


Stretch out the fore,middle & thumb of the  Mag field (fore finger)
lefthand so that they are right hand to another.
    If the fore finger points in the direction of magnetic field
(north to south) and middle finger points towards  Current
the direction of current & thumb will point (Middle finger)
in the direction of motion of conductor. Motion of conductor
(thumb)

Fleming's Right hand rule :


The direction of induced emf can be easily found Motion of conductor
by applying Flaming right hand rule. (thumb)
   Hold the thumb,fore finger & middle finger
of the right hand at right angles to the another.
If the thumb point to the direction of motion  Mag field  EMF
& fore finger to the direction of mag field & (fore finger) (Middle finger)
middle finger will point the direction of induced emf.

Gauss Law:
The electric flux passing through any closed surface is equal to the total charge enclosed 
by that surface.
∫ D.∆ = εQ

Coulomb's Law:
It states that " the force b/w two small charged objects size is proportional to the magnitude of 
each charge & Inversely proportional to the square of the distance b/w them.
F Proportional Q1 Q2 / r^2 F = Q1 Q2 /  4∏εr^2
             
Ampere's ckt Law:
It states that " the line integral of magnetic field intensity H arround any closed path 
is equal to the direct current enclosed by that path.
∫H.dl = I

Biot savart Law:


It states that " magnetic flux density at any point due to current is proportional to the
 current element & sine of the angle b/w the element length and line joining and inversely 
proportional to the square of distance b/w them.
dB = μ0 Idl sin θ / 4∏r^2

Pointing theorem :
The vector product of electric field intensity and magnetic field intensity at any point is 
ameasure of the rate if energy flow per unit area at that point.
P = E X H
Thevenin's theorem :
It states that " any complex n/w can be replaced by series ckt consisting of an
 ideal voltage source & a resistance.
~~~ A
            A + R
   Vth
            B          -
B
Complex n/w
Norton's theorem :
It states that " any complex n/w can be replaced by parallel ckt consisting of an
 ideal current source & a resistance.
A

            A RN
  In
            B ~
B
Complex n/w

calculation.xls Electrical law & machines 19 of  33
ELECTRICAL FUNDAMENDALS,LAW'S,MACHINES PRE : SPS

calculation.xls Electrical law & machines 20 of  33
ELECTRICAL FUNDAMENDALS,LAW'S,MACHINES PRE : SPS

Super position theorem :


It states that " the voltage or current present in a component is equal to the sum of 
voltage or current which exist independently.
or In a linear biletral electrical n/w contain several n/w the current flowing through each resistance 
is equal to the algebraic sum of seperated resistor.

Max power transfer theorem :


It states that " given a linear biletral n/w represented by a thevenin equivlaent ckt the 
max power will be transferred to aresistive load, when the load resistance is equal to 
thevenin's resistance.
I   =    Vth / (Rs + RL) ~~~ A

           + Rth    RL


  Vth
         -
B

Telegen's theorem :
It states that " in a given n/w the algebraic sum of the power delivered by all source is equal 
to the algebraic sum of the power absorbed by all elements.
This theorem is based on Kirchoff's law.

Electrical Machines
3Ph Induction Motor :
Principle
* 3ph supply is gn to the stator.
* Revolving magnetic field is produced in the stator.
* Revolving magnetic field is cut by the stator conductor.
* Emf induced in the stator conductor.
* The emf induced in the rotor due to lenz law.
Types
* Squirrel cage I.M
* Slip ring I.M
Speed control of I.M
Stator side Rotor side
* By changing the voltage * By rotor resistance control
* By changing the frequency * By operating two motors in casecade.
* By changing the no of poles * By injecting emf in the rotor.

Slip : Difference b/w synchronous speed(Ns) & rotor speed(N) is known as slip. S = (Ns - N) / Ns

Starting of I.M
In 3ph IM is directly switched on the supply,they draw starting current equal to 5 to 8 times of   
full load current & starting torque equal to 1 to 1.5 times of full load torque.This amount of
starting current is affects the system voltage.
ie To limit the starting current & to improve the starting torque.Hence 3ph I.M suitable starts
are used .such as 
Starters: * Primary resistance or stator resistance starter (starting torque is improved
* Auto transformer starter by adding resistance in
* Star - delta starter the rotor ckt with out using
* Rotor resistance starter starter)
* DOL Starter

1Ph Induction Motor :


1ph I.M is similar to polyphase I.M except that 
a.) stator is provided with a 1ph winding   b) centrifugal switch is used
It is not a self starting reason is,
*     A 1ph supply is gn to a stator wdg produces a flux which is only alternating.
ie alternates along one space axis only.
*     It is not a synchrously revolving (rotating) flux as in the case of 2 or 3ph stator wdg 
fed from 2 or 3ph supply.
*     Now an alternating flux acting on a stationary squirrel cage rotor can not produce rotation.
To make 1ph I.M self starting,following types are used
1.Split phase I.M ( Resistance start,capacitor start & permanent split capacitor motor)
2.Shaded pole I.M 3.Repulsion motor 4.Universal Motor (both ac & dc supply0

calculation.xls Electrical law & machines 21 of  33
ELECTRICAL FUNDAMENDALS,LAW'S,MACHINES PRE : SPS

Making 1ph I.M Self starting:


* Temerorly converted in to a 2ph motor during starting period
* For this purpose the stator of a 1ph motor is provided with an extra wdg known as starting 
or auxillary wdgs in addition to the main wdg
* The two wdgs are spaced 90 deg electrically apart&connected in parallel across the 1ph supply
* It is so arranged that the phase difference b/w the currents in the 2 stator wdgs is very large
(Ideal value being 90deg)
* Hence motor behaves like a 2ph motor.The two currents produce a rotating flux & hence
make the motor self starting.

DC Motor :
DC Motor is a machine which converts electrical energy in to Mechanical energy.
Eg:Grinder,mixy,water pump
Principle
When a current carrying conductor is placed in a magnetic field a force acting on the conductor
and trice to push the conductor whether upward or down ward direction depends upon the
force acting on the conductor.
Direction of the force acting on the conductor can be find out by flamming left hand rule.(F =BIL)
Types
* DC series Motor
* DC shunt Motor
* DC compound Motor ( 1.Cummulative DC Comp.motor, 2.Differential DC Comp.motor)
Characteristics
* Speed vs Current  
    Electrical characteristics
* Torque vs Current  
* Speed vs Torque       Mechanical characteristics
Speed control
DC Series Motor DC Shunt Motor
* Armature diverted metod * Armature control
* Field diverted metod * Field control
* Voltage control method * Voltage control or Ward leonard system.
Starters
* Two point Starter
* Three point Starter ( Line,field,armature)
* Four point Starter ( Line plus,Line minus,field,armature)
Losses
* copper loss
* Iron or core loss

DC Generator :
DC Generator is a machine which converts Mechanical energy in to electrical energy.
Principle
The energy conversion is based on the principle of the production of dynamically induced emf.
  When ever a conductor cuts magnetic flux,dynamically induced emf is produced in according 
to Faraday's law of electro magnetic induction.
* Field system = Stationary
* Armature system = Rotating
Types
* Seperately excited generator
* Self excited generator (1.Series,2.shunt,3.compound i.Long shunt ii.short shunt)
Characteristics
* Open ckt characters ( E0  vs  If )
* Internal characters  ( E  vs  IL )
* External characters ( Supply voltage  vs  IL )
Excitation:
By giving external DC Supply to the field of the generator is known as.
Losses
* copper loss or Variable
* Constant or stray loss (1.Iron or core loss, 2. friction loss)
Application
DC Series Gen DC Shunt Gen Compound Gen
* Series arc Lighting * source for battery charging * supply power to railway ckt
* Series incandescent Lighting * Electro plating & electrolysis * Incandesent lamp
* Booster * Elevator motors

calculation.xls Electrical law & machines 22 of  33
ELECTRICAL FUNDAMENDALS,LAW'S,MACHINES PRE : SPS

Alternator or AC Generator :
Principle Faraday's law of electromagnetic induction.
Direction Can be found out by flamming right hand rule
Armature winding  = Stationary  = Stator
Field winding        = Rotating     = Rotor
When ever a conductor cuts the flux an emf induced in the armature conductor.
Rotor * Salient or Projecting pole type ( Low & medium speed)
* Smooth cylindrical type ( Very high speed,
used in steam turbine driven alternator or turbo alternator
Parallel
* Voltage must be same.
*  Phase sequence must be same.
* Frequency must be same.
When 2 alternators are connected in parallel to supply power to a common load is
known as synchronising.

Synchronous Motor :
Synchronous motor identical with two motors.
Principle Similar to 3ph I.M
Construction Similar to alternator It is not a self starting.
When 3ph supply is gn to the stator a revolving magnetic field is produced.The revolving 
magnetic field is the nature of poles ie N & S.
when DC excitation is gn to the field wdg of the rotor & hence rotor poles Nr & Sr is formed.
Starters
* Starting by damper wdg.
* Starting by separate I.M
* Starting by DC Motor couple to synchronous motor
Hunting The oscillation due to load condition & the periodic change in speed is known as.
Application
* Rubber mills * textile mill
* Paper mill * It is used to drive continuously operating & constant speed equipment 
* crushers like fan,blowers,centrifugal pump

Synchronous Motor Induction Motor


* Not a self starting * self starting
* Constant speed at any spped * speed fall slidly with increase of load
* operated at various pf * operated at only lagging pf
* A separte DC excited is needed * excited is not needed
* change in i/p voltage does not * change in i/p voltage affect the torque
affect the torque
* cost is very high * cost is low

Hysteresis Motor :
It is similar to synchronous motor with out DC excitation/
A 1ph or 3ph supply is gn to the motor the torque is produced in the motor due to hysterisis &
eddy current induced in the rotor by action of rotating flux of stator wdg.
Principle
When a 3ph or 1ph supply is gn to the stator a rotating or revolving magnetic field is produced 
in the stator.The revolving magnetic field magnetise the rotor rising & induces the holes. 
Application
* Sound reproduction system (eg: Record players,tape recorders)

calculation.xls Electrical law & machines 23 of  33
PRE:SPS

STANDARDS
IS     = Indian Standards
IEC   = International Electro technical Commision
IEEE = International Electrical Electronics Engineer
ANSI = American National Standard Institute
ISO  =  International Standard Organization
BS    = British Standars Institution
NEC  = National Electric Code
NEMA =National Electrical Manufactures Association
SI.NO DESCRIPTION IS IEC ANSI/IEEE

1 Power Trafo IS 2026 IEC 60076 ANSI/IEEE C57.12.01


Dist.Trafo IS 1180
Dry type trafo IEC 60726 ANSI/IEEE C57.12.01
Instrument trafo ANSI/IEEE C57.13
Trafo oil      IS 335 IEC 60354
On load tap changer            -  IS 8648 IEC 60542 / IEC 60214

2 CT           IS 2705 IEC 60044 / IEC 60185 BS 3938

3 PT or VT IS 3156 IEC 60186

4 Switchgear arrangement IS 5578
HV AC CB IEC 60265
HV CB IS 13118 IEC 62271 Part 100
HV Dis Connect switches IEC 62271 Part 102
HV Switches IEC 60265
HV Air switches ANSI/IEEE C37.3
HV testing ANSI/IEEE 4
HV fuse IEC 60281 ANSI/IEEE C37.4
SF6 IEC 60376
Switchgear up to 52kV IS 3427 IEC 60298 ANSI/IEEE C37.20
GIS Switchgear above 72.5kV IEC 60517
Gas insulated substation ANSI/IEEE C37.122
LV Switchgear & contro gear IEC 60947 / MEMA 250
LV CB IS 2516 IEC 60157-1
CB for O/C Protection IS 8828
Switchgear Spec. IEC 60694
Isolator or disconnecto Earthing switch IS 1818 IEC 129
Control Switches IEC 60337
HRC Fuse IS 2208
Catridge Fuse link for MCB IEC 60127
AC contactors IS 2959 IEC 60158-1
Al Busbar IS 5082
IP degree of Protection IEC 60529
MCCB NEMA AB1
Steel structure ISO 630

calculation.xls  Standards  24 OF 33
PRE:SPS

STANDARDS
5 Cable IS 7098(Part 2) IEC 60502
BS 6622
Power cable 30kv to 150kV IEC 60840
Cable Sizing IEC 60287 IEEE S 135
PVC Al      IS 1554
PVC cable IEC 60227
PVC Insulation PVC Sheath cable IEC 60189
XLPE Al  IS 7098
OFC Cable IEC 60794
Cable laying & Install IS 1255(84)
Over Head Conductor IS 398 IEC 1089
Elect test mehod for Elect cables IEC 60885
Loading test on Over Head line tower IEC 60652

6 Earthing  IS 3043(1987) IEEE-80


Earthing trafo  3151(1982)
Indust.Earthing IEEE-142
Neutral grounding devices IEEE std 32

7 Lighting  IS 3646(1966) IES Lighting Handbook  ANSI/IEEE C.2 NESC


Indust.Light  IS 6665
Emergency Lighting IS 9593
Plugs & Sockets IEC 60083 / IEC 60309
HPMV Lamp IEC 60188
HPSV Lamp IEC 60622

8 Lightning  IS 2309,IS 3070 IEC 60099

9 Battery sizing IS 1651 IEEE 485


Lead acid Vent type Battery IEC 60896
DC Power Supply IEC 478

10 Capacitor  IS 13925(88) IEC 60871 / IEC 60549 IEEE 18


Series Capacitor IEC 143
Ser.Reactor  IS 5553 IEC 60289
Insulation.Material  IS 1271
Surge capacitor     IS 2834 IEC 60094

11 Elect.Relay for power sys.prot. IS 3231 IEC 60255 / BS 142 ANSI/IEEE C37.90


Electricity Meter IS 722 ANSI C12.1

12 Induction Motor IS 325 IEEE 841 TEFC SC I.M 


Rotating Elect Machines IEC 60034 UPTO & 370KW
Test procedure for Motors & gen NEMA MG 1 IEEE 112
AC Motor protection ANSI C37.96
Thermal protection of Motor  ANSI/UL 547
Synchronous Motor ANSI C50
13 Post Insulator IS 2544 IEC60273 / IEC 60660 ANSI C29
14 Wiring Installation IS 732
15 Insulation Co-ordination IEC 60071

16 Short Ckt  IS 13234 / 1992 IEC 909 / 1988  ANSI/IEEE 141 / 1986 

calculation.xls  Standards  25 OF 33
IEEE ANSI Device Definitions
 
IEEE Device Numbers and Functions For Switchgear Apparatus
Selections from ANSI C37.2-1991

2    Time-delay starting or closing relay is a device that functions to
      give a desired amount of time delay before or after any point of
      operation in a switching sequence or protective relay system, except
      as specifically provided by device functions 48, 62, and 79.

3    Checking or interlocking relay is a relay that operates in response to
      the position of a number of other devices (or to a number of
      predetermined conditions) in an equipment, to allow an operating
      sequence to proceed, or to stop, or to provide a check of the
      position of these devices or of these conditions for any purpose.

12   Overspeed device is usually a direct-connected speed switch which
      functions on machine overspeed.

14   Underspeed device is a device that functions when the speed of a
      machine falls below a predetermined value.

21   Distance relay is a relay that functions when the circuit admittance,
      impedance, or reactance increases or decreases beyond a predetermined
      value.

24   Volts per hertz relay is a relay that functions when the ratio of
      voltage to frequency exceeds a preset value.  The relay may have an
      instantaneous or a time characteristic.

25   Synchronizing or synchronism-check device is a device that operates
      when two ac circuits are within the desired limits of frequency,
      phase angle, and voltage, to permit or to cause the paralleling of
      these two circuits.

26   Apparatus thermal device is a device that functions when the
      temperature of the protected apparatus (other than the load-carrying
      windings of machines and transformers as covered by device function
      number 49), or of a liquid or other medium exceeds a predetermined
      value; or when the temperature of the protected apparatus or of any
      medium decreases below a predetermined value.

27   Undervoltage relay is a relay which operates when its input voltage is
      less than a predetermined value.

30   Annunciator relay is a nonautomatically reset device that gives a num-
      ber of separate visual indications upon the functioning of protective
      devices, and which may also be arranged to perform a lockout function.

32   Directional power relay is a relay which operates on a predetermined
      value of power flow in a given direction, or upon reverse power flow
      such as that resulting from the motoring of a generator upon loss of
      its prime mover.
36   Polarity or polarizing voltage device is a device that operates, or
      permits the operation of, another device on a predetermined polarity
      only, or verifies the presence of a polarizing voltage in an
      equipment.

37   Undercurrent or underpower relay is a relay that functions when the
      current or power flow decreases below a predetermined value.

38   Bearing protective device is a device that functions on excessive
      bearing temperature, or on other abnormal mechanical conditions
      associated with the bearing, such as undue wear, which may eventually
      result in excessive bearing temperature or failure.

39   Mechanical condition monitor is a device that functions upon the
      occurrence of an abnormal mechanical condition (except that
      associated with bearings as covered under device function 38), such
      as excessive vibration, eccentricity, expansion, shock, tilting, or
      seal failure.

40   Field relay is a relay that functions on a given or abnormally low
      value or failure of machine field current, or on an excessive value
      of the reactive component of armature current in an ac machine
      indicating abnormally low field excitation.

46   Reverse-phase or phase-balance current relay is a relay that functions
     when the polyphase currents are of reverse-phase sequence, or when
     the polyphase currents are unbalanced or contain negative phase-
     sequence components above a given amount.

47   Phase-sequence or phase-balance voltage relay is a relay that
      functions upon a predetermined value of polyphase voltage in the
      desired phase sequence or when the polyphase voltages are unbalanced
      or when the negative phase-sequence voltage exceeds a given amount.

48   Incomplete sequence relay is a relay that generally returns the
      equipment to the normal, or off, position and locks it out if the
      normal starting, operating, or stopping sequence is not properly
      completed within a predetermined time.

49   Machine or transformer thermal relay is a relay that functions when
      the temperature of a machine armature winding or other load-carrying
      winding or element of a machine or power transformer exceeds a
      predetermined value.

50   Instantaneous overcurrent relay is a relay that functions
      instantaneously on an excessive value of current.

51   AC time overcurrent relay is a relay that functions when the ac input
      current exceeds a predetermined value, and in which the input current
      and operating time are inversely related through a substantial
      portion of the performance range.

52   AC circuit breaker is a device that is used to close and interrupt an
      ac power circuit under normal conditions or to interrupt this circuit
      under fault or emergency conditions.
55   Power factor relay is a relay that operates when the power factor in
      an ac circuit rises above or falls below a predetermined value.

56   Field application relay is a relay that automatically controls the
      application of the field excitation to an ac motor at some
      predetermined point in the slip cycle.

59   Overvoltage relay is a relay which operates when its input voltage is
      more than a predetermined value.

60   Voltage or current balance relay is a relay that operates on a given
      difference in voltage, or current input or output, of two circuits.

62   Time-delay stopping or opening relay is a time-delay relay that serves
      in conjunction with the device that initiates the shutdown, stopping,
      or opening operation in an automatic sequence or protective relay
      system.

63   Pressure switch is a switch which operates on given values, or on a
      given rate of change, of pressure.

64   Ground detector relay is a relay that operates on failure of machine
      or other apparatus insulation to ground.
     Note:  This function number is not applied to a device connected in
      secondary circuit of current transformers in a normally grounded
      the power system, where other device numbers with a suffix G or N
      should be used, that is, 51N for an ac time overcurrent relay
      connected in the secondary neutral of the current transformers.

67   AC directional overcurrent relay is a relay that functions on a
      desired value of ac overcurrent flowing in a predetermined direction.

68   Blocking relay is a relay that initiates a pilot signal for blocking
      of tripping on external faults in a transmission line or in other
      apparatus under predetermined conditions, or cooperates with other
      devices to block tripping or to block reclosing on an out-of-step
      condition or on power swings.

74   Alarm relay is a relay other than an annunciator, as covered under
      device function 30, that is used to operate, or to operate in
      connection with, a visual or audible alarm.

76   DC overcurrent relay is a relay that functions when the current in a
      dc circuit exceeds a given value.

77   Telemetering device is a transmitter used to generate and transmit to
      a remote location an electrical signal representing a measured
      quantity, or a receiver used to receive the electrical signal from a
      remote transmitter and convert the signal to represent the original
      measured quantity.

78   Phase-angle measuring or out-of-step protective relay is a relay that
      functions at a predetermined phase angle between two voltages or
      between two currents or between voltage and current.

79   AC reclosing relay is a relay that controls the automatic reclosing
      and locking out of an ac circuit interrupter.

80   Flow switch is a switch which operates on given values, or on a given
      rate of change, of flow.

81   Frequency relay is a relay that responds to the frequency of an
      electrical quantity, operating when the frequency or rate of change
      of frequency exceeds or is less than a predetermined value.

84   Operating mechanism is the complete electrical mechanism or
      servomechanism, including the operating motor, solenoids, position
      switches, etc., for a tap changer, induction regulator, or any
      similar piece of apparatus which otherwise has no device function
      number.

85   Carrier or pilot-wire receiver relay is a relay that is operated or
      restrained by a signal used in connection with carrier-current or dc
      pilot-wire fault relaying.

86   Lockout relay is a hand or electrically reset auxiliary relay that is
      operated upon the occurrence of abnormal conditions to maintain
      associated equipment or devices inoperative until it is reset.

87   Differential protective relay is a protective relay that functions on
      a percentage or phase angle or other quantitative difference of two
      currents or of some other electrical quantities.

90   Regulating device is a device that functions to regulate a quantity,
      or quantities, such as voltage, current, power, speed, frequency,
      temperature, and load, at a certain value or between certain
      (generally close) limits for machines, tie lines, or other apparatus.

94   Tripping or trip-free relay is a relay that functions to trip a
      circuit breaker, contactor, or equipment, or to permit immediate
      tripping by other devices; or to prevent immediate reclosure of a
      circuit interrupter if it should open automatically even though its
      closing circuit is maintained closed.

95-99   Used only for specific applications in individual installations if
         none of the functions assigned to the numbers between 1 to 94 is
         suitable.

Suffix Letters
 Suffix letters may be used with device function numbers for various
purposes.  They permit a manifold multiplication of available function
designations for the large number and variety of devices used in the many
types of equipment covered by this standard.  They may also serve to denote
individual or specific parts or auxiliary contacts of these devices or
certain distinguishing features, characteristics, or conditions which
describe the use of the device or its contacts in the equipment.

A     Alarm or auxiliary power
B     Bus, battery or blower
BL    Block (valve)
BP    Bypass
BT    Bus tie
C     Capacitor, condenser, compensator, carrier current or coil
CC    Closing coil
F     Feeder of field, filament, filter or fan
G     Generator or ground <1>
H     Heater or housing
L     Line or logic
M     Motor or metering
N     Neutral<1> or network
SI    Seal-in
TC    Trip coil
X     Auxiliary relay
Y     Auxiliary relay
Z     Auxiliary relay

<1>  Suffix N is generally used in preference to G for devices connected
   the secondary neutral of current transformers, or in the secondary of
   a current transformer whose primary winding is located in the neutral
   of a machine or power transformer, except in the case of transmission
   line relaying, where the suffix G is more commonly used for those
   relays that operate on ground faults.

Other Suffix Letters
A     Accelerating or automatic
B     Blocking or backup
C     Close or cold
E     Emergency or engaged
F     Failure or forward
H     Hot or high
HR    Hand reset
HS    High speed
L     Left, local, low, lower or leading
M     Manual
O     Open or over
OFF   Off
ON    On
P     Polarizing
R     Right, raise, reclosing, receiving, remote or reverse
S     Sending or swing
T     Test, trip or trailing
TDC   Time-delay closing
TDO   Time-delay opening
U     Up or under

Device Contacts
 The letters a and b shall be used for all auxiliary, position, and limit
switch contacts for such devices and equipment as circuit breakers,
contactors, valves and rheostats, and contacts or relays:

a-Contact that is open when the main device is in the standard reference
   position, commonly referred to as the nonoperated or de-energized
   position, and that closes when the device assumes the opposite position.

b-Contact that is closed when the main device is in the standard reference
   position, commonly referred to as the nonoperated or de-energized
   position, and that opens when the device assumes the opposite position.
The simple designation a or b is used in all cases where there is no
need to adjust the contacts to change position at any particular point
in the travel of the main device, or where the part of the travel where
the contacts change position is of no significance in the control or
operating scheme.  Hence the a and b designation usually are sufficient
for circuit breaker auxiliary switches.
ANSI Device Numbers PRE: SPS

ANSI Nos Descriptions Functions

2 Timer 

21 Distance relay Distance relay is a relay that functions when the circuit admittance,
impedance, or reactance increases or decreases beyond a predetermined
value.

24 Over load relay

27 Under voltage relay Undervoltage relay is a relay which operates when its input voltage is
less than a predetermined value.

32 Reverse power relay Directional power relay is a relay which operates on a predetermined
value of power flow in a given direction, or upon reverse power flow
such as that resulting from the motoring of a generator upon loss of
its prime mover.

49 Thermal O/L protection Machine or transformer thermal relay is a relay that functions when
the temperature of a machine armature winding or other load-carrying
winding or element of a machine or power transformer exceeds a
predetermined value.

50 Instanttaneous O/C protection  Instantaneous overcurrent relay is a relay that functions
instantaneously on an excessive value of current.

50N Instanttaneous E/F protection 

51 IDMT O/C protection AC time overcurrent relay is a relay that functions when the ac input
current exceeds a predetermined value, and in which the input current
and operating time are inversely related through a substantial
portion of the performance range.

51N IDMT E/F protection
51G Stand by earth fault relay
52x Breaker aux.contact multiplier.

59 Over voltage Relay Overvoltage relay is a relay which operates when its input voltage is
more than a predetermined value.

59N Neutral displacement relay
60 Vector surge relay

63 Aux relay for trafo trip/alarm  Pressure switch is a switch which operates on given values, or on a
or Buckloz relay given rate of change, of pressure.

63x Trafo fault relay
64R Restricted E/F relay
64F Rotor E/F relay
80 DC Supervision relay
81 Frequency relay Frequency relay is a relay that responds to the frequency of an
electrical quantity, operating when the frequency or rate of change
of frequency exceeds or is less than a predetermined value.

85 Pilot wire relay Carrier or pilot-wire receiver relay is a relay that is operated or
restrained by a signal used in connection with carrier-current or dc
pilot-wire fault relaying.

86 Master tripping relay
87 Differential relay Differential protective relay is a protective relay that functions on
a percentage or phase angle or other quantitative difference of two
currents or of some other electrical quantities.

94 Anti pumping relay Tripping or trip-free relay is a relay that functions to trip a
circuit breaker, contactor, or equipment, or to permit immediate
tripping by other devices; or to prevent immediate reclosure of a
circuit interrupter if it should open automatically even though its
closing circuit is maintained closed.

95 Trip ckt supervision relay
96 Gas pressure low
97 PT Fuse failure relay
98 Motor protection relay

You might also like