DEFINITIONS
The initial non-operational checking for field instruments to be performed at
calibration workshop before installation, to ensure that each instrument is
functionally correct and correctly calibrated.
WORKSHOP CALIBRATION
5.1 All transmitters associated with the Process Control System and/or any other
safety system shall be calibrated / tested from the primary element
through to the output terminals. Actual pressure shall be applied to the
transmitter process connection and a full five point calibration carried out.
Full calibration tests shall be carried out on all pressure differential pressure
and DP type level transmitters.
5.2 Temperature transmitters shall have a simulated RTD input injected at the
input terminals for a full five point calibration check. RTD primary elements
shall be tested at ambient and 100°C.
5.3 Ranges used in the calibration checks shall be in accordance with the latest
instrument specification sheet. Vendor calibration sheet shall only be used
as reference documents.
Release
Air Manifold Manifold Point
Compres No.1 No.2
sor
Drain Drain
Figure 25: TYPICAL TEST SET-UP FOR PRESSURE RELIEF VALVE
3
2
Figure 26
ITEM DESCRIPTION
1 Air Regulator
2 Test Gauge
3 Test Bench with Manifold
4 Valve
5 Relief Valve/Safety Valve under Testing
OTHERS INSTRUMENTS
The following instruments will not be tested in the workshop due to safety reason
and the unavailability of the required test equipment and facilities. However, they
have to be checked by visual check and need to be calibrated on-line during
Commisioning phase.
Rotameters
Purge Meters
Calibration and tested in factory.
PD Meter
Chromatographs Analyzer
2 Oil Pressure Calibrator DPI 610 0.025%FS 0 – 135 bar With Druck
Ext. Sensor 700bar
3 Oil Pressure Calibrator DPI 615 0.025%FS 0 to 400bar Druck