Professional Documents
Culture Documents
Part 1: Gibson
Speed Control of
Refrigeration
Compressors with
intelligent Frequency
Inverters
Design considerations and experience
The control of suction pressure 1.1 Introduction compressor connected in parallel with
by varying the speed of refrigera- several fixed speed compressors, see
With speed control refrigeration Fig. 1.1.
tion compressors provides many compressors are operated outside the
advantages. The following abbreviations will be used
normal area of operation defined and
in this article:
If the installation is designed cor- specified by the manufacturer. It is
rectly then important considera- therefore very important to take certain
tions such as improved quality of electrical and refrigeration technology VsC: Variable-speed Compressor
stored goods, energy saving, im- restraints into consideration. FsC: Fixed speed Compressor
proved performance at light re- This article will investigate compressor FI: Frequency Inverter
frigeration loads and increased packs with a "master" variable-speed In the systems which are described here,
working life can be easily
achieved.
Figure 1.1:
Refrigeration
system with a
Variable-speed
Compressor
(VsC) and two
Fixed-speed
Compressors
(FsCs).
Right:
FrigoPack
intelligent
Dr. J.P. Gibson Frequency
KIMO Refrigeration HVAC Ltd., Fürth Inverter (FI)
1.2 Advantages
The following essential advantages are
obtained by continually adapting the
power of a compressor pack by control-
ling the speed of a VsC:
• Improved cooling quality by maintain-
ing a constant suction pressure* (refer
to Fig. 1.3)
• Wider range of operation of the refrig-
eration power+ (refer to Fig. 1.5)
• Increased power by increasing the
speed of the VsC+ (refer to Fig. 1.7)
• Energy saving*
• Longer compressor lifetime +
Figure 1.3: • Better possibilities of providing moni-
Typical toring, remote setting and diagnostics+
compressor
bank with 1.3 Closed-loop control range of
intelligent the refrigeration power
frequency
inverter The comparison of a compressor pack
with the following units is shown in Fig.
1.5:
− 3 / 4 x FsC (conventional multi-stage
control)
− VsC (using a master compressor regu-
lated using an FI) + 2 x FsCs.
At almost all operating points it is possi-
ble to provide the required refrigeration
power without having to frequently switch
the compressors on or off. This provides
the following decisive benefits:
• Fluctuation of the suction pressure,
caused by switching on or off a FsC
are minimized, refer to Fig. 1.4.
• The starting frequency of the compres-
sors is significantly reduced, the life-
higher than at 50 Hz in spite of the − Frame size with large motor (motor 1) -
magnetic field-weakening of the motor also for operation with a higher evapo-
These measurements and tests contra- ration temperature
dict the statement, which is often made The refrigeration-related performance
that operation in magnetic field-weaken- data of a typical semi-hermetic compres-
ing above 50 Hz can be problematical. It sor, with different motor sizes, is sche-
is incorrect to compare the thermal matically shown in Fig. 1.8.
behaviour of a semi-hermetic When a compressor is operated with
compressor motor with the thermal speed/frequency control, this represents
behaviour of an industrial motor. an increased thermal load of the motor in
It is important to carefully evaluate the the limits operating range. At a lower
Figure 1.7: Increased refrigeration maximum permissible upper speed, the volume flow of refrigerant is
power when operating a speed/frequency for the following rea- lower and at high speed, the current is
compressor at 60 Hz using a sons: higher due to the magnetic field weak-
frequency inverter • The increased refrigeration power ening. These potential problems can be
provides the necessary reserves in usually completely resolved by using the
1.6 Maximum speed/frequency of order to guarantee operation at the compressor version with the larger
a VsC (increased power) peak refrigeration power (especially in motor. This can be explained as follows:
It makes considerable sense to use an FI summer) without having to overdimen- • At the critical operating points, the
to increase the maximum speed. Almost sion the compressors in the bank electric power Pe drawn by the smaller
all of the compressors are mechanically • It is especially important to avoid over- motor (M2) is significantly greater than
designed for operation on 60 Hz electri- dimensioning the compressor bank, that of the larger motor (M1), see Fig.
cal supplies. The refrigeration power of a especially for operation in the partial 1.9.
compressor can be easily increased by load area (refer to the previous sec- • The larger motor (M1) has a larger
approx. 20% - see Fig. 1.7. tion). internal surface for cooling with refrig-
With some compressors and with some erant (suction gas cooling).
manufacturers it is often possible to 1.7 Selecting the VsC • At the specified operating point (see
increase the speed even further. The Positive experience has been gained Fig. 1.9), the larger motor (M1) has a
manufacturer must be contacted on a using the following compressor types: lower loading which means that the
case-for-case basis, specifying the winding temperature increase is sig-
installation data. Operation up to 65 Hz − Semi-hermetic reciprocating compres- nificantly lower.
(approx. 30 % increase) or even up to 70 sors
The starting phase of a VsC is of deci-
Hz (approx. 40 % increase) is often − Screw compressors sive significance for disturbance-free
possible. The application limits generally − Fully hermetic reciprocating compres- operation of the refrigeration system.
lie in the area of thermal and flow-related sors from several manufacturers This especially applies to small com-
stressing in the discharge area of the − Scroll compressors from several pressors with two cylinders which require
compressor. manufacturers a high starting torque. According to pub-
The measurement results of a semi- − Open and membrane type compres- lished information[2], torque reserves of
hermetic compressor with a 400 V, 50 sors. 60 % are required for starting.
Hz motor winding are shown in Fig. 1.6. In the field, the compressors must be
The following should be noted: The reciprocating compressor, which is
well-established worldwide, will now be able to start at high evaporation pres-
• The speed (Fmech) above 50 Hz in- discussed in more detail. sures. This means that it is not sufficient
creases slightly lower than proportional to just consider a particular operating
Almost every manufacturer offers two point. Example: If the power is inter-
with the electrical frequency due to the
motor versions for every mechanical rupted for several minutes, the evapora-
decreasing magnetic flux in the motor
frame size: tion pressure rapidly increases, the con-
(magnetic field weakening)
− Frame size with small motor (motor 2) densation pressure is still high – and the
• The refrigeration-related power (Qo)
for operation with restricted suction required starting torque is now quite
also increases slightly lower than pro-
pressure or limited evaporation tem- significant.
portional (approx. 30 % increased
perature
power at 70 Hz compared with opera-
tion at 50 Hz)
• The temperature of the winding
(Twind) for operation at 60 Hz is lower
than that for operation at 50 Hz due to
the higher volume flow. However, this
is a characteristic of the compressor
being tested and cannot be used to
make a general statement
• For the compressor being tested, the
temperature at 70 Hz is insignificantly
1,00
R404A/30-M1
0,90
R404A/40-M1
R404A/50-M1
0,80 R404A/30-M2
R404A/40-M2
0,70 R404A/50-M2
R134a/50-M1
Pe [pu]
0,60 R134a/60-M1
R134a/70-M1
0,50 R134a/30-M2
R134a/40-M2
0,40
R134a/50-M2
0,30
0,20
0,00 2,00 4,00 6,00 8,00 10,00
Pressure / Druck Po [bara]
Figure 1.9: Relative electric power consumption Pe [pu] of a compressor as a function of the suction pressure Po when
using motors M2 (small) and M1 (large) at a condensing temperature of 30, 40, and 50 °C
If the compressor was not able to start, It is necessary to use what first appears three FsCs. An external compressor
then the motor winding does not have an to be an over-dimensioned FI in order to pack step-controller is not required and
opportunity to cool down, the winding ensure reliable operation. This means is also not permissible (otherwise there
temperature and therefore the winding that the FI is mainly dimensioned to would be competing with the integrated
resistance significantly increase at each achieve the correct starting torque. suction pressure controller). The mini-
start attempt. This generally ends in the There is nothing worse than a mum running and switch-off times,
motor being tripped by its thermal ther- compressor that cannot start. This specified by the various compressor
mistor monitoring. The motor winding is means that it does not make sense to manufacturers, are taken into account in
significantly stressed. dimension an FI according to the rated the software. A block diagram of the
The authors of this article recommend operating point as is generally the case closed-loop control and common system
that this technology is ONLY applied for for fan and pump drives. control are shown in Fig. 1.10.
compressors with larger motors. The This new technology can only be widely In order to increase the system availabil-
additional costs for the compressor com- used if the necessary rated power of the ity, a high-pressure limiter control func-
pared with the aggravation associated FI has been clearly defined. The authors tion is optionally available. This is
with starting problems is negligible. have drawn-up so-called compressor extremely useful in the following cases:
"Cross Reference Lists" [3] for this pur- • When the condensing power for high
1.8 Selecting the rated power of pose. refrigeration power is not sufficient in
the FIs The required FIs for all common com- summer
pressors summarized in the form of a • There is dirt or obstructions in the
The following criteria should be taken data base taking into account experience
into consideration: condenser
gained in the field with "problematical
• Required starting torque depending on • One or more condenser fans have
compressors".
the compressor design and/or the failed
number of cylinders, refer for example 1.9 Closed-loop control related • The evaporator has ice build-up when
to [2] aspects used in the heat pump mode
• Possible measures to reduce the start- • Noise abatement restrictions only
ing torque, e.g.: The integrated closed-loop suction pres- allow the condenser, depending on the
sure control ensures that the speed of time of day, to be used at reduced
− Start unloading arrangement (sole- the VsC is set corresponding to the
noid valve between the pressure and speed
actual refrigeration requirement. An FsC
suction sides of the compressor
is only switched in if the refrigeration When a limit pressure is exceeded,
opened during starting) the speed of the VsC is
power of the VsC is no longer sufficient.
− Pressure limiter in the suction gas The integrated refrigeration software of automatically reduced.
line or at the evaporator the FrigoPack system can control up to