8BK80
Indoor Metal-clad Switchgear with Vacuum Circuit Breaker
on withdrawable truck upto 36 kV

Answers for energy.


Indoor Metal-clad Switchgear with Vacuum Circuit
Breaker on withdrawable truck upto 36 kV

Construction Special features


• Class PM air insulated switchgear • Circuit breaker mounted on withdrawable truck
• Single busbar system • Safe easy truck movement behind closed cubicle door
• Circuit breaker mounted on withdrawable truck • Earthed metal partitions and shutters
• Hollow triangular busbars
Standards • Shutters with rotational movement which reduces
• I.S. 3427 and IS 12729 electrical stresses
• IEC 62271-100 • Access to cable terminals from the rear
• IEC 62271-200 • Individually padlockable shutters for bus and cable side
• IEC 62271-1 • Simplicity and robustness of operating mechanism with
minimum linkages
Personnel safety
• Independent pressure relief vents for all HT compartments
• All switching operations performed with front door
• Cable termination height upto 900 mm
closed
• Earthed metal partitions and shutters prevent contact with
live parts

Tolerance to environment
• Full metal enclosure ensures high resistance to ingress and
interference under all operating conditions
• Insulators have high anti-tracking qualities

Operational security /Maintenance


• Full mechanical interlocking
• Access door fully integrated in interlock system
• Service-proven maintenance free vacuum circuit breaker,
hermetically sealed vacuum interrupters, low maintenance
drive mechanism

Technical data
Rated Voltage, Frequency (50Hz) 24 kV 36 kV
Rated Current of the Feeders Upto 2500 A* Upto 2500 A*
Rated Current of the Busbar Upto 3150 A* Upto 3150 A*
Rated Power Frequency Withstand Voltage (RMS) 1min 50 kV 70 kV
Rated Lighting Impulse withstand Voltage (peak) 1.2/50 Micro sec. 125 kV 170 kV
Rated Short Circuit Breaking Current Upto 26.3 kA Upto 26.3 kA
Rated Short Time Withstand Current (3 sec) Upto 26.3 kA Upto 26.3 kA
Dimensions (standard)
Width (mm) 1000 1000
Height (mm) 2300** 2550**
Depth (mm) 2320** 2320**
* greater than 1250A on request
** LV chamber/panel height/depth variable as per number of equipments to be mounted

2
Classification of 8BK80-36kV Switchgear
According to IEC 62271-200

Resistance to internal arcs Construction and design


Classification    IAC Class of partitions PM
Accessibility Service continuity category LSC 2B
-  Front    Type A Compartment accessibility (standard)
-  Lateral    Type A -  Busbar compartment Tool-based
-  Rear    Type A -  Switching-device compartment Interlock-based
Test current    26.3 kA -  Low-voltage compartment Tool-based
Test duration    0.1 Sec -  Connection compartment Tool-based
Rear connection Tool-based

Standards, specifications, and covers do not open. as a result of paint or sticker outside the enclosure.
guidelines Deformations are accepted burning are also excluded. • To attain the maximum
conditionally. rated normal currents, the
Resistance to internal arc –  Criterion 5
faults –  Criterion 2 panels may be provided
The enclosure remains with natural or forced
• Safety of operating No fragmentation of connected to its earthing ventilation.
personnel ensured by enclosures occurs within point.
tests to verify resistance to the time specified for test. Protection against solid
internal arc faults. Projections of small parts up foreign bodies, electric shock
Current-carrying capacity
to 60g are accepted. and ingress of water.
• Internal arc tests in • According to IEC 62
accordance with IEC 62 8Bk80 switchgear fulfills acc.
–  Criterion 3 271-200 current-carrying
271-200, Annex A. to the standards
capacities refer to the
Arcing does not cause holes -IEC 62 271-200
• The switchgear compiles following ambient
in the accessible sides up to -IEC 60 529.
with criteria 1 to 5 temperatures:
a height of 2m. –  Maximum of The following degrees of
specified in the mentioned
standards for the basic 24-hour mean +350 C Protection:
–  Criterion 4
version up to 26.3 kA –  Maximum +400 C - Enclosuer: IP4X
Indicators do not ignite due - Compartments: IP2X
• Definitions of criteria: to the effect of hot gases. • The current-carrying
Ignition caused by glowing capacity of the panels
–  Criterion 1 and busbars depends on
particles rather than hot
Correctly secured doors gases is allowed. Ignitions the ambient temperature

The perfect solution for every application


Power supply systems
• Power supply companies
• Power generation companies
Industry
• Cement industry
• Automobile industry
• Metal industry
• Rolling mills
• Textile and food industries
• Chemical and fertilizer
• Oil and Gas
• Petrochemical plants
• Diesel power plants
• Distribution stations

3
ISO 9001, ISO 14001
Certification

Western Region Eastern Region Southern Region


Mumbai Kolkata Chennai
3rd Floor, R&D Tech Centre 43, Shanti Palli 144, Mahatma Gandhi Road,
Opposite Airoli Railway Station Rasbihari Bypass Connector P.O. Box No. 3323
Thane Belapur Road Kolkata - 700 042, West Bengal (India) Chennai - 600 034, Tamil Nadu (India)
Thane - 400 601, Maharashtra (India) Tel.: +91 33 3093 9302 Tel.: +91 44 3047 4444
Tel.: +91 22 2764 5136 Fax: +91 33 3093 9012 Fax: +91 44 3047 4450
Fax: +91 22 2764 5148
Northern Region International Sales
Vadodara
3rd Floor, OHM Business Park Delhi R&D Technology Centre
Opp. Balaji Hospital 3rd Floor, Tower - B 2nd Floor, Kalwa Works, PO Box
Ellora Park (East), Subhanpura Plot No. 6 - A, Sector - 18 Thane Belapur Road
Vadodara - 390 023, Gujarat (India) Maruti Industrial Area, HUDA Thane - 400 601, Maharashtra (India)
Tel.: +91 265 669 2111 Gurgaon - 122 015, Haryana (India) Tel.: +91 22 2764 5021
Fax: +91 265 669 2190 Tel.: +91 124 3837377 Fax: +91 22 2764 5024
Fax: +91 124 3836620
Pune
Vasant Vihar
Shirole Road
Pune - 411 004, Maharashtra (India)
Tel.: +91 20 2570 6000
Fax: +91 20 2570 6060

Siemens Ltd. ENE-10-005-009


Energy Sector
Power Distribution - Medium Voltage
R&D Building
Thane Belapur Road
Thane 400 601
India
Tel.: +91 22 2764 5005 / 6
Fax: +91 22 2764 0030
Product upgradation is a continuous process. Hence,
www.siemens.com/medium-voltage-devices Printed in India data in this catalog is subject to change without prior