You are on page 1of 56

1 2 3 4 5 6 7 8

A
11KV GENERATOR PROTECTION PANEL A

LIST OF DOCUMENTS
B DRAWING DESCRIPTION. REVISION DATE ISSUE B

3269PN491-GL-01 GENERAL ARRANGEMENT & LEGEND B 3/31/2012 For Approval


3269PN491-S-01 SCHEMATIC DIAGRAM OF GENERATOR PROTECTION PANEL B 3/31/2012 For Approval
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

C
K Digitally signed by K
POORNACHANDRA RAO
DN: cn=K POORNACHANDRA
C

POORNAC RAO, c=IN, o=BHEL, ou=BHEL


RCPURAM,
email=kpcrao@bhelhyd.co.in

HANDRA Reason: Reviewed by BHEL.


Drawing is revised based on your
comments on Rev-A. Pls. check
D
RAO and approve.
Date: 2012.04.02 10:00:14 +05'30'
D

PANEL TYPES : +R1

E
CUSTOMER: BHARAT HEAVY ELECTRICALS LTD. E
HYDERABAD
LIST OF REFERNCE DOCUMENTS CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA.
1) SLD: 1-561-01-31581, REV-02
2) TRIP LOGIC DIAGRAM: 1-561-01-31582, REV-01 CONSULTANT: DEVELOPMENT CONSULTANTS
PVT LTD.
PROJECT: ROHIT FERRO TECH LTD.
F 67.5MW CAPTIVE POWER PLANT, JAJPUR F
Schneider Electric Infrastructure Ltd
C117A00076 DATED:16-01-2012
CHENNAI , INDIA
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

B B
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

SHEET DESCRIPTION
C C
000 INDEX SHEET
001 GENERAL ARRANGEMENT
002 BILL OF MATERIALS RELAY PANEL: +R1
003 BILL OF MATERIALS RELAY PANEL: +R1
004 BILL OF MATERIALS RELAY PANEL: +R1
005 BILL OF MATERIALS RELAY PANEL: +R1
006 BILL OF MATERIALS RELAY PANEL: +R1

D D

E E

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PREPARED : GD REVISION: B SHT : 000 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
INDEX SHEET DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 001
PO. No.& Date: C117A00076 DATED:16-01-2012
DRG. NO.: 3269PN491-GL-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

800

+R1
A cl A

60.11G 60.22G 60.31G 60.32G

64R

B B
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

GPRM

C GPRR C

2200

86A1 86B1 86C1 195

D D
86A2 86B2 86C2 295
BLKC

BLKD
BLKA

BLKB

50ZX

E E

ANTIVIBRATION PAD
100

15

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PREPARED : GD REVISION: B SHT : 001 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. GENERAL ARRANGEMENT APPROVED : APS CONT: 002
RELAY PANEL
PO. No.& Date: C117A00076 DATED:16-01-2012
+R1 DRG. NO.: 3269PN491-GL-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

FRONT VIEW EQUIPMENTS:


Designation Manufacturer Material Description Comment
A 60.11G ALSTOM MVAPM32D1AA2001A VOLTAGE BALANCING RELAY , 110V 50 HZ : FLAG-YES : 2M 2C SR :110-125/220-250V DC WD:F1MVAPM32001 FOR PT-1,2,3(CORE-2) A

60.22G ALSTOM MVAPM32D1AA2001A VOLTAGE BALANCING RELAY , 110V 50 HZ : FLAG-YES : 2M 2C SR :110-125/220-250V DC WD:F1MVAPM32001 FOR PT-4,5,6(CORE-2)

60.31G ALSTOM MVAPM32D1AA2001A VOLTAGE BALANCING RELAY , 110V 50 HZ : FLAG-YES : 2M 2C SR :110-125/220-250V DC WD:F1MVAPM32001 FOR PT-7,8,9(CORE-1)

60.32G ALSTOM MVAPM32D1AA2001A VOLTAGE BALANCING RELAY , 110V 50 HZ : FLAG-YES : 2M 2C SR :110-125/220-250V DC WD:F1MVAPM32001 FOR PT-7,8,9(CORE-2)

64R P39191P00A ROTOR E/F INJECTION UINT, AUX VOTL: 60-250V DC/100-240V AC, CASE: 80TE(SPECIAL), MOUNTING: PANEL

B HIGH SPEED TRIP RELAY, HI BURDEN : FLAG-YES : 220V DC(50 TO 120%) : 16M 4B ER/HR CONTACT CONFIG: B
86A1 EASUN TR241-220V-16M4B-HRER-E4
CASE SIZE:E4 :WIRING DIAGRAM No: 8112W0084.
HIGH SPEED TRIP RELAY, HI BURDEN : FLAG-YES : 220V DC(50 TO 120%) : 16M 4B ER/HR CONTACT CONFIG:
86A2 EASUN TR241-220V-16M4B-HRER-E4
CASE SIZE:E4 :WIRING DIAGRAM No: 8112W0084.
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

HIGH SPEED TRIP RELAY, HI BURDEN : FLAG-YES : 220V DC(50 TO 120%) : 16M 4B ER/HR CONTACT CONFIG:
86B1 EASUN TR241-220V-16M4B-HRER-E4
CASE SIZE:E4 :WIRING DIAGRAM No: 8112W0084.
HIGH SPEED TRIP RELAY, HI BURDEN : FLAG-YES : 220V DC(50 TO 120%) : 16M 4B ER/HR CONTACT CONFIG:
86B2 EASUN TR241-220V-16M4B-HRER-E4
CASE SIZE:E4 :WIRING DIAGRAM No: 8112W0084.
HIGH SPEED TRIP RELAY, HI BURDEN : FLAG-YES : 220V DC(50 TO 120%) : 16M 4B ER/HR CONTACT CONFIG:
86C1 EASUN TR241-220V-16M4B-HRER-E4
CASE SIZE:E4 :WIRING DIAGRAM No: 8112W0084.
C HIGH SPEED TRIP RELAY, HI BURDEN : FLAG-YES : 220V DC(50 TO 120%) : 16M 4B ER/HR CONTACT CONFIG: C
86C2 EASUN TR241-220V-16M4B-HRER-E4
CASE SIZE:E4 :WIRING DIAGRAM No: 8112W0084.
TRIP COIL SUPERVISION RELAY, 2M 2B SR : FLAG-REV : 220V DC(80 TO 120%); 400ms RESET DELAY :WIRING
195 EASUN XR351-220V-2M2B-SR-E4
DIAGRAM No: 8112W00132
TRIP COIL SUPERVISION RELAY, 2M 2B SR : FLAG-REV : 220V DC(80 TO 120%); 400ms RESET DELAY :WIRING
295 EASUN XR351-220V-2M2B-SR-E4
DIAGRAM No: 8112W00132

BLKA SWITRON ERMLG 01 TEST BLOCK

BLKB SWITRON ERMLG 01 TEST BLOCK

D BLKC SWITRON ERMLG 01 TEST BLOCK D

BLKD SWITRON ERMLG 01 TEST BLOCK

GEN PROTN. RELAY, AUX VOTL: 110-250V DC/100-240V AC, INOM:1A/5A, VNOM:100-120V AC, OPTO I/P: 16, O/P
GPRM SCHNEIDER ELECTRIC P343316Q6M0368K MAIN-1 PROTN
CONTACT: 32, RTD I/P: 10, CLIO I/P: 4, CLIO O/P: 4, PROTOCOL: MODBUS, CASE: 80TE, MOUNTING: PANEL
GEN PROTN. RELAY, AUX VOTL: 110-250V DC/100-240V AC, INOM:1A/5A, VNOM:100-120V AC, OPTO I/P: 16, O/P
GPRR SCHNEIDER ELECTRIC P343316Q6M0368K MAIN-2 PROTN
CONTACT: 32, RTD I/P: 10, CLIO I/P: 4, CLIO O/P: 4, PROTOCOL: MODBUS, CASE: 80TE, MOUNTING: PANEL

E E

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PREPARED : GD REVISION: B SHT : 002 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
BILL OF MATERIALS RELAY PANEL: +R1 DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 003
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-GL-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

REAR VIEW EQUIPMENTS:

Designation Manufacturer Material Description Comment


A A
30A RELPOL GBR42014231125WT MINIATURE AUXILIARY RELAY;MODEL:R4 ;4 CHANGE OVER;AUX SUPPLY: 220V DC

30B RELPOL GBR42014231125WT MINIATURE AUXILIARY RELAY;MODEL:R4 ;4 CHANGE OVER;AUX SUPPLY: 220V DC

30C RELPOL GBR42014231125WT MINIATURE AUXILIARY RELAY;MODEL:R4 ;4 CHANGE OVER;AUX SUPPLY: 220V DC

30D RELPOL GBR42014231125WT MINIATURE AUXILIARY RELAY;MODEL:R4 ;4 CHANGE OVER;AUX SUPPLY: 220V DC

CIL IMTECH/WIPRO/PHILIPS CIL-11W-230VAC COMPACT FLOURESCENT LAMP - 11W 230V AC

B B
E1 COOPER BUSSMANN/GE - LINK

E2 COOPER BUSSMANN/GE - LINK


This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

E3 COOPER BUSSMANN/GE - LINK

E4 COOPER BUSSMANN/GE - LINK

E5 COOPER BUSSMANN/GE - LINK

C C
E6 COOPER BUSSMANN/GE - LINK

E7 COOPER BUSSMANN/GE - LINK

E8 COOPER BUSSMANN/GE - LINK

E8 COOPER BUSSMANN/GE - LINK

E9 COOPER BUSSMANN/GE - LINK

D E9 COOPER BUSSMANN/GE - LINK D

E10 COOPER BUSSMANN/GE - LINK

FS1 COOPER BUSSMANN/GE - FUSE - 10A, DC

FS2 COOPER BUSSMANN/GE - FUSE - 10A, DC

FS3 COOPER BUSSMANN/GE - FUSE - 10A, DC

E FS4 COOPER BUSSMANN/GE - FUSE - 10A, DC E

FS5 COOPER BUSSMANN/GE - FUSE - 6A, DC

FS6 COOPER BUSSMANN/GE - FUSE - 6A, DC

FS7 COOPER BUSSMANN/GE - FUSE - 4A, DC

FS8 COOPER BUSSMANN/GE - FUSE - 4A, DC

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PREPARED : GD REVISION: B SHT : 003 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
BILL OF MATERIALS RELAY PANEL: +R1 DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 004
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-GL-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

REAR VIEW EQUIPMENTS:

Designation Manufacturer Material Description Comment


A A
FS9 COOPER BUSSMANN/GE - FUSE - 4A, DC

FS10 COOPER BUSSMANN/GE - FUSE - 4A, DC

FS11 COOPER BUSSMANN/GE - FUSE - 6A, DC

FS12 COOPER BUSSMANN/GE - FUSE - 6A, DC

FS13 COOPER BUSSMANN/GE - FUSE - 4A, DC

B B
FS14 COOPER BUSSMANN/GE - FUSE - 4A, DC

FS15 COOPER BUSSMANN/GE - FUSE - 4A, DC


This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

FS16 COOPER BUSSMANN/GE - FUSE - 4A, DC

FS17 COOPER BUSSMANN/GE - FUSE - 4A, DC

FS18 COOPER BUSSMANN/GE - FUSE - 4A, DC

C C
FS19 COOPER BUSSMANN/GE - FUSE - 4A, DC

FS20 COOPER BUSSMANN/GE - FUSE - 4A, DC

FS21 COOPER BUSSMANN/GE - FUSE - 4A, DC

FS22 COOPER BUSSMANN/GE - FUSE - 4A, DC

FS23 COOPER BUSSMANN/GE - FUSE - 4A, DC

D FS24 COOPER BUSSMANN/GE - FUSE - 4A, DC D

FS25 COOPER BUSSMANN/GE - FUSE - 4A, DC

FS26 COOPER BUSSMANN/GE - FUSE - 4A, DC

FS91 COOPER BUSSMANN/GE - FUSE - 16A, AC

FS111 COOPER BUSSMANN/GE - FUSE - 2A, AC

E FS131 COOPER BUSSMANN/GE - FUSE - 2A, AC E

FS151 COOPER BUSSMANN/GE - FUSE - 2A, AC

FS211 COOPER BUSSMANN/GE - FUSE - 2A, AC

FS213 COOPER BUSSMANN/GE - FUSE - 2A, AC

FS231 COOPER BUSSMANN/GE - FUSE - 2A, AC

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PREPARED : GD REVISION: B SHT : 004 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
BILL OF MATERIALS RELAY PANEL: +R1 DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 005
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-GL-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

REAR VIEW EQUIPMENTS:

Designation Manufacturer Material Description Comment


A A
FS233 COOPER BUSSMANN/GE - FUSE - 2A, AC

FS251 COOPER BUSSMANN/GE - FUSE - 2A, AC

FS253 COOPER BUSSMANN/GE - FUSE - 2A, AC

FS311 COOPER BUSSMANN/GE - FUSE - 2A, AC

FS331 COOPER BUSSMANN/GE - FUSE - 2A, AC

B B
FS351 COOPER BUSSMANN/GE - FUSE - 2A, AC

FS411 COOPER BUSSMANN/GE - FUSE - 2A, AC


This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

FS431 COOPER BUSSMANN/GE - FUSE - 2A, AC

FS451 COOPER BUSSMANN/GE - FUSE - 2A, AC

FS511 COOPER BUSSMANN/GE - FUSE - 2A, AC

C C
FS531 COOPER BUSSMANN/GE - FUSE - 2A, AC

FS551 COOPER BUSSMANN/GE - FUSE - 2A, AC

FS611 COOPER BUSSMANN/GE - FUSE - 2A, AC

FS631 COOPER BUSSMANN/GE - FUSE - 2A, AC

FS651 COOPER BUSSMANN/GE - FUSE - 2A, AC

D HS SWITRON HS-230VAC HEATER SWITCH D

HT SOFIA/TELELEC HT-60W-230AC HEATER 230V AC 50HZ, 60W

LK91 COOPER BUSSMANN/GE - LINK

LK171 COOPER BUSSMANN/GE - LINK

LK271 COOPER BUSSMANN/GE - LINK

E LK371 COOPER BUSSMANN/GE - LINK E

LK471 COOPER BUSSMANN/GE - LINK

LK571 COOPER BUSSMANN/GE - LINK

LK671 COOPER BUSSMANN/GE - LINK

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PREPARED : GD REVISION: B SHT : 005 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
BILL OF MATERIALS RELAY PANEL: +R1 DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 006
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-GL-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

REAR VIEW EQUIPMENTS:

Designation Manufacturer Material Description Comment


A A
PS ANCHOR PS-5-15A-230VAC POWER SOCKET 5/15A WITH SWITCH + 3PIN PLUG, 230V AC

R1 - - RESISTOR, 3.3K-OHMS, 30W

R2 - - RESISTOR, 3.3K-OHMS, 30W

R3 - - RESISTOR, 3.3K-OHMS, 30W

R4 - - RESISTOR, 3.3K-OHMS, 30W

B B
R5 - - RESISTOR, 3.3K-OHMS, 30W

R6 - - RESISTOR, 3.3K-OHMS, 30W


This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

RR - - CLIO REPEATER FOR INJECTION KIT

TS MAVIS/ APT CTRLS/TELELECTS-30-90DEG-230VAC THERMOSTAT 230V AC, 30-90 DEG

X1 CONNECTWELL STH4 NON DISCONNECTING TERMINAL BLOCK

C C
X2 CONNECTWELL STH4DTSH DISCONNECTING TERMINAL BLOCK

X3 CONNECTWELL STH4DT DISCONNECTING TERMINAL BLOCK

X4 CONNECTWELL STH4 NON DISCONNECTING TERMINAL BLOCK

X5 CONNECTWELL STH4 NON DISCONNECTING TERMINAL BLOCK

X7 CONNECTWELL STH4 NON DISCONNECTING TERMINAL BLOCK

D X8 CONNECTWELL STH4 NON DISCONNECTING TERMINAL BLOCK D

X100 CONNECTWELL STH4 NON DISCONNECTING TERMINAL BLOCK

X101 CONNECTWELL STH4 NON DISCONNECTING TERMINAL BLOCK

X200 CONNECTWELL STH4 NON DISCONNECTING TERMINAL BLOCK

X201 CONNECTWELL STH4 NON DISCONNECTING TERMINAL BLOCK

E E

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PREPARED : GD REVISION: B SHT : 006 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
BILL OF MATERIALS RELAY PANEL: +R1 DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: NIL
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-GL-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
SHEET DESCRIPTION SHEET DESCRIPTION
000 INDEX SHEET 046 RELAY LED CONFIGURATION
001 LIST OF SYMBOLS 047 TERMINAL BLOCK REFERENCE
A 002 SINGLE LINE DIAGRAM NO_S… A
003 SINGLE LINE DIAGRAM
004 GROUP-1 OUTRIP LOGIC DIAGRAM
005 GROUP-2 TRIP LOGIC DIAGRAM
006 AC DISTRIBUTION
007 DC DISTRIBUTION
008 DC DISTRIBUTION
009 VT DISTRIBUTION
010 VT DISTRIBUTION
B B
011 VT DISTRIBUTION
012 VOLTAGE BALANACE
013 GEN PROTN-GPRM CT CIRCUIT
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

014 GEN PROTN GPRM-PT CKT


015 GEN PROTN-GPRM OPTO CKT
016 GEN PROTN-GPRM OPTO CKT
017 GEN PROTN-GPRM CLIO CKT
018 GEN PROTN-GPRR CT CIRCUIT
019 GEN PROTN GPRR-PT CKT
C C
020 GEN PROTN-GPRR OPTO CKT
021 GEN PROTN-GPRR OPTO CKT
022 GEN PROTN-GPRR CLIO CKT
023 ROTOR E/F CKT
024 CONTACT MULTIPLICATION CKT.
025 UNIT LOCKOUT RELAY-86A1
026 TURBINE LOCKOUT RELAY-86B1
027 GENERATOR LOCKOUT RELAY-86C1
028 UNIT LOCKOUT RELAY-86A2
D D
029 TURBINE LOCKOUT RELAY-86B2
030 GENERATOR LOCKOUT RELAY-86C2
031 GCB-52G CLOSING&TRIP COIL-1
032 GCB-52G TRIP COIL-2
033 GEN FIELD CB & AVR TRIP
034 TURBINE CB TRIP & AUTO TRIP
035 ANNUNCIATION CONTACT DISTRIBUTION
036 ANNUNCIATION CONTACT DISTRIBUTION
E 037 ANNUNCIATION CONTACT DISTRIBUTION E
038 ANNUNCIATION CONTACT DISTRIBUTION
039 ANNUNCIATION CONTACT DISTRIBUTION
040 ANNUNCIATION CONTACT DISTRIBUTION
041 SPARE CONTACT DISTRIBUTION
042 SPARE CONTACT DISTRIBUTION
043 TEST BLOCK DISTRIBUTION
044 RELAY CONTACT DISTRIBUTION
045 RELAY CONTACT DISTRIBUTION
F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 000 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
INDEX SHEET DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 001
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

LIST OF STANDARD SYMBOLS


SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION
A A

COMPACT NORMALLY OPEN NON-DISCONNETING TERMINAL GROUP STANDARDS


FLOURESCENT RESISTOR CONTACT SELF TB FOR INTER PANEL
LAMP RESET BUS WIRING TB REF FUNCTION
X1 AC/DC CIRCUITS
NON-DISCONNETING X2 CT CIRCUITS
CONTROL / NORMALLY CLOSE
DOOR/HEATER TB FOR SCADA/BCU
SELECTOR CONTACT SELF X3 PT CIRCUITS
SWITCH
SWITCH RESET X4 CONTROL INPUTS (TO OPTO/CONT MUL. RELAY)
NON-DISCONNETING
TB X5 CONTROL OUTPUTS (TO CB CONTROL)
CHANGEOVER X6 CONTROL OUTPUTS (TO ISOL./ESW. CONTROL)
B HEATER TEST BLOCK CONTACT SELF TB PRIMARY X7 SPARE OUTPUTS B
RESET EQUIPMENTS X8 TEMP SCANNER/SCADA/RTU/DCS CKTS
X9 INDICATION/ANNUNCIATON CKTS
DIODE
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

SW POWER NORMALLY OPEN X9-DI-SLOT BCU DI INPUTS


POTENTIO
SOCKET WITH CONTACT HAND X9-DO-SLOT BCU DO INPUTS
METER
SWITCH RESET X9-AI-SLOT BCU AI INPUTS
SEMAPHORE X10 FOR INTER PANEL CABLES
X100 BUS WIRING CT/PT CKTS (INTRA-BAY)
NORMALLY CLOSE X101-X109 BUS WIRING CONTROL CKTS (INTRA-BAY)
POTENTIAL CONTACT HAND X200 BUS WIRING CT/PT CKTS (INTER-BAY)
THERMOSTAT
TRANSFORMER CLIO INPUT
C RESET X201-X209 BUS WIRING CONTROL CKTS (INTER-BAY) C

CHANGEOVER
CURRENT
FUSE CONTACT HAND CLIO OUTPUT
TRANSFORMER
RESET

BUS WIRE FERRULE NUMBERING STANDARDS


LINK REPRESENTATION
+

SOURCE / TARGET FERRULE CIRCUIT


DIGITAL OPTO "A" CT CIRCUIT-MAIN PROTECTION
POWER SUPPLY
D INPUT CT CIRCUIT-BUSBAR PROTECTION D
NORMAL WIRE
"B"
MCB REPRESENTATION "C" CT CIRCUIT-BACKUP PROTECTION
- SOURCE / TARGET "D" CT CIRCUIT-METERING
"E" VT CIRCUIT-PROTECTION/METERING
"G" VT CIRCUIT-SYNCHRONISING
INDICATING "H" AUXILARY AC CIRCUIT
LAMPS SELT-RESET SLOW "J" AUXILARY DC CIRCUIT
SELF-RESET
OPERAING COIL "K" CONTROL CIRCUIT
COIL WITH/
WITH REVERSE/
WITHOUT FLAG "L" INDICATION & ALARM CIRCUITS
PUSH BUTTON FORWARD FLAG
"P" DC CIRCUIT- BUSBAR PROTECTION CIRCUIT
NC CONTACT
E "S" SCADA/EVENT LOGGER/DAS CIRCUITS E
"U" SPARE CONTACTS
PUSH BUTTON
ANNUNCIATOR
NO CONTACT
HAND-RESET WINDOW INPUT
COIL WITH/
WITHOUT FLAG
METROSIL
DISCONNETING TB

NOTE: RELAY CONTACTS SHOWN WITH CONTACT DE ENERGIZED CONDITION.

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 001 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
LIST OF SYMBOLS DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 002
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

E
B
A

D
C
220kV,1000A,40kA FOR 3sec,50HZ MAIN BUS

PROJECT
ES

1
1

GTCB

ES

HYDERABAD
GEN. TR.
UAT-I 80MVA, 230/11KV UAT-II
8MVA,11KV/6.9KV,Z=7% Z=12.5% OFAF 8MVA,11KV/6.9KV,Z=7%
Dyn1 ONAN/ONAF OLTC WITH +5% @2.5% Dyn1 ONAN/ONAF
OCTC +5% @ 2.5% OCTC +5% @ 2.5%

: ROHIT FERRO TECH LTD.

PO. No.& Date: C117A00076 DATED:16-01-2012


TO UNIT SWITCHGEAR
TO UNIT SWITCHGEAR

2
2

GCB CUBICLE
VT
TO SYNCHRONIZATION

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD.


11kV/√3/110V/√3/110V/√3/110V/√3
75VA, CL: 0.2,3P,3P

67.5MW CAPTIVE POWER PLANT, JAJPUR


LA1,2,3

ES

M
M ISOLATOR

GCB
ES

3
3

*FROM
SYNCH PT

PVT LTD.
SC 1,2,3 PTSP CUBICLE FOR CUSTOMER USE/DCS
(4-20)mA DC
LA1,2,3
60 60 T2 T2
V F
PT 1,2,3 G12 G11 V HZ
SHORTING ARRANGEMENT MCB1 3 1
VSS DF DV SYN
F1,2,3

**IPBD MCB2
AS 25G SW
CUSTOMER’S SCOPE

CONSULTANT: DEVELOPMENT CONSULTANTS


BHEL’S SCOPE PT 4,5,6 DIGITAL CLK
MCB3

CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA.


F4,5,6

4
4

MCB4

60
G22

PT 7,8,9 60 60
MCB6 G32 G21

F7,8,9 SPARE
MCB5
60
G31

5
5

CT 13,14,15 3

CT 16,17,18 3
Ve
MV T1 T2 T2 T1 R T2 T3 T2 R T1 T1
A1 A2 A3 MW PF MVA TVM
AR W A VA W W VA V F
CT-19,20,21 3 M PF M M M M
AVR Ie

NV RS 485 COMM. TO TURBINE


PORT(DCS) (4-20mA DC) MFGR
** FOR CUSTOMER USE
EXF (4-20mA DC)

PANEL TYPE : +R1


AF

6
6

CT 1,2,3

86 86 86
A B C
SINGLE LINE DIAGRAM

95 95 95
CT 4,5,6 3 GPR 1 GPR 2 A B C
PMG BLEX DW GF 24G 59G1 24G 59G1
27G 59G2 27G 59G2
64R 32G 64G1 32G 64G1
TS
GENERATOR G 37G 64G2 37G 64G2
TITLE : 11KV GENERATOR PROTECTION PANEL

27/40G 64G3 27/40G 64G3


40G 78G 40G 78G
46G 81G1 46G 81G1
50G 81G2 50G 81G2
50LBB 81G3 50LBB 81G3
7
7

51G1 81G4 51G1 81G4


CT 24,25,26 FOR PERFORMANCE TESTING 51V 87G 51V 87G
3

CT 7,8,9
3
PREPARED : GD
REVIEWED : THY
APPROVED : APS

CT 10,11,12
3

FOR OVER ALL DIFFERENTIAL


CUSTOMER’S SCOPE

CT 27,28,29
3 PROTECTION
DRG. NO.: 3269PN491-S-01

S01
REVISION: B

SLD
DATE: 3/31/2012

LINK
1 1
8
8

S01 CT-22 CT-23 S01


SLD SLD
**NGT **LR
SHT : 002

CONT: 003
F
E
B
A

D
C
1 2 3 4 5 6 7 8

PROTECTIVE RELAYS
A LEGEND: A
G GENERATOR 70MW, 11KV, 3000RPM, 0.8PF 24G V/HZ PROTECTION (GEN. OVER FLUXING)
AVR AUTOMATIC VOLTAGE REGULATOR 27G, 27/40G UNDER VOLTAGE RELAYS
PMG PERMANENT MAGNET GENERATOR 32G,37G REVERSE & LOW FORWARD POWER RELAY
BLEX BRUSHLESS EXCITER 40G LOSS OF EXCITATION RELAY
DW DIODE WHEEL 46G NEGATIVE PHASE SEQUENCE CURRENT RELAY
EXF GENERATOR EXCITER FIELD 50G DEAD MACHINE PROTECTION
GF GENERATOR FIELD 50LBB BREAKER FAILURE PROTECTION
TS 32 POINT GENERATOR TEMPERATURE SCANNER 51G1 DEFINITE TIME OVER CURRENT RELAY
A1,A2,A3 AMMETER FOR GENERATOR STATOR CURRENT (5000A) 51V VOLTAGE RESTRAINT OVER CURRENT RELAY
AF GENERATOR FIELD AMMETER (0-1200A) 59G1,59G2 OVER VOLTAGE PROTECTION STAGE-1 & 2
MW MEGAWATT METER (0-100MW) 60-G11,G12,G21
PT FUSE MONITERING RELAYS
MVAR MEGA VAR METER (100MVAR LEAD-0-100MVAR LAG) 60-G22,G31,G32
B B
MVA MEGA VOLTAMPS METER (0-100MVA) 64R ROTOR E/F PROTECTION-2 STAGES (PART OF GPR)
TVM TRIVECTOR METER FOR GENERATOR 64G1, 64G2 GENERATOR STATOR E/F RELAY (95&100%)
PF POWER FACTOR METER (0.5 LAG - 1 - 0.5 LEAD) 64G3 STATOR STAND BY E/F PROTECTION
V GENERATOR VOLTMETER (0-15KV) 78G POLE SLIPPING PROTECTION OF GENERATOR
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

F FREQUENCYMETER (45-55 HZ) 81G1,81G2 UNDER FREQUENCY PROTECTION STAGE-1&2


DF DUAL FREQUENCY METER FOR SYNCH. (45-55 HZ) 81G3,81G4 OVER FREQUENCY PROTECTION STAGE-1&2
DV DUAL VOLTMETER FOR SYNCH 86A,86B,86C LOCKOUT RELAYS (GROUP 1&2)
Ie EXCITER FIELD AMMETER (0-20A) 87G DIFFERENTIAL RELAY (PART OF GPR -1 &2)
Ve EXCITER FIELD VOLTMETER (0-150V) 95A,95B,95C SUPERVISION RELAYS FOR LOCKOUT RELAYS
NV NULL VOLTMETER [(+15)-0-(-15V)]
F1-F9 PT FUSES
MFGR PAPERLESS MULTI FUNCTION GRAPHIC RECORDER
C VSS VOLTAGE SELECTOR SWITCH C
POTENTIAL TRNSFORMERS
T1,T2,T3/MW MEGAWATT TRANSDUCER RANGE 0 TO 100MW
T1,T2/MVAR MVAR TRANSDUCER, RANGE 100MVAR LAG TO 100MVAR LEAD
SN PT REF PURPOSE RATIO ACC. CLASS BURDEN CONNECTION
T2/PF POWER FACTOR TRANSDUCER, RANGE 0.5 LAG TO 0.5 LEAD
T1,T2/HZ FREQUENCY TRANSDUCER, RANGE 45 TO 55HZ 1,2,3 -CORE-1 PROTECTION 11KV/r3 / 110V/r3 3P 30VA STAR/STAR
1
T1,T2/V VOLTAGE TRANSDUCERS, RANGE 0 TO 15KV 1,2,3 -CORE-2 MET & SYNCH 11KV/r3 / 110V/r3 0.2 60VA STAR/STAR
T2/A CURRENT TRANSDUCER, RANGE 0 – 5000A 4,5,6 -CORE-1 PROTECTION 11KV/r3 / 110V/r3 3P 30VA STAR/STAR
2
SC SURGE CAPACITOR, 0.25 MICRO FARAD, 18Kv 4,5,6 -CORE-2 AVR CH-1 11KV/r3 / 110V/r3 0.2 30VA STAR/STAR
AS AUTO SYNCHRONISER 7,8,9 -CORE-1 AVR CH-2 11KV/r3 / 110V/r3 3P 30VA STAR/STAR
3
LA LIGHTINING ARRESTER 7,8,9 -CORE-2 FOR PERFOMANCE
11KV/r3 / 110V/r3 0.2 30VA STAR/STAR
NGT NEUTRAL GROUNDING TRANSFORMER TESTING
52 11KV GEN. CIRCUIT BREAKER
D MCB1 TO 6 MINATURE CIRCUIT BREAKERS D
CURRENT TRANSFORMERS
SYN SYNCHROSCOPE
LR LOADING RESISTOR
SN PT REF PURPOSE RATIO BURDEN ACC. CLASS NO OF CT’S LOCATION
SW SYNCHROSCOPE CUT OFF SWITCH
GPR GENERATOR PROTECTION RELAY 1 1,2,3,4,5,6 GEN. PROTECTION 5000/1A -- PS 6 PH. SIDE IPB
25G CHECK SYNC RELAY 2 7,8,9,10,11,12 GEN. PROTECTION 5000/1A -- PS 6 N. SIDE IPB
IPB ISOLATED PHASE BUS DUCT 3 13 TO 18 AVR 5000/1A 30VA 0.2 6 PH. SIDE IPB
4 19,20,21 METERING 5000/1A 60VA 0.2 3 PH. SIDE IPB
5 FOR PERFOMANCE
24,25,26 5000/1A 30VA 0.2 3 N. SIDE IPB
TESTING
FOR OVERALL DIFF,
6 27,28,29 5000/1A -- PS 3 N. SIDE IPB
PROTN RELAY

E 7 **22 & 23 PROTECTION TO BE FURNISHED BY CUSTOMER 2 NGT SEC. SIDE E

PS CLASS CT’S SHALL HAVE FOLLOWING SPECS.


VK>400V, IM<30mA@Vk/2, Rsec<5OHMS@75*C
Pls. provide these details.

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 003 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
SINGLE LINE DIAGRAM DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 004
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
PROTN.
LOC DESCRIPTION SETTING NOTE:- LEGEND:-
CODE
A 1. RELAY SETTING WILL BE FURNISHED DURING ERECTION.
AR RELEASE OF CO2 2.GPR MAIN & REDUNDANT RELAYS SHALL BE PROVIDED OR - OR GATE
87G GRP GEN. DIFFERENTIAL PROTN.
WITH INDEPENDENT LOCKOUT RELAYS.
A
A AND - AND GATE A
64G1 ## PROTECTION FUNCTIONS MARKED WITH THIS SYMBOL
GRP STATOR EARTH FAULT PROTN. (95% & 100%) ARE NOT IN BHEL HYD SCOPE OF SUPPLY.
64G2
- NOT GATE
A 86A1 & 86A2 – UNIT LOCKOUT RELAYS
50G GRP DEAD MACHINE PROTN. 86B1 & 86B2 – TURBINE LOCKOUT RELAYS
86C1 & 86C2 – GEN. LOCKOUT RELAYS AR - AUX RELAY
A 95A1,95B1,95C1 – SUPERVISION RELAYS FOR LOCKOUT
A
1 st STAGE RELAYS A - ANNUNCIATOR
64R GRP GEN. ROTOR EARTH FAULT PROTN.
2 nd STAGE
A A
GRP - GEN. RELAY PANEL
RELEASE OF CO2 TCP - TURBINE CONTROL PANEL t - TIMER
80º C
26 GCP STATOR FRAME TEMPERATURE HIGH GCP - GEN. CONTROL PANEL
100º C AR
GCB - GEN. CIRCUIT BREAKER
B EFB - EXC. FIELD CIRCUIT BREAKER B
5 GCP EMERGENCY TRIP PUSH BUTTON OPTD. - AR ESV - EMERGENCY STOP VALVE
X1 - PROTECTION PT HEALTHY
A Y - GCB CLOSED
X1 Y1 - EXC. FLD CB CLOSED
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

GEN. OVER CURRENT WITH VOLTAGE


51V GRP AND
RESTRAINT RELAY
A

t
32G GRP REVERSE POWER PROTN. 0.5% AND
A A
X1
TO OPEN 52GCB & EFB TO OPEN 52GCB & EFB
0.5 sec OR 86A1 86C1
A BREAKERS BREAKERS.
40G GRP LOSS OF EXCITATION PROTN.
AND
95 EXC. FIELD BREAKER TO OPEN 52GCB & EFB 95
X1 A1 TRIP SIGNAL. BREAKERS.
C1
AND
C C
A

t TO INITIATE 50LBB TO INITIATE 50LBB


LOSS OF EXCITATION PROTN. AND
27/40G GRP 70% PROTECTION PROTECTION
WITH U/V PROTN.
2 sec
A A
A
1 st STAGE 1 st STAGE
46G GRP GEN NEGATIVE PH. SEQ. PROTN. t TURBINE SOLENOID 24G GRP GEN. OVER FLUXING PROTN. t
2 nd STAGE 2 nd STAGE AND
VALVE TRIP X1
2 sec 0.5 sec
A
27G GRP GEN. UNDER VOLTAGE PROTN. 90% X1 t
A AND
A OR 86B1
81.1G 1 st STAGE
GRP GEN. UNDER FREQUENCY PROTN. t GEN CB CLOSED 2 sec
81.2G 2 nd STAGE CHANGE OF REGN.
95 A
A
D 2 sec B1 FROM CH-1 TO CH-2 D
A
81.3G 1 st STAGE 59G1 115% t
GRP GEN. OVER FREQUENCY PROTN. GRP GEN. OVER VOLTAGE PROTN. 0.2 sec
81.4G 2 nd STAGE t 59G2 125% t 2 sec
GT HV CB CLOSED
A OR
0.5 sec A

ALL DEVICES CONNECTED TO CLASS-B TRIP 78G GRP GEN. POLE SLIPPING PROTN. AND
X1
A
# 87UT-1
TCP TRIP FROM ESV UT DIFFERENTIAL OPTD.
# 87UT-2
A
A TO OPEN TIE BREAKERS AND
50LBB GRP GEN. CB FAILURE PROTN. OTHER FAULT FEEDEING # 87GT GT DIFFERENTIAL OPTD.
BREAKERS.
A A
E GEN. OVER CURRENT RELAY WITH TIME 105%
E
51G1 GRP # 87OA OVERALL DIFFERENTIAL OPTD.
DELAY PROTN. OPTD. 10 sec
X1
A A
60G12 X1
GRP PT FUSE FAIL PROTN. OPTD. PROTN. 37G GRP LOW FORWARD POWER PROTN. 0.5% t AND
60G21
2 sec
A GEN CB CLOSED
60G11 GRP METERING PT FUSE FAIL PROTN. OPTD. METG
TURBINE TRIPPED
A OR
60G22 86B OPTD
GRP AVR PT FUSE FAIL PROTN. OPTD. AVR CHANGEOVER OF REGN.
60G31
FROM AUTO TO MANUAL

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 004 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
GROUP-1 OUTRIP LOGIC DIAGRAM DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 005
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
PROTN.
LOC DESCRIPTION SETTING NOTE:- LEGEND:-
CODE
A 1. RELAY SETTING WILL BE FURNISHED DURING ERECTION.
AR RELEASE OF CO2 2.GPR MAIN & REDUNDANT RELAYS SHALL BE PROVIDED OR - OR GATE
87G GRP GEN. DIFFERENTIAL PROTN.
WITH INDEPENDENT LOCKOUT RELAYS.
A A A
## PROTECTION FUNCTIONS MARKED WITH THIS SYMBOL AND - AND GATE
64G1
GRP STATOR EARTH FAULT PROTN. (95% & 100%) ARE NOT IN BHEL HYD SCOPE OF SUPPLY.
64G2
- NOT GATE
A 86A1 & 86A2 – UNIT LOCKOUT RELAYS
50G GRP DEAD MACHINE PROTN. 86B1 & 86B2 – TURBINE LOCKOUT RELAYS
86C1 & 86C2 – GEN. LOCKOUT RELAYS AR - AUX RELAY
A 95A1,95B1,95C1 – SUPERVISION RELAYS FOR LOCKOUT
A
1 st STAGE RELAYS A - ANNUNCIATOR
64R GRP GEN. ROTOR EARTH FAULT PROTN.
2 nd STAGE
A A
GRP - GEN. RELAY PANEL
RELEASE OF CO2 TCP - TURBINE CONTROL PANEL t - TIMER
80º C
26 GCP STATOR FRAME TEMPERATURE HIGH GCP - GEN. CONTROL PANEL
100º C AR
GCB - GEN. CIRCUIT BREAKER
B EFB - EXC. FIELD CIRCUIT BREAKER B
5 GCP EMERGENCY TRIP PUSH BUTTON OPTD. - AR ESV - EMERGENCY STOP VALVE
X1 - PROTECTION PT HEALTHY
A Y - GCB CLOSED
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

GEN. OVER CURRENT WITH VOLTAGE X1 Y1 - EXC. FLD CB CLOSED


51V GRP AND
RESTRAINT RELAY
A

t
32G GRP REVERSE POWER PROTN. 0.5% AND
A A
X1
TO OPEN 52GCB & EFB TO OPEN 52GCB & EFB
0.5 sec OR 86A2 86C2
A BREAKERS BREAKERS.
40G GRP LOSS OF EXCITATION PROTN.
AND
95
A2
EXC. FIELD BREAKER TO OPEN 52GCB & EFB 95

C X1 TRIP SIGNAL. BREAKERS.


C2
C
AND
A

t TO INITIATE 50LBB TO INITIATE 50LBB


LOSS OF EXCITATION PROTN. AND
27/40G GRP 70% PROTECTION PROTECTION
WITH U/V PROTN.
2 sec
A A
A
st
1 STAGE 1 st STAGE
46G GRP GEN NEGATIVE PH. SEQ. PROTN. t TURBINE SOLENOID 24G GRP GEN. OVER FLUXING PROTN. t
2 nd STAGE 2 nd STAGE AND
VALVE TRIP X1
2 sec 0.5 sec
A
27G GRP GEN. UNDER VOLTAGE PROTN. 90% X1 t
A AND
A OR 86B2
81.1G 1 st STAGE
GRP GEN. UNDER FREQUENCY PROTN. t GEN CB CLOSED 2 sec
81.2G 2 nd STAGE CHANGE OF REGN.
A
D A
95
B2 FROM CH-1 TO CH-2 D
2 sec A
81.3G 1 st STAGE 59G1 115% t
GRP GEN. OVER FREQUENCY PROTN. GRP GEN. OVER VOLTAGE PROTN. 0.2 sec
81.4G 2 nd STAGE t 59G2 125% t 2 sec
GT HV CB CLOSED
A OR
0.5 sec A

ALL DEVICES CONNECTED TO CLASS-B TRIP 78G GRP GEN. POLE SLIPPING PROTN. AND
X1
A
# 87UT-1
TCP TRIP FROM ESV UT DIFFERENTIAL OPTD.
# 87UT-2
A TO OPEN TIE BREAKERS AND A

50LBB GRP GEN. CB FAILURE PROTN. OTHER FAULT FEEDEING # 87GT GT DIFFERENTIAL OPTD.
BREAKERS.
E A A E
GEN. OVER CURRENT RELAY WITH TIME 105%
51G1 GRP # 87OA OVERALL DIFFERENTIAL OPTD.
DELAY PROTN. OPTD. 10 sec
X1
A A
60G12 X1
GRP PT FUSE FAIL PROTN. OPTD. PROTN. 37G GRP LOW FORWARD POWER PROTN. 0.5% t AND
60G21
2 sec
A GEN CB CLOSED
60G11 GRP METERING PT FUSE FAIL PROTN. OPTD. METG
TURBINE TRIPPED
A
OR
60G22 86B OPTD
GRP AVR PT FUSE FAIL PROTN. OPTD. AVR CHANGEOVER OF REGN.
60G31
FROM AUTO TO MANUAL

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 005 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
GROUP-2 TRIP LOGIC DIAGRAM DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 006
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

+C2 +ACDB

3269PN491-S-02/004.1B

3269PN491-S-02/004.2B
A A

240V AC, 50HZ

PH NU
X201 X201
1 2

H1 H2
+R1
B B
X201 X201
X1 X1
1 2 1 2
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

H1

H2

C C

1 1

FS91 LK91
16A

2 2
H3

H7

H3 H3

D 1 D
HS

2
H5

1 1

SW

TS PS

2 2
E 3 E
H4

CIL
1

4
HT
2

H7

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 006 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
AC DISTRIBUTION DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 007
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

+C2

3269PN491-S-02/006.6C

3269PN491-S-02/006.6C
A A

X201 X201
+VE -VE
3 4

J7 J8
+R1
B B

X201 X201
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

3 4

J7
/008.2B

J8
/008.2B

1 1 1 1 1 1 1 1 1 1 1 1
C C
FS1 FS2 FS3 FS4 FS5 FS6 FS7 FS8 FS9 FS10 FS11 FS12
10A 10A 10A 10A 6A 6A 4A 4A 4A 4A 6A 6A

2 2 2 2 2 2 2 2 2 2 2 2
U101

U102

U201

U202

K101

K102

K901

K902

K701

K702

K201

K202
/012.4C
/015.1B

/023.3E

/023.3E

/012.4A

/020.1B
/015.1F

/020.1F
X5 X5 X5 X5
D 19 20 21 22 D

TO GPRM TO ROTOR TO VOLT. TO GPRR


PROTN E/F RELAY BALANCE PROTN
SPARE SPARE CKT
CKT CKT CKT

E E

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 007 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
DC DISTRIBUTION DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 008
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A
+R1

/007.7B J7

/007.7C J8

B B
1 1 1 1 1 1 1 1 1 1 1 1 1 1

FS13 FS14 FS15 FS16 FS17 FS18 FS19 FS20 FS21 FS22 FS23 FS24 FS25 FS26
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

4A 4A 4A 4A 4A 4A 4A 4A 4A 4A 4A 4A 4A 4A

2 2 2 2 2 2 2 2 2 2 2 2 2 2

K401

K402

K501

K502

K601

K602

K451

K452

K551

K552

K651

K652

K801

K802
C C
/025.1C

/026.1C

/027.1C

/028.1C

/029.1C

/030.1C

/024.1C

/024.1E
/025.1F

/026.1F

/027.1F

/028.1F

/029.1F

/030.1F
TO GRP-1 TRIP TO GRP-1 TRIP TO GRP-1 TRIP TO GRP-2 TRIP TO GRP-2 TRIP TO GRP-2 TRIP
TO CONTACT
RELAY RELAY RELAY RELAY RELAY RELAY
MULTI. CKT.
86A 86B 86C 86A 86B 86C

D D

E E

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 008 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
DC DISTRIBUTION DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 009
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

+GEN PT +PTJB +R1

A A

MCB1 FS111
X3 E111 1 2 E113 Pls. note that the Voltage balance
/014.4D
2A Relay is part of Multi function
1
FS131 numerical relay, therefore no
X3 E131 1 2 E133 separate 60 type relay is
/014.4D
2A provided for this purpose.
2
FS151 TO GPRM
X3 E151 1 2 E153
/014.4D
2A
B 3 B
LK171
X3 E171 1 2 E173
/014.4D
4
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

PT 1,2,3 1
CORE : 1
11KV/ 3/110V/ 3 E1
30VA, CL-3P
2

1 2
11KV BUS

C 1 2 C

1 2 +C2

X200 X200
MCB2 FS211 E215
3269PN491-S-02/009.2E
X3 E211 1 2 E215 1 1

5 2A
X200 X200
FS231 E235
3269PN491-S-02/009.2E
X3 E231 1 2 E235 2 2

D 6 2A D
X200 X200
FS251 E255
3269PN491-S-02/009.2E
X3 E251 1 2 E255 3 3

7 2A
X200 E275
X200
LK271 3269PN491-S-02/009.2F
X3 E271 1 2 E275 4 4
TO METERING/
8
1 SYNCH. CKT
PT 1,2,3
CORE : 2
11KV/ 3/110V/ 3 E2
60VA, CL-0.2
FS213
2 1 2 E213
/012.2A
2A
E E
FS233
TO VOLTAGE
1 2 E233
/012.2A BALANCE
2A RELAY 60.11G
FS253
1 2 E253
/012.2B
2A

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 009 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
VT DISTRIBUTION DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 010
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

+GEN PT +PTJB +R1

A A

Pls. note that the Voltage balance


MCB3 FS311
Relay is part of Multi function
X3 E311 1 2 E313
/019.4D numerical relay, therefore no
9 2A
separate 60 type relay is
FS331
X3 E331 1 2 E333
provided for this purpose.
B /019.4D B
10 2A
TO GPRR
FS351
X3 E351 1 2 E353
/019.4D
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

11 2A
LK371
X3 E371 1 2 E373
/019.4E
12
PT 4,5,6 1
CORE : 1
11KV/ 3/110V/ 3 E3
30VA, CL-3P
2
C 1 2 C
11KV BUS

1 2

1 2

D D

MCB4 FS411
X3 E411 1 2 E413
/012.2B
13 2A
FS431
TO VOLTAGE
X3 E431 1 2 E433
/012.2C BALANCE
14 2A RELAY 60.22G
FS451
X3 E451 1 2 E453
/012.2C
15 2A
LK471
X3 E471 1 2 X3
E E
16 17
1
PT 4,5,6
11KV/ 3/110V/ 3 18 TO AVR CH-1
E4
30VA, CL-0.2
19
2
E473
20

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 010 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
VT DISTRIBUTION DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 011
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+GEN PT +PTJB +R1

A A

MCB5 FS511
X3 E511 1 2 E513
/012.2D
21 2A
FS531
X3 E531 1 2 E533
/012.2D
22 2A TO VOLTAGE
FS551 BALANCE
X3 E551 1 2 E553 RELAY 60.31G
/012.2D
23 2A

B LK571 B
X3 E571 1 2 X3
24 25
PT 7,8,9 1
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

CORE : 1
11KV/ 3/110V/ 3 E5
30VA, CL-0.2
X3
2
26
1 2
X3
11KV BUS

27 TO AVR CH-2

1 2 X3
C C
28

X3
1 2
29

MCB6 FS611
X3 E611 1 2 E613
/012.2E
30 2A
FS631
X3 E631 1 2 E633
/012.2E
D 31 2A
TO VOLTAGE D
FS651 BALANCE
X3 E651 1 2 E653 RELAY 60.32G
/012.2E
32 2A
LK671
X3 E671 1 2 X3
33 34
PT 7,8,9 1
CORE : 2
11KV/ 3/110V/ 3 E6
30VA, CL-0.2
X3
2
35

E X3 E

36 TO PERFORAMENCE
TESTING
X3
37

X3
38

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 011 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
VT DISTRIBUTION DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 012
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+R1

MVAPM32

A 60.11G A
.6C

/009.6E E213 /007.5D K701


23

FROM PT-1,2,3 /009.6E E233


A 13 11 13 11 13 11 13 11
CORE-2 25

/009.6E E253
27
MVAPM32 MVAPM32 MVAPM32 MVAPM32
60.11G COIL C 60.22G COIL C 60.31G COIL C 60.32G COIL C
A B .6C .7C .6E .7E

RLB-3

RLB-3

RLB-3

RLB-3
B B
MVAPM32 14 14 14 14

60.22G

K711

K713

K715

K717
.7C
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

/010.7D E413
23
FROM PT-4,5,6 E433
/010.7E A 19 15 19 15 19 15 19 15
CORE-2 25
RLB-1 RLB-1 RLB-1 RLB-1
/010.7E E453 60.31G 60.32G 60.22G 60.11G
27 .6E .7E .7C .6C

17 17 17 17
A B
C /007.5D K702 C

60.11G 60.22G
MVAPM32 23 23
COIL A-B 25 .3A COIL A-B 25 .3B
27 27
60.31G
13 13
.6E COIL C 14 .5A COIL C 14 .6A
11 11
/011.6A E513
8 8 VOLTAGE BALANCE CKT 19 15 .7C VOLTAGE BALANCE CKT 19 15 .6C
23 17 17
RLC-4 RLC-4
E533 20 20
FROM PT-7,8,9 /011.6B A 60.22G 60.31G SPARE
18
16 /041.1B SPARE
18
16 /041.3B
CORE-1 25 .7C .6E
SPARE 5 1 /041.1B SPARE 5 1 /041.3B
/011.6B E553 3 3
10 10
27 6 6
D SPARE
4
2 /041.2B SPARE
4
2 /041.4B D

K719

Signal

K723

K725
PT 1,2,3 CORE-2 FUSE FAIL 7 9 /038.2D PT 4,5,6 CORE-2 FUSE FAIL 7 9 /038.4D
A B
8 10 TO AVR PT CH. OVER CKT. 8 10 .4D

X4 X4 X4 X4
1 2 3 4

MVAPM32 TO AVR PT TO AVR PT 60.31G


60.32G CH. OVER CKT. CH. OVER CKT. 23
COIL A-B 25 .3D 60.32G
.7E 27 23
13 COIL A-B 25 .3E
E613 COIL C 14 .7A 27
/011.6D 11 13
23 COIL C 14 .8A
VOLTAGE BALANCE CKT 19 15 .5C 11
E633 17
FROM PT-7,8,9 /011.6D A 60.12 and 60.21 ARE PART VOLTAGE BALANCE CKT 19 15 .6C
E 25 20 17 E
CORE-2 OF MULTI FUNCTION SPARE
18
16 /041.5B
E653 20
/011.6D NUMERICAL RELAYS 5 SPARE
18
16 /041.7B
27 SPARE 1 /041.5B
GPR-M & GPR-R. 3
SPARE 5 1 /041.7B
SPARE 6 2 /041.6B 3
4
A SPARE 6 2 /041.8B
B PT 7,8,9 CORE-1 FUSE FAIL 7 9 /038.5D 4

TO AVR PT CH. OVER CKT. 8 10 .5D PT 7,8,9 CORE-2 FUSE FAIL 7 9 /038.5D

8 10

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 012 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
VOLTAGE BALANACE DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. SCHEME METERING/EXTN APPROVED : APS CONT: 013
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+R1

P343
GPRM
A BUS SIDE /044.1A A

+CTJB BLKA 5A 1A A173


E1 E2
/043.1A
X2 A111 21 22 A113
E3
1

2 5A 1A
E4 E5
/043.1A
A131 23 24 A133
E6
3

4 5A 1A
B E7 E8 B
/043.1A
A151 25 26 A153
E9
5
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

CT 4,5,6
RATIO : 5000/1A 6 /043.1A
CLASS : PS A171 27 28 A173
Vk>400V,Im<30mA@Vk/2, 7 E9
Rsec<5OHMS @75*C 2
A171S 1
8

C C

GENERATOR G
+CTJB

D D
BLKB
CT 7,8,9 /043.2A
X2 A271 27 28 A273 A273
RATIO: 5000/1A
CLASS : PS 9
Vk>400V,Im<30mA@Vk/2,
Rsec<5OHMS @75*C
10 5A 1A
C7 C8
/043.2A
A251 25 26 A253
C9
11

12 5A 1A
E C4 C5 E
/043.2A
A231 23 24 A233
C6
13

14 5A 1A
C1 C2
/043.2A
A211 21 22 A213
C3
15 E10
NGT SIDE A271S 1 2

16

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 013 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
GEN PROTN-GPRM CT CIRCUIT DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 014
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

+R1

A A

P343
GENERATOR G GPRM
+NGT JB /044.1E

BLKB 5A 1A IN

/043.2A C10 C11


X3 C171 9 10
C12
B 39 B

C175S
40

X3
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

41 E7 IN
1 2 5A 1A SENSITIVE

SLD CT-22 42 C13 C14


***
X3 C15
1

43

**LR /043.2A
C **NGT C175 11 12 C177 C

44
P343
GPRM
BLKA /044.2A

/043.1A
E113 5 6 E115 VA
/009.6A
C19

/043.1A
E133 7 8 E135 VB
/009.6B
C20
D FROM PT-1,2,3 D
CORE-1 /043.1A
E153 9 10 E155 VC
/009.6B
C21

/043.1A
E173 11 12 E175 VN
/009.6B
C22

BLKB
/043.2A
E81 5 6 E83 V NEUTRAL
C23

E /043.2A E
E85 7 8 E87
C24

E81
/019.4E

TO GPRR
E85
/019.4E NOTE:
** DETAILS TO BE FURNISHED BY CUSTOMER

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 014 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
GEN PROTN GPRM-PT CKT DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 015
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
GROUP-1 TRIP RELAYS OPTD./LBB INITIATION GROUP-2 TRIP RELAYS OPTD./LBB INITIATION
52X1 GCB FCB OPEN
CLOSED 86A1 86B1 86C1 86A2 86B2 86C 2

+C2
A A

3269PN491-S-02/036.6C

3269PN491-S-02/036.7C
+FCB

X201 X201
25 26

B B
K103 K111
+R1

X201 X201
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

X4 X4
25 26 5 6

/007.4D K101

13
BLKA
/043.1A
14
C K103 C
/016.1C

19 19 19 19 19 19

86A1 86B1 86C1 86A2 86B2 86C2


/025.7C /026.7C /027.7C /028.7C /029.7C /030.7C

21 21 21 21 21 21
K103

K111

K113

K115

K117

K119

K121

K123

K125
D P343 D
+

M2 E2 E4 E6 E8 E10 E12 E14 E16


GPRM
/044.3A

P343
GPRM
/044.6E

- E1 E3 E5 E7 E9 E11 E13 E15


M1
K104

E E
K104
/016.1E

13
BLKB
/043.2A
14

/007.4D K102

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 015 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
GEN PROTN-GPRM OPTO CKT DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 016
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
GROUP-1 TRIP RELAYS SUPERVISION
GTCB CLOSED SPARE SPARE SPARE SPARE
95A1 95B1 95C1

A A
+GTCB

B B
+R1
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

X4 X4
7 8

/015.7C K103

X4
13
X4
10

C C

X4 X4 X4
9 11 12
X4
K401 K501 K601 14
/025.6C /026.5C /027.6C
K127

K401

K501

K601

K129

K131

K133

K141
P343 G2 G4 G6 G8 G10 G12 G14 G16
GPRM
D /044.3D
D

G1 G3 G5 G7 G9 G11 G13 G15


K407

K507

K605

E E
/015.7E K104
1 1 1

R1 R2 R3
3.3K 3.3K 3.3K

2 2 2

K409 K509 K609


/025.6E /026.5E /027.6E

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 016 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
GEN PROTN-GPRM OPTO CKT DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 017
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

FROM INJECTION UNIT


SPARE SPARE SPARE SPARE SPARE SPARE SPARE
ROTOR E/F PROTN

A A

+R1
B B
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

/023.8B S1112

/023.8B S1111

C C
X8 X8 X8 X8 X8 X8 X8 X8 X8 X8 X8 X8 X8 X8
1 2 3 4 5 6 7 8 9 10 11 12 13 14
S1111

S1112

S1113

S1114

S1115

S1116

S1117

S1118

S1119

S1120

S1121

S1122

S1123

S1124

S1125

S1126
D P343 C16 C17 C18 C20 C21 C22 C24 C25 C26 C28 C29 C30 C1 C2 C3 C5 C6 C7 C9 C10 C11 C13 C14 C15 D
GPRM
/044.5A
20mA

20mA

20mA

20mA

20mA

20mA

20mA

20mA
1mA

1mA

1mA

1mA

1mA

1mA

1mA

1mA
I/P-1 I/P-2 I/P-3 I/P-4 O/P-1 O/P-2 O/P-3 O/P-4

E E

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 017 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
GEN PROTN-GPRM CLIO CKT DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 018
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+R1

P343
GPRR
A /045.1A A

BUS SIDE +CTJB BLKC 5A 1A A373


E1 E2
/043.4A
X2 A311 21 22 A313
E3
17

18 5A 1A
E4 E5
/043.4A
A331 23 24 A333
E6
19

20 5A 1A
B E7 E8 B
/043.4A
A351 25 26 A353
E9
21
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

RATIO : 5000/1A 22 /043.4A


CLASS : PS A371 27 28 A373
Vk > 400V 23 E8
Imag<30mA @ Vk/2 2
A371S 1
Rsec<5OHMS@75*C
24

C C

GENERATOR G
+CTJB

D D
BLKD
/043.5A
X2 A471 27 28 A473 A473
RATIO : 5000/1A
CLASS : PS 25
Vk > 400V
Imag<30mA @ Vk/2
26 5A 1A
Rsec<5OHMS@75*C
C7 C8
/043.5A
A451 25 26 A453
C9
27

28 5A 1A
E C4 C5 E
/043.5A
A431 23 24 A433
C6
29

30 5A 1A
C1 C2
/043.5A
A411 21 22 A413
C3
31 E9
NGT SIDE A471S 1 2

32

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 018 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
GEN PROTN-GPRR CT CIRCUIT DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 019
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

+R1

A A

P343
GPRR
/045.1E

BLKD 5A 1A IN

/043.5A C10 C11


C271 9 10
C12
B B
GENERATOR G
+NGT JB
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

IN
5A 1A SENSITIVE
X3 C13 C14
45
C15

C275S
46
/043.5A
X3 C275 11 12 C277
C E8 C
47
1 2
SLD CT-23 48
RATIO :***
1

P343
GPRR
BLKC /045.2A
**LR
**NGT /043.4A
E313 5 6 E315 VA
/010.7B
C19

/043.4A
E333 7 8 E335 VB
D FROM PT-4,5,6 /010.7B D
C20
CORE-1
/043.4A
E353 9 10 E355 VC
/010.7B
C21

/043.4A
E373 11 12 E375 VN
/010.7B
C22

BLKD
/043.5A
E81 5 6 E89 V NEUTRAL
/014.4E
C23
E FROM NGT E
/043.5A
E85 7 8 E89A
/014.4F
C24

NOTE:
** DETAILS TO BE FURNISHED BY CUSTOMER

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 019 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
GEN PROTN GPRR-PT CKT DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 020
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
GROUP-1 TRIP RELAYS OPTD./LBB INTIATION. GROUP-2 TRIP RELAYS OPTD./LBB INITIATION
52X1 GCB FCB OPEN
CLOSED 86A1 86B1 86C1 86A2 86B2 86C2

+C2
A A
+FCB

3269PN491-S-02/036.7C

3269PN491-S-02/036.8C
X201 X201
27 28

B B
K203 K211
+R1

X201 X201
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

/007.6D K201 K201


X4 X4
27 28 15 16

13
BLKC
/043.4A
14

K203
/021.1C
C C

20 20 20 20 20 20

86A1 86B1 86C1 86A2 86B2 86C2


/025.7C /026.7C /027.7C /028.7C /029.7C /030.7C

22 22 22 22 22 22
K203

K211

K213

K215

K217

K219

K221

K223

K225
P343
+

M2 E2 E4 E6 E8 E10 E12 E14 E16


GPRR
D /045.3A
D

P343
GPRR
/045.6E

- E1 E3 E5 E7 E9 E11 E13 E15


M1
K204

E K204
E
/021.1E

13
BLKD
/043.5A
14

/007.6D K202 K202

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 020 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
GEN PROTN-GPRR OPTO CKT DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 021
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
GROUP-2 TRIP RELAYS SUPERVISION
GTCB CLOSED 95A2 95B2 95C2 SPARE SPARE SPARE SPARE

A A
+GTCB

B B

+R1
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

X4 X4
17 18

/020.7C K203

X4 X4
20 23

C C

/028.6C K451 /029.5C K551 /030.6C K651


X4 X4 X4 X4
19 21 22 24

K235

K237

K239

K241
P343 G2 G4 G6 G8 G10 G12 G14 G16
GPRR
D /045.3D
D

G1 G3 G5 G7 G9 G11 G13 G15


K457

K557

K657

E K204
E
/020.7E

1 1 1

R5 R6 R4
3.3K 3.3K 3.3K

2 2 2

K455 K555 K655


/028.6E /029.5E /030.6E

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 021 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
GEN PROTN-GPRR OPTO CKT DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 022
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

FROM INJECTION UNIT


SPARE SPARE SPARE SPARE SPARE SPARE SPARE
ROTOR E/F PROTN

A A

+R1
B B
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

/023.8C S2112

/023.8C S2111

C C
X8 X8 X8 X8 X8 X8 X8 X8 X8 X8 X8 X8 X8 X8
17 18 19 20 21 22 23 24 25 26 27 28 29 30
S2111

S2112

S2113

S2114

S2115

S2116

S2117

S2118

S2119

S2120

S2121

S2122

S2123

S2124

S2125

S2126
D P343 C16 C17 C18 C20 C21 C22 C24 C25 C26 C28 C29 C30 C1 C2 C3 C5 C6 C7 C9 C10 C11 C13 C14 C15 D
GPRR
/045.5A
20mA

20mA

20mA

20mA

20mA

20mA

20mA

20mA
1mA

1mA

1mA

1mA

1mA

1mA

1mA

1mA
I/P-1 I/P-2 I/P-3 I/P-4 O/P-1 O/P-2 O/P-3 O/P-4

E E

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 022 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
GEN PROTN-GPRR CLIO CKT DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 023
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A +R1 A

TO DCS

P391
X8 X8
64R 15 16

TO ROTOR WATCH DOG


S111
X4 S1A C10
B A16 C9 PR5104
B
25 S112
C12 RR
B16
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

S1111

20mA ANALOUGE O/P


/017.2C
X4 S11 13
C18 42 S1112
26 /017.2B
S13 11
C17 43

S2A S15 S2111


/022.2C
B8 41 23
X4 S2112
/022.2B
C 27
A8 52 21 C

C5 K901 +VE
X4 S3A 31
TO ROTOR C6 K902 -VE
28
33
A3
CALIBRATION
RESISTOR 500OHM

A5

B3
D D
CALIBRATION
RESISTOR 500OHM

B5

K901 +VE
C2
K902 -VE

C1

E E

/007.4D K901

/007.5D K902

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 023 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
ROTOR E/F CKT DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 024
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

STATOR FRAME TEMP STATOR FRAME TEMP


EMERGENCY TRIP GEN DIFF PROTN. OPTD LBB PROTN. OPTD TO RELEASE CO2
HIGH(100ºC) HIGH(80ºC)

A +C2 A

3269PN491-S-02/023.1C

3269PN491-S-02/023.1C
X201 X201
5 6
B B

K801 K805
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

+R1

X201 X201
X4 X4 X4 X4
29 30 5 6 67 68

/008.7C K801

C C

L9 L9 J9 J9
RL5 RL5 RL21 RL21 32 34 22 24
GPRM GPRR GPRM GPRR
/044.6B /045.6B /044.7B /045.7B
30A 30C
.1E .4E
L10 L10 J10 J10
31 21
K803

K805

K807

K809

K827

K811

K813

K815

K817
D X4 X4 X4 X4 D
31 32 33 34
A1 A1 A1 27 A1
AR101
30A COIL 30B COIL 30C COIL 50ZX COIL 30D COIL
.1E .2E .4E .6E .7E
TO RELEASE OF TO RELEASE OF
A2 A2 A2 28 A2 CO2 CO2

50ZX
/008.7C K802 27 COIL 28 .4D

TO ANNUN 3 5 /036.7E
E 30A 30B 30C SPARE 4 6 /042.6B 30D E
A1 COIL A2 .2D A1 COIL A2 .2D A1 COIL A2 .3D SPARE 7 9 /042.7B A1 COIL A2 .5D
12 12 12 SPARE 8 10 /042.7B 12
TO 86A1 TRIP RELAY 11 /025.4D TO 86A1 TRIP RELAY 11 /025.3D GEN DIFF PROTN OPTD. TO ANNUN 11 /035.1E TO ANNUN 11 /040.7D
14 14 14 14
SPARE 11 13 /042.8B
TO 86A2 TRIP RELAY 22 22 22 22
24 21 /028.4D TO 86A2 TRIP RELAY
24 21 /028.3D TO RELEASE OF CO2
24 21 .7D 24 21
12 14
TO RELEASE OF CO2 32 32 32 32
34 31 .7D 34 31 34 31 15 17 34 31

STATOR FRAME TEMP HIGH 42 42 42 42


44 41 /037.4E 44 41 44 41 16 18
44 41

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 024 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
CONTACT MULTIPLICATION CKT. DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 025
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
GPRM EMERGENCY STATOR TEMP GROUP-1 TRIP RELAY 86A1
PROTN OPTD HIGH-100 C AVR TRIP CUSTOMER USE
TRIP SUPERVISION TO GPRM

A A

B B
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

+R1

X4 X4 X4 X4
35 36 37 38

C C

/008.2C K401 K401


/016.3C
86A1
27 OP 28 .2E

55 RE 56
1
BLKA TO GCB CLSG I/L 3 5 /031.8D
/043.1A
2 TO FCB CLSG I/L 4 6 /033.3D
TO GCB TRIP COIL-1 7 9 /031.6C
12 14 12 14
TO GCB TRIP COIL-2 8 10 /032.6C
K405

30B 30A TO FCB TRIP 11 13 /033.1C


/024.2E /024.1E
D TO AVR TRIP 12 14 /033.5C D
L1 11 11 TO GCB AUTO TRIP INDI. 15 17 /034.4C
RL1
TO FCB AUTO TRIP INDI. 16 18 /034.7C
GPRM
/044.6A LBB INI. TO GPRR 19 21 /015.3D

L2 LBB INI. TO GPRM 20 22 /020.3D

TO AVR CLSG I/L 31 33 /033.7D

SPARE 32 34 /041.1D
TO 86B1 TRIP RELAY 35 37 /026.3D

86A1 OPTD TO ANNUN. 36 38 /037.2E


K409
27 24 /016.3F SPARE 39 41 /041.1D
E SPARE 40 42 /041.2D E
SPARE 43 45 /041.2D

TR241 44 46
86A1 OP
47 49
.7C
48 50
28

/008.3C K402

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 025 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
UNIT LOCKOUT RELAY-86A1 DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 026
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
GPRM GROUP-1 TRIP GROUP-1 TRIP RELAY 86B1
CUSTOMER USE TRIP FROM ESV
PROTN OPTD RELAY 86A1 OPTD SUPERVISION TO GPRM

A A

B B
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

+R1

X4 X4 X4 X4
39 40 69 70

C C
86B1
/008.3C K501 K501 27 OP 28 .2E
/016.3C

55 RE 56

3 TO GCB CLSG I/L 3 5 /031.8C


BLKA TO TURBINE CLSG I/L 4 6 /034.3D
/043.1A
4 TO TURBINE TRIP 7 9 /034.1C

8 10

11 13
K523

12 14
D TO GCB AUTO TRIP INDI. 15 17 /034.5C
D
L3 35
16 18
RL2
GPRM 86A1 LBB INI. TO GPRR 19 21 /015.4D
/044.6A /025.7C
LBB INI. TO GPRM 20 22 /020.4D
L4 37 31 33

32 34 /041.3D
35 37
K503

86B1 OPTD TO ANNUN. 36 38 /037.2E

39 41 /041.4D
K509
/016.3F
40 42 /041.4D
E 27 24 E
43 45 /041.5D
44 46

47 49
TR241
48 50
86B1 OP
.7C

28
/008.3C K502

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 026 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
TURBINE LOCKOUT RELAY-86B1 DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 027
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

GPRM 87UT-1 DIFF. PROTN. 87UT-2 DIFF. PROTN. 87GT DIFF. PROTN. 87OA DIFF. PROTN. GROUP-1 TRIP RELAY 86C1
CUSTOMER USE
PROTN OPTD OPTD. OPTD. OPTD. OPTD. SUPERVISION TO GPRM

A A

B B
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

+R1

X4 X4 X4 X4 X4 X4 X4 X4 X4 X4
41 42 43 44 45 46 47 48 49 50
86C1
C 27 OP 28 .2E C
/008.4C K601 K601
/016.4C 55 RE 56

TO GCB CLSG I/L 3 5 /031.8C


17 TO FCB CLSG I/L 4 6 /033.3C
BLKA
/043.1A TO GCB TRIP COIL-1 7 9 /031.6C
18 TO GCB TRIP COIL-2 8 10 /032.6C

TO FCB TRIP 11 13 /033.1C


K607

TO AVR TRIP 12 14 /033.6C


TO GCB AUTO TRIP INDI. 15 17 /034.5C
L7
TO FCB AUTO TRIP INDI. 16 18 /034.7C
D RL4 D
GPRM LBB INI. TO GPRR 19 21 /015.4D
/044.6B
LBB INI. TO GPRM 20 22 /020.4D
L8 TO AVR CLSG I/L 31 33 /033.7C

SPARE 32 34 /041.6D
K603

35 37

86C1 OPTD TO ANNUN. 36 38 /037.3E


SPARE 39 41 /041.6D

K609 SPARE 40 42 /041.7D


/016.4F
SPARE 43 45 /041.8D
27 24
E 44 46 E
47 49
48 50
TR241
86C1 OP
.7C

28

/008.4C K602

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 027 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
GENERATOR LOCKOUT RELAY-86C1 DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 028
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
GPRR EMERGENCY STATOR TEMP GROUP-2 TRIP RELAY 86A2
PROTN OPTD HIGH-100deg C AVR TRIP CUSTOMER USE
TRIP SUPERVISION TO GPRR

A A

B B

+R1
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

X4 X4 X4 X4
51 52 53 54

C C

/008.4C K451 K451


/021.3C
86A2
27 OP 28 .2E

55 RE 56
1
BLKC TO GCB CLSG I/L 3 5 /031.8D
/043.4A
2 TO FCB CLSG I/L 4 6 /033.3D
TO GCB TRIP COIL-1 7 9 /031.6C
22 24 22 24
TO GCB TRIP COIL-2 8 10 /032.7C
K453

30B 30A TO FCB TRIP 11 13 /033.2C


/024.2E /024.1E
D TO AVR TRIP 12 14 /033.6C D
L1 21 21 TO GCB AUTO TRIP INDI. 15 17 /034.5C
RL1
TO FCB AUTO TRIP INDI. 16 18 /034.8C
GPRR
/045.6A LBB INI. TO GPRR 19 21 /015.5D

L2 LBB INI. TO GPRM 20 22 /020.5D

TO AVR CLSG I/L 31 33 /033.8D

K459 SPARE 32 34 /041.1E


TO 86B2 TRIP RELAY 35 37 /029.3D

86A2 OPTD TO ANNUN. 36 38 /037.2D


K455
27 24 /021.3F SPARE 39 41 /041.1E
E SPARE 40 42 /041.2E E
SPARE 43 45 /041.2E

TR241 44 46
86A2 OP
47 49
.7C
48 50
28

/008.5C K452

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 028 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
UNIT LOCKOUT RELAY-86A2 DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 029
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
GPRR GROUP-2 TRIP GROUP-2 TRIP RELAY 86B2
CUSTOMER USE TRIP FROM ESV
PROTN OPTD RELAY 86A2 OPTD SUPERVISION TO GPRR

A A

B B
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

+R1

X4 X4 X4 X4
55 56 71 72

C C
86B2
/008.5C K551 K551 27 OP 28 .2E
/021.3C

55 RE 56

3 TO GCB CLSG I/L 3 5 /031.8C


BLKC TO TURBINE CLSG I/L 4 6 /034.3C
/043.4A
4 TO TURBINE TRIP 7 9 /034.2C

8 10

11 13
K553

12 14
D TO GCB AUTO TRIP INDI. 15 17 /034.6C
D
L3 35
16 18
RL2
GPRR 86A2 LBB INI. TO GPRR 19 21 /015.6D
/045.6A /028.7C
LBB INI. TO GPRM 20 22 /020.6D
L4 37 31 33

SPARE 32 34 /041.3E
35 37
K559

86B2 OPTD TO ANNUN. 36 38 /037.3D

SPARE 39 41 /041.4E
K555
/021.3F
SPARE 40 42 /041.4E
E 27 24 E
SPARE 43 45 /041.5E
44 46

47 49
TR241
48 50
86B2 OP
.7C

28
/008.5C K552

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 029 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
TURBINE LOCKOUT RELAY-86B2 DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 030
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

GPRR 87UT-1 DIFF. PROTN. 87UT-2 DIFF. PROTN. 87GT DIFF. PROTN. 87OA DIFF. PROTN. GROUP-2 TRIP RELAY 86C2
CUSTOMER USE
PROTN OPTD OPTD. OPTD. OPTD. OPTD. SUPERVISION TO GPRR

A A

B B
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

+R1

X4 X4 X4 X4 X4 X4 X4 X4 X4 X4
57 58 59 60 61 62 63 64 65 66
86C2
C 27 OP 28 .2E C
/008.6C K651 K651
/021.4C 55 RE 56

TO GCB CLSG I/L 3 5 /031.8C


17 TO FCB CLSG I/L 4 6 /033.3C
BLKC
/043.4A TO GCB TRIP COIL-1 7 9 /031.7C
18 TO GCB TRIP COIL-2 8 10 /032.7C

TO FCB TRIP 11 13 /033.2C


K653

TO AVR TRIP 12 14 /033.6C


TO GCB AUTO TRIP INDI. 15 17 /034.6C
L7
TO FCB AUTO TRIP INDI. 16 18 /034.8C
D RL4 D
GPRR LBB INI. TO GPRR 19 21 /015.6D
/045.6B
LBB INI. TO GPRM 20 22 /020.6D
L8 TO AVR CLSG I/L 31 33 /033.8C

SPARE 32 34 /041.6E
K659

35 37

86C2 OPTD TO ANNUN. 36 38 /037.3D


SPARE 39 41 /041.6E

K655 SPARE 40 42 /041.7E


/021.4F
SPARE 43 45 /041.8E
27 24
E 44 46 E
47 49
48 50
TR241
86C2 OP
.7C

28

/008.6C K652

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 030 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
GENERATOR LOCKOUT RELAY-86C2 DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 031
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

TRIP RELAY OPERATED TO GCB GCB CLOSING


GCB TRIP COIL SUPERVISION-TC-1 TC-1 I/L

+R1
A A

K93
B B

3 3
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

X7 27
1 86C1 86C2

RLA-1

RLB-1
/027.7C /030.7C
19 23
5 5
CUSTOMER

XR351

K92

K94
USE

XR351 XR351 7 7 7 7
195 COIL RLC
195 COIL RLA 195 COIL RLB .4D
.4D .4D 86A1 86C1 86A2 86C2
/025.7C /027.7C /028.7C /030.7C
28 3 3
C C
9 9 9 9
X7 20 24 86B1 86B2
2 /026.7C /029.7C

5 5

K91

K95
195
3 3
19 COIL RLA 20 .2B
86A1 86A2
23 COIL RLB 24 .3B /025.7C /028.7C
D D
27 COIL RLC 28 .4B
5 5
SPARE 8 10 /042.1B

7 9
K1

K2

K11

K13

K15

K81

K82

K69

K97
TO ANNUN. 4 6 /040.7D
X201 X201 X201 X201
X5 X5 X5 X5 X5 SPARE 3 5 /042.2B
1 2 3 4 5 11 12 9 10

K81 K82 K69 K97


+GCB +C2

X201 X201 X201 X201


E 11 12 9 10
E

3269PN491-S-02/027.3E

3269PN491-S-02/027.3E

3269PN491-S-02/027.2E

3269PN491-S-02/027.2E
+VE -VE POST CLOSE PRE-CLOSE
SUPVN SUPVN

TO GCB TRIP COIL-1 TO GCB CLOSING I/L

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 031 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
GCB-52G CLOSING&TRIP COIL-1 DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 032
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

GCB TRIP COIL SUPERVISION TC-2 TRIP RELAY OPERATED TO GCB TC-2

A +R1 A

B B
X7 27
3
19 23

RLA-1

RLB-1
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

XR351 XR351 8 8 8 8
SPARE

XR351
295 COIL RLA 295 COIL RLB
.4D .4D 295 COIL RLC 86A1 86C1 86A2 86C2
.4D /025.7C /027.7C /028.7C /030.7C

28 10 10 10 10
20 24
X7
4
C C

295
19 COIL RLA 20 .3B

K83

K84
23 COIL RLB 24 .3B

27 COIL RLC 28 .4B


D SPARE 8 10 /042.3B
D
7 9
X201 X201
TO ANNUN. 4 6 /040.6D
13 14
K51

Signal

K61

K63

K65

SPARE 3 5 /042.3B

X5 X5 X5 X5 X5
6 7 8 9 10

K83 K84
+GCB +C2

X201 X201
E 13 14
E

3269PN491-S-02/027.4E

3269PN491-S-02/027.4E
+VE -VE POST CLOSE PRE-CLOSE
SUPVN SUPVN

TO GBC TRIP COIL-2

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 032 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
GCB-52G TRIP COIL-2 DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAIPUR PVT LTD. APPROVED : APS CONT: 033
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

TRIP RELAY OPTD TRIP RELAY OPTD


FCB CLOSING I/L AVR CLOSING I/L
TO TRIP FCB TO AVR TRIP

A +R1 A

K627

K87
B B
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

4 4 31 31

86C1 86C2 86C1 86C2


/027.7C /030.7C /027.7C /030.7C

6 6 33 33

11 11 11 11 12 12 12 12

86A1 86C1 86A2 86C2 86A1 86C1 86A2 86C2


C /025.7C /027.7C /028.7C /030.7C /025.7C /027.7C /028.7C /030.7C C

K628

K626

K86

K88
13 13 13 13 14 14 14 14
4 4 31 31

86A1 86A2 86A1 86A2


/025.7C /028.7C /025.7C /028.7C

6 6 33 33
K626

K627

K625

K624

K71

K73

K85

K89
D D
X201 X201 X201 X201
19 20 17 18

X5 X5 X5 X5
11 12 13 14

K626 K627 K625 K624


+C2 +AVR

X201 X201 X201 X201


19 20 17 18 1 1 1 1
3269PN491-S-02/028.4E

3269PN491-S-02/028.4E

3269PN491-S-02/028.2E

3269PN491-S-02/028.2E

E 2 2 2 2 E

TO TRIP AVR
TO AVR CLSG I/L

TO TRIP TO CLOSING I/L


EXCITER FIELD CB

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 033 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
GEN FIELD CB & AVR TRIP DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 034
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

TRIP RELAY OPTD TURBINE


AUTO TRIP INDICATION TO CONTROL PANEL FOR INDICATION
TO TRIP TURBINE CLOSING I/L

A +R1 A

B B

4
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

86B2
/029.7C

7 7

86B1 86B2 K58 15 15 15 15 15 15 16 16 16 16


/026.7C /029.7C
C 86A1 86B1 86C1 86A2 86B2 86C2 86A1 86C1 86A2 86C2 C
9 9
/025.7C /026.7C /027.7C /028.7C /029.7C /030.7C /025.7C /027.7C /028.7C /030.7C

4 17 17 17 17 17 17 18 18 18 18

86B1
/026.7C

6
K55

K56

K57

K59

L1

L70

L75

L76
D D
X201 X201 X201 X201
8 15 76 16

X5 X5 X5 X5
15 16 17 18

L1 L70 L75 L76


+TURBINE +C2

X201 X201 X201 X201


1 1 1 1 8 15 76 16
3269PN491-S-02/027.6B
3269PN491-S-02/006.6D

E 2 2 2 2 E

TO TURBINE
TO TRIP
CLOSING
TURBINE
I/L

TO GCB TO FCB

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 034 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
TURBINE CB TRIP & AUTO TRIP DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 035
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
GEN. DIFFL GEN. ROTOR GEN.STATOR E/F GEN. STATOR E/F LOSS OF EXCITATION LOSS OF EXCITATION LOW FORWARD NEG. PHASE SEQ. UNDER FREQ. STG-2
PROTN OPTD E/F STG-2 OPTD. (0-95%) OPTD (0-100%) OPTD WITH U/V WITHOUT U/V POWER PROTN. STG-2 OPTD OPTD.
OPTD.

A +C2 A
3269PN491-S-02/023.2C

3269PN491-S-02/037.2C

3269PN491-S-02/037.2C

3269PN491-S-02/037.3C

3269PN491-S-02/037.3C

3269PN491-S-02/037.4C

3269PN491-S-02/037.4C

3269PN491-S-02/037.5C

3269PN491-S-02/037.5C

3269PN491-S-02/037.5C
X201 X201 X201 X201 X201 X201 X201 X201 X201 X201
30 31 32 33 34 35 36 37 38 39

B B
L101 L103 L105 L107 L109 L111 L113 L115 L117 L119
+R1

X201 X201 X201 X201 X201 X201 X201 X201 X201 X201
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

30 31 32 33 34 35 36 37 38 39
L101

L103

L105

L107

L109

L111

L113

L115

L117

L119
C C

L11 L13 L14 L16 L17 K1 K3 K5 K7 K9


RL6 RL7 RL8 RL9 RL10 RL11 RL12 RL13
GPRR GPRR GPRR GPRR GPRR GPRR GPRR GPRR
/045.6B /045.6B /045.6B /045.6C /045.6C /045.6C /045.6C /045.6D

L12 L15 L18 K2 K4 K6 K8 K10

D D
L105

L107

L109

L111

L113

L115

L117

L119
12 14 L11 L13 L14 L16 L17 K1 K3 K5 K7 K9
RL6 RL7 RL8 RL9 RL10 RL11 RL12 RL13
30C GPRM GPRM GPRM GPRM GPRM GPRM GPRM GPRM
/024.4E /044.6B /044.6B /044.6B /044.6C /044.6C /044.6C /044.6C /044.6D

11 L12 L15 L18 K2 K4 K6 K8 K10

E E
L101
/036.1E

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 035 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
ANNUNCIATION CONTACT DISTRIBUTION DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. TRIP CONTACTS APPROVED : APS CONT: 036
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
GEN UNDER VOLTAGE
OVER FREQ. DEAD MACHINE REVERSE POWER GEN OVERFLUX POLE SLIPPING GEN OVER VOLTAGE
VOLTAGE PROTN. LBB PROTN. OPTD. RESTRAINT O/C
STG-2 OPTD PROTN OPTD PROTN OPTD STG-2 OPTD PROTN OPTD STG-2 OPTD
OPTD. OPTD

A +C2 A

3269PN491-S-02/037.6C

3269PN491-S-02/037.6C

3269PN491-S-02/038.2B

3269PN491-S-02/038.2B

3269PN491-S-02/038.2B

3269PN491-S-02/038.3B

3269PN491-S-02/038.3B

3269PN491-S-02/038.4B

3269PN491-S-02/038.4B
X201 X201 X201 X201 X201 X201 X201 X201 X201
40 41 42 43 44 45 46 47 48

B B
L121 L123 L125 L127 L129 L131 L133 L135 L137
+R1

X201 X201 X201 X201 X201 X201 X201 X201 X201


This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

40 41 42 43 44 45 46 47 48
L121

L123

L125

L127

L129

L131

L133

L135

L137
C C

K11 K13 K14 K16 K17 J1 J3 J5 J7 J11


RL14 RL15 RL16 RL17 RL18 RL19 RL20 RL22
GPRR GPRR GPRR GPRR GPRR GPRR GPRR GPRR
/045.6D /045.6D /045.6D /045.7A /045.7A /045.7A /045.7B /045.7B

K12 K15 K18 J2 J4 J6 J8 J12

D D

K11 K13 K14 K16 K17 J1 J3 J5 J7 3 J11


RL14 RL15 RL16 RL17 RL18 RL19 RL20 RL-1 RL22
GPRM GPRM GPRM GPRM GPRM GPRM GPRM 50ZX GPRM
/044.6D /044.6D /044.6D /044.7A /044.7A /044.7A /044.7B /024.6E /044.7B

K12 K15 K18 J2 J4 J6 J8 5 J12

E E
/035.8E L101 L101
/037.1E

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 036 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
ANNUNCIATION CONTACT DISTRIBUTION DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. TRIP CONTACTS APPROVED : APS CONT: 037
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
GROUP-1 / 2 86A TRIP GROUP-1 / 2 86B TRIP GROUP-1 / 2 86C TRIP STATOR FRAME TEMP
RELAY OPTD. RELAY OPTD. RELAY OPTD. HIGH(100 DEG)

A +C2 A

3269PN491-S-02/038.5B

3269PN491-S-02/038.5B

3269PN491-S-02/038.6B

3269PN491-S-02/038.6B
X201 X201 X201 X201
49 50 51 52

B B
L139 L141 L143 L145
+R1

X201 X201 X201 X201


This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

49 50 51 52
L139

L141

L143

L145
C C

36 36 36

86A2 86B2 86C2


/028.7C /029.7C /030.7C

38 38 38

D D

36 36 36 42 44

86A1 86B1 86C1 30A


/025.7C /026.7C /027.7C /024.1E

38 38 38 41

E E
/036.8E L101

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 037 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
ANNUNCIATION CONTACT DISTRIBUTION DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. TRIP CONTACTS APPROVED : APS CONT: 038
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
PT 1,2,3 CORE-1 PT 1,2,3 CORE-2 PT 4,5,6 CORE-1 PT 4,5,6 CORE-2 PT 7,8,9 CORE-1 PT 7,8,9 CORE-2 GPRM RELAY GPRR RELAY
FUSE FAIL FUSE FAIL FUSE FAIL FUSE FAIL FUSE FAIL FUSE FAIL FAULTY FAULTY

A +C2 A
3269PN491-S-02/043.2C

3269PN491-S-02/043.2C

3269PN491-S-02/043.3C

3269PN491-S-02/043.3C

3269PN491-S-02/043.4C

3269PN491-S-02/043.4C

3269PN491-S-02/043.4C

3269PN491-S-02/043.5C

3269PN491-S-02/043.5C
X201 X201 X201 X201 X201 X201 X201 X201 X201
53 54 55 56 57 58 59 60 61

B B
L201 L203 L205 L207 L209 L211 L213 L215 L217

+R1
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

X201 X201 X201 X201 X201 X201 X201 X201 X201


53 54 55 56 57 58 59 60 61
L201

L203

L205

L207

L209

L211

L213

L215

L217
C C

M11 M11
J13 J14 7 J13 J14 7 7 7 WD1 WD1
RL23 RLC-3 RL23 RLC-3 RLC-3 RLC-3 GPRM GPRR
/044.7E /045.7E
GPRM 60.11G GPRR 60.22G 60.31G 60.32G
/044.7B /012.6C /045.7B /012.7C /012.6E /012.7E
D M12 M12 D
J15 9 J15 9 9 9

L201
E /039.1E E

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 038 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
ANNUNCIATION CONTACT DISTRIBUTION DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. NON-TRIP CONTACTS APPROVED : APS CONT: 039
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
UNDER/OVER
GEN ROTOR E/F STG-1 GEN OVER VOLTAGE NEG. PHASE SEQ. GEN O/C WITH TIME OVER FLUXING
FREQUENCY STG-1
OPTD. STG-1 OPTD. STG-1 OPTD. DELAY OPTD. STG-1 OPTD.
OPTD.

A +C2 A

3269PN491-S-02/044.2B

3269PN491-S-02/044.2B

3269PN491-S-02/044.2B
3269PN491-S-02/043.6C

3269PN491-S-02/043.6C

3269PN491-S-02/043.7C
X201 X201 X201 X201 X201 X201
62 63 64 65 66 67

B B
L219 L221 L223 L225 L227 L229

+R1
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

X201 X201 X201 X201 X201 X201


62 63 64 65 66 67
L219

L221

L223

L225

L227

L229
C C
H9
J16 J17 H1 H3 H5 H7 RL29
RL24 RL25 RL26 RL27 RL28 GPRR
GPRR /045.7D
GPRR GPRR GPRR GPRR
/045.7B /045.7C /045.7C /045.7C /045.7C
H10
J18 H2 H4 H6 H8

D D

J16 J17 H1 H3 H5 H7 H9
RL24 RL25 RL26 RL27 RL28 RL29
GPRM GPRM GPRM GPRM GPRM GPRM
/044.7B /044.7C /044.7C /044.7C /044.7C /044.7D

J18 H2 H4 H6 H8 H10

/038.8E L201 L201


E /040.1E E

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 039 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
ANNUNCIATION CONTACT DISTRIBUTION DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. NON TRIP CONTACTS APPROVED : APS CONT: 040
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
86A1 TRIP RELAY 86B1 TRIP RELAY 86C1 TRIP RELAY 86A2 TRIP RELAY 86B2 TRIP RELAY 86C2 TRIP RELAY GCB TRIP COIL STATOR FRAME TEMP
FAULTY FAULTY FAULTY FAULTY FAULTY FAULTY FAULTY HIGH(80 DEG)

+C2
A A

3269PN491-S-02/044.3B

3269PN491-S-02/044.3B

3269PN491-S-02/044.4B

3269PN491-S-02/044.4B

3269PN491-S-02/044.5B

3269PN491-S-02/044.5B

3269PN491-S-02/044.6B

3269PN491-S-02/044.6B
X201 X201 X201 X201 X201 X201 X201 X201
68 69 70 71 72 73 74 75

L231 L233 L235 L237 L239 L241 L243 L245


B B
+R1

X201 X201 X201 X201 X201 X201 X201 X201


This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

68 69 70 71 72 73 74 75
L231

L233

L235

L237

L239

L241

L243

Signal
C C

H11 H13 H14 H16 H17 H11 H13 H14 H16 H17 4 4 12 14
RL30 RL31 RL32 RL30 RL31 RL32 RLC-3 RLC-3
GPRM GPRM GPRM GPRR GPRR GPRR 295 195 30D
/044.7D /044.7D /044.7D /045.7D /045.7D /045.7D /032.4D /031.4D /024.7E

H12 H15 H18 H12 H15 H18 6 6 11

D D

/039.6E L201

E E

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 040 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
ANNUNCIATION CONTACT DISTRIBUTION DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. NON-TRIP CONTACTS APPROVED : APS CONT: 041
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SPARE CONTACTS DISTRIBUTION

+R1
A A

60.11G 60.22G 60.31G 60.32G

20 16 5 1 6 2 20 16 5 1 6 2 20 16 5 1 6 2 20 16 5 1 6 2
RLB-2 RLC-1 RLC-2 RLB-2 RLC-1 RLC-2 RLB-2 RLC-1 RLC-2 RLB-2 RLC-1 RLC-2

/012.6C /012.6C /012.6C /012.7C /012.7C /012.7C /012.6E /012.6E /012.6E /012.7E /012.7E /012.7E

B 18 3 4 18 3 4 18 3 4 18 3 4 B
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28

C 86A1 86B1 86C1 C

32 39 40 43 32 39 40 43 32 39 40 43

/025.7C /025.7C /025.7C /025.7C /026.7C /026.7C /026.7C /026.7C /027.7C /027.7C /027.7C /027.7C

34 41 42 45 34 41 42 45 34 41 42 45

X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7
29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52

D D

86A2 86B2 86C2

32 39 40 43 32 39 40 43 32 39 40 43

/028.7C /028.7C /028.7C /028.7C /029.7C /029.7C /029.7C /029.7C /030.7C /030.7C /030.7C /030.7C
E E
34 41 42 45 34 41 42 45 34 41 42 45

X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7
53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 041 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
SPARE CONTACT DISTRIBUTION DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 042
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SPARE CONTACTS DISTRIBUTION

+R1
A A

195 295 GPRM GPRR 50ZX

8 3 8 3 L5 L5 4 7 8 11
RLC-1 RLC-4 RLC-1 RLC-4 RL3 RL3 RL-2 RL-3 RL-4 RL-5

/031.4D /031.4D /032.4D /032.4D /044.6A /045.6A /024.6E /024.6E /024.6E /024.6E

B 10 5 10 5 L6 L6 6 9 10 13 B
U1

U2

U3

U4

U5

U6

U7

U8

U9

U10

U11

U12

U13

U14

U15

U16

U17

U18

U19

U20
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7 X7
77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96

C C

D D

E E

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 042 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
SPARE CONTACT DISTRIBUTION DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 043
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

+R1

A A

BLKA BLKB BLKC BLKD


1 2 /025.2C 1 2 1 2 /028.2C 1 2

3 4 /026.2C 3 4 3 4 /029.2C 3 4

5 6 /014.6D 5 6 /014.6E 5 6 /019.6D 5 6 /019.6E


7 8 /014.6D 7 8 /014.6E 7 8 /019.6D 7 8 /019.6E
B 9 10 /014.6D 9 10 /014.6B 9 10 /019.6D 9 10 /019.6B B
11 12 /014.6D 11 12 /014.6C 11 12 /019.6E 11 12 /019.6C
13 14 /015.1C 13 14 /015.1E 13 14 /020.1C 13 14 /020.1E
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

15 16 15 16 15 16 15 16

17 18 /027.2C 17 18 17 18 /030.2C 17 18

19 20 19 20 19 20 19 20

21 22 /013.5A 21 22 /013.5F 21 22 /018.5A 21 22 /018.5F

23 24 /013.5B 23 24 /013.5E 23 24 /018.5B 23 24 /018.5E

25 26 /013.5B 25 26 /013.5E 25 26 /018.5B 25 26 /018.5E

27 28 /013.5B 27 28 /013.5D 27 28 /018.5B 27 28 /018.5D


C C

D D

E E

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 043 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
TEST BLOCK DISTRIBUTION DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 044
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+R1
GPRM GPRM GPRM

VA L1 J1
/025.2D /036.3E
A E1 5A C19 20mA C16 L2 RL1 RL17 J2 GEN OVERFLUX STG-2 OPTD A
TO 86A1 TRIP RELAY
E1 1mA C17 L3 J3
E2 I/P-1 /036.4E
VB E2 C18 /026.2D L4 RL2 RL18 J4
1A TO 86B1 TRIP RELAY POLE SLIPPING OPTD
C20 20mA C20 L5 J5
E3 /042.4B /036.5E
E3 1mA C21 L6 RL3 RL19 J6 OVER VOLTAGE STG-2 OPTD
I/P-2 (ANY TRIP)
E4 5A VC E4 C22 L7 J7
/027.2D /036.6E
C21 C24 L8 RL4 RL20 J8 UNDER VOLTAGE PROTN. OPTD.
E5 /014.7D TO 86C1 TRIP RELAY
1A E5 20mA C25 L9 J9
I/P-3 /024.4D
VN E6 1mA C26 /024.3D L10 RL5 RL21 J10
GEN. DIFFL PROTN OPTD LBB PROTN. OPTD.
E6
C22 C28 L11 J11
/035.2E /036.7E
E7 5A E7 20mA C29 L12 RL6 RL22 J12 VOLTAGE RESTRAINT O/C OPTD.
I/P-4 GEN. ROTOR E/F STG-2 OPTD.
E8 1mA C30 L14 J14
E8
1A C23 /035.3E L13 J13 /038.2D
B /015.2D
20mA
GEN E/F (0-95%) OPTD L15 RL7 RL23 J15 PT 1,2,3 CORE-1 FUSE FAIL B
E9 C1
/013.7A E9
V NEUTRAL E10 L17 J17
C7 5A C24 1mA C2 /035.3E L16 J16 /039.2E
O/P-1 GEN E/F (0-100%) OPTD GEN ROTOR E/F STG-1 OPTD
L18 RL8 RL24 J18
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

E11
C8
1A E12 C3
/017.2D
C9
E13 20mA C5
C4 5A E14
1mA C6
C5 O/P-2
1A E15 K1 H1
/035.4E /039.2E
E16 C7 K2 RL9 RL25 H2 GEN O/V STG-1 OPTD
C6 LOSS OF EXCITATION WITH U/V
K3 H3
/039.3E
C C1 5A 20mA C9 /035.5E
LOSS OF EXCITATION WITH U/V K4 RL10 RL26 H4 NEG. PHASE SEQ. STG-1 OPTD
C
K5 H5
C2 /039.4E
1mA C10 /035.6E K6 RL11 RL27 H6
1A O/P-3 LOW FORWARD POWER PROTN. UNDER/OVER FREQ. STG-1 OPTD
K7 H7
C3 /039.5E
C11 /035.6E K8 RL12 RL28 H8
NEG. PHASE SEQ STG-2 OPTD. GEN O/C WITH TIME DELAY OPTD
K9 H9
/035.7E /039.6E
20mA C13 K10 RL13 RL29 H10 OVER FLUXING STG-1 OPTD
UNDER FREQ. STG-2 OPTD.
G1 K11 H11
/036.1E /040.1E
G2 1mA C14 K12 RL14 RL30 H12 86A1TRIP RELAY FAULTY
O/P-4 OVER FREQ STG-2 OPTD
K14 H14
G3 C15 /036.2E K13 H13 /040.2E
DEAD MACHINE PROTN OPTD K15 RL15 RL31 H15 86B1 TRIP RELAY FAULTY
G4
K17 H17
D D
G5 /036.3E K16 H16 /040.3E
REVERSE POWER PROTN OPTD RL16 RL32 86C1 TRIP RELAY FAULTY
G6 K18 H18

G7
G8

/016.2D
C10 5A G9
G10
C11
1A M11
WD1 /038.6D
G11 M12 RELAY FAULTY TO ANNUN
C12
/014.7B G12 M13
WD2 M14
E C13 G13
E
5A
G14
C14
1A
G15
C15
G16 M2 -

/015.1D
M1 +

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 044 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
RELAY CONTACT DISTRIBUTION DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 045
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+Loc
GPRR GPRR GPRR

E1 5A VA E1 L1 J1
/028.2D /036.4D
A C19 E2 20mA C16 L2 RL1 RL17 J2 GEN OVERFLUX STG-2 OPTD A
E2 TO 86A2 TRIP RELAY
1A 1mA C17 L3 J3
I/P-1 /036.4D
VB C18 /029.2D L4 RL2 RL18 J4
E3 TO 86B2 TRIP RELAY POLE SLIPPING OPTD
E3
C20 E4 20mA C20 L5 J5
/042.5B /036.5D
E4 5A 1mA C21 L6 RL3 RL19 J6 OVER VOLTAGE STG-2 OPTD
I/P-2 (ANY TRIP)
VC C22 L7 J7
E5 E5
/030.2D /036.6D
1A C21 E6 C24 L8 RL4 RL20 J8 UNDER VOLTAGE PROTN. OPTD.
/019.7D TO 86C2 TRIP RELAY
20mA C25 L9 J9
E6 I/P-3 /024.5D
VN 1mA C26 /024.3D L10 RL5 RL21 J10
E7 GEN. DIFFL PROTN OPTD LBB PROTN. OPTD.
E7 5A C22 E8 C28 L11 J11
/035.2D /036.7D
20mA C29 L12 RL6 RL22 J12 VOLTAGE RESTRAINT O/C OPTD.
E8 /020.2D I/P-4 GEN. ROTOR E/F STG-2 OPTD.
1A E9 1mA C30 L13 J13
C23 E10 /035.3D L14 J14 /038.3D
B /018.7A E9
20mA
GEN E/F (0-95%) OPTD L15 RL7 RL23 J15 PT 4,5,6 CORE-1 FUSE FAIL B
C1
C7 5A V NEUTRAL
E11 L16 J16
C24 E12 1mA C2 /035.4D L17 J17 /039.2C
C8 O/P-1 GEN E/F (0-100%) OPTD GEN ROTOR E/F STG-1 OPTD
L18 RL8 RL24 J18
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

1A
E13 C3
C9
E14 /022.2D
C4 5A 20mA C5

C5 E15
1A E16 1mA C6
O/P-2
K1 H1
C6 /039.3C
C7 /035.5D K2 RL9 RL25 H2
LOSS OF EXCITATION WITH U/V GEN O/V STG-1 OPTD
C1 5A K3 H3
/039.4C
C 20mA C9 /035.5D K4 RL10 RL26 H4 NEG. PHASE SEQ. STG-1 OPTD
C
C2 LOSS OF EXCITATION WITH U/V
1A K5 H5
/035.6D /039.4C
1mA C10 K6 RL11 RL27 H6 UNDER/OVER FREQ. STG-1 OPTD
C3 O/P-3 LOW FORWARD POWER PROTN.
K7 H7
/035.7D /039.5C
C11 K8 RL12 RL28 H8 GEN O/C WITH TIME DELAY OPTD
NEG. PHASE SEQ STG-2 OPTD.
K9 H9
/035.7D /039.6C
20mA C13 K10 RL13 RL29 H10 OVER FLUXING STG-1 OPTD
UNDER FREQ. STG-2 OPTD.
K11 H11
/036.1D /040.4D
G1 1mA C14 K12 RL14 RL30 H12 86A2 TRIP RELAY FAULTY
O/P-4 OVER FREQ STG-2 OPTD
G2 K13 H13
C15 /036.2D K14 H14 /040.5D
DEAD MACHINE PROTN OPTD K15 RL15 RL31 H15 86B2 TRIP RELAY FAULTY
G3
K16 H16
D G4 D
/036.3D K17 H17 /040.5D
REVERSE POWER PROTN OPTD RL16 RL32 86C2 TRIP RELAY FAULTY
K18 H18
G5
G6

G7
G8

/021.2D
G9
C10 5A G10 M11
WD1 /038.7D
M12 RELAY FAULTY TO ANNUN
C11
1A G11 M13
G12 WD2 M14
E /019.7B
C12 E
G13
C13 5A G14

C14
1A G15 -
G16 M2
C15 /020.1D
+
M1

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 045 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
RELAY CONTACT DISTRIBUTION DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 046
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

MiCOMP343 LED CONFIGURATION(GPRM)


MiCOMP343 LED CONFIGURATION(GPRR)

A A
GENERATOR DIFF. PROTN
REV POWER PROTN

ROTOR E/F PROTN.


STATOR E/F PROTN

NEG. PHASE SEQUENCE PROTN


UNDER VOLTAGE PROTN

OVER CURRENT PROTN


OVER VOLTAGE PROTN

DEAD MACHINE PROTN


OVER FREQUENCY PROTN

POLE SLIPPING PROTN


LOSS OF EXCITATION
B B
LBB PROTN
UNDER FREQUENCY PROTN

VOLTAGE RESTRAINT O/C PROTN


LOW FORWARD POWER
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

INBUILT FUNCTIONS OF GPRM:


INBUILT FUNCTIONS OF GPRR:

1) 87G- GENERATOR DIFFERENTIAL PROTN. 1) 87G- GENERATOR DIFFERENTIAL PROTN.


2) 64G- ROTOR E/F PROTN. 2) 64G- ROTOR E/F PROTN.
3) 64G1/G2-GENERATOR E/F PROTN(0-95% & 0-100%) 3) 64G1/G2-GENERATOR E/F PROTN(0-95% & 0-100%)
C 4) 37G-LOW FORWARD POWER 4) 37G-LOW FORWARD POWER C
5) 40G- LOSS OF EXCITATION PROTN 5) 40G- LOSS OF EXCITATION PROTN
6) 27/40G- LOSS OF EXCITATION WITH U/V PROTECTION 6) 27/40G- LOSS OF EXCITATION WITH U/V PROTECTION
7) 46G- NEGATIVE PHASE SEQUENCE 7) 46G- NEGATIVE PHASE SEQUENCE
8) 81- UNDER FREQUENCY PROTN STG-1&2 8) 81- UNDER FREQUENCY PROTN STG-1&2
9) 81O- OVER FREQUENCY PROTN STG-1&2 9) 81O- OVER FREQUENCY PROTN STG-1&2
10) 50LBB- GEN. CB FAILURE PROTECTION 10) 50LBB- GEN. CB FAILURE PROTECTION
11) 50G- OVER CURRENT PROTN WITH TIME DELAY 11) 50G- OVER CURRENT PROTN WITH TIME DELAY
12) 61B- DEAD MACHINE PROTN 12) 61B- DEAD MACHINE PROTN
13) 32G- REVERSE POWER PROTN 13) 32G- REVERSE POWER PROTN
14) 24G- OVER FLUXING PROTN 14) 24G- OVER FLUXING PROTN
15) 78G- POLE SLIPPING PROTN 15) 78G- POLE SLIPPING PROTN
D 16) 51V- GEN OVERCURRENT WITH VOLTAGE RESTRAINT PROTN 16) 51V- GEN OVERCURRENT WITH VOLTAGE RESTRAINT PROTN D
17) 27G- UNDER VOLTAGE PROTN 17) 27G- UNDER VOLTAGE PROTN
18) 59G- OVER VOLTAGE PROTN STG-1&2 18) 59G- OVER VOLTAGE PROTN STG-1&2

E E

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 046 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
RELAY LED CONFIGURATION DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: 047
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+R1

TAG REF TAG REF TAG REF TAG REF TAG REF TAG REF TAG REF TAG REF TAG REF
X1 : 1 /006.3B X2 : 1 /013.3A X3 : 1 /009.4A X4 : 1 /012.4D X4 : 51 /028.4C X5 : 1 /031.1E X7 : 1 /031.2B X7 : 51 /041.8D X8 : 1 /017.3C
A X1 : 2 /006.4B X2 : 2 /013.3B X3 : 2 /009.4B X4 : 2 /012.4D X4 : 52 /028.4C X5 : 2 /031.1E X7 : 2 /031.2C X7 : 52 /041.8D X8 : 2 /017.3C A
X1 : 3 SPARE X2 : 3 /013.3B X3 : 3 /009.4B X4 : 3 /012.5D X4 : 53 /028.5C X5 : 3 /031.2E X7 : 3 /032.2B X7 : 53 /041.1E X8 : 3 /017.3C
X2 : 4 /013.3B X3 : 4 /009.4B X4 : 4 /012.5D X4 : 54 /028.5C X5 : 4 /031.3E X7 : 4 /032.2C X7 : 54 /041.1E X8 : 4 /017.4C
X2 : 5 /013.3B X3 : 5 /009.4D X4 : 5 /015.7B X4 : 55 /029.4C X5 : 5 /031.4E X7 : 5 /041.1B X7 : 55 /041.1E X8 : 5 /017.4C
X2 : 6 /013.3B X3 : 6 /009.4D X4 : 6 /015.7B X4 : 56 /029.4C X5 : 6 /032.1E X7 : 6 /041.1B X7 : 56 /041.2E X8 : 6 /017.4C
X2 : 7 /013.3B X3 : 7 /009.4D X4 : 7 /016.2B X4 : 57 /030.2C X5 : 7 /032.2E X7 : 7 /041.1B X7 : 57 /041.2E X8 : 7 /017.5C
X2 : 8 /013.3C X3 : 8 /009.4D X4 : 8 /016.2B X4 : 58 /030.3C X5 : 8 /032.2E X7 : 8 /041.2B X7 : 58 /041.2E X8 : 8 /017.5C
X2 : 9 /013.3D X3 : 9 /010.5B X4 : 9 /016.5C X4 : 59 /030.3C X5 : 9 /032.3E X7 : 9 /041.2B X7 : 59 /041.2E X8 : 9 /017.5C
X2 : 10 /013.3E X3 : 10 /010.5B X4 : 10 /016.5C X4 : 60 /030.3C X5 : 10 /032.3E X7 : 10 /041.2B X7 : 60 /041.3E X8 : 10 /017.6C
X2 : 11 /013.3E X3 : 11 /010.5B X4 : 11 /016.5C X4 : 61 /030.4C X5 : 11 /033.5D X7 : 11 /041.3B X7 : 61 /041.3E X8 : 11 /017.6C
X2 : 12 /013.3E X3 : 12 /010.5B X4 : 12 /016.6C X4 : 62 /030.4C X5 : 12 /033.7D X7 : 12 /041.3B X7 : 62 /041.4E X8 : 12 /017.6C
X2 : 13 /013.3E X3 : 13 /010.5D X4 : 13 /016.6C X4 : 63 /030.5C X5 : 13 /033.7D X7 : 13 /041.3B X7 : 63 /041.4E X8 : 13 /017.6C
X2 : 14 /013.3E X3 : 14 /010.5E X4 : 14 /016.6C X4 : 64 /030.5C X5 : 14 /033.8D X7 : 14 /041.4B X7 : 64 /041.4E X8 : 14 /017.7C
B X2 : 15 /013.3F X3 : 15 /010.5E X4 : 15 /020.7B X4 : 65 /030.6C X5 : 15 /034.1D X7 : 15 /041.4B X7 : 65 /041.4E X8 : 15 /023.5B B
X2 : 16 /013.3F X3 : 16 /010.5E X4 : 16 /020.7B X4 : 66 /030.6C X5 : 16 /034.2D X7 : 16 /041.4B X7 : 66 /041.5E X8 : 16 /023.6B
X2 : 17 /018.3A X3 : 17 /010.7E X4 : 17 /021.2B X4 : 67 /024.5C X5 : 17 /034.3D X7 : 17 /041.5B X7 : 67 /041.5E X8 : 17 /022.3C
X2 : 18 /018.3B X3 : 18 /010.7E X4 : 18 /021.2B X4 : 68 /024.5C X5 : 18 /034.3D X7 : 18 /041.5B X7 : 68 /041.5E X8 : 18 /022.3C
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

X2 : 19 /018.3B X3 : 19 /010.7E X4 : 19 /021.5C X4 : 69 /026.4C X5 : 19 /007.2D X7 : 19 /041.5B X7 : 69 /041.6E X8 : 19 /022.3C


X2 : 20 /018.3B X3 : 20 /010.7E X4 : 20 /021.5C X4 : 70 /026.5C X5 : 20 /007.2D X7 : 20 /041.5B X7 : 70 /041.6E X8 : 20 /022.4C
X2 : 21 /018.3B X3 : 21 /011.4A X4 : 21 /021.5C X4 : 71 /029.4C X5 : 21 /007.3D X7 : 21 /041.6B X7 : 71 /041.6E X8 : 21 /022.4C
X2 : 22 /018.3B X3 : 22 /011.4B X4 : 22 /021.6C X4 : 72 /029.5C X5 : 22 /007.3D X7 : 22 /041.6B X7 : 72 /041.7E X8 : 22 /022.4C
X2 : 23 /018.3B X3 : 23 /011.4B X4 : 23 /021.6C X4 : 73 SPARE X7 : 23 /041.7B X7 : 73 /041.7E X8 : 23 /022.5C
X2 : 24 /018.3C X3 : 24 /011.4B X4 : 24 /021.6C X4 : 74 SPARE X7 : 24 /041.7B X7 : 74 /041.7E X8 : 24 /022.5C
X2 : 25 /018.3D X3 : 25 /011.6B X4 : 25 /023.3B X4 : 75 SPARE X7 : 25 /041.7B X7 : 75 /041.8E X8 : 25 /022.5C
X2 : 26 /018.3E X3 : 26 /011.6B X4 : 26 /023.3B X4 : 76 SPARE X7 : 26 /041.7B X7 : 76 /041.8E X8 : 26 /022.6C
X2 : 27 /018.3E X3 : 27 /011.6C X4 : 27 /023.3C X4 : 77 SPARE X7 : 27 /041.8B X7 : 77 /042.1B X8 : 27 /022.6C
C X2 : 28 /018.3E X3 : 28 /011.6C X4 : 28 /023.3C X4 : 78 SPARE X7 : 28 /041.8B X7 : 78 /042.2B X8 : 28 /022.6C
C
X2 : 29 /018.3E X3 : 29 /011.6C X4 : 29 /024.1C X4 : 79 SPARE X7 : 29 /041.1D X7 : 79 /042.2B X8 : 29 /022.6C
X2 : 30 /018.3E X3 : 30 /011.4D X4 : 30 /024.2C X4 : 80 SPARE X7 : 30 /041.1D X7 : 80 /042.2B X8 : 30 /022.7C
X2 : 31 /018.3F X3 : 31 /011.4D X4 : 31 /024.7D X4 : 81 SPARE X7 : 31 /041.1D X7 : 81 /042.3B X8 : 31 SPARE
X2 : 32 /018.3F X3 : 32 /011.4D X4 : 32 /024.7D X4 : 82 SPARE X7 : 32 /041.2D X7 : 82 /042.3B X8 : 32 SPARE
X2 : 33 SPARE X3 : 33 /011.4D X4 : 33 /024.7D X4 : 83 SPARE X7 : 33 /041.2D X7 : 83 /042.3B X8 : 33 SPARE
X2 : 34 SPARE X3 : 34 /011.6D X4 : 34 /024.8D X4 : 84 SPARE X7 : 34 /041.2D X7 : 84 /042.3B X8 : 34 SPARE
X2 : 35 SPARE X3 : 35 /011.6E X4 : 35 /025.4C X4 : 85 SPARE X7 : 35 /041.2D X7 : 85 /042.4B X8 : 35 SPARE
X2 : 36 SPARE X3 : 36 /011.6E X4 : 36 /025.4C X4 : 86 SPARE X7 : 36 /041.3D X7 : 86 /042.4B X8 : 36 SPARE
X2 : 37 SPARE X3 : 37 /011.6E X4 : 37 /025.5C X7 : 37 /041.3D X7 : 87 /042.5B
X2 : 38 SPARE X3 : 38 /011.6F X4 : 38 /025.5C X7 : 38 /041.4D X7 : 88 /042.5B
X3 : 39 /014.3B X4 : 39 /026.4C X7 : 39 /041.4D X7 : 89 /042.6B
D X3 : 40 /014.3B X4 : 40 /026.4C X7 : 40 /041.4D X7 : 90 /042.6B D
X3 : 41 /014.3B X4 : 41 /027.2C X7 : 41 /041.4D X7 : 91 /042.7B
X3 : 42 /014.3B X4 : 42 /027.2C X7 : 42 /041.5D X7 : 92 /042.7B
X3 : 43 /014.3C X4 : 43 /027.3C X7 : 43 /041.5D X7 : 93 /042.7B
X3 : 44 /014.3C X4 : 44 /027.3C X7 : 44 /041.5D X7 : 94 /042.7B
X3 : 45 /019.3C X4 : 45 /027.4C X7 : 45 /041.6D X7 : 95 /042.8B
X3 : 46 /019.3C X4 : 46 /027.4C X7 : 46 /041.6D X7 : 96 /042.8B
X3 : 47 /019.3C X4 : 47 /027.4C X7 : 47 /041.6D X7 : 97 SPARE
X3 : 48 /019.3C X4 : 48 /027.5C X7 : 48 /041.7D X7 : 98 SPARE
X3 : 49 SPARE X4 : 49 /027.5C X7 : 49 /041.7D X7 : 99 SPARE
X3 : 50 SPARE X4 : 50 /027.6C X7 : 50 /041.7D X7 : 100 SPARE
X3 : 51 SPARE X7 : 101 SPARE
X3 : 52 SPARE X7 : 102 SPARE
E X3 : 53 SPARE X7 : 103 SPARE E
X3 : 54 SPARE X7 : 104 SPARE
X3 : 55 SPARE
X3 : 56 SPARE
X3 : 57 SPARE
X3 : 58 SPARE

F CUSTOMER : BHARAT HEAVY ELECTRICALS LTD. CLIENT: ROHIT FERRO TECH LTD, JAJPUR, ORISSA. TITLE : 11KV GENERATOR PROTECTION PANEL PREPARED : GD REVISION: B SHT : 047 F
HYDERABAD
PROJECT : ROHIT FERRO TECH LTD. CONSULTANT: DEVELOPMENT CONSULTANTS REVIEWED : THY
TERMINAL BLOCK REFERENCE DATE: 3/31/2012
67.5MW CAPTIVE POWER PLANT, JAJPUR PVT LTD. APPROVED : APS CONT: NIL
PO. No.& Date: C117A00076 DATED:16-01-2012
PANEL TYPE : +R1 DRG. NO.: 3269PN491-S-01