1. Wrap around gusset to beam bolted connection – Can we use 2 bolts instead of 3. I know
connection will pass but will geometry work?
2. Rat holes are not provided on the longitudinal beams W200x31 for bottom flange to column
web/doubler plate CJP weld.
3. (1) – Stiffener required Ea. side on the bottom beam at the blocking location for transportation.
7/25/18
PR504 Tekla Model Review Rev0