Room No. Room class Pressure Temperatur Minimum Duration Times per Max flow Daily usage Remark
Sl. No. POU (kg/day)
(EU cGMP) (1/2) e (°C) required flow (min) day (kg/ h)
(kg/h)
General Production Area
01 Material Washing Area N/A Ambient 800 10 5 420

02 Granulation -01 D 22 ± 2°C 500 15 3 375

03 Granulation - 02 D 22 ± 2°C 500 15 3 375

04 Tablet Coating -02 D 22 ± 2°C 800 10 2 267

05 Tablet Coating - 03 D 22 ± 2°C 800 10 2 267

06 Syrup Preparation Room D 22 ± 2°C 1000 25 4 1667

07 Liquid Processing Room D 22 ± 2°C 1200 40 2 1600

Glass Bottle washing Room N/A comfort 500 10 10 833


08
09 Antacid Processing Room C 22 ± 2°C 800 20 2 533

Cream ointment processing area D 22 ± 2°C 500 8 2 133


10
Cephalosporin Production Area ( Single line Distribution) 0

11 Bottle Wash Room N/A comfort 500 10 6 500

12 Tablet Coating Room D 22 ± 2°C 800 5 2 133

Total 7103