TECHNICAL MANUAL

MANUFACTURER: TELEFIRE Fire & Gas Detectors LTD


5 HALAPID ST.
P.O.B 7036
PETACH-TIKVA 49250
ISRAEL

TEL: 972-3-9211955
GSA1000EN FAX: 972-3-9211816
01/03/98 E-Mail: marketing@telefire.co.il
REV : 1.05 Web Site: http//:www.telefire.co.il
TELEFIRE Ltd. GSA-1000 Technical Manual

Table of Contents

1. GSA-1000 GENERAL DESCRIPTION .................................................................................................3


1.1. TECHNICAL DETAILS ........................................................................................................................................4
1.2. PUSH-BUTTONS FUNCTIONS IN A NORMAL OPERATION.........................................................................5
1.3. DISPLAY AND LAMPS........................................................................................................................................5
1.4. DIGITAL DISPLAY ..............................................................................................................................................6

2. PROGRAMMING....................................................................................................................................7
2.1. PUSH-BUTTONS IN PROGRAM MODE ............................................................................................................7
2.2. DIGITAL DISPLAY IN PROGRAMMING MODE .............................................................................................7

3. REMARKS..............................................................................................................................................10

4. WALK TEST ..........................................................................................................................................11

5. BATTERY TEST....................................................................................................................................11

6. SYSTEMS FUSES ..................................................................................................................................11

7. GENERAL INSTRUCTION FOR INSTALLATION ........................................................................12


7.1. INSTALLATION .................................................................................................................................................12
7.2. MARKING ...........................................................................................................................................................12
7.3. TESTS ..................................................................................................................................................................12

8. GSA-1000/4N FEATURES ....................................................................................................................13

9. 16 ZONE CONTROL PANEL ..............................................................................................................13

10. APPENDIX NO. 1 - LIST OF DRAWINGS ........................................................................................14

GSA!000EN REV.: 1.05 (01/03/98) 2


TELEFIRE Ltd. GSA-1000 Technical Manual

1. GSA-1000 GENERAL DESCRIPTION

The GSA-1000 manufactured by Telefire, is a fire alarm and automatic extinguishing control
panel. The unit is computerized and it has the ability to work in different modes, that can be
programmed and changed any time in the field without any special tools. The access is for
authorized personnel only.

The system can work in two or three-wire mode. The system controls 4, 8 or 16 detection lines -
according to the Control Panel capacity and the related programmable outputs lines that enable
the operation of sirens, automatic extinguishing devices, evacuation alarm or any other outputs
devices.

In addition there are separate general outputs for fire alarm


bells , automatic dialer, magnetic door releasers and "dry" contacts for general alarm and
trouble. enabling interface to other systems.

The system modes enable to work as a regular control panel, an extinguishing control panel
including crossed zones, extinguisher delay and alarm evacuation or a any combination of both.

The display of the control panel is clear and detailed. It is based on LED, digital display and
optional liquid crystal display (LCD). The control panel can be expanded to 16 detection zones
and it includes the source for computer communication, digital secondary board etc. All the
control panel lines are protected again short-circuit and cut. The output lines are constantly
controlled and automatically disconnected, in over current condition.

The battery is supervised including loading test to insure normal operation in main failure
condition. Each event in the system is clearly displayed to allow easy and fast trouble detection
by the user, technician or service personal of the different levels.

The system includes alarm verification for better reliability, and walk test mode for easy servicing.

The GSA-1000 is manufactured in 4 models :-

a. GSA-1000/4N 4 Zone Fire Detection Control Panel


(without extinguishing).

b. GSA-1000/4 4 Zone Fire Detection Control Panel


and Automatic Extinguishing.

c. GSA-1000/8 8 Zone Fire Detection Control Panel


and Automatic Extinguishing.

d. GSA-1000/16 16 Fire Detection Control Panel


and Automatic Extinguishing.

GSA!000EN REV.: 1.05 (01/03/98) 3


TELEFIRE Ltd. GSA-1000 Technical Manual

Remarks :-

a. The GSA-1000 4,8 and 16 are programmable and the GSA-1000/4N has
fixed functions (See page 13).

b. The GSA-1000 4,8 and 16 can be connected to a Digital Remote Panel type
TDA-1000. See the Technical Manual TDA-1000.

1.1. TECHNICAL DETAILS

* Input voltage - 230 Vac


* Input current - 0.2A
* Battery`s voltage - 24 Vdc
* Battery's capacity - 1.2-6AH
* Max. D.C. current - 1.5A (option 3A)
* Detection zones - 8, current limited (two-wire mode)
* Outputs - 8, for comprehensive current of 0.8A for activating at the same time or 0.5A per
output for a single operation.
* Dialer output - 0.3A
* Alarm bell output - 0.3A
* Magnetic doors' outputs - 1A
* Extinguishing delay - 30 seconds
* Extinguishing pulse duration - 15 seconds
* EOL. (END OF LINE) value - 5.1K
* Resistance range for alarm state - 50-570 Ohm
* D.C standby current - 75mA
* D.C alarm current alarm - 150mA (not including output device current)

GSA!000EN REV.: 1.05 (01/03/98) 4


TELEFIRE Ltd. GSA-1000 Technical Manual

1.2. PUSH-BUTTONS FUNCTIONS IN A NORMAL OPERATION

RESET - reset to normal operation after an alarm condition


SOUND OFF - for silencing alarm bells and trouble sounders
INHIBIT - inhibit or stops the extinguishing process
MEMORY - recall the content of the event memory such as
alarm and trouble
- advancing the zone number for deactivation
or reactivating
ON/OFF - activating or reactivating alarm zone
TEST - use to test on the display and output devices
except extinguishing outputs

1.3. DISPLAY AND LAMPS

AC - indicates the main Voltage


OPERATION - lits when system is in normal operation
G. ALARM - lits in alarm condition
SILENCED - blinks after Sound_Off operation
G. TROUBLE - lits in case of trouble in the system
BATTERY - indicates trouble in battery.
INHIBIT - indicates the inhibit of the extinguishing process
ALARM - lits when the display zone is in alarm condition
TROUBLE - lits when the display zone is in trouble condition
* MEMORY - indicates that there are more events then shown
on the display

* When displaying a zone for ON/OFF process the memory lamp will blink for about 5 sec.,
during this time you can change the ON/OFF status for the display zone

GSA!000EN REV.: 1.05 (01/03/98) 5


TELEFIRE Ltd. GSA-1000 Technical Manual

1.4. DIGITAL DISPLAY

The control panel is equipped with two 7 signments display, that blinks the number 8 in normal
operation condition.

In case of main power failure they will turn off, to reduce standby current consumption.

In case of alarm or trouble, the display indicators as follows:

The left digit displays the zones number or the output number, the right digit displays the
condition.

The point in the left digit serves to extinguish between Input zone and Output zone.

DIGIT
LEFT RIGHT DESCRIPTION

1-8 Number of detection zone


1.-8. Number of output
- Disconnect trouble
| Short circuit trouble
U Unused - zone in off condition
H Horn output
d Dialer output
G + Positive ground fault detection
G - Negative ground fault detection
b F Battery fail (low Voltage)
b C Battery connection (batt. disconnect)
b A Weak battery (unable to deliver high current)
U Detectors voltage failure
U - Tension failure
- - System in walk test condition
C - Trouble in RS232 communication to the computer.
C Trouble in the communication between the master to the
slave board in the 16 zone Control Panel.

Remarks :-

If F1 to F5 is displayed, call your service supporter or return the equipment to the manufacturer.

GSA!000EN REV.: 1.05 (01/03/98) 6


TELEFIRE Ltd. GSA-1000 Technical Manual

2. PROGRAMMING
The modes of operation are field programmable and can be performed as follows:

In the top middle of the control card there is a program jumper marked as W01, connect the
jumper between points 1 & 2 - program mode.

2.1. PUSH-BUTTONS IN PROGRAM MODE

^ - Advanced mode, zone number, and output number-displayed ^


in the left digit.

ON/OFF - Change condition - displayed in the right digit

TEST - Advanced backwards mode, zone number, and output


number displayed in the left digit

MEMORY - Storing the setting in a permanent memory - to be used


before going back to normal operation.

RESET - Going back to the first step of programming

2.2. DIGITAL DISPLAY IN PROGRAMMING MODE

Left digit - Indicates mode of operation, zone number and, output number.
Right digit - Indicates condition of operation for the displayed in the left digit.

The program can be divided to 3 blocks:


I General condition
II Programming input zones parameters
III Programming outputs parameters

Remarks:-

a.To change the mode, zone or output (left digit) use the ∧ and TEST push-buttons.

b.To change condition use the ON/OFF key.

GSA!000EN REV.: 1.05 (01/03/98) 7


TELEFIRE Ltd. GSA-1000 Technical Manual

2.2.1. GENERAL CONDITION

DIGIT
LEFT RIGHT DESCRIPTION .
(modes & G. output)

A 2 two wire operation


A 3 three wire operation
b 0 without alarm verification
b 1 with alarm verification
C 0-7 time delay-in blocks of 8 sec. operates only
when alarm verification is activated (B 1)
Example: C 2 represents 16 sec. alarm delay.
d 0 8 zone control panel
d 1 16 zone control panel
E 0 without external communication
E 1 with external communication
F 0 trouble contact normal activation
F 1 trouble contact resets in sound off condition
h 0 alarm contact normal activation
h 1 alarm contact resets in SOUND-OFF condition

2.2.2. DETECTORS ZONE (INPUT)

DIGIT
LEFT RIGHT DESCRIPTION
(zone number)

1-8 0 detector zone in normal operation


1-8 1 detector zone with delayed alarm [according time
delay setting (C) ]
1-8 2 cross zoning between two zones for alarm purpose

NOT FOR EXTINGUISHING !!! to be preformed in the


following groups 1&2 3&4 5&6 7&8

GSA!000EN REV.: 1.05 (01/03/98) 8


TELEFIRE Ltd. GSA-1000 Technical Manual

In the 16 zone Control Panel, in the programming mode only the input or output lines with two
digits will be displayed as follows :-

Display Zone Number


A 10
b 11
C 12
d 13
E 14
F 15
G 16

2.2.3. OUTPUT LINES

DIGIT
LEFT RIGHT DESCRIPTION
(output number)

1.-8. 0 general alarm

1.-8. 1 general alarm silenced

1.-8. 2 1:1 auxiliary zone alarm - each output will be


activated according its input zone

1.-8. 3 1:1 zone 1 will activate output 1 etc. silenced

1.-8. 4 1:1 immediate extinguishing output

1.-8. 5 1:1 30 sec. extinguishing output

1.-8. 6 crossed zone immediate extinguishing output

1.-8. 7 crossed zone 30 sec. delayed extinguishing output

1.-8. 8 crossed zone evacuation alarm

Remarks -

An output that is defined as an extinguishing output must be terminated with the End-Of-Line
circuit type EXT-1.

GSA!000EN REV.: 1.05 (01/03/98) 9


TELEFIRE Ltd. GSA-1000 Technical Manual

3. REMARKS

* Extinguisher output is activated for 15 sec. only.

* Crossed zones outputs are relatively to input zones in pairs


1&2 3&4 5&6 7&8

* Do not mix between the cross zoning for alarm purposes (to be set in the detector zone
programming) and the cross zoning for extinguishing purposes(to be set in output
programming).

* During programming when keys are not used for about 5 minutes the buzzer will remind you not
to forget the system in program mode.

At the end of setting, push the MEMORY key, wait for the letter P to appear on the display and
after its being turn off, put the program jumper back to normal (points 2 & 3).

When activating RESET push-button the system will display in the left digit the wiring mode (the
number 2 or 3) the point indicates if alarm verification is being activated and in the right digit the
number of extinguishers.

After activating an extinguisher the system will display the letter E and a number. EG - the
number of the activated extinguisher. Using the RESET key will not erase this situation, to insure
changing or refilling the extinguisher.

To bring the system back to normal operation, bring the system to program mode for a few sec.
and return to normal operation and then the letter E will disappeared.

EXT-1 : Automatic extinguishing End-Of-Line device.

When using the EXT-1 install the card in the End-Of-Line as close as possible to the
extinguisher.

When using a detonator, disconnect jumper JP1.

When using a solenoid, observe the existence of a jumper JP1.

GSA!000EN REV.: 1.05 (01/03/98) 10


TELEFIRE Ltd. GSA-1000 Technical Manual

4. WALK TEST
The GSA-1000 has a walk test mode for periodically detector zoning To activate this mode push
simultaneously the TEST & ON keys, the indication on the display is - - during the test, the alarm
disabled.

The control performed automatic reset after about 15 sec. from receiving an alarm from a
detector. In case of a second alarm from another zone (a true alarm), the alarm will be activated.

To stop the test mode push the RESET key.

Anyway after 30 minutes on the test mode the system will automatically reset itself.

5. BATTERY TEST
The GSA-1000 performs automatically rechargeable battery supervision and test, including the
capability to deliver enough power to activate the system’s components.

The charger is a constant voltage type.

6. SYSTEMS FUSES

Fuse
Location Number Function Value
Transformer Main Fuse Main’s Input Protection 0.5A
Power Supply Board F1 Battery Circuit Protection 3A
Main Board F1 Programmable Output’s Protection 2A
F1 General Horn and Dialer Protection 1A
F3 Door Holder Output Protection 1A
F4 Detection Line Protection 0.5A

WARNING : avoid damaging the unit by replacing the correct values of fuses.

GSA!000EN REV.: 1.05 (01/03/98) 11


TELEFIRE Ltd. GSA-1000 Technical Manual

7. GENERAL INSTRUCTION FOR INSTALLATION

7.1. INSTALLATION

Connect the mains to the system directly to a circuit breaker, not shared by other circuits. Connect
the building ground to the control panel box by using the marked grounding terminal.

Use approved wires according to local regulations, but in any case use a wire thicker than 0.8 mm
diameter.

Calculate the total current needed for the automatic dialer, automatic extinguishers, horns, etc. Do
not exceed a total current of 1A.

Connections to the system during installation or maintenance will be done when all power sources
are disconnected (mains and batteries).

The harming of the automatic extinguishing will be after testing the systems for a commanded period
of 1 week.

7.2. MARKING

Mark all wires connected to the detection zones and outputs.

Write the zone names on the panel front in the space provided for that.

Stick the name and telephone of the installer, for service.

7.3. TESTS

Perform a operating test at least twice a year.

Activate all the system devices.

Disarm the automatic extinguisher during the test!

GSA!000EN REV.: 1.05 (01/03/98) 12


TELEFIRE Ltd. GSA-1000 Technical Manual

8. GSA-1000/4N FEATURES

The GSA-1000/4N is equipped with fixed features as follows : -

1. Only the first 4 detection zones are active.

2. The general outputs and relays operate in the same mode as the GSA-1000/8.

3. The outputs 1 to 8 are programmed as follows : -

Output 1 : activated in case of alarm in zone 1 - not silenced.

Output 2 : activated in case of alarm in zone 2 - not silenced.

Output 3 : activated in case of alarm in zone 3 - not silenced.

Output 4 : activated in case of alarm in zone 4 - not silenced.

Output 5 : general output - not silenced.

Output 6 : general output - not silenced.

Output 7 : general output - silenced.

Output 8 : general output - silenced.

Remarks : -

a. The alarm verification feature is continuously activated.


b. Outputs 1 to 4 serve as a private output related to each zone.
c. Outputs 5 and 6 are general outputs.
d. Outputs 7 and 8 are general outputs - silenced, identical to the general horn output.

9. 16 ZONE CONTROL PANEL

In the 16 Zone Control Panel 2 main boards are used. The upper one is equipped with a display card
and serves as the master board. The lower board has no display and serves as a slave.

Zone or output 1 on the lower panel will be displayed as zone number 9.

Zone or output 8 on the lower panel will be displayed as zone number 16.

The general outputs on the main board serve both cards.

The data between the two boards is transferred to the COM connectors located in the upper right
side of each board.

GSA!000EN REV.: 1.05 (01/03/98) 13


TELEFIRE Ltd. GSA-1000 Technical Manual

10. APPENDIX NO. 1 - LIST OF DRAWINGS

DRAWING S/N TITLE

1 MAIN BOARD CONNECTIONS

2 DETECTION ZONES CONNECTIONS &


PROGRAMMABLE OUTPUT CONNECTIONS

3 GENERAL OUTPUT CONNECTIONS

4 POWER SUPPLY/BATTERY CHARGER FOR THE GSA-


1000

5 BEAM DETECTOR CONNECTIONS TO THE GSA-1000

6 BREAK GLASS CALL POINT CONNECTIONS

7 STANDARD DETECTION LINE WITH PRIVATE/PRIVATE


& GROUPING LAMPS CONNECTIONS

GSA!000EN REV.: 1.05 (01/03/98) 14


GSA-1000 Technical Manual

Communication
Holders

Trouble
Relay

Connector to
Relay
Alarm

Dialer
Door

Auxiliary Connection
Horn

Out
Out

Remote Panel or
Computer
NC C NO NC C NO
J01 12 3 Progra-
J06 J08
mming
J03 W01 Jumper
Power Connector

GSA-1000 FIRE ALARM CONTROL PANEL


from the
Power Supply
MAIN BOARD CONNECTIONS

DRAWING NO. 1
ALARM G. ALARM
TROUBLE BELL SILENCED A.C. POWER

15
MEMORY G. TROUBLE
BATTERY OPERATE
INHIBIT
ON/OF TEST SOUND OF RESET

GSA!000EN REV.: 1.05 (01/03/98)


J04 J07

24

15
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
Programmable Output Connections Detection Zones Connections Optional
TELEFIRE Ltd.

To gas or beam
Detectors 24V
TELEFIRE Ltd. GSA-1000 Technical Manual

F04 Detector's power protection


1/2 A

J07

24
15
1 2 3 4 5 6 7 8

Supervised two-wire detection zone


Detector

E.O.L.* * End-Of-Line
5.1K

PROGRAMMABLE OUTPUT CONNECTIONS

Output
circuits
protection

J04
1 2 3 4 5 6 7 8

E.O.L.
5.1K E.O.L. output for
Supervised Outputs EXT-1
extinguishing
LAMP
Lamp
EXT-1

To the From the


Automatic Control Panel
Extinguisher Extinguishing
output

GSA-1000 FIRE ALARM CONTROL PANEL

DRAWING NO. 2

GSA!000EN REV.: 1.05 (01/03/98) 16


TELEFIRE Ltd. GSA-1000 Technical Manual

GENERAL OUTPUT CONNECTIONS

5.1K
TDM-500 Automatic Dialer E.O.L
and Announciator
( + ) A 24V

(-)
GND
P.O

NOT SUPERVISED SUPERVISED

General Horn
Output

Alarm Trouble Dialer


Magnetic Door
Relay Dry Relay Dry Output
Holder Output
Contacts Contacts

NC C NO NC C NO

J03

1A F03
Door Holder
Output Protection

F02
1A
General Horn and
Dialer Protection

GSA-1000 FIRE ALARM CONTROL PANEL

DRAWING NO. 3

GSA!000EN REV.: 1.05 (01/03/98) 17


TELEFIRE Ltd. GSA-1000 Technical Manual

POWER SUPPLY / BATTERY CHARGER FOR THE GSA-1000

J01
Power Output to
the Main Board

F01
Battery Fuse
3A

J03 J02
Battery
Connections
A.C. Input from 24 Vdc
the Transformer
27Vac

Grounding Battery Battery


Connection 12V 12V

* Observe polarity of battery connections

* Charging current and battery voltage are


adjusted and monitored by the microcomputer

Main
Supply 0
Input Main Fuse
F 1/2A
230Vac

GSA-1000 FIRE ALARM CONTROL PANEL

DRAWING NO. 4

GSA!000EN REV.: 1.05 (01/03/98) 18


TELEFIRE Ltd. GSA-1000 Technical Manual

BEAM DETECTOR CONNECTIONS TO THE GSA-1000

F04 Detection Line


1/2 A Protection

24
15
1 2 3 4 5 6 7 8
E.O.L. Device

Zone

Resistor
200R
24Vdc

24 Vdc IN
Trouble Contact
Alarm Contact

BEAM DETECTOR
N.O

N.C

GSA-1000 FIRE ALARM CONTROL PANEL

DRAWING NO. 5

GSA!000EN REV.: 1.05 (01/03/98) 19


TELEFIRE Ltd. GSA-1000 Technical Manual

BREAK GLASS CALL-POINT CONNECTIONS

(+) (+)

1 1A
Continuation of Line
2 2A or E.O.L. Resistor

(-) (-)
Break Glass Unit
TPB!10

Break Glass Call Poit Type KR70/SR/D including Internal Resistor 270R *

CALL POINT CROSS-ZONE CONNECTIONS FOR EXTINGUISHING PURPOSES

(+) (+)

Continuation of Line A
Zone A
or E.O.L. Resistor
(!) (!)

Diode Diode
1N4002 1N4002

1 1A

2 2A

(+) (+)

Zone B
Break Glass Unit Continuation of Line B
TPB!10 or E.O.L. Resistor
(!) (!)

*
Connect the wire to the diodes by welding and cover with isolation tube **

GSA-1000 FIRE ALARM CONTROL PANEL

DRAWING NO. 6

GSA!000EN REV.: 1.05 (01/03/98) 20


TELEFIRE Ltd. GSA-1000 Technical Manual

STANDARD DETECTION LINE WITH PRIVATE LAMPS CONNECTIONS

Private
Private Lamp
Lamp
TFL-1 TFL-1 Private
Lamp
E.O.L
5.1K

Line Out
Lamp
Lamp Output
Output

Line In
Line In
Detector Base Last Detector Base
TFB-110 TFB-110

STANDARD DETECTION LINE WITH PRIVATE AND GROUPING LAMPS CONNECTIONS

Grouping Lamp
TFL-1

Private Private Lamp


Lamp
TFL-1 TFL-1

1N 4002 diode E.O.L


5.1K

Lamp Line Out Lamp Line Out


Output Output

Line In Line In

Detector Base Last Detector Base


TFB-110 TFB-110

GSA-1000 FIRE ALARM CONTROL PANEL

DRAWING NO. 7
g1000h08 (3/98)

GSA!000EN REV.: 1.05 (01/03/98) 21