Bushing-Type Current Transformers

(BCT)

Instrument Transformers, Inc.

is a recognized world leader in the design and manufacture of

Instrument transformers. As part of ITI’s product scope, the company

produces a diversif ied range of bushing current transformers. BCT which

are installed on 600 Volt , and higher electrical systems.

Type B07- Current Transformers are for use over outdoor bushings of

Power Transformers, Bulk Oil Circuit Breakers and other Dead - Tank

Circuit Breakers.

The B07 bushing type mounts externally over the apparatus bushing on

the cover of the apparatus. These transformers are used primarily for

relaying but may also be used for metering where rating allows.

1
www.GEMultilin.com
Features

• Conforms to IEEE Std., • Weather resistant

C57.13 or IEC, 60044-1.

Consult factory for other


• High mechanical impact
standards
and dielectric strength

• Weather proof outdoor

terminal box of heavy, • Completely encapsulated

molded, weatherproof, in polyurethane

polyester resin,

glass-reinforced

• Easy installed
• Conduit connections - Two

1” threaded hubs for

horizontal take-off and a 1”


• Clearly identif ied
IPS knockout in the
secondary terminals
bottom

• Stainless steel or
• Mounting feet can be located anywhere
aluminum, nameplate
around the inner or outer periphery

• Broad range of sizes

and ratios

2
www.GEMultilin.com
Construction
The box is f itted with two 1” IPS In an installation where it is not

threaded openings for horizontal desirable for the relay to “see” a

conduit takeoff and and one bushing flash-over, the mounting

knockout in the bottom for 1” IPS clamps should be placed around

The toroidal cores are made of conduit , the flange for the cover the outer periphery of the

cold-rolled, high-permeability, is at 45 degree angle which gives transformer. The ground

grain-oriented, silicon steel, maximum accessibility for wiring conductor should not pass

annealed after forming under and connecting. through the window.

precisely controlled conditions.

The grain of the core steel is In an installation where it is

oriented in the direction of the desirable for the relay to “see”

magnetic flux, thus minimizing the bushing flash-over current ,

the core losses and maximizing the mounting clamps should be

the accuracy.. positioned around the inner

periphery and the ground

W indings conductors should pass through

The winding are wound over the window. The inside diameter

the insulated core on large of the current transformer should

toroidal winding machines. be increased by 4” to

They are fully distributed around accommodate this arrangement .

the core on all taps so that the Ground Shield

leakage reactance is low on Ground shields are available. Mounting Clamps

each tap. The installation of the current The mounting clamps are of

transformer reduces the aluminum and held together with

Encapsulation line-to-ground strike distance of the 1/2” stainless steel studs

The core and coils are the apparatus on which it is (continuously threaded) and the

encapsulated in polyurethane. mounted, a ground shield should stainless steel nuts, that make it

The system used is a proprietary be used. very easy to install. Mounting

formulation. It was developed The ground shields are clamps also support optional

specif ically to meet the rigorous ground shield.

electrical, physical and chemical Clamps can be placed at any

requirements of outdoor, convenient location around the

electrical insulation. inner or outer periphery of the

This encapsulation system transformer. Three complete sets

demonstrates excellent weather are included with each trans-

resistance. former.

The U.V.-stabilized insulation has

adequate elasticity to

compensate for dimensional

changes of the core, caused by

temperature variations, without

cracking or crazing. fabricated of aluminum and f it

closely over the top of the

Secondary Terminals and current transformer.

The shield purpose is to prevent


Conduit Box
a bushing flash-over from
The secondary terminals are #10-
penetrating the insulation and
32 screws in tappedbosses. The
impressing a high voltage upon
terminals are housed in a
the secondary winding,
polyester terminal box of sturdy
interconnecting cables, and
construction with a neoprene
relays.
gasket and polyester cover.

3
www.GEMultilin.com
Type BO7
Current Transformer

Standard Selection

STANDARD CURRENT TRANSFORMERS SELECTION GUIDE*

DIM
Catalog Relaying DIM DIM Approx.
“C”**
Ratio
Number Accuracy “A”** “B”** Weight
MAX.

B07—601—12 600:5MR C400 12.00 24.75 4.50 245 lbs.

B07—601—18 600:5MR C400 18.00 31.00 4.50 340 lbs.

B07—601—20 600:5MR C400 20.00 33.00 4.25 355 lbs.

B07—601—22 600:5MR C400 22.00 35.00 4.25 385lbs.

B07—601—26 600:5MR C400 26.00 39.00 4.25 425 lbs.

B07—601—28 600:5MR C400 28.00 40.75 4.25 450 lbs.

B07—601—32 600:5MR C400 32.00 43.50 5.00 475 lbs.

B07—122—12 1200:5MR C800 12.00 24.75 4.50 233 lbs.

B07—122—18 1200:5MR C800 18.00 30.75 4.50 307 lbs.

B07—122—20 1200:5MR C800 20.00 32.75 4.50 331 lbs.

B07—122—22 1200:5MR C800 22.00 34.75 4.50 356 lbs.

B07—122—26 1200:5MR C800 26.00 38.75 4.50 406 lbs.

B07—122—28 1200:5MR C800 28.00 40.75 4.50 429 lbs.

B07—122—32 1200:5MR C800 32.00 43.50 4.75 460 lbs.

B07—202—12 2000:5MR C800 12.00 24.75 3.75 200 lbs.

B07—202—18 2000:5MR C800 18.00 30.75 3.75 240 lbs.

B07—202—20 2000:5MR C800 20.00 32.75 3.75 255 lbs.

B07—202—22 2000:5MR C800 22.00 31.00 3.75 275 lbs.

B07—202—26 2000:5MR C800 26.00 38.75 3.75 315 lbs.

B07—202—28 2000:5MR C800 28.00 40.75 3.75 325 lbs.

B07—202—32 2000:5MR C800 32.00 43.50 3.75 355 lbs.

B07—302—12 3000:5MR C800 12.00 24.75 3.75 144 lbs.

B07—302—18 3000:5MR C800 18.00 30.75 3.75 189 lbs.

B07—302—20 3000:5MR C800 20.00 32.75 3.75 202 lbs.

B07—302—22 3000:5MR C800 22.00 34.75 3.75 215 lbs.

B07—302—26 3000:5MR C800 26.00 38.75 3.75 243 lbs.

B07—302—28 3000:5MR C800 28.00 40.75 3.75 257 lbs.

B07—302—32 3000:5MR C800 32.00 43.50 3.75 268 lbs.

* CONSULT FACTORY FOR OTHER SIZES & RATINGS

** ALL DIMENSIONS ARE + 0.25 TOLERANCE.

4
www.GEMultilin.com
Type BO7
Ground Shield

Standard Selection

Approx. DIM DIM DIM


Part Number Model Number
Weight “A” “B” “C”

1221B27396—10 B07—GS—1225 7.5 lbs. 12.00 25.19 26.94

1221B27396—11 B07—GS—1831 10 lbs. 18.00 31.19 32.94

1221B27396—12 B07—GS—2033 11 lbs. 20.00 33.19 34.94

1221B27396—13 B07—GS—2235 11.5 lbs. 22.00 35.19 36.94

1221B27396—14 B07—GS—2639 13 lbs. 26.00 39.19 40.94

1221B27396—15 B07—GS—2841 14 lbs. 28.00 41.19 42.94

1221B27396—16 B07—GS—3244 14 lbs. 32.00 43.19 45.69

TYPE B07 STANDARD MULTI RATIO TAPS *

Nominal Ratio - 600:5 Nominal Ratio - 1200:5 Nominal Ratio - 2000:5 Nominal Ratio - 3000:5

Available Available Available Available


Connections Connections Connections Connections
Ratios Ratios Ratios Ratios

600:5 X1-X5 1200:5 X1-X5 3000:5 X1-X5

500:5 X2-X5 1000:5 X2-X5 2000:5 X1-X5 2500:5 X2-X5

450:5 X3-X5 900:5 X3-X5 1600:5 X2-X5 2200:5 X3-X5

400:5 X1-X4 800:5 X1-X4 1500:5 X1-X4 2000:5 X1-X4

300:5 X2-X4 600:5 X2-X4 1200:5 X1-X3 1500:5 X2-X4

250:5 X3-X4 500:5 X3-X4 1100:5 X2-X4 1200:5 X3-X4

200:5 X4-X5 400:5 X4-X5 800:5 X2-X3 1000:5 X4-X5

150:5 X1-X3 300:5 X1-X3 400:5 X4-X5 800:5 X1-X3

100:5 X1-X2 200:5 X1-X2 500:5 X1-X2 500:5 X1-X2

50:5 X1-X3 100:5 X1-X3 300:5 X3-X4 300:5 X1-X3

* NON-STANDARD ANSI TAPS ARE ALSO AVAILABLE

5
www.GEMultilin.com
Other Cast Resin BCTS

Outdoor
600 V Class, 10 kV BIL, 60 Hz

Features

• Flexibility of customer specif ied

size and accuracy rating allows

for custom-f it with this

economical design

• Ratios may be supplied as

single-ratios , dual-ratio,
Bushing Type CT,
or multi-ratios per standard
600 V Class,
IEEE taps. Non-standard
10kV BIL, 60 Hz
taps also available

• Optional aluminum ground

shield design to provide

bushing flashover protection

Shown with terminal


• Permanent stainless steel or
cover off
aluminum nameplate, with

pertinent information, mounted

on the transformer

• Conforms to IEEE Standard


Construction Quoting and ordering
C57.13
information
• Weather proof Polyurethane.

• Typical excitation data This encapsulation system


1) Minimum Inside Diameter
demonstrates excellent
available upon request
2) Maximum Outside Diameter
weather resistance as

described in the proceeding


3) Maximum Height allowed
• Three-point mounting bracket
B07 pages 4) Specify Ratio
arrangement supplied with
(Single, Dual or Multi-ratio)
every transformer, mounting
• Toroidal core is made
clamps and stainless steel 5) Accuracy Requirements
cold-rolled, grain-oriented
all-thread studs and hardware 6) Burden Requirements
silicon steel that is annealed
provides easy mounting
7) Rating Factor
after forming to minimize

core loss 8) Any other mechanical or


Application
environmental limitations
Externally mounted bushing
• Fully distributed, copper
current transformer for use over
secondary winding, on all
apparatus bushing on power
taps, provides a low leakage
transformers and circuit breakers
reactance on each ratio

This design can be manufactured


• Spacious, f iberglass-rein
to customer specif ied size and
forced polyester conduit box
electrical rating to use on
supplied with two 1” threaded
applications where the
hubs and a 1” I.P.S. knockout in
standard B07 design is
thebottom. Secondary
unsuitable. A variety of relay
terminals are #10-32 brass
accuracy and metering accuracy
screws in tapped inserts
ratings can be obtained

6
www.GEMultilin.com
Tape Wrapped

BCTS
600 V Class, 10 kV BIL, 60 Hz

Features

• Economical design for

custom-f it to purchaser’s

size and electrical rating

requirements

• May be used in oil, above oil,

under cans, or indoor applications

Bushing Type CT,

• Ratios may be supplied as 600 V Class,

single-ratios , dual-ratio, 10kV BIL, 60 Hz

or multi-ratios per standard

IEEE taps. (Non-standard

taps also available)

Construction Quoting and ordering

information
• Pressboard nameplate
• Units can be tapped with

aff ixed to unit , with pertinent cloth or polyester

information and polarity 1) Minimum Inside Diameter

marking • Fully impregnated cotton 2) Maximum Outside Diameter

tape wrapped BCTs are 3) Maximum Height allowed

• Conforms to IEEE Standard fully compatible with


4) Specify Ratio
C57.13 hot transformer oil and
(Single, Dual or Multi-ratio)
prevents moisture intrusion
5) Accuracy Requirements
into the core and windings.
• Typical excitation data
6) Burden Information
polyester tape over windings
available upon request
also provides additional 7) Rating Factor

moisture protection 8) Any other mechanical or


• Lead wire length sized to

environmental limitations
purchase’s specif ication
• Toroidal core is made

cold-rolled, grain-oriented
Application
silicon steel that is annealed
For use around apparatus
after forming to minimize
bushings indoor, or internally
core loss
mounted applications in

transformer oil, or above the oil,


• Fully distributed, copper
inside of circuit breakers or power
secondary winding, on all
transformers. Design manufactured
taps, provides a low leakage
for custom-f it applications in
reactance on each ratio
current transformer pocket areas

inside of electrical equipment .


• 600 Volt rated, #10 AWG

oil-compatible, wire-marked

leads, sized to purchaser

specif ications

7
www.GEMultilin.com
www.GEMultilin.com
USA, Canada, Asia, Latin America Europe, Middle East , Africa

Tel: +1-800-547-8629 Tel: +34-94-485-88-00

Fax: +1-905-201-2455 Fax: +34-94-485-88-45

e-mail: sales.multilin@ge.com e-mail: gemultilin.euro@ge.com

Bushing Current Transformer Please refer to our website www.GEMultilin.com for more detailed contact information CS00A40726 Rev.1 6/06