The document summarizes the electrical load calculations and space requirements for a sports hall educational facility. It calculates the total KVA load as 18.36 KVA by summing the loads of the ground floor and second floor. It recommends having 2 generator sets of 9.1822 KVA each plus 1 spare generator set of the same size, for a total generator capacity of 27.5467 KVA. It also provides the recommended dimensions for the switch gear room, generator set room with and without acoustics, and transformer.
The document summarizes the electrical load calculations and space requirements for a sports hall educational facility. It calculates the total KVA load as 18.36 KVA by summing the loads of the ground floor and second floor. It recommends having 2 generator sets of 9.1822 KVA each plus 1 spare generator set of the same size, for a total generator capacity of 27.5467 KVA. It also provides the recommended dimensions for the switch gear room, generator set room with and without acoustics, and transformer.
The document summarizes the electrical load calculations and space requirements for a sports hall educational facility. It calculates the total KVA load as 18.36 KVA by summing the loads of the ground floor and second floor. It recommends having 2 generator sets of 9.1822 KVA each plus 1 spare generator set of the same size, for a total generator capacity of 27.5467 KVA. It also provides the recommended dimensions for the switch gear room, generator set room with and without acoustics, and transformer.