1 Scope............................................................. 2
2 Conflicts and Deviations................................ 2
3 References..................................................... 2
4 Engineering Units........................................... 4
5 Definitions...................................................... 4
6 Cable Specifications....................................... 5
7 Marking........................................................ 19
8 Testing......................................................... 20
9 Other Miscellaneous Requirements............. 21
1 Scope
2.1 Any conflicts between this specification and other applicable Saudi Aramco
Materials System Specifications (SAMSSs), Engineering Standards (SAESs),
Standard Drawings, (SASDs), or industry standards, codes, and forms shall be
resolved in writing by the Company or Buyer Representative through the
Manager, Process and Control Systems Department of Saudi Aramco, Dhahran.
2.2 Direct all requests to deviate from this specification in writing to the Company
or Buyer Representative, who shall follow internal company procedure
SAEP-302 and forward such requests to the Manager, Process and Control
Systems Department of Saudi Aramco, Dhahran.
3 References
Materials or equipment supplied to this specification shall comply with the latest edition
of the references listed below, unless otherwise noted.
Page 2 of 21
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-913
Issue Date: 24 January 2012
Next Planned Update: 24 January 2017 Instrumentation and Thermocouple Cable
Fieldbus Foundation
FF-844 H1 Cable Test Specification
British Standard
BS 6387 Performance Requirements for Cables Required to
Maintain Circuit Integrity under Fire
Conditions
Military Specification
MIL-W-25038 General Specification for High Temp, Fire
Resistant, and Flight Critical Electrical Wire
Page 3 of 21
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-913
Issue Date: 24 January 2012
Next Planned Update: 24 January 2017 Instrumentation and Thermocouple Cable
4 Engineering Units
All dimensions and measurements shall be in the “International System of Units” (SI),
and may be followed by the equivalent value in English units bracketed in parentheses
( ). When not critical, the equivalent dimensions and measurements may be rounded off
to their nearest practical value.
5 Definitions
Crosslink: A process in which chemical bonds are established between long chain
polymer molecules. When applied to polyolefin materials, the material properties
change from thermoplastic to thermoset plastic.
ITC: Instrumentation tray cable, per NFPA 70, NEC Article 727.
PLTC: Power-limited tray cable, per NFPA 70, NEC Article 725.
Page 4 of 21
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-913
Issue Date: 24 January 2012
Next Planned Update: 24 January 2017 Instrumentation and Thermocouple Cable
6 Cable Specifications
6.1 General
Due to differences in manufacturing and design, some cables will require fillers,
binders and separator tapes. These components shall be provided whenever they
comprise an integral part of the standard design of the cable. The utilization of
these components shall not constitute a deviation from this Specification.
6.2.1 Conductor
Flame retardant PVC, nylon- jacketed PVC (For Type TC cables only)
or thermoset crosslinked polyolefin (XLPO or XLPE), minimum
temperature rating 90°C.
Page 5 of 21
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-913
Issue Date: 24 January 2012
Next Planned Update: 24 January 2017 Instrumentation and Thermocouple Cable
0.38 mm (15 mils) minimum average thickness for Types PLTC and
ITC Cables.
6.2.6 Assembly
40 to 60 mm.
One black wire, one white wire for pairs; one black wire, one white
wire, one red wire for triads; or as specified on Form 8020-913-ENG,
Line Item 14.
Page 6 of 21
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-913
Issue Date: 24 January 2012
Next Planned Update: 24 January 2017 Instrumentation and Thermocouple Cable
6.3.1 Conductor
Flame retardant PVC, nylon- jacketed PVC (For Type TC cables only)
or thermoset crosslinked polyolefin (XLPO or XLPE), minimum
temperature rating 90°C.
0.38 mm (15 mils) minimum average thickness for Types PLTC and
ITC Cables.
6.3.6 Assembly
40 to 60 mm.
One black wire, one white wire for pairs; one black wire, one white
wire, one red wire for triads; or as specified on Form 8020-913-ENG,
Page 7 of 21
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-913
Issue Date: 24 January 2012
Next Planned Update: 24 January 2017 Instrumentation and Thermocouple Cable
Page 8 of 21
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-913
Issue Date: 24 January 2012
Next Planned Update: 24 January 2017 Instrumentation and Thermocouple Cable
6.4.1 Conductor
Flame retardant PVC, nylon- jacketed PVC (For Type TC cables only)
or thermoset crosslinked polyolefin (XLPO or XLPE), minimum
temperature rating 90°C.
0.38 mm (15 mils) minimum average thickness for Types PLTC and
ITC Cables.
6.4.6 Assembly
40 to 60 mm.
Page 9 of 21
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-913
Issue Date: 24 January 2012
Next Planned Update: 24 January 2017 Instrumentation and Thermocouple Cable
One black wire, one white wire for pairs; one black wire, one white
wire, one red wire for triads; or as specified on Form 8020-913-ENG,
Line Item 14.
Page 10 of 21
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-913
Issue Date: 24 January 2012
Next Planned Update: 24 January 2017 Instrumentation and Thermocouple Cable
6.5.1 Conductor
Flame retardant PVC, nylon- jacketed PVC (For Type TC cables only)
or thermoset crosslinked polyolefin (XLPO or XLPE), minimum
temperature rating 90°C.
Page 11 of 21
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-913
Issue Date: 24 January 2012
Next Planned Update: 24 January 2017 Instrumentation and Thermocouple Cable
0.38 mm (15 mils) minimum average thickness for Types PLTC and
ITC Cables.
6.5.6 Assembly
40 to 60 mm.
One black wire, one white wire for pairs; one black wire, one white
wire, one red wire for triads; or as specified on Form 8020-913-ENG,
Line Item 14.
Page 12 of 21
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-913
Issue Date: 24 January 2012
Next Planned Update: 24 January 2017 Instrumentation and Thermocouple Cable
Page 13 of 21
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-913
Issue Date: 24 January 2012
Next Planned Update: 24 January 2017 Instrumentation and Thermocouple Cable
6.6.1 Conductor
Page 14 of 21
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-913
Issue Date: 24 January 2012
Next Planned Update: 24 January 2017 Instrumentation and Thermocouple Cable
300 V.
6.6.6 Assembly
40 to 60 mm.
Page 15 of 21
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-913
Issue Date: 24 January 2012
Next Planned Update: 24 January 2017 Instrumentation and Thermocouple Cable
Page 16 of 21
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-913
Issue Date: 24 January 2012
Next Planned Update: 24 January 2017 Instrumentation and Thermocouple Cable
Page 17 of 21
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-913
Issue Date: 24 January 2012
Next Planned Update: 24 January 2017 Instrumentation and Thermocouple Cable
6.8.2.1 Spur cables shall meet sections 6.8.1.1 and 6.8.1.3 above.
6.8.2.2 Spur cables shall also meet the applicable cable specifications
in Group 2 above.
Exceptions:
6.8.3.1 For all FF cables, spur and trunk, the outer jacket color shall
be orange.
6.8.3.2 For all armored FF cables, spur and trunk, the inner and outer
jacket color of the armored cable shall be orange.
6.8.3.3 For all FF cables, spur and trunk, the conductor color code
shall be black and white with bare tinned copper conductor
for the drain/shield arrangement.
6.9 Options
Page 18 of 21
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-913
Issue Date: 24 January 2012
Next Planned Update: 24 January 2017 Instrumentation and Thermocouple Cable
Armored cable shall have served steel wire or interlocked steel armor
under an extruded PVC outer jacket. Steel armor shall be galvanized.
Exception:
7 Marking
The following information shall be clearly marked on the outer jacket of the
cable, in no specific order:
a) Manufacturer's name, trade name, catalog or type number
b) Number of pairs/triads
c) Conductor size in mm² or AWG
d) Voltage rating (300 or 600 V) for ITC or TC cables only.
e) Type of cable (PLTC, TC or equivalent)
f) Approval mark of listing authority (UL, IEC, or as applicable)
g) “Sunlight resistant” designation, in Manufacturer's standard nomenclature,
for Type TC cable (Optional for Type PLTC cable)
h) “Direct burial” designation, if applicable per UL 13 or UL 1277, in
Manufacturer's standard nomenclature
i) “Oil resistant” designation, in manufacturer's standard nomenclature, for
Type TC Cable (preferred for Types ITC and PLTC Cable)
j) For FOUNDATION™ Fieldbus cables, “TYPE A” shall be marked.
In addition, all FF cables shall be listed as PLTC or ITC and shall bear any
other mandatory marking specified in FF-844.
Page 19 of 21
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-913
Issue Date: 24 January 2012
Next Planned Update: 24 January 2017 Instrumentation and Thermocouple Cable
Each reel shall have a weatherproof (metal or plastic) tag, securely attached to a
flange of the reel and plainly stating:
a) Manufacturer's trade name
b) Date of manufacture
c) Conductor size
d) Cable rating
e) Type of cable
f) Temperature designation
g) Minimum bend radius
h) Maximum pulling tension
i) Shipping length and diameter of cable
j) Saudi Aramco Purchase Order number
8 Testing
Type Tests: Each cable type shall be type tested, with the test conducted and certified
by an approved third party testing authority.
Page 20 of 21
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-913
Issue Date: 24 January 2012
Next Planned Update: 24 January 2017 Instrumentation and Thermocouple Cable
8.2.4 All Foundation Fieldbus (FF) cables shall be tested to ensure full
compliance to IEC 61158-2 Section 12.8.2 and FF-844 and shall be
registered by Fieldbus Foundation.
9.1 Inspection
Revision Summary
24 January 2012 Revised the “Next Planned Update.” Reaffirmed the content of the document, and reissued
with minor revision to clarify the requirement to specify “tinned” copper conductors if the
primary insulation is corrosive or otherwise specified in the data sheet.
Page 21 of 21