How to calculate a re sprinkler system


 Category: Hydraulic calculation for re protection engineers (/Table/Support/Hydraulic-calculation-for- re-protection-engineers/)

The long way - by hand


In this article, will demonstrate some of the basics for carrying out re sprinkler calculations by the long hand method with just the aid of a
scienti c calculator or our own hydraulic calculator - Hcal2 (/products/hcalc.html) which you can freely download from our website.  

We will for this example use simple three sprinklers and three pipes which would of course be part of a much larger re sprinkler system.
These basic procedures can also be used for calculating many other types of systems such as re hydrant, hose reel or the discharge from a
water cannon or monitor we can also use the same principal for almost all other water-based re protection systems if we have a k-factor for
the output device ( re sprinkler, water mist nozzle and so on).

In this example, will we use a very simple system with just three sprinklers and three pipes this is often called a range pipe or branch pipe,
which is part of a larger tree system. A tree system is end feed, that is water is only fed from one direction as opposed to a grid or loop system
when water may arrive at the sprinkler head from more than one direction. 

Below is a diagram of the three sprinklers and three pipes which we will calculate.  We have dimensioned the pipe lengths and given each
junction point a unique node reference number which we use throughout the calculations. 

For each pipe, we need to know the pipe length, internal diameter (ID) of the pipe and the pipe material so we can determine the pipes c-factor,
the table below summarises the pipe data which we will need for the calculation for this example: 

Node Ref  Pipe Size ID (mm)  Length (m) C-factor

130-120 27.30 3.20 120

120-110  27.30  3.20  120 

110-100 36.00  3.20  120 

We will also we will need some additional information such as the type sprinkler head, the area each head is covering, the design density for
each sprinkler head in the system.

https://www.canutesoft.com/how-to-calculate-a-fire-sprinkler-system.html 1/6
For this example, we will use the following design parameters:How to calculate a fire sprinkler system
5/22/2018

design density: 7.50 mm/min


sprinkler head: K-factor of 70 with a minimum pressure 0.5 bar
head area: 10.20 m2

In this example, we have kept it very simple and used the same sprinkler head for all three sprinklers but this may not always be the case so
again it way be useful to summarises the information in a table such as this: 

Node Ref  Design Density Sprinkler k-factor Sprinkler minimum Head area (m2)
(mm/min) pressure (Bar)

130 7.50 70 0.5 10.20

120 7.50 70 0.5 10.20

110 7.5 70 0.5 10.20

The rst step is to calculate the minimum ow which will be required at the most remote sprinkler which in this case is at node [130], this is a
two-step process as will need to calculate the minimum ow required to satisfy the 7.50 mm/min design density and then nd the ow rate
from the sprinkler given the sprinklers minimum pressure requirement, whichever is the greater ow will become our initial ow from the rst
sprinkler at node [130].

We will rst calculate the ow given the design density of 7.50 mm/min and the area the head is covering, we do this by multiplying the design
density (/support-topmenu/support-basichydraulics/54-design-density.html) by the head area:

Equation 1:

q1 = (design density) x (area per sprinkler)

In this example, this gives:

          q1 = 7.50 mm/min x 10.20 m2 = 76.50 L/min

The second step is to calculate the minimum ow from the sprinkler given the K-Factor and the minimum head pressure by using the standard
K-Factor formula (/support-topmenu/support-basichydraulics/27-k-factor-formula.html):

Equation 2:

q = kp0.5

Where

p = the required pressure


q = the required ow from the rst sprinkler
k = the discharge coe cient of the sprinkler (k-factor)

In this example, this gives:

                q = 70 x 0.50.5 = 49.50 L/min

By comparing the two calculations above we can see that the minimum ow required from the sprinkler head will be 76.50 L/min as this is the
highest ow rate from the two calculations and is required to meet the 7.50 mm/min design density.  We can also see that the minimum
sprinkler pressure of 0.5 bar is not su cient to produce the require ow rate so the next step will be to determine what pressure will be
https://www.canutesoft.com/how-to-calculate-a-fire-sprinkler-system.html 2/6
required to produce the require ow of 76.50 L/min at the rstHow
5/22/2018 sprinkler head ata node
to calculate [130] we
fire sprinkler can do this by using equation 3.
system

Equation 3

                p = (q/k)2

In the example, this gives:

                p = (76.50 / 70)0.5 = 1.194 bar

We have now determined the minimum pressure and ow for the rst sprinkler at node [130] which will be 76.50 L/min @ 1.19 bar the next
step is to calculate the pressure drop in the pipe between node [130] and [120] and for this we will use the Hazen-Williams pressure loss
formula (/support-topmenu/support-basichydraulics/26-the-hazen-williams-formula-for-use-in- re-sprinkler-systems.html).

Equation 4

Where

p = pressure loss in bar per meter


Q = ow through the pipe in L/min
C = friction loss coe cient
d = internal diameter of the pipe in mm

We know that the ow rate from the sprinkler at node [130] is 76.50 L/min and this will be the ow rate in the rst pipe between nodes [130]-
[120]. As the pipe has an internal diameter of 27.30 mm and has a C value of 120 this will give us:

The pressure loss in the rst pipe is 0.027 Bar/m and the total pressure loss in the pipe is 0.086 bar. 

We now need to add the pressure loss in the pipe to the start pressure at the sprinkler head at node [130] which was 1.19 bar to nd to
pressure at node [120] and at the seconded sprinkler head at node [120] this gives us 1.194 + 0.086 = 1.28 bar. 

The next step is to nd the ow from the seconded sprinkler head at node [120] to do this we will use the K-Factor formula

Equation 5

This gives 70 x 1.2800.5 = 79.20 L/min from the sprinkler head at node [120] which we now add to the ow in the rst pipe node [130]-[120] to
nd the total ow in the second pipe [120]-[110] to nd the total ow in the seconded pipe which is 155.70 L/min.
https://www.canutesoft.com/how-to-calculate-a-fire-sprinkler-system.html 3/6
5/22/2018 How to calculate a fire sprinkler system

Having found the total ow in the seconded pipe [120]-[110] we can now nd the pressure loss in, to do this we will use the Hazen-Williams
pressure loss, formula 4 which we used above this gives us:   

We now add the pressure loss 0.317 bar to the pressure at node [120] to nd the pressure at node [110] this give us: 0.317 + 1.280 = 1.597 bar

We now need to nd the ow from the sprinkler at node [110] we do this by using the k-factor given in equation 5 as we now know the pressure
at node [110] is 1.597 bar, this gives 70 x 1.5970.5 = 88.50 L/min from the sprinkler head at node [110].  We now add this ow to the ow in the
seconded pipe [120]-[110] to nd the total ow in the third pipe [110]-[100] which will give us the ow of 244.20 L/min. 

The last step is to nd the pressure loss in the third pipe [110]-[100] and again we will use Hazen-Williams pressure loss formula given is
formula 4 above. However, the last pipe has an internal diameter of 36.0 mm so this gives us:

https://www.canutesoft.com/how-to-calculate-a-fire-sprinkler-system.html 4/6
5/22/2018 How to calculate a fire sprinkler system

We now add the pressure loss in this pipe to the pressure at node [110] to nd the pressure at node [100] this will be 0.189 + 1.597 = 1.786 bar. 
We have now complete the calculation for all three sprinkler heads and have found the source pressure and ow required for this system is:

244.20 L/min @ 1.786 Bar

This pressure and ow is offer referred to as the source requirement for the system and is the minimum pressure and ow required for the
system for it to be able to provide the required design density (in this example 7.50 mm/min) at the most remote head [MRH] at node [130]. 

You should also be able to see that only the Most Remote Head has the minimum requirement of 7.50 mm/min design density and all the
other sprinklers will have a higher pressure as they are hydraulically closer to the water source so they will have a higher pressure and will
discharge more water through the sprinkler this can be seen in the table below: 

Node Ref  min Design Density Pressure  Flow from sprinkler Head Area Actual
(mm/min) (Bar) (L/min) (m2) Design Density

 130 [MRH] 7.50 1.194 76.50 10.20 7.50

120 7.50 1.280 79.20 10.20 7.76

130 7.50 1.597 88.50 10.20 8.68

Sprinkler calculation step by step

1. Calculate minimum ow from the MRH with the sprinkler minimum pressure and k-factor
2. Calculate the minimum ow given the system design density and sprinkler head area.
3. If the calculation in step 2 is the highest ow demand, then calculate the required head pressure otherwise we can use the minimum
sprinkler pressure in step 1.
4. Calculate the pressure loss in the pipe.
5. Add the head pressure to the pressure loss in step 4 to determine the pressure at the next sprinkler.
6. Use the k-factor formula to determine the ow from the sprinkler head.
7. Repeat step 4 to 6 until you do not have any more sprinklers or pipes

Next  (/Hydraulic-calculation-for- re-protection-engineers/reynolds-number.html)

https://www.canutesoft.com/how-to-calculate-a-fire-sprinkler-system.html 5/6
5/22/2018 How to calculate a fire sprinkler system

COPYRIGHT NOTICE (/WEBSITE-POLICY-TERMS-AND-CONDITIONS-OF-TRADE/WEBSITE-INTELLECTUAL-PROPERTY-


NOTICES.HTML)
PRIVACY POLICY (/WEBSITE-POLICY-TERMS-AND-CONDITIONS-OF-TRADE/PRIVACY-POLICY.HTML)

© 2018 Canute LLP

https://www.canutesoft.com/how-to-calculate-a-fire-sprinkler-system.html 6/6

You might also like