Large-scale Photovoltaic

Power Generation Systems

01D1-E-0001
Our photovoltaic power generation systems provide eco-friendly energy.

■ Maximizing Output Power from ■ Total System Construction from ■ System Stabilization Technology ■ Secure Support System in Japan
Photovoltaic Power Generation PCS to System Interconnection Power stabilizers, private power generators, and and Abroad
High-efficiency three-level inverter with our original Fuji Electric offers a wide product lineup from high-voltage hybrid power supplies such as wind power Our service engineers provide secure maintenance support for
and extra-high-voltage interconnection facilities that we have customer facilities from Hokkaido to Okinawa in Japan and at
RB-IGBT generation and fuel cells
developed as a heavy electrical equipment manufacturer to international service locations.
At Fuji Electric we develop and manufacture high-efficiency power Fuji Electric has developed its system stabilization technology for
supply-and-demand monitoring and PCS units. We support
conditioner systems (PCS) in-company using our unique more than 20 years.
total system introduction of photovoltaic power generation
proprietary reverse-blocking insulated gate bipolar transistor We make use of various types of power supply equipment such as
facilities for our customers.
(RB-IGBT) technology. Our power conditioners, which are at the private power generators and wind power generators and power
industry’s highest level and use the maximum power point accumulation technology developed for UPS to supply stable
tracking control (MPPT) that we have refined through long power by combining power supply types tailored to each region.
development, enable maximum output power from photovoltaic
power generation.
1 2
Total Engineering Solutions from System Fuji Electric provides comprehensive system
Planning to Maintenance proposals for efficient operation from solar cells
Fuji Electric is a full-service equipment manufacturer, a peripheral equipment supplier, and a total to power transmission.
engineering solution provider of photovoltaic power generation systems from system design to
construction management.

■ Fuji Electric System Solutions ■ One-line Diagram


Fuji Electric provides photovoltaic power generation systems ● Long history of accomplishments and experience since
optimized for each region by combining our in-depth experience foundation in 1923 (Solar cell characteristics, inverter
and advanced technologies. technology, and system interconnection technology) Connection
● Advanced technologies (RB-IGBT and system
box,
PCS current PV panel
Interconnection with
interconnection technology) transmission line of
collection
box
electric power utility
company
PCS Main transformer
● High efficiency Transformation system ● System interconnection technology
(98.5% for DC 1,000 V specifications) (Power conditioner system) ● Smart grid monitoring technology
GIS VCT
● Series expanded to DC 600 V ● Large-scale plant technology
specifications Extra-high-voltage facility High-voltage
(22 to 154 kV) facility
● Substation configuration for easy (6.6 kV)
construction*
Connection
*: Integrated configuration includes power conditioner box,
system (PCS), switchgear, and step-up transformer. PCS current PV panel
collection
box

● System-matched Modules ● Overseas and Japanese


power generation operators
(public and private sector)

PV module Sales and after-sales service

PCS PCS

Power conditioner

Key technology PCS PCS

Other principal components


Total system design
(Electric equipment, system interconnection, stabilizer, IT, etc.)
PCS PCS

Total engineering
(Installation, construction, quality assurance, after-sales service, etc.)

3 4
As the PCS is the core of the system, we provide
a large-capacity PCS of the highest efficiency that
incorporates advanced power semiconductors.
(The series lineup was reinforced with the addition of a new 500 kW model.)

■ Features

Adoption of new IGBT and new circuit system World’s highest efficiency 98.5% Single unit capacity 1,000 kW
Fuji Electric commercialized the world’s first three-level module
(DC 1,000 V product) Fuji Electric successfully developed a PCS with a single unit be optimized, resulting in significant reductions in construction
in which a new RB-IGBT* and an existing IGBT are integrated in Compared to existing products, our new power conversion capacity of 1,000 kW. and building costs.
one package. technology, which uses a new three-level conversion circuit in For large-scale photovoltaic power generation systems, this
Application of this new module to a new three-level conversion the new module, reduces switching loss in the IGBT device and large single unit capacity enables the number of PCS units to
circuit enables a large reduction both in power loss and in the also reduces filter loss by reducing to one half the harmonic
number of parts, resulting in high efficiency and low noise in the content in PWM waveform outputted by the inverter. This results
equipment. in the world highest efficiency of 98.5% (DC 1,000 V product). INV1 1000 kVA
LB
We have also achieved EURO efficiency of 98.2% (DC 1,000 V
*: RB-IGBT: Reverse Blocking-Insulated Gate-Bipolar Transistor product).
New IGBT module
99
INV2
98
97
96
Efficiency [%]

95
94
93
INV3
92
91
90
89
0 20 40 60 80 100 INV4
Output [%]

New IGBT module Note: Internal power supply is not included. IEC61683 efficiency tolerance is indicated.

New three-level conversion circuit


Outdoor substation type
Output line voltage waveform
Fuji Electric provides a substation type of PCS that can be
Existing system
(two-level system)
installed outdoors.
A switchgear, a step-up transformer, and PCS that can be Standard FRT function
installed outdoors are integrated on a common base in a single
The fault ride through (FRT) function that is becoming occurs in the system, the inverter can output three-phase
unit. This eliminates the need for a building for storing panels
Output line voltage waveform essential in PCS for large-scale photovoltaic power current in a specified range to suppress power supply
and air-conditioning facilities. Since this substation is
New system generation is provided as a standard function. variations in the system.
(new three-level system) transported to the site as an integrated unit, on-site construction
Even if a three-phase or two-phase short circuit accident
costs can be greatly reduced.
With the installation of an optional fuse for a DC branch in the
AC voltage
PCS, the panel output collected in the current collection box can
U-V phase (red)
be connected to the PCS as is.
V-W phase (green)
Reduction of power loss W-U phase (blue)
200 V/DIV
ACL and wiring loss
100
Switching loss AC current
U phase (red)
80
V phase (green)
Loss[%]

60 W phase (blue)
25 A/DIV
40

20

0 Existing system New system


(two-level system) (new three-level system) 3.6s 3.62s 3.64s 3.66s 4.6s 4.62s 4.64s

5 6
Specifications Example of appearance Operation screen Example of outside dimensions
(Front view)
Step-up transformer
LBS panel
(Top view)
Step-up transformer
LBS panel

2400
2130
PCS

2830
PCS

800 1000 1000 800 1200 1200


Concrete foundation
3600 2550

150
High-voltage main circuit
DC main circuit 6150
Base (1) Cable and ground wire (Unit: mm)
cable and ground wire

■ PCS (DC 1000 V) specifications (Outdoor self-standing type) ■ PCS (DC 750 V) specifications (Outdoor self-standing type)
Item Series name PVI1000-3/1000 Remarks Item Series name PVI750ー3/750 Remarks
Rated output 1000 kW Rated output 750kW
Insulation system Transformerless system Insulation system Transformerless system
Electric specifications DC input voltage range 1000 V Electric specifications DC input voltage range 750 V
(DC input) DC input voltage (MPPT range) 460 V to 950 V (DC input) DC input voltage (MPPT range) 320 V to 750 V
Number of DC input branches 4 24 branches (Option) Number of DC input branches 4 16 branches (Option)
Electric specifications Rated output capacity 1000 kW Electric specifications Rated output capacity 750 kW
(AC output) Rated output voltage 270 V ー10 % to +12 % (AC output) Rated output voltage 200 V ー10 % to +12 %
Rated frequency 50/60 Hz ±5 % Rated frequency 50/60 Hz ±5 %
Number of output phases Three-phase, three-wire; isolated neutral system supported. Number of output phases Three-phase, three-wire; isolated neutral system supported.
Rated output current 2138 A Rated output current 2165 A
Output power factor >0.99(at rated output) Individual operation Q output excluded Output power factor >0.99(at rated output) Individual operation Q output excluded
(when output is 1/8 of rated output). (when output is 1/8 of rated output).
Output current distortion factor (total) <5 % (at rated output) Output current distortion factor (total) <5 % (at rated output)
Output current distortion factor (each) <3 % (at rated output) Output current distortion factor (each) <3 % (at rated output)
Equipment highest efficiency 98.5 % Equipment highest efficiency 97.8 %
Equipment efficiency (Euro efficiency) 98.2 % Equipment efficiency (Euro efficiency) 97.4 %
Overload capacity 100 % continuous Overload capacity 100 % continuous
Noise 85 dB Noise 85 dB
System interconnection System protection OV, UV, OF, UF System interconnection System protection OV, UV, OF, UF
Individual operation detection system (passive) Detection of voltage phase jump Individual operation detection system (passive) Detection of voltage phase jump
Individual operation detection system (active) Reactive power variation system Individual operation detection system (active) Reactive power variation system
Voltage rise suppression function Reactive current compensation, Voltage rise suppression function Reactive current compensation,
active current output suppression active current output suppression
FRT Vmin=15 %,0.625 S Recovery time 3 s Based on the country’s grid code. FRT JEAC9701ー2010 Based on the country’s grid code
Panel structure Installation system Outdoor self-standing type Measures against salt damage are optional. (conforms to supplementary version of 2011)
Applicable IP IP54 Panel structure Installation system Outdoor self-standing type Measures against salt damage are optional.
System type Substation system Integrated step-up transformer and switchgear Applicable IP IP54
Cable lead-in Lower part System type Substation system Integrated step-up transformer and switchgear.
Cooling system Forced-air cooling Cable lead-in Lower part
Dimensions PCS single unit (W × D × H) 3600×2130×2830 mm Cooling system Forced-air cooling
Substation (W × D × H) 6150×2400×2830 mm Dimensions PCS single unit (W × D × H) 3600×2130×2830 mm
Mass PCS single unit About 7000 kg Substation (W × D × H) 6150×2400×2830 mm
Substation About 12500 kg Mass PCS single unit About 7000 kg
Environmental conditions Storage temperature −20 ℃ to +50 ℃ Substation About12500 kg
Operating temperature −10 ℃ to +40 ℃ High-temperature option available for +50 °C. Environmental Storage temperature −20 ℃ to +50 ℃
Relative humidity 15 to 95 % Non-condensing conditions Operating temperature −10 ℃ to +40 ℃ High-temperature option available for +50 °C.
Altitude 2000 m or less High-altitude option available for over 2000 m. Relative humidity 15 to 95 % Non-condensing
Relevant standard IEC62109-1 Altitude 2000 m or less
Communication system RS-485/MOD BUS/TCP Relevant standard JIS, JEM, JEC
Communication system RSー485/MOD BUS/TCP

■ Switchgear and step-up transformer (1000 kW) specifications ■ Switchgear and step-up transformer (750kW) specifications
Item Rated output 1000 kW Remarks
Item Rated output 750 kW Remarks
Electric specifications of Power supply voltage 4.16 to 34.5 kV
Electric specifications Power supply voltage 6.6 kV
switchgear Power supply frequency 50/60 Hz of switchgear Power supply frequency 50/60 Hz
Number of power supply phases Three-phase, three-wire
Number of power supply phases Three-phase, three-wire
Rated current 200 A
Rated current 200 A
Breaking capacity 12.5 kA Values other than the left value are optional.
Breaking capacity 12.5 kA Values other than the left value are optional.
Electric specifications of Capacity 1000 kVA
Electric specifications Capacity 750 kVA
step-up transformer Number of phases Three-phase of step-up transformer Number of phases Three-phase
Frequency 50/60 Hz
Frequency 50/60 Hz
Cooling system Oil-immersed self-cooling
Cooling system Oil-immersed self-cooling
Connection system  ー
Connection system  ー
Others Contact prevention plate is provided.
Others Contact prevention plate is provided.

7 8
PCS optional

New
System Configuration Example
Series !

■ PCS (DC 750 V) specifications (Indoor self-standing type) ■ One-line diagram (10MW, Outdoor self-standing type, Example of a 1,000 kW PCS)
Item Series name PVI750ー3/500 Remarks
Rated output 500kW
Insulation system Transformerless system
Electric specifications DC input voltage range 750V
(DC input) DC input voltage (MPPT range) 320V to 700V
Number of DC input branches 5 Optional Demarcation point
Electric specifications Rated output capacity 500kW
(AC output) Rated output voltage 200V ー10% to +12%
Rated frequency 50/60Hz
Number of output phases Three-phase, three-wire; isolated neutral system supported.
Rated output current 1444A
Output power factor >0.99 (at rated output) Individual operation Q output excluded
Output current distortion factor (total) <5% (at rated output)
Output current distortion factor (each) <3% (at rated output)
Equipment highest efficiency 97.7%
Equipment efficiency (Euro efficiency) 97.3%
Overload capacity 100% continuous
Noise 75dB or less
System System protection OV, UV, OF, UF
interconnection Individual operation detection system (passive) Detection of voltage phase jump
Individual operation detection system (active) Reactive power variation system
Voltage rise suppression function Reactive current compensation, active current output suppression
FRT Vmin=15%,0.625s Recovery time 3 s Based on the country’s grid code
Panel structure Installation system Outdoor self-standing type
Applicable IP ー
System type ー Station service transformer panel
Cable lead-in Lower part VCB
Cooling system Forced-air cooling (52F1)

Dimensions PCS single unit (W × D × H) 2400×900×1950 mm 2CT


PF LBS
Substation (W × D × H) ー LA×3 F-MPC60B
Station service transformer
Mass PCS single unit 2000kg NGR ZCT
51G three-phase mold
Substation ー U> U>
From temporary
Environmental Storage temperature −20℃ to +50℃ Aerial wire
generator DT DT

conditions Operating temperature −10℃ to +40℃ -MC -MC


PAS
(with VT, LA and SOG)
Relative humidity 5 to 90% Non-condensing
V V
2CT 2CT
Wh A Wh A

Altitude 1000m or less No. 1 high-voltage air break switch No.1 Substation
Relevant standard JIS, JEM, JEC MCCB MCCB MCCB MCCB MCCB
LBS
MCCB MCCB
Communication system RSー485 No. 1 step-up transformer
Spare Others(meteorological (Outdoor oil-immersed self-cooling type)
Rectifier panel equipment, display)
Spare
MCCB Storage
High-voltage panel Monitoring protection cubicle MCCB No.1 PCS

■ Switchgear and step-up transformer (500kW) specifications


battery
Rectifier panel Monitoring protection cubicle CT1, 2
SD
MCCB MCCB
Storage MC11 MC21 MC31 MC41
Item Rated output 500 kW Remarks battery
DC panel L12 L22 L32 L42
Electric specifications Power supply voltage 6.6 kV MCCB U> C1 L11 C2 L21 C3 L31 C4 L41
of switchgear Power supply frequency 50/60 Hz MCCB MCCB MCCB Z >
DCCT11,12 DCCT21,22 DCCT31,32 DCCT41,42
Number of power supply phases Three-phase, three-wire PWU1 PWU2 PWU3 PWU4
Monitoring protection cubicle
Rated current 200 A Spare
Breaking capacity 12.5 kA Values other than the left value are optional. High-voltage panel F11,12 F21,22 F31,32 F41,42 27
59
Electric specifications Capacity 500 kVA DCCT10 DCCT30 64

of step-up transformer Number of phases Three-phase MCB11 MCB31


67S
95LH

Frequency 50/60 Hz
Cooling system Oil-immersed self-cooling
Connection system  ー
Solar cell Solar cell Solar cell Solar cell
Others Contact prevention plate is provided.
4 blocks
9 10
System Configuration Example

■ One-line diagram (10MW, Outdoor self-standing type, Example of a 1,000 kW PCS)

66 kV transmission line

Demarcation point

Monitoring and control panel (outdoor)

3BCT
VD F-MPC
ES (manual) LA×3 W/TD
ES (manual) (89R)(Electrically operated)
DS Var/TD
VCB(52R) C-GIS
Outdoor meter panel
(Supplied by electric power ES (manual)
utility company) VCT EVT CLR
VCT F-MPC V/TD
Monitoring and control panel
(indoor)

Tr-1
Main transformer
F-MPC 3BCT
Three-phase outdoor oil-immersed self-cooling
Bus duct

LA×3 EVT CLR 64G Incoming panel


F-MPC To each PCS panel
5CT F-MPC

(52S)
VCB

Station service transformer panel Feeder panel


VCB
(52F1) VCB VCB
(54F2) (52F3)
2CT 2CT 2CT
PF LBS
LA×3 F-MPC60B LA×3 F-MPC LA×3 F-MPC60B
Station service transformer
NGR ZCT ZCT ZCT
51G three-phase mold

U> U>
From temporary
Aerial wire Aerial wire Aerial wire
generator DT DT
-MC -MC
PAS PAS PAS
2CT
V
2CT
V (with VT, LA and SOG) (with VT, LA and SOG) (with VT, LA and SOG)
Wh A Wh A

No. 1 high-voltage air break switch No.1 Substation No.2 No.3 No.4 No. 5 high-voltage air break switch No.5 Substation No.6 No.7 No.8 No. 5 high-voltage air break switch No.9 Substation No.10
LBS LBS LBS
MCCB MCCB MCCB MCCB MCCB MCCB MCCB
No. 1 step-up transformer No. 5 step-up transformer No. 5 step-up transformer
Spare Others(meteorological (Outdoor oil-immersed self-cooling type) (Outdoor oil-immersed self-cooling type) (Outdoor oil-immersed self-cooling type)
Rectifier panel equipment, display)
Spare
MCCB Storage
High-voltage panel Monitoring protection cubicle MCCB No.1 PCS MCCB No.5 PCS MCCB No.9 PCS
battery
Rectifier panel Monitoring protection cubicle CT1, 2 CT1,2 CT1,2
SD
MCCB MCCB
Storage MC11 MC21 MC31 MC41 Same as Same as Same as MC11 MC21 MC31 MC41 Same as Same as Same as MC11 MC21 MC31 MC41 Same as
battery
on the left on the left on the left on the left on the left on the left on the left
DC panel L12 L22 L32 L42 L12 L22 L32 L42 L12 L22 L32 L42
MCCB U> C1 L11 C2 L21 C3 L31 C4 L41 C1 L11 C2 L21 C3 L31 C4 L41 C1 L11 C2 L21 C3 L31 C4 L41
MCCB MCCB MCCB Z >
DCCT11,12 DCCT21,22 DCCT31,32 DCCT41,42 DCCT11,12 DCCT21,22 DCCT31,32 DCCT41,42 DCCT11,12 DCCT21,22 DCCT31,32 DCCT41,42
PWU1 PWU2 PWU3 PWU4 PWU1 PWU2 PWU3 PWU4 PWU1 PWU2 PWU3 PWU4
Monitoring protection cubicle
Spare
High-voltage panel F11,12 F21,22 F31,32 F41,42 27 27 F11,12 F21,22 F31,32 F41,42 27
59 59 59
DCCT10 DCCT30 64 DCCT10 DCCT30 64 DCCT10 DCCT30 64
67S 67S 67S
MCB11 MCB31 95LH MCB11 MCB31 95LH MCB11 MCB31 95LH

Same as Same as Same as Same as Same as Same as Same as


Solar cell Solar cell Solar cell Solar cell on the left on the left on the left Solar cell Solar cell Solar cell Solar cell on the left on the left on the left Solar cell Solar cell Solar cell Solar cell on the left

4 blocks 4 blocks 4 blocks


10 11 12
System Configuration Example

■ One-line diagram (2MW, Outdoor self-standing type, Example of a 1,000 kW PCS)

6.6 kV transmission line

Demarcation point

Installation of electric pole


VCT
PAS
VD
Incoming panel
Installation of
electric pole (89R)
DS (remote manual operation)
Incoming panel

2VT
Supply meter panel 64G
RPS VCB(52R) F-MPC60B
Wh To each PCS panel
2CT
RPS
Wh ZPD

Station service transformer panel

(52F2)
VCB
PF:20A LBS (52F1)
VCB

Station service transformer three-phase mold

PV feeder panel
2CT 2CT
V V F-MPC60B F-MPC60B
ZCT ZCT

No.1 Substation No.2 Substation


No. 1 high-voltage air break switch No. 2 high-voltage air break switch
2CT
2CT LBS LBS
Wh A Wh A

No. 1 step-up transformer No. 2 step-up transformer


(Outdoor oil-immersed self-cooling type) (Outdoor oil-immersed self-cooling type)
MCCB MCCB MCCB MCCB MCCB

No.1 Substation No.2 Substation


Power load Spare MCB11 MCB11
Spare 6.6 kV cubicle Remote monitoring CT1,2 CT1,2
Measuring instrument

MC11 MC21 MC31 MC41 MC11 MC21 MC31 MC41

L12 L22 L32 L42 L12 L22 L32 L42

C1 C2 C3 C4 C1 C2 C3 C4
L11 L21 L31 L41 L11 L21 L31 L41

DCCT11,12 DCCT21,22 DCCT31,32 DCCT41,42 DCCT11,12 DCCT21,22 DCCT31,32 DCCT41,42


PWU1 PWU2 PWU3 PWU4 PWU1 PWU2 PWU3 PWU4

Z Z
27 27
DCCT10 DCCT30 DCCT10 DCCT30
59 59
64 64
F11,12 F31,32 67S F11,12 F31,32 67S
95LH 95LH
MCB11 MCB31 MCB11 MCB31

Solar cell Solar cell Solar cell Solar cell Solar cell Solar cell Solar cell Solar cell

4 blocks 4 blocks

13 14
System Configuration Example

■ One-line diagram (2MW, Indoor self-standing type, Example of a 500 kW PCS)

6.6 kV transmission line

Demarcation point

Installation of electric pole


PAS VCT

Installation of Incoming panel


VD
electric pole
DS(89R)(remote manual operation)
Incoming panel
Supply meter panel
RPS 2VT
VCB(52R) 64G FーMPC60B
Wh
RPS 2CT To each PCS panel
Wh
ZPD

Station service transformer panel

VCB(52F2)
PF:20A LBS VCB(52F1)

Station service transformer three-phase mold


PV feeder panel
2CT 2CT
V V FーMPC60B FーMPC60B
ZCT ZCT

No. 1 high-voltage air break switch No. 2 high-voltage air break switch
2CT LBS LBS
2CT
Wh A Wh A

No. 1 step-up transformer No. 2 step-up transformer


(Outdoor oil-immersed self-cooling type) (Outdoor oil-immersed self-cooling type)
MCCB MCCB MCCB MCCB MCCB
Stored inside container Stored inside container
No.1ーPCS No.2ーPCS No.1ーPCS No.2ーPCS
Power load Spare MCB (500kW) MCB (500kW) MCB (500kW) MCB (500kW)
Spare 6.6 kV cubicle Remote monitoring
CT CT CT CT
Measuring instrument

MC11 MC21 MC11 MC21 MC11 MC21 MC11 MC21

L12 L22 L12 L22 L12 L22 L12 L22


C C C C C C C C

L11 L21 L11 L21 L11 L21 L11 L21

DCCT DCCT DCCT DCCT DCCT DCCT DCCT DCCT

PWU1 PWU2 PWU1 PWU2 PWU1 PWU2 PWU1 PWU2


MCB1

MCB2

MCB3

MCB4

MCB5

MCB1

MCB2

MCB3

MCB4

MCB5

MCB1

MCB2

MCB3

MCB4

MCB5

MCB1

MCB2

MCB3

MCB4

MCB5
Branch circuit breaker Branch circuit breaker
(standard equipment) (standard equipment) Branch circuit breaker Branch circuit breaker
(standard equipment) (standard equipment)

Solar Solar Solar Solar Solar Solar Solar Solar Solar Solar Solar Solar
cell cell cell cell cell cell cell cell cell cell cell cell

Solar Solar Solar Solar Solar Solar Solar Solar


cell cell cell cell cell cell cell cell

15 16
A monitoring unit quickly collects information
on proper photovoltaic power generation and
the state of each component.

■ Features
The SCADA system has the highest quality and cost performance in the industry.
The system has many features such as a web function, multilingual function, Web functions and multilingual functions
high speed, extensibility, and reliability. ● Real-time information on plant status can be accessed from
The system can be applied to a large-scale power generation system with several to more than 400,000 I/O points. anywhere in the world at any time. (Web connection license is
provided)
● Language switching is based on a table system for easy
High speed Extensibility Reliability switching to other languages. (For display, Windows fonts are
Optimal performance is achieved The number of signals can be A system with minimal data loss is used.)
every time. extended from 75 to 400,000. achieved with a PC-based
High-speed data collection and display Various systems from small- to configuration.
are achieved even in large-scale large-scale configurations can be Communication functions and server
systems by optimizing every supported. Also partial system functions can be provided in
communication and reducing introduction is possible to reduce initial completely redundant configurations to Graphic screen display
unnecessary communication. investment. build a system that is safe, secure and
trouble-free, even in the event of any Menu screen (top menu, overall area) Monitoring of each area of photovoltaic panel
malfunctions in a PC or in the network.

■ System Configuration Example


Large-scale photovoltaic power generation installation area
System
PV facility interconnection
PV facility 22 to154kV
Thermometer Thermometer facility
Extra-high-voltage
incoming panel
Sunshine
recorder Sunshine
recorder
(Purchasing power)

(Selling power)

Common screen functions


Skeleton monitoring screen (for example, trends) Form output function

AI: Signal line RS-485


Modbus, etc. AI: Signal line

RS panel Remote monitoring Client display RS panel RS panel RS panel


server

Citect SCADA using smartphone


Remote monitoring control area
A smartphone can be used as a maintenance management
Internet(WAN/VPN) tool for facilities.
Trends and alarms can be checked through a wireless
Remote monitoring Windows remote desktop connection.
from existing personal
The state of computers is possible.
installation areas such
as skeleton areas can
be monitored from a
Radio equipment
remote site. Remote monitoring control personal computer

17 18
About Microgrids
Fuji Electric also develops renewable energy solutions such as photovoltaic power generation and
wind power generation for isolated islands. These microgrid configurations can achieve balanced
operation with diesel power generation using a system with an advanced high-performance power
PCS and a lithium ion capacitor mounted stabilizer. We participate in many verification tests aiming
to reduce CO2 emissions and power generation costs.

■ Conceptual diagram of microgrid MEMO

Load curve (old)

(New)
Interconnection point
Electric power network on isolated islands total output Interconnection point output

Large output
variation
Compensation
output

Output PCS

Storage battery
PCS

On-island diesel
power generation system Large output variation
Control unit
Wind power generation(WT)
Output

PCS

PCS: Power conditioner

Photovoltaic (PV) power generation


Electric power network based on renewable energy

Description of verification tests


• 6 islands in Kyushu (verification research in progress)
• 3 islands in Okinawa (verification research in progress)
<Case Study on Tarama Island in Okinawa>
Our lithium ion capacitor equipped stabilizer was introduced to enable high charging and discharging output and
high reliability.

Kuroshima Island (Kyushu) Takarajima Island (Kyushu) Tarama Island (Okinawa)

19 20
Printed on recycled paper

Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan
Phone : (03)5435-7111

Internet address : http://www.fujielectric.co.jp


Information in this catalog is subject to change without notice. 2012-8(H2012/E2012)PST/CTP10Ok Printed in Japan