Professional Documents
Culture Documents
DC Motors
D Line
Dear Customer
Thank you for purchasing a WEG DC Motor. It is a product developed with high levels of
quality and efficiency to ensure excellent performance.
Electric energy plays an outstanding role in the comfort and well-being of humankind. Being
responsible for the production of this energy, the electric motor needs to be identified and
treated as a machine whose characteristics demand special care, particularly with regard to
storage, installation and maintenance procedures.
All efforts have been made to ensure that the information contained in this manual can be
reliably used for setting up and running the WEG motor.
So please read this manual carefully before the installation, operation or maintenance of your
motor for a continuous and safe operation and to ensure that all measures have been taken
for your safety and the safety of your facilities. If any doubts persist, please contact WEG.
Keep this manual always close to the motor for prompt reference when required.
ATTENTION
1. It is absolutely necessary to follow the procedures contained in this manual for the warranty to be valid.
2. The motor installation, operation and maintenance must be executed by qualified personnel.
NOTES
1. The total or partial reproduction of the information supplied in this manual is authorized, provided that
reference is made to its source;
2. If this manual is lost, an electronic PDF file is available from our website www.weg.net or another
printed copy can be requested.
CONTENTS
1 INTRODUCTION .................................................................................................. 7
3 INSTALLATION...................................................................................................10
3.1 MECHANICAL ASPECTS ................................................................................................................10
3.1.1 Foundations..................................................................................................................................................................... 10
3.1.2 Types of bases ................................................................................................................................................................ 12
3.1.3 Alignment / leveling.......................................................................................................................................................... 12
3.1.4 Couplings......................................................................................................................................................................... 13
3.1.5 Motors protection............................................................................................................................................................ 14
3.1.6 Space heaters ................................................................................................................................................................. 17
3.2 COMMISSIONING ...........................................................................................................................17
3.2.1 Preliminary inspection...................................................................................................................................................... 17
3.2.2 Operation ......................................................................................................................................................................... 17
4 MAINTENANCE ..................................................................................................18
4.1 CLEANLINESS/INSULATION RESISTANCE ....................................................................................18
4.2 BRUSH HOLDERS ..........................................................................................................................18
4.3 NEUTRAL ZONE ADJUSTMENT .....................................................................................................18
4.4 CHECKING OF COMMUTATION.....................................................................................................19
4.5 BRUSHES .......................................................................................................................................19
4.5.1 Suitability of brushes to load conditions ......................................................................................................................... 20
4.6 COMMUTATOR...............................................................................................................................20
4.7 BEARINGS ......................................................................................................................................21
4.7.1 Quality and quantity of grease......................................................................................................................................... 25
4.7.2 Lubricating instructions.................................................................................................................................................... 25
4.7.3 Replacement of bearings................................................................................................................................................ 26
4.8 COOLING SYSTEM.........................................................................................................................26
4.8.1 Air filters for DNF and DCF models................................................................................................................................. 26
4.8.2 Air filters for DNA, DCA, DNW and DCW models ......................................................................................................... 26
4.9 DISASSEMBLY/ASSEMBLY............................................................................................................27
4.9.1 Operation to uncouple tachogenerator 1R (details for coupling – see tachogenerator manual)................................ 27
4.9.2 Operations to uncouple tachogenerator TCW .............................................................................................................. 27
4.9.3 Disassembly/assembly of DC motor.............................................................................................................................. 27
4.10 MAINTENENCE SCHEDULE ...........................................................................................................28
9 REPAIR SHOPS..................................................................................................34
1 INTRODUCTION
All standard and procedures included in this manual must be followed accordingly to ensure a proper operation to the
equipment as well as to ensure safety conditions to the personnel involved in the motor operation.
Following these procedures is also important for the Warranty Policy as explained at the end of this manual.
Therefore, we strongly recommend to any user of WEG DC Motors to read carefully this manual before motor installation and
operation. In case you still have further doubts, please contact WEG.
DANGER
The noncompliance with the procedures recommended in this warning may result in death, serious injuries
and considerable material damages.
ATTENTION
The noncompliance with the procedures recommended in this warning may result in material damages.
NOTE
The purpose of this text is to supply important information for the correct and good performance of this
product.
2 GENERAL INSTRUCTIONS
The following guidelines show the approximate insulation On new motors, lower values are sometimes obtained, as
resistance values that can be expected from a clean and solvents are present in the insulating varnishes which
dry motor at 40ºC temperature ambient, when test become volatile in a later stage during normal operation.
voltage is applied for a period of one minute, supplied by This does not necessarily mean that the motor is not
the curve of figure 2.1, as per NBR 5165 Standard. suitable for operation once the insulation resistance will
The RM insulation resistance is given by the formula: increase after a certain period of operation.
On old motors, still in operation, higher values are
Rm = Un + 1 normally obtained. The comparison with values obtained
Where: from previous tests on the same motor under identical
Rm - Minimum insulation resistance recommended in load, temperature and humidity conditions will be a better
Mega Ohm with the winding at a temperature of 40ºC; indication of the insulation conditions in comparison to
Un - Rated voltage of the motor in kV. the value obtained from a single test. Any sudden or high
reduction of the value requires careful attention.
If the test is performed at a different temperature, it is The insulation resistance is normally measured with a
necessary to correct the reading to 40ºC by using an Megometer.
insulation resistance variation curve in relation to If the insulation resistance is lower than the values
temperature, given by the motor itself. If this curve is not obtained by the above mentioned formula, motors must
available it is possible to use an approximate correction be submitted to a drying process.
given by the curve of figure 2.1, as per NBR 5165
Standard. 2.4 HANDLING
Use only the existing eyebolts to lift the motor. Never lift
the motor by the shaft. Check the motor weight. Lifting
and lowering must be done gently in order to avoid
damage to the bearings. The eyebolts attached to
bearing housing, heat exchanger, endbells, etc, should
be used to handle these components only, not complete
motor.
3 INSTALLATION
Electric motors should be installed in locations of easy access for inspection and maintenance, specially on bearings
(relubrication), inspection of brushes, etc. If the surrounding atmosphere contains humidy, corrosive or flammable
substances or particles, it is essential to ensure an adequate degree of protection.
Under no circumstances, motors can be enclosed in boxes or covered with materials which may impede or reduce the free
circulation of cooling air. Motors fitted with external cooling must be located at least 50mm from the ground to permit free air
circulation. The air inlet and outlet should never be obstructed or reduced by conductors, pipes or other objects. The
installation site should permit conditions of air renewal at a rate of 200m³ per minute for each 100 kW of motor output.
ATTENTION
On the concrete base, a metallic plate to
support the leveling bolt must be provided.
Shims
Foundation blocks
Anchorage bolts
Anchorage blocks
Steel foundation
Intermediate base
Anchorage block
Foundation blocks
Height compensation
(leveling or shims)
a) Concrete of bases (or fixed in the concrete bases) The electric motor must be accurately aligned with the
As mentioned above, the concrete bases are the most driven machine, particularly in cases of direct coupling.
commonly used for the fixation of these motors. An incorrect alignment can cause bearing damage,
The type and size of the foundation - as well as other vibrations, shaft breaking and brushes sparking.
fixing devices for this purpose will depend on the type The best way to ensure correct alignment is to use dial
and size of the motor. indicator placed on each coupling half, one reading
radially and the other axially.
b) Slide rails In this way, simultaneous readings can be informed and
When drive system is done by pulleys, the motor should one can check any parallel (figure 3.3) or concentricity
be mounted on slide rails and the lower part of the belt deviations (figure 3.4) by rotating the shaft. The dial
must be tractioned. indicator should not exceed 0.05mm. If the operator is
The rail that stays near the drive pulley is positioned in sufficiently skilled, he can obtain alignment with clearance
such a manner that the adjusting bolt be between the gauge and a steel ruler, providing that the couplings be
motor and the driven machine. The other rail must be perfect and centered (figure 3.5).
positioned with the bolt in the opposite position, as
shown in figure 3.2.
c) Metallic bases
Metallic bases must have a flat surface under motor feet
in order to avoid frame deformation. The bearing housing
surface should be so determined that under the feet of Figure 3.5: Axial clearance of 3 to 4 mm (centered bushings).
the motor one can place shims of approximately 2mm
thickness. On the alignment/leveling it is important to take into
Motor should not be removed from their common metallic consideration the effect of the temperature over the
bases for alignment; metallic bases should be leveled on motor and driven machine. The different expansion levels
the actual foundation. of the coupled machines can modify the
When a metallic base is used to adjust the height of the alignment/leveling during motor operation.
motor shaft end with the machine shaft end, it should be After the set is perfectly aligned either at cold or at hot,
leveled on the concrete base. motor must be bolted, as shown in figure 3.6. There are
After the base has been leveled, foundation studs instruments which use visible laser ray added by specific
tightened, and the coupling checked, the metal base and computer programs that can perform and ensure high
the studs are then cemented. precision alignment.
3.1.4 Couplings
a) Direct coupling
Whenever possible, it is recommended to use direct Figure 3.8: Disassembly of pulleys.
coupling due to lower cost, less space required, no belt
slippage and lower accident risk. The correct positioning of a pulley is shown in figure 3.9.
In case of speed ratio drives, it is also common to use
direct coupling with a gearbox.
ATTENTION
Align carefully the shaft ends using, whenever
possible, flexible coupling.
c) Belt/pulley coupling
Belt transmission is the most commonly used when a
speed ratio is required.
ºC 0 1 2 3 4 5 6 7 8 9
0 100.00 100.39 100.78 101.17 101.56 101.95 102.34 102.73 103.12 103.51
10 103.90 104.29 104.68 105.07 105.46 105.95 106.24 106.63 107.02 107.40
20 107.79 108.18 108.57 108.96 109.35 109.73 110.12 110.51 110.90 111.28
30 111.67 112.06 112.45 112.83 113.22 113.61 113.99 114.38 114.77 115.15
40 115.54 115.93 116.31 116.70 117.08 117.47 117.85 118.24 118.62 119.01
50 119.40 119.78 120.16 120.55 120.93 121.32 121.70 122.09 122.47 122.86
60 123.24 123.62 124.01 124.39 124.77 125.16 125.54 125.92 126.31 126.69
70 127.07 127.45 127.84 128.22 128.60 128.98 129.37 129.75 130.13 130.51
80 130.89 131.27 131.66 132.04 132.42 132.80 133.18 133.56 133.94 134.32
90 134.70 135.08 135.46 135.84 136.22 136.60 136.98 137.36 137.74 138.12
100 138.50 138.88 139.26 139.64 140.02 140.39 140.77 141.15 141.53 141.91
110 142.29 142.66 143.04 143.42 143.80 144.17 144.55 144.93 145.31 145.68
120 146.06 146.44 146.81 147.19 147.57 147.94 148.32 148.70 149.07 149.45
130 149.82 150.20 150.57 150.95 151.33 151.70 152.08 152.45 152.83 153.20
140 153.58 153.95 154.32 154.70 155.07 155.45 155.82 156.19 156.57 156.94
150 157.31 157.69 158.06 158.43 158.81 159.18 159.55 159.93 160.30 160.67
NOTE
When motors are supplied with accessories T-box, the connection terminals for thermal protectors and other
accessories are available in this T-box. If not, they are available in the main T-box.
ATTENTION
Remember that the motors will only be protected if the protectors are correctly connected to the control devices
and these be operating perfectly.
CONNECTING DIAGRAMS OF THERMISTORS (PTC) In the excitation pole (with 3 wires) - Code 9221.
In the compensation winding with 3 wires (one per pole) - 5. Are brushes perfectly set on the commutator and
Code 9233. freely moving in the brush pocket with correct
pressure?
6. Is rotation direction of the independent ventilation
correct?
7. Is air inlet free of any obstacle?
8. Is air filter clean?
One in the commutation winding and the other in the 9. Is insulation resistance within acceptable and safe
compensation winding - Code 9234. levels?
10. Are protection devices connected and operating
correctly?
11. Make sure all power supply cables, bolts and nuts
are firmily tightened for perfect contact. Besides that,
electrical connection must be made as indicated on
the connection diagram.
One per bearing - Code 9235.
3.2.2 Operation
3.2 COMMISSIONING
4 MAINTENANCE
A well-programmed maintenance schedule of DC motors, when correctly used, includes a periodical inspection of insulation
levels, bearing lubrication and useful life, vibration levels, wear of brushes and commutator as well as brush holder
conditions.
Frame must be kept clean, free of dust, oil and dirt in order to make the cooling process easier.
In case one of the above items are not followed accordingly, you might have unexpected stops of the equipment. Inspection
cycles depend on the type of motor and the conditions under which it operates.
DANGER
Before touching any internal part of the machine, make sure it is de-energized.
4.1 CLEANLINESS/INSULATION Brush holders are adjusted at the factory to the optimums
operating position. This position (neutral zone) is indicated
RESISTANCE by marks in the brush-holder. Once brush holder has been
adjusted, position should not be changed at it is used for
A regular inspection at intervals based on the type of any load value. If a dismantling of the set is required, then
service is the best way to avoid unexpected and anti- follow the mark when assembling it.
economical stops.
Motor should be kept clean, free of dust, dirt and oil
through periodical checking. Special attention must be 4.3 NEUTRAL ZONE ADJUSTMENT
given to brush holders and terminals. Brushes must be
removed and cleaned to ensure free moving in the brush Quando for substituído ou recondicionado o rotor, é
pocket. Dust and dirt on the windings can be removed provável que a posição do porta-escovas tenha que ser
with a hard brush (not metallic), and oil can be removed alterado. Para ajustar as escovas na posição neutra
with a suitable solvent. (calagem das escovas) proceder da seguinte forma
Filters must be cleaned regularly as well as felts. In case of (método prático):
air-water heat exchangers, radiator tubes must be cleaned
periodically and kept free of any obstracting object to COARSE ADJUSTMENT
facilitate air circulation. Commutator must be kept free of
dust, oil, etc. 1. Unscrew the bolts that fasten the brush-holder ring;
Insulation resistance must be checked regularly to monitor 2. Energize armature (50 to 80% of rated current for 30
the windings. It is recommended to use a 500V Megger. sec. max.); field remains switched-off. To limit current,
A winding presenting an insulation value equal to below use a low voltage such as battery.
formula is considered satisfactory:
ATTENTION
RM = Un+1, where Un in kV (as per item 2.3.2).
The maximum time of 30 sec. must be
4.2 BRUSH HOLDERS respected in order not to damage
commutator.
Brush holders must permit free sliding of brushes.
However, excessive clearance can cause vibration and 3. In case neutral zone is disadjusted trents to turn. For
further sparking. adjustment of neutral zone, turn brush holder's ring in
Normally, spring pressure ranges from 200 to 250 g/cm², the reverse side to the motor turn direction;
except for special cases. The distance between brush- 4. When rotor remains stop, then neutral zone will be
holder and commutator surface is approximately 2mm to adjusted.
avoid rupture of brushes and damage to commutator.
NOTE
If you turn brush-holder ring to the rightside
and rotor turns in the opposite direction, then
the commutation pole leads, which are
connected to the brush holder, are reserved.
Connect leads correctly and proceed as per
items 1, 2 and 3 above.
FINE ADJUSTMENT
ATTENTION
If poles must be extracted, then original air
gap have to be respected accordingly at the
time of the assembly. Also brush holder ring
must be adjusted to neutral position (see Figure 4.2: Sparking level
items 4.3 and 4.4).
4.5 BRUSHES
There is a factory-specified brush type for each DC motor
and you should always use same type and quantity of
brushes as supplied originally (pay attention to item 4.5.1).
Never use assorted brushes of different types.
The type of brushes for DC Motors are determined based
on the motor speed, voltage, current, etc.
NOTE
Any change of type and quantity of brushes
must be done under instruction of WEG as
different types of brushes cause performance
alterations to the machine in operation.
Table 4.1: Commutator diameter (mm) Make sure no piece of mica remains in the slot sides. Use
magnifying glass, if required.
COMMUTATOR DIAMETER (mm) Only the excess of the edge should be removed. Hence,
FRAME remove a minimum quantity of copper.
NEW OUTWORN
90 85 82
ATTENTION
100 85 82
A continuous operation with commutator
112 (2p) 92 89 worn can cause excessive sparking and
112 (4p) 105 102 damage totally the motor.
132 125 121
160 145 137 4.7 BEARINGS
180 170 162
160 152
The purpose of this maintenance is to lengthen bearing
200 life. Maintenance includes:
190 180 a. Attention to the overall status of the bearings;
225 180 170 b. Cleaning and lubrication;
250 (C )* 210 200
c. Inspection in details of the bearings.
Motor noise should be measured at regular intervals of
250 210 200 one to four months. A well-tuned ear is perfectly capable
280 (C )* 240 228 of distinguishing unusual noises, even with rudimentary
DNF280 240 228
tools such as a screw driver, etc.. A continuous “zum”
indicates that the bearing is operating in perfect condition.
315 270 258 Bearing temperature control is also part of routine
355 270 258 maintenance. The temperature rise of grease lubricated
bearings can not exceed 60ºC (measured at the external
400 320 306
bearing cap).
450 380 364 Temperature control can be done by means of external
* Compensated machine thermometers or by embedded thermal elements.
Bearings should be lubricated to avoid metallic contact of
The mica lowering must be done in such a way that the the moving parts, and also for protection against corrosion
“P” depth of the slot between blades remains from 0.7 to and wear. Lubricant properties deteriorate in the course of
1.2mm. Full care is required in this operation. time and due to mechanical operation and, furthermore, all
Instead of conic tools, cylindric milling machine or flat lubricants are subject to contamination under working
blades should be used for such work. conditions. For this reason, lubricants must be renewed or
Resulting wedges must be eliminated and the chamfering replaced from time to time.
should remain as shown in the below figure 4.4. For motors up to frame 132, bearings are permanently
lubricated which makes maintenance easy. At the end of
the useful life, bearings must be replaced.
For motors in frame 160 and larger, a grease fitting for
lubrication is provided. Type and amount of grease and
relubrication intervals are found in the lubrication
nameplate. The minimum period of useful life of lubricating
grease is found in tables 4.2 and 4.3, and the types of
bearings used are found in table 4.4.
Amount of Amount of
Frame Front bearing Inside diameter Rear bearing Inside diameter
grease grease
90 6205-2RS 25 5 6205-2RS 25 5
100 6305-2RS 25 5 6305-2RS 25 5
112-2P 6306-2RS 30 10 6306-2RS 30 10
112-4P 6307-2RS 35 10 6307-2RS 35 10
132 6308-2RS 40 10 6308-2RS 40 10
160 6310 50 15 6210 50 10
180 6312 60 20 6212 60 15
200 6314 70 25 6214 70 15
225 6316 C3 80 35 6216 80 20
250 6318 C3 90 40 6216 C3 80 20
280 6320 C3 100 50 6218 C3 90 20
315 6321 C3 105 55 6220 C3 100 30
355 6324 C3 120 75 6224 C3 120 45
400 6326 C3 130 85 6226 C3 130 45
450 6330 C3 150 105 6230 C3 150 60
ATTENTION
Standard grease used on WEG motors is Polyurea-based POLIREX EM (Supplier: ESSO). For relubricated
bearings (motors of frames 160 and above), the specification of this grease as well as lubrication intervals are
supplied on the bearing nameplate attached to motor frame.
4.7.1 Quality and quantity of grease If this procedure is not possible due to existing parts near
the nipple (pulleys, etc), which can be harmful to the
Correct lubrication is important for proper bearing operation. It operator, the following procedure should be followed:
means to say the grease must be applied correctly and in Inject about half the estimated amount of grease and
sufficient amount. On the other hand, insufficient or excessive run the motor at full speed for approximately one
greasing is prejudicial. minute;
Excessive greasing causes overheating due to high resistance Switch off the motor and inject the remaining grease.
encountered by the rotating parts and, in particular, by the
compacting of the lubricant and its eventual loss of lubricating
qualities. ATTENTION
This can cause leakage with the grease penetrating into the Never mix greases with different base
motor winding, commutator rings or brushes. components.
A lithium base and grease must use for lubrication of electric Example: A calcium based grease must not
motor bearings. This grease should never be mixed with sodium be mixed with a polyurea based grease.
or calcium base grease.
4.7.3 Replacement of bearings Areas poorly sealed causing penetration of dust, oil, water
or steam must be fixed.
Bearings should not be removed from the shaft, unless Motor must be cooled in accordance with specified air
this is absolutely necessary. Shaft should not suffer any flow.
knock or shock as they can cause marks on bearing
races. 4.8.1 Air filters for DNF and DCF models
These marks, although invisible with naked eye, can result
in noisy bearings and quick bearing wear. The DC Motors provided with independent forced
ventilation have an air filter in inlet air to the fan, to avoid
dust and surrounding air particles to come into the motor
(see the figure below).
Based on the type of cooling system, WEG DC motors 4.8.2 Air filters for DNA, DCA, DNW and DCW
can be divided in several groups as follows: models
Self-cooling (DNS/DCS type);
Forced cooling (DNF/DCF and DNX/DCX types);
Without cooling (DNE type); Filter
Air-air heat exchanger (DNA+DCA type);
Air-water heat exchanger (DNW+DCW type).
DC motors provided with heat exchanger have an air filter 4.9.2 Operations to uncouple tachogenerator
inside the heat exchanger holding the dust coming from TCW
the brushes and avoiding dust ingress into the motor
frame. Motors built up to frame 132, rotor of TCW generator is
The filter is made using metallic plates with filtering blanket mounted directly on the motor shaft, and the TCW frame
(see the figure below): fixed to motor endshield.
For frames 160 and up, TCW rotor is mounted on a
support and this is fixed to motor shaft. TCW frame is
fixed to motor endshield.
Filtering blanket class G-4, with
gradual density.
Gravimetrical efficiency bigger 4.9.3 Disassembly/assembly of DC motor
than 90%.
NOTE
Before servicing any internal part of the motor,
check for tensions by opening all armature
and field power supply cables.
The filter must be inspected regularly and replaced 1. Firstly remove cooling system (heat
whenever necessary, following the procedure below: exchanger or sirocco, if any);
1. Open the cover for filter access; 2. After removing tachogenerator (if any),
2. Remove the metallic frames with the filter blankets; open motor inspection covers and remove
3. The filtering blankets can be cleaned with air jet or, brushes;
depending on the dirt degree, washed with water and
average detergent. In case the filter is impregnated
with dust and grease, it is necessary to wash it with
gasoline, trichloroethylene or hot water with P3 NOTE
additive. It is recommended to check condition of
4. If necessary, replace the blankets following the air flux brushes for any abnormal detail. If brushes are
orientation described below: in good condition, keep them in a safe place.
1. Protect commutator with cardboard
sleeve for any damage during
disassembly;
2. Remove the external N.D.E. bearing cap,
unscrew ND Endshield and remove it;
3. Remove the rotor from the motor
together with drive endshield.
5. Put back and fix the plates with the blankets inside the
heat exchanger.
Measure insulation
resistance;
Frame and
armature Follow values indicated in
item 2.3.2. ;
windings.
If required, clean motor
completely.
5 CONNECTION DIAGRAM
Connection diagram with independent excitation – Code Connection diagram with additive compound excitation –
9201. Code 9213.
CW Rotation CW Rotation
CW Rotation
CCW Rotation
6 SPARE PARTS
Air outlet
Air inlet
Darkening in certain
Contact WEG;
plates;
These products, when operated under the conditions stipulated by WEG in the operating manual for such product, are
warranted against defects in workmanship and materials for twelve (12) months from startup date or eighteen (18) months
from manufacturer shipment date, whichever occurs first.
However, this warranty does not apply to any product which has been subject to misuse, misapplication, neglect (including
without limitation, inadequate maintenance, accident, improper installation, modification, adjustment, repair or any other
cases originated from inadequate applications).
The company will neither be responsible for any expenses incurred in installation, removal from service, consequential
expenses such as financial losses nor transportation costs as well as tickets and accommodation expenses of a technician
when this is requested by the customer.
The repair and/or replacement of parts or components, when effected by WEG within the Warranty period do not give
Warranty extension, unless otherwise expressed in writing by WEG.
This constitutes WEG’s only warranty in connection with this sale and is in lieu of all other warranties, expressed or implied,
written or oral.
There are no implied warranties of merchantability or fitness for a particular purpose that apply to this sale.
No employee, agent, dealer, repair shop or other person is authorized to give any warranties on behalf of WEG nor to
assume for WEG any other liability in connection with any of its products.
In case this happens without WEG' s authorization, Warranty is automatically cancelled.
LIABILITY
Except as specified in the foregoing paragraph entitled "Warranty Terms for Engineering Products", the company shall have
no obligation or liability whatsoever to the purchaser, including, without limitation, any claims for consequential damages or
labor costs, by reason of any breach of the express warranty described therein.
The purchaser further hereby agrees to indemnify and hold the company harmless from any causes of action (other than
cost of replacing or repairing the defective product as specified in the foregoing paragraph entitled "Warranty Terms for
Engineering Products", arising directly or indirectly from the acts, omissions or negligence of the purchaser in connection
with or arising out of the testing, use, operation, replacement or repair of any product described in this quotation and sold or
furnished by the company to the purchaser.
1012.05/0708
9 REPAIR SHOPS
ATTENTION
Analyze accreditation level and in case of any doubt, contact WEG service departament.
Phone: (47) 3276-4328
BRAZIL
BAHIA GOIÁS BELO HORIZONTE (31250-710)
BARREIRAS (47800-000) ACREÚNA (75960-000) LEOPOLDO E SILVA LTDA
ELÉTRICA RAPOSO LTDA AILDO BORGES CABRAL R: Caldas da Rainha, 1340 – Bairro
Rua Prof. José Seabra, 22 Rua Amaury P. Caetano, nº 117-Centro São Francisco
Tel.: (77) 611 1812 Tel./Fax: (64) 3645 1491 Tel.: (31) 3491 1096
Fax: (77) 611 6149 Nível: 3.3 Fax: (31) 3492 8944
Nível: 3.2 acabral@dgmnet.com.br Nível: 1.1, 2.3 e 3.1
eletricaraposo@uol.com.br comercial@leopoldoesilva.com.br
GOIÂNIA (74435-190)
SIMÕES FILHO (40310-100) AJEL SERVICE LTDA SARZEDO (30660-220)
STAUMMAQ SERV. TEC. AUT. MOT. E Rua 12, nº 206 - Bairro Aeroviário DATA ENGENHARIA LTDA
MAQS. LTDA Tel.: (62) 3295 3188 R: São Judas Tadeu, 280
Via Urbana, 01-CIA-SUL-Simoes Filho Fax: (62) 3295 1890 Tel.: (31) 3577 0404
Tel.: (71) 22036301 Nível: 1.1, 2.1 e 3.3 Fax: (31) 3577 6877
Fax: (71) 22036310 ajelservice@ajelservice.com.br Nível: 1.4, 2.5 e 3.5
Nível: 1.1, 2.2 e 3.3 data@dataengenharia.com.br
staummaq@terra.com.br MARANHÃO
SARZEDO (32450-000)
SÃO LUIS (65054-100)
TEIXEIRA DE FREITAS (45995-000) MPC COM. SERV. ELETR. LTDA
ELÉTRICA VISÃO COM. E SERVS.
JOÃO SANDRO MARTINS R: São Judas Tadeu, 144
LTDA
RODRIGUES Tel.: (31) 3577 7766
Rua Projetada 2, Qd L, s/n - Forquilha
Av. Pres.Getúlio Vargas, 324-São José Fax: (31) 3577 7002
Tel.: (98) 3245 4500
Tel.: (73) 32926399 Nível: 1.2, 2.3 e 3.3
Fax: (98) 3244 1144
Fax: (73) 32925600 mpcservice@mpcservice.com.br
Nível: 3.4
Nível: 1.2, 2.2, 3.2, 4 e 5.2 eletricavisao@eletricavisao.com.br
eletrweg@uol.com.br PARÁ
BELÉM (66113-010)
MATO GROSSO
CEARÁ ELETROTÉCNICA WILSON LTDA
SINOP (78550-000)
FORTALEZA (60325-330) Travessa Djalma Dutra, 682
ELETROTÉCNICA PAGLIARI LTDA
ISELÉTRICA LTDA Tel./Fax: (91) 3244 5191
Rua Colonizador Enio Pepino, 1505 –
Av. José Bastos, 933, Otavio Bonfim Nível: 2.1 e 3.4
Setor Industrial Sul
Tel.: (85) 3281 7177 eletrotecnicawilsonltda@bol.com.br
Tel.: (66) 3511 9400
Fax: (85) 3281 5681 Fax: (66) 3511 9404
Nível: 3.4 Nível: 1.2 e 3.4 PARAÍBA
adm@iseletrica.com.br pagli@terra.com.br JOÃO PESSOA (58011-200)
G.M.S. SERVS. E COM. LTDA
MARACANAÚ (61900-000) R: Índio Piragibe, 418 - Varadouro
MATO GROSSO DO SUL
P.W.ELETROTÉCNICA COM.E Tel./ Fax: (83) 3241 2620
CAMPO GRANDE (79006-600)
SERV.LTDA Nível: 3.1
BERGO ELETRICIDADE COM. DE
Av.Dr.Mendel Steinbruch, 2807, Lojas gmsmotores@veloxmail.com.br
SERVS. LTDA
B/C R: Brigadeiro Tobias, 415
Tel.: (85) 3297 2434 Tel./Fax: (67) 3331 3362 PARANÁ
Fax: (85) 3297 2434 Nível: 3.4 CURITIBA (81610-020)
Nível: 1.2, 2.2, 3.2, 4 e 5.2 bergoms@gmail.com C.O.MUELLER COM.MOT.BOMBAS
pweletrotecnica@secrel.com.br R: Anne Frank, 1134
DOURADOS (79841-000) Tel.: (41) 3276 9041
ESPÍRITO SANTO ÁVILA DA CRUZ & CIA. LTDA-ME Fax: (41) 3276 0269
ARACRUZ (29190-000) Av. Marcelino Pires, 7120 Nível:1.1 e 3.3
ESTEL – MÁQS.E SERV.INDS. LTDA Tel.: (67) 3424 4132 at.weg@comueller.com.br
Rua Luiz Musso, 240 - Centro Fax: (67) 3424 2468
Tel.: (27) 3256 1711 Nível: 3.4 FRANCISCO BELTRÃO (85601-190)
Fax: (27) 3256 3138 uriasweg@terra.com.br FLESSAK ELETRO IND. LTDA
Nível: 1.1, 2.2 e 3.4 Av. Duque de Caxias, 282 - Alvorada
estel@estel.com.br Tel./Fax: (46) 3520 1060
MINAS GERAIS
Nível: 1.4, 2.4 e 3.5
ARCOS (35588-000)
SERRA (29160-440) flessak@flessak.com.br
ELETROMECANICA GOMIDE LTDA
TEREME TEC.RECUP.MAQS.ELETR. Rua Jacinto da Veiga, 147 - Centro
LTDA PONTA GROSSA (84001-970)
Tel.: (37) 3351 1709
Rua D, 100 – Bairro Novo Horizonte SS MOTORES ELETRICOS LTDA
Fax: (37) 3351 2507
Tel.: (27) 3228 2320 Av. Ernesto Vilela, 537-Fundos
Nível: 1.1, 2.2 e 3.3
Fax: (27) 3338 1755 Tel.: (42) 3222 2166
gomide@twister.com.br
Nível: 1.2, 2.2, 3.2, 4 e 5.2 Fax: (42) 3222 2374
tereme@tereme.com.br Nível: 1.1, 2.2 e 3.3
OTHER COUTRIES
ACCREDITATION LEVEL
1. INDUCTION MOTORS
1.1. Up to frame 355 – Low Voltage – squirrel cage
1.2. Up to frame 355 – Low Voltage – squirrel cage and slip ring
1.3. Up to frame 500 – High and Low Voltage (up to 6.6 KV) – Cages and Rings
1.4. Up to frame 500 and above – High and Low Voltage
(up to 6.6 KV) – squirrel cage and slip ring
2. DC ENGINES
2.1. Up to frame 132
2.2. Up to frame 180
2.3. Up to frame 280
2.4. Up to frame 355
2.5. Up to frame 355 and above
3. SYNCHRONOUS GENERATORS
3.1. Up to frame 160 (Self-adjusted)
3.2. Up to frame 225 (Low Voltage)
3.3. Up to frame 250 (Low Voltage)
3.4. Up to frame 400 (Low Voltage)
3.5. Up to frame 400 and above – High and Low Voltage (6.6 KV)
4. TACHOGENERATOR
ANOTAÇÕES