GENERAL:
5330 8400 3300 2193 G1. THE DESIGN ON THIS DRAWING IS COPYRIGHT AND REMAINS THE PROPERTY OF
TONDOLO ARCHITECTS.
1030 6340 1030 G2. THE DRAWING MAY NOT BE COPIED OR REPRODUCED IN WHOLE OR IN PART
WITHOUT THE WRITTEN PERMISSION OF TONDOLO ARCHITECTS.
G3. ANY CONSTRUCTION WORK UNDERTAKEN PRIOR TO MUNICIPAL APPROVAL OF

340
THE PROJECT SHALL BE UNDERTAKEN AT THE RISK OF THE CLIENT.

680
G4. ALL WORK TO COMPLY WITH NBR AND BUILDING STANDARDS ACT 103 OF 1977,
SANS 10400 AND SANS 204.

120
800 G5. THIS DRAWING IS NOT TO BE SCALED, FIGURED DIMENSIONS PREVAIL.
G6. ALL RELEVANT DETAILS, DIMENSIONS AND LEVELS TO BE CHECKED ON SITE
220

340
BEFORE COMMENCEMENT OF ANY WORK. DISCREPANCIES TO BE

220
800 IMMEDIATELY REPORTED TO THE ARCHITECT. THE ARCHITECT ACCEPTS NO
RESPONSIBILITY FOR THE MISINTERPRETATION OF DRAWINGS.
G7. SAMPLES OF ALL SPECIFIED PRODUCTS TO BE SUBMITTED FOR APPROVAL TO

120

154
7 THE ARCHITECT BEFORE FITTING ON SITE.
366 5
WALKWAY WALKWAY 223 G8. A FULL SET OF THE LATEST DRAWINGS ARE TO BE KEPT AND MAINTAINED ON
SITE FOR REFERENCE.

2000
920
5 CONSTRUCTION:
110

3960

3960

3960

340
C1. REINFORCED CONCRETE, STRUCTURAL STEELWORK INCLUDING CONNECTIONS

3530
OF BALUSTRADES AND LAMINATED BEAMS TO STRUCTURES, LOAD BEARING

220
0
5330 8400 5493 185 MASONRY WALLS AND TIMBER STRUCTURES ALL TO BE IN ACCORDANCE WITH
THE STRUCTURAL ENG'S DESIGN AND SPECS.
1100 340 3890 340 7720 340 C2. ALL MECHANICAL VENTILATION TO BE ACCORDING TO ENG'S DETAILS AND SPECS.
110

360
C3. DPC TO ALL WALLS AT FLOOR LEVEL, UNDER WINDOW CILLS, AGAINST

329
895 RETAINING WALLS AT CHANGES IN FLOOR LEVELS, BELOW CONCRETE SURFACE
620

0
4
110

2
BEDS AND AT JUNCTIONS OF P.C COPINGS.
PORTICO 895
SINK
STAFF C4. ALL GLAZING TO BE IN ACCORDANCE WITH SANS 10400 PART N AND SANS 204.
ALL GLAZING, EXCEPT WHERE INDICATED, IS TO BE LAMINATED SAFETY GLASS
110 PERMANENTLY MARKED WITH GLASS CODE AND READILY VISIBLE.
RESTROOM
1280

1x30m FHR

110
C5. WINDOW AREA TO BE MINIMUM 10% OF FLOOR AREA. OPENING SECTIONS OF
2x4,5kg DCP HB WINDOWS AND DOORS TO BE MINIMUM 5% OF FLOOR AREA FOR VENTILATION.
0
118 187

185

316
WC

360
0
C6. WATERPROOFING OF FLAT ROOFS TO BE UNDERTAKEN ACCORDING TO

0
WC

0
MANUFACTURER'S DETAILS AND SPECS.

340
STAFF
250

250

154
282
C7. PITCHED ROOFS WITH STEEL OR TILED COVERING TO BE WATERPROOFED

340
AGAINST PARAPET WALLS WITH 1.2mm GS FLASHING AND COUNTER FLASHING,

718
WC DISABLED W.C AND ALL JOINTS SEALED ACCORDING TO MANUFACTURER'S DETAILS AND SPECS.

185

220
3280 WHB
250 SEWER AND STORM WATER:

0
FR

110
900
COUNCELING
966

WC WHB P1. ALL PLUMBING WORK TO BE CARRIED OUT BY LICENSED PLUMBERS AND WORK
9 TO COMPLY WITH SANS 10400 P.
217 P2. ALL DRAINAGE RUNS TO BE ACCESSIBLE ALONG THEIR ENTIRE LENGTH.
WC 700

142
110

360
P3. ALL HOT AND COLD WATER RETICULATION, BULK SEWER AND STORM WATER
110

COLLECTION TO BE ACCORDING TO ENG'S DETAILS AND SPECS.

2223

220

0
0
110

186
WHB
PUBLIC 5 P5. VENT. PIPES TO EXTEND 2m ABOVE ANY WINDOW OR DOOR OPENING IN THE

0
STAFF 153
3110

STAFF
959

WC BUILDING OR ANY OTHER BUILDING WITHIN A DISTANCE OF 6m.

360
FEMALE W.C

148
P6. IE TO ALL BENDS AND JUNCTIONS OF SOIL AND WASTE PIPES.

220
WHB MALE W.C FEMALE W.C

0
P7. RE TO HEADS OF DRAINS AND AT A MAX 25m INTERVALS ALONG RUNS OF DRAINS.

164
P8. RESEAL TRAPS TO ALL WASTE FITTINGS.

4100
0 250

426
158 P9. CI COVERS AT GROUND LEVEL FITTED IE AND RE MANHOLES
110

0
0
FILING ROOM 265

110
2
WHB

110
900
URL 0
7500 3500 220 WHB 110 P13. GEYSERS INSTALLED ACCORDING TO MANUFACTURER'S SPECS, WITH A
966

WC DRIP TRAY AND TO SABS 0524 REGULATIONS.


SKYLIGHT

190
WHB P14. MIN. FALL OF 100m LONG DRAINS TO BE 1:60, WITH A MIN. COVER OF 300mm. FALLS

100
0 EXCEEDING 1:10 TO BE PROVIDED WITH BACK DROPS.

4536
190

0
P15. SOIL DRAINS UNDER GROUND SLABS TO BE FITTED IN PC CHAMBER FILLED WITH

0
110

0 CRUSHED STONE AND PC COVER WITHOUT CHANGES IN DIRECTION. NO SEWER IS


321 TO BE CAST IN FOUNDATION FOOTING.
WHB
CABLE TRAY MOUNTED TO
UNDERSIDE OF COUNTER, 220
CORRIDOR P17. ALL BRANCH DRAINS EXCEEDING 6m IN LENGTH TO BE VENTED.

142
WC P18. uPVC SEWER PIPES TO SABS 791 CLASS 34 STANDARDS AND LAID IN
STATIONERY

250
SEE W417 ACCORDANCE WITH THE MANUFACTURER'S DETAILS AND SPEC.

0
80
114 0 144
6 P19. HOT AND COLD WATER PIPES FOR INTERNAL RETICULATION TO BE CLASS 1
140 STORE COPPER TUBING AND INSULATED ACCORDING TO SANS 204.
1850

RECEPTION 373
0 8800 SKYLIGHT 250 FIRE PROTECTION:
17115

110

4134
1850 110 2040 340

220

138
WAITING AREA 220 F1. ALL WORK TO COMPLY WITH SABS 0400-1990, OCCUPANCY CLASSIFICATION E2.
11 997 F2. INSTALLATION OF FIRE EQUIPMENT TO BE ACCORDING TO SABS 0105 FOR
PUBLIC 0

0
200 EXTINGUISHERS, SABS 543 FOR FIRE HOSE REELS AND SABS 1128 PART 1

9600

9600
1400
0
122
9720

0 FOR HYDRANTS.
DISABLED W.C 389

5254
F3. STRUCTURAL ELEMENTS AND COMPONENTS TO COMPLY WITH REQUIREMENTS
2380 110 AS SPECIFIED IN THE RATIONAL FIRE REPORT AND SANS 10400-T 4.7,
110

AND TO HAVE FIRE STABILITY OF MIN. 120 MINUTES.

296
0 FILING ROOM

220
F5. PORTABLE FIRE EXTINGUISHERS TO BE HUNG ON PURPOSE MADE BOARDS AND
259

0
600x600mm MILD FIXED IN SECURE POSITIONS AS INDICATED ON THE PLAN AT A HEIGHT NOT
URL STEEL CEILING EXCEEDING 750mm.
ACCESS PANEL
SKYLIGHT 220 F6. FIRE HYDRANTS TO INCLUDE 75mm PILLAR WITH DOUBLE HEADED BOOSTER
ABOVE 110 CONNECTION, PRESSURE GAUGE AND NON-RETURN VALVE TO ENG. SPECS.
F7. SMOKE CONTROL AND DETECTION INSTALLED ACCORDING TO ENG'S DETAIL
URL AND SPEC. AND RATIONAL FIRE DESIGN REPORT.
PUBLIC
2400

246
7 OFFICE 2 F8. EMERGENCY LIGHTING TO BE INSTALLED ACCORDING TO THE ENG'S SPECS.
F9. SYMBOLIC SAFETY SIGNS TO BE IN ACCORDANCE WITH SABS CODE 1186 AND
MALE W.C

220
AC POSITIONED AS REQUIRED BY THE FIRE DEPARTMENT.

300
UNIT F10. FIRE DOORS TO BE FITTED WITH EMERGENCY EXIT LOCKSETS.

110
F11. CLASS B FIRE DOORS TO COMPLY WITH SABS CODE 1253 AND TO BE FITTED

0
WITH APPROVED SELF-CLOSING OR AUTOMATIC CLOSING DEVICES.
URL

900
CLEANERS RM MOVEMENT JOINTS
4420

E1. ALL MOVEMENT JOINTS ACCORDING TO ENG'S DETAIL AND SPEC.


700 POWER E2. NO STRUCTURAL, FLOOR OR WALL FINISH TO BE TAKEN OVER EXPANSION JOINTS.
4100

242
SKIRTING
110

170
TIMBER

220
WT

20
0
W1. TIMBER WALL PLATES TO BE TANALIZED.
SERVER RM W2. STRUCTURAL TIMBER TO BE IN ACCORDANCE WITH SABS 1245 AND MARKED WITH

1809

135
6 STRESS GRADE. LAMINATED TIMBER TO COMPLY WITH SABS 1460
900

WC WHB 312

300
600x600mm POWER W3. THE CONTRACTOR TO PROTECT ALL TIMBER MATERIALS AGAINST WEATHER

50
FAX ROOM W4. TRUSS HOLD-DOWN, CONNECTIONS, HANGERS AND CLEATS TO BE IN

0
CEILING ACCESS SKIRTING
PANEL TO SPEC
CORRIDOR ACCORDANCE WITH ENG'S DETAILS AND SPEC.
W5. THE CONTRACTOR TO CHECK CORRECT FIXING OF ALL SPECIFIED BRACING
110

1793
W6. ALL TRUSSES AND TIMBER LOAD BEARING STRUCTURES TO BE IN ACCORDANCE

250
TO ENG'S DETAIL & SPECS. INCLUDING TRUSS HOLD-DOWN, CONNECTIONS,
7500 460 2930 HANGERS AND CLEATS.
WHB
90 900

WC

116
COPIER FAX 0
150 OFFICE 1

888
158
0

7
0
732

110
340

250

450
220

110

FOR TENDER ONLY


128
1100 340 3310 340 8880 340 2470 250 OFFICE 3

5 1
4750 2720
0
398
2000

1890

PORTICO
POWER

300
2965

SKIRTING
110

0
0
144

500
450

OFFICE 4

0
965

965

POWER
515

SKIRTING

110
1030 7500 1030 * * *
450
BOARDROOM REV DATE DESCRIPTION
4750 9560 2720

17030 THIS DRAWING IS COPYRIGHT OF TONDOLO PARTNERSHIP

138
300

885
117

0
0

0
01

220
0
400

ELECTRICAL LEGEND DIRECTOR


220
WALL MOUNTED LIGHT TELEPHONE 110
TEL 6
CONNECTION POWER 1400 122

110
SKIRTING 116
8
110 250
POLE LIGHT TV AERIAL 6

300
TV 900 259
CONNECTION

0
CLIENT
RECESSED LIGHT IN SINGLE PLUG POINT 135
0 0 250
SLAB/CEILING. 300mm ABOVE FFL 398 200
5

487
8
116
WALL MOUNTED NORTH WEST PROVINCIAL

0
EMERGENCY LIGHT SINGLE PLUG POINT
GOVERNMENT

0
135
300mm ABOVE FFL 1200mm ABOVE FFL
9
330

220
DEPARTMENT OF HEALTH

400
WALL MOUNTED DIMMER SWITCH 306
4
EX 0

0
EXAMINATION LIGHT 732

300
TWO WAY SWITCH
INTERCOM

0
0
150

140
5
200

0
PROJECT
ONE WAY SWITCH PROPOSED NEW COMMUNITY HEALTH
POLE INTERCOM
CENTRE IN

128
900
250 RECEPTION

250
ELECTRICITY D.B BOARD
BED HEAD LIGHT

0
METER
340
1 240 SAFE MATLOSANA
*

220

340
EF EXTRACT FAN GS GEYSER *
*
SMOKE DETECTOR DISTRIBUTION BOARD
UNIT

300

153
MAIN RECEPTION AND

0
NETWORK N

0
PIPE 20mm POWER SKIRTING
PORTICO ADMINISTRATION - UNIT 5
0
118
SINGLE PHASE
DOOR BELL WORKING DRAWINGS
ISOLATOR

487
0
WALL MOUNTED
HB 3L HYDROBOIL ELECTRIC HEATER
ELECTRICAL LAYOUT PLAN

220
600x600mm 1200x600mm 546
0
FLUORESCENT TUBE FLUORESCENT TUBE 0
782 SCALE DATE DRAWN
1200mm SUSPENDED 1200mm FLUORESCENT 1:50 2015.03.20 *

140
FLUORESCENT TUBE TUBE

0
PROJ NO REV DRAWING NO
NOTE:
0 1. THIS DRAWING IS TO BE USED ONLY FOR ELECTRICAL LAYOUTS.
*
118
2011 / 44 DATE
W601
ELECTRICAL LAYOUT PLAN

250
2. ALL DIMENSIONS TO BE CHECKED ON SITE BEFORE ANY
SCALE 1:50 COMMENCEMENT OF WORKS.
*