Professional Documents
Culture Documents
by
WAYNE SWANEPOEL
MAGISTER INGENERIAE
in
MECHANICAL ENGINEERING
in the
FACULTY OF ENGINEERING
at the
OCTOBER 1998
ABSTRACT
Keywords:
refrigeration cycles
refrigerant mixture
pure refrigerants
non-azeotropic refrigerants
binary
wet compression
dry compression
ii
ACKNOWLEDGEMENTS
A special word of thanks to my wife for her emotional support during this research period.
I would like to thank Prof. J.P. Meyer for his professional guidance and support during this
exciting period.
Thank you for the financial support provided by the FRD and ESCOM.
ifi
• The top performing non-azeotropic mixtures produce higher COP G 's than
the top performing pure refrigerants. It should be kept in mind, however,
that this conclusion is based on the method of comparison between non-
azeotropes and pure refrigerants chosen for this study. The chosen method
of comparison for this study is summarised in Figure I. Viewing Figure I,
it can be seen that the evaporation and condensation temperatures chosen
for the evaluation of a pure refrigerant, are retained as respectively
bubble point and dew point temperatures for the evaluation of the non-
azeotropic mixture. Other methods of comparison may lead to different
results.
Tcond
Pure refrigerant
Non-azeotrove
Tevap
The top performing refrigerants are summarised in Tables I and II. In both
the tables the non-azeotropic mixtures were divided into three categories
according to the amount of temperature glide displayed by each of them. A
"low temperature glide" is defined by a refrigerant having a temperature
glide that lies between 0°C and 5°C. A "medium temperature glide" is
defined by a refrigerant having a temperature glide that lies between 5°C and
10°C. A refrigerant that has a temperature glide higher than 10°C falls in the
"high temperature glide" category. All the refrigerants were divided into
groups of "phased-out", "temporarily acceptable" and "acceptable"
refrigerants. These three groups correspond to the groups identified by the
Montreal Protocol: "phased-out" refrigerants being CFC's or similar
refrigerants phased-out since January 1996, "temporarily acceptable"
refrigerants being HCFC's or similar refrigerants that will be phased-out in
future under the Montreal Protocol, and "acceptable" refrigerants being thoSe
deemed acceptable for use in future. The phased-out refrigerants are analysed
but omitted here for obvious reasons, while Table I lists the temporarily
acceptable refrigerant mixtures and Table II shows the acceptable refrigerant
mixtures.
Table I The highest COP, values for each of the three levels of temperature
glides, considering only temporarily acceptable refrigerant mixtures. The first
value in each block is the COP, (with the relevant inlet vapour quality in
brackets), the second is the specific cooling capacity (kJ/kg) and the third is the
compressor displacement per kilowatt cooling (litre/s)
Table II The highest COP, values for each of the three levels of temperature
glides, considering only acceptable refrigerant mixtures. The first value in each
block is the COP, (with the relevant inlet vapour quality in brackets), the
second is the specific cooling capacity (kJ/kg) and the third is the compressor
displacement per kilowatt cooling (litre/s)
V
4. The refrigerants evaluated were evaluated for both wet and dry compression
processes. This resulted in the identification of refrigerants susceptible to
the advantages of wet compression.
The following conclusions were made:
120°C
cc?
E.' 50°C Condens in
7°C Evaporating
gr-
-70°C
Figure II The T-s graph of NH3 as an example Figure III The T-s graph of RC318 as an
of a bell- shaped curve example of a curve with a re- entrant
saturated vapour line
From the pure refrigerants with bell-shaped T-s graphs, only R32 and
NH3 produce higher COP c 's when wet compression is used. Wet
compression, however, reduces the cooling capacity and increases the
compressor displacement.
TABLE OF CONTENTS
ABSTRACT
ACKNOWLEDGEMENTS ii
CONTRIBUTIONS OF THIS STUDY iii
TABLE OF CONTENTS vi
LIST OF FIGURES viii
LIST OF TABLES iz
NOMENCLATURE x
INTRODUCTION 2
1.1 BACKGROUND 2
1.2 PREVIOUS WORK 5
1.3 PURPOSE OF THIS STUDY 5
1.4 SCOPE OF THIS STUDY 6
REFERENCES 66
VIII
LIST OF FIGURES
Figure 1 Vapour-compression cycle for an (a) azeotropic and (b) non-azeotropic refrigerant
Figure 2 Vapour-compresion cycle for wet (1' to 2') and dry (1 to 2) compression for a (a)
pure refrigerant and a (b) non-azeotropic refrigerant mixture
Figure 3 The COP, results for air conditioning, using E245, R143 and NH 3
Figure 4 The specific cooling capacity results for air conditioning, using E245, R143 and NH3
Figure 5 The amount of refrigerant circulated for each kilowatt of air cooling using E245, R143
and NH3
Figure 6 The compressor displacement rate for each kilowatt of air cooling using E245, R143
and NH3
Figure 7 The T-s graph of NH 3 as an example of a bell- shaped curve
Figure 8 The T-s graph of RC318 as an example of a curve with a re- entrant saturated vapour
line
Figure 9 A comparison between the evaporation and condensation temperatures of a pure
refrigerant, and the bubble point and dew point temperatures of a non-azeotropic
mixture
Figure 10 Graph showing the discontinuity in the calculation of the COP, values for
R13b1/R152a (0.9/0.1)
Figure 11The compressor displacement and refrigerant circulated per kilowatt of cooling for
R32/R143 (0.3/0.7)
Figure 12The COP, values for R32/R143 (0.3/0.7)
Figure 13The specific cooling capacity and specific work for R32/R143 (0.3/0.7)
Figure 14 The COP, plotted as a function of the corresponding temperature glide for all the non-
azeotropes considered
Figuie 15The temperature glide distribution for R13b1/R152a
Figure 16The temperature glide distribution for R32/R142b
Figure 17The temperature glide distribution for R22/R218
ix
LIST OF TABLES
Table 1 List of pure refrigerants analysed for spatial air conditioning applications
Table 2 A summary of the maximum COP c values obtained through calculation for every pure
refrigerant. Also tabulated are the corresponding specific cooling capacity (kJ/kg) and
compressor displacement (Us) per kilowatt of cooling. These values are compared with
the values obtained at 10°C superheat, since it is commonly found in practise that the
refrigerant is compressed at this superheated value
Table 3 A list of pure refrigerants where higher COP c values were obtained by using wet
compression over dry compression. Also tabulated are the changes in COP O, specific
cooling capacity and compressor displacement values relative to the values at 10°C
superheated. A negative value indicates a decrease when wet compression is used
Table 4 The considered pure refrigerants are divided into two groups: Those refrigerants with a
bell- shaped T-s curve (refer to Figure 7); and those refrigerants with a T-s curve with a
re- entrant saturated vapour line (refer to Figure 8).
Table 5 A list of the refrigerant mixtures analysed
Table 6 A summary of the maximum COP c and corresponding specific cooling capacity (kJ/kg)
and compressor displacement (Us) per kilowatt of cooling. Also tabulated are the same
values obtained at 10°C superheat
Table 7 The top 10 refrigerant mixtures with the highest percentage improvement in COP c
obtained by using wet compression over dry compression. Also tabulated are the
changes in COPc, specific cooling capacity and compressor displacement values
relative to the values at 10°C superheated as a percentage
Table 8 The top 30 list for the highest COPc's and at what vapour quality this was achieved
Table 9 The top 30 list for the highest COPc 's for air conditioning for each of the three levels of
temperature glides.
Table 10 Table showing the three categories of refrigerant mixtures of Table 8 identified in the
light of the environmental restrictions
Table 11 The highest COP c 's for air conditioning for each of the three levels of temperature
glides. Only temporarily acceptable refrigerant mixtures are considered. The first value
is the COPc (with the relevant inlet vapour quality in brackets), the second is the
specific cooling capacity (kJ/kg) and the third is the compressor displacement per
kilowatt cooling (litre/s).
Table 12 The highest COP c 's for air conditioning for each of the three levels of temperature
glides. Only acceptable refrigerant mixtures are considered. The first value is the COP.
(with the relevant inlet vapour quality in brackets), the second is the specific cooling
capacity (kJ/kg) and the third is the compressor displacement per kilowatt cooling
(litre/s).
NOMENCLATURE
h Specific enthalpy (J kg -I )
w Specific work (J kg -I )
x Vapour quality
1. INTRODUCTION
1.1 BACKGROUND
The Montreal Protocol was the dawn of a new age for industries, including the
air conditioning and refrigerating industry which were consuming and producing
these compounds. Short to medium term alternatives (HCFC's) were almost
readily available, but the industry was continuously faced with the challenge of
finding suitable replacements for ozone depleting compounds. Although
numerous studies have revealed various possibilities, the search for a more
efficient, cheaper and safer refrigerant is a never-ending one. The reason for
this statement is partly due to the fact that, although refrigerants are used in a
pure state, research revealed that mixtures of refrigerants can reveal some
interesting results as well. This provides an extra degree of freedom and
literally thousands of new refrigerants can be "formed". Since the advent of the
Montreal Protocol, much work has been done in an attempt to find replacements
for CFC's. These include studies on pure refrigerants, as well as mixtures of
refrigerants (see i.e. References 2 to 12).
These refrigerants can be divided into two main groups, azeotropes and non-
azeotropes. The major difference between the two groups can best be explained
by referring to Figure 1. The standard vapour-compression cycles for the two
different groups of refrigerants are presented for negligible pressure drop. The
main difference, as can be seen in the figure, lies in the region underneath the
saturation curve. This coincides with the condensing (points 2' to 3) and
evaporating processes at constant pressure (points 4 to 1) in Figure 1. These
two processes are isotropic (at constant temperature) for the azeotropes
underneath the saturation curve, as is shown in Figure la.
Figure 1 Vapour-compression cycle for an (a) azeotropic and (b) non-azeotropic refrigerant
Another possible danger of wet compression that accelerates wear, is that the
droplets of liquid may wash the lubricating oil from the walls of the cylinder.
Although wet compression is therefore likely to damage compressors that are
currently used in industry, advancements are made rapidly in materials,
lubricants and new types of compressors. It would therefore not be farfetched to
hope that wet compression might be a practical reality in the near future.
Figure 2 Vapour-compression cycle for wet (1' to 2') and dry (1 to 2) compression for a (a)
pure refrigerant and a (b) non-azeotropic refrigerant mixture
An example is given in one of the case studies considered by Itard 14 , where wet
compression could increase the COP from 69.3% to 94.8%! The results of Itard 14
are therefor exciting. However, one should not forget that only four refrigerants
(three pure and one non-azeotropic) of all the possible pure refrigerants and
non-azeotropic mixtures available on the market, were considered. Only one
heat pump application is considered in the paper of Itard 14 , namely at an
evaporating temperature of 10°C and a condensing temperature of 60°C.
The outline of this paper is as follows: Part I deals with pure refrigerant
refrigeration cycles and Part II is devoted to non-azeotropic mixtures. In each
part the refrigerants considered are given, the cycle analyses are explained,
whereafter the results are discussed taking into consideration the environmental
impact.
CHAPTER TWO
8
Table 1 lists the 34 pure refrigerants that are considered in this paper. From the
list of 38 refrigerants provided in REFPROP, not all of the pure refrigerants are
defined for the 7°C to 50°C temperature range, which means that their critical
points lay within or very close to this region. Since points close to the critical
point prompt unreliable results, the performance of the following pure
refrigerants: R13; R14; R23; R744 was not analysed.
Table 1. List of pure refrigerants analysed for spatial air conditioning applications
Seeing that this study focuses on wet compression, it inevitably implies that
many calculations will be done based on data from within the two- phase region.
It is as a result of this that the evaluation takes place over a wide spectrum of
compressor inlet vapour qualities. This quality ranges from 0.3 to 1.0 in
increments of 0.1, and for superheat values of 10°C and 20°C. Some refrigerants
were evaluated from a higher quality, for example R134a. This is due to the fact
that in some cases isenthalpic expansion through the expansion valve leaves the
9
refrigerant at a higher vapour quality than 0.3 at the evaporator inlet, which
results in, when attempting calculation, ambiguous refrigerant performance
values.
The specific work done by the compressor, specific cooling capacity, COP C ,
refrigerant circulated for one kilowatt of cooling and compressor displacement
per kilowatt of cooling, were calculated for each of the refrigerants in Table 1
for the different compressor inlet qualities discussed in the previous paragraph.
A compressor isentropic efficiency of 75% was used and the condenser sub-
cooling was assumed to be zero. Isenthalpic expansion was also used for all
refrigerants and zero pressure drop was assumed through the condenser and
evaporator.
The specific work done by the compressor for dry or superheated compression is
calculated as
w= h2 -hl (1)
The specific work done by the compressor for wet compression is calculated as
q= - ha
q=hr -h4
The required refrigerant mass flow for 1 kW of cooling for dry compression is
calculated as
mr = 1/(h i - ha ) (8) •
The required refrigerant mass flow for 1 kW of cooling for wet compression is
calculated as
mr = 1/(hi• - ha ) (9)
The required compressor displacement rate per kilowatt of cooling for dry
compression is calculated as
The required compressor displacement rate per kilowatt of cooling for wet
compression is calculated as
The compressor discharge temperature was also obtained from the condensing
pressure and enthalpy at point 2.
2.3 RESULTS
The values obtained from using this method, is a good reflection of a refrigerant
under the same conditions in practice. The method does however not take into
account the pressure losses incurred in the evaporator and condenser and the
input power needed for example for fans and auxiliary equipment. This fact
must be kept in mind when reviewing this work, since the results produced will
lead for example to higher COP c's than would be experienced in practice.
Furthermore, the methodology followed resulted in a large volume of data of
which the detailed results are reproduced in the Appendices. The results are
represented in Appendices AAAA to AABL. Only limited results will be presented
in this document due to the fact that the results were specifically selected to
present a sufficient understanding and perspective of the use of wet compression
versus dry compression.
11
2.3.1 PERFORMANCE
The results for air conditioning, using three different refrigerants, are shown in -
NH3
R143
E245
00 C.' U
0 0 0 0 0 0
csi
Vapour quality
Figure 3 The COPS results for cooling R143, E245 and NH3
The cooling capacity results (Figure 4) shows that for NH3 and to .a lesser extent
with R143, the rate in increase of cooling capacity decreases as the vapour
quality approaches one. With E245, the rate in increase of cooling capacity
remains constant. Generally the cooling capacity decreases with wet
compression as can be expected, although the gradient changes at an inlet
vapour quality of one.
1200
1000 —
71) 800 NH3
600 -`- R143
cr 400 — E245
........
200 — ......... -
....... -
0 ... ".
I I I I
M Tr v-) `0 N 013.
6 6 6 0 o 0
O
•—• Cs1
Vapour quality
Figure 4 The specific cooling capacity results R143, E245 and NH3
12
250.00
200.00
150.00
NH3
an
sal 100.00 R143
50.00 - E245
0.00
0
0 0 0 0 0 • 0
0 0
N •
Vapour quality
Figure 5 The amount of refrigerant circulated for each kilowatt of cooling using R143, E245 and
NH3
60.00
50.00
40.00 -
NH3
1-1 30.00
. 8143
20.00 E245
10.00
0.00
v. Is al O I I
0 0 o 0 0 0 0 W
0 0
Vapour quality
Figure 6 The compressor displacement rate for each kilowatt of cooling using R143, E245 and
NH3
13
Table 2 lists the highest COP values obtained through calculation for every pure
refrigerant considered, whether it is with wet or dry compression. Also tabulated
are the corresponding specific cooling capacity (kJ/kg) and compressor
displacement (1/s)/(kW cooling) values. These values are compared with the
values obtained at 10°C superheat, since it is commonly found in practise that
the refrigerant is compressed at this superheated value.
From Table 2 it can be seen that the following refrigerants respond favourably
to wet compression as they have higher COP c values in the two-phase region:
R32 and NH3.
The highest COP value, that of ammonia, is obtained through the process of wet
compression. A COP value of 4.28 at a vapour quality of 0.9 is 7.2% higher than
the COP value of 3.99 at 10°C. Ammonia's specific cooling capacity decreased
with 14.3% against the 16.8% decrease considering R32. Wet compression of
ammonia doesn't affect the required compressor displacement rate to acquire
lkW of cooling.
It should be noted that although the COP values increase substantially, the
specific cooling capacity decreases. In the case of R32 the required compressor
displacement rate to acquire 1 kW of cooling increases with 3.1%. This means
that for wet compression more of the refrigerant is needed to have the same
cooling affect obtained from dry compression, which may require larger and
more expensive compressors.
14
Table 2 A summary of the maximum COPc values obtained through calculation for every pure
refrigerant. Also tabulated are the corresponding specific cooling capacity (kElcg) and
compressor displacement (Us)/(kW cooling) values. These values are compared with the values
obtained at 10°C superheat, since it is commonly found in practise that the refrigerant is
compressed at this superheated value
15
Table 2 (continued)
16
Table 2 A summary of the highest COP values obtained through calculation for every pure
refrigerant. Also tabulated are the corresponding specific cooling capacity (k.1/kg) and
compressor displacement (1/s)/(kW cooling) values. These values are compared with the values
obtained at 10°C superheat, since it is commonly found in practise that the refrigerant is
compressed at this superheated value
18
—_
101°C
Temperature [°C] •
50° Conden m
7°C Evaporat
-49°C
Entropy [kJ/kg•K]
Figure 8 The T-s graph of RC318 as an example of a curve with a re- entrant saturated
vapour line
Table 4 The considered pure refrigerants are divided into two groups: Those refrigerants with a
bell- shaped T-s curve (refer to Figure 7); and those refrigerants with a T-s curve with a re-
entrant saturated vapour line (refer to Figure 8).
19
None of the refrigerants with re-entrant saturated vapour lines prompted results
with higher COP values when considering wet compression. On the other hand,
not all the refrigerants with bell-shaped T-s curves proved advantageous to the
practise of wet compression. The refrigerants mentioned above for which wet
compression is advantageous, all fall in the bell-shaped T-s graph group, and yet
not all the refrigerants enjoy the advantages of wet compression.
2.3.4 CONCLUSION
From the 34 pure refrigerants analysed, all those with re-entrant saturated
vapour lines produce better COP c 's when the refrigerant is superheated before
entering the compressor. Only two of the refrigerants (R32 and NH3) with bell-
shaped T-s curves, consistently produce higher COI:Vs when wet compression is
used. It can therefore be concluded that in general it has been found that wet
compression is not attractive when pure refrigerants are used.
20
CHAPTER THREE
21
3.1 INTRODUCTION
Refrigerant Mixtures
R11/R114 R143/R43a R32/R143
R12/R152a R22/R114 R32/R152a
R12/R22 R22/R134a R13b1/R152a
R123/R134a R22/R142b R32/R142b
R124/R125 R22/R152a R22/R124
R125/R142b R22/R218 R22/R143
R125/R143 R290/R600 R218/RC318
R125/R143a R32/R124 R134a/R143
R125/RC318 R32/R125 R12/R13
R134a/R143a R32/R134a R124/R143a
R142b/R143a
The refrigerant mixtures selected were refrigerants that had recently been
considered in literature (References 2 to 11, 16 and 17). In literature, either
specific or just a few mixing concentrations were considered, where the full
range of concentrations was considered in this study.
As with pure refrigerants, some mixtures at certain mass ratios were omitted
from the analyses because their critical temperatures would come to close to the
dew point temperature of 50°C for air conditioning applications.
the evaporator (point A), the bubble point, corresponds to the evaporation
temperature use with the pure refrigerant. The inlet of the condenser (point B),
the dew point, is at the same temperature as that for the condensation process of
the pure refrigerant.
The quality ranges investigated were again from 0.3 to one in increments of 0.1
as well for superheat values of 10°C and 20°C. The compressor isentropic
efficiency, sub-cooling, expansion and pressure drop assumptions, were the
same as for pure refrigerants.
Tcond Yil•••••••••■■■••••
Pure refrigerant
Non-azeotrone
Tevap
3.3 RESULTS
Table 6 (continued) A summary of the maximum COP and corresponding specific cooling
capacity (kJ/kg) and compressor displacement (Us) per kilowatt of cooling. Also tabulated are the
same values obtained at 10°C superheat
24
Table 6 (continued) A summary of the highest COP and corresponding specific cooling capacity
(kJ/kg) and compressor displacement (I/s)/(kW cooling) values obtained through calculation for
each refrigerant mixture. Also tabulated are the same values obtained at 10°C superheat
25
Table 6 (continued) A summary of the highest COP and corresponding specific cooling capacity
(kJ/kg) and compressor displacement (1/s)/(kW cooling) values obtained through calculation for
each refrigerant mixture. Also tabulated are the same values obtained at 10°C superheat
26
Table 6 (continued) A summary of the highest COP and corresponding specific cooling capacity
(kJ/kg) and compressor displacement (1/s)/(kW cooling) values obtained through calculation for
each refrigerant mixture. Also tabulated are the same values obtained at 10°C superheat
27
Table 6 (continued) A summary of the highest COP and corresponding specific cooling capacity
(kJ/kg) and compressor displacement (Us)/(kW cooling) values obtained through calculation for
each refrigerant mixture. Also tabulated are the same values obtained at 10°C superheat
28
Table 6 (continued) A summary of the highest COP and corresponding specific cooling capacity
(kJ/kg) and compressor displacement (Us)/(kW cooling) values obtained through calculation for
each refrigerant mixture. Also tabulated are the same values obtained at 10°C superheat
29
Table 6 (continued) A summary of the highest COP and corresponding specific cooling capacity
(kJ/kg) and compressor displacement (1/s)/(kW cooling) values obtained through calculation for
each refrigerant mixture. Also tabulated are the same values obtained at 10°C superheat
30
Table 6 (continued) A summary of the highest COP and corresponding specific cooling capacity
(kJ/kg) and compressor displacement (Us)/(kW cooling) values obtained through calculation for
each refrigerant mixture. Also tabulated are the same values obtained at 10°C superheat
31
Table 6 (continued) A summary of the highest COP and corresponding specific cooling capacity
(kJ/kg) and compressor displacement (Us)/(kW cooling) values obtained through calculation for
each refrigerant mixture. Also tabulated are the same values obtained at 10°C superheat
32
Table 6 (continued) A summary of the highest COP and corresponding specific cooling capacity
(kJ/kg) and compressor displacement (1/s)/(kW cooling) values obtained through calculation for
each refrigerant mixture. Also tabulated are the same values obtained at 10°C superheat
33
Table 6 (continued) A summary of the highest COP and corresponding specific cooling capacity
(kJ/kg) and compressor displacement (Us)/(kW cooling) values obtained through calculation for
each refrigerant mixture. Also tabulated are the same values obtained at 10°C superheat
34
Table 6 (continued) A summary of the highest COP and corresponding specific cooling capacity
(kJ/kg) and compressor displacement (1/s)/(kW cooling) values obtained through calculation for
each refrigerant mixture. Also tabulated are the same values obtained at 10°C superheat
35
Table 6 (continued) A summary of the highest COP and corresponding specific cooling capacity
(kJ/kg) and compressor displacement (1/s)/(kW cooling) values obtained through calculation for
each refrigerant mixture. Also tabulated are the same values obtained at 10°C superheat
36
Table 6 (continued) A summary of the highest COP and corresponding specific cooling capacity
(kJ/kg) and compressor displacement (l/s)/(kW cooling) values obtained through calculation for
each refrigerant mixture. Also tabulated are the same values obtained at 10°C superheat
37
Table 6 (continued) A summary of the highest COP and corresponding specific cooling capacity
(kJ/kg) and compressor displacement (1/s)/(kW cooling) values obtained through calculation for
each refrigerant mixture. Also tabulated are the same values obtained at 10°C superheat
38
Table 6 (continued) A summary of the highest COP and corresponding specific cooling capacity
(kJ/kg) and compressor displacement (l/s)/(kW cooling) values obtained through calculation for
each refrigerant mixture. Also tabulated are the same values obtained at 10°C superheat
39
Table 6 (continued) A summary of the highest COP and corresponding specific cooling capacity
(kJ/kg) and compressor displacement (1/s)/(kW cooling) values obtained through calculation for
each refrigerant mixture. Also tabulated are the same values obtained at 10°C superheat
40
Table 6 A summary of the highest COP and corresponding specific cooling capacity (kJ/kg) and
compressor displacement (l/s)/(kW cooling) values obtained through calculation for each
refrigerant mixture. Also tabulated are the same values obtained at 10°C superheat
41
The identification of the maximum COP c values in Table 6 was, however, not as
simple as for pure refrigerants. It was found that certain mixtures have
discontinuities in performance results at certain vapour qualities. In Figure 10,
an example is given of R13b1 with R152a at a concentration of 10%/90%. It can
be concluded that an unexpected peak exists at a vapour quality of 0.6. The
reason for these peaks or dips, which occurred rather frequently, is unclear and
was not investigated in detail. It might be from inaccurate thermodynamic
properties predicted by REFPROP 15 or from inaccurate interaction parameters.
In REFPROP mixture calculations require interaction parameters for each binary
pair of components in the mixture. Values of interaction parameters based on
experimental data are stored within REFPROP for more than 60 binary pairs,
whereas other pairs are calculated using an estimation algorithm.
Reviewing Table 6, it seems from a COP c point of view that for air
conditioning, the following refrigerant mixtures respond consistently favourably
to wet compression: R11/R114, R12/R22, R124/R125, R142b/R143a,
,
Calculated
Trend
Figure 10 Graph showing the discontinuity in the calculation of the COP c values for
R13b1/R152a (0.9/0.1)
42
As with pure refrigerants, the specific cooling capacity decreases and the
compressor displacement increases with the use of wet compression as can be
expected. It was found, however, that for some refrigerant mixtures, for example
R32/R143 (0.3/0.7), the compressor displacement reaches a relative low value at
approximately the same vapour quality where the maximum COP, is reached
(see Figures 11, 12 and 13).. It is interesting to note that this phenomenon occurs
especially in refrigerant mixtures that produce higher COP values with wet
compression. The opposite also seems true: refrigerant mixtures for which the
compressor displacement decreases when it is superheated, do not tend to enjoy
the advantages of wet compression.
0.35 16
0.30 14
12
0.25
10
0.20 --4"-
- yr
8
j." 0.15 - —U—m
0.10 - - 4
-N
0.05 - 2
0.00 0
0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 10SH 20SH
Vapour quality
Figure 11 The compressor displacement and refrigerant circulated per
kilowatt of cooling for R32/R143 (0.3/0.7)
COP
Trend
1 2 3 4 5 6 7 8 9 10
Vapour quality
Figure 12 The COP. values for R32/R143 (0.3/0.7)
43
Figure 13 The specific cooling capacity and specific work for R32/R143 (0.3/0.7)
Table 7 is similar to Table 3 for pure refrigerants, but because of the amount of
refrigerant mixtures analysed, only the top 10 mixtures that gained the most in
COPE using wet compression, are presented. Reviewing Tables 3 and Table 7
together, it can be seen that the non-azeotropic mixtures tend to gain more from
wet compression than the pure refrigerants when considering the coefficient of
performance. The cooling capacities, however, decrease in general. Another
advantage of some of the non-azeotropes, is the fact that the compressor
displacement does not necessarily increase substantially when wet compression
is applied.
Table 7 The top 10 refrigerant mixtures with the highest percentage improvement in COP
obtained by using wet compression over dry compression. Also tabulated are the changes in
COP-, specific cooling capacity- and compressor displacement values relative to the values at
10°C superheated as a percentage
44
Table 7 (continued) The top 10 refrigerant mixtures with the highest percentage
improvement in COP obtained by using wet compression over dry compre§sion. Also tabulated
are the changes in COP-, specific cooling capacity- and compressor displacement values relative
to the values at 10°C superheated as a percentage
Although the COP value increased favourably, the changes in the specific
cooling capacity and the compressor displacement values really lower the newly
generated expectation and excitement that wet compression seems to have
working with this non-azeotrope.
The second highest percentage improvement in COP (Table 7), 11.3%, is found
through the process of wet compression when considering R143/R143a (0.9/0.1)
at a vapour quality of 0.9. A COP, value of 6.59 at a vapour quality of 0.9 is
11.3% higher than the COP, value of 5.92 at 10°C superheat, and 35.1% higher
than the 4.28 of Ammonia (best performing pure refrigerant) at the same vapour
quality. The specific cooling capacity decreased with 15.5%, while the required
compressor displacement rate to acquire 1 kW of cooling increased with only
2.3%. From a specific cooling capacity and compressor displacement point of
view, this refrigerant mixture clearly outperforms the rest of the refrigerant
mixtures in Table 7.
45
It is interesting to note that R22 appears six and R12 five times in Table 7. Of
this 11 times they appear together three times as mixtures (R12/R22). R12's
composition ranges from 20% to 40%. As the composition of R12 increases, so
does the COP, percentage improvement decrease from 9.1% to 7.6%. The
specific cooling capacity and the compressor displacement seem to remain
constant.
Because of the vast amount of refrigerant mixtures analysed, the study produced
an interesting by-product. Quite a few of the mixtures analysed are not
commonly used today. The study therefor provides a look into the behaviour of
some of these less known refrigerant mixtures. One of the interesting
discoveries made is the high COP, values achieved using certain refrigerant
mixtures.
To obtain a holistic view of what all the results generated actually mean, it was
necessary to further investigate the results listed in the appendices as well as in .
Table 6. Up to this point most of the focus was on how the refrigerant mixtures
reacted to the process of wet compression. The question that now needs to be
answered is how the process of wet compression compares to that of dry
compression. It was decided to have a look at the highest performing refrigerant
mixtures from a COP, point of view.
Table 8 lists the top 30 refrigerant mixtures with the highest COP, values,
whether it is obtained by wet or dry compression. This means that Table 8,
which is solely based on the refrigerant mixture's ability to perform, represents
10.8% of the total refrigerant mixtures considered in this study. The refrigerants
are listed in an order of a decreasing COP, value. Apart from the COP, value,
the corresponding specific cooling capacity- and compressor displacement
values are also listed against the relevant vapour quality.
The highest COP, value of 14.75 was calculated for R123/R134a (0.7/0.3) at a vapour
quality of 1.0. The mixture has the highest temperature glide of all the mixtures
considered in Table 8, namely that of 27.29°C. It can be concluded that the high
COP, can be contributed to the low amount of work that needs to be done by the
compressor, seeing that the dew point is set at 50°C.
Table 8 The top 30 refrigerant mixtures with the highest COP, values, whether it is obtained
by using wet or dry compression. Also tabulated are specific cooling capacity- and compressor
displacement values at the relevant vapour quality
47
Table 8 (continued) The top 30 refrigerant mixtures with the highest COP c values, whether
it is obtained by using wet or dry compression. Also tabulated are specific cooling capacity- and
compressor displacement values at the relevant vapour quality
48
Only 10% (3 out of 30) of the highest COP, values listed in Table 8 represent
refrigerant mixtures that respond positively to the process of wet compression.
Thus 90% of all maximum COP, values are achieved for superheating and not
with wet compression.
It is interesting to note that the first seven entries (23%) in Table 8 all have
temperature glides greater than 25°C. Eleven refrigerant mixtures (37%) have
temperature glides that lie between 20°C and 25°C. A further ten refrigerant
mixtures (33%) have temperature glides that lie between 15°C and 20°C. Only
two refrigerant mixtures (7%) have temperature glides that lie between 10°C and
15°C. None of the refrigerant mixtures that prompt the highest COP, (refer to
Table 8) values have temperature glides that lie between 0°C and 10°C.
it is interesting to note that it seems that the following trend exists: The higher
the temperature glide, the higher the COP,. It may be premature to make such a
statement based only on the data listed in Table 8 which represents only 11.8%
of the total refrigerant mixtures considered. Temperature glide is further
investigated in paragraph 3.3.1.
It seems that, from Table 8, the higher the temperature glide, the higher the
COP,. This seems obvious if one is reminded that the evaporator outlet
temperature is then closer to the condenser inlet temperature on the
Temperature-Entropy diagram. This results in less work required from the
compressor.
To prove the theory in the preceding paragraph, all the refrigerant mixtures
considered in this study needs to be taken into account. Table 6 lists the COP,
values, amongst others, obtained at various vapour qualities and superheat
values. To come to-any relevant conclusions on how the COP, and temperature
glide react to each other, any generalisation needs to be based on fact.
49
Considering Table6, the only common COP S value entered for all the refrigerant
mixtures is at 10°C superheat. Thus the only given constant is a compressor
inlet temperature of 10°C superheat, which also forms the base on which any
conclusions are made.
All the COP S values in Table 6 are sorted in a descending order, after which it is
plotted on a graph (refer to Figure 14) as a function of the corresponding
temperature glide.
Reviewing Figure 14 it can be seen that 82% of the refrigerants have COP c
values between 3 and 7. For the same refrigerants the temperature glide lie
between 0°C and 13°C. This means that 82% of all the refrigerants are
concentrated on only 10% of the total area represented by the graph.
The data in Figure 14 is plotted with a standard deviation of 10%. The trendline
is plotted from which Equation (12) is derived. It successfully predicts the COP,
.
as a function of the temperature glide and has an average error of 7%. 52% of
the calculated values of the COP, -by using Equation (12)- has a COP, error •
smaller than 5%. 31% of the refrigerant mixtures have errors between 6% and
10%. Twenty-five refrigerant mixtures (10%) have errors between 11% and 15%.
The remaining 7% refrigerant mixtures have errors higher than 15%.
The second issue is that of grouping the refrigerant mixtures into three different
temperature glide categories in order to make relevant conclusions. The majority
of the refrigerants fall into a category similar to the one in Figure 15. This is
the temperature glide for R13b1/R152a, and reviewing this, it can be seen that
for small quantities (10-20%) of a specific refrigerant in the mixture, it almost
behaves like an azeotrope and the glide is small. For mixtures where the mixing
ratio is in the region of 40%:60% to 50%:50%, the temperature glide reaches a
maximum.
The third category is for the temperature glide distribution like R22/R218 as
shown in Figure 17. This distribution has a bathtub shape with the minimum
glide where the mass ratio of the binary mixture is 40%:60%. It therefor
becomes a near-azeotrope.
The refrigerant mixtures analysed were divided into three groups, according to
the amount of temperature glide during the evaporation process. Table 9
represents the top 30 refrigerant mixtures, based on maximum COP c , for a low
temperature glide (0-5°C), a medium temperature glide (5-10°C) and a high
temperature glide (>10°C).
52
Table 9 (continued) The top 30 list for the highest COP for each of the three
levels of temperature glides. The first value in each block is the COP S (with the
relevant inlet vapour quality), the second is the specific cooling capacity (kJ/kg)
and the third is the compressor displacement per kilowatt cooling (litre/s).
54
It can be seen from Table 9 that the highest COP, (5.96(20SH)) obtained with a
low temperature glide is for R218/RC318 (0.9/0.1). R11/R114 represents 30% of
Table 9, which means that 100% of the studies conducted on R11/R114 resulted
in being tabulated in Table 9 amongst the top 30 with low temperature glides.
R12/R152a, R134a/R143 and R22/R152a all represent 10% of the entries in
Table 9.
R143/R143a (0.9/0.1) topped the chart for the medium temperature glide (5°C-
10°C) with a COP, of 6.588(0.9). R22/R142b represents 17% of the top 30 •
entries, while R134a/R143 represents 13%.
Only 27% of the COP, entries in the low and medium temperature glide
categories are as a result of the process of wet compression. Only 10% of the
COP, entries in the high temperature glide category are as a result of the
process of wet compression. Dry compression dominates the chart as is
expected. Although the COP, values in Table 9 are not as spectacular as in
Table 8, they are a great improvement on the values for pure refrigerants.
In some cases, when wet compression takes place at inlet qualities of 0.9, it is
not uncommon for the refrigerant to discharge at temperatures higher than the
dew point temperature. Even then it was found that the discharge temperature is
still much lower than the discharge temperature had dry compression been used.
It can therefor be concluded that wet compression leads to a decrease in the
discharge temperature for the few refrigerants that favour wet compression.
3.3.4 CONCLUSIONS
All the refrigerant mixtures with a re-entrant saturation vapour line on the T-s
curve produce better COP c values when the refrigerant is superheated before
entering the compressor. From the group of refrigerant mixtures with bell-
shaped T-s curves, quite a few were identified that produce better COP S values
through the process of wet compression. From Table 6, it seems that especially
R11/R114, R32/R142b, R32/R142b and R32/R143 perform better under wet
compression conditions. The use of wet compression unfortunately also results
in a drop in cooling capacity and in some cases, an increase in the compressor
displacement. It was also found that many non-azeotropic refrigerant mixtures
produce higher COP S values than pure refrigerants.
56
Two criteria are instrumental in determining the impact a certain refrigerant has
on the environment, namely its ozone depletion potential (ODP) and its global
warming potential (GWP). Cavallini" identified a possible working region for
refrigerants after the phase-out of CFC's. This working region includes
refrigerants with an ODP of less than 0.1 (with R11 given a value of one as the
norm) and a GWP of less than 4000 (with reference to CO2, with an Integration
Time Horizon of 100 years). With the phase-out of HCFC's, this window will
shrink to a single line, which will only include refrigerants with zero ODP,
while the GWP will be limited, given the current global warming issue.
Table 11 The highest COP, values for each of the three levels of temperature
glides, considering only temporarily acceptable refrigerant mixtures. The first
value in each block is the COP, (with the relevant inlet vapour quality in
brackets), the second is the specific cooling capacity (kJ/kg) and the third is the
compressor displacement per kilowatt cooling (litre/s)
It can be seen that Table 11 only has seven entries. The reason for this is that
out of the 30 entries in Table 9, only 7 entries are temporarily acceptable from
an environmental perspective, considering low and high temperature glides.
From Table 11, it seems that for respectively low and medium temperature glide
mixtures, R22/R134a (0.7/0.3) and R22/R142b (0.3/0.7) provide medium term
solutions. Obviously R22/R142b is chosen above R22/R134a seeing that its COP
is 24% and its specific cooling capacity 58% higher than the same values of
R22/12.134a. Unfortunately, though, the required compressor displacement rate
increased by 25%.
Comparing high with medium temperature glide, the COP, value of 14.07
recorded for R123/R134a (0.6/0.4) is more than double . than the COP, of
R22/R142b. Unfortunately, for R123/R134a, the required compressor
displacement rate is 20% higher, and the specific cooling capacity 2% lower.
58
Table 12 The highest COP, values for each of the three levels of temperature
glides, considering only acceptable refrigerant mixtures. The first value in each
block is the COP, (with the relevant inlet vapour quality in brackets), the
second is the specific cooling capacity (kJ/kg) and the third is the compressor
displacement per kilowatt cooling (litre/s)
From Table 12, it seems that concentrations of R290/R600 possess the best
combination of the thermodynamic characteristics. It provides both a high COP,
as well as a high specific cooling capacity. Unfortunately this mixture carries a
high risk of flammability (see later the paragraph on flammability and toxicity).
(0.4/0.6) has the lowest compressor displacement per kilowatt cooling in the
medium temperature glide category.
In the discussion of the impact refrigerants have on the environment, R123 has
been identified as a temporarily acceptable refrigerant. This is because R123 is
a HCFC that is, under the Montreal Protocol, scheduled-for phase-out with the
rest of the HCFC's currently in use. R123, unlike the majority of HCFC's has
both a low GWP (Global Warming Potential) and ODP (Ozone Depletion
Potential). R123 has an atmospheric lifetime of 1.4 years, which gives a virtual
guarantee that no R123 would possibly enter the stratosphere. Also, it has been
shown 2° that under certain conditions, the use of R123 has a negligible impact
on the ozone layer. This has led to some controversy in the US air-conditioning
industry over the Protocol grouping of all HCFC's under one blanket. This, and
the fact that R123 is regarded in some circles as still the best alternative for
R112, may put some pressure on authorities to rethink the phase-out of R123.
Should this happen, R123 will remain an important role player in the heating,
ventilation and air-conditioning industry in future.
toxicity and the "B" higher toxicity. These designations are applied with the
numbers of flammability to complete the safety classification. For example: R22
is classified Al, no flame propagation, lower toxicity; NH 3 (R717) is classified
B2, low flammability, higher toxicity.
For refrigerant mixtures, the classification is rather more complex. For example,
the mixture might have one classification as it is purchased, but should the
components separate, this classification can change. For this reason the
refrigerants in Tables 10 to 12 were classified according to the original
components. From the refrigerant components in these tables the majority was
classified Al and A2. The only exceptions were R123 (B1), R290 (A3) and R600
(A3). For this reason, note should be taken of the hazards presented by mixtures
of R123/R134a and R290/R600, as identified in Tables 10 to 12.
61
CHAPTER FOUR
62
The purpose of this study was to determine the effect of wet compression on the
performance of a wide variety of pure refrigerants and refrigerant mixtures. A
total of 34 pure refrigerants and 31 binary refrigerants were analysed. The
binary refrigerant mixtures were analysed at mass ratio intervals of 10%, which
brought the total number of mixtures analysed at almost 300. To determine the
effect of wet compression on these refrigerants, the cooling coefficient of
performance, specific work done by the compressor, specific cooling capacity,
refrigerant circulated and the compressor displacement rate were calculated at
different inlet qualities. These qualities ranged from a vapour quality of 0.3 to
one at 0.1 intervals, and for 10°C and 20°C superheat.
4.2 CONCLUSIONS
After analysing the 34 pure refrigerants it was concluded that all of them can be
divided into two distinctive groups, depending on the shape of their temperature
entropy curves. Two common shapes were identified: a bell shape and a re-
entrant curve. From the 34 pure refrigerants analysed, all those with re-entrant
saturated vapour lines produce better COP,'s when the refrigerant is superheated
before entering the compressor. Only two of the refrigerants (R32 and NH3) with
bell-shaped T-s curves, consistently produce higher COP c 's when wet
compression is used. It can therefore be concluded that in general it has been
found that wet compression is not attractive when pure refrigerants are used.
It was also found that the temperature glide of each refrigerant mixture plays, an
important role in how it will perform. It was possible to define an accurate
approximation of the COP, as a function of the temperature glide for all the
refrigerant mixtures considered. The approximation has an average error of 7%.
The refrigerant mixtures were grouped into three different temperature glide
categories, depending on its type of temperature glide distribution. The highest
COP, obtained with a low temperature glide was for R218/RC318 (0.9/0.1).
R143/R143a (0.9/0.1) topped the chart for the medium temperature glide whilst
R123/R134a (0.6/0.4) out performed the rest in the high temperature glide
category. Although the COP, values were not so spectacular, they are a great
improvement on the values for pure refrigerants.
The impact of the refrigerants on the environment was also taken into account.
Three types of refrigerants were identified: phased-out refrigerants, refrigerants
that are temporarily acceptable and acceptable refrigerants. With the phased-out
refrigerants ignored, the temporarily acceptable mixtures with the best
combination of high COP, and cooling capacity were R22/R134a (0.7/0.3) for
low, R22/R142b (0.3/0.7) for medium and R123/R134a (0.6/0.4) for high
temperature glide categories. R22/R134a was compressed at a vapour quality of
0.9, R22/R142b at 20SH and R123/R134a at 10SH.
64
The top performing refrigerant mixtures were also evaluated for flammability
and toxicity using the ASHRAE 34-1992 Standard. Only mixtures of
R123/R134a and R290/R600 were identified as exceptional hazards regarding
flammability and toxicity.
A final look at the top performing refrigerant mixtures revealed that only 27%
of the refrigerant mixtures in the low and medium temperature glide categories
prefer the process of wet compression. Only 10% of the refrigerant mixtures in
the high temperature glide category prefer the process of wet compression.
Non-azeotropic mixtures tend to gain more from wet compression than pure
refrigerants when considering the COP c values. Unfortunately, though, the
cooling capacities decrease in general. Another advantage of some of the non-
azeotropes is that the compressor displacement does not necessarily increase
substantially when wet compression is applied.
4.3 RECOMMENDATION
REFERENCES
66
Rowland, F.S. Stratospheric ozone depletion: identifying the problem and the solution,
ASHRAE Journal, (September 1997), pp. 29-31
Cavallini, A. Working fluids for mechanical refrigeration, International Journal of
Refrigeration; (1996) 19(8), 485-496
Lorentzen, G. The use of natural refrigerants: a complete solution to the CFC/HCFC
predicament, International Journal of Refrigeration, (1995) 18(3), 190 197
-
Linton, J.W., Snelson, W.K., Hearty, P.F., Triebe, A.R. System performance of near
azeotropic mixtures of R-134a and R-152a , ASHRAE Technical Data Bulletin, (1993) 9(4), 55-
60
Radermacher, R., Jung, D. Theoretical analysis of replacement refrigerants for residential
uses, ASHRAE Technical Data Bulletin (1993) 9(4), 1 11
-
Stoecker, W.F., Jones, J.W. Refrigeration and Air Conditioning, McGraw Hill, 3rd ed.
-
(1982) 193-195
Itard, L.C.M. Wet compression versus dry compression in heat pumps working with pure
refrigerants or non-azeotropic mixtures, International Journal of Refrigeration (1995) 18(7) 495,
504
MST REFPROP Standard Reference Database 23. MST Thermodynamic properties of
refrigerants and refrigerant mixtures Version 4.0, Thermophysics Division, National Institute of
Standards and Technology, (November 1993) Gaithersburg, MD 20899
Kruse, H., Kuever, M., Guast, U., Schroeder, M., Upmeier, B. Theoretical and
Experimental Investigations of Advantageous Refrigerant Mixture Applications, ASHRAE
Technical Data Bullitin (1985), 96 131
-
Nagel, M., Bier, K. Vapour-liquid equilibrium of ternary mixtures of the refrigerants R32,
R125, and R134a, International Journal of Refrigeration, (1995), 18(8), 534 543
-
Cavallini, A. CFC and HCFC substitution — short-and long-term solutions, IIR Bulletin,
(1994), 94(6), 2-15
Calm, J.M., Didion, D.A. Trade-offs in refrigerant selections: past, present and future
Refrigerants for the 21st Century (1997), 6-19
67
Sanvordenker, K.S. Status of CFC and HCFC alternatives Refrigerants for the 21st Century
(1997), 111-116rade-offs in refrigerant selections: past, present and future
ASHRAE Standard 34-1992 Number Designation and Safety Classification of Refrigerants,
American Society of Heating, Refrigeration and Air-Conditioning Engineers, Inc., Atlanta, GA,
USA (1992), 1-9