PLC Based Industrial Automation System
_______________________________________________________________________

PLC Based Industrial Automation System

Gavali Amit Bhimrao, Patil Mahadev S.


Department of Electronics and Telecommunication
Rajarambapu Institute of Technology Rajaramnagar, Islampur, Sangli, India
Email: amitgavali9011@gmail.com, mahadev.patil@ritindia.edu

Abstract - This paper describes how the present I (a) RELAY SYSTEM:
automation system comes in to existence through its
various stages. In the past, automation is done through The relay, which operates much like a solenoid, is an
relays and contactor logics. Since the human intervention is
electromagnetic device that consists of a coil with a soft
more, the scope of errors was also more. But with the
advent of microprocessors & microcontrollers several new
iron core and electric contacts mounted on, but insulated
tools as PLCs (Programmable Logic controllers) come in to from, the moving armature or plunger. The relay allows
use. These have reduced human intervention. Which in one circuit to control another.
turn has increased accuracy, precision and efficiency.

Keywords Automation, PLC, PLC based Control Panel

I. INTRODUCTION

Automation, a Greek word means self dedicated.


Automation is the key to modernization and has been
conceptually understood as a way to increase efficiently
and to improve productivity. The process of having
machine follow a predetermined sequence of operation Figure 2: Relay mechanism
with little or no human labor, using special equipment
and devices that perform and control manufacturing Relay Operation: When current is supplied to the coil, the
processes is known as automation. The goals of resulting magnetic field pulls the armature and the
automation are Integration of various aspects of contacts toward the coil. The relay is in energized
manufacturing operations to reduce labor cost. The position when the armature is fully seated. Contacts that
fundamental constituents of any automated process are were open are now closed. These contacts are referred to
(1) a power source, (2) a feedback control mechanism, as the normally open (NO) contacts. Contacts that were
and (3) a programmable command as shown in figure 1. closed are now open. These contacts are called the
normally closed (NC) contacts. Therefore, the terms

condition of the contacts when the relay coil is de-


energized. A relay may have one or both types of
contacts and may also have multiple sets of contacts for
controlling several circuits at once. When the coil circuit
is opened, current cannot flow in the coil, the magnetic
field collapses, and the relay de-energizes. A spring
attached to the armature returns the contacts to their
Figure 1: Fundamental constituents automated process normal positions.

Automation tools: Relays comes in different configurations are SPST


(Single Pole Single Throw) is the simplest only two
I. Relays and contactor logic contacts, SPDT (Single Pole Double Throw) has three
contacts. The contacts are usually labled common,
II. Programming logic controllers (PLC) normally open & normally closed. The normally closed

_______________________________________________________________________
International Conference On Recent Trends In Engineering And Management Science - RTEM
ISBN: 978-3-642-24819-9, 20th April 2014, Nagpur
19
PLC Based Industrial Automation System
_______________________________________________________________________
contact will be connected to the common contact when system provides the driving force to close the contacts.
no power is applied to the coil. The normally open The enclosure system is a frame housing the contact and
contact will be open (i.e. not connected) when no power the electromagnet. Enclosures are made of insulating
is applied to the coil. When the coil is energized the materials like Bakelite, Nylon 6, and thermosetting
common is connected to the normally open contact and plastics to protect and insulate the contacts and to
the normally closed contact is left floating. The double provide some measure of protection against personnel
pole version are the same as the single pole version touching the contacts. Open-frame contactors may have
except there are two switches that open and close a further enclosure to protect against dust, oil, explosion
together. Select a relay with contact that can handle the hazards and weather. The major disadvantage of relays
voltage and current requirements of the load. Keep in and controller logic is that it does not have any
mind that some loads (such as motor) draw more current redundant system it means that if system fails then, it
when first turned on than they do not at steady state. does not have any controlling system to continue its
controlling and monitoring process. So if system fails
Relay Application: The relay can be used to open and then we have to rectify the control system so that
close high-voltage or high-current circuits with relatively controlling & monitoring could be restarted.
little voltage and current in the coil circuit. The
controlling circuit is electrically isolated from the II PROGRAMMING LOGIC CONTROLLER:
controlled circuit. In other words, current from the
controlling circuit does not flow in the controlled circuit. A digitally operating electronic apparatus which uses a
The link between the two circuits is strictly magnetic. programmable memory for the internal storage of
The relay is also useful for remote be located at one point instructions by implementing specific functions such as
and other circuit components located some distance logic sequencing, timing, counting, and arithmetic to
away. Because the controlling circuit is usually operated control, through digital or analog input/output modules.
by a low-current power source, relatively small gage
wires can be used to connect the remote switch device. A Programmable Logic Controller or Programmable
Controller is a digital computer used for automation of
Relay Ratings: The electrical contacts are rated for the electromechanical processes, such as control of
voltage and current that they can safely switch. The relay machinery on factory assembly. PLCs are used in many
is also rated for the voltage and current required to industries and machines. Unlike general- purpose
properly energize the coil. If a time delay is desired, thus computers, the PLC is designed for multiple inputs and
value must also be specified. The value of these ratings output arrangements, extended temperature ranges,
will depend on how the relay is used in the system. immunity to electrical noise, and resistance to vibration
and impact. Programs to control machine operation are
Disadvantages of Relay System: The maintenance cost typically stored in battery-backed-up or non-volatile
of the relay system is quite high, as the frequent memory. A PLC is an example of a hard real time
maintenance is required in it. A driver circuit is required system since output results must be produced in
along with larger relays. Very high human intervention response to input conditions within a limited time.
is required in this system. They do not allow manual
adjustment of the relay state when the control power is
off. These are only use for ON/OFF control.
Intermediate controlling is not possible by the relays.
They increased electrical noise when conducting.

I (b) CONTACTOR LOGIC:

A contactor is an electrically controlled switch (relay)


used for switching a power circuit. A contactor is
activated by a control input which is a lower voltage /
current than that which the contactor is switching.
Contactors come in many forms with varying capacities Figure 3: Block diagram of PLC
and features. Unlike a circuit breaker a contractor is not
intended to interrupt a short circuit current. PLC has 4 main units: 1) Programmable Memory- The
instruction for logical control sequence is stored here. 2)
Basic Features of Contactor Logic are as follows: A Data Memory- The status of the switches interlocks, past
contactor is composed of three different systems. The values of data and other working data is stored here. 3)
contact system is the current carrying part of the O/P Devices- These are hardware or software drives for
contactor. This includes Power Contacts, Auxiliary industrial process actuators, such as solenoid, switches,
Contacts, and Contact Springs. The electromagnet motor and valves. 4) I/P Devices- These are hardware or
software driver for industrial process sensors such as
_______________________________________________________________________
International Conference On Recent Trends In Engineering And Management Science - RTEM
ISBN: 978-3-642-24819-9, 20th April 2014, Nagpur
20
PLC Based Industrial Automation System
_______________________________________________________________________
switch status sensors, proximity detectors interlock program, the number of I/Os, and the amount of
setting. communication required.

Working principal of PLC: Inputs Modules: Inputs come


from sensors that physically translate into electrical
signals. The simplest form of inputs are digital. In
smaller PLCs the inputs are normally built in and are
specified when purchasing the PLC. For larger PLCs the
inputs are purchased as modules, or cards, with 8, 16,
32, 64, 96 inputs of the same type on each card.

Figure 6: Scan cycle of PLC

A PLC resolves the logic of a ladder diagram (program)


rung by rung, from the top to the bottom. Usually, all the
outputs are updated based on the status of the internal
registers. Then the input states are checked and the
corresponding input registers are updated. This process
is run in a endless cycle. The time it takes to finish one
cycle is called the scan time. In some controllers the idle
state is eliminated. In this case, the scan time varies
depends on the program length.Scan cycle depends upon
Figure 4: Example of input card number of I/Os. More I/Os more scan time. Application
decides the scan time of a PLC. Scan time in normal
Outputs Modules: Output modules rarely supply any applications is 1 ms to 2 ms & in bigger applications 100
power, but instead act as switches. External power ms to 200 ms
supplies are connected to the output card and the card
will switch the power on or off for each output. A Advantages of using PLC llows: Cost
common choice when purchasing output cards is relay effective for controlling complex systems. Flexible and
transistors or triacs. Relays are the most flexible output can be reapplied to control other systems quickly and
devices. They are capable of switching both AC and DC easily. Computational abilities allow more sophisticated
outputs. But, they are slower, cost more, and they will control. Trouble shooting aids make programming easier
wear out after millions of cycles. The most important and reduce downtime. Reliable components make these
consideration when selecting relays, or relay outputs on likely to operate for years before failure.
a PLC, is the rated current and voltage
III. SWITCHED MODE POWER SUPPLY
A switched-mode power supply is an electronic power
supply that incorporates a switching regulator to convert
electrical power efficiently. Like other power supplies,
an SMPS transfers power from a source, like mains
power, to a load, such as a personal computer, while
converting voltage and current characteristics. An SMPS
is usually employed to efficiently provide a regulated
output voltage, typically at a level different from the
input voltage. (Figure7. Shows DELTA SMPS supply
Figure 5: Example of output card 230 VDC, 5A)

Scanning Principle of PLC: The PLC program is


executed as part of a repetitive process referred to as a
scan. A PLC scan starts with the CPU reading the status
of inputs. The application program is executed using the
status of the inputs. Once the program is completed, the
CPU performs internal diagnostics and communication
tasks. The scan cycle ends by updating the outputs, then
starts over. The cycle time depends on the size of the
Figure 7: Switched Mode Power Supply
_______________________________________________________________________
International Conference On Recent Trends In Engineering And Management Science - RTEM
ISBN: 978-3-642-24819-9, 20th April 2014, Nagpur
21
PLC Based Industrial Automation System
_______________________________________________________________________

IV. MINIATURE CIRCUIT BREAKER used. Relays are used where it is necessary to control a
circuit by a low-power signal (with complete electrical
A circuit breaker is an automatically operated electrical isolation between control and controlled circuits), or
switch designed to protect an electrical circuit from where several circuits must be controlled by one signal.
damage caused by overload or short circuit. Its basic Relays were used extensively in telephone exchanges
function is to detect a fault condition and interrupt and early computers to perform logical operations. A
current flow. Unlike a fuse, which operates once and type of relay that can handle the high power required to
then must be replaced, a circuit breaker can be reset directly control an electric motor or other loads is called
(either manually or automatically) to resume normal a contractor. Solid-state relays control power circuits
operation. Circuit breakers are made in varying sizes, with no moving parts, instead using a semiconductor
from small devices that protect an individual household device to perform switching. Relays with calibrated
appliance.(Figure.8 shows SEIMENS MCB 2P C4A, 1P operating characteristics and sometimes multiple
C2A) operating coils are used to protect electrical circuits from
overload or faults; in modern electric power systems
these functions are performed by digital instruments still
called "protective relays". (Figure. 9 shows CONNECT
WELL 8 channel, 5A, coil-24VDC)
VI. SOFTWARE FOR PLC
CoDeSys V2.3: CoDeSys is a complete development
environment for Nexgenie messung PLC. CoDeSys
stands for Controlled Development System. CoDeSys
puts a simple approach to the powerful IEC language at
the disposal of the PLC programmer. Use of the editors
and debugging functions is based upon the proven
Figure 8: Miniature Circuit Breaker development program environments of advanced
All circuit breakers have common features in their programming languages. POU (Program Organization
operation, although details vary substantially depending Unit) Functions, function blocks, and programs are
on the voltage class, current rating and type of the circuit POUs which can be supplemented by actions. Each POU
breaker. The circuit breaker must detect a fault consists of a declaration part and a body. The body is
condition, in low-voltage circuit breakers this is usually written in one of the IEC programming languages which
done within the breaker enclosure. Circuit breakers for include IL, ST, SFC, FBD, LD or CFC. CoDeSys
large currents or high voltages are usually arranged with supports all IEC standard POUs. POU can call up other
pilot devices to sense a fault current and to operate the POUs. However, recursions are not allowed. Function A
trip opening mechanism. Once a fault is detected, function is a POU, which yields exactly one data
contacts within the circuit breaker must open to interrupt element (which can consist of several elements, such as
the circuit, some mechanically-stored energy ( such as fields or structures) when it is processed, and whose call
springs) contained within the breaker is used to separate in textual language can occur as an operator in
the contacts, although some of the energy required may expressions.
be obtained from the fault current itself. Small circuit
breakers may be manually operated.

V. RELAY BOARD

Figure 9: Relay board


A relay is an electrically operated switch. Many relays
use an electromagnet to operate a switching mechanism
mechanically, but other operating principles are also
_______________________________________________________________________
International Conference On Recent Trends In Engineering And Management Science - RTEM
ISBN: 978-3-642-24819-9, 20th April 2014, Nagpur
22
PLC Based Industrial Automation System
_______________________________________________________________________
Third, we wrote ladder diagram for a program by
sequence of operations that was determined in the first
step. Finally, program uploaded into the PLC controller
memory. When finished with programming, checkup is
done for any existing errors in a program code (using
functions for diagnostics) and, if possible, an entire
operation is simulated. Before this system is started, we
need to check once again whether all input and output
instruments are connected to correct inputs or outputs.
By bringing supply in, system starts working.

Figure 10: Example of Ladder diagram Advantages of control panel that is based on a PLC
controller can be presented in few basic points:
Compared to conventional process control system,
VII. ELECTRICAL CONTROL PANEL number of wires needed for connections is reduced.
Consumption is greatly reduced because a PLC
In an automated system, a PLC controller is usually the consumes less than a bunch of relays. Diagnostic
central part of a process control system. With the functions of a PLC controller allow for fast and easy
execution of a program stored in program memory, PLC error detection. Change in operating sequence or
continuously monitors status of the system through application of a PLC controller to a different operating
signals from input devices. Based on the logic process can easily be accomplished by replacing a
implemented in the program, PLC determines which program through a console or using a PC software (not
actions need to be executed with output instruments. requiring changes in wiring, unless addition of some
Most disadvantages of a classic control panel are too input or output device is required). It is cheaper
much work required in connecting wire, Difficulty with compared to a conventional system, especially in cases
changes or replacements, Difficulty in finding errors; where a large number of I/O instruments are needed and
requiring skillful work force, When a problem occurs, when operational functions are complex Reliability of a
hold-up time is indefinite, usually long. PLC is greater than that of an electro-mechanical relay
or a timer (shown in figure 12)

Material which is required for making PLC based


control panel for PLC based fully automatic hydraulic
press machine shown in figure 12. Specifications of PLC
used are: Nexgenie NG16DL, Input power: 24VDC,
2.4W. Expansions: 4 maximum, Program software: IEC
61131-3 compatible programming software CoDeSys,
Programming languages: Ladder language, Expansions
modules (NE08IX): Nexgenie PLC expansion 8 i/p,
24VDC, Seimens MCB 2P C4A, MCB 1P C2A, MCB
2P C16A, Seimens 9A Contactor, Delta SMPS supply
Figure 11: Example of conventional control panel 230AC, output 24VDC 5A, Connect Well 8 ch. coil-
(Contactor logic control panel) 24VDC, connecting strips, 16 pin, 10 pin 16A male-
female socket.
Systematic approach in designing a process control
system: First, we need to select an instrument or a
system that we wish to control. Function of a process
control system is constantly watched by input devices
(sensors) that give signals to a PLC controller. In
response to this, PLC controller sends a signal to
external output devices (operative instruments) that
actually control how system functions in an assigned
manner.

Secondly, we need to specified all input and output


instruments that will be connected to a PLC controller.
Input devices are various switches, sensors and such.
Output devices are solenoids, motors, relays as well as
instruments for sound and light signalization. Figure 12: PLC based electrical control panel
_______________________________________________________________________
International Conference On Recent Trends In Engineering And Management Science - RTEM
ISBN: 978-3-642-24819-9, 20th April 2014, Nagpur