Modbus Register Mapping

Control

PS0500
PC500/PC550
PCC 1301
PowerCommand 1.1
PowerCommand 1.2
PowerCommand 2.2
PowerCommand 2.3
PowerCommand 3.3
DMC 1000
DMC 1500
MCM 3320
AUX101/102

English
Original Instructions 10-2015 A029X159 (Issue 14)
Table of Contents
1. IMPORTANT SAFETY INSTRUCTIONS ....................................................................................... 1
1.1 Warning, Caution, and Note Styles Used in This Manual ...................................................... 1
1.2 Fuel and Fumes Are Flammable ............................................................................................ 1
1.2.1 Gaseous Fuels ............................................................................................................. 2
1.2.2 Exhaust Gases Are Deadly.......................................................................................... 2
1.3 Moving Parts Can Cause Severe Personal Injury or Death ................................................... 2
1.4 Do Not Operate in Flammable and Explosive Environments ................................................. 3
1.5 Electrical Shock Can Cause Severe Personal Injury Or Death.............................................. 3
1.5.1 Medium Voltage Equipment (601 V to 15 kV) ............................................................. 3
1.6 General Safety Precautions.................................................................................................... 4
1.7 Decommissioning and Disassembly ....................................................................................... 6

2. INTRODUCTION............................................................................................................................ 7
2.1 CPG Controllers...................................................................................................................... 7
2.2 Bit Mapping ............................................................................................................................. 7

3. PCC 1301/POWERCOMMAND 1.X/PS0500 MODBUS REGISTER MAP.................................... 9

4. POWERCOMMAND 2.X/3.X MODBUS REGISTER MAP........................................................... 43


4.1 Modbus Communications ..................................................................................................... 43
4.2 Parametrics (Analog Values) ................................................................................................ 43

5. POWERCOMMAND 2.X/3.X MODBUS FAULT STATUS BITMAPS ........................................ 337

6. NFPA 110 AND EXTENDED ANNUNCIATION BITMAP .......................................................... 379

7. DMC 1000 MODBUS PARAMETRIC DATA .............................................................................. 383

8. DMC 1000 MODBUS ENUMERATED DATA ............................................................................ 411

9. DMC 1000 MODBUS BITMAP DATA ........................................................................................ 431

10. DMC 1500 COMMUNICATION SERVER 1 ............................................................................. 435


10.1 Modbus Address: 2 (Slave) .............................................................................................. 435
10.2 Generator Set Bus Data ................................................................................................... 438
10.3 Utility Bus Data ................................................................................................................. 439
10.4 ATS 1-5 DATA .................................................................................................................. 441
10.5 Word Data......................................................................................................................... 442
10.6 ATS 6-10 DATA ................................................................................................................ 443

11. DMC 1500 COMMUNICATION SERVER 2 ............................................................................. 447


11.1 Modbus Address: 1 (Slave) .............................................................................................. 447
11.2 Generator Raw Data Gen 1-5........................................................................................... 451
11.3 Word Data......................................................................................................................... 452
11.4 Generator Raw Data Gen 6-8........................................................................................... 454

A029X159 (Issue 14) i


Table of Contents 10-2015

12. MCM3320 MODBUS REGISTER MAP .................................................................................... 457


12.1 Modbus Communications ................................................................................................. 457
12.2 Reference Documents ...................................................................................................... 457
12.3 Serial Port Configuration................................................................................................... 457
12.4 Device Addresses ............................................................................................................. 457
12.5 Power-Up Time ................................................................................................................. 457
12.6 Response Time................................................................................................................. 457
12.7 Data Formatting ................................................................................................................ 457
12.8 Modbus Activity LED......................................................................................................... 458
12.9 Supported Functions......................................................................................................... 458
12.10 Holding Register Function............................................................................................... 458
12.11 Preset Single/Preset Multiple Registers Function........................................................... 458
12.12 Diagnostic Counters........................................................................................................ 459
12.13 Register Maps................................................................................................................. 459
12.14 Application Layer ............................................................................................................ 459
12.15 Read Hold Registers....................................................................................................... 459
12.16 Set Single Register ......................................................................................................... 460
12.17 Modbus Loopback........................................................................................................... 460
12.18 Set Multiple Registers ..................................................................................................... 460
12.19 Modbus Register Table................................................................................................... 460

13. MCM3320 MODBUS FAULT STATUS BITMAPS.................................................................... 543

14. MCM3320 MODBUS ADDRESS 42506, 42507....................................................................... 545

15. PC500/550 MODBUS TCP REGISTER MAP .......................................................................... 547

16. AUX101/102 MODBUS REGISTER MAP ................................................................................ 555

ii A029X159 (Issue 14)


1 Important Safety Instructions
SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be
followed during installation and maintenance of the generator set and batteries.
Before operating the generator set, read the Operator's Manual and become familiar with it
and the equipment. Safe and efficient operation can be achieved only if the equipment is
properly operated and maintained. Many accidents are caused by failure to follow
fundamental rules and precautions.

1.1 Warning, Caution, and Note Styles Used in This


Manual
The following safety styles and symbols found throughout this manual indicate potentially
hazardous conditions to the operator, service personnel, or equipment.

DANGER
Indicates a hazardous situation that, if not avoided, will result in death or serious injury.

WARNING
Indicates a hazardous situation that, if not avoided, could result in death or serious
injury.

CAUTION
Indicates a hazardous situation that, if not avoided, could result in minor or moderate injury.

NOTICE
Indicates information considered important, but not hazard-related (e.g., messages relating to
property damage).

1.2 Fuel and Fumes Are Flammable


Fire, explosion, and personal injury or death can result from improper practices.
• DO NOT fill fuel tanks while the engine is running unless the tanks are outside the engine
compartment. Fuel contact with hot engine or exhaust is a potential fire hazard.
• DO NOT permit any flame, cigarette, pilot light, spark, arcing equipment, or other ignition
source near the generator set or fuel tank.
• Fuel lines must be adequately secured and free of leaks. Fuel connection at the engine
should be made with an approved flexible line. Do not use copper piping on flexible lines
as copper will become brittle if continuously vibrated or repeatedly bent. Do not use zinc
coated fuel lines with diesel fuel.
• Make sure all fuel supplies have a positive shutoff valve.

A029X159 (Issue 14) 1


1. Important Safety Instructions 10-2015

• Make sure the battery area has been well-ventilated prior to servicing near it. Lead-acid
batteries emit a highly explosive hydrogen gas that can be ignited by arcing, sparking,
smoking, etc.

1.2.1 Gaseous Fuels


Natural gas is lighter than air, and will tend to gather under covered areas. Propane is heavier
than air, and will tend to gather in sumps or low areas. NFPA code requires all persons handling
propane to be trained and qualified.

1.2.2 Exhaust Gases Are Deadly


• Provide an adequate exhaust system to properly expel discharged gases away from
enclosed or sheltered areas, and areas where individuals are likely to congregate. Visually
and audibly inspect the exhaust system daily for leaks per the maintenance schedule.
Make sure that exhaust manifolds are secured and not warped. Do not use exhaust gases
to heat a compartment.
• The exhaust vent should be high enough to help clear gases, avoid accumulation of snow,
and in accordance with all local mechanical codes.
• Make sure the unit is well ventilated.
• Engine exhaust and some of its constituents are known to the state of California to cause
cancer, birth defects, and other reproductive harm.

1.3 Moving Parts Can Cause Severe Personal Injury or


Death
• Keep hands, clothing, and jewelry away from moving parts.
• Before starting work on the generator set, disconnect the battery charger from its AC
source, then disconnect the starting batteries using an insulated wrench, negative (–) cable
first. In lean-burn natural gas (LBNG) generator sets, also make sure the starter's air
supply line is disconnected or completely vented until the generator set is ready to start.
This will prevent accidental starting.
• Make sure that fasteners on the generator set are secure. Tighten supports and clamps;
keep guards in position over fans, drive belts, etc.
• Do not wear loose clothing or jewelry in the vicinity of moving parts or while working on
electrical equipment. Loose clothing and jewelry can become caught in moving parts.
• If any adjustments must be made while the unit is running, use extreme caution around hot
manifolds, moving parts, etc.

2 A029X159 (Issue 14)


10-2015 1. Important Safety Instructions

1.4 Do Not Operate in Flammable and Explosive


Environments
Flammable vapor can cause an engine to over speed and become difficult to stop, resulting in
possible fire, explosion, severe personal injury, and death. Do not operate a generator set
where a flammable vapor environment can be created, unless the generator set is equipped
with an automatic safety device to block the air intake and stop the engine. The owners and
operators of the generator set are solely responsible for operating the generator set safely.
Contact your authorized Cummins Power Generation distributor for more information.

1.5 Electrical Shock Can Cause Severe Personal Injury


Or Death
• Remove electric power before removing protective shields or touching electrical
equipment. Use rubber insulated mats placed on dry wood platforms over floors that are
metal or concrete when around electrical equipment. Do not wear damp clothing
(particularly wet shoes) or allow skin surface to be damp when handling electrical
equipment. Do not wear jewelry. Jewelry can short out electrical contacts and cause shock
or burning.
• Use extreme caution when working on electrical components. High voltages can cause
injury or death. DO NOT tamper with interlocks.
• Follow all applicable state and local electrical codes. Have all electrical installations
performed by a qualified licensed electrician. Tag and lock open switches to avoid
accidental closure.
• DO NOT CONNECT GENERATOR SET DIRECTLY TO ANY BUILDING ELECTRICAL
SYSTEM. Hazardous voltages can flow from the generator set into the utility line. This
creates a potential for electrocution or property damage. Connect only through an
approved isolation switch or an approved paralleling device.

1.5.1 Medium Voltage Equipment (601 V to 15 kV)


• Medium voltage acts differently than low voltage. Special equipment and training is
required to work on or around medium voltage equipment. Operation and maintenance
must be done only by persons trained and experienced to work on such devices. Improper
use or procedures will result in severe personal injury or death.
• Do not work on energized equipment. Unauthorized personnel must not be permitted near
energized equipment. Due to the nature of medium voltage electrical equipment, induced
voltage remains even after the equipment is disconnected from the power source. Plan the
time for maintenance with authorized personnel so that the equipment can be de-energized
and safely grounded.

A029X159 (Issue 14) 3


1. Important Safety Instructions 10-2015

1.6 General Safety Precautions


WARNING
Hot Pressurized Liquid
Contact with hot liquid can cause severe burns.
Do not open the pressure cap while the engine is running. Let the engine cool down before
removing the cap. Turn the cap slowly and do not open it fully until the pressure has been
relieved.

WARNING
Moving Parts
Moving parts can cause severe personal injury.
Use extreme caution around moving parts. All guards must be properly fastened to prevent
unintended contact.

WARNING
Toxic Hazard
Used engine oils have been identified by some state and federal agencies to cause cancer or
reproductive toxicity.
Do not ingest, breathe the fumes, or contact used oil when checking or changing engine oil.
Wear protective gloves and face guard.

WARNING
Electrical Generating Equipment
Incorrect operation can cause severe personal injury or death.
Do not operate equipment when fatigued, or after consuming any alcohol or drug.

WARNING
Toxic Gases
Substances in exhaust gases have been identified by some state and federal agencies to cause
cancer or reproductive toxicity.
Do not breathe in or come into contact with exhaust gases.

WARNING
Combustible Liquid
Ignition of combustible liquids is a fire or explosion hazard which can cause severe burns or
death.
Do not store fuel, cleaners, oil, etc., near the generator set.

WARNING
High Noise Level
Generator sets in operation emit noise, which can cause hearing damage.
Wear appropriate ear protection at all times.

4 A029X159 (Issue 14)


10-2015 1. Important Safety Instructions

WARNING
Hot Surfaces
Contact with hot surfaces can cause severe burns.
Wear appropriate PPE when working on hot equipment and avoid physical contact with hot
surfaces.

WARNING
Electrical Generating Equipment
Incorrect operation and maintenance can result in severe personal injury or death
Make sure that only suitably trained and experienced service personnel perform electrical and/or
mechanical service.

WARNING
Toxic Hazard
Ethylene glycol, used as an engine coolant, is toxic to humans and animals.
Wear appropriate PPE. Clean up coolant spills and dispose of used coolant in accordance with
local environmental regulations.

WARNING
Combustible Liquid
Ignition of combustible liquids is a fire or explosion hazard which can cause severe burns or
death.
Do not use combustible liquids like ether.

WARNING
Automated Machinery
Accidental or remote starting of the generator set can cause severe personal injury or death.
Isolate all auxiliary supplies and use an insulated wrench to disconnect the starting battery
cables (negative [–] first).

WARNING
Fire Hazard
Materials drawn into the generator set are a fire hazard. Fire can cause severe burns or death.
Keep the generator set and the surrounding area clean and free from obstructions.

WARNING
Fire Hazard
Materials drawn into the generator set are a fire hazard. Fire can cause severe burns or death.
Make sure the generator set is mounted in a manner to prevent combustible materials from
accumulating under the unit.

WARNING
Fire Hazard
Accumulated grease and oil are a fire hazard. Fire can cause severe burns or death.
Keep the generator set and the surrounding area clean and free from obstructions. Repair oil
leaks promptly.

A029X159 (Issue 14) 5


1. Important Safety Instructions 10-2015

NOTICE
Keep multi-class ABC fire extinguishers handy. Class A fires involve ordinary
combustible materials such as wood and cloth. Class B fires involve combustible and
flammable liquid fuels and gaseous fuels. Class C fires involve live electrical
equipment. (Refer to NFPA No. 10 in applicable region.)

NOTICE
Before performing maintenance and service procedures on enclosed generator sets, make sure
the service access doors are secured open.

NOTICE
Stepping on the generator set can cause parts to bend or break, leading to electrical
shorts, or to fuel, coolant, or exhaust leaks. Do not step on the generator set when
entering or leaving the generator room.

1.7 Decommissioning and Disassembly


NOTICE
Decommissioning and disassembly of the generator set at the end of its working life must
comply with local guidelines and legislation for disposal/recycling of components and
contaminated fluids. This procedure must only be carried out by suitably trained and
experienced service personnel. For more information contact your authorized distributor.

6 A029X159 (Issue 14)


2 Introduction
2.1 CPG Controllers
NOTICE

• CPG Controllers that have Modbus RS485 Communication built-in have a dedicated
MODBUS holding register for "Save Trims". The number of write cycles on any Flash
memory device are finite.
• Only save trims once all configuration changes are complete; saving them on a schedule
can reduce the lifetime of the physical control. Do not save trims unless a change has
occurred.

NOTICE
There is a fixed number of write cycles available in the life of the control. Once these
are used up, the control must be replaced.

This note is targeted to, but not limited to, the following Modbus registers per CPG device. If the
device is not listed in the table, please reference the dedicated Modbus Register for "Save
Trims".

Device Holding Register Access Specifications Description


Address
PC 1.x 40004 Read and Write 0: No action Save configuration
PSO 500 1: Save unconditional parameters or
adjustments to non-
PCC 1301 volatile memory.
PCC 1302 Perform Save Trims
after all configurations
PC 2.x 43910 Read and Write 0: Do nothing have been updated.
PC 3.x 1: Save Trims Do not save trims
PCC 2300 unless a change has
PCC 3300 occurred.

DMC 1000 /DMC 42004 Read and Write 0: Do nothing


1: Save Trims
Default: Do Nothing
AUX 101 43052 Read and Write 0: Do Nothing
1: Save Trims

2.2 Bit Mapping


NOTICE
Bit-mapped registers are based in a 0 bit system. For a 16 bit register, 0 is the low-order
bit and 15 is the high-order bit.

A029X159 (Issue 14) 7


2. Introduction 10-2015

This page is intentionally blank.

8 A029X159 (Issue 14)


3 PCC 1301/PowerCommand 1.x/PS0500
Modbus Register Map
The controller contains data that can be read by a Master device communicating via Modbus
RTU protocol on a two-wire RS485 multi-drop bus. The Cummins control is a Slave unit.
For more information about the Modbus protocol, refer to Modbus Application Protocol V1.1b3
and Modbus Serial Line Implementation Guide V1.02, both available at www.modbus.org.
RS485 Pins
• A (+) TB2-3
• B (-) TB2-4
• Common TB2-1

NOTICE
Earlier versions of software may not support all of the Modbus registers in the following
table. If a particular register is not available in your installation, it is possible that the
Modbus connection is working but the controller software does not support that
particular register.

NOTICE
For the PS0500 control, Modbus functionality is ONLY available from software version
6.02 and later.

NOTICE
If an address or bit is not listed in this table it is not implemented.

NOTICE
The Master device can read 1-16 contiguous registers, write 1-16 contiguous registers,
or read diagnostic counters.

Addr. Parameter Access Specifications Description Control


40004 Save Trims Read and 0: No action Save configuration PC1.x,
Write 1: Save Unconditional parameters or adjustments to PS0500,
non-volatile memory. Perform
Save Trims after all PCC1301
configurations have been
updated. Do not save trims
unless a change has
occurred.
40009 Controller Read Only Multiplier: 1 Device type of Controller PC1.x,
Type Size(Bits): 8 PS0500,
Sign: U PCC1301
Lower Limit: 0
Upper Limit: 255

A029X159 (Issue 14) 9


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40010 Operation Read Only 0: Off Current position of the PC1.x,
Mode Switch 1: Auto generator set switch panel PS0500,
Position off-Run-Auto switch as seen
2: Manual by the generator set control PCC1301

40011 Genset State Read Only 0: Ready The parameter reflects PC1.x,
1: Precrank current state of genset PS0500,
2: Ramp PCC1301
3: Running
40012 Active Fault Read Only Multiplier: 1 This register contains the PC1.x,
Offset: 0 fault code number of currently PS0500,
active fault. See service
Size(Bits) 16 manual for list of supported PCC1301
Sign: U fault codes.
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
40013 Active Fault Read Only 0: Normal Fault TypeThis register PC1.x,
Type 1: Warning contains the fault type of PS0500,
currently active fault
4: Shutdown PCC1301
40016 NFPA 110 Read Only Multiplier: 1 16 bit number to represent PC1.x,
fault register Offset: 0 the status of the NFPA110 PS0500,
logical. (See Table 2 on
Size(Bits): 16 page 379) PCC1301
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
40017 Extended Read Only Multiplier: 1 16 bit number to represent PC1.x,
Annunciation Offset: 0 the status of the NFPA110 PS0500,
fault register logical. (See Table 2 on
Size(Bits): 16 page 379) PCC1301
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
40018 Alternator L1- Read Only Multiplier: 1 Generator set L1-N Voltage PC1.x,
N Voltage Offset: 0 PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA
40019 Alternator L2- Read Only Multiplier: 1 Generator set L2-N Voltage PC1.x,
N Voltage Offset: 0 PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA

10 A029X159 (Issue 14)


10-2015 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


40020 Alternator L3- Read Only Multiplier: 1 Generator set L3-N Voltage PC1.x,
N Voltage Offset: 0 PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA
40022 Alternator L1- Read Only Multiplier: 1 Generator set L1-L2 Voltage PC1.x,
L2 Voltage Offset: 0 PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA
40023 Alternator L2- Read Only Multiplier: 1 Generator set L2-L2 Voltage PC1.x,
L3 Voltage Offset: 0 PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA
40024 Alternator L3- Read Only Multiplier: 1 Generator set L3-L1 Voltage PC1.x,
L1 Voltage Offset: 0 PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA
40025 Alt Voltage Read Only Multiplier: 1 Generator set line to line PC1.x,
Offset: 0 average voltage PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA
40026 Alternator L1 Read Only Multiplier: 0.1 Monitors the generator set L1 PC1.x,
Current Offset: 0 current value PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: amps
Lower Limit: 0
Upper Limit: 65535
Default: NA

A029X159 (Issue 14) 11


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40027 Alternator L2 Read Only Multiplier: 0.1 Monitors the generator set L2 PC1.x,
Current Offset: 0 current value PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: amps
Lower Limit: 0
Upper Limit: 65535
Default: NA
40028 Alternator L3 Read Only Multiplier: 0.1 Monitors the generator set L3 PC1.x,
Current Offset: 0 current value PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: amps
Lower Limit: 0
Upper Limit: 65535
Default: NA
40029 Genset Read Only Multiplier: 0.1 Generator set average PC1.x,
average Offset: 0 current PS0500,
current
Size(Bits): 16 PCC1301
Sign: U
Units: amps
Lower Limit: 0
Upper Limit: 65535
Default: NA
40040 Alternator Read Only Multiplier: 1 Alternator output volt- PC1.x,
output volt- Offset: 0 amperes (phase a) PS0500,
amperes
(phase a) Size(Bits): 16 PCC1301
Sign: U
Units: kVa
Lower Limit: 0
Upper Limit: 65535
Default: NA
40041 Alternator Read Only Multiplier: 1 Alternator output volt- PC1.x,
output volt- Offset: 0 amperes (phase b) PS0500,
amperes
(phase b) Size(Bits): 16 PCC1301
Sign: U
Units: kVa
Lower Limit: 0
Upper Limit: 65535
Default: NA
40042 Alternator Read Only Multiplier: 1 Alternator output volt- PC1.x,
output volt- Offset: 0 amperes (phase c) PS0500,
amperes
(phase c) Size(Bits): 16 PCC1301
Sign: U
Units: kVa
Lower Limit: 0
Upper Limit: 65535
Default: NA

12 A029X159 (Issue 14)


10-2015 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


40043 Alternator Read Only Multiplier: 1 Alternator output volt- PC1.x,
output volt- Offset: 0 amperes (total) PS0500,
amperes
(total) Size(Bits): 16 PCC1301
Sign: U
Units: kVa
Lower Limit: 0
Upper Limit: 65535
Default: NA
40044 Average Alt Read Only Multiplier: 0.1 Average alternator line PC1.x,
Line Offset: 0 frequency PS0500,
Frequency
Size(Bits): 16 PCC1301
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 65535
Default: NA
40058 Rated Read Only Multiplier: 0.1 Monitors the generator set PC1.x,
Alternator L1 Offset: 0 standby L1 current PS0500,
Current (%) percentage output.
Size(Bits): 16 PCC1301
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 65535
Default: NA
40059 Rated Read Only Multiplier: 0.1 Monitors the generator set PC1.x,
Alternator L2 Offset: 0 standby L2 current PS0500,
Current (%) percentage output.
Size(Bits): 16 PCC1301
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 65535
Default: NA
40060 Rated Read Only Multiplier: 0.1 Monitors the generator set PC1.x,
Alternator L3 Offset: 0 standby L3 current PS0500,
Current (%) percentage output.
Size(Bits): 16 PCC1301
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 65535
Default: NA
40061 Battery Read Only Multiplier: 0.1 Value of battery voltage PC1.x,
Voltage Offset: 0 PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA

A029X159 (Issue 14) 13


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40062 Oil Pressure Read Only Multiplier: 1 Monitor point for oil pressure PC1.x,
Offset: 0 PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: kPa
Lower Limit: 0
Upper Limit: 65535
Default: NA
40064 Coolant Read Only Multiplier: 0.1 Monitor point for Coolant PC1.x,
Temperature Offset: 0 Temperature PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: degc
Lower Limit: 0
Upper Limit: 65535
Default: NA
40068 Engine Read Only Multiplier: 1 Monitor point for Average PC1.x,
Speed Offset: 0 Engine Speed PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Rpm
Lower Limit: 0
Upper Limit: 65535
Default: NA
40069 Total Runs Read Only Multiplier: 1 Parameter reflects total PC1.x,
Offset: 0 number of starts PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
40070 Engine Run Read Only Multiplier: 1 Total Engine Run Time PC1.x,
Time (High Offset: 0 PS0500,
byte)
Size(Bits): 16 PCC1301
Sign: U
Units: Sec
Lower Limit: 0
Upper Limit: 65535
Default: NA
40071 Engine Run Read Only Multiplier: 1 Total Engine Run time PC1.x,
Time (Low Offset: 0 PS0500,
byte)
Size(Bits): 16 PCC1301
Sign: U
Units: Sec
Lower Limit: 0
Upper Limit: 65535
Default: NA

14 A029X159 (Issue 14)


10-2015 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


40210 AUX101 Read Only Multiplier: 0.01 AUX101 Speed Bias PCC1301
Speed Bias Offset: 0
Size(Bits): 16
Sign: S
Units: RPM
Lower Limit: -100
Upper Limit: 100
Default: NA
40211 AUX101 Read Only Multiplier: 0.01 AUX101 Voltage Bias PCC1301
Voltage Bias Offset: 0
Size(Bits): 16
Sign: S
Units: Volt
Lower Limit: -100
Upper Limit: 100
Default: NA
40229 Barometric Read Only Multiplier : 0.1 Monitor point for the PC 1.x
Absolute Offset: 0 Barometric Absolute Pressure
Pressure
Size (Bits) : 16
Sign: U
Units: PSI
Lower Limit: 0
Upper Limit: 19
Default: NA
40242 LTA Read Only Multiplier : 1 The processed value of the PC 1.x
Temperature Offset: 0 LTA Temperature sensor for
the System IO Module.
Size (Bits) : 16
Sign: S
Units: degF
Lower Limit: NA
Upper Limit: NA
Default: NA
40254 Fuel Pressure Read Only 0. Invalid Indicates if the fuel pressure PC 1.x
Valid 1. Valid is valid/invalid from the
AUX101 or ECM datalink.
40278 Configurable Read Only 0. Inactive Measured state of hardware PC 1.x
Input #4 1. Active input
Status

40300 Genset start Read and 0: Stop Remote start via Modbus PC1.x,
stop control Write 1: Start PS0500,
via Modbus
PCC1301
40301 Fault reset Read and 0: Inactive Fault reset PC1.x,
via Modbus Write 1: Active PCC1301,
(No logical)
PS0500
40535 Customer Read Only 0. Inactive Output of Customer Output 1 PC 1.x
Output 1 1. Active Event command
Event
40536 Customer Read Only 0. Inactive Output of Customer Output 2 PC 1.x
Output 2 1. Active Event command
Event

A029X159 (Issue 14) 15


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40583 Dead Battery Read Only Multiplier : 1 Tracks the number of crank PC 1.x
Prevention Offset: 0 attempts in order to limit the
Counter attempts when the battery is
Size (Bits) : 8 so low that the control resets
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA

40587 Exercise Read Only 0. Inactive Displays the status of PC 1.x


Scheduler 1. Active Exercise Scheduler
Status
43000 Alternator Read and Multiplier: 1 This register represents PC1.x,
Nominal Write Offset: 0 Alternator nominal voltage PS0500,
Voltage
Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 190
Upper Limit: 600
Default: 208
43001 Alternator Read and 0: 60 Hz Set to 50 Hz or 60 Hz PC1.x,
Frequency Write 1: 50 Hz PS0500,
Switch
PCC1301
43002 Single/3 Read and 0: Single Phase Generator output connection PC1.x
Phase Write 1: Three Phase type
Connection
43003 Connection Read and 0: Delta Alternator connection type PC1.x,
Type Write 1: Wye PS0500,
PCC1301
43004 Glow Plug Read and 0: Disable Glow plug driver feature PC1.x,
Enable Write 1: Enable enable PS0500,
PCC1301
43005 Charging Read and 0: Disable Used to disable the controller PC1.x,
Alternator Write 1: Enable related charging alt functions. PS0500,
Functions
Disable PCC1301

43006 Start Time Read and Multiplier: 1 Remote start time delay PC1.x,
Delay Write Offset: 0 setting PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Sec
Lower Limit: 0
Upper Limit: 300
Default: 0

16 A029X159 (Issue 14)


10-2015 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43007 Stop Time Read and Multiplier: 1 Remote stop time delay PC1.x,
Delay Write Offset: 0 setting PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Sec
Lower Limit: 0
Upper Limit: 600
Default: 0
43008 Cycle Crank Read and Multiplier: 1 Maximum number of start PC1.x,
Attempts Write Offset: 0 attempts for cycle crank PS0500,
mode
Size(Bits): 16 PCC1301
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 7
Default: 3
43009 Cycle Crank Read and Multiplier: 1 Maximum starter engage time PC1.x,
Engage Time Write Offset: 0 for cycle crank mode PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: sec
Lower Limit: 3
Upper Limit: 30
Default: 15
43010 Cycle Crank Read and Multiplier: 1 Engine starting cycle crank PC1.x,
Reset Time Write Offset: 0 attempts setting PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: sec
Lower Limit: 0
Upper Limit: 60
Default: 30
43011 Fault bypass Read and 0: Disable Operator panel Enable for PC1.x,
(battle short) Write 1: Enable Battle Short PCC1301
feature
enable

A029X159 (Issue 14) 17


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43012 Battle Short Read and 0: None, Switch Input for Battle Short. PC1.x
Switch Input Write 1: Configurable Input #1, 0= None
2: Configurable Input #2, 1=Customer Input 1
3: Configurable Input #3, 2=Customer Input 2
4: Configurable Input #4, 3 =Customer Input 3
5: Operator Panel 4 =Customer Input 4
5=Operator Panel
PCC1301 Modbus mapping
for parameters having
different limits as compared
to PC1.x and PS0500 See
Table 1 on page 37.

NOTE: For PC1.x SW


versions less than 2.73,
’Battle Short Switch Input’
range is 0 to 3. For PC1.x
SW versions 2.73 and greater
’Battle Short Switch Input’
range is 0 to 5

43013 AVR Enable Read and 0: Disable Automatic voltage regulation PC1.x,
Write 1: Enable enable PCC1301
43014 V/Hz Knee Read and Multiplier: 0.1 Automatic voltage regulator PC1.x,
Frequency Write Offset: 0 volts per hertz roll off knee PCC1301
setting
Size(Bits): 16
Sign: S
Units: Hz
Lower Limit: 0
Upper Limit: 1000
Default: 500
43015 V/Hz Rolloff Read and Multiplier: 0.1 Automatic voltage regulator PC1.x,
Slope Write Offset: 0 volts per hertz roll off slope PCC1301
setting
Size(Bits): 16
Sign: U
Units: %v/Hz
Lower Limit: 0
Upper Limit: 50
Default: 22
43016 AVR Gain Read and Multiplier: 1 Automatic voltage regulator PC1.x,
Adjust Write Offset: 0 gain setting PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 5
Upper Limit: 1000
Default: 100

18 A029X159 (Issue 14)


10-2015 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43017 AVR K2 Gain Read and Multiplier: 1 Automatic voltage regulator PC1.x,
Adjust Write Offset: 0 K2 gain setting PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 5
Upper Limit: 1000
Default: 100
43018 AVR D Gain Read and Multiplier: 1 Automatic voltage regulator PC1.x,
Adjust Write Offset: 0 K2 gain setting PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 95
Upper Limit: 105
Default: 100
43019 Electronic Read and 0: Disable Electronic governor enable PC1.x,
Governor Write 1: Enable feature PCC1301
Enable
43020 Initial Crank Read and Multiplier: 0.1 Electronic governing initial PC1.x,
Fueling Write Offset: 0 duty cycle setting PCC1301
Command
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 500
Default: 250
43021 Initial Crank Read and Multiplier: 0.1 Time spent at Initial Crank PC1.x,
Fueling Write Offset: 0 Fueling Command PCC1301
Period
Size(Bits): 8
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 100
Default: 20
43022 Crank Fueling Read and Multiplier: 0.1 Electronic governing start PC1.x,
Ramp Rate Write Offset: 0 ramp duty cycle setting PCC1301
Size(Bits): 16
Sign: U
Units: %/sec
Lower Limit: 50
Upper Limit: 1000
Default: 250
43023 Maximum Read and Multiplier: 0.1 Electronic governing PC1.x,
Crank Fueling Write Offset: 0 maximum duty cycle setting PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 500
Upper Limit: 1000
Default: 1000

A029X159 (Issue 14) 19


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43024 Governor Read and Multiplier: 1 Electronic governing gain PC1.x,
Gain Adjust Write Offset: 0 setting PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 5
Upper Limit: 1000
Default: 100
43025 Gov K2 Gain Read and Multiplier: 1 Electronic governor K2 gain PC1.x,
Adjust Write Offset: 0 setting PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 5
Upper Limit: 1000
Default: 100
43026 Gov D Gain Read and Multiplier: 1 Electronic governor damping PC1.x,
Adjust Write Offset: 0 adjustment PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 95
Upper Limit: 105
Default: 100
43027 Crank Exit Read and Multiplier: 0.1 Electronic governing crank PC1.x,
Fueling Write Offset: 0 exit fuel duty cycle setting PCC1301
Command
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 1000
Default: 250
43028 Dither Factor Read and Multiplier: 1 Electronic governing dither PC1.x,
Write Offset: 0 factor setting PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 30
Default: 25
43029 Governor Read and Multiplier: 1 Electronic governing start PC1.x,
Ramp Time Write Offset: 0 ramp time setting PCC1301
Size(Bits): 16
Sign: U
Units: sec
Lower Limit: 0
Upper Limit: 15000
Default: 25

20 A029X159 (Issue 14)


10-2015 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43030 Governor Read and Multiplier: 1 Engine speed at which PC1.x,
Enable Write Offset: 0 governor is enabled PS0500,
Speed
Size(Bits): 16 PCC1301
Sign: U
Units: RPM
Lower Limit: 0
Upper Limit: 1400
Default: 1100
43031 Minimum Read and Multiplier: 1 Setting for electronic PC1.x,
Governor Write Offset: 0 governor minimum duty cycle PCC1301
Duty Cycle
Size(Bits): 8
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 100
Default: 20
43032 Maximum Read and Multiplier: 1 Setting for electronic PC1.x,
Governor Write Offset: 0 governor maximum duty cycle PCC1301
Duty Cycle
Size(Bits): 8
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 100
Default: 95
43033 Model Read and Multiplier: 1 Byte 1 for model number PC1.x,
number Write Offset: 0 PS0500,
character #1
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43034 Model Read and Multiplier: 1 Byte 2 for model number PC1.x,
number Write Offset: 0 PS0500,
character #2
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43035 Model Read and Multiplier: 1 Byte 3 for model number PC1.x,
number Write Offset: 0 PS0500,
character #3
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

A029X159 (Issue 14) 21


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43036 Model Read and Multiplier: 1 Byte 4 for model number PC1.x,
number Write Offset: 0 PS0500,
character #4
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43037 Model Read and Multiplier: 1 Byte 5 for model number PC1.x,
number Write Offset: 0 PS0500,
character #5
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43038 Model Read and Multiplier: 1 Byte 6 for model number PC1.x,
number Write Offset: 0 PS0500,
character #6
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43039 Model Read and Multiplier: 1 Byte 7 for model number PC1.x,
number Write Offset: 0 PS0500,
character #7
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43040 Model Read and Multiplier: 1 Byte 8 for model number PC1.x,
number Write Offset: 0 PS0500,
character #8
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43041 Model Read and Multiplier: 1 Byte 9 for model number PC1.x,
number Write Offset: 0 PS0500,
character #9
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

22 A029X159 (Issue 14)


10-2015 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43042 Model Read and Multiplier: 1 Byte 10 for model number PC1.x,
number Write Offset: 0 PS0500,
character #10
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43043 Model Read and Multiplier: 1 Byte 11 for model number PC1.x,
number Write Offset: 0 PS0500,
character #11
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43044 Model Read and Multiplier: 1 Byte 12 for model number PC1.x,
number Write Offset: 0 PS0500,
character #12
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43045 Model Read and Multiplier: 1 Byte 13 for model number PC1.x,
number Write Offset: 0 PS0500,
character #13
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43046 Model Read and Multiplier: 1 Byte 14 for model number PC1.x,
number Write Offset: 0 PS0500,
character #14
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43047 Model Read and Multiplier: 1 Byte 15 for model number PC1.x,
number Write Offset: 0 PS0500,
character #15
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

A029X159 (Issue 14) 23


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43048 Model Read and Multiplier: 1 Byte 16 for model number PC1.x,
number Write Offset: 0 PS0500,
character #16
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43049 Serial number Read and Multiplier: 1 Byte 1 for serial number PC1.x,
character #1 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43050 Serial number Read and Multiplier: 1 Byte 2 for serial number PC1.x,
character #2 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43051 Serial number Read and Multiplier: 1 Byte 3 for serial number PC1.x,
character #3 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43052 Serial number Read and Multiplier: 1 Byte 4 for serial number PC1.x,
character #4 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43053 Serial number Read and Multiplier: 1 Byte 5 for serial number PC1.x,
character #5 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

24 A029X159 (Issue 14)


10-2015 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43054 Serial number Read and Multiplier: 1 Byte 6 for serial number PC1.x,
character #6 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43055 Serial number Read and Multiplier: 1 Byte 7 for serial number PC1.x,
character #7 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43056 Serial number Read and Multiplier: 1 Byte 8 for serial number PC1.x,
character #8 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43057 Serial number Read and Multiplier: 1 Byte 9 for serial number PC1.x,
character #9 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43058 Serial number Read and Multiplier: 1 Byte 10 for serial number PC1.x,
character #10 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43059 Serial number Read and Multiplier: 1 Byte 11 for serial number PC1.x,
character #11 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

A029X159 (Issue 14) 25


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43060 Serial number Read and Multiplier: 1 Byte 12 for serial number PC1.x,
character #12 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43061 Serial number Read and Multiplier: 1 Byte 13 for serial number PC1.x,
character #13 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43062 Serial number Read and Multiplier: 1 Byte 14 for serial number PC1.x,
character #14 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43063 Serial number Read and Multiplier: 1 Byte 15 for serial number PC1.x,
character #15 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43064 Serial number Read and Multiplier: 1 Byte 16 for serial number PC1.x,
character #16 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43065 Configurable Read and 0: None Configurable Input #1 Fault PC1.x,
Input #1 Fault Write 1: Warning Level Response PS0500,
Level
Response 2: Shutdown PCC1301

43066 Configurable Read and 0: None Configurable Input #2 Fault PC1.x,


Input #2 Fault Write 1: Warning Level Response PS0500,
Level
Response 2: Shutdown PCC1301

26 A029X159 (Issue 14)


10-2015 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43067 Configurable Read and Multiplier: 1 Configurable customer output PC1.x,
Customer Write Offset: 0 1. Default set for FC 1540 PS0500,
Output 1 which is COMMON
Size(Bits): 16 WARNING fault. PCC1301
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 1540
43068 Configurable Read and Multiplier: 1 Configurable customer output PC1.x,
Customer Write Offset: 0 2. Default set for FC 1541 PS0500,
Output 2 which is COMMON
Size(Bits): 16 SHUTDOWN fault. PCC1301
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 1541
43069 Voltage Read and Multiplier: 0.0001 Make actual voltage match PC1.x
Regulator Write Offset: 0 Nominals 60Hz when Set
Calibration point = 100%.
60Hz Size(Bits): 16
PCC1301 Modbus mapping
Sign: U for parameters having
Units: % different limits as compare to
Lower Limit: 9000 PC1.x See Table 1 on page
Upper Limit: 11000 37.
Default: 10000
43070 Voltage Read and Multiplier: 0.0001 Make actual voltage match PC1.x
Regulator Write Offset: 0 Nominals 50Hz when Set
Calibration point = 100%.
50Hz Size(Bits): 16
PCC1301 Modbus mapping
Sign: U for parameters having
Units: % different limits as compare to
Lower Limit: 9000 PC1.x See Table 1 on page
Upper Limit: 11000 37.
Default: 10000
43071 Frequency Read and Multiplier: 0.1 PC1.x,
Adjust Trim Write Offset: 0 PCC1301
Size(Bits): 16
Sign: S
Units: Hz
Lower Limit: -600
Upper Limit: 600
Default: 0

A029X159 (Issue 14) 27


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43072 Alternator L1- Read and Multiplier: 0.0001 60 Hz line 1 to neutral PC1.x,
N 60Hz Write Offset: 0 metering voltage calibration. PS0500
Voltage PCC1301 Modbus mapping
Display Size(Bits): 16
for parameters having
Adjust Sign: U different limits as compare to
Units: % PC1.x and PS0500 See
Lower Limit: 9000* Table 1 on page 37.
Upper Limit: 11000*
Default: 10000 *NOTE: For PS0500 control,
SW versions <6.03 the range
is 6000 to 14000. For
PS0500 control, SW versions
>6.03 the range is 9000 to
11000.
43073 Alternator L2- Read and Multiplier: 0.0001 60 Hz line 2 to neutral PC1.x,
N 60Hz Write Offset: 0 metering voltage calibration PS0500
Voltage *NOTE: For PS0500 control,
Display Size(Bits): 16
SW versions <6.03 the range
Adjust Sign: U is 6000 to 14000. For
Units: % PS0500 control, SW versions
Lower Limit: 9000* >6.03 the range is 9000 to
Upper Limit: 11000* 11000.
Default: 10000
43074 Alternator L3- Read and Multiplier: 0.0001 60 Hz line 3 to neutral PC1.x,
N 60Hz Write Offset: 0 metering voltage calibration PS0500
Voltage *NOTE: For PS0500 control,
Display Size(Bits): 16
SW versions <6.03 the range
Adjust Sign: U is 6000 to 14000. For
Units: % PS0500 control, SW versions
Lower Limit: 9000* >6.03 the range is 9000 to
Upper Limit: 11000* 11000.
Default: 10000
43075 Alternator L1- Read and Multiplier: 0.0001 50 Hz line 1 to neutral PC1.x,
N 50Hz Write Offset: 0 metering voltage calibration PS0500
Voltage *NOTE: For PS0500 control,
Display Size(Bits): 16
SW versions <6.03 the range
Adjust Sign: U is 6000 to 14000. For
Units: % PS0500 control, SW versions
Lower Limit: 9000* >6.03 the range is 9000 to
Upper Limit: 11000* 11000.
Default: 10000
43076 Alternator L2- Read and Multiplier: 0.0001 50 Hz line 2 to neutral PC1.x,
N 50Hz Write Offset: 0 metering voltage calibration PS0500
Voltage *NOTE: For PS0500 control,
Display Size(Bits): 16
SW versions <6.03 the range
Adjust Sign: U is 6000 to 14000. For
Units: % PS0500 control, SW versions
Lower Limit: 9000* >6.03 the range is 9000 to
Upper Limit: 11000* 11000.
Default: 10000

28 A029X159 (Issue 14)


10-2015 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43077 Alternator L3- Read and Multiplier: 0.0001 50 Hz line 3 to neutral PC1.x,
N 50Hz Write Offset: 0 metering voltage calibration PS0500
Voltage *NOTE: For PS0500 control,
Display Size(Bits): 16
SW versions <6.03 the range
Adjust Sign: U is 6000 to 14000. For
Units: % PS0500 control, SW versions
Lower Limit: 9000* >6.03 the range is 9000 to
Upper Limit: 11000* 11000.
Default: 10000
43078 Alternator L1 Read and Multiplier: 0.001 60 Hz line 1 metering current PC1.x,
60Hz Current Write Offset: 0 calibration PS0500,
Adjust
Size(Bits): 16 PCC1301
Sign: U
Units: %
Lower Limit: 8000
Upper Limit: 12000*
Default: 1000
43079 Alternator L2 Read and Multiplier: 0.001 60 Hz line 2 metering current PC1.x,
60Hz Current Write Offset: 0 calibration PS0500,
Adjust
Size(Bits): 16 PCC1301
Sign: U
Units: %
Lower Limit: 8000
Upper Limit: 12000*
Default: 1000
43080 Alternator L3 Read and Multiplier: 0.0001 Adjust to make displayed PC1.x
60Hz Current Write Offset: 0 current match actual values in
Adjust 50Hz applications.
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: .8
Upper Limit: 1.2
Default: 1
43081 Alternator L1 Read and Multiplier: 0.001 50 Hz line 1 metering current PC1.x,
50Hz Current Write Offset: 0 calibration PS0500,
Adjust
Size(Bits): 16 PCC1301
Sign: U
Units: %
Lower Limit: 8000
Upper Limit: 12000*
Default: 1000
43082 Alternator L2 Read and Multiplier: 0.001 50 Hz line 2 metering current PC1.x,
50Hz Current Write Offset: 0 calibration PS0500,
Adjust
Size(Bits): 16 PCC1301
Sign: U
Units: %
Lower Limit: 8000
Upper Limit: 12000*
Default: 1000

A029X159 (Issue 14) 29


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43083 Alternator L3 Read and Multiplier: 0.001 50 Hz line 3 metering current PC1.x,
50Hz Current Write Offset: 0 calibration PS0500,
Adjust
Size(Bits): 16 PCC1301
Sign: U
Units: %
Lower Limit: 8000
Upper Limit: 12000*
Default: 1000
43084 Annunciator Read and 0: None Sets the genset response to PC1.x,
#1 Switch Write 1: Warning an active Annunciator #1 PCC1301
Fault switch input.
Response 2: Shutdown

43085 Annunciator Read and 0: None Sets the genset response to PC1.x,
#2 Switch Write 1: Warning an active Annunciator #2 PCC1301
Fault switch input.
Response 2: Shutdown

43086 Annunciator Read and 0: None Sets the genset response to PC1.x,
#3 Switch Write 1: Warning an active Annunciator #3 PCC1301
Fault switch input.
Response 2: Shutdown

43087 Annunciator Read and Multiplier: 1 Annunciator configurable PC1.x,


Output 1 Write Offset: 0 output #1 event code number PCC1301
Event
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43088 Annunciator Read and Multiplier: 1 Annunciator configurable PC1.x,
Output 2 Write Offset: 0 output #2 event code number PCC1301
Event
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43089 Annunciator Read and Multiplier: 1 Annunciator configurable PC1.x,
Output 3 Write Offset: 0 output #3 event code number PCC1301
Event
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43090 Annunciator Read and Multiplier: 1 Annunciator configurable PC1.x,
Output 4 Write Offset: 0 output #4 event code number PCC1301
Event
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

30 A029X159 (Issue 14)


10-2015 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43344 Clock Date Read Write Multiplier : 1 Use to set or read the current PC 1.x
Offset: 0 date.
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 31
Default: NA
43345 Clock Hours Read Write Multiplier : 1 Use to set or read the current PC 1.x
Offset: 0 hour.
Size (Bits) : 8
Sign: U
Units: hours
Lower Limit: 1
Upper Limit: 12
Default: 0
43346 Clock Read Write Multiplier : 1 Use to set or read the current PC 1.x
Minutes Offset: 0 minute.
Size (Bits) : 8
Sign: U
Units: minutes
Lower Limit: 0
Upper Limit: 59
Default: 0
43347 Clock Mode Read Write 0. NORMAL_MODE Allows user to go into Set PC 1.x
1. SET_MODE Mode for Clock setup and in
Clock Save Mode
2. SAVE_CLOCK_MODE
43348 Clock Month Read Write Multiplier : 1 Use to set or read the current PC 1.x
Offset: 0 month.
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 12
Default: NA
43349 Clock Read Only Multiplier : 1 Use to set or read the current PC 1.x
Seconds Offset: 0 second.
Size (Bits) : 8
Sign: U
Units: seconds
Lower Limit: NA
Upper Limit: NA
Default: 0

A029X159 (Issue 14) 31


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43350 Clock Year Read Write Multiplier : 1 Use to set or read the current PC 1.x
Offset: 0 year.
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 99
Default: NA
43351 Daylight Read Write Multiplier : 1 Use to set the hour of the day PC 1.x
Savings End Offset: 0 when daylight savings time
Hour ends.
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 23
Default: 2
43352 Daylight Read Write Multiplier : 1 Use to set the month when PC 1.x
Savings End Offset: 0 daylight savings time ends.
Month
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 12
Default: 10
43353 Daylight Read Write 0. Default Use to set the end week PC 1.x
Savings End 1.FIRST_OCCURRENCE occurrence in a daylight
Week Occ savings End month.
Month 2. SECOND_OCCURRENCE
3. THIRD_OCCURRENCE
4. FOURTH_OCCURRENCE
5. FIFTH_OCCURRENCE
43354 Daylight Read Write 0. Sunday Use to set the day of the PC 1.x
Savings Start 1. Monday week when daylight savings
Day time starts.
2. Tuesday
3. Wednesday
4. Thursday
5. Friday
6. Saturday
43355 Daylight Read Write Multiplier : 1 Use to set the hour of the day PC 1.x
Savings Start Offset: 0 when daylight savings time
Hour starts.
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 23
Default: 2

32 A029X159 (Issue 14)


10-2015 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43356 Daylight Read Write Multiplier : 1 Use to set the month when PC 1.x
Savings Start Offset: 0 daylight savings time starts.
Month
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 12
Default: 4
43357 Daylight Read Write 0. Default Use to set the week PC 1.x
Savings Start 1.FIRST_OCCURRENCE occurrence in a daylight
Week Occ savings start month.
Month 2. SECOND_OCCURRENCE
3. THIRD_OCCURRENCE
4. FOURTH_OCCURRENCE
5. FIFTH_OCCURRENCE
43358 Daylight Read Write Multiplier : 1 Use to set the amount of PC 1.x
Savings Time Offset: 0 daylight savings time
Adjustment adjustment applied.
Size (Bits) : 8
Sign: U
Units: minutes
Lower Limit: 0
Upper Limit: 120
Default: 60
43359 Daylight Read Write 0. Disabled Use to enable the daylight PC 1.x
Savings Time 1. Enabled savings time feature.
Enable
43376 Scheduler Read Write 0. PCCNet Devices User to set Duration in PC 1.x
Prog Duration 1. Group for PCCNet device Minutes for Exercise
(Mins) interface parameters Scheduler

43377 Scheduler Read Write 0. Disabled Trim - user to edit for running PC 1.x
Prog x 1. Enabled the Scheduler Exercise
Enable Program
43378 Scheduler Read Write 0. Weekly User to select the Exercise PC 1.x
Prog Repeat 1. Bi-Monthly Scheduler Interval
Interval
2. Monthly
3. Quarterly
4. Semi-Annual
43380 Scheduler Read Write 0. Sunday User can set the Start Day of PC 1.x
Prog Start 1. Monday the week, month for Ex
Day Scheduler
2. Tuesday
3. Wednesday
4. Thursday
5. Friday
6. Saturday
43381 Scheduler Read Write Multiplier : 1 User to set Start Hour For Ex PC 1.x
Prog Start Offset: 0 Scheduler
Hour
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 12
Default: 2

A029X159 (Issue 14) 33


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43382 Scheduler Read Write Multiplier : 1 User to set Start Minute for PC 1.x
Prog Start Offset: 0 Exercise Scheduler
Minute
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 59
Default: 1
43383 Daylight Read Write 0. Sunday Use to set the day of the PC 1.x
Savings End 1. Monday week when daylight savings
Day time ends.
2. Tuesday
3. Wednesday
4. Thursday
5. Friday
6. Saturday
43719 AUX101 Read Only Multiplier: 1 AUX101 input as alternator PCC1301
Alternator Offset: 0 temperature
Temp
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43722 AUX101 Read Only Multiplier: 1 AUX101 input as ambient PCC1301
Ambient Offset: 0 temperature
Temp
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43723 AUX101 input Read Only Multiplier: 1 AUX101 input 1 voltage PCC1301
1 voltage Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43724 AUX101 input Read Only Multiplier: 1 AUX101 input 2 voltage PCC1301
2 voltage Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

34 A029X159 (Issue 14)


10-2015 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43725 AUX101 input Read Only Multiplier: 1 AUX101 input 3 voltage PCC1301
3 voltage Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43726 AUX101 input Read Only Multiplier: 1 AUX101 input 4 voltage PCC1301
4 voltage Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43727 AUX101 input Read Only Multiplier: 1 AUX101 input 5 voltage PCC1301
5 voltage Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43728 AUX101 input Read Only Multiplier: 1 AUX101 input 6 voltage PCC1301
6 voltage Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43729 AUX101 input Read Only Multiplier: 1 AUX101 input 67voltage PCC1301
67voltage Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43730 AUX101 input Read Only Multiplier: 1 AUX101 input 8 voltage PCC1301
8 voltage Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

A029X159 (Issue 14) 35


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43741 AUX101 Read Only Multiplier: 1 AUX101 input as Exhaust PCC1301
Exhaust Offset: 0 temperature
Temp
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43745 AUX101 Fuel Read Only Multiplier: 1 AUX101 input as Fuel level PCC1301
Level Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43750 AUX101 Read Only Multiplier: 1 AUX101 input as Intake PCC1301
Intake Offset: 0 Manifold Temp
Manifold
Temp Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43757 AUX101 Oil Read Only Multiplier: 1 AUX101 input as oil Temp PCC1301
Temp Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43793 Configurable Read Only 0. Inactive Measured state of hardware PC 1.x
Input #1 1. Active input
Status
43794 Configurable Read Only 0. Inactive Measured state of hardware PC 1.x
Input #2 1. Active input
Status
43795 Configurable Read Only 0. Inactive Measured state of hardware PC 1.x
Input #3 1. Active input
Status

43822 Re-Transfer Read Write Multiplier : 1 This is the delay after the PC 1.x
Delay Offset: 0 Utility has returned and
before the Transfer switch is
Size (Bits) : 8 moved back to the Utility side
Sign: U position
Units: NA
Lower Limit: 0
Upper Limit: 59
Default: 1

36 A029X159 (Issue 14)


10-2015 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43825 Transfer Read Write Multiplier : 1 This is the delay after the PC 1.x
Delay Offset: 0 genset is started before the
transfer switch is moved to
Size (Bits) : 16 the genset side position.
Sign: U
Units: seconds
Lower Limit: 60
Upper Limit: 600
Default: 300
43905 Network Read and 0: Normal Used to command a fixed PC1.x
Speed Adjust Write 1: Active 0.5 Hz increase in the speed
Command setpoint.

TABLE 1. PCC1301 MODBUS MAPPING FOR PARAMETERS HAVING DIFFERENT LIMITS AS


COMPARED TO PC1.X AND PS05000

Addr. Parameter Access Specifications Description Control


43012 Battle Short Read and 0: None, Switch Input for Battle Short PCC1301
Switch Input Write 1: Configurable Input #1, ONLY
2: Configurable Input #2,
3: Configurable Input #3
43069 Voltage Read and Multiplier: 0.0001 Make actual voltage match PCC1301
Regulator Write Offset: 0 Nominals 60Hz when Set point ONLY
Calibration = 100%.
60Hz Size(Bits): 16
Sign: U
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
43070 Voltage Read and Multiplier: 0.0001 Make actual voltage match PCC1301
Regulator Write Offset: 0 Nominals 50Hz when Set point ONLY
Calibration = 100%.
50Hz Size(Bits): 16
Sign: U
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
43072 Alternator L1- Read and Multiplier: 0.0001 60 Hz line 1 to neutral PCC1301
N 60Hz Write Offset: 0 metering voltage calibration. ONLY
Voltage
Display Size(Bits): 16
Adjust Sign: U
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000

A029X159 (Issue 14) 37


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43073 Alternator L2- Read and Multiplier: 0.0001 60 Hz line 2 to neutral PCC1301
N 60Hz Write Offset: 0 metering voltage calibration ONLY
Voltage
Display Size(Bits): 16
Adjust Sign: U
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
43074 Alternator L3- Read and Multiplier: 0.0001 60 Hz line 3 to neutral PCC1301
N 60Hz Write Offset: 0 metering voltage calibration ONLY
Voltage
Display Size(Bits): 16
Adjust Sign: U
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
43075 Alternator L1- Read and Multiplier: 0.0001 50 Hz line 1 to neutral PCC1301
N 50Hz Write Offset: 0 metering voltage calibration ONLY
Voltage
Display Size(Bits): 16
Adjust Sign: U
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
43076 Alternator L2- Read and Multiplier: 0.0001 50 Hz line 2 to neutral PCC1301
N 50Hz Write Offset: 0 metering voltage calibration ONLY
Voltage
Display Size(Bits): 16
Adjust Sign: U
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
43077 Alternator L3- Read and Multiplier: 0.0001 50 Hz line 3 to neutral PCC1301
N 50Hz Write Offset: 0 metering voltage calibration ONLY
Voltage
Display Size(Bits): 16
Adjust Sign: U
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
47031 Auto Mains Read Write 0. At Utility Trim to Enable Disable the PC 1.x
Failure 1. At Genset ATS Functionality
Enable 2. Unknown Position
3. Not Available

38 A029X159 (Issue 14)


10-2015 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


47032 Transition to Read Write Multiplier : 1 This is the delay after the PC 1.x
Genset Delay Offset: 0 transfer switch is commanded
to move to generator side
Size (Bits) : 8 awaiting for the feedback.
Sign: U
Units: seconds
Lower Limit: 1
Upper Limit: 10
Default: 3
47033 Re-Transition Read Write Multiplier : 1 This is the delay after the PC 1.x
to Utility Offset: 0 transfer switch is commanded
Delay to move to utility side awaiting
Size (Bits) : 8 for the feedback.
Sign: U
Units: seconds
Lower Limit: 1
Upper Limit: 10
Default: 3
47034 Utility Fail To Read Write Multiplier : 1 This is the delay after the PC 1.x
Close Delay Offset: 0 transfer switch is moved to
utility side, awaiting for the fault
Size (Bits) : 8 to become active or inactive.
Sign: U
Units: seconds
Lower Limit: 1
Upper Limit: 10
Default: 3
47035 Genset Fail Read Write Multiplier : 1 This is the delay after the PC 1.x
To Close Offset: 0 transfer switch is moved to
Delay genset side, awaiting for the
Size (Bits) : 8 fault to become active or
Sign: U inactive.
Units: seconds
Lower Limit: 1
Upper Limit: 10
Default: 5
47036 Transfer Read Write Multiplier : 1 This is the delay after the PC 1.x
Switch Signal Offset: 0 transfer switch is moved to any
Unknown of the sides, awaiting for the
Warning Size (Bits) : 8 fault to become active or
Delay Sign: U inactive.
Units: seconds
Lower Limit: 5
Upper Limit: 10
Default: 5
47037 Transfer Read Only 0. At Utility This is the status of the PC 1.x
Switch 1. At Genset transfer switch depending upon
Feedback the feedback received
Status 2. Unknown Position
3. Not Available

A029X159 (Issue 14) 39


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


47038 Transfer Read Only 0. Not Available This is the status of the PC 1.x
Retransfer 1. OFF transfer and retransfer process
Status 2. Transfer Start
3. Retransfer Start
4. Transfer Progress
5. Retransfer Progress
6. Transfer Complete
7. Retransfer Complete
8. Transfer Failed
9. Retransfer Failed
47039 Transfer Read Only 0. At Utility This is the status of the PC 1.x
Switch 1. At Genset transfer switch depending upon
the fault
2. Unknown Position
3. Not Available
47040 Clock Cycle Read Write 0. AM Used to set AM_PM Cycle or PC 1.x
1. PM Read the same

47041 Scheduler Read Write 0. AM User can set the AM/PM period PC 1.x
Prog Start 1. PM for Scheduler
Period
47042 Transfer Read Write 0. Disable Trim to enable transfer switch PC 1.x
Switch 1. Enable feedback logic
Feedback
Enable
47043 Fuel System Read Write 0. Diesel Type of fuel and ignition PC 1.x
1. Gas system used by genset

47044 Gas Fuel Read Write 0. Natural Gas Trim to set the type of gaseous PC 1.x
Type 1. Propane fuel
2. Dual
47045 Low Fuel Read Only 0.Inactive Displays Inactive/Active status PC 1.x
Pressure 1.Active of Switch
Switch
47046 Low Fuel Read Write 0. Active Closed State selection of Low fuel PC 1.x
Pressure 1. Active Open pressure switch
Switch Active
State
Selection
47047 LTA Read Only Multiplier : 1 The processed value of the PC 1.x
Temperature Offset: 0 LTA Temperature sensor for
the System IO Module
Size (Bits) : 16
Sign: S
Units: DegF
Lower Limit: NA
Upper Limit: NA
Default: NA
47048 Intake Read Write 0. Disabled Trim to enable the detection of PC 1.x
Manifold Over 1. Enabled Intake Manifold Backfire
Pressure(IMO condition
P) Enable
47049 Intake Read Write 0. SPN 105 Source for Intake Manifold PC 1.x
Manifold 1. SPN 52 Temperature. SPN 105 Default
Temperature Source and SPN 52 when the
Source IMOP is Enabled

40 A029X159 (Issue 14)


10-2015 3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


47050 Intake Read Write Multiplier : 0.1 Threshold to decide the Intake PC 1.x
Manifold Offset: 0 Manifold Backfire condition,
Temp Rate of Value entered is for degF/secs,
Change Size (Bits) : 8 degF/2secs is obtained by a
Threshold Sign: U scalar of 2 in PCC software
Units: DegF/sec
Lower Limit: 2
Upper Limit: 10
Default: 5
47051 Annunciator Read Only 0. Driver Off State of output as seen by the PC 1.x
Output 1 1.Driver On Annunciator
Status
47052 Annunciator Read Only 0. Driver Off State of output as seen by the PC 1.x
Output 1 1.Driver On Annunciator
Status
47053 Annunciator Read Only 0. Driver Off State of output as seen by the PC 1.x
Output 3 1.Driver On Annunciator
Status
47054 Annunciator Read Only 0. Driver Off State of output as seen by the PC 1.x
Output 4 1.Driver On Annunciator
Status
47055 KTA Fuel Read Only Multiplier : 0.1 The D.F.P for the KTA engines PC 1.x
Differential Offset: 0 high side sensor
Pressure
High Side Size (Bits) : 16
Sign: S
Units: PSI
Lower Limit: NA
Upper Limit: NA
Default: NA
47056 KTA Fuel Read Only Multiplier : 0.1 The D.F.P for the KTA engines PC 1.x
Differential Offset: 0 low side sensor
Pressure Low
Side Size (Bits) : 16
Sign: S
Units: PSI
Lower Limit: NA
Upper Limit: NA
Default: NA
47057 Air Shutoff Read Only Multiplier : 0.01 The Air Shutoff Valve Voltage PC 1.x
Valve Offset: 0 configured for SID sender input
Voltage 7 or 8. (Enabled only for Oil
Size (Bits) : 16 and Gas Features)
Sign: S
Units: Vdc
Lower Limit: NA
Upper Limit: NA
Default: NA

A029X159 (Issue 14) 41


3. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


47058 Percent Dirty Read Only Multiplier : 0.1 The calculated level at which PC 1.x
Fuel Filter Offset: 0 the fuel filter is clogged
Size (Bits) : 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
47059 QSK Read Only Multiplier : 0.1 The fuel pressure measure on PC 1.x
Differential Offset: 0 the QSK engines low side of
Pressure Low the fuel filter
Side Size (Bits) : 16
Sign: S
Units: PSI
Lower Limit: NA
Upper Limit: NA
Default: NA
47060 Main Relay Read Only Multiplier : 1 System IO Main Relay Status PC 1.x
Status Offset: 0
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
47061 Expansion Read Only Multiplier : 1 System IO Expansion Relay PC 1.x
Relay Status Offset: 0 Status
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA

42 A029X159 (Issue 14)


4 PowerCommand 2.x/3.x Modbus
Register Map
4.1 Modbus Communications
Use the following equation to calculate the value of 32-bit parameters.
• A = high register value
• B = low register value
parameter = (A * 65536 * multiplier) + (B * multiplier)
alternate formula: parameter = ((A*65536)+B)* multiplier
For example: Engine Running Time is a 32-bit parameter in registers 40070 and 40071.
• Register 40070 has 322 (high register value = A).
• Register 40071 has 15637 (low register value = B).
Engine Running Time = (322 * 65536 * 0.1) + (15637 * 0.1)
The engine run-time is 2111823 seconds, or 586.6 hours.
To write a 32-bit value to 2 Modbus registers, calculate the value for each register as follows:
• A (High register value) = INT ((Parameter / Multiplier) / 65536))
• B (Low register value) = INT ((Parameter / Multiplier) % (65536))
• % = Modulus (the remainder of integer division)
For example: To write Load Demand Genset Run Hours = 80000.5
• Register 40769 (high register value A) should be written to INT ((80000.5/0.1)/65536) = 12
• Register 40770 (low register value B) should be written to INT ((80000.5/.01)%65536) =
13573
To write 32-bit values to 2 modbus addresses always write the high register value followed by
the low register value. Both registers must be written to change the 32-bit value in the control.

4.2 Parametrics (Analog Values)


Unsupported (Not Available) Data=> "Not Available" data shall be represented as highest
positive value for that parameter. For example for a two byte, unsigned integer that would be
65535. For a signed integer that would be 32767.
• Parameters which are not available due to the sensor not being installed, or not enabled in
the controllers configuration will classified like this.
Network Failed Data=> "Network Failure" data shall be represented as three less than the
highest positive value for that parameter. For example for a two byte, unsigned integer that
would be 65532. For a signed integer that would be 32764.
• Data that comes from a network that has failed, such as sensors on the PCCnet I/O
Module or sensor data coming in via the CAN datalink will be classified like this.

A029X159 (Issue 14) 43


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Hardware/Component Failure=> "Hardware/Component Failure" data shall be represented as


four less than the highest positive value for that parameter. For example for a two byte,
unsigned integer that would be 65531. For a signed integer that would be 32763.
• A hardware/component failure that provides the data, such as the voltage, current and
power data that comes from an external metering chip will be classified like this.
Out of Range High/Out of Range=> "Out of Range High/Out of Range" data shall be
represented as one less than the highest positive value for that parameter. For example for a
two byte, unsigned integer that would be 65534. For a signed integer that would be 32766.
• Data that has been determined to be out of range high or out of range (when there is no
distinction between out of range high and out of range low) due to an open sensor for
example, will be classified like this.
Out of Range Low=> "Out of Range Low" data shall be represented as two less than the
highest positive value for that parameter. For example for a two byte, unsigned integer that
would be 65533. For a signed integer that would be 32765.
• Data that has been determined to be out of range low due to a shorted sensor for example,
will be classified like this.
Data within Normal Operating Range (Valid)=> Anything other than above.

NOTICE
Earlier versions of software may not support all of the Modbus registers in the following
table. If a particular register is not available in your installation, it is possible that the
Modbus connection is working but the controller software does not support that
particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

NOTICE
The Master device can read 1-40 contiguous registers, write 1-40 contiguous registers,
or read diagnostic counters.

NOTICE
The lowest Modbus register value is considered as the High Register Value and the
highest Modbus register value is considered as the Low Register Value.

44 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40010 Control Read Only 0: Off Current position of the PC 2.x,
Switch 1: Auto generator set switch panel PC 3.x
Position Off-Run-Auto switch as seen
2: Manual by the generator set control.
SEE ALSO ADDRESS
40580.
NOTE: Both address 40580
and 40010 show the same
information however the
specification for each is
different.
40011 Genset Run Read Only 0: Stop Current genset operating PC 2.x,
Sequence 1: Time Delay to Start mode. Modbus mapping shall PC3.x
State be in both addresses 43500
2: Warmup at Idle and 40011
3: Rated Freq and Voltage
4: Cooldown / Stop Delay
5: Cooldown at Idle
6: Rated to Idle Transition
Delay
40012 Most Recent Read Only Multiplier: 1 This Modbus Register PC 2.x,
Fault or Offset: 0 displays most recent Fault or PC 3.x
Warning Warning. It is not mapped
Size (bits): 16 with any logical.
Sign: U
Unit:
Lower Limit:
Upper Limit: 65530
40013 Modbus Read Only 0: None This register returns the Fault PC 2.x,
register 1: Warning Type of the Fault Code. This PC 3.x
40013 is not associated with any
2: Shutdown logical.
40014 Genset % Read Only Multiplier: 0.01 Monitors the total generator PC 2.x,
Standby Total Offset: 0 set standby KW percentage PC 3.x
kW output.
Size (bits): 16
Sign: S
Unit: %
Lower Limit:
Upper Limit:
40016 NFPA 110 Read Only Multiplier: 1.0 16-bit number to represent PC 2.x,
Logical Offset: 0 the status of the NFPA 110 PC 3.x
Status logical. See NFPA 110
Size (bits): 16 bitmap.
Sign: U
Unit:
Lower Limit:
Upper Limit:
40017 Extended Read Only Multiplier: 1.0 16-bit number to represent PC 2.x,
NFPA 110 Offset: 0 the status of the NFPA 110 PC 3.x
Logical logical. See NFPA 110
Status Size (bits): 16 bitmap.
Sign: U
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 45


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40018 Genset L1N Read Only Multiplier: 1 Generator set L1N voltage PC 2.x,
Voltage Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40019 Genset L2N Read Only Multiplier: 1 Generator set L2N voltage PC 2.x,
Voltage Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40020 Genset L3N Read Only Multiplier: 1 Generator set L3N voltage PC 2.x,
Voltage Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40021 Genset LN Read Only Multiplier : 1 Genset Line to Neutral PC 2.x,
Average Offset: 0 average voltage PC 3.x
Voltage
Size (Bits) : 16
Sign: U
Units: Vac
Upper Limit: NA
Default: 0
40022 Genset L1L2 Read Only Multiplier: 1 Generator set L1L2 voltage PC 2.x,
Voltage Lower Limit: NA PC 3.x
Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40023 Genset L2L3 Read Only Multiplier: 1 Generator set L2L3 voltage PC 2.x,
Voltage Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40024 Genset L3L1 Read Only Multiplier: 1 Generator set L3L1 voltage PC 2.x,
Voltage Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

46 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40025 Genset LL Read Only Multiplier: 1 Generator set Line to Line PC 2.x,
Average Offset: 0 average voltage PC 3.x
Voltage
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40026 Genset L1 Read Only Multiplier: 1 Monitors the generator set L1 PC 2.x,
Current Offset: 0 current value. PC 3.x
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:
40027 Genset L2 Read Only Multiplier: 1 Generator set L2 current PC 2.x,
Current Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:
40028 Genset L3 Read Only Multiplier: 1 Generator set L3 current PC 2.x,
Current Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:
40029 Genset Read Only Multiplier: 1 Generator set average PC 2.x,
Average Offset: 0 current PC 3.x
Current
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:
40030 Genset Read Only Multiplier: 1 Generator set neutral current PC 3.x
Neutral Offset: 0
Current
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:
40031 Genset L1 Read Only Multiplier: 1 Generator set L1 kW PC 2.x,
kW Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: kW
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 47


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40032 Genset L2 Read Only Multiplier: 1 Generator set L2 kW PC 2.x,
kW Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: kW
Lower Limit: -32768
Upper Limit: 32762
40033 Genset L3 Read Only Multiplier: 1 Generator set L3 kW PC 2.x,
kW Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: kW
Lower Limit: -32768
Upper Limit: 32762
40034 Genset Total Read Only Multiplier: 1 Generator set total kW PC 2.x,
kW Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: kW
Lower Limit:
Upper Limit:
40035 Genset L1 Read Only Multiplier: 1 Generator set L1 kVAR PC 2.x,
kVAR Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit:
40036 Genset L2 Read Only Multiplier: 1 Generator set L2 kVAR PC 2.x,
kVAR Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit: -32768
Upper Limit: 32762
40037 Genset L3 Read Only Multiplier: 1 Generator set L3 kVAR PC 2.x,
kVAR Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit
40038 Genset Total Read Only Multiplier: 1 Generator set total kVAR PC 2.x,
kVAR Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit

48 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40039 Genset Total Read Only Multiplier: 0.01 Generator set total power PC 2.x,
Power Factor Offset: 0 factor (L1+L2+L3) PC 3.x
Size (bits): 8
Sign: S
Unit: PF
Lower Limit:
Upper Limit
40040 Genset L1 Read Only Multiplier: 1 Generator set L1 kVA PC 2.x,
kVA Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit
40041 Genset L2 Read Only Multiplier: 1 Generator set L2 kVA PC 2.x,
kVA Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit
40042 Genset L3 Read Only Multiplier: 1 Generator set L3 kVA PC 2.x,
kVA Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit kVA
Lower Limit:
Upper Limit
40043 Genset Total Read Only Multiplier: 1 Generator set total kVA PC 2.x,
kVA Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit
40044 Genset Read Only Multiplier : 0.01 Genset Frequency OP. PC 2.X,
Frequency Offset: 0 Modbus has different PC 3.X
OP multiplier than PCCnet. For
Size (bits): 16 Modbus use only,
Sign: U Multiplier/Units = 0.1 Hz
Unit: Hz
Lower Limit: NA
Upper Limit: NA
40046 Genset Total Read Only Multiplier: 1 Generator set total negative PC 2.x,
Negative kWh Offset: 0 kWh accumulation PC 3.x
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 49


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40047 Genset Total Read Only Multiplier: 1 Generator set total negative PC 2.x,
Negative kWh Offset: 0 kWh accumulation PC 3.x
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:
40048 Genset Total Read Only Multiplier: 1 Generator set total positive PC 2.x,
Positive kWh Offset: 0 kWh accumulation PC 3.x
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit: 0
Upper Limit: 4294967290
40049 Genset Total Read Only Multiplier: 1 Generator set total positive PC 2.x,
Positive kWh Offset: 0 kWh accumulation PC 3.x
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit: 0
Upper Limit: 4294967290
40050 Genset Total Read Only Multiplier: 1 Generator set total net kWh PC 2.x,
Net kWh Offset: 0 accumulation PC 3.x
Size (bits): 32
Sign: S
Unit: kWh
Lower Limit: -2147483648
Upper Limit: 2147483643
40051 Genset Total Read Only Multiplier: 1 Generator set total net kWh PC 2.x,
Net kWh Offset: 0 accumulation PC 3.x
Size (bits): 32
Sign: S
Unit: kWh
Lower Limit: -2147483648
Upper Limit: 2147483643
40052 Genset Total Read Only Multiplier: 1 Generator set total negative PC 2.x,
Negative Offset: 0 kVARh accumulation PC 3.x
kVARh
Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:
40053 Genset Total Read Only Multiplier: 1 Generator set total negative PC 2.x,
Negative Offset: 0 kVARh accumulation PC 3.x
kVARh
Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:

50 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40054 Genset Total Read Only Multiplier: 1 Generator set total positive PC 2.x,
Positive Offset: 0 kVARh accumulation PC 3.x
kVARh
Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit: 0
Upper Limit: 4294967290
40055 Genset Total Read Only Multiplier: 1 Generator set total positive PC 2.x,
Positive Offset: 0 kVARh accumulation PC 3.x
kVARh
Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit: 0
Upper Limit: 4294967290
40056 Genset Total Read Only Multiplier: 1 Generator set total net PC 2.x,
Net kVARh Offset: 0 kVARh accumulation PC 3.x
Size (bits): 32
Sign: S
Unit: kVARh
Lower Limit: -2147483648
Upper Limit: 2147483643
40057 Generator set Read Only Multiplier: 1 Generator set total net PC 2.x,
Total Net Offset: 0 kVARh accumulation PC 3.x
kVARh
Size (bits): 32
Sign: S
Unit: kVARh
Lower Limit: -2147483648
Upper Limit: 2147483643
40058 Genset % Read Only Multiplier: 0.1 Monitors the generator set PC 2.x,
Standby L1 Offset: 0 standby L1 current PC 3.x
Current percentage output.
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
40059 Genset % Read Only Multiplier: 0.1 Monitors the generator set PC 2.x,
Standby L2 Offset: 0 standby L2 current PC 3.x
Current percentage output.
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
40060 Genset % Read Only Multiplier: 0.1 Monitors the generator set PC 2.x,
Standby L3 Offset: 0 standby L3 current PC 3.x
Current percentage output.
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 51


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40061 Battery Read Only Multiplier: 0.1 Battery voltage value. PC 2.x,
Voltage Offset: 0 Modbus and PCCNet has PC 3.x
different multiplier value. For
Size (bits): 16 Modbus use only,
Sign: U multiplier/units = 0.1 volts
Unit: Vdc
Lower Limit:
Upper Limit:
40062 Oil Pressure Read Only Multiplier: 1 Monitor point for the Oil PC 2.x,
Offset: 0 Pressure. Modbus and PC 3.x
PCCNet have different
Size (bits): 16 multiplier value. For Modbus
Sign: U use only, Multiplier/Units =
Unit: kPa 1kPa
Lower Limit:
Upper Limit:
40063 Oil Read Only Multiplier: 0.1 Monitor point for the Oil PC 2.x,
Temperature Offset: 0 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit:
Upper Limit:
40064 Coolant Read Only Multiplier: 0.1 Monitor point for the Coolant PC 2.x,
Temperature Offset: 0 Temperature. Modbus PC 3.x
mapping shall be to both
Size (bits): 16 46126 and 40064 addresses.
Sign: S For Modbus use only,
Unit: degC Multiplier/Units = 0.1C
Lower Limit:
Upper Limit:
40065 Intake Read Only Multiplier: 0.1 To monitor Intake Manifold PC 2.x,
Manifold Offset: 0 Temperature. This parameter PC 3.x
Temperature represents ”Intake Manifold
Size (bits): 16 Temperature 1”.
Sign: S
Unit: degF
Lower Limit: -40
Upper Limit: 410
40065 Intake Read Only Multiplier: 0.1 To monitor Intake Manifold PC 2.x,
Manifold Offset: 0 Temperature. This parameter PC 3.x
Temperature represents ”Intake Manifold
Size (bits): 16 Temperature 1”.
Sign: S
Unit: degF
Lower Limit: -40
Upper Limit: 410

52 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40066 Fuel Read Only Multiplier: 0.1 Monitor point for the Fuel PC 2.x,
Temperature Offset: 0 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -40
Upper Limit: 410
40067 Fuel Rate Read Only Multiplier: 0.05 Monitor point for the Fuel PC 2.x,
Offset: 0 Rate PC 3.x
Size (bits): 16
Sign: S
Unit: gal/hr
Lower Limit:
Upper Limit:
40068 Average Read Only Multiplier: 1 Monitor point for the Average PC 2.x,
Engine Offset: 0 Engine Speed. Modbus and PC 3.x
Speed PCCNet have different
Size (bits): 16 multiplier value. For Modbus
Sign: U use only, Multiplier/Units = 1
Unit: RPM RPM
Lower Limit:
Upper Limit:
40069 Total Start Read Only Multiplier : 1 Total number of start PC 2.X,
Attempts OP Offset: 0 attempts PC3.X
Size (bits): 16
Sign: U
Unit: NAr
Lower Limit: 0
Upper Limit: 65535
40070 Engine Read Only Multiplier: 0.1 Total engine run time. PC 2.x,
Running Time Offset: 0 Modbus has different PC 3.x
multiplier than PCCNet. For
Size (bits): 32 Modbus use only,
Sign: U multiplier/units = 0.1 Sec
Unit: seconds
Lower Limit:
Upper Limit:
40071 Engine Read Only Multiplier: 0.1 Total engine run time. PC 2.x,
Running Time Offset: 0 Modbus has different PC 3.x
multiplier than PCCnet. For
Size (bits): 32 Modbus use only,
Sign: U multiplier/units = 0.1 Sec
Unit: seconds
Lower Limit:
Upper Limit:
40072 Total Fuel Read Only Multiplier: 0.1 Total fuel consumption since PC 2.x,
Consumption Offset: 0 start of engine. PC 3.x
Size (bits): 32
Sign: U
Unit: gallons
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 53


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40073 Total Fuel Read Only Multiplier: 0.1 Total fuel consumption since PC 2.x,
Consumption Offset: 0 start of engine. PC 3.x
Size (bits): 32
Sign: U
Unit: gallons
Lower Limit:
Upper Limit:
40074 Total Number Read Only Multiplier: 1 Total number of generator set PC 2.x,
of Runs Offset: 0 runs. PC 3.x
Size (bits): 32
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967295

40075 Total Number Read Only Multiplier: 1 Total number of generator set PC 2.x,
of Runs Offset: 0 runs. PC 3.x
Size (bits): 32
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967295
40076 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Run Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40076-
40092 for 17 char of this
string.
40077 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Run Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40076-
40092 for 17 char of this
string.
40078 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Run Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40076 -
40092 for 17 char of this
string.

54 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40079 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Run Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40076-
40092 for 17 char of this
string.
40080 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Run Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40076-
40092 for 17 char of this
string.
40081 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Run Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40076-
40092 for 17 char of this
string.
40082 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Run Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40076-
40092 for 17 char of this
string.
40083 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Run Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40076-
40092 for 17 char of this
string.

A029X159 (Issue 14) 55


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40084 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Run Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40076-
40092 for 17 char of this
string.
40085 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Run Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40076-
40092 for 17 char of this
string.
40086 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Run Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40076-
40092 for 17 char of this
string.
40087 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Run Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40076-
40092 for 17 char of this
string.
40088 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Run Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40076-
40092 for 17 char of this
string.

56 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40089 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Run Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40076-
40092 for 17 char of this
string.
40090 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Run Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40076-
40092 for 17 char of this
string.
40091 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Run Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40076-
40092 for 17 char of this
string.
40092 Runs Reset Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Time Offset: 0 record of the last time the PC 3.x
Run Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40076-
40092 for 17 char of this
string.
40096 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Start Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40096-
0112 for 17 char of this string.

A029X159 (Issue 14) 57


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40097 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Start Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40096-
0112 for 17 char of this string.
40098 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Start Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40096-
0112 for 17 char of this string.
40099 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Start Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40096-
0112 for 17 char of this string.
40100 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Start Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40096-
0112 for 17 char of this string.
40101 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Start Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40096-
0112 for 17 char of this string.
40102 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Start Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40096-
0112 for 17 char of this string.

58 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40103 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Start Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40096-
0112 for 17 char of this string.
40104 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Start Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40096-
0112 for 17 char of this string.
40105 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Start Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40096-
0112 for 17 char of this string.
40106 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Start Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40096-
0112 for 17 char of this string.
40107 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Start Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40096-
0112 for 17 char of this string.
40108 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Start Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40096-
0112 for 17 char of this string.

A029X159 (Issue 14) 59


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40109 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Start Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40096-
0112 for 17 char of this string.
40110 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Start Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40096-
0112 for 17 char of this string.
40111 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Start Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40096-
0112 for 17 char of this string.
40112 Start Read Only Multiplier: 1 Real Time Clock stamp PC 2.x,
Attempts Offset: 0 record of the last time the PC 3.x
Reset Time Start Attempts were reset.
Size (bits): 144 This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus
implementation or the Real
Upper Limit: time stamp will use 40096-
0112 for 17 char of this string.
40118 Utility L1N Read Only Multiplier: 1 Utility L1N voltage PC 3.x
Voltage Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

40119 Utility L2N Read Only Multiplier: 1 Utility L2N voltage PC 3.x
Voltage Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

60 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40120 Utility L3N Read Only Multiplier: 1 Utility L3N voltage PC 3.x
Voltage Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40121 Utility LN Read Only Multiplier : 1 Utility Line to Neutral average PC3.X
Average Offset: 0 voltage
Voltage Size (bits): 16
Sign: U
Unit: Vac
Lower Limit: NA
Upper Limit: NA
40122 Utility L1L2 Read Only Multiplier: 1 Utility L1L2 voltage PC 3.x
Voltage Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40123 Utility L2L3 Read Only Multiplier: 1 Utility L2L3 voltage PC 3.x
Voltage Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40124 Utility L3L1 Read Only Multiplier: 1 Utility L3L1 voltage PC 3.x
Voltage Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40125 Utility LL Read Only Multiplier: 1 Utility Line to Line average PC 3.x
Average Offset: 0 voltage
Voltage
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40126 Utility L1 Read Only Multiplier: 1 Utility L1 current PC 3.x
Current Offset: 0
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 61


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40127 Utility L2 Read Only Multiplier: 1 Utility L2 current PC 3.x
Current Offset: 0
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:
40128 Utility L3 Read Only Multiplier: 1 Utility L3 current PC 3.x
Current Offset: 0
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:
Offset: 0
40129 Utility Read Only Multiplier : 1 Utility average current PC 3.x
Average Offset: 0
Current
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit: NA
Upper Limit: NA
Default: NA
40131 Utility L1 kW Read Only Multiplier: 1 Utility L1 kW PC 3.x
Offset: 0
Size (bits): 16
Sign: S
Unit: kW
Lower Limit:
Upper Limit:

40132 Utility L2 kW Read Only Multiplier: 1 Utility L2 kW PC 3.x


Offset: 0
Size (bits): 16
Sign: S
Unit: kW
Lower Limit:
Upper Limit:
40133 Utility L3 kW Read Only Multiplier: 1 Utility L3 kW PC 3.x
Offset: 0
Size (bits): 16
Sign: S
Unit: kW
Lower Limit:
Upper Limit:

62 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40134 Utility Total Read Only Multiplier: 1 Utility total kW PC 3.x
kW Offset: 0
Size (bits): 16
Sign: S
Unit: kW
Lower Limit:
Upper Limit:
40135 Utility L1 Read Only Multiplier: 1 Utility L1 kVAR PC 3.x
kVAR Offset: 0
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit:

40136 Utility L2 Read Only Multiplier: 1 Utility L2 kVAR PC 3.x


kVAR Offset: 0
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit:
40137 Utility L3 Read Only Multiplier: 1 Utility L3 kVAR PC 3.x
kVAR Offset: 0
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit:
40138 Utility Total Read Only Multiplier: 1 Utility total kVAR PC 3.x
kVAR Offset: 0
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit:
40139 Utility Total Read Only Multiplier: 0.01 Utility total power factor PC 3.x
Power Factor Offset: 0
Size (bits): 8
Sign: S
Unit: PF
Lower Limit:
Upper Limit:
40140 Utility L1 kVA Read Only Multiplier: 1 Utility L1 kVA PC 3.x
Offset: 0
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 63


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40141 Utility L2 kVA Read Only Multiplier: 1 Utility L2 kVA PC 3.x
Offset: 0
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:
40142 Utility L3 kVA Read Only Multiplier: 1 Utility L3 kVA PC 3.x
Offset: 0
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:
40143 Utility Total Read Only Multiplier: 1 Utility total kVA PC 3.x
kVA Offset: 0
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:
40144 Utility Read Only Multiplier: 0.001 Utility line frequency PC 3.x
Frequency Offset: 0
Size (bits): 32
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
40145 Utility Read Only Multiplier: 0.001 Utility line frequency PC 3.x
Frequency Offset: 0
Size (bits): 32
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
40146 Utility Total Read Only Multiplier: 1 Utility total negative kWh PC 3.x
Negative kWh Offset: 0 accumulation
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:

40147 Utility Total Read Only Multiplier: 1 Utility total negative kWh PC 3.x
Negative kWh Offset: 0 accumulation
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:

64 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40148 Utility Total Read Only Multiplier: 1 Utility total positive kWh PC 3.x
Positive kWh Offset: 0 accumulation
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:
40149 Utility Total Read Only Multiplier: 1 Utility total positive kWh PC 3.x
Positive kWh Offset: 0 accumulation
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:
40150 Utility Total Read Only Multiplier: 1 Utility total net kWh PC 3.x
Net kWh Offset: 0 accumulation
Size (bits): 32
Sign: S
Unit: kWh
Lower Limit:
Upper Limit:
40151 Utility Total Read Only Multiplier: 1 Utility total net kWh PC 3.x
Net kWh Offset: 0 accumulation
Size (bits): 32
Sign: S
Unit: kWh
Lower Limit:
Upper Limit:
40152 Utility Total Read Only Multiplier: 1 Utility total negative kVARh PC 3.x
Negative Offset: 0 accumulation
kVARh
Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:
40153 Utility Total Read Only Multiplier: 1 Utility total negative kVARh PC 3.x
Negative Offset: 0 accumulation
kVARh
Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:
40154 Utility Total Read Only Multiplier: 1 Utility total positive kVARh PC 3.x
Positive Offset: 0 accumulation
kVARh
Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 65


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40155 Utility Total Read Only Multiplier: 1 Utility total positive kVARh PC 3.x
Positive Offset: 0 accumulation
kVARh
Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:
40156 Utility Total Read Only Multiplier: 1 Utility total net kVARh PC 3.x
Net kVARh Offset: 0 accumulation
Size (bits): 32
Sign: S
Unit: kVARh
Lower Limit:
Upper Limit:
40157 Utility Total Read Only Multiplier: 1 Utility total net kVARh PC 3.x
Net kVARh Offset: 0 accumulation
Size (bits): 32
Sign: S
Unit: kVARh
Lower Limit:
Upper Limit:
40158 Genset Bus Read Only Multiplier: 1 Generator set Bus L1N PC 3.x
L1N Voltage Offset: 0 voltage
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

40159 Genset Bus Read Only Multiplier: 1 Generator set Bus L2N PC 3.x
L2N Voltage Offset: 0 voltage
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40160 Genset Bus Read Only Multiplier: 1 Generator set Bus L3N PC 3.x
L3N Voltage Offset: 0 voltage
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40161 Genset Bus Read Only Multiplier : 1 Genset Bus Line to Neutral PC 3.x
LN Average Offset: 0 average voltage
Voltage
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

66 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40162 Genset Bus Read Only Multiplier: 1 Generator set Bus L1L2 PC 3.x
L1L2 Voltage Offset: 0 voltage
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40163 Genset Bus Read Only Multiplier: 1 Generator set Bus L2L3 PC 3.x
L2L3 Voltage Offset: 0 voltage
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40164 Genset Bus Read Only Multiplier: 1 Generator set Bus L3L1 PC 3.x
L3L1 Voltage Offset: 0 voltage
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40165 Genset Bus Read Only Multiplier: 1 Generator set Bus Line to PC 3.x
LL Average Offset: 0 Line average voltage
Voltage
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40166 Genset Bus Read Only Multiplier: 1 Generator set Bus L1 current PC 3.x
L1 Current Offset: 0
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit: 0
Upper Limit: 65530
40167 Genset Bus Read Only Multiplier: 1 Generator set Bus L2 current PC 3.x
L2 Current Offset: 0
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:
40168 Genset Bus Read Only Multiplier: 1 Generator set Bus L3 current PC 3.x
L3 Current Offset: 0
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 67


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40169 Genset Bus Read Only Multiplier : 1 Genset Bus Average current PC3.X
Average Offset: 0
Current
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit: NA
Upper Limit: NA
40171 Genset Bus Read Only Multiplier: 1 Generator set Bus L1 kW PC 3.x
L1 kW Offset: 0
Size (bits): 16
Sign: S
Unit: kW
Lower Limit: -32768
Upper Limit: 32762
40172 Genset Bus Read Only Multiplier: 1 Generator set Bus L2 kW PC 3.x
L2 kW Offset: 0
Size (bits): 16
Sign: S
Unit: kW
Lower Limit: -32768
Upper Limit: 32762
40173 Genset Bus Read Only Multiplier: 1 Generator set Bus L3 kW PC 3.x
L3 kW Offset: 0
Size (bits): 16
Sign: S
Unit: kW
Lower Limit:
Upper Limit:
40174 Genset Bus Read Only Multiplier: 1 Generator set Bus total kW PC 3.x
Total kW Offset: 0
Size (bits): 16
Sign: S
Unit: kW
Lower Limit:
Upper Limit:
40175 Genset Bus Read Only Multiplier: 1 Generator set bus L1 kVar PC 3.x
L1 kVAR Offset: 0
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit: -32678
Upper Limit: 32672
40176 Genset Bus Read Only Multiplier: 1 Generator set bus L2 kVAR PC 3.x
L2 kVAR Offset: 0
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit: -32678
Upper Limit: 32672

68 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40177 Genset Bus Read Only Multiplier: 1 Generator set bus L3 kVAR PC 3.x
L3 kVAR Offset: 0
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit:
40178 Genset Bus Read Only Multiplier: 1 Generator set bus total kVAR PC 3.x
Total kVAR Offset: 0
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit:
40179 Genset Bus Read Only Multiplier: 0.01 Generator set Bus Total PC 3.x
Total Power Offset: 0 power factor
Factor
Size (bits): 8
Sign: S
Unit: PF
Lower Limit:
Upper Limit:
40180 Genset Bus Read Only Multiplier: 1 Generator set Bus L1 kVA PC 3.x
L1 kVA Offset: 0
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:
40181 Genset Bus Read Only Multiplier: 1 Generator set Bus L2 kVA PC 3.x
L2 kVA Offset: 0
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:
40182 Genset Bus Read Only Multiplier: 1 Generator set Bus L3 kVA PC 3.x
L3 kVA Offset: 0
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:
40183 Genset Bus Read Only Multiplier: 1 Generator set bus total kVA PC 3.x
Total kVA Offset: 0
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 69


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40184 Genset Bus Read Only Multiplier: 0.001 Generator set bus line PC 3.x
Frequency Offset: 0 frequency
Size (bits): 32
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
40185 Genset Bus Read Only Multiplier: 0.001 Generator set bus line PC 3.x
Frequency Offset: 0 frequency
Size (bits): 32
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
40186 Genset Bus Read Only Multiplier: 1 Generator set bus total PC 3.x
Total Offset: 0 negative kWh accumulation
Negative kWh
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:
40187 Genset Bus Read Only Multiplier: 1 Generator set bus total PC 3.x
Total Offset: 0 negative kWh accumulation
Negative kWh
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:
40188 Genset Bus Read Only Multiplier: 1 Generator set bus total PC 3.x
Total Positive Offset: 0 positive kWh accumulation
kWh
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:
40189 Genset Bus Read Only Multiplier: 1 Generator set bus total PC 3.x
Total Positive Offset: 0 positive kWh accumulation
kWh
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:
40190 Genset Bus Read Only Multiplier: 1 Generator set bus total net PC 3.x
Total Net Offset: 0 kWh accumulation
kWh
Size (bits): 32
Sign: S
Unit: kWh
Lower Limit:
Upper Limit:

70 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40191 Genset Bus Read Only Multiplier: 1 Generator set bus total net PC 3.x
Total Net Offset: 0 kWh accumulation
kWh
Size (bits): 32
Sign: S
Unit: kWh
Lower Limit:
Upper Limit:
40192 Genset Bus Read Only Multiplier: 1 Generator set bus total PC 3.x
Total Offset: 0 negative kVARh accumulation
Negative
kVARh Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:
40193 Genset Bus Read Only Multiplier: 1 Generator set bus total PC 3.x
Total Offset: 0 negative kVARh accumulation
Negative
kVARh Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:
40194 Genset Bus Read Only Multiplier: 1 Generator set bus total PC 3.x
Total Positive Offset: 0 positive kVARh accumulation
kVARh
Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:
40195 Genset Bus Read Only Multiplier: 1 Generator set bus total PC 3.x
Total Positive Offset: 0 positive kVARh accumulation
kVARh
Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:
40196 Genset Bus Read Only Multiplier: 1 Generator set Bus total net PC 3.x
Total Net Offset: 0 kVARh accumulation
kVARh
Size (bits): 32
Sign: S
Unit: kVARh
Lower Limit:
Upper Limit:
40197 Genset Bus Read Only Multiplier: 1 Generator set Bus total net PC 3.x
Total Net Offset: 0 kVARh accumulation
kVARh
Size (bits): 32
Sign: S
Unit: kVARh
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 71


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40198 Ground Read Only Multiplier: 0.1 Ground current PC 3.x
Current Offset: 0
Size (bits): 16
Sign: U
Unit: amp
Lower Limit:
Upper Limit:
40199 Genset Read Only Multiplier: 0.01 Generator set Negative PC 3.x
Negative Offset: 0 Sequence Current as Percent
Sequence of Standby Current Rating
Current % Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
40201 Coolant Read Only 0: PGBU Either PGBU(Onan) or PC 2.x,
Temperature 1: EBU EBU(Cummins) sensor. PC 3.x
Sensor Type
40207 Battery Read Only Multiplier: 0.001 The Battery Charger PC 2.x,
Charger Offset: 0 Alternator Flash Voltage after PC 3.x
Alternator all scaling and validity
Flash Voltage Size (bits): 16 checks.
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 35
40208 Battery 1 Read Only Multiplier : 0.01 Battery 1 Voltage measured PC 3.x
Voltage Offset: 0 through AUX101. Applicable
(Aux101) when multiple batteries are
Size (bits): 16 used.
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 3850
Default: NA
40209 Battery 2 Read Only Multiplier : 0.01 Battery 2 Voltage measured PC 3.x
Voltage Offset: 0 through AUX101. Applicable
(Aux101) when multiple batteries are
Size (bits): 16 used.
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 3850
Default: NA
40210 External Read Only Multiplier: 0.01 Monitor point for the external PC 2.x,
Speed Bias Offset: 0 speed bias input. PC 3.x
Input
Size (bits): 16
Sign: S
Unit: %
Lower Limit: -100
Upper Limit: 100

72 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40211 External Read Only Multiplier: 0.01 Monitor point for the external PC 2.x,
Voltage Bias Offset: 0 voltage bias input. PC 3.x
Input
Size (bits): 16
Sign: S
Unit: %
Lower Limit: -100
Upper Limit: 100
40212 Battery 3 Read Only Multiplier : 0.01 Battery 3 Voltage measured PC 3.x
Voltage Offset: 0 through AUX101. Applicable
(Aux101) when multiple batteries are
Size (bits): 16 used.
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 3850
Default: NA
40213 Battery 4 Read Only Multiplier : 0.01 Battery 4 Voltage measured PC 3.x
Voltage Offset: 0 through AUX101. Applicable
(Aux101) when multiple batteries are
Size (bits): 16 used.
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 3850
Default: NA
40214 kVAR Load Read Only Multiplier : 0.01 EU scaled value for the kVAR PC 3.x
Setpoint Offset: 0 load setpoint
Size (bits): 16
Sign: S
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
40217 kVAR Load Read Only Multiplier : 0.01 EU Scaled value for the PC 3.x
Share Level Offset: 0 kVAR load share level analog
input
Size (bits): 16
Sign: S
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
40219 kW load Read Only Multiplier : 0.01 EU scaled value for the kW PC 3.x
setpoint Offset: 0 load setpoint
Size (bits): 16
Sign: S
Unit: %
Lower Limit:
Upper Limit: 125.01
Default: NA

A029X159 (Issue 14) 73


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40222 kW Load Read Only Multiplier : 0.01 EU Scaled value for the kW PC 3.x
Share Level Offset: 0 load share level analog input
Size (bits): 16
Sign: S
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
40224 kVAR Load Read Only Multiplier : 0.1 uA signal being injected into PC 3.x
Share Output Offset: 0 a 10K ohm resistor network
Predictor
Size (bits): 16
Sign: S
Unit: uA
Lower Limit: NA
Upper Limit: NA
Default: NA
40225 KW Load Read Only Multiplier : 0.1 uA signal being injected into PC 3.x
Share Output Offset: 0 a 10K ohm resistor network
Predictor
Size (bits): 16
Sign: S
Unit: uA
Lower Limit: NA
Upper Limit: NA
Default: NA
40226 Speed Bias Read Only Multiplier: 0.01 Configurable analog output PC 3.x
Output / Offset: 0 voltage output value
Configurable (predicted)
Analog output Size (bits): 16
#1 Output Sign: S
Predictor Unit: Vdc
Lower Limit: NA
Upper Limit: NA
40227 Voltage Bias Read Only Multiplier: 0.01 Configurable analog output PC 3.x
Output / Offset: 0 voltage output value
Configurable (predicted)
Analog output Size (bits): 16
#2 Output Sign: S
Predictor Unit: Vdc
Lower Limit:
Upper Limit:
40228 Amber Read Only 0: Inactive Engine Control System PC 2.x,
Warning 1: Active indicates a warning condition. PC 3.x
Lamp Status
40229 Barometric Read Only Multiplier: 0.1 Monitor point for the PC 2.x,
Absolute Offset: 0 Barometric Absolute PC 3.x
Pressure Pressure. Displayed as
Size (bits): 16 ”Ambient Pressure” in the
Sign: U HMI.
Unit: psi
Lower Limit:
Upper Limit:

74 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40230 Boost Read Only Multiplier: 0.1 Monitor point for the Boost PC 2.x,
Pressure Offset: 0 Absolute Pressure PC 3.x
Size (bits): 16
Sign: U
Unit: psi
Lower Limit:
Upper Limit:
40231 CAN Datalink Read Only 0: Inactive Indicates the status of the PC 2.x,
Status 1: Active CAN datalink PC 3.x
2: Failed
40232 Crankcase Read Only Multiplier: 0.1 Monitor point for the PC 2.x,
Pressure Offset: 0 Crankcase Pressure. PC 3.x
Size (bits): 16
Sign: S
Unit: psi
Lower Limit: -35.67
Upper Limit: 38
40235 ECM Derate Read Only 0: No Derate Request Request made by the ECS for PC 2.x,
Request 1: Derate Request a reduction in load PC 3.x
2: Error
3: Don’t Care
40236 Engine Read Only 0: ECM Monitor point for the output of PC 2.x,
Application 1: Hydro-Mechanical the Engine application type. PC 3.x
Type Either ECM (CAN) or Hydro-
Mechanical.
40237 Engine State Read Only 0: Stop ECS engine state indication PC 2.x,
1: Ventilation PC 3.x
2: Start
3: Run
4: Normal Shutdown
5: Emergency Shutdown
6: Error
7: Don’t Care
8: Rapid Start
9: Reserved
10: Reserved
11: Reserved
12: Reserved
13: Reserved
14: Reserved
15: Don’t Care / Take No
Action
40238 PGI Major Read Only Multiplier :1 Displays Power Generation PC 3.x
Version Offset: 0 Interface Major Version to
which Engine Software is
Size (bits): 8 complying
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 225
Default: NA

A029X159 (Issue 14) 75


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40239 PGI Minor Read Only Multiplier :1 Displays Power Generation PC 3.x
Version Offset: 0 Interface Minor Version to
which Engine Software is
Size (bits): 8 complying
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 225
Default: NA
40240 PGI Read Only Multiplier :1 Displays Power Generation PC 3.x
Informational Offset: 0 Interface Informational
Version Version to which Engine
Size (bits): 8 Software is complying
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 225
Default: NA
40242 Aftercooler Read Only Multiplier: 0.1 Monitor point for the PC 2.x,
Temperature Offset: 0 Aftercooler Temperature. PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -40
Upper Limit: 410
Default: NA
40243 Internal ECM Read Only Multiplier : 0.1 Internal temperature of the PC 3.x
Module 1 Offset: 0 engine electronic control
Temperature module 1
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: NA
Upper Limit: NA
Default: NA
40244 Internal ECM Read Only Multiplier : 0.1 Internal temperature of the PC 3.x
Module 2 Offset: 0 engine electronic control
Temperature module 2
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: NA
Upper Limit: NA
Default: NA
40245 Internal ECM Read Only Multiplier : 0.1 Internal temperature of the PC 3.x
Module 3 Offset: 0 engine electronic control
Temperature module 3
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: NA
Upper Limit: NA
Default: NA

76 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40246 Internal ECM Read Only Multiplier : 0.1 Internal temperature of the PC 3.x
Module 4 Offset: 0 engine electronic control
Temperature module 4
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: NA
Upper Limit: NA
Default: NA
40247 ECM Module Read Only Multiplier : 0.1 Engine Control Module 1 PC 3.x
1 Battery Offset: 0 Battery Voltage.
Voltage
Size (bits): 16
Sign: U
Units: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA
40248 ECM Module Read Only Multiplier : 0.1 Engine Control Module 2 PC 3.x
2 Battery Offset: 0 Battery Voltage.
Voltage
Size (bits): 16
Sign: U
Units: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA
40249 ECM Module Read Only Multiplier : 0.1 Engine Control Module 3 PC 3.x
3 Battery Offset: 0 Battery Voltage.
Voltage
Size (bits): 16
Sign: U
Units: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA
40250 ECM Module Read Only Multiplier : 0.1 Engine Control Module 4 PC 3.x
4 Battery Offset: 0 Battery Voltage.
Voltage
Size (bits): 16
Sign: U
Units: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA
40254 Fuel Supply Read Only Multiplier: 0.1 Monitor point for the Fuel PC 2.x,
Pressure Offset: 0 Supply Pressure. Displayed PC 3.x
as ”Fuel Supply Pressure” in
Size (bits): 16 the HMI.
Sign: U
Unit: psi
Lower Limit: 0
Upper Limit: 145

A029X159 (Issue 14) 77


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40257 Intake Read Only Multiplier : 0.1 Monitor point for the Intake PC 2.x,
Manifold 4 Offset: 0 Manifold 4 Temperature PC 3.x
Temperature
Size (bits): 16
Sign: S
Units: degF
Lower Limit: -40
Upper Limit: 410
Default: NA
40258 Fuel Outlet Read Only Multiplier: 0.1 Monitor point for the Fuel PC 2.x,
Pressure Offset: 0 Outlet Pressure. Displayed as PC 3.x
”Fuel Rail Pressure” in the
Size (bits): 32 HMI.
Sign: U
Unit: psi
Lower Limit: 0
Upper Limit: 36404
40259 Fuel Outlet Read Only Multiplier: 0.1 Monitor point for the Fuel PC 2.x,
Pressure Offset: 0 Outlet Pressure. Displayed as PC 3.x
”Fuel Rail Pressure” in the
Size (bits): 32 HMI.
Sign: U
Unit: psi
Lower Limit: 0
Upper Limit: 36404
40260 Intake Read Only Multiplier: 0.1 Monitor point for the Intake PC 2.x,
Manifold 2 Offset: 0 Manifold 2 Temperature PC 3.x
Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -40
Upper Limit: 410
40261 Intake Read Only Multiplier: 0.1 Monitor point for the Intake PC 2.x,
Manifold 3 Offset: 0 Manifold 3 Temperature PC 3.x
Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -40
Upper Limit: 410
40264 Percent Read Only Multiplier: 1 Monitor point for the percent PC 2.x,
Engine Offset: 0 engine torque output and the PC 3.x
Torque/Duty governor percent duty cycle
Cycle Size (bits): 16 output when used with the
Sign: S HM ECM
Unit: %
Lower Limit: -40
Upper Limit: 410
40276 Post-Filter Oil Read Only Multiplier: 0.1 Monitor point for the Post- PC 2.x,
Pressure Offset: 0 Filter Oil Pressure PC 3.x
Size (bits): 16
Sign: U
Unit: psi
Lower Limit: 0
Upper Limit: 145

78 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40277 Pre-Filter Oil Read Only Multiplier: 0.1 Monitor point for the Pre-Filter PC 2.x,
Pressure Offset: 0 Oil Pressure PC 3.x
Size (bits): 16
Sign: U
Unit: psi
Lower Limit: 0
Upper Limit: 145
40278 Configurable Read Only 0: Inactive Configurable Input #14 input PC 2.x,
Input #14 1: Active software state status. Gives PC 3.x
Switch software Inactive/Active state
40279 Turbocharger Read Only Multiplier: 1 Monitor point for the PC 2.x,
1 Speed Offset: 0 Turbocharger 1 Speed PC 3.x
Size (bits): 32
Sign: U
Unit: RPM
Lower Limit: 0
Upper Limit: 257000
40280 Turbocharger Read Only Multiplier: 1 Monitor point for the PC 2.x,
1 Speed Offset: 0 Turbocharger 1 Speed PC 3.x
Size (bits): 32
Sign: U
Unit: RPM
Lower Limit: 0
Upper Limit: 257000
40281 Turbocharger Read Only Multiplier: 0.1 Monitor point for the PC 2.x,
2 Boost Offset: 0 Turbocharger 2 Boost PC 3.x
Pressure Pressure
Size (bits): 32
Sign: U
Unit: psi
Lower Limit:
Upper Limit:
40282 Water in Fuel Read Only 0: No Water in Fuel Indication PC 2.x,
Indicator 1: Yes PC 3.x
40282 Water in Fuel Read Only 0: Off The controller mode PC 2.x,
Indicator 1: Ready PC 3.x
2: Setup
3: Starting
4: Idle
5: Rated
6: Stop Normal
7: Stop Emergency
8: Factory Test
9: Wait to Power Down
40285 Power Down Read Only Multiplier: 1 Timer to count down the time PC 2.x,
Mode Timer Offset: 0 before the control goes to PC 3.x
sleep
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 600

A029X159 (Issue 14) 79


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40286 Setup Mode Read Only Multiplier : 1 Time spent in Setup Mode. PC 2.x
Timer Offset: 0 PC3.x
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: NA
Upper Limit: NA
Default: NA
40287 Tool Wake-up Read only 0: Inactive The control output to the PC 2.x
Command 1: Active common wake-up line to PC 3.x
wake up other devices
40289 Active Read only 0: None Indicates the currently active PC 2.x
Schedule 1: Program 1 scheduler program or PC 3.x
exception.
2: Program 2
3: Program 3
4: Program 4
5: Program 5
6: Program 6
7: Program 7
8: Program 8
9: Program 9
10: Program 10
11: Program 11
12: Program 12
13: Exception 1
14: Exception 2
40290 Controller On Read Only Multiplier : 1 Controller ON time in PC 2.x
Time Offset: 0 seconds. Upper limit is 136 PC 3.x
years.
Size (bits): 32
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 4294967295
Default: NA
40291 Controller On Read Only Multiplier : 1 Controller ON time in PC 2.x
Time Offset: 0 seconds. Upper limit is 136 PC 3.x
years.
Size (bits): 32
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 4294967295
Default: NA
40298 Runs Since Read Only Multiplier: 1 Number of runs since the last PC 2.x,
Reset Offset: 0 reset. Upper limit is 2^32 -1. PC 3.x
Size (bits): 32
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967290

80 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40299 Runs Since Read Only Multiplier: 1 Number of runs since the last PC 2.x,
Reset Offset: 0 reset. Upper limit is 2^32 -1. PC 3.x
Size (bits): 32
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967290
40300 Remote Start Read/Write 0: Inactive Modbus Remote Start PC 2.x,
Switch(Modb 1: Active PC 3.x
us)
40301 Fault Reset Read/Write 0: Inactive Modbus fault reset. PC 2.x,
(Modbus) 1: Active PC 3.x
40320 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40321 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40322 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40323 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40324 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 81


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40325 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40326 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40327 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40328 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40329 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40330 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40331 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:

82 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40332 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40333 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40334 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40335 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40336 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:

40337 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x


No1 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40338 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 83


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40339 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No1 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40340 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40341 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40342 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40343 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40344 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40345 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

84 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40346 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40347 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40348 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40349 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40350 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40351 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40352 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 85


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40353 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40354 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text operator panel when this fault
Size (bits): 168 becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40355 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40356 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40357 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40358 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40359 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No2 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

86 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40360 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40361 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40362 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40363 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40364 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40365 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40366 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 87


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40367 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40368 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40369 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40370 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40371 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40372 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40373 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

88 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40374 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40375 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40376 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40377 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40378 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40379 Start Inhibit Read/Write Multiplier: 1 Trim to define the 20 PC 3.x
No3 Fault Offset: 0 character string for use by the
Text Operator panel when this
Size (bits): 168 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40422 Fault Status Read Only Multiplier : 1 16 bit fault bitmap for Modbus PC 2.x
Bitmap 23 Offset: 0 interface. PC 3.x
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA

A029X159 (Issue 14) 89


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40423 Fault Status Read Only Multiplier : 1 16 bit fault bitmap for Modbus PC 2.x
Bitmap 24 Offset: 0 interface. PC 3.x
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA
40424 Fault Status Read Only Multiplier : 1 16 bit fault bitmap for Modbus PC 2.x
Bitmap 25 Offset: 0 interface. PC3.x
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA
40425 Event Status Read Only Multiplier : 1 16 bit fault bitmap for Modbus PC 2.x
Bitmap 2 Offset: 0 interface. PC 3.x
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40426 Event Status Read Only Multiplier : 1 16 bit fault bitmap for Modbus PC 2.x
Bitmap 3 Offset: 0 interface. PC 3.x
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40427 Fault Status Read Only Multiplier : 1 16 bit fault bitmap for Modbus PC 2.x
Bitmap 26 Offset: 0 interface. PC 3.x
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40428 Fault Status Read Only Multiplier : 1 16 bit event bitmap for PC 3.x
Bitmap 32 Offset: 0 Modbus interface and Tier4F
16 bit Diesel Fault Bitmap for
Size (bits): 16 Modbus interface
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

90 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40430 Event Status Read Only Multiplier : 1 16 bit fault bitmap for Modbus PC 2.x
Bitmap 1 Offset: 0 interface. PC 3.x
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40431 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap 1 Offset: 0 Modbus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40432 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap 2 Offset: 0 Modbus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40433 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap 3 Offset: 0 Modbus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40434 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap 4 Offset: 0 Modbus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40435 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap 5 Offset: 0 Modbus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

A029X159 (Issue 14) 91


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40436 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap 6 Offset: 0 Modbus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40437 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap 7 Offset: 0 Modbus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40438 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap 8 Offset: 0 Modbus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40439 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap 9 Offset: 0 Modbus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40440 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
10
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40441 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
11
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

92 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40442 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
12
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40443 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
13
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40444 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
14
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40445 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
15
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40446 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
16
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40447 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
17
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

A029X159 (Issue 14) 93


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40448 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
18
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40449 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
19
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40450 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
20
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40451 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
21
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40452 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
22
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40453 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
23
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

94 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40454 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
24
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40455 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
25
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40456 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
26
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40457 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
27
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40458 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
28
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40459 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
29
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

A029X159 (Issue 14) 95


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40460 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
30
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40461 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
31
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40462 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
32
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40463 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
33
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40464 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
34
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40465 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
35
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

96 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40466 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
36
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40467 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
37
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40468 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
38
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40469 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
39
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA
40470 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
40
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40471 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
41
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

A029X159 (Issue 14) 97


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40472 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
42
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40473 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
43
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40474 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
44
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40475 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
45
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40476 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
46
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40477 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
47
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

98 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40478 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
48
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40479 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
49
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40480 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
50
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40481 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
51
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40482 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
52
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40483 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
53
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

A029X159 (Issue 14) 99


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40484 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
54
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40485 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
55
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40486 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
56
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40487 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
57
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40488 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
58
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40489 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
59
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

100 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40490 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
60
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40491 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
61
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40492 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
62
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40493 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
63
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40494 Fault Status Read Only Multiplier : 1 16 bit Gas fault bitmap for PC 3.x
Gas Bitmap Offset: 0 Modbus interface.
64
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA
40495 AT Fault Read Only Multiplier : 1 16 bit AT Fault Bitmap for PC 3.x
Status Bitmap Offset: 0 Modbus interface
1
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

A029X159 (Issue 14) 101


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40496 Fault Status Read Only Multiplier : 1 16 bit fault bitmap for Modbus PC 3.x
Bitmap 27 Offset: 0 interface
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA
40497 Fault Status Read Only Multiplier : 1 16 bit fault bitmap for Modbus PC 3.x
Bitmap 28 Offset: 0 interface
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA
40498 Fault Status Read Only Multiplier : 1 16 bit fault bitmap for Modbus PC 3.x
Bitmap 29 Offset: 0 interface
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA
40499 Fault Status Read Only Multiplier : 1 16 bit fault bitmap for Modbus PC 3.x
Bitmap 30 Offset: 0 interface
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA
40500 Low Fuel Read Only 0: Inactive Low Fuel input software state PC 2.x,
Switch 1: Active status. Gives software PC 3.x
Inactive/Active state
40501 Low Read Only 0: Inactive This is the status of the PC 2.x,
Fuel/Configur 1: Active Configurable Input #6. PC 3.x
able Input #6
Switch
40503 Differential Read Only 0: Inactive Differential fault trip monitor PC 3.x
Fault Trip 1: Active point
2: Reserved
3: Not Available
40504 Master First Read Only 0: Inactive This is the status of the PC 3.x
Start Input A 1: Active Master First Start A input

40505 Fire Trip Read Only 0: Inactive Fire trip monitor point. PC 3.x
1: Active
40506 Master First Read Only 0: Inactive Master First Start Input B PC 3.x
Start Input B 1: Active input software state status.
Switch Gives software Inactive/Active
state.

102 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40507 Masterless Read Only 0: Inactive Masterless Load Demand PC 3.x
Load 1: Active Enable Switch function output
Demand status. Gives software
Enable Inactive/Active state
Switch
40508 Predictive Read Only 0: Inactive Predictive Load Enable PC 3.x
Load Enable 1: Active Switch function output status.
Switch Gives software Inactive/Active
state
40509 PTC Mode Read Only 0: Inactive PTC Mode Switch function PC 3.x
Switch 1: Active output status. Gives software
Inactive/Active state
40510 Extended Read Only 0: Inactive This is the status of the PC 3.x
Parallel/Confi 1: Active Configurable Input #32.
gurable Input
#32 Switch
40511 Ramp Read Only 0: Load Ramp Load/Unload input PC 3.x
Load/Unload 1: Unload software state status
Switch
40512 Remote E- Read Only 0: Inactive Remote E–stop input PC 2.x,
stop Switch 1: Active software state status. Gives PC 3.x
software Inactive/Active state
40513 Remote Start Read Only 0: Inactive Remote Start input software PC 2.x,
Switch 1: Active state status. Gives software PC 3.x
Inactive/Active state
40514 Retransfer Read Only 0: Inactive Retransfer Inhibit input PC 3.x
Inhibit Switch 1: Active software state status. Gives
software Inactive/Active state
40515 Retransfer Read Only 0: Inactive This is the status of the PC 3.x
Inhibit/Config 1: Active Configurable Input #21.
urable Input
#21 Switch
40516 Rupture Read Only 0: Inactive Rupture Basin input software PC 2.x,
Basin Switch 1: Active state status. Gives software PC 3.x
Inactive/Active state
40517 Rupture Read Only 0: Inactive This is the status of the PC 2.x,
Basin/Configu 1: Active Configurable Input #12. PC 3.x
rable Input
#12 Switch
40518 Speed Droop Read Only 0: Inactive Monitors the Speed Droop PC 2.x,
Enable 1: Active Enable Switch function; PC 3.x
Switch Inactive or Active state
40519 Start Type Read Only 0: Inactive Start Type input software PC 2.x,
Switch 1: Active state status. Gives software PC 3.x
Inactive/Active state
40520 Sync Enable Read Only 0: Inactive Sync Enable input software PC 3.x
Switch 1: Active state status. Gives software
Inactive/Active state
40521 Sync Read Only 0: Inactive This is the status of the PC 3.x
Enable/Confi 1: Active Configurable Input #30.
gurable Input
#30 Switch
40522 Tool Wakeup Read Only 0: Inactive Tool Wake-up input software PC 2.x,
Switch 1: Active state status. Gives software PC 3.x
Inactive/Active state

A029X159 (Issue 14) 103


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40523 Transfer Read Only 0: Inactive Transfer Inhibit input software PC 3.x
Inhibit Switch 1: Active state status. Gives software
Inactive/Active state
40524 Transfer Read Only 0: Inactive This is the status of the PC 3.x
Inhibit/Config 1: Active Configurable Input #20.
urable Input
#20 Switch
40525 Utility CB Read Only 0: Inactive This is the status of the PC 3.x
Inhibit/Config 1: Active Configurable Input #25.
urable Input
#25 Switch
40526 Utility CB Pos Read Only 0: Inactive This is the status of the PC 3.x
B/Configurabl 1: Active Configurable Input #23.
e Input #23
Switch
40527 Utility CB Read Only 0: Inactive This is the status of the PC 3.x
Tripped/Confi 1: Active Configurable Input #24.
gurable Input
#24 Switch
40528 Utility Single Read Only 0: Inactive This is the status of the PC 3.x
Mode 1: Active Configurable Input #29.
Verify/Config
urable Input
#29 Switch
40529 Utility CB Read Only 0: Inactive Utility CB Inhibit input PC 3.x
Inhibit Switch 1: Active software state status. Gives
software Inactive/Active state
40530 Utility CB Pos Read Only 0: Inactive Utility CB Pos A input PC 3.x
A Switch 1: Active software state status. Gives
software Inactive/Active state
40531 Utility CB Pos Read Only 0: Inactive Utility CB Pos B input PC 3.x
B Switch 1: Active software state status. Gives
software Inactive/Active state
40532 Utility CB Read Only 0: Inactive Utility CB Tripped input PC 3.x
Tripped 1: Active software state status. Gives
Switch software Inactive/Active state
40533 Utility Single Read Only 0: Inactive Utility Single Mode Verify PC 3.x
Mode Verify 1: Active input software state status.
Switch Gives software Inactive/Active
state
40534 Voltage Read Only 0: Inactive Voltage Droop Enable Switch PC 2.x,
Droop Enable 1: Active function output status. Gives PC 3.x
Switch software Inactive/Active state.
40535 Configurable Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Output #1 1: Active is Inactive or Active PC 3.x
Status
40536 Configurable Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Output #2 1: Active is Inactive or Active PC 3.x
Status
40537 Configurable Read Only 0: Inactive Indicates if the output’s status PC 3.x
Output #20 1: Active is Inactive or Active
Status
40538 Configurable Read Only 0: Inactive Indicates if the output’s status PC 3.x
Output #21 1: Active is Inactive or Active
Status

104 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40539 Configurable Read Only 0: Inactive Indicates if the output’s status PC 3.x
Output #22 1: Active is Inactive or Active
Status
40540 Configurable Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Output #3 1: Active is Inactive or Active PC 3.x
Status
40541 Configurable Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Output #4 1: Active is Inactive or Active PC 3.x
Status
40542 Delayed Off / Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Configurable 1: Active is Inactive or Active PC 3.x
Output #10
Status
40543 Fuel Shutoff Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Status 1: Active is Inactive or Active PC 3.x
40545 Genset CB Read Only 0: Inactive Indicates if the output’s status PC 3.x
Open Status 1: Active is Inactive or Active

40546 Hold Power Read Only 0: Inactive Indicates if the output’s status PC 2.x,
On Driver 1: Active is Inactive or Active PC 3.x
Status
40547 Keyswitch Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Status 1: Active is Inactive or Active PC 3.x
40548 KW/kVAR Read Only 0: Inactive Indicates if the output’s status PC 3.x
Load Share 1: Active is Inactive or Active
Relay Status
40549 Load Dump / Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Configurable 1: Active is Inactive or Active PC 3.x
Output #11
Status
40550 Local Status / Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Configurable 1: Active is Inactive or Active PC 3.x
Output #7
Status
40551 Master First Read Only 0: Inactive Indicates if the output’s status PC 3.x
Start Output 1: Active is Inactive or Active
Status
40552 Oil Priming Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Pump / 1: Active is Inactive or Active PC 3.x
Configurable
Output #6
Status
40553 Ready To Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Load 1: Active is Inactive or Active PC 3.x
/Configurable
Output #5
Status
40554 Run Relay #1 Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Status 1: Active is Inactive or Active PC 3.x
40555 Run Relay #2 Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Status 1: Active is Inactive or Active PC 3.x
40556 Speed/Voltag Read Only 0: Inactive Indicates if the output’s status PC 3.x
e Bias Relay 1: Active is Inactive or Active
Status

A029X159 (Issue 14) 105


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40557 Starter Status Read Only 0: Inactive Indicates if the output’s status PC 2.x,
1: Active is Inactive or Active PC 3.x
40558 Tool Wake-up Read Only 0: Inactive Indicates if the output’s status PC 2.x,
Driver Status 1: Active is Inactive or Active PC 3.x
40559 Utility CB Read Only 0: Inactive Indicates if the output’s status PC 3.x
Close Status 1: Active is Inactive or Active

40560 Utility CB Read Only 0: Inactive Indicates if the output’s status PC 3.x
Open Status 1: Active is Inactive or Active

40561 Common Read Only 0: Inactive The status of the Common PC 2.x,
Alarm Fault 1: Active Alarm Fault PC 3.x
Status
40562 Common Read Only 0: Inactive The status of the common PC 2.x,
Shutdown 1: Active shutdown command PC 3.x
Command
40563 Common Read Only 0: Inactive The status of the Common PC 2.x,
Shutdown 1: Active Shutdown Event PC 3.x
Event Status
40564 Common Read Only 0: Inactive The status of the common PC 3.x
Shutdown 1: Active shutdown w/Cooldown
w/Cooldown command
Command
40565 Common Read Only 0: Inactive The status of the Common PC 2.x,
Warning 1: Active Warning Event PC 3.x
Event Status
40566 Delayed Read Only 0: Inactive Monitor point for the Delayed PC 2.x,
Shutdown 1: Active shutdown flag. PC 3.x
Flag
40567 Delayed Read Only Multiplier : 0.1 Monitor point for the Delayed PC 2.x,
Shutdown Offset: 0 shutdown timer. PC 3.x
Timer
Size (bits): 16
Sign: U
Units: Seconds
Lower Limit: 0
Upper Limit: 3
Default: NA
40568 Derate Read Only Multiplier : 1 The requested % derate from PC 2.x
Request Offset: 0 the derate request logic. PC 3.x
Size (bits): 8
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 100
Default: NA
40569 Fault Read Only 0: Inactive The status of the Fault PC 2.x,
Detection 1: Active Detection Reset logic. PC 3.x
Reset
40570 Fault Reset Read Only 0: Inactive One shot due to fault reset PC 2.x,
Command 1: Active switch being active. PC 3.x

106 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40571 Remote Read Only 0: Inactive Becomes active when a PC 2.x,
Shutdown 1: Active remote fault reset signal has PC 3.x
Fault Reset been initiated.
Signal
40572 Shutdown Read Only 0: Inactive The status of the Shutdown PC 2.x,
Fault Reset 1: Active Fault reset logic. PC 3.x
40573 Battle Short Read Only 0: Inactive Monitor point indicating the PC 2.x,
Flag 1: Active enabled/disabled status of the PC 3.x
battle short function
40574 Auto Read Only 0: Not Auto The output of the Auto PC 2.x,
Command 1: Auto Command OR logic PC 3.x
40575 Auto Read Only Multiplier : 1 Bitmask to show the inputs to PC 2.x,
Command Offset: 0 the Command output which PC 3.x
Inputs are currently on
Size (bits): 8
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
40576 AVR Read Only 0: Voltage The operational mode of the PC 2.x,
Regulation 1: Current AVR as a voltage or a current PC 3.x
Mode regulator
40577 Base Read Only Multiplier: 0.001 Provides a point to monitor PC 2.x,
Frequency Offset: 0 the base frequency PC 3.x
Size (bits): 32
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
40578 Base Read Only Multiplier: 0.001 Provides a point to monitor PC 2.x,
Frequency Offset: 0 the base frequency PC 3.x
Size (bits): 32
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
40579 Battery Read Only Multiplier : 0.1 Time spent while the charger PC 2.x,
Charging Offset: 0 is sensed as failed PC 3.x
Fault
Integrator Size (bits): 16
Sign: U
Unit: Hz
Lower Limit: 0
Upper Limit: 300
Default: NA

A029X159 (Issue 14) 107


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40580 Control Read Only 0: Off Current position of the PC 2.x,
Switch 1: Manual generator set switch panel PC 3.x
Position Off-Run-Auto switch as seen
2: Auto by the generator set control.
SEE ALSO ADDRESS
40010.
NOTE: Both address 40580
and 40010 show the same
information however the
specification for each is
different.
40581 Controlled Read /Write 0: Inactive Indicates status of the PC 3.x
Shutdown 1: Pending controlled shutdown logic
Status
2: Shutdown
40582 Crank Read Only 0: False Monitor Point indicates if PC 2.x,
Allowed 1: True Cranking is Allowed by the PC 3.x
Prelube State Machin
40583 Dead Battery Read Only Multiplier : 1 Tracks the number of crank PC 2.x,
Prevention Offset: 0 attempts in order to limit the PC 3.x
Counter attempts when the battery is
Size (bits): 8 so low that the control resets
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 250
Default: NA
40584 Delayed Off Read Only 0: Inactive The status of the delayed run PC 2.x,
Command 1: Active command off logic. PC 3.x
2: Reserved
3: Not Available
40586 Excitation Read Only 0: Disabled Shows the enable status of PC 2.x,
State 1: Enabled the excitation enabled = PC 3.x
regulator on.
40587 Exercise Read Only 0: Inactive The output of the Exercise PC 2.x,
Command 1: Active Command OR logic PC 3.x
2: Reserved
3: Not Available
40588 Exercise Read Only Multiplier : 1 Bitmask to show the inputs to PC 2.x,
Command Offset: 0 the Command output which PC 3.x
Inputs are currently on
Size (bits): 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 250
Default: NA
40589 Exercise Read Only Multiplier: 0.1 Time remaining until exercise PC 2.x,
Time Offset: 0 stop sequence begins PC 3.x
Remaining
Size (bits): 16
Sign: U
Unit: hours
Lower Limit: 0
Upper Limit: 25

108 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40590 Extended Read Only 0: Stop The output of the Extended PC 2.x,
Parallel 1: Start Parallel Switch Command OR PC 3.x
Switch logic
Command
40591 Extended Read Only Multiplier : 1 Bitmask to show the inputs to PC 3.x
Parallel Offset: 0 the Command output which
Switch are currently on
Command Size (bits): 8
Inputs Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
40592 Battle Short Read Only 0: Inactive Indicates status of battle short PC 2.x,
Command 1: Active inputs PC 3.x
40593 Shutdown Read Only 0: Inactive Indicates whether or not the PC 2.x,
Fault 1: Active genset will ignore non-critical PC 3.x
Override shutdown faults
40595 Final Read Only Multiplier: 0.001 The frequency scaled version PC 2.x,
Frequency Offset: 0 of the final speed reference PC 3.x
Reference
Size (bits): 32
Sign: U
Unit: Hz
Lower Limit: 0
Upper Limit: 100
40596 Final Read Only Multiplier: 0.001 The frequency scaled version PC 2.x,
Frequency Offset: 0 of the final speed reference PC 3.x
Reference
Size (bits): 32
Sign: U
Unit: Hz
Lower Limit: 0
Upper Limit: 100
40598 Fuel Shutoff Read Only 0: Inactive The result of the FSO driver PC 2.x,
Command 1: Active output command logic PC 3.x
2: Reserved
3: Not Available
40599 Genset Run Read Only 0: Emergency Stop Genset run / stop states PC 2.x,
Command 1: Stop PC 3.x
2: Load Demand Stop
3: Run
40600 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 109


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40601 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40602 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40603 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40604 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40605 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,


Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40606 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40607 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

110 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40608 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40609 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40610 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40611 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40612 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40613 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x, PC
Input #1 Fault Offset: 0 character string for use by the 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40614 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 111


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40615 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #1 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40620 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40621 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40622 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40623 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40624 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40625 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

112 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40626 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40627 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40628 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40629 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40630 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40631 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40632 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 113


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40633 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x, PC
Input #2 Fault Offset: 0 character string for use by the 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40634 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x, PC
Input #2 Fault Offset: 0 character string for use by the 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40635 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #2 Fault Offset: 0 character string for use by the PC 3.x
Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40640 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40641 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x, PC
Input #13 Offset: 0 character string for use by the 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40642 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x, PC
Input #13 Offset: 0 character string for use by the 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40643 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

114 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40644 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40645 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40646 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40647 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40648 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40649 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40650 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 115


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40651 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40652 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40653 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40654 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40655 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #13 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40660 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40661 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

116 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40662 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40663 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40664 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40665 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40666 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40667 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40668 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 117


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40669 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40670 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40671 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40672 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x, PC
Input #14 Offset: 0 character string for use by the 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40673 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40674 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40675 Configurable Read/Write Multiplier: 1 Trim to define the 16 PC 2.x,
Input #14 Offset: 0 character string for use by the PC 3.x
Fault Text Operator panel when this
Size (bits): 136 fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

118 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40709 Device Type Read Only Multiplier: 1 This Modbus register is PC 3.x
(Modlon) Offset: 0 created for Modlon register
mapping. This parameter is
Size (bits): 8 not associated with any
Sign: U logical.
Unit:
Lower Limit:
Upper Limit:
40710 Control Read Only 0: Off This Modbus register is PC 3.x
Switch 1: Manual created for Modlon register
Position mapping.
(Modlon) 2: Auto

40711 Genset Run Read Only 0: Stop This Modbus register is PC 3.x
Sequence 1: Time Delay to Start created for Modlon register
State mapping.
(Modlon) 2: Warmup at Idle
3: Rated Freq and Voltage
4: Cooldown / Stop Delay
5: Cooldown at Idle
6: Rated to Idle Transition
Delay
40712 Most Recent Read Only Multiplier: 1 This Modbus register is PC 3.x
Fault or Offset: 0 created for Modlon register
Warning mapping. This Modbus
(Modlon) Size (bits): 16 register is not associated with
Sign: U any logical Address
Unit: Fault Code
Lower Limit:
Upper Limit:
40713 Fault Type Read Only 0: None This Modbus register is PC 3.x
(Modlon) 1: Warning created for Modlon register
mapping. This Modbus
2: Derate register is not associated with
3: Shutdown with cooldown any logical address.
4: Shutdown
40714 Genset % Read Only Multiplier: 0.5 This Modbus register is PC 3.x
Standby Total Offset: 0 created for Modlon register
kW (Modlon) mapping. Monitors the total
Size (bits): 16 generator set standby KW
Sign: U percentage output. Modbus
Unit: % has different multiplier than
Lower Limit: PCCnet. For Modlon use
only, use multiplier 0.5 %
Upper Limit:
40715 Genset Total Read Only Multiplier: 1 This Modbus register is PC 3.x
kW (Modlon Offset: 0 created for Modlon register
GenStatus) mapping. Generator set total
Size (bits): 16 kW.
Sign: U
Unit: kW
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 119


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40716 NFPA 110 Read Only Multiplier: 1 This Modbus register is PC 3.x
Logical Offset: 0 created for Modlon register
Status mapping. 32–bit number to
(Modlon) Size (bits): 32 represent the status of the
Sign: U NFPA 110 logical. See
Unit: NFPA110 bitmap. (See Table
Lower Limit: 1 on page 37).
Upper Limit:
40717 NFPA 110 Read Only Multiplier: 1 This Modbus register is PC 3.x
Logical Offset: 0 created for Modlon register
Status mapping. 32-bit number to
(Modlon) Size (bits): 32 represent the status of the
Sign: U NFPA 110 logical. (See Table
Unit: 1 on page 37).
Lower Limit:
Upper Limit:
40718 Genset Read Only Multiplier: 0.1 This Modbus register is PC 3.x
Frequency Offset: 0 created for Modlon register
OP (Modlon) mapping. Generator set
Size (bits): 16 Frequency OP. Modbus has
Sign: U different multiplier than
Unit: Hz PCCNet. For Modlon use
Lower Limit: only, Multiplier/Units = 0.1 Hz
Upper Limit:
40719 Genset Total Read Only Multiplier: 0.00005 This Modbus register is PC 3.x
Power Factor Offset: 0 created for Modlon register
(Modlon) mapping. Generator set total
Size (bits): 16 power factor (L1+L2+L3).
Sign: S Modbus and PCCNet has
Unit: PF different multiplier value. For
Lower Limit: Modlon, use 0.00005 PF.
Upper Limit:
40720 Genset Total Read Only Multiplier: 1 This Modbus register is PC 3.x
kVA (Modlon) Offset: 0 created for Modlon register
mapping. Generator set total
Size (bits): 16 kVA
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:
40721 Genset Total Read Only Multiplier: 1 This Modbus register is PC 3.x
kW (Modlon Offset: 0 created for Modlon register
GenACData) mapping. Generator set total
Size (bits): 16 kW in Gen AC Data.
Sign: S
Unit: kW
Lower Limit:
Upper Limit:
40722 Genset Total Read Only Multiplier: 1 This Modbus register is PC 3.x
kVAR Offset: 0 created for Modlon register
(Modlon) mapping. Generator set total
Size (bits): 16 kVAR
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit:

120 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40723 Genset L1L2 Read Only Multiplier: 1 This Modbus register is PC 3.x
Voltage Offset: 0 created for Modlon register
(Modlon) mapping. Generator set L1L2
Size (bits): 16 voltage
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40724 Genset L2L3 Read Only Multiplier: 1 This Modbus register is PC 3.x
Voltage Offset: 0 created for Modlon register
(Modlon) mapping. Generator set L2L3
Size (bits): 16 voltage
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40725 Genset L3L1 Read Only Multiplier: 1 This Modbus register is PC 3.x
Voltage Offset: 0 created for Modlon register
(Modlon) mapping. Generator set L3L1
Size (bits): 16 voltage
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40726 Genset L1N Read Only Multiplier: 1 This Modbus register is PC 3.x
Voltage Offset: 0 created for Modlon register
(Modlon) mapping. Generator set L1N
Size (bits): 16 voltage
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40727 Genset L2N Read Only Multiplier: 1 This Modbus register is PC 3.x
Voltage Offset: 0 created for Modlon register
(Modlon) mapping. Generator set L2N
Size (bits): 16 voltage
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40728 Genset L3N Read Only Multiplier: 1 This Modbus register is PC 3.x
Voltage Offset: 0 created for Modlon register
(Modlon) mapping. Generator set L3N
Size (bits): 16 voltage
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40729 Genset L1 Read Only Multiplier: 1 Monitors the generator set L1 PC 3.x
Current Offset: 0 current value.
(Modlon)
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 121


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40730 Genset L2 Read Only Multiplier: 1 Generator set L2 current PC 3.x
Current Offset: 0
(Modlon)
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:
40731 Genset L3 Read Only Multiplier: 1 This Modbus register is PC 3.x
Current Offset: 0 created for Modlon register
(Modlon) mapping. Generator set L3
Size (bits): 16 current
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:
40732 Genset % Read Only Multiplier: 0.5 This Modbus register is PC 3.x
Standby L1 Offset: 0 created for Modlon register
Current mapping. Monitors the
(Modlon) Size (bits): 16 generator set standby L1
Sign: U current percentage output.
Unit: % Modbus and PCCNet have
Lower Limit: different multiplier value. For
Modlon use 0.5 %
Upper Limit:
40733 Genset % Read Only Multiplier: 0.5 This Modbus register is PC 3.x
Standby L2 Offset: 0 created for Modlon register
Current mapping. Monitors the
(Modlon) Size (bits): 16 generator set standby L2
Sign: U current percentage output.
Unit: % Modbus and PCCNet has
Lower Limit: different multiplier value. For
Modlon, use 0.5 %
Upper Limit:
40734 Genset % Read Only Multiplier: 0.5 This Modbus register is PC 3.x
Standby L3 Offset: 0 created for Modlon register
Current mapping. Monitors the
(Modlon) Size (bits): 16 generator set standby L3
Sign: U current percentage output.
Unit: % Modbus and PCCNet has
Lower Limit: different multiplier value. For
Modlon use 0.5 %
Upper Limit:
40735 Battery Read Only Multiplier: 0.1 This Modbus register is PC 3.x
Voltage Offset: 0 created for Modlon register
(Modlon) mapping. Battery voltage
Size (bits): 16 value. Modbus and PCCNet
Sign: S has different multiplier value.
Unit: Vdc For Modlon use 0.1volts
Lower Limit:
Upper Limit:
40736 Oil Pressure Read Only Multiplier: 0.1 This Modbus register is PC 3.x
(Modlon) Offset: 0 created for Modlon register
mapping. Monitor point for the
Size (bits): 16 Oil Pressure. Modbus and
Sign: U PCCNet have different
Unit: kPa multiplier value. For Modlon,
Lower Limit: use 0.1 KPA
Upper Limit:

122 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40737 Oil Read Only Multiplier: 0.1 This Modbus register is PC 3.x
Temperature Offset: 0 created for Modlon register
(Modlon) mapping. Monitor point for the
Size (bits): 16 Oil Temperature. Modbus and
Sign: S PCCNet has different
Unit: degK multiplier value. For Modlon
Lower Limit: use 0.1 deg Kelvin
Upper Limit:
40738 Coolant Read Only Multiplier: 0.1 This Modbus register is PC 3.x
Temperature Offset: 0 created for Modlon register
(Modlon) mapping. Monitor point for the
Size (bits): 16 Coolant Temperature.
Sign: S Modbus and PCCNet has
Unit: degK different multiplier value. For
Lower Limit: Modlon, use 0.1deg Kelvin.
Upper Limit:
40739 Intake Read Only Multiplier: 0.1 This Modbus register is PC 3.x
Manifold Offset: 0 created for Modlon register
Temperature mapping. To monitor Intake
(Modlon) Size (bits): 16 Manifold Temperature.
Sign: S Modbus and PCCNet has
Unit: degK different multiplier value. For
Lower Limit: -40 Modlon, use 0.1 deg Kelvin
Upper Limit: 410
40740 Fuel Read Only Multiplier: 0.1 This Modbus register is PC 3.x
Temperature Offset: 0 created for Modlon register
(Modlon) mapping. Monitor point for the
Size (bits): 16 Fuel Temperature. Modbus
Sign: S and PCCNet has different
Unit: degK multiplier value. For Modlon,
Lower Limit: -40 use 0.1 deg Kelvin.
Upper Limit: 410
40741 Fuel Rate Read Only Multiplier: 0.01 This Modbus register is PC 3.x
(Modlon) Offset: 0 created for Modlon register
mapping. Monitor point for the
Size (bits): 16 Fuel Rate. Modbus and
Sign: U PCCNet has different
Unit: gal/hr multiplier value. For Modlon,
Lower Limit: use 0.01 gph
Upper Limit:
40742 Average Read Only Multiplier: 1 This Modbus register is PC 3.x
Engine Offset: 0 created for Modlon register
Speed mapping. Monitor point for the
(Modlon) Size (bits): 16 Average Engine Speed.
Sign: U Modbus and PCCNet have
Unit: RPM different multiplier value. For
Lower Limit: Modlon, use 1 RPM.
Upper Limit:
40743 Total Number Read Only Multiplier: 1 This Modbus register is PC 3.x
of Runs Offset: 0 created for Modlon register
(Modlon) mapping. Total number of
Size (bits): 32 generator set runs.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967295

A029X159 (Issue 14) 123


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40744 Engine Read Only Multiplier: 0.1 This Modbus register is PC 3.x
Running Time Offset: 0 created for Modlon register
(Modlon) mapping. Total engine run
Size (bits): 16 time. Modbus has different
Sign: U multiplier than PCCNet. For
Unit: seconds Modbus, use 0.1 sec
Lower Limit:
Upper Limit:
40745 Engine Read Only Multiplier: 0.1 This Modbus register is PC 3.x
Running Time Offset: 0 created for Modlon register
(Modlon) mapping. Total engine run
Size (bits): 16 time. Modbus has different
Sign: U multiplier than PCCNet. For
Unit: seconds Modbus, use 0.1 sec
Lower Limit:
Upper Limit:
40746 Genset Total Read Only Multiplier: 1 This Modbus register is PC 3.x
Net kWh Offset: 0 created for Modlon register
(Modlon) mapping. Generator set total
Size (bits): 32 net kWh accumulation
Sign: S
Unit: kWh
Lower Limit: -2147483648
Upper Limit: 2147483643
40747 Genset Total Read Only Multiplier: 1 This Modbus register is PC 3.x
Net kWh Offset: 0 created for Modlon register
(Modlon) mapping. Generator set total
Size (bits): 32 net kWh accumulation
Sign: S
Unit: kWh
Lower Limit: -2147483648
Upper Limit: 2147483643
40748 Total Fuel Read Only Multiplier: 0.01 This Modbus register is PC 3.x
Consumption Offset: 0 created for Modlon register
(Modlon) mapping. Total fuel
Size (bits): 32 consumption since start of
Sign: U engine. Modbus and PCCNet
Unit: gallons has different multiplier value.
Lower Limit: For Modlon, use 0.01 Gallons
Upper Limit:
40749 Total Fuel Read Only Multiplier: 0.01 This Modbus register is PC 3.x
Consumption Offset: 0 created for Modlon register
(Modlon) mapping. Total fuel
Size (bits): 32 consumption since start of
Sign: U engine. Modbus and PCCNet
Unit: gallons has different multiplier value.
Lower Limit: For Modlon, use 0.01 Gallons
Upper Limit:
40750 Utility/Genset Read Only Multiplier: 0.1 This Modbus register is PC 3.x
Bus Offset: 0 created for Modlon register
Frequency mapping. Utility line
(Modlon) Size (bits): 16 frequency or Generator set
Sign: U Bus Frequency depending on
Unit: Hz Paralleling Application.
Lower Limit: Modbus and PCCNet has
different multiplier value. For
Upper Limit: Modlon, use 0.1 Hz.

124 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40751 Utility/Genset Read Only Multiplier: 1 This Modbus register is PC 3.x
Bus L1L2 Offset: 0 created for Modlon register
Voltage mapping. Utility L1L2 Voltage
(Modlon) Size (bits): 16 or Generator set Bus L1L2
Sign: U voltage depending on
Unit: Vac paralleling application.
Lower Limit:
Upper Limit:
40752 Utility/Genset Read Only Multiplier: 1 This Modbus register is PC 3.x
Bus L2L3 Offset: 0 created for Modlon register
Voltage mapping. Utility L2L3 voltage
(Modlon) Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40753 Utility/Genset Read Only Multiplier: 1 This Modbus register is PC 3.x
Bus L3L1 Offset: 0 created for Modlon register
Voltage mapping. Utility L3L1 voltage
(Modlon) Size (bits): 16 or Generator set Bus L3L1
Sign: U voltage depending on
Unit: Vac paralleling application.
Lower Limit:
Upper Limit:
40754 Utility/Genset Read Only Multiplier: 1 This Modbus register is PC 3.x
Bus L1N Offset: 0 created for Modlon register
Voltage mapping. Utility L1N voltage
(Modlon) Size (bits): 16 or Generator set Bus L1N
Sign: U voltage depending on
Unit: Vac paralleling application.
Lower Limit:
Upper Limit:
40755 Utility/Genset Read Only Multiplier: 1 This Modbus register is PC 3.x
Bus L2N Offset: 0 created for Modlon register
Voltage mapping. Utility L2N voltage
(Modlon) Size (bits): 16 or Generator set Bus L2N
Sign: U voltage depending on
Unit: Vac paralleling application.
Lower Limit:
Upper Limit:
40756 Utility/Genset Read Only Multiplier: 1 This Modbus register is PC 3.x
Bus L3N Offset: 0 created for Modlon register
Voltage mapping. Utility L3N voltage
(Modlon) Size (bits): 16 or Generator set Bus L3N
Sign: U voltage depending on
Unit: Vac paralleling application.
Lower Limit:
Upper Limit:
40757 Customer Read Only Multiplier: 1 This Modbus register is PC 3.x
Faults Offset: 0 created for Modlon register
(Modlon) mapping. 16 bit fault bitmap
Size (bits): 16 for Modbus interface.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

A029X159 (Issue 14) 125


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40760 ES State Read Only 0: Standby This Modbus register is PC 3.x
(Modlon) 1: Dead Bus created for Modlon register
mapping. Internal paralleling
2: Synchronize status variable
3: Load Share
4: Load Goven
40761 Load Read Only 0: Inactive This Modbus register is PC 3.x
Demand Stop 1: Active created for Modlon register
Command mapping. Modbus input for
(Modlon) load demand stop command.
40764 Genset CB Read Only 0: Open This Modbus register is PC 3.x
Position 1: Closed created for Modlon register
Status mapping. indicates generator
(Modlon) 2: Not Available set breaker position
40765 Utility CB Read Only 0: Open This Modbus register is PC 3.x
Position 1: Closed created for Modlon register
Status mapping. indicates utility
(Modlon) 2: Not Available breaker position
40766 Remote Start Read/Write 0: Inactive This Modbus register is PC 3.x
Switch(Modlo 1: Active created for Modlon register
n) mapping. Modbus Remote
Start
40767 Fault Reset Read/Write 0: Inactive This Modbus register is PC 3.x
(Modlon) 1: Active created for Modlon register
mapping. Modbus fault reset.
40768 System Read Only 0: Inactive Indicates communication PC 3.x
Network 1: Active status of the local genset on
Datalink System Network (used for
Status 2: Failed load demand). Available on
PCC3300MLD controls only.
40769 Load Read/Write Multiplier: 1 Run hour accumulator used PC 3.x
Demand Offset: 0 for load demand run hour
Genset Run equalization. This is writable.
Size: 32 Available on PCC3300MLD
Hours (Upper
Register Sign: U controls only.
value) Units: Hours
Lower Limit: 0
Upper Limit: 999999.9
Default: 0
40770 Load Read/Write Multiplier: 1 Run hour accumulator used PC 3.x
Demand Offset: 0 for load demand run hour
Genset Run equalization. This is writable.
Size: 32 Available on PCC3300MLD
Hours (Lower
Register Sign: U controls only.
value) Units: Hours
Lower Limit: 0
Upper Limit: 999999.9
Default: 0
40771 Load Read Only 0: Inactive Indicates the status of the PC 3.x
Demand 1: Active spare capacity request input.
Spare When ACTIVE additional
Capacity spare capacity (set by Load
Request Demand Spare Capacity
Status Request Value) is requested.
Available on PCC3300MLD
controls only.

126 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40772 System Read Only 0: On Indicates the status of the on- PC 3.x
Network 1: Off board CAN termination
Termination resistor switch (S1). Available
Resistor on PCC3300MLD controls
Switch Status only.

40773 Genset ID Read/Write 0: Gen1 9: Gen10 Genset identifier. All load PC 3.x
1: Gen2 10: Gen11 demand gensets must have a
unique Genset ID. Available
2: Gen3 11: Gen12 on PCC3300MLD controls
3: Gen4 12: Gen13 only. Setup Mode must be
4: Gen5 13: Gen14 enabled to modify the value.
5: Gen6 14: Gen15 See Modbus Address 43343.
6: Gen7 15: Gen16
7: Gen8
8: Gen9
40774 Load Read/Write Multiplier: 1 Sets the kW value of PC 3.x
Demand Offset: 0 additional capacity to be
Spare requested from the system
Capacity Size(Bits): 32 when the Load Demand
Request Sign: U Spare Capacity Request
Value (Upper Units: kW Status is YES. Available on
Register Lower Limit: 0 PCC3300MLD controls only.
value) Setup Mode must be enabled
Upper Limit: 80000 to modify the value. See
Default: 0 Modbus Address 43343.
40775 Load Read/Write Multiplier: 1 Sets the kW value of PC 3.x
Demand Offset: 0 additional capacity to be
Spare requested from the system
Capacity Size(Bits): 32 when the Load Demand
Request Sign: U Spare Capacity Request
Value (Lower Units: kW Status is YES. Available on
Register Lower Limit: 0 PCC3300MLD controls only.
value) Setup Mode must be enabled
Upper Limit: 80000 to modify the value. See
Default: 0 Modbus Address 43343.
40776 Load Read/Write 0: Disable Disables or Enables load PC 3.x
Demand 1: Enable demand on this genset only.
Genset When set to disable the
Enable genset is not included in the
load demand system and can
be removed without triggering
a com error. Available on
PCC3300MLD controls only.
Setup Mode must be enabled
to modify the value. See
Modbus Address 43343.
40777 System Read Only 0: Out of Sync Indicates whether the system PC 3.x
Settings 1: In Sync settings on the local genset
Status are in sync with ones from
other genset in the network.
Available on PCC3300MLD
controls only.

A029X159 (Issue 14) 127


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40800 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40801 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40802 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40803 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40804 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40805 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40806 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

128 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40807 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40808 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40809 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40810 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40811 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40812 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40813 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 129


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40814 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40815 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40816 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40817 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40818 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40819 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40820 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

130 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40821 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40822 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40823 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40824 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC
Input 7 Fault Offset: 0 field to allow for the entry of 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40825 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC
Input 7 Fault Offset: 0 field to allow for the entry of 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40826 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC
Input 7 Fault Offset: 0 field to allow for the entry of 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40827 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC
Input 7 Fault Offset: 0 field to allow for the entry of 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 131


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40828 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40829 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40830 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40831 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC
Input 7 Fault Offset: 0 field to allow for the entry of 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40832 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40833 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40834 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

132 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40835 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40836 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40837 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40838 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40839 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40840 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40841 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 133


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40842 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40843 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text string to enter the PC 3.x
configurable fault text for this
fault.
40844 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40845 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40846 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40847 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40848 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

134 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40849 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40850 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40851 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC
Fault 9 Text Offset: 0 string to enter the 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40852 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40853 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40854 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40855 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 135


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40856 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40857 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40858 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40859 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40860 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40861 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40862 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

136 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40863 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC
Fault 10 Text Offset: 0 string to enter the 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40864 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC


Fault 10 Text Offset: 0 string to enter the 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40865 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC


Fault 10 Text Offset: 0 string to enter the 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40866 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC
Fault 10 Text Offset: 0 string to enter the 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40867 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC
Fault 10 Text Offset: 0 string to enter the 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40868 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 137


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40869 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40870 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40871 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40872 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40873 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40874 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

138 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40875 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40876 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40877 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40878 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40879 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40880 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 139


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40881 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40882 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40883 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40884 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40885 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40886 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40887 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

140 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40888 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40889 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40890 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40891 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40892 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40893 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40894 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 141


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40895 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40896 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40897 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40898 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40899 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40900 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40901 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

142 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40902 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40903 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40904 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40905 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40906 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40907 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40908 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 143


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40909 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40910 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40911 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40912 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40913 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40914 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

144 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40915 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40916 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40917 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40918 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40919 Aux102 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40920 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC
Fault 9 Text Offset: 0 string to enter the 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40921 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC
Fault 9 Text Offset: 0 string to enter the 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 145


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40922 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x, PC
Fault 9 Text Offset: 0 string to enter the 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40923 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40924 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40925 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40926 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40927 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40928 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

146 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40929 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40930 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40931 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40932 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40933 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40934 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40935 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 147


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40936 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40937 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40938 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40939 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 9 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40940 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40941 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40942 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

148 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40943 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40944 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40945 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40946 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40947 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40948 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40949 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 149


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40950 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40951 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40952 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40953 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40954 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40955 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

150 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40956 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40957 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40958 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40959 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 10 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40960 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40961 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 151


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40962 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40963 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40964 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40965 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40966 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40967 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40968 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

152 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40969 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40970 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40971 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40972 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40973 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40974 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40975 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 153


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40976 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40977 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40978 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40979 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 11 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40980 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40981 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40982 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

154 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40983 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40984 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40985 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40986 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40987 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40988 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 155


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


40989 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40990 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40991 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40992 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40993 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40994 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

156 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


40995 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40996 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40997 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40998 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40999 Aux102 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Fault 12 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

41000 Load Read/Write 0: Disable Disables or Enables load PC 3.x


Demand 1: Enable demand operation of all
System connected gensets. Available
on PCC3300MLD controls
Enable only.
41001 Load Read/Write 0: Run Hours Equalization Sets the sequencing priority PC 3.x
Demand (Run Hr Eql) for load demand. Available on
1: Fixed Sequence (Fixed PCC3300MLD controls only.
Type
Seq)

A029X159 (Issue 14) 157


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


41002 Load Read/Write 0: kW Sets whether the load PC 3.x
Demand 1: %kW demand start/stop control is
Threshold based on a relative (%) or
Method absolute (kW) threshold.
Available on PCC3300MLD
controls only.
41003 Load Read/Write Multiplier: 1 When the ratio of load to PC 3.x
Demand Start Offset: 0 capacity is greater than this
Threshold value the next genset will
(%kW) Size(Bits): 8 start. Must be greater than
Sign: U Load Demand Stop
Units: % Threshold by at least 5%.
Lower Limit: 25 Available on PCC3300MLD
controls only.
Upper Limit: 100
Default: 80

41004 Load Read/Write Multiplier: 1 When surplus capacity is less PC 3.x


Demand Start Offset: 0 than this value the next
Threshold genset will start. Must be less
(kW) Size(Bits): 16 than Load Demand Stop
Sign: U Threshold (kW). Available on
Units: kW PCC3300MLD controls only.
Lower Limit: 5
Upper Limit: 5000
Default: 500

41005 Load Read/Write Multiplier: 1 When the ratio of load to PC 3.x


Demand Stop Offset: 0 capacity is less than this
Threshold value the next genset will
(%kW) Size(Bits): 8 stop. Must be less than Load
Sign: U Demand Start Threshold by
Units: % at least 5%. Available on
Lower Limit: 20 PCC3300MLD controls only.
Upper Limit: 95
Default: 60

41006 Load Read/Write Multiplier: 1 When surplus capacity is PC 3.x


Demand Stop Offset: 0 greater than this value the
Threshold next genset will stop. Must be
(kW) Size(Bits): 16 greater than Load Demand
Sign: U Start Threshold (kW).
Units: kW Available on PCC3300MLD
Lower Limit: 5 controls only.
Upper Limit: 5000
Default: 1000
41007 Load Read/Write Multiplier: 1 When the difference between PC 3.x
Demand Run Offset: 0 Load Demand Genset Run
Hours Hours between any running
Differential Size(Bits): 16 genset and any stopped
Sign: U genset reaches this value the
Units: Hours stopped genset will be
Lower Limit: 1 started. Available on
PCC3300MLD controls only.
Upper Limit: 250
Default: 50

158 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


41008 Load Read/Write Multiplier: 1 Sets the time delay that the PC 3.x
Demand Offset: 0 system waits for a genset to
Genset Fail come online before declaring
Delay Size(Bits): 16 it as failed. Available on
Sign: U PCC3300MLD controls only.
Units: seconds
Lower Limit: 10
Upper Limit: 900
Default: 60

41009 Load Read/Write Multiplier: 1 Sets the time delay before PC 3.x
Demand Offset: 0 gensets are allowed to stop
Initial Delay after initial start or after
Size(Bits): 16 resuming halted load
Sign: U demand. Available on
Units: seconds PCC3300MLD controls only.
Lower Limit: 60
Upper Limit: 1500
Default: 300

41010 Load Read/Write Multiplier: 1 Sets the time delay before PC 3.x
Demand Start Offset: 0 next genset is allowed to
Delay start. Available on
Size(Bits): 16 PCC3300MLD controls only.
Sign: U
Units: seconds
Lower Limit: 0
Upper Limit: 1500
Default: 10

41011 Load Read/Write Multiplier: 1 Sets the time delay before PC 3.x
Demand Stop Offset: 0 next genset is allowed to
Delay stop. Available on
Size(Bits): 16 PCC3300MLD controls only.
Sign: U
Units: seconds
Lower Limit: 60
Upper Limit: 1500
Default: 300

41012 Clear Lost Read/Write 0: No When set to YES all gensets PC 3.x
Gensets 1: Yes in state ”Lost” will change to
Local state ”Gen Does Not Exist” in
order to clear Lost Genset
Warning. Available on
PCC3300MLD controls only.

A029X159 (Issue 14) 159


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


41013 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x
Demand 1: Gen2 priority 1. Used when Load
Fixed Priority Demand Type is set to Fixed
2: Gen3 Sequence. Available on
1
3: Gen4 PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

41014 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x


Demand 1: Gen2 priority 2. Used when Load
Fixed Priority Demand Type is set to Fixed
2: Gen3 Sequence. Available on
2
3: Gen4 PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

41015 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x


Demand 1: Gen2 priority 3. Used when Load
Fixed Priority Demand Type is set to Fixed
2: Gen3 Sequence. Available on
3
3: Gen4 PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

160 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


41016 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x
Demand 1: Gen2 priority 4. Used when Load
Fixed Priority Demand Type is set to Fixed
2: Gen3 Sequence. Available on
4
3: Gen4 PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

41017 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x


Demand 1: Gen2 priority 5. Used when Load
Fixed Priority Demand Type is set to Fixed
2: Gen3 Sequence. Available on
5
3: Gen4 PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

41018 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x


Demand 1: Gen2 priority 6. Used when Load
Fixed Priority Demand Type is set to Fixed
2: Gen3 Sequence. Available on
6
3: Gen4 PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

A029X159 (Issue 14) 161


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


41019 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x
Demand 1: Gen2 priority 7. Used when Load
Fixed Priority Demand Type is set to Fixed
2: Gen3 Sequence. Available on
7
3: Gen4 PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

41020 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x


Demand 1: Gen2 priority 8. Used when Load
Fixed Priority Demand Type is set to Fixed
2: Gen3 Sequence. Available on
8
3: Gen4 PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
41021 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x
Demand 1: Gen2 priority 9. Used when Load
Fixed Priority Demand Type is set to Fixed
2: Gen3 Sequence. Available on
9
3: Gen4 PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

162 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


41022 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x
Demand 1: Gen2 priority 10. Used when Load
Fixed Priority Demand Type is set to Fixed
2: Gen3 Sequence. Available on
10
3: Gen4 PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

41023 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x


Demand 1: Gen2 priority 11. Used when Load
Fixed Priority Demand Type is set to Fixed
2: Gen3 Sequence. Available on
11
3: Gen4 PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

41024 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x


Demand 1: Gen2 priority 12. Used when Load
Fixed Priority Demand Type is set to Fixed
2: Gen3 Sequence. Available on
12
3: Gen4 PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

A029X159 (Issue 14) 163


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


41025 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x
Demand 1: Gen2 priority 13. Used when Load
Fixed Priority Demand Type is set to Fixed
2: Gen3 Sequence. Available on
13
3: Gen4 PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

41026 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x


Demand 1: Gen2 priority 14. Used when Load
Fixed Priority Demand Type is set to Fixed
2: Gen3 Sequence. Available on
14
3: Gen4 PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

41027 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x


Demand 1: Gen2 priority 15. Used when Load
Fixed Priority Demand Type is set to Fixed
2: Gen3 Sequence. Available on
15
3: Gen4 PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

164 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


41028 Load Read/Write 0: Gen1 Assigns a genset to fixed PC 3.x
Demand 1: Gen2 priority 16. Used when Load
Fixed Priority Demand Type is set to Fixed
2: Gen3 Sequence. Available on
16
3: Gen4 PCC3300MLD controls only.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

41029 System Read/Write 0: Inactive When set to YES all the PC 3.x
Network 1: Active system network faults in the
Remote Fault system would be reset.
Reset Available on PCC3300MLD
controls only.

41030 Synchronize Read/Write 0: No When set to YES system PC 3.x


System 1: Yes settings from the genset will
Settings be broadcasted and
synchronized to all other
gensets in the network.
Available on PCC3300MLD
controls only.
41031 Battery Read Only 0: Inactive Battery Charger 2 Failed PC 3.x
Charger 2 1: Active Switch function output status;
Failed Switch gives software Inactive/Active
state
41032 Battery Read Only 0: Inactive Battery Charger 3 Failed PC 3.x
Charger 3 1: Active Switch function output status;
Failed Switch gives software Inactive/Active
state
41033 Battery Read Only 0: Inactive Battery Charger 4 Failed PC 3.x
Charger 4 1: Active Switch function output status;
Failed Switch gives software Inactive/Active
state
41034 Intake Air Read Only 0: Inactive Intake Air Restriction PC 3.x
Restriction 1: Active Indicator 1 fault switch
Indicator 1 function output status; gives
fault switch software Inactive/Active state
41035 Intake Air Read Only 0: Inactive Intake Air Restriction PC 3.x
Restriction 1: Active Indicator 2 fault switch
Indicator 2 function output status; gives
fault switch software Inactive/Active state
41036 Intake Air Read Only 0: Inactive Intake Air Restriction PC 3.x
Restriction 1: Active Indicator 3 fault switch
Indicator 3 function output status; gives
fault switch software Inactive/Active state

A029X159 (Issue 14) 165


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


41037 Intake Air Read Only 0: Inactive Intake Air Restriction PC 3.x
Restriction 1: Active Indicator 4 fault switch
Indicator 4 function output status; gives
fault switch software Inactive/Active state
41038 Starter Air Read Only 0: Inactive Starter Air Supply Pressure PC 3.x
Supply 1: Active Low Fault Switch function
Pressure Low output status; gives software
Fault Switch Inactive/Active
41039 Starter Air Read Only 0: Inactive Starter Air Tank Volume Low PC 3.x
Tank Volume 1: Active Fault Switch function output
Low Fault status; gives software
Switch Inactive/Active state
41300 AmpSentry Read Only 0: Inactive A protection mode that PC 3.x
Maintenance 1: Active causes the alternator to
Mode Status shutdown instantly when a
short circuit is detected. Used
to limit arc flash energy with
personnel working
41301 AMM PC Read Only 0: Inactive Detects whether any service PC 3.x
Tool Detected 1: Active tool is connected via TB15 or
J14 by validating if a
read/write command has
been exchanged via MON
using a five second
decremental timer. If the timer
expires, then it is determine
service tool is no longer
connected.
41302 AMM Disable Read Only Multiplier : 1 Countdown timer when PC 3.x
Walkaway Units: Seconds walkaway is complete.
Timer Value
Offset: 0
Lower Limit: NA
Size (Bits) : 16
Upper Limit: NA
Sign: U
Default: NA

41400 Fault Status Read Only Multiplier : 1 16 bit fault bitmap for Modbus PC 3.x
Bitmap 31 Units: NA interface.
Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA
41401 Fault Status Read Only Multiplier : 1 16 bit Diesel Fault Bitmap for PC 3.x
Bitmap 33 Units: NA Modbus interface
Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA

166 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


41402 Fault Status Read Only Multiplier : 1 16 bit Diesel Fault Bitmap for PC 2.x,
Bitmap 34 Units: NA Modbus interface PC 3.x
Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA
41403 AT Fault Read Only Multiplier : 1 16 bit AT Fault Bitmap for PC 3.x
Status Bitmap Units: NA Modbus interface
2
Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA
41404 AT Fault Read Only Multiplier : 1 16 bit AT Fault Bitmap for PC 3.x
Status Bitmap Units: NA Modbus interface
3
Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA
41405 AT Fault Read Only Multiplier : 1 16 bit AT Fault Bitmap for PC 3.x
Status Bitmap Units: NA Modbus interface
4
Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA

41406 AT Fault Read Only Multiplier : 1 16 bit AT Fault Bitmap for PC 3.x
Status Bitmap Units: NA Modbus interface
5
Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA
41407 AT Fault Read Only Multiplier : 1 16 bit AT Fault Bitmap for PC 3.x
Status Bitmap Units: NA Modbus interface
6
Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA

A029X159 (Issue 14) 167


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


41408 AT Fault Read Only Multiplier : 1 16 bit AT Fault Bitmap for PC 3.x
Status Bitmap Units: NA Modbus interface
7
Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA
41409 AT Fault Read Only Multiplier : 1 16 bit AT Fault Bitmap for PC 3.x
Status Bitmap Units: NA Modbus interface
8
Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA
41416 Fault Status Read Only Multiplier : 1 16 bit Diesel Fault Bitmap for PC 3.x
Bitmap 35 Units: NA Modbus interface
Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA
41417 Fault Status Read Only Multiplier : 1 16 bit Diesel Fault Bitmap for PC 3.x
Bitmap 36 Units: NA Modbus interface
Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA
41418 Fault Status Read Only Multiplier : 1 16 bit Diesel Fault Bitmap for PC 3.x
Bitmap 37 Units: NA Modbus interface
Offset: 0
Lower Limit: 0
Size (Bits) : 16
Upper Limit: 65535
Sign: U
Default: NA
42000 Load Read Only 0: Off Indicates the status of Load PC 3.x
Demand 1: Halted Demand operation. Available
State on PCC3300MLD controls
2: Initial Delay only.
3: Load Monitor

168 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


42001 Load Read Only Multiplier: 1.0 Indicates the total load of PC 3.x
Demand Offset: 0 System Network connected
Genset Bus gensets. Available on
Total kW Size (bits): 32 PCC3300MLD controls only.
(Upper Sign: U
Register Units: kW
value) Lower Limit: 0
Upper Limit: 80000
Default: 0
42002 Load Read Only Multiplier: 1.0 Indicates the total load of PC 3.x
Demand Offset: 0 System Network connected
Genset Bus gensets. Available on
Total kW Size (bits): 32 PCC3300MLD controls only.
(Lower Sign: U
Register Units: kW
value) Lower Limit: 0
Upper Limit: 80000
Default: 0
42003 Load Read Only Multiplier: 1.0 Indicates the total load of PC 3.x
Demand Offset: 0 System Network connected
Surplus gensets. Available on
Capacity Size (bits): 32 PCC3300MLD controls only.
(Upper Sign: U
Register Units: kW
value) Lower Limit: 0
Upper Limit: 80000
Default: 0
42004 Load Read Only Multiplier: 1.0 Indicates the total load of PC 3.x
Demand Offset: 0 System Network connected
Surplus gensets. Available on
Capacity Size (bits): 32 PCC3300MLD controls only.
(Lower Sign: U
Register Units: kW
value) Lower Limit: 0
Upper Limit: 80000
Default: 0
42005 Load Read Only Multiplier: 1.0 Indicates the total amount of PC 3.x
Demand Offset: 0 online kW bus capacity for
Online load demand. Only gensets
Capacity Size (bits): 32 which are eligible for load
(Upper Sign: U demand are counted.
Register Units: kW Available on PCC3300MLD
value) Lower Limit: 0 controls only.
Upper Limit: 80000
Default: 0
42006 Load Read Only Multiplier: 1.0 Indicates the total amount of PC 3.x
Demand Offset: 0 online kW bus capacity for
Online load demand. Only gensets
Capacity Size (bits): 32 which are eligible for load
(Lower Sign: U demand count. Available on
Register Units: kW PCC3300MLD controls only.
value) Lower Limit: 0
Upper Limit: 80000
Default: 0

A029X159 (Issue 14) 169


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


42007 Load Read Only Multiplier: 1.0 Indicates the time remaining PC 3.x
Demand Offset: 0 before gensets are allowed to
stop after initial start or after
Initial Delay Size (bits): 16 resuming halted load
Timer Sign: U demand. This timer is set by
Units: Seconds Load Demand Initial Delay.
Lower Limit: 0 Available on PCC3300MLD
controls only.
Upper Limit: 1500
Default: 0
42008 Load Read Only Multiplier: 1.0 Indicates the time remaining PC 3.x
Demand Start Offset: 0 before next genset is allowed
Delay Timer to start. This timer is set by
Size (bits): 16 Load Demand Start Delay.
Sign: U Available on PCC3300MLD
Units: Seconds controls only.
Lower Limit: 0
Upper Limit: 1500
Default: 0
42009 Load Read Only Multiplier: 1.0 Indicates the time remaining PC 3.x
Demand Stop Offset: 0 before next genset is allowed
Delay Timer to stop. This timer is set by
Size (bits): 16 Load Demand Stop Delay.
Sign: U Available on PCC3300MLD
Units: Seconds controls only.
Lower Limit: 0
Upper Limit: 1500
Default: 0
42010 Load Read Only 0: No Indicates when the current PC 3.x
Demand 1: Yes load and spare capacity
Spare requirements are satisfied.
Available on PCC3300MLD
Capacity controls only.
Available

42011 Load Read Only Multiplier: 1.0 Indicates the total kW value PC 3.x
Demand Offset: 0 of all currently active spare
capacity requests in the
Total Spare Size (bits): 32 system. Available on
Capacity Sign: U PCC3300MLD controls only.
Requested Units: kW
(Upper
Register Lower Limit: 0
value) Upper Limit: 80000
Default: 0

42012 Load Read Only Multiplier: 1.0 Indicates the total kW value PC 3.x
Demand Offset: 0 of all currently active spare
capacity requests in the
Total Spare Size (bits): 32 system. Available on
Capacity Sign: U PCC3300MLD controls only.
Requested Units: kW
(Lower
Register Lower Limit: 0
value) Upper Limit: 80000
Default: 0

170 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


42013 Load Read Only Multiplier: 1.0 The kW load at which the PC 3.x
Demand Next Offset: 0 next genset will be started.
Start Available on PCC3300MLD
Threshold Size (bits): 32 controls only.
(kW) (Upper Sign: U
Register Units: kW
value) Lower Limit: 0
Upper Limit: 80000
Default: 0

42014 Load Read Only Multiplier: 1.0 The kW load at which the PC 3.x
Demand Next Offset: 0 next genset will be started.
Start Available on PCC3300MLD
Threshold Size (bits): 32 controls only.
(kW) (Lower Sign: U
Register Units: kW
value) Lower Limit: 0
Upper Limit: 80000
Default: 0

42015 Load Read Only Multiplier: 1.0 The kW load at which the PC 3.x
Demand Next Offset: 0 next genset will be stopped.
Stop Available on PCC3300MLD
Threshold Size (bits): 32 controls only.
(Upper Sign: U
Register Units: kW
value) Lower Limit: 0
Upper Limit: 80000
Default: 0

42016 Load Read Only Multiplier: 1.0 The kW load at which the PC 3.x
Demand Next Offset: 0 next genset will be stopped.
Stop Available on PCC3300MLD
Threshold Size (bits): 32 controls only.
(Lower Sign: U
Register Units: kW
value) Lower Limit: 0
Upper Limit: 80000
Default: 0

A029X159 (Issue 14) 171


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


42017 Load Read Only 0: Gen1 Indicates the next genset to PC 3.x
Demand Next 1: Gen2 start by ID. Available on
Gen to start PCC3300MLD controls only.
(kW) 2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
42018 Load Read Only 0: Gen1 Indicates the next genset to PC 3.x
Demand Next 1: Gen2 stop by ID. Available on
Gen to Stop PCC3300MLD controls only.
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
42019 Load Read Only 0: Inactive Indicates the status of the PC 3.x
Demand 1: Active Load Demand Inhibit input.
Inhibit Local When ACTIVE all the gensets
will start. Available on
PCC3300MLD controls only.
43000 Genset % Read Only Multiplier: 0.1 Monitors the generator set PC 2.x,
Application Offset: 0 application L1 current PC 3.x
L1 Current percentage output.
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
43001 Genset % Read Only Multiplier: 0.1 Monitors the generator set PC 2.x,
Application Offset: 0 application L2 current PC 3.x
L2 Current percentage output.
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:

172 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43002 Genset % Read Only Multiplier: 0.1 Monitors the generator set PC 2.x,
Application Offset: 0 application L1 kVA PC 3.x
L1 kVA percentage output.
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
43003 Genset % Read Only Multiplier: 0.1 Monitors the generator set PC 2.x,
Application Offset: 0 application L3 current PC 3.x
L3 Current percentage output.
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
43004 Genset % Read Only Multiplier: 0.1 Monitors the generator set PC 2.x,
Application Offset: 0 application L2 kVA PC 3.x
L2 kVA percentage output.
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
43005 Genset % Read Only Multiplier: 0.1 Monitors the generator set PC 2.x,
Application Offset: 0 application L3 kVA PC 3.x
L3 kVA percentage output.
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
43006 Genset % Read Only Multiplier: 0.1 Monitors the generator set PC 2.x,
Application Offset: 0 application L1 KW PC 3.x
L1 kW percentage output.
Size (bits): 16
Sign: S
Unit: %
Lower Limit:
Upper Limit:
43007 Genset % Read Only Multiplier: 0.1 Monitors the generator set PC 2.x,
Application Offset: 0 application L2 KW PC 3.x
L2 kW percentage output.
Size (bits): 16
Sign: S
Unit: %
Lower Limit:
Upper Limit:
43008 Genset % Read Only Multiplier: 0.1 Monitors the generator set PC 2.x,
Application Offset: 0 application L3 KW PC 3.x
L3 kW percentage output.
Size (bits): 16
Sign: S
Unit: %
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 173


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43009 Genset % Read Only Multiplier: 0.1 Monitors the total generator PC 2.x,
Application Offset: 0 set application kVA PC 3.x
Total kVA percentage output.
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
43010 Genset % Read Only Multiplier: 0.1 Monitors the total generator PC 2.x,
Application Offset: 0 set application KW PC 3.x
Total kW percentage output.
Size (bits): 16
Sign: S
Unit: %
Lower Limit:
Upper Limit:
43011 Genset % Read Only Multiplier : 0.1 Monitors the genset standby PC 2.x,
Standby L1 Offset: 0 L1 kVA percentage output. PC 3.x
kVA
Size (bits): 16
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
43012 Genset % Read Only Multiplier : 0.1 Monitors the genset standby PC 2.x,
Standby L3 Offset: 0 L3 kVA percentage output. PC 3.x
kVA
Size (bits): 16
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
43013 Genset % Read Only Multiplier : 0.1 Monitors the genset standby PC 2.x,
Standby L2 Offset: 0 L2 kVA percentage output. PC 3.x
kVA
Size (bits): 16
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43014 Genset % Read Only Multiplier : 0.1 Monitors the genset standby PC 2.x,
Standby L1 Offset: 0 L1 KW percentage output. PC 3.x
kW
Size (bits): 16
Sign: S
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA

174 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43015 Genset % Read Only Multiplier : 0.1 Monitors the genset standby PC 2.x,
Standby L2 Offset: 0 L2 KW percentage output. PC 3.x
kW
Size (bits): 16
Sign: S
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43016 Genset % Read Only Multiplier : 0.1 Monitors the genset standby PC 2.x,
Standby L3 Offset: 0 L3 KW percentage output. PC 3.x
kW
Size (bits): 16
Sign: S
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43017 Genset % Read Only Multiplier: 0.1 Monitors the total generator PC 2.x,
Standby Total Offset: 0 set standby kVA percentage PC 3.x
kVA output.
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
43018 Genset Read Only Multiplier: 0.1 The generator set kVA rating. PC 2.x,
Application Offset: 0 PC 3.x
kVA rating
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:
43019 Genset Read Only Multiplier: 0.1 The generator set KW rating. PC 2.x,
Application Offset: 0 PC 3.x
kW rating
Size (bits): 16
Sign: U
Unit: kW
Lower Limit:
Upper Limit:
43020 Genset Read Only Multiplier: 1 The value of the generator PC 2.x,
Application Offset: 0 set application nominal PC 3.x
Nominal current. Displayed as
Current Size (bits): 16 ”Generator set Application
Sign: U Rated Current” in HMI
Unit: Amps
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 175


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43021 Genset Read Only Multiplier: 0.01 Generator set average PC 2.x,
Average Offset: 0 voltage percentage. PC 3.x
Voltage%
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
43030 Genset L1 Read Only Multiplier: 0.01 Generator set L1 power factor PC 2.x,
Power Factor Offset: 0 PC 3.x
Size (bits): 8
Sign: S
Unit: PF
Lower Limit:
Upper Limit:
43031 Genset L1L2 Read Only Multiplier: 0.01 Generator set L1L2 voltage PC 2.x,
Phase Offset: 0 phase angle PC 3.x
Difference
Size (bits): 16
Sign: U
Unit: Degrees
Lower Limit:
Upper Limit:
43032 Genset L1L2 Read Only Multiplier: 0.01 Generator set L1L2 voltage% PC 2.x,
Voltage% Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
43033 Genset L1N Read Only Multiplier: 0.01 Generator set L1N voltage% PC 2.x,
Voltage% Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
43044 Genset L2 Read Only Multiplier: 0.01 Generator set L2 power factor PC 2.x,
Power Factor Offset: 0 PC 3.x
Size (bits): 8
Sign: S
Unit: PF
Lower Limit: -1.28
Upper Limit: 1.27
43045 Genset L2L3 Read Only Multiplier: 0.01 Generator set L2L3 voltage PC 2.x,
Phase Offset: 0 phase angle PC 3.x
Difference
Size (bits): 8
Sign: U
Unit: Degrees
Lower Limit: 0
Upper Limit: 655.3

176 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43046 Genset L2L3 Read Only Multiplier: 0.01 Generator set L2L3 voltage% PC 2.x,
Voltage% Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
43047 Genset L2N Read Only Multiplier: 0.01 Generator set L2N voltage% PC 2.x,
Voltage% Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: %
Lower Limit: 0
Upper Limit: 655.3
43058 Genset L3 Read Only Multiplier: 0.01 Generator set L3 power factor PC 2.x,
Power Factor Offset: 0 PC 3.x
Size (bits): 8
Sign: S
Unit: PF
Lower Limit: -1.28
Upper Limit: 1.22
43059 Genset L3L1 Read Only Multiplier: 0.01 Generator set L3L1 voltage PC 2.x,
Phase Offset: 0 phase angle PC 3.x
Difference
Size (bits): 8
Sign: U
Unit: Degrees
Lower Limit: 0
Upper Limit: 655.3
43060 Genset L3L1 Read Only Multiplier: 0.01 Generator set L3L1 voltage% PC 2.x,
Voltage% Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: %
Lower Limit: 0
Upper Limit: 655.3
43061 Genset L3N Read Only Multiplier: 0.01 Generator set L3N voltage% PC 2.x,
Voltage% Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
43062 Genset Read Only Multiplier: 0.1 kVA rating for the generator PC 2.x,
Standby kVA Offset: 0 set in Standby configuration. PC 3.x
rating
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 177


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43063 Genset Read Only Multiplier: 0.1 KW rating for the generator PC 2.x,
Standby kW Offset: 0 set in Standby configuration. PC 3.x
rating
Size (bits): 16
Sign: U
Unit: kW
Lower Limit:
Upper Limit:
43064 Genset Read Only Multiplier: 1 The value of the generator PC 2.x,
Standby Offset: 0 set standby nominal current. PC 3.x
Nominal Displayed as ”Generator set
Current Size (bits): 16 Standby Rated Current” in
Sign: U HMI
Unit: Amps
Lower Limit:
Upper Limit:
43065 Genset Total Read Only Multiplier: 1 Generator set total kVAh PC 2.x,
kVAh Offset: 0 accumulation PC 3.x
Size (bits): 32
Sign: U
Unit: kVAh
Lower Limit:
Upper Limit:
43066 Genset Total Read Only Multiplier: 1 Generator set total kVAh PC 2.x,
kVAh Offset: 0 accumulation PC 3.x
Size (bits): 32
Sign: U
Unit: kVAh
Lower Limit:
Upper Limit:
43067 Genset Total Read Only Multiplier: 0.01 Total kVAR’s per Standby PC 2.x,
kVARs per Offset: 0 kVA. PC 3.x
Standby kVA
Size (bits): 16
Sign: S
Unit: %
Lower Limit:
Upper Limit:
43100 Genset Bus Read Only Multiplier : 0.01 Genset Bus average PC 3.x
Average Offset: 0 voltage%
Voltage%
Size (bits): 16
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43111 Genset Bus Read Only Multiplier: 0.01 Generator set Bus L1 power PC 3.x
L1 Power Offset: 0 factor
Factor
Size (bits): 8
Sign: S
Unit: PF
Lower Limit: -1.28
Upper Limit: 1.22

178 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43112 Genset Bus Read Only Multiplier: 0.01 Generator set bus L1L2 PC 3.x
L1L2 Phase Offset: 0 voltage phase angle
Difference
Size (bits): 16
Sign: U
Unit: Degrees
Lower Limit:
Upper Limit:
43113 Genset Bus Read Only Multiplier : 0.01 Genset Bus L1L2 voltage% PC 3.x
L1L2 Offset: 0
Voltage%
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
43114 Genset Bus Read Only Multiplier : 0.01 Genset Bus L1N voltage% PC 3.x
L1N Offset: 0
Voltage%
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43125 Genset Bus Read Only Multiplier: 0.01 Generator set Bus L2 power PC 3.x
L2 Power Offset: 0 factor
Factor
Size (bits): 8
Sign: S
Unit: PF
Lower Limit: NA
Upper Limit: NA
43126 Genset Bus Read Only Multiplier: 0.01 Generator set bus L2L3 PC 3.x
L2L3 Phase Offset: 0 voltage phase angle
Difference
Size (bits): 16
Sign: U
Unit: Degrees
Lower Limit: NA
Upper Limit: NA
43127 Genset Bus Read Only Multiplier : 0.01 Genset Bus L2L3 voltage% PC 3.x
L2L3 Offset: 0
Voltage%
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA

A029X159 (Issue 14) 179


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43128 Genset Bus Read Only Multiplier : 0.01 Genset Bus L2N voltage% PC 3.x
L2N Offset: 0
Voltage%
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43139 Genset Bus Read Only Multiplier: 0.01 Generator set Bus L3 power PC 3.x
L3 Power Offset: 0 factor
Factor
Size (bits): 8
Sign: S
Unit: PF
Lower Limit: -1.28
Upper Limit: 1.22
43140 Genset Bus Read Only Multiplier: 0.01 Generator set bus L3L1 PC 3.x
L3L1 Phase Offset: 0 voltage phase angle
Difference
Size (bits): 16
Sign: U
Unit: Degrees
Lower Limit:
Upper Limit:
43141 Genset Bus Read Only Multiplier : 0.01 Genset Bus L3L1 voltage% PC 3.x
L3L1 Offset: 0
Voltage%
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43142 Genset Bus Read Only Multiplier : 0.01 Genset Bus L3N voltage% PC 3.x
L3N Offset: 0
Voltage%
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43143 Genset Bus Read Only Multiplier: 1 Generator set bus total kVAh PC 3.x
Total kVAh Offset: 0 accumulation
Size (bits): 32
Sign: U
Unit: kVAh
Lower Limit:
Upper Limit:
Default: NA

180 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43144 Genset Bus Read Only Multiplier: 1 Generator set bus total kVAh PC 3.x
Total kVAh Offset: 0 accumulation
Size (bits): 32
Sign: U
Unit: kVAh
Lower Limit:
Upper Limit:
43145 Sync Phase Read Only Multiplier : 0.01 Other meter to genset meter PC 3.x
Difference Offset: 0 L1 voltage phase angle
Size (bits): 16
Sign: S
Units: deg
Lower Limit: NA
Upper Limit: NA
Default: NA
43146 Paralleling Read/Write 0: None Determines what the function PC 3.x
Application 1: Utility of the Other Meter is.
2: Genset Bus
43147 System Total Read Only Multiplier : 1 Sum of genset bus and utility PC 3.x
kVA Offset: 0 bus kVA
Size (bits): 16
Sign: U
Units: kVA
Lower Limit: NA
Upper Limit: NA
Default: NA
43148 System Total Read Only Multiplier : 1 Sum of genset bus and utility PC 3.x
kVAR Offset: 0 bus kVAR
Size (bits): 16
Sign: S
Units: kVAR
Lower Limit: NA
Upper Limit: NA
Default: NA
43149 System Total Read Only Multiplier : 1 Sum of genset bus and utility PC 3.x
kW Offset: 0 bus kW
Size (bits): 16
Sign: U
Units: kW
Lower Limit: NA
Upper Limit: NA
Default: NA
43150 System Total Read Only Multiplier : 0.01 System total power factor PC 3.x
Power Factor Offset: 0 (totalized value of utility bus
plus genset bus)
Size (bits): 8
Sign: U
Units: PF
Lower Limit: NA
Upper Limit: NA
Default: NA

A029X159 (Issue 14) 181


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43151 Utility Read Only Multiplier : 0.01 Utility average voltage% PC 3.x
Average Offset: 0
Voltage%
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43162 Utility L1 Read Only Multiplier: 0.01 Utility L1 power factor PC 3.x
Power Factor Offset: 0
Size (bits): 8
Sign: S
Unit: PF
Lower Limit: NA
Upper Limit: NA
43163 Utility L1L2 Read Only Multiplier: 0.01 Utility L1L2 voltage phase PC 3.x
Phase Offset: 0 angle
Difference
Size (bits): 16
Sign: U
Unit: Degrees
Lower Limit: NA
Upper Limit: NA
43164 Utility L1L2 Read Only Multiplier : 0.01 Utility L1L2 voltage% PC 3.x
Voltage% Offset: 0
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43165 Utility L1N Read Only Multiplier : 0.01 Utility L1N voltage% PC 3.X
Voltage% Offset: 0
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43176 Utility L2 Read Only Multiplier: 0.01 Utility L2 power factor PC 3.x
Power Factor Offset: 0
Size (bits): 8
Sign: S
Unit: PF
Lower Limit:
Upper Limit:

182 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43177 Utility L2L3 Read Only Multiplier: 0.01 Utility L2L3 voltage phase PC 3.x
Phase Offset: 0 angle
Difference
Size (bits): 16
Sign: U
Unit: Degrees
Lower Limit:
Upper Limit:
43178 Utility L2L3 Read Only Multiplier : 0.01 Utility L2L3 voltage% PC 3.x
Voltage% Offset: 0
Size (bits): 16
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
43179 Utility L2N Read Only Multiplier : 0.01 Utility L2N voltage% PC 3.x
Voltage% Offset: 0
Size (bits): 16
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43190 Utility L3 Read Only Multiplier: 0.01 Utility L3 power factor PC 3.x
Power Factor Offset: 0
Size (bits): 8
Sign: S
Unit: PF
Lower Limit: NA
Upper Limit: NA
43191 Utility L3L1 Read Only Multiplier: 0.01 Utility L3L1 voltage phase PC 3.x
Phase Offset: 0 angle
Difference
Size (bits): 16
Sign: U
Unit: Degrees
Lower Limit: NA
Upper Limit: NA
43192 Utility L3L1 Read Only Multiplier : 0.01 Utility L3L1 voltage% PC 3.x
Voltage% Offset: 0
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA

A029X159 (Issue 14) 183


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43193 Utility L3N Read Only Multiplier : 0.01 Utility L3N voltage% PC 3.x
Voltage% Offset: 0
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43194 Utility Total Read Only Multiplier: 1 Utility total kVAh PC 3.x
kVAh Offset: 0 accumulation
Size (bits): 32
Sign: U
Unit: kVAh
Lower Limit:
Upper Limit:
43195 Utility Total Read Only Multiplier: 1 Utility total kVAh PC 3.x
kVAh Offset: 0 accumulation
Size (bits): 32
Sign: U
Unit: kVAh
Lower Limit:
Upper Limit:
43196 Exhaust Read Only Multiplier : 0.1 Monitor point for the Exhaust PC 3.x
Stack Offset: 0 Stack Temperature Right
Temperature Bank received from ECM
Right Bank Size (bits): 16
Sign: S
Units: degF
Lower Limit: -459
Upper Limit: 3155
Default: NA
43197 Exhaust Read Only Multiplier : 0.1 Monitor point for the Exhaust PC 3.x
Stack Offset: 0 Stack Temperature Left Bank
Temperature received from ECM
Left Bank Size (bits): 16
Sign: S
Units: degF
Lower Limit: -459
Upper Limit: 3155
Default: NA
43200 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
uses addresses 43200-43219
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit: -459
Upper Limit: 3155

184 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43201 Genset Model Read Only Multiplier: 1 Number indentifying the PC 2.x,
Number Offset: 0 model of this generator set. PC 3.x
Modbus uses addresses
Size (bits): 168 43200-43219 for the 20
Sign: C characters of this string.
Unit:
Lower Limit:
Upper Limit:
43202 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
uses addresses 43200-43219
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43203 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
uses addresses 43200-43219
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43204 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
uses addresses 43200-43219
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43205 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
uses addresses 43200-43219
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43206 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
uses addresses 43200-43219
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43207 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
uses addresses 43200-43219
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 185


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43208 Genset Model Read Only Multiplier: 1 Number indentifying the PC 2.x,
Number Offset: 0 model of this generator set. PC 3.x
Modbus uses addresses
Size (bits): 168 43200-43219 for the 20
Sign: C characters of this string.
Unit:
Lower Limit:
Upper Limit:
43209 Genset Model Read Only Multiplier: 1 Number indentifying the PC 2.x,
Number Offset: 0 model of this generator set. PC 3.x
Modbus uses addresses
Size (bits): 168 43200 - 43219 for the 20
Sign: C characters of this string.
Unit:
Lower Limit:
Upper Limit:
43210 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
uses addresses 43200-43219
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43211 Genset Model Read Only Multiplier: 1 Number indentifying the PC 2.x,
Number Offset: 0 model of this generator set. PC 3.x
Modbus uses addresses
Size (bits): 168 43200-43219 for the 20
Sign: C characters of this string.
Unit:
Lower Limit:
Upper Limit:
43212 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
uses addresses 43200-43219
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43213 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
uses addresses 43200-43219
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43214 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
uses addresses 43200-43219
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:

186 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43215 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
uses addresses 43200-43219
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43216 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
uses addresses 43200-43219
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43217 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
uses addresses 43200-43219
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43218 Genset Model Read Only Multiplier: 1 Number indentifying the PC 2.x,
Number Offset: 0 model of this generator set. PC 3.x
Modbus uses addresses
Size (bits): 168 43200-43219 for the 20
Sign: C characters of this string.
Unit:
Lower Limit:
Upper Limit:
43219 Genset Model Read Only Multiplier: 1 Number identifying the model PC 2.x,
Number Offset: 0 of this generator set. Modbus PC 3.x
uses addresses 43200-43219
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43220 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
uses addresses 43220-43239
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43221 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
uses addresses 43220-43239
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 187


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43222 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
uses addresses 43220-43239
Size (bits): 168 for the 20 characters of this
Sign: C string. Uses logical addresses
Unit: 2048 - 6063 to store the first
Lower Limit: 16 characters. The last 4 are
stored in 691-694.
Upper Limit:
43223 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
uses addresses 43220-43239
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43224 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
uses addresses 43220-43239
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43225 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
uses addresses 43220-43239
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43226 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
uses addresses 43220-43239
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43227 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
uses addresses 43220-43239
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43228 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
uses addresses 43220-43239
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:

188 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43229 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
uses addresses 43220-43239
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43230 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
uses addresses 43220-43239
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43231 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
uses addresses 43220-43239
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43232 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
uses addresses 43220-43239
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43233 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
uses addresses 43220-43239
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43234 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
uses addresses 43220-43239
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43235 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
uses addresses 43220-43239
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 189


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43236 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
uses addresses 43220-43239
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43237 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
uses addresses 43220-43239
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43238 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
uses addresses 43220-43239
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43239 Genset Serial Read Only Multiplier: 1 Serial number of identifying PC 2.x,
Number Offset: 0 this generator set. Modbus PC 3.x
uses addresses 43220-43239
Size (bits): 168 for the 20 characters of this
Sign: C string.
Unit:
Lower Limit:
Upper Limit:
43240 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number model number. Modbus uses
Size (bits): 168 addresses 43240-43259 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43241 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number model number. Modbus uses
Size (bits): 168 addresses 43240-43259 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43242 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number model number. Modbus uses
Size (bits): 168 addresses 43240-43259 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:

190 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43243 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number model number. Modbus uses
Size (bits): 168 addresses 43240-43259 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43244 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number model number. Modbus uses
Size (bits): 168 addresses 43240-43259 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43245 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number model number. Modbus uses
Size (bits): 168 addresses 43240-43259 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43246 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number model number. Modbus uses
Size (bits): 168 addresses 43240-43259 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43247 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number model number. Modbus uses
Size (bits): 168 addresses 43240-43259 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43248 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number model number. Modbus uses
Size (bits): 168 addresses 43240-43259 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43249 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number model number. Modbus uses
Size (bits): 168 addresses 43240-43259 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 191


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43250 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number model number. Modbus uses
Size (bits): 168 addresses 43240-43259 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43251 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number model number. Modbus uses
Size (bits): 168 addresses 43240-43259 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:

43252 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,


Model Offset: 0 generator sets alternator PC 3.x
Number model number. Modbus uses
Size (bits): 168 addresses 43240-43259 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43253 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number model number. Modbus uses
Size (bits): 168 addresses 43240-43259 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:

43254 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,


Model Offset: 0 generator sets alternator PC 3.x
Number model number. Modbus uses
Size (bits): 168 addresses 43240-43259 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43255 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number model number. Modbus uses
Size (bits): 168 addresses 43240-43259 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:

192 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43256 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number model number. Modbus uses
Size (bits): 168 addresses 43240-43259 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43257 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number model number. Modbus uses
Size (bits): 168 addresses 43240-43259 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43258 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number model number. Modbus uses
Size (bits): 168 addresses 43240-43259 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43259 Alternator Read Only Multiplier: 1 Number identifying this PC 2.x,
Model Offset: 0 generator sets alternator PC 3.x
Number model number. Modbus uses
Size (bits): 168 addresses 43240-43259 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43260 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number serial number. Modbus uses
Size (bits): 168 addresses 43260-43279 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43261 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number serial number. Modbus uses
Size (bits): 168 addresses 43260-43279 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:

43262 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,


Serial Offset: 0 this generator sets alternator PC 3.x
Number serial number. Modbus uses
Size (bits): 168 addresses 43260-43279 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 193


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43263 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number serial number. Modbus uses
Size (bits): 168 addresses 43260-43279 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43264 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number serial number. Modbus uses
Size (bits): 168 addresses 43260-43279 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43265 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number serial number. Modbus uses
Size (bits): 168 addresses 43260-43279 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43266 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number serial number. Modbus uses
Size (bits): 168 addresses 43260-43279 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:

43267 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,


Serial Offset: 0 this generator sets alternator PC 3.x
Number serial number. Modbus uses
Size (bits): 168 addresses 43260-43279 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43268 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number serial number. Modbus uses
Size (bits): 168 addresses 43260-43279 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:

194 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43269 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number serial number. Modbus uses
Size (bits): 168 addresses 43260-43279 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43270 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number serial number. Modbus uses
Size (bits): 168 addresses 43260-43279 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43271 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number serial number. Modbus uses
Size (bits): 168 addresses 43260-43279 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43272 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number serial number. Modbus uses
Size (bits): 168 addresses 43260-43279 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43273 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number serial number. Modbus uses
Size (bits): 168 addresses 43260-43279 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:

43274 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,


Serial Offset: 0 this generator sets alternator PC 3.x
Number serial number. Modbus uses
Size (bits): 168 addresses 43260-43279 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43275 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number serial number. Modbus uses
Size (bits): 168 addresses 43260-43279 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 195


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43276 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number serial number. Modbus uses
Size (bits): 168 addresses 43260-43279 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:

43277 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x, PC


Serial Offset: 0 this generator sets alternator 3.x
Number serial number. Modbus uses
Size (bits): 168 addresses 43260-43279 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43278 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number serial number. Modbus uses
Size (bits): 168 addresses 43260-43279 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43279 Alternator Read Only Multiplier: 1 Unique number identifying PC 2.x,
Serial Offset: 0 this generator sets alternator PC 3.x
Number serial number. Modbus uses
Size (bits): 168 addresses 43260-43279 for
Sign: C the 20 characters text string.
Unit:
Lower Limit:
Upper Limit:
43280 Coolant Level Read Only 0: Inactive Coolant Level input software PC 2.x,
Switch 1: Active state status. Gives software PC 3.x
Inactive/Active state
43281 Coolant Read Only 0: Inactive This is the status of the PC 2.x,
Level/Configu 1: Active Configurable Input #5. PC 3.x
rable Input #5
Switch
43283 Fault Reset Read Only 0: Inactive Fault Reset input software PC 2.x,
Switch 1: Active state status. Gives software PC 3.x
Inactive/Active state
43284 Fault Read Only 0: Inactive This is the status of the PC 2.x,
Reset/Config 1: Active Configurable Input #10. PC 3.x
urable Input
#10 Switch
43285 Genset CB Read Only 0: Inactive This is the status of the PC 3.x
Inhibit/Config 1: Active Configurable Input #28.
urable Input
#28 Switch
43286 Genset CB Read Only 0: Inactive This is the status of the PC 3.x
Pos 1: Active Configurable Input #26.
B/Configurabl
e Input #26
Switch

196 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43287 Genset CB Read Only 0: Inactive This is the status of the PC 3.x
Tripped/Confi 1: Active Configurable Input #27.
gurable Input
#27 Switch
43288 Genset CB Read Only 0: Inactive Genset CB Inhibit input PC 3.x
Inhibit Switch 1: Active software state status. Gives
software Inactive/Active state
43289 Genset CB Read Only 0: Inactive Genset CB Pos A input PC 3.x
Pos A Switch 1: Active software state status. Gives
software Inactive/Active state
43290 Genset CB Read Only 0: Inactive Genset CB Pos B input PC 3.x
Pos B Switch 1: Active software state status. Gives
software Inactive/Active state
43291 Genset CB Read Only 0: Inactive Genset CB Tripped input PC 3.x
Tripped 1: Active software state status. Gives
Switch software Inactive/Active state
43292 Ground Fault Read Only 0: Inactive Ground Fault Switch function PC 2.x,
Switch 1: Active output status. Gives software PC 3.x
Inactive/Active state
43293 High Alt Read Only 0: Inactive High Alt Temperature Switch PC 2.x,
Temp Switch 1: Active function output status. Gives PC 3.x
software Inactive/Active state
43295 Load Read Only 0: Inactive This is the status of the PC 3.x
Demand 1: Active Configurable Input #31.
Stop/Configur
able Input
#31 Switch
43296 Local E-stop Read Only 0: Inactive Monitors the E–Stop switch. PC 2.x,
Switch 1: Active PC 3.x
43297 Low Coolant Read Only 0: Inactive Low Coolant #2 Switch PC 2.x,
#2 Switch 1: Active function output status. Gives PC 3.x
software Inactive/Active state
43298 Low Engine Read Only 0: Inactive Low Engine Temperature PC 2.x,
Temperature 1: Active Switch function output status. PC 3.x
Switch Gives software Inactive/Active
state
43299 Low Fuel In Read Only 0: Inactive Low Fuel In Day Tank Switch PC 2.x,
Day Tank 1: Active function output status. Gives PC 3.x
Switch software Inactive/Active state
43300 Genset Bus Read/Write 0: Delta Delta or Wye for Utility PC 3.x
Delta/Wye 1: Wye connection
Connection
43301 Genset Bus Read Only Multiplier: 1 Generator set Bus nominal PC 3.x
Nominal Offset: 0 voltage
Voltage
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit: 110
Upper Limit: 45000
43302 Genset Read Only 0: Delta Delta or Wye for Generator PC 2.x,
Delta/Wye 1: Wye set connection PC 3.x
Connection

A029X159 (Issue 14) 197


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43303 Genset Read Only Multiplier: 1 Generator set nominal line- PC 2.x,
Nominal Offset: 0 line voltage PC 3.x
Voltage
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit: 110
Upper Limit: 45000
43304 Single/3 Read Only 0: Single Phase Setup mode interlocked. PC 2.x,
Phase 1: Three Phase Generator set’s single PC 3.x
Connection phase/3 phase metering
setup configuration.
43306 Utility Read/Write 0: Delta Delta or Wye for Utility PC 3.x
Delta/Wye 1: Wye connection
Connection
43307 Utility Read Only Multiplier: 1 Utility nominal voltage PC 3.x
Nominal Offset: 0
Voltage
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit: 110
Upper Limit: 45000
43309 Overfrequenc Read/Write 0: Disabled Enables over frequency PC 2.x,
y Enable 1: Enabled diagnostic witness test. PC 3.x
43310 Overload Read/Write Multiplier: 1 The time delay until an PC 2.x,
Warning Set Offset: 0 overload condition is reported PC 3.x
Time as a fault
Size (bits): 8
Sign: U
Unit: seconds
Lower Limit: 1
Upper Limit: 120
43311 Overload Read/Write Multiplier: 0.01 Sets the Overload Warning PC 2.x,
Warning Offset: 0 fault trip threshold as PC 3.x
Threshold percentage of generator set
Size (bits): 16 application kW rating.
Sign: U
Unit: %
Lower Limit: 80
Upper Limit: 140
43312 Overload Read / Write Multiplier : 1 The time delay until an PC 3.x
Shutdown Set Offset: 0 overload condition is reported
Time as Shutdown fault
Size (bits): 16
Sign: U
Units: Seconds
Lower Limit: 1
Upper Limit: 120
Default: 60

198 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43313 Overload Read / Write Multiplier : 0.01 Sets the Overload Shutdown PC 3.x
Shutdown Offset: 0 fault trip threshold as
threshold percentage of genset
Size (bits): 16 application kW rating. To
Sign: U disable the Overload
Units: % shutdown fault set the value
Lower Limit: 70 to 655.35 or Not Available.
Upper Limit: 655.35
Default: 655.35
43314 Prelube Read / Write 0: GCS Selects whether prelube PC 3.x
Function 1: ECS function is being controlled by
Owner GCS or ECS
43315 Non Read / Write 0: Allow Start Selects whether to allow or PC 3.x
Lubricated 1: Block Start block genset starting when
Non- not lubricated in case of Non-
Emergency Emergency start. Applicable
Start only when Prelube Function
Owner = ECS
43338 CAN Failure Read/Write Multiplier: 1 Sets the maximum number of PC 2.x,
Retries Offset: 0 CAN communication retries PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 10
43339 Auto Sleep Read/Write 0: Awake in Auto Trim that determines if the PC 2.x,
Enable 1: Sleep in Auto control will stay awake in PC 3.x
Auto mode or Fall asleep in
Auto mode.
43340 Max Setup Read/Write Multiplier: 1 Max time allowed in Setup PC 2.x,
Mode Time Offset: 0 Mode. PC 3.x
Size (bits): 16
Sign: U
Unit: Seconds
Lower Limit: 30
Upper Limit: 3600
43341 Power Down Read/Write 0: Disable Trim to enable Sleep Mode PC 2.x,
Mode Enable 1: Enable PC 3.x
43342 Power Down Read/Write Multiplier: 1 Timer setting for the Power PC 2.x,
Mode Time Offset: 0 Down delay feature PC 3.x
Delay
Size (bits): 16
Sign: U
Unit: Seconds
Lower Limit: 0
Upper Limit: 600
43343 Setup Mode Read/Write 0: Disable Volatile to allow entry into PC 2.x,
Enable 1: Enable Setup Mode PC 3.x

A029X159 (Issue 14) 199


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43344 Clock Date Read/Write Multiplier: 1 Use to set or read the current PC 2.x,
Offset: 0 date. PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 31
43345 Clock Hour Read/Write Multiplier: 1 Use to set or read the current PC 2.x,
Offset: 0 hour. PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 32
43346 Clock Minute Read/Write Multiplier: 1 Use to set or read the current PC 2.x,
Offset: 0 minute. PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 59
43347 Clock Mode Read/Write 0: Normal Use to set the real time clock PC 2.x,
1: Set Clock and save settings. PC 3.x
2: Save Clock
43348 Clock Month Read/Write Multiplier: 1 Use to set or read the current PC 2.x,
Offset: 0 month. PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 12
43349 Clock Second Read/Write Multiplier: 1 Use to set or read the current PC 2.x,
Offset: 0 second. PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 59
43350 Clock Year Read/Write Multiplier: 1 Use to set or read the current PC 2.x,
Offset: 0 year. PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 99

200 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43351 Daylight Read/Write Multiplier: 1 Use to set the hour of the day PC 2.x,
Savings End Offset: 0 when daylight savings time PC 3.x
Hour ends.
Size (bits): 8
Sign: U
Unit:
Lower Limit: 2
Upper Limit: 19
43352 Daylight Read/Write Multiplier: 1 Use to set the month when PC 2.x,
Savings End Offset: 0 daylight savings time ends. PC 3.x
Month
Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 12
43353 Daylight Read/Write 0: First Occurrence Use to set the week of the PC 2.x,
Savings End 1: Second Occurrence month when daylight savings PC 3.x
Week time ends.
Occurrence in 2: Third Occurrence
Month 3: Fourth Occurrence
4: Last Occurrence
43354 Daylight Read/Write 0: Sunday Use to set the day of the PC 2.x,
Savings Start 1: Monday week when daylight savings PC 3.x
Day time starts.
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
43355 Daylight Read/Write Multiplier: 1 Use to set the hour of the day PC 2.x,
Savings Start Offset: 0 when daylight savings time PC 3.x
Hour starts.
Size (bits): 8
Sign: U
Unit:
Lower Limit: 2
Upper Limit: 19
43356 Daylight Read/Write Multiplier: 1 Use to set the month when PC 2.x,
Savings Start Offset: 0 daylight savings time starts. PC 3.x
Month
Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 12
43357 Daylight Read/Write 0: First Occurrence Use to set the week of the PC 2.x,
Savings Start 1: Second Occurrence month when daylight savings PC 3.x
Week time starts.
Occurrence in 2: Third Occurrence
Month 3: Fourth Occurrence
4: Last Occurrence

A029X159 (Issue 14) 201


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43358 Daylight Read/Write Multiplier: 1 Use to set the amount of PC 2.x,
Savings Time Offset: 0 daylight savings time PC 3.x
Adjustment adjustment applied.
Size (bits): 8
Sign: U
Unit: Minutes
Lower Limit: 0
Upper Limit: 120
43359 Daylight Read/Write 0: Disabled Use to enable the daylight PC 2.x,
Savings Time 1: Enabled savings time feature. PC 3.x
Enable
43360 Exercise Read/Write 0: Disabled Enables the exercise PC 2.x,
Scheduler 1: Enabled scheduler. PC 3.x
Enable
43361 Reset Fuel Read/Write 0: Inactive The reset trip fuel PC 2.x,
Consumption 1: Active consumption command. PC 3.x
43362 Reset Runs Read/Write 0: Inactive The reset runs command. PC 2.x,
1: Active PC 3.x
43363 Reset Start Read/Write 0: Inactive The reset start attempts PC 2.x,
Attempts 1: Active command. PC 3.x
43364 Scheduler Read/Write Multiplier: 1 Used to select an exception PC 2.x,
Exception Offset: 0 to adjust. PC 3.x
Select
Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 6
43365 Scheduler Read / Write Multiplier : 1 Used to adjust the date for PC 2.x,
Exception x Offset: 0 the selected exception. PC 3.x
Date
Size (bits): 8
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 31
43366 Scheduler Read / Write Multiplier : 1 Used to adjust the length in PC 2.x,
Exception x Offset: 0 days for the selected PC 3.x
Duration exception.
Days Size (bits): 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 44
43367 Scheduler Read / Write Multiplier : 1 Used to adjust the length in PC 2.x,
Exception x Offset: 0 hours for the selected PC 3.x
Duration exception.
Hours Size (bits): 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 23

202 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43368 Scheduler Read / Write Multiplier : 1 Used to adjust the length in PC 2.x,
Exception x Offset: 0 minutes for the selected PC 3.x
Duration exception.
Minutes Size (bits): 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 59
Default: 0
43369 Scheduler Read / Write 0 : Disable Used to enable or disable the PC 2.x,
Exception x 1 : Enable selected exception. PC 3.x
Enable
43370 Scheduler Read / Write Multiplier : 1 Used to adjust the starting PC 2.x
Exception x Offset: 0 hour for the selected PC 3.x
Hour exception.
Size (bits): 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 23
Default: 0
43371 Scheduler Read / Write Multiplier : 1 Used to adjust the starting PC 2.x,
Exception x Offset: 0 minute for the selected PC 3.x
Minute exception.
Size (bits): 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 59
Default: 0
43372 Scheduler Read / Write Multiplier : 1 Used to adjust the starting PC 2.x,
Exception x Offset: 0 month for the selected PC 3.x
Month exception.
Size (bits): 8
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 12
Default: 1
43373 Scheduler Read / Write 0: Once Only Used to adjust the repeat PC 2.x,
Exception x 1: Every Year interval for the selected PC 3.x
Repeat exception.
43374 Scheduler Read/Write Multiplier: 1 Used to select a program to PC 2.x,
Program Offset: 0 adjust. PC 3.x
Select
Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 12

A029X159 (Issue 14) 203


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43375 Scheduler Read / Write Multiplier : 1 Used to adjust the length in PC 2.x,
Program x Offset: 0 hours for the selected PC 3.x
Duration program.
Hours Size (bits): 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 23
Default: 0
43376 Scheduler Read / Write Multiplier : 1 Used to adjust the length in PC 2.x,
Program x Offset: 0 minutes for the selected PC 3.x
Duration program.
Minutes Size (bits): 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 59
Default: 0
43377 Scheduler Read/Write 0: Disable Used to enable or disable the PC 2.x,
Program x 1: Enable selected program. PC 3.x
Enable
43378 Scheduler Read / Write 0: Once Used to adjust the repeat PC 2.x,
Program x 1: Every Week interval for the selected PC 3.x
Repeat program.
Interval 2: Every 2 Weeks
3: Every 3 Weeks
4: Every 4 Weeks
5: Every 5 Weeks
6: First Week of Month
7: Second Week of Month
8: Third Week of Month
9: Fourth Week of Month
10: Last Week of Month
43379 Scheduler Read/Write 0: No Load Used to adjust the run mode PC 3.x
Program x 1: With Load for the selected program.
Run Mode
2: Extended Parallel
43380 Scheduler Read / Write 0: Sunday Used to adjust the start day PC 2.x,
Program x 1: Monday of the week for the selected PC 3.x
Start Day program.
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
43381 Scheduler Read / Write Multiplier : 1 Used to adjust the start hour PC 2.x,
Program x Offset: 0 for the selected program. PC 3.x
Start Hour
Size (bits): 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 23
Default: 0

204 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43382 Scheduler Read / Write Multiplier : 1 Used to adjust the start PC 2.x,
Program x Offset: 0 minute for the selected PC 3.x
Start Minute program.
Size (bits): 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 59
Default: 0
43383 Daylight Read/Write 0: Sunday Use to set the day of the PC 2.x,
Savings End 1: Monday week when daylight savings PC 3.x
Day time ends.
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
43501 Genset Run Read Only 0: Emergency Remote Start Source or type of current PC 2.x,
Type 1: Non Emergency Remote genset run (if running) or PC 3.x
Start previous genset run (if
stopped).
2: Load Demand Start
3: Manual Run
4: Exercise
43502 Idle Rated Read Only 0: Idle The output command of the PC 2.x,
Command 1: Rated Idle/Rated Logic PC 3.x
43503 Idle Request Read Only 0: False Indicates a request to go to PC 2.x,
1: True manual idle. Manual idle PC 3.x
allowed if breaker is open or
not controlled
43506 Load Dump Read Only 0: Inactive Monitors the software PC 2.x,
Command 1: Active command to the load dump PC 3.x
driver output
2: Reserved
3: Not Available
43507 Load Dump Read Only 0: Inactive Monitors the state of the load PC 2.x,
Overload 1: Active dump overload detection PC 3.x
Condition algorithm
2: Reserved
3: Not Available
43508 Load Dump Read Only 0: Inactive The state of the load dump PC 2.x,
Underfrequen 1: Active underfrequency detection PC 3.x
cy Condition algorithm
2: Reserved
3: Not Available
43509 Low Battery Read Only Multiplier: 0.1 The low battery voltage PC 2.x,
Voltage Offset: 0 threshold when the generator PC 3.x
Running set is in rated mode
Threshold Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 205


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43510 Low Battery Read Only Multiplier: 0.1 The low battery voltage PC 2.x,
Voltage Offset: 0 threshold when the generator PC 3.x
Stopped set is not in rated mode
Threshold Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit:
Upper Limit:
43511 Low Battery Read Only Multiplier: 0.1 The selection of the running PC 2.x,
Voltage Offset: 0 or stopped threshold PC 3.x
Threshold
Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit:
Upper Limit:
43512 Manual Read Only 0: Not Manual The output of the Manual PC 2.x,
Command 1: Manual Command OR logic PC 3.x
43513 Manual Read Only Multiplier : 1 Bitmask to show the inputs to PC 2.x,
Command Offset: 0 the Command output which PC 3.x
Inputs are currently on
Size (bits): 8
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
43515 Oil Priming Read Only 0: Inactive The Prelube Driver PC 2.x,
Pump 1: Active Command. PC 3.x
Command
2: Reserved
3: Not Available
43516 Prelube Mode Read Only 0: Crank After Prelube Set to a required mode based PC 2.x,
1: Crank With Prelube on the type of starting PC 3.x
requirement
2: Prelube Only
43517 Prelube State Read Only 0: Complete The monitor point for the PC 2.x,
1: Armed prelube state. PC 3.x
2: Prelube Output ON
3: Prelube Output OFF
4: Enable Crank
43518 PTC Genset Read Only 0: Off Current mode for the genset PC 3.x
Operating 1: Manual operation part of the PTC
Mode function
2: Normal
3: Normal Override
4: Test
5: Exercise
6: Utility Fail
7: Extended Parallel
43519 PTC Mode Read Only 0: Inactive The output of the PTC Mode PC 3.x
Switch 1: Active Switch Command OR logic
Command
2: Reserved
3: Not Available

206 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43520 PTC Mode Read Only Multiplier : 1 Bitmask to show the inputs to PC 3.x
Switch Offset: 0 the Command output which
Command are currently on.
Inputs Size (bits): 8
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
43521 PTC Status Read Only 0: Off/ Not Enabled Indicates what the current PC 3.x
1: Manual Mode state is of PTC control action
2: Normal Utility
3: Retransfer
4: Retransfer Override
5: Emergency Test
6: Normal Test
7: Exercise
8: Utility Failure
9: Extended Parallel
43522 PTC Transfer Read Only 0: Off Operation mode for the PC 3.x
Pair 1: Manual breaker pair portion of the
Operating PTC function
Mode 2: Normal
3: Normal Override
4: Test
5: Exercise
6: Utility Fail
7: Extended Parallel
43523 Ready to Read Only 0: Inactive The state that the Ready to PC 2.x,
Load 1: Active Load Driver output is being PC 3.x
Command commanded to
2: Reserved
3: Not Available
43524 Remote Start Read Only 0: Stop The output of the Remote PC 2.x,
Command 1: Start Start Command OR logic PC 3.x
43526 Remote Start Read Only 0: Off Status of remote start and PC 2.x,
State 1: Remote Start load demand stop inputs PC 3.x
2: Load Demand Stop
3: Load Demand Start
43527 RMS Read Only Multiplier : 0.01 The RMS voltage (or current) PC 2.x,
Regulation Offset: 0 error at the AVR PC 3.x
Error
Size (bits): 16
Sign: S
Units: %
Lower Limit: -100
Upper Limit: 100
Default: NA
43528 Run Read Only 0: Off The signal that is PC 2.x,
Command 1: Run commanding a change to the PC 3.x
run mode
43529 Run Relay Read Only 0: Inactive The status of relay command PC 2.x,
Command 1: Active when genset is in frequency PC 3.x
and rated mode.

A029X159 (Issue 14) 207


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43530 Speed and Read Only 0: Inactive Monitor point for the PC 3.x
Voltage Bias 1: Active command which closes the
Relay on-board relay enabling the
Command voltage and speed bias
outputs.
43531 Speed Bias Read Only Multiplier : 0.01 Indicates amount of speed PC 3.x
Command Offset: 0 bias offset GCS is
commanding to ECS
Size (bits): 16 governor or external governor
Sign: S
Units: %
Lower Limit: 0
Upper Limit: NA
Default: NA
43533 Start Read Only Multiplier: 1 Time remaining until start is PC 2.x,
Countdown Offset: 0 initiated PC 3.x
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 300
Default: NA
43536 Start Type Read Only 0: Emergency The output of the Start Type PC 2.x,
Command 1: Non Emergency Command OR logic PC 3.x
43537 Start Type Read Only Multiplier : 1 Bitmask to show the inputs to PC 2.x,
Command Offset: 0 the Command output which PC 3.x
Inputs are currently on
Size (bits): 8
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
43538 Starter Read Only 0: Inactive State of hardware output. PC 2.x,
Command 1: Active PC 3.x
2: Reserved
3: Not Available
43539 Stop Read Only Multiplier: 1 Time remaining until PC 2.x,
Countdown Offset: 0 generator set stops PC 3.x
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 5000
43540 Switch Panel Read Only 0: None Status of run and exercise PC 2.x,
Run Request 1: Manual commands from display panel PC 3.x
2: Exercise

208 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43542 Target Read Only Multiplier : 0.01 The target voltage without PC 2.x,
Voltage Offset: 0 ramping and torque match PC 3.x
voltage rolloff effects
Size (bits): 16
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 150
Default: NA
43543 Time At No Read Only Multiplier: 1 Amount of time the generator PC 2.x,
Load Offset: 0 set has run at no load PC 3.x
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 600
Default: NA
43544 Time at Read Only Multiplier: 1 Amount of time spend in PC 2.x,
Rated Offset: 0 Rated Cooldown PC 3.x
Cooldown
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 5000
43546 Voltage Bias Read Only Multiplier : 0.01 Indicates amount of voltage PC 3.x
Command Offset: 0 bias offset GCS is
commanding to an external
Size (bits): 16 regulator
Sign: S
Units: %
Lower Limit: 0
Upper Limit: NA
Default: NA
43547 Voltage Read Only Multiplier: 0.01 The voltage setpoint PC 2.x,
Setpoint Offset: 0 command PC 3.x
Size (bits): 16
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 150
43550 Weak Battery Read Only Multiplier: 0.1 Monitor point for the weak PC 2.x,
Threshold Offset: 0 battery voltage threshold PC 3.x
Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: 6
Upper Limit: 16

A029X159 (Issue 14) 209


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43551 Weak Battery Read/Write Multiplier: 1 The time delay until a weak PC 2.x,
Voltage Set Offset: 0 battery condition is reported PC 3.x
Time as a fault
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 1
Upper Limit: 5
43552 Paralleling Read Only Multiplier : 0.01 Voltage offset to voltage PC 2.x,
Voltage Ref Offset: 0 regulator for paralleling PC 3.x
Offset function
Size (bits): 16
Sign: S
Units: %
Lower Limit: NA
Upper Limit: NA
43553 Synchronizer Read Only 0: Synchronizer Off Indicates whether PC 3.x
Status 1: Synchronizer On synchronizer is on or off

43554 Active Read Only Multiplier: 0.1 Countdown value of the PC 3.x
Transition Offset: 0 active transition timer
Timer
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit:
Upper Limit:
43555 Active Read Only 0: None Indicates the active transition PC 3.x
Transition 1: Programmed Transition type for PTC
Type
2: Transfer
3: Retransfer
4: Max Parallel
43556 Arbitration Read Only 0: Off Indicates current arbitration PC3.x
State 1: Arbitrate0 state
2: Winner
3: Arbitrate1
4: Sleep
43557 Arbitration Read Only Multiplier : 1 Arbitration loop countdown PC 3.x
Timer Offset: 0 timer
Size (bits): 16
Sign: U
Units: msec
Lower Limit: NA
Upper Limit: NA
Default: NA
43567 Genset Read Only 0: Unknown Indicates genset breaker PC 3.x
Current 1: Closed position based on current
Based
Breaker
Position

210 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43558 ES State Read Only 0: Standby Internal paralleling status PC 3.x
1: Dead Bus variable
2: Synchronize
3: Load Share
4: Load Govern

43559 First Start Read Only 0: First Start Not Allowed Indicates status of the first PC 3.x
State 1: First Start Requested start system
2: First Start Permitted
43560 Genset CB Read Only 0: Inactive Generator set cb close PC 3.x
Close 1: Active command status
Command
43561 Genset CB Read Only 0: Inactive Status of gen fail to close PC 3.x
Fail To Close 1: Active lockout function
Lockout
43562 Genset CB Read Only 0: Open Indicates generator set PC 3.x
Position 1: Closed breaker position
Status
2: Not Available
43563 Genset Read Only 0: Not Available Indicates status of the PC 3.x
Availability 1: Available generator set source
Status
2: Unknown
43564 Bus Status Read Only 0: Unavailable Indicates status of the bus PC 3.x
1: Dead
2: Live
43565 Genset CB Read Only 0: Inactive Generator set cb inhibit PC 3.x
Inhibit 1: Active command
Command
43566 Genset CB Read Only 0: Inactive Generator set cb tripped PC 3.x
Tripped 1: Active command
Command
43568 Genset Read Only Multiplier: 0.1 Indicates the lower drop-out PC 3.x
Frequency Offset: 0 threshold in Hz for generator
Lower Drop- set frequency sensor
Out Size (bits): 16
Threshold Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
43569 Genset Read Only Multiplier: 0.1 Indicates the lower pick-up PC 3.x
Frequency Offset: 0 threshold in Hz for generator
Lower Pick- set frequency sensor
Up Threshold Size (bits): 16
Sign: U
Unit: Hz
Lower Limit:
Upper Limit
43570 Genset Read Only 0: Unknown Indicates generator set PC 3.x
Frequency 1: Picked Up frequency sensor status
Sensor
Status 2: Dropped Out

A029X159 (Issue 14) 211


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43571 Genset Read Only Multiplier: 0.1 Indicates the upper drop-out PC 3.x
Frequency Offset: 0 threshold in Hz for generator
Upper Drop- set frequency sensor
Out Size (bits): 16
Threshold Sign: U
Unit: Hz
Lower Limit:
Upper Limit
43572 Genset Read Only Multiplier: 0.1 Indicates the upper pick-up PC 3.x
Frequency Offset: 0 threshold in Hz for generator
Upper Pick- set frequency sensor
Up Threshold Size (bits): 16
Sign: U
Unit: Hz
Lower Limit:
Upper Limit
43573 Genset Loss Read Only 0: Unknown Indicates generator set loss PC 3.x
of Phase 1: Picked Up of phase sensor status
Sensor
Status 2: Dropped Out

43574 Genset Read Only Multiplier: 1 Indicates the drop-out PC 3.x


Overvoltage Offset: 0 threshold in volts for
Drop-Out generator set over voltage
Threshold Size (bits): 16 sensor
Sign: U
Unit: Vac
Lower Limit:
Upper Limit
43575 Genset Read Only Multiplier: 1 Indicates the pick-up PC 3.x
Overvoltage Offset: 0 threshold in volts for
Pick-Up generator set over voltage
Threshold Size (bits): 16 sensor
Sign: U
Unit: Vac
Lower Limit:
Upper Limit
43576 Genset Read Only 0: Unknown Indicates generator set over PC 3.x
Overvoltage 1: Picked Up voltage sensor status
Sensor
Status 2: Dropped Out

43577 Genset Read Only 0: Unknown Indicates generator set phase PC 3.x
Phase 1: Picked Up rotation sensor status
Rotation
Sensor 2: Dropped Out
Status
43578 Genset Read Only Multiplier: 1 Indicates the drop-out PC 3.x
Undervoltage Offset: 0 threshold in volts for
Drop-Out generator set under voltage
Threshold Size (bits): 16 sensor
Sign: U
Unit: Vac
Lower Limit:
Upper Limit

212 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43579 Genset Read Only Multiplier: 1 Indicates the pick-up PC 3.x
Undervoltage Offset: 0 threshold in volts for
Pick-Up generator set under voltage
Threshold Size (bits): 16 sensor
Sign: U
Unit: Vac
Lower Limit:
Upper Limit
43580 Genset Read Only 0: Unknown Indicates generator set under PC 3.x
Undervoltage 1: Picked Up voltage sensor status
Sensor
Status 2: Dropped Out

43581 Master First Read Only 0: Inactive Status of the first start output PC 3.x
Start Output 1: Active command
Command
43582 Maximum Read Only Multiplier : 0.1 Countdown value of the PC 3.x
Parallel Timer Offset: 0 maximum parallel timer
Size (bits): 16
Sign: U
Units: Seconds
Lower Limit: NA
Upper Limit: NA
Default: NA
43583 Maximum Read Only 0: Not Timing Indicates status of the PC 3.x
Parallel Timer 1: Timing maximum parallel timer
Status
2: Expired
43584 Paralleling Read Only 0: Isochronous Indicates which speed control PC 2.x,
Speed 1: Droop algorithm is in effect PC 3.x
Control Mode
2: Synchronize
3: Load Share
4: Load Govern
43585 Paralleling Read Only 0: Isochronous Indicates which voltage PC 2.x,
Voltage 1: Droop control algorithm is in effect PC 3.x
Control Mode
2: Synchronize
3: Load Share
4: Load Govern
43586 Programmed Read Only Multiplier : 0.1 Countdown value of the PC 3.x
Transition Offset: 0 programmed transition timer
Timer
Size (bits): 16
Sign: U
Units: Seconds
Lower Limit: NA
Upper Limit: NA
Default: NA
43587 Programmed Read Only 0: Not Timing Indicates status of the PC 3.x
Transition 1: Timing programmed transition timer
Timer Status
2: Expired
43588 PTC Enable Read Only 0: Disable Indicates if PTC functions are PC 3.x
Status 1: Enable running

A029X159 (Issue 14) 213


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43589 PTC Read Only 0: Open Transition Indicates the transition type PC 3.x
Operating 1: Hard Closed Transition currently in effect
Transition
Type 2: Soft Closed Transition

43590 PTC State Read Only 0: PTC Not Enabled Indicates the connected state PC 3.x
1: No Source Connected of the Power Transfer Control
2: Utility Connected
3: Genset Connected
4: Paralleled
43591 Retransfer Read Only Multiplier: 0.1 Countdown value of the PC 3.x
Timer Offset: 0 retransfer timer
Size (bits): 16
Sign: U
Units: Seconds
Lower Limit: NA
Upper Limit: NA
Default: NA
43592 Retransfer Read Only 0: Not Timing Indicates status of the PC 3.x
Timer Status 1: Timing retransfer timer
2: Expired
43593 Speed Droop Read Only 0: Inactive Command value of speed PC 2.x,
Enable 1: Active droop enable PC 3.x
Command
43594 Speed Droop Read Only 0: Droop Disabled Indicates whether or not PC 2.x,
Status 1: Droop Enabled speed droop is in effect PC 3.x
43595 Transfer Read Only Multiplier : 0.1 Countdown value of the PC3.x
Timer Offset: 0 transfer timer
Size (bits): 16
Sign: U
Units: Seconds
Lower Limit: NA
Upper Limit: NA
Default: NA
43596 Transfer Read Only 0: Not Timing Indicates status of the PC 3.x
Timer Status 1: Timing transfer timer
2: Expired
43597 Utility CB Read Only 0: Inactive Utility cb close command PC 3.x
Close 1: Active status
Command
43598 Utility CB Read Only 0: Inactive Utility cb open command PC 3.x
Open 1: Active status
Command
43599 Utility CB Read Only 0: Open Indicates utility breaker PC 3.x
Position 1: Closed position
Status
2: Not Available
43600 Load Govern Read/Write 0: Genset kW Use to select how generator PC 3.x
kW Method 1: Genset kW w/Utility set kW output will be
Constraint controlled when paralleled to
utility.
2: Utility kW

214 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43608 Configurable Read/Write Multiplier: 1 The event code for this PC 2.x,
Output #1 Offset: 0 output. PC 3.x
Event Code
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43610 Configurable Read/Write Multiplier: 1 The event code for this PC 2.x,
Output #2 Offset: 0 output. PC 3.x
Event Code
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43613 Configurable Read/Write Multiplier: 1 The event code for this PC 3.x
Output #20 Offset: 0 output.
Event Code
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43616 Configurable Read/Write Multiplier: 1 The event code for this PC 3.x
Output #21 Offset: 0 output.
Event Code
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43619 Configurable Read/Write Multiplier: 1 The event code for this PC 3.x
Output #22 Offset: 0 output.
Event Code
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43622 Configurable Read/Write Multiplier: 1 The event code for this PC 2.x,
Output #3 Offset: 0 output. PC 3.x
Event Code
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43625 Configurable Read/Write Multiplier: 1 The event code for this PC 2.x,
Output #4 Offset: 0 output. PC 3.x
Event Code
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

A029X159 (Issue 14) 215


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43641 Delayed Read/Write 0: Disabled Enables the Delayed PC 2.x,
Shutdown 1: Enabled Shutdown feature. PC 3.x
Enable
43642 Delayed Read/Write Multiplier: 0.1 Sets the shutdown fault PC 2.x,
Shutdown Offset: 0 delayed time delay for the PC 3.x
Time Delay Delayed Shutdown feature.
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 3
43643 Remote Fault Read/Write 0: Disable Trim to enable Remote Fault PC 2.x,
Reset 1: Enable Reset. Can only reset PC 3.x
Enabled Warning Faults
43644 Fail To Read/Write Multiplier: 1 Trim to set the time for a PC 2.x, PC
Shutdown Offset: 0 shutdown fault to be active 3.x
Delay and the generator set not
Size (bits): 16 shutting down before the Fail
Sign: U to Shutdown fault occurs.
Unit: seconds
Lower Limit: 0
Upper Limit: 30
43645 LCL Read/Write 0: None Sets low coolant level fault PC 2.x,
Detection 1: Warning response to None, Warning, PC 3.x
Response or Shutdown.
2: Shutdown
43646 LCT Warning Read/Write Multiplier: 1 Sets time to clear the low PC 2.x,
Clear Time Offset: 0 coolant temperature fault. PC 3.x
Size (bits): 8
Sign: U
Unit: Minutes
Lower Limit: 0
Upper Limit: 30
43647 LCT Warning Read/Write Multiplier: 1 Sets time to set the low PC 2.x,
Set Time Offset: 0 coolant temperature fault. PC 3.x
Size (bits): 8
Sign: U
Unit: Minutes
Lower Limit: 0
Upper Limit: 30
43648 LCT Warning Read/Write Multiplier: 1 Sets threshold for the low PC 2.x,
Threshold Offset: 0 coolant temperature fault PC 3.x
warning.
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -20
Upper Limit: 100

216 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43649 V/Hz Knee Read/Write Multiplier: 0.1 The voltage will roll off PC 2.x,
Frequency Offset: 0 (decrease) proportionally to PC 3.x
the V/Hz setup, once the
Size (bits): 16 frequency drops below the
Sign: U set point in the V/Hz Knee
Unit: Hz Frequency. This allows the
Lower Limit: 0 generator set to recover
faster when the frequency
Upper Limit: 10 drops.
43650 V/Hz Rolloff Read/Write Multiplier: 0.1 The amount of voltage roll off PC 2.x,
Slope Offset: 0 when the frequency is below PC 3.x
the knee frequency
Size (bits): 16
Sign: U
Unit: % / Hz
Lower Limit: 0
Upper Limit: 10
43651 12 V High Read Only Multiplier: 0.1 Sets 12V high battery voltage PC 2.x,
Battery Offset: 0 fault threshold. PC 3.x
Voltage
Threshold Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: 14
Upper Limit: 17
43652 12 V Low Read Only Multiplier: 0.1 Sets 12V low battery voltage PC 2.x,
Battery Offset: 0 fault threshold for generator PC 3.x
Voltage set operation while in rated
Running Size (bits): 16 mode
Threshold Sign: U
Unit: Vdc
Lower Limit: 12
Upper Limit: 16
43653 12 V Low Read Only Multiplier: 0.1 Sets 12V low battery voltage PC 2.x,
Battery Offset: 0 fault threshold for generator PC 3.x
Voltage set operation in all modes
Stopped Size (bits): 16 except rated
Threshold Sign: U
Unit: Vdc
Lower Limit: 11
Upper Limit: 13
43654 12 V Weak Read/Write Multiplier: 0.1 Sets 12V weak battery PC 2.x,
Battery Offset: 0 voltage fault threshold PC 3.x
Voltage
Threshold Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: 6
Upper Limit: 10
43655 24 V High Read Only Multiplier: 0.1 Sets 24V high battery voltage PC 2.x,
Battery Offset: 0 fault threshold PC 3.x
Voltage
Threshold Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: 28
Upper Limit: 34

A029X159 (Issue 14) 217


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43656 24 V Low Read Only Multiplier: 0.1 Sets 24V low battery voltage PC 2.x,
Battery Offset: 0 fault threshold for generator PC 3.x
Voltage set operation while in rated
Running Size (bits): 16 mode
Threshold Sign: U
Unit: Vdc
Lower Limit: 24
Upper Limit: 28
43657 24 V Low Read Only Multiplier: 0.1 Sets 24V low battery voltage PC 2.x,
Battery Offset: 0 fault threshold for generator PC 3.x
Voltage set operation in all modes
Stopped Size (bits): 16 except rated
Threshold Sign: U
Unit: Vdc
Lower Limit: 24
Upper Limit: 26
43658 24 V Weak Read/Write Multiplier: 0.1 Sets 24V weak battery PC 2.x,
Battery Offset: 0 voltage fault threshold PC 3.x
Voltage
Threshold Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: 12
Upper Limit: 16
43659 Adjustable Read/Write Multiplier: 0.01 Sets the RPM/Hz conversion PC 2.x,
Freq/Speed Offset: 0 factor when the Freq to PC 3.x
Gain Speed Gain Select trim is set
Size (bits): 16 to this trim
Sign: U
Unit: RPM/Hz
Lower Limit: 12
Upper Limit: 240
43660 Alternate Read Only 0: 50 Hz Sets the generator set PC 2.x,
Frequency 1: 60 Hz nominal frequency. PC 3.x
Switch
43661 AVR Gain Read/Write Multiplier: 0.01 A trim that allows the user to PC 2.x,
Adjust Trim Offset: 0 modify the overall gains of the PC 3.x
AVR.
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0.05
Upper Limit: 10
43662 Charging Read/Write Multiplier: 0.1 Sets the time delay for the PC 2.x,
Alternator Offset: 0 charging alt failure fault PC 3.x
Fault Time
Delay Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 2
Upper Limit: 300

218 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43663 Continuous Read/Write Multiplier: 1 Sets the maximum amount of PC 2.x,
Crank Offset: 0 time to engage the starter PC 3.x
Engage Time when using the continuous
Size (bits): 16 cranking method
Sign: U
Unit: seconds
Lower Limit: 40
Upper Limit: 100
43664 Controlled Read/Write Multiplier: 1 Delay allowed for a shutdown PC 3.x
Shutdown Offset: 0 with cooldown fault prior to
Advance shutting down the generator
Notice Delay Size (bits): 16 set
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 300
43665 Crank Read/Write Multiplier: 1 Sets the maximum number of PC 2.x,
Attempts Offset: 0 times to engage the starter PC 3.x
when attempting to start
Size (bits): 16 engine using the cycle
Sign: U cranking method
Unit: seconds
Lower Limit: 1
Upper Limit: 7
43666 Cycle / Cont Read Only 0: Cycle Selects whether to use PC 2.x,
Crank Select 1: Continuous continuous cranking or cycle PC 3.x
cranking when attempting to
start engine
43667 Cycle Crank Read/Write Multiplier: 1 Sets the maximum amount of PC 2.x,
Engage Time Offset: 0 time to engage the starter PC 3.x
during a single crank attempt
Size (bits): 16 when using the cycle
Sign: U cranking method
Unit: seconds
Lower Limit: 2
Upper Limit: 20
43668 Cycle Crank Read/Write Multiplier: 1 Sets the amount of time to PC 2.x,
Rest Time Offset: 0 wait between crank attempts PC 3.x
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 7
Upper Limit: 40
43669 Delayed Off Read/Write Multiplier: 0.1 Time delay between when the PC 2.x,
FSO Relay Offset: 0 Delayed Off Command turns PC 3.x
Time off and Run Command turns
Size (bits): 16 off
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 120

A029X159 (Issue 14) 219


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43670 External AVR Read / Write Multiplier : 0.1 Sets the knee frequency for PC 2.x,
Knee Offset: 0 the fixed knee freq logic. PC 3.x
Frequency
Size (bits): 16
Sign: U
Units: Hz
Lower Limit: 0
Upper Limit: 10
Default: NA
43671 External Bias Read/Write 0: Disabled Enables the external bias PC 3.x
Commands 1: Enabled (speed and voltage
Enable commands) to the hardware
outputs.
43672 Frequency Read/Write Multiplier: 0.01 A method of adding in a PC 2.x,
Adjust Offset: 0 frequency offset to the base PC 3.x
frequency subject to high and
Size (bits): 16 low limit calibrations
Sign: S
Units: Hz
Lower Limit: -6
Upper Limit: 6
43673 Genset Read/Write Multiplier: 0.1 Sets the total exercise time PC 2.x,
Exercise Offset: 0 not including warmup at idle PC 3.x
Time or idle cooldown time
Size (bits): 16
Sign: U
Unit: hours
Lower Limit: 0
Upper Limit: 25
43674 Governor Read Only Multiplier: 0.01 A trim that allows the user to PC 2.x,
Gain Adjust Offset: 0 modify the overall gain of the PC 3.x
governor
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0.05
Upper Limit: 15
43675 High Battery Read Only Multiplier: 1 The time delay until a high PC 2.x,
Voltage Set Offset: 0 battery voltage condition is PC 3.x
Time reported as a fault.
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 2
Upper Limit: 60
43676 High Battery Read Only Multiplier: 0.1 The high battery voltage PC 2.x,
Voltage Offset: 0 threshold PC 3.x
Threshold
Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit:
Upper Limit:

220 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43677 Idle Read/Write Multiplier: 0.25 Sets time to run at idle before PC 2.x,
Cooldown Offset: 0 shutting down generator set PC 3.x
Time on normal stops
Size (bits): 16
Sign: U
Unit: minutes
Lower Limit: 0
Upper Limit: 60
43678 Idle Speed Read Only Multiplier: 1 Sets the speed at which the PC 2.x,
Offset: 0 engine will idle subject to high PC 3.x
and low limit calibrations
Size (bits): 16
Sign: U
Unit: RPM
Lower Limit: 700
Upper Limit: 1100
43679 Idle to Rated Read/Write Multiplier: 0.1 The time over which the PC 2.x,
Ramp Time Offset: 0 speed reference is to ramp PC 3.x
from idle speed to rated
Size (bits): 16 speed
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 30
43680 Idle Warmup Read/Write Multiplier: 1 Coolant temperature PC 2.x,
Coolant Offset: 0 threshold to end idle warmup PC 3.x
Temp time
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -40
Upper Limit: 300
43681 Idle Warmup Read/Write Multiplier: 1 Sets maximum idle warmup PC 2.x,
Time Offset: 0 time. Warmup time may be PC 3.x
less if coolant temperature
Size (bits): 16 exceeds threshold
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 3600
43682 Load Dump Read/Write 0: Overload Enables the load dump output PC 2.x,
Activation 1: Underfrequency as a function of the overload PC 3.x
Method and underfrequency
2: Overload or conditions
Underfrequency
3: Disabled
43683 Load Dump Read/Write Multiplier: 1 The time delay until the load PC 2.x,
Overload Set Offset: 0 dump overload condition is PC 3.x
Time set active
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 120

A029X159 (Issue 14) 221


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43684 Load Dump Read/Write Multiplier: 1 The load dump overload PC 2.x,
Overload Offset: 0 threshold as a percentage of PC 3.x
Threshold the generator set application
Size (bits): 16 rating
Sign: U
Unit: %
Lower Limit: 80
Upper Limit: 140
43685 Load Dump Read/Write Multiplier: 1 The frequency amount which PC 2.x,
Underfrequen Offset: 0 the load dump PC 3.x
cy Offset underfrequency threshold is
Size (bits): 16 below the final frequency
Sign: S reference
Unit: Hz
Lower Limit: 0
Upper Limit: 10
43686 Load Dump Read/Write Multiplier: 1 The time delay until the load PC 2.x,
Underfrequen Offset: 0 dump underfrequency PC 3.x
cy Set Time condition is set active
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 20
43687 Load Dump Read Only Multiplier: 0.1 The frequency trip threshold PC 2.x,
Underfrequen Offset: 0 for the load dump PC 3.x
cy Threshold underfrequency condition
Size (bits): 16
Sign: U
Unit: Hz
Lower Limit: 0
Upper Limit: 90
43688 Low Battery Read Only Multiplier: 1 The time delay until a low PC 2.x,
Voltage Set Offset: 0 battery voltage condition is PC 3.x
Time reported as a fault
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 2
Upper Limit: 60
43689 Low Fuel in Read/Write Multiplier: 1 Low Fuel in Day Tank Fault PC 2.x,
Day Tank Offset: 0 time delay from switch input PC 3.x
Time
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 20
43690 Low Fuel Read/Write Multiplier: 1 A trim that sets the delay time PC 2.x,
Set/Clear Offset: 0 for generating the inactive PC 3.x
Time and active faults
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 2
Upper Limit: 60

222 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43691 Manual Read/Write 0: Normal Use to command idle speed PC 2.x,
Warmup 1: Bypass Warmup or to bypass idle warmup PC 3.x
Bypass during a manual run
43692 Max Idle Read/Write Multiplier: 0.1 Sets the fault time for the Too PC 2.x,
Time Offset: 0 Long in Idle fault PC 3.x
Size (bits): 16
Sign: U
Unit: minutes
Lower Limit: 0
Upper Limit: 20
43693 Nominal Read Only 0: 12V Selects the generator set’s PC 2.x,
Battery 1: 24V nominal battery operating PC 3.x
Voltage voltage
43694 Prelube Cycle Read/Write 0: Disabled Enables Or Disables the PC 2.x,
Enable 1: Enabled cyclic mode of prelube PC 3.x
operation
43695 Prelube Cycle Read/Write Multiplier: 0.1 Sets the period of the Prelube PC 2.x,
Time Offset: 0 Cycle Iteration PC 3.x
Size (bits): 16
Sign: U
Unit: hours
Lower Limit: 1
Upper Limit: 1000
43696 Prelube Read/Write 0: Disabled Selects whether the Prelube PC 2.x,
Function 1: Enabled function is enabled or PC 3.x
Enable disabled. This is Setup mode
interlocked
43697 Prelube Oil Read/Write Multiplier: 0.1 The oil pressure value which PC 2.x,
Pressure Offset: 0 when reached the prelube PC 3.x
Threshold driver will turn off
Size (bits): 16
Sign: U
Unit: psig
Lower Limit: 0
Upper Limit: 10
43698 Prelube Read/Write Multiplier: 0.1 Sets the maximum time for PC 2.x,
Timeout Offset: 0 which the Prelube Driver will PC 3.x
Period Remain ON
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 30
43699 Rated to Idle Read/Write Multiplier: 0.1 The time over which the PC 2.x,
Ramp Time Offset: 0 speed reference is to ramp PC 3.x
from rated speed to idle
Size (bits): 16 speed
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 30
43700 Utility Read Only 0: Not Available Indicates status of the utility PC 3.x
Availability 1: Available source
Status
2: Unknown

A029X159 (Issue 14) 223


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43701 Utility CB Read Only 0: Inactive Utility cb inhibit command PC 3.x
Inhibit 1: Active
Command
43702 Utility CB Read Only 0: Inactive Utility cb tripped command PC 3.x
Tripped 1: Active
Command
43703 Utility Current Read Only 0: Unknown Indicates utility breaker PC 3.x
Based 1: Closed position based on current
Breaker
Position
43704 Utility Read Only Multiplier: 0.1 Indicates the lower drop-out PC 3.x
Frequency Offset: 0 threshold in Hz for utility
Lower Drop- frequency sensor
Out Size (bits): 16
Threshold Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
43705 Utility Read Only Multiplier: 0.1 Indicates the lower pick-up PC 3.x
Frequency Offset: 0 threshold in Hz for utility
Lower Pick- frequency sensor
Up Threshold Size (bits): 16
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
43706 Utility Read Only 0: Unknown Indicates utility frequency PC 3.x
Frequency 1: Picked Up sensor status
Sensor
Status 2: Dropped Out

43707 Utility Read Only Multiplier: 0.1 Indicates the upper drop-out PC 3.x
Frequency Offset: 0 threshold in Hz for utility
Upper Drop- frequency sensor
Out Size (bits): 16
Threshold Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
43708 Utility Read Only Multiplier: 0.1 Indicates the upper pick-up PC 3.x
Frequency Offset: 0 threshold in Hz for utility
Upper Pick- frequency sensor
Up Threshold Size (bits): 16
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
43709 Utility Loss of Read Only 0: Unknown Indicates utility loss of phase PC 3.x
Phase 1: Picked Up sensor status
Sensor
Status 2: Dropped Out

224 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43710 Utility Read Only Multiplier: 1 Indicates the drop-out PC 3.x
Overvoltage Offset: 0 threshold in volts for utility
Drop-Out over voltage sensor
Threshold Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
43711 Utility Read Only Multiplier: 1 Indicates the pick-up PC 3.x
Overvoltage Offset: 0 threshold in volts for utility
Pick-Up over voltage sensor
Threshold Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
43712 Utility Read Only 0: Unknown Indicates utility over voltage PC 3.x
Overvoltage 1: Picked Up sensor status
Sensor
Status 2: Dropped Out

43713 Utility Phase Read Only 0: Unknown Indicates utility phase rotation PC 3.x
Rotation 1: Picked Up sensor status
Sensor
Status 2: Dropped Out

43714 Utility Read Only Multiplier: 1 Indicates the drop-out PC 3.x


Undervoltage Offset: 0 threshold in volts for utility
Drop-Out under voltage sensor
Threshold Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
43715 Utility Read Only Multiplier: 1 Indicates the pick-up PC 3.x
Undervoltage Offset: 0 threshold in volts for utility
Pick-Up under voltage sensor
Threshold Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
43716 Utility Read Only 0: Unknown Indicates utility under voltage PC 3.x
Undervoltage 1: Picked Up sensor status
Sensor
Status 2: Dropped Out

43717 Voltage Read Only 0: Inactive Command value of voltage PC 2.x,


Droop Enable 1: Active droop enable PC 3.x
Command

43719 Alternator Read Only Multiplier: 1 Monitor point for the PC 2.x,
Temperature Offset: 0 Alternator Temperature 1 PC 3.x
1 (Aux101) input from the Aux 101 I/O
Size (bits): 16 module.
Sign: S
Unit: degF
Lower Limit: -32767
Upper Limit: 32762

A029X159 (Issue 14) 225


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43720 Alternator Read Only Multiplier: 1 Monitor point for the PC 2.x,
Temperature Offset: 0 Alternator Temperature 2 PC 3.x
2 (Aux101) input from the Aux 101 I/O
Size (bits): 16 module.
Sign: S
Unit: degF
Lower Limit: -32767
Upper Limit: 32762
43721 Alternator Read Only Multiplier: 1 Monitor point for the PC 2.x,
Temperature Offset: 0 Alternator Temperature 3 PC 3.x
3 (Aux101) input from the Aux 101 I/O
Size (bits): 16 module.
Sign: S
Unit: degF
Lower Limit: -32767
Upper Limit: 32762
43722 Ambient Read Only Multiplier: 1 Monitor point for the Ambient PC 2.x,
Temperature Offset: 0 Temperature input from the PC 3.x
(Aux101) Aux 101 I/O module.
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -32767
Upper Limit: 32762
43723 Aux101 0 Read Only Multiplier: 0.01 Monitor point for the module 0 PC 2.x,
Analog Input Offset: 0 analog input 1 in volts PC 3.x
1 Voltage
Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit: -500
Upper Limit: 500
43724 Aux101 0 Read Only Multiplier: 0.01 Monitor point for the module 0 PC 2.x,
Analog Input Offset: 0 analog input 2 in volts PC 3.x
2 Voltage
Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit: -500
Upper Limit: 500
43725 Aux101 0 Read Only Multiplier: 0.01 Monitor point for the module 0 PC 2.x,
Analog Input Offset: 0 analog input 3 in volts PC 3.x
3 Voltage
Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:
43726 Aux101 0 Read Only Multiplier: 0.01 Monitor point for the module 0 PC 2.x,
Analog Input Offset: 0 analog input 4 in volts PC 3.x
4 Voltage
Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:

226 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43727 Aux101 0 Read Only Multiplier: 0.01 Monitor point for the module 0 PC 2.x,
Analog Input Offset: 0 analog input 5 in volts PC 3.x
5 Voltage
Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:
43728 Aux101 0 Read Only Multiplier: 0.01 Monitor point for the module 0 PC 2.x,
Analog Input Offset: 0 analog input 6 in volts PC 3.x
6 Voltage
Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:
43729 Aux101 0 Read Only Multiplier: 0.01 Monitor point for the module 0 PC 2.x,
Analog Input Offset: 0 analog input 7 in volts PC 3.x
7 Voltage
Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:
43730 Aux101 0 Read Only Multiplier: 0.01 Monitor point for the module 0 PC 2.x,
Analog Input Offset: 0 analog input 8 in volts PC 3.x
8 Voltage
Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:
43731 Aux101 1 Read Only Multiplier: 0.01 Monitor point for the module 1 PC 2.x,
Analog Input Offset: 0 analog input 1 in volts PC 3.x
1 Voltage
Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit: -500
Upper Limit: 500
43732 Aux101 1 Read Only Multiplier: 0.01 Monitor point for the module 1 PC 2.x,
Analog Input Offset: 0 analog input 2 in volts PC 3.x
2 Voltage
Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit: -500
Upper Limit: 500
43733 Aux101 1 Read Only Multiplier: 0.01 Monitor point for the module 1 PC 2.x,
Analog Input Offset: 0 analog input 3 in volts PC 3.x
3 Voltage
Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 227


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43734 Aux101 1 Read Only Multiplier: 0.01 Monitor point for the module 1 PC 2.x,
Analog Input Offset: 0 analog input 4 in volts PC 3.x
4 Voltage
Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:
43735 Aux101 1 Read Only Multiplier: 0.01 Monitor point for the module 1 PC 2.x,
Analog Input Offset: 0 analog input 5 in volts PC 3.x
5 Voltage
Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:
43736 Aux101 1 Read Only Multiplier: 0.01 Monitor point for the module 1 PC 2.x,
Analog Input Offset: 0 analog input 6 in volts PC 3.x
6 Voltage
Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:
43737 Aux101 1 Read Only Multiplier: 0.01 Monitor point for the module 1 PC 2.x,
Analog Input Offset: 0 analog input 7 in volts PC 3.x
7 Voltage
Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:
43738 Aux101 1 Read Only Multiplier: 0.01 Monitor point for the module 1 PC 2.x,
Analog Input Offset: 0 analog input 8 in volts PC 3.x
8 Voltage
Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:
43739 Battery Read Only 0: Inactive Monitor point for the battery PC 2.x,
Charger AC 1: Active charger failure input from the PC 3.x
Failure PCCNet annunciator.
(HMI113)
43740 Drive End Read Only Multiplier: 1 Monitor point for the Drive PC 2.x,
Bearing Offset: 0 End Bearing Temperature PC 3.x
Temperature input from the I/O module.
(Aux101) Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -32767
Upper Limit: 32762

228 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43741 Exhaust Read Only Multiplier: 1 Monitor point for the Exhaust PC 2.x,
Stack Offset: 0 Stack Temperature1 input PC 3.x
Temperature from the I/O module.
1 (Aux101) Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -32767
Upper Limit: 32762
43742 Exhaust Read Only Multiplier: 1 Monitor point for the Exhaust PC 2.x,
Stack Offset: 0 Stack Temperature2 input PC 3.x
Temperature from the I/O module.
2 (Aux101) Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -32767
Upper Limit: 32762
43745 Fuel Level % Read Only Multiplier: 0.1 Monitor point for the % fuel PC 2.x,
(PCCNet) Offset: 0 level input from the I/O PC 3.x
module.
Size (bits): 16
Sign: S
Unit: %
Lower Limit:
Upper Limit:
43746 Fuel Level Read Only Multiplier: 1 Monitor point for the fuel level PC 2.x,
(PCCNet) Offset: 0 (in gallons) input from the I/O PC 3.x
module.
Size (bits): 16
Sign: S
Unit:
Lower Limit:
Upper Limit:
43747 HMI113 Fault Read Only 0: Inactive Monitor point for input #1 PC 2.x,
1 Status 1: Active from the annunciator. PC 3.x
43748 HMI113 Fault Read Only 0: Inactive Monitor point for input #2 PC 2.x,
2 Status 1: Active from the annunciator. PC 3.x
43749 HMI113 Fault Read Only 0: Inactive Monitor point for the input #3 PC 2.x,
3 Status 1: Active from the annunciator. PC 3.x
43750 Intake Read Only Multiplier: 1 Monitor point for the Intake PC 2.x,
Manifold Offset: 0 Manifold Temperature 1 input PC 3.x
Temperature from the I/O module.
1 (Aux101) Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -32768
Upper Limit: 32762
43751 Low Coolant Read Only 0: Inactive Monitor point for the Low PC 2.x,
Level 1: Active Coolant Level input from the PC 3.x
(HMI113) PCCNet annunciator.
43752 Low Fuel Read Only 0: Inactive Monitor point for the Low Fuel PC 2.x,
Level 1: Active Level input from the PCCNet PC 3.x
(HMI113) annunciator.

A029X159 (Issue 14) 229


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43755 Non-Drive Read Only Multiplier: 1 Monitor point for the Non- PC 2.x,
End Bearing Offset: 0 Drive End Bearing PC 3.x
Temperature Temperature input from the
(Aux101) Size (bits): 16 I/O module.
Sign: S
Unit: degF
Lower Limit: -32768
Upper Limit: 32762
43756 Number of Read Only Multiplier: 1 Used to monitor the amount PC 2.x,
Connected Offset: 0 of connected bargraph PC 3.x
Bargraph modules.
Modules Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255
43757 Oil Read Only Multiplier: 1 Monitor point for the Oil PC 2.x,
Temperature Offset: 0 Temperature input from the PC 3.x
(Aux101) I/O Module.
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -65534
Upper Limit: 65535
43758 Modbus Bus Read Only Multiplier: 1 Modbus bus message count PC 2.x,
Message Offset: 0 PC 3.x
Count
Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit
43759 Modbus CRC Read Only Multiplier: 1 Modbus CRC errors count PC 2.x,
Errors Count Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit
43760 Modbus Read Only Multiplier: 1 Modbus exception count PC 2.x,
Exception Offset: 0 PC 3.x
Count
Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit
43761 Modbus No Read Only Multiplier: 1 Modbus no response count PC 2.x,
Response Offset: 0 PC 3.x
Count
Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit

230 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43762 Modbus Read Only Multiplier: 1 Modbus slave message count PC 2.x,
Slave Offset: 0 PC 3.x
Message
Count Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit
43763 Frequency Read Only Multiplier: 0.001 frequency match error value PC 3.x
Match Error Offset: 0 used by frequency match PI
loop
Size (bits): 16
Sign: S
Unit: Hz
Lower Limit:
Upper Limit
43764 Frequency Read Only Multiplier : 0.001 Offset to the frequency match PC 3.x
Match Offset Offset: 0 error calculation
Size (bits): 16
Sign: S
Unit: Hz
Lower Limit:
Upper Limit
Default: NA
43765 Load Dump Read Only 0: Inactive Indicates a load dump is PC 2.x,
Request 1: Active desired due to load PC 3.x
exceeding derate level.
43766 Load Govern Read Only 0: Not Applicable Indicates status of load PC 3.x
kVAR Ramp 1: Ramp Load govern kVAR ramping control
State
2: Track Target
3: Ramp Unload
4: Ramp Unload Complete
43767 Load Govern Read Only Multiplier: 0.01 Indicates the final target PC 3.x
kVAR Target Offset: 0 setpoint for generator set
kVAR output when paralleled
Size (bits): 16 to utility
Sign: S
Unit: %
Lower Limit:
Upper Limit
Default: NA
43768 Load Govern Read Only 0: Not Applicable Indicates status of load PC 3.x
kW Ramp 1: Ramp Load govern kW ramping control
State
2: Track Target
3: Ramp Unload
4: Ramp Unload Complete

A029X159 (Issue 14) 231


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43769 Load Govern Read Only Multiplier: 0.01 Indicates the final target PC 3.x
kW Target Offset: 0 setpoint for generator set kW
output when paralleled to
Size (bits): 16 utility
Sign: S
Unit: %
Lower Limit:
Upper Limit
Default: NA
43770 Permissive Read Only 0: Not Allowed Indicates when permissive PC 3.x
Close 1: Allowed sync check conditions have
Allowed been met

43772 Permissive Read Only Multiplier : 0.01 Phase error signal for the PC 3.x
Phase Match Offset: 0 permissive sync check
Error algorithm
Size (bits): 16
Sign: S
Units: deg
Lower Limit: NA
Upper Limit: NA
Default: NA
43773 Phase Match Read Only Multiplier: 0.01 Phase error signal for the PC 3.x
Error Offset: 0 synchronizer control algorithm
Size (bits): 16
Sign: S
Units: deg
Lower Limit:
Upper Limit:
43774 Ramp Read Only 0: Load Indicates overall status of PC 3.x
Load/Unload 1: Unload ramp load unload inputs
Command
43775 Utility Read Only 0: Not Available Indicates unloaded status of PC 3.x
Unloaded 1: Not Unloaded the utility source
Status
2: Unloaded
43776 Genset CB Read Only 0: Inactive Indicates if the output’s status PC 3.x
Close Status 1: Active is Inactive or Active

43777 Start Read Only 0: Inactive This is the status of the PC 2.x,
Type/Configu 1: Active Configurable Input #11. PC 3.x
rable Input
#11 Switch
43778 Scheduler Read Only 0: Off Indicates the current run PC 2.x,
Run 1: No Load command coming from the PC 3.x
Command scheduler.
2: With Load
3: Extended Parallel
43785 Start Read Only Multiplier: 1 Number of start attempts PC 2.x,
Attempts Offset: 0 since the last reset. PC 3.x
Since Reset
Size (bits): 32
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967290

232 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43786 Start Read Only Multiplier: 1 Number of start attempts PC 2.x,
Attempts Offset: 0 since the last reset. PC 3.x
Since Reset
Size (bits): 32
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967290
43787 Total Start Read Only Multiplier: 1 Total number of start PC 2.x,
Attempts Offset: 0 attempts. PC 3.x
Size (bits): 32
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967290
43788 Total Start Read Only Multiplier: 1 Total number of start PC 2.x,
Attempts Offset: 0 attempts. PC 3.x
Size (bits): 32
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967290
43789 Backup Start Read Only 0: Inactive This is the status of the PC 3.x
Disconnect/C 1: Active Configurable Input #33.
onfigurable
Input #33
Switch
43790 Backup Start Read Only 0: Inactive Status of the Backup Start PC 3.x
Disconnect 1: Active Disconnect Switch Input
Switch
43791 Battery Read Only 0: Inactive Battery Charger Failed Switch PC 2.x,
Charger 1: Active function output status; gives PC 3.x
Failed Switch software Inactive/Active state
43792 Battle Short Read Only 0: Inactive Battle Short Switch function PC 2.x,
Switch 1: Active output status (Active or PC 3.x
Inactive)
43793 Configurable Read Only 0: Inactive Configurable Input #1 input PC 2.x,
Input #1 1: Active software state status. Gives PC 3.x
Switch software Inactive/Active state
43794 Configurable Read Only 0: Inactive Configurable Input #2 input PC 2.x,
Input #2 1: Active software state status. Gives PC 3.x
Switch software Inactive/Active state
43795 Configurable Read Only 0: Inactive Configurable Input #13 input PC 2.x,
Input #13 1: Active software state status. Gives PC 3.x
Switch software Inactive/Active state
43796 Genset CB Read Only 0: Inactive Generator set cb open PC 3.x
Open 1: Active command status
Command

A029X159 (Issue 14) 233


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43797 Number of Read Only Multiplier : 1 Used to monitor the amount PC 2.x,
Connected Offset: 0 of connected Battery PC 3.x
Battery Chargers
Chargers Size (bits): 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43800 Rated Read/Write Multiplier: 1 Minimum time to spend at PC 2.x,
Cooldown Offset: 0 rated speed less than 10% PC 3.x
Time load before normal shutdown
Size (bits): 16 is allowed
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 600
43801 Rated to Idle Read/Write Multiplier: 0.1 Sets the delay time for PC 2.x,
Transition Offset: 0 transitioning from Rated to PC 3.x
Delay Idle speed. 0 seconds =
Size (bits): 16 feature is disabled.
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 10
43802 Rupture Read/Write Multiplier: 0.1 Rupture Basin fault time PC 2.x,
Basin Time Offset: 0 delay PC 3.x
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 20
43803 Start Time Read/Write Multiplier: 1 Sets the time to wait from PC 2.x,
Delay Offset: 0 receiving a valid remote start PC 3.x
signal until starting the
Size (bits): 16 generator set
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 300
43804 Starting to Read/Write Multiplier: 0.1 The time over which the PC 2.x,
Rated Ramp Offset: 0 speed reference is to ramp PC 3.x
Time from starting speed to rated
Size (bits): 16 speed
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 300
43805 Time Delay to Read/Write Multiplier: 1 Sets time to run at rated PC 2.x,
Stop Offset: 0 speed before going to PC 3.x
cooldown at idle. Does not
Size (bits): 16 apply to manual runs
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 600

234 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43806 Voltage Read/Write Multiplier: 0.01 A trim that allows the user to PC 2.x,
Adjust Offset: 0 add/subtract an offset to the PC 3.x
nominal voltage when
Size (bits): 16 calculating the voltage
Sign: S setpoint
Unit: %
Lower Limit: -5
Upper Limit: 5
43807 Voltage Read/Write Multiplier: 0.01 The time period over which PC 2.x,
Ramp Time Offset: 0 the voltage setpoint PC 3.x
command should rise from
Size (bits): 16 0% to the target voltage
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 5
43808 Commit to Read Only 0: Not Committed PTC - Indicates if system is PC 3.x
Transfer 1: Committed committed to transferring to
State generator set
43810 Battle Short Read/Write 0: Inactive Trim to enable Battle Short PC 2.x,
Switch 1: Committed via Modbus. PC 3.x
(Modbus)
43811 Exercise Read/Write 0: Inactive Modbus exercise switch PC 2.x,
Switch 1: Active PC 3.x
(Modbus)
43813 Extended Read/Write 0: Inactive Modbus extended parallel PC 2.x,
Parallel 1: Active switch PC 3.x
Switch
(Modbus)
43814 PTC Mode Read/Write 0: Inactive Modbus PTC Mode switch PC 3.x
Switch 1: Active
(Modbus)
43815 Start Type Read/Write 0: Emergency Modbus start type switch PC 2.x,
(Modbus) 1: Non Emergency PC 3.x
43816 Sync Disable Read / Write 0: Inactive Use to turn off synchronizer PC 3.x
1: Active for testing purposes

43817 Genset Read/Write 0: Inactive Identical operation to the PC 3.x


Circuit 1: Active configurable input of the
Breaker same name. Opens genset
Inhibit breaker if closed; inhibits
closure if genset breaker is
open
43818 Isolated Bus Read/Write 0: Constant Sets the speed control PC 2.x,
Speed 1: Droop method for isolated bus PC 3.x
Control paralleling. Parameter is also
Method known as Load Share Speed
Droop Control Method
43819 Isolated Bus Read/Write 0: Constant Sets the voltage control PC 2.x,
Voltage 1: Droop method for isolated bus PC 3.x
Control paralleling
Method

A029X159 (Issue 14) 235


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43820 Maximum Read/Write Multiplier: 0.1 Sets the maximum time that PC 3.x
Parallel Time Offset: 0 the generator set can remain
(TDMP) paralleled to the utility during
Size (bits): 16 closed transition transfers
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 1800
43821 Programmed Read/Write Multiplier: 0.1 Sets the time delay from PC 3.x
Transition Offset: 0 when one source opens until
Delay (TDPT) the other closes during open
Size (bits): 16 transition transfers
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 60
43822 Retransfer Read/Write Multiplier: 0.1 Sets the amount of time that PC 3.x
Delay (TDEN) Offset: 0 the utility source must be
available before the control
Size (bits): 16 will retransfer to that source.
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 1800
43823 Synchronizer Read/Write 0: Phase Match Sets the speed control PC 3.x
Speed 1: Slip Frequency method for synchronizing.
Control
Method 2: External

43824 Synchronizer Read/Write 0: Voltage Match Sets the voltage control PC 3.x
Voltage 1: External method for synchronizing.
Control
Method
43825 Transfer Read/Write Multiplier: 0.1 Sets the amount of time that PC 3.x
Delay (TDNE) Offset: 0 the generator set source must
be available before the
Size (bits): 16 control will transfer to that
Sign: U source.
Unit: seconds
Lower Limit: 0
Upper Limit: 120
43826 Transition Read/Write 0: Open Transition Sets the load transfer PC 3.x
Type 1: Hard Closed Transition transition type for use when
Generator set Application
2: Soft Closed Transition Type = Power Transfer
Control.
43827 Retransfer Read/Write 0: Inactive Identical operation to the PC 3.x
Inhibit 1: Active configurable input of the
same name. Normally inhibits
retransfer to the utility; under
some conditions it is ignored;
not the same as utility circuit
breaker inhibit.
43828 Utility Circuit Read/Write 0: Inactive Identical operation to the PC 3.x
Breaker 1: Active configurable input of the
Inhibit same name. Opens utility
main if closed; inhibits closure
if utility main is open.

236 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43829 Utility Parallel Read/Write 0: Load Govern Sets the speed control PC 3.x
Speed 1: Droop method for utility paralleling.
Control
Method
43830 Utility Parallel Read/Write 0: Load Govern Sets the voltage control PC 3.x
Voltage 1: Droop method for utility paralleling.
Control
Method 2: Load Govern with Droop
Feed Forward
43831 Aux101 Read/Write 0: Critical Device Response Selects the generator set PC 2.x,
Device 0 1: Non-Critical Device reaction to a loss of a Device PC 3.x
PCCNet Response 0 I/O module as critical
Failure (Shutdown) or non-critical
Response (Warning).
Type
43832 Aux101 Read/Write 0: Critical Device Response Selects the generator set PC 2.x,
Device 1 1: Non-Critical Device reaction to a loss of a Device PC 3.x
PCCNet Response 1 I/O module as critical
Failure (Shutdown) or non-critical
Response (Warning).
Type
43834 HMI113 Read/Write 0: Critical Device Response Selects the generator set PC 2.x,
Annunciator 1: Non-Critical Device reaction to a loss of an PC 3.x
PCCNet Response annunciator as critical or non-
Failure critical. Selecting critical will
Response cause a shutdown when the
Type annunciator loses
communication.
43835 HMI1xx Read / Write 0: Critical Device Response Selects the genset reaction to PC 2.x,
PCCNet 1: Non-Critical Device a loss of an HMI1xx Operator PC 3.x
Failure Response Panel as critical or non-
Response critical. A critical response will
Type shutdown the genset when
PCCNet communication is
lost.
43836 HMI220 Read/Write 0: Critical Device Response Selects the generator set PC 2.x,
PCCNet 1: Non-Critical Device reaction to a loss of an PC 3.x
Failure Response HMI220 operator panel as
Response critical or non-critical. A
Type critical response will
shutdown the generator set
when PCCNet communication
is lost.
43837 HMI320 Read/Write 0: Critical Device Response Selects the generator set PC 2.x,
PCCNet 1: Non-Critical Device reaction to a loss of an PC 3.x
Failure Response HMI320 operator panel as
Response critical or non-critical. A
Type critical response will
shutdown the generator set
when PCCNet communication
is lost.
43838 HMI4xx Read / Write 0: Critical Device Response Selects the genset reaction to PC 2.x
PCCNet 1: Non-Critical Device a loss of an HMI4xx Operator PC 3.x
Failure Response Panel as critical or non-
Response critical. A critical response will
Type shutdown the genset when
PCCNet communication is
lost.

A029X159 (Issue 14) 237


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43839 PCCNet Read/Write Multiplier: 1 Selects the time allowed for PC 2.x,
Device Offset: 0 arbitration to occur before a PC 3.x
Failure Time PCCNet failure fault is
Delay Size (bits): 16 generated.
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 250
43840 Test With Read/Write 0: Disabled Use to choose whether a test PC 3.x
Load Enable 1: Enabled is with load or without load.

43841 Transfer Read/Write 0: Inactive Identical operation to the PC 3.x


Inhibit 1: Active configurable input of the
same name. Normally inhibits
transfer to the genset; under
some conditions it is ignored;
not the same as genset circuit
breaker inhibit.
43842 Commit to Read/Write 0: Utility Disconnect PTC - sets point at which PC 3.x
Transfer 1: Genset Start system commits to transfer to
Method generator set
2: No Commit
43843 Commit to Read/Write Multiplier: 1 PTC - sets time system will PC 3.x
Transfer Offset: 0 wait for generator set when
Timeout committed to transfer
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 3200
43844 Commit to Read Only Multiplier: 0.05 PTC - remaining time system PC 3.x
Transfer Offset: 0 to wait for generator set when
Timer committed to transfer
Size (bits): 16
Sign: U
Unit: sec
Lower Limit:
Upper Limit:
43845 Modbus Read/Write Multiplier: 1 Time delay before the control PC 2.x,
Failure Time Offset: 0 activates the Modbus failure PC 3.x
Delay fault after the Master is
Size (bits): 16 sensed as no longer present.
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 10
43846 Modbus Read/Write 0: Do Nothing When set to Reset PC 2.x,
Communicati 1: Reset Commands Commands will reset the PC 3.x
ons Lost Modbus control logicals to an
Response inactive state when Modbus
Method communications are lost
43847 Modbus Clear Read/Write 0: Do Nothing Resets all Modbus counters, PC 2.x,
Counters 1: Clear Counters including J14 if applicable. PC 3.x

238 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43848 Controlled Read/Write Multiplier: 1 maximum ramp unload time PC 3.x
Shutdown Offset: 0 during a shutdown with
Max Ramp cooldown
Unload Time Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 300
43849 Genset kVAR Read/Write Multiplier: 1 Sets the generator set load PC 3.x
Setpoint Offset: 0 govern kVAR base load
internal operating setpoint in
Size (bits): 16 units of kVAR. Requires that
Sign: S Load Govern kVAR Setpoint
Unit: kVAR Source = Internal and Load
Lower Limit: 0 Govern kVAR Method =
generator set kVAR.
Upper Limit: 20000
43850 Genset kVAR Read/Write Multiplier: 0.01 Sets the generator set load PC 3.x
Setpoint Offset: 0 govern kVAR base load
Percent internal operating setpoint
Size (bits): 16 in % of standby kVA rating.
Sign: S Requires that Load Govern
Unit: % kVAR Setpoint Source =
Lower Limit: 0 Internal and Load Govern
kVAR Method = generator set
Upper Limit: 60 kVAR.
43851 Genset kW Read/Write Multiplier: 1 Sets the generator set load PC 3.x
Setpoint Offset: 0 govern kW base load internal
operating setpoint in units of
Size (bits): 16 kW. Requires that Load
Sign: S Govern kW Setpoint Source =
Unit: kW Internal and Load Govern kW
Lower Limit: 0 Method = Genset kW.
Upper Limit: 20000
43852 Genset kW Read/Write Multiplier: 0.01 Sets the generator set load PC 3.x
Setpoint Offset: 0 govern kW base load internal
Percent operating setpoint in % of
Size (bits): 16 standby rating. Requires that
Sign: S Load Govern kW Setpoint
Unit: % Source = Internal and Load
Lower Limit: 0 Govern kW Method = Genset
kW.
Upper Limit: 100
43853 Genset Read/Write Multiplier: 0.01 Sets the load govern setpoint PC 3.x
Power Factor Offset: 0 for generator set power factor
Setpoint control. Requires that Load
Size (bits): 8 Govern kVAR Setpoint
Sign: S Source = Internal and Load
Unit: PF Govern kVAR Method =
Lower Limit: 0.7 Genset Power Factor.
Upper Limit: 1
43854 Load Read/Write 0: Inactive Modbus input for activating PC 3.x
Demand Stop 1: Active load demand stop on the
(Modbus) generator set
43855 Load Govern Read/Write 0: Genset kVAR Use to select how generator PC 3.x
kVAR Method 1: Genset Power Factor set kVAR output will be
controlled when paralleled to
2: Utility kVAR utility.
3: Utility Power Factor

A029X159 (Issue 14) 239


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43856 Load Govern Read/Write Multiplier: 1 Sets load govern kVAR ramp PC 3.x
kVAR Ramp Offset: 0 load rate = Genset Standby
Load Time kVA * 0.6/ this time.
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 900
43857 Load Govern Read/Write Multiplier: 1 Sets load govern kVAR ramp PC 3.x
kVAR Ramp Offset: 0 unload rate = Genset
Unload Time Standby kVA * 0.6/ this time.
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 900
43858 Utility Breaker Read/Write 0: After Transfer Delay PTC - point in time at which PC 3.x
Opening 1: Upon Utility Failure system opens utility breaker
Point
43859 Load Govern Read/Write Multiplier: 1 Sets load govern kW ramp PC 3.x
kW Ramp Offset: 0 load rate = Genset Standby
Load Time kW rating/ this time.
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 900
43860 Load Govern Read/Write Multiplier: 1 Sets load govern kW ramp PC 3.x
kW Ramp Offset: 0 unload rate = Genset
Unload Time Standby kW rating/ this time.
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 900
43861 Ramp Read/Write 0: Load Use to control ramp load and PC 3.x
Load/Unload 1: Unload unload via Modbus
(Modbus)
43862 Slip Read/Write Multiplier: 0.001 Sets the synchronizer slip PC 3.x
Frequency Offset: 0 frequency. Requires that
Sync Speed Control Method
Size (bits): 16 = Slip Frequency.
Sign: S
Unit: Hz
Lower Limit: -3
Upper Limit: 3
43863 Utility kVAR Read/Write Multiplier: 1 Sets the utility kVAR peak PC 3.x
Setpoint Offset: 0 shave internal operating
setpoint in units of kVAR.
Size (bits): 16 Requires that Load Govern
Sign: S kVAR Setpoint Source =
Unit: kVAR Internal and Load Govern
Lower Limit: -20000 kVAR Method = Utility kVAR
Upper Limit: 20000

240 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43864 Utility kVAR Read/Write Multiplier: 0.01 Sets the utility kVAR peak PC 3.x
Setpoint Offset: 0 shave internal operating
Percent setpoint in % of generator set
Size (bits): 16 standby kVA rating. Requires
Sign: S that Load Govern kVAR
Unit: % Setpoint Source = Internal
Lower Limit: -320 and Load Govern kVAR
Method = Utility kVAR.
Upper Limit: 320
43865 Utility kW Read/Write Multiplier: 1 Sets the utility kW minimum PC 3.x
Constraint Offset: 0 load level for constrained
base load mode of operation.
Size (bits): 16 Requires that Load Govern
Sign: S kW Setpoint Source =
Unit: kW Internal and Load Govern kW
Lower Limit: -20000 Method = Genset kW w/Utility
Constraint.
Upper Limit: 20000
43866 Utility kW Read/Write Multiplier: 0.01 Sets utility kW minimum load PC 3.x
Constraint Offset: 0 level for constrained base
Percent load mode in % of generator
Size (bits): 16 set standby rating. Requires
Sign: S that Load Govern kW
Unit: % Setpoint Source = Internal
Lower Limit: -320 and Load Govern kW Method
= Genset kW w/Utility
Upper Limit: 320 Constraint.
43867 Utility kW Read/Write Multiplier: 1 Sets the utility kW peak PC 3.x
Setpoint Offset: 0 shave internal operating
setpoint in units of kW.
Size (bits): 16 Requires that Load Govern
Sign: S kW Setpoint Source =
Unit: kW Internal and Load Govern kW
Lower Limit: -20000 Method = Utility kW.
Upper Limit: 20000
43868 Utility kW Read/Write Multiplier: 0.01 Sets the utility kW peak PC 3.x
Setpoint Offset: 0 shave internal operating
Percent setpoint in % of generator set
Size (bits): 16 standby rating. Requires that
Sign: S Load Govern kW Setpoint
Unit: % Source = Internal and Load
Lower Limit: -320 Govern kW Method = Utility
kW.
Upper Limit: 320
43869 Utility Power Read/Write Multiplier: 0.01 Sets the internal setpoint for PC 3.x
Factor Offset: 0 utility power factor control
Setpoint mode when paralleled to
Size (bits): 16 utility. Requires that Load
Sign: S Govern kVAR Setpoint
Unit: PF Source = Internal and Load
Lower Limit: 0.7 Govern kVAR Method =
Utility Power Factor.
Upper Limit: 1
43870 Aux101 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 2 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

A029X159 (Issue 14) 241


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43871 Aux101 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 4 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43872 Aux101 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 5 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43873 Aux101 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 6 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43874 Aux101 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 7 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43875 Aux101 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 1 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43876 Aux101 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 2 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43877 Aux101 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 3 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

242 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43878 Aux101 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 4 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43879 Aux101 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 5 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43880 Aux101 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 6 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43881 Aux101 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 7 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43882 Aux101 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 8 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43883 Aux102 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 10 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43884 Aux102 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 11 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

A029X159 (Issue 14) 243


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43885 Aux102 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 12 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43886 Aux102 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 13 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43887 Aux102 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 14 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43888 Aux102 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 15 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43889 Aux102 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 16 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43890 Aux102 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 9 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43891 Aux102 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 10 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

244 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43892 Aux102 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 11 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43893 Aux102 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,


Output 12 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43894 Aux102 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,


Output 13 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43895 Aux102 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,


Output 14 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43896 Aux102 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,


Output 15 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43897 Aux102 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,


Output 16 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

A029X159 (Issue 14) 245


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43898 Aux102 1 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 9 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43900 HMI113 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,


Output 1 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43901 HMI113 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,


Output 2 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43902 HMI113 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,


Output 3 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43903 HMI113 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,


Output 4 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43905 Network Read/Write 0: Normal Used to command a fixed 0.5 PC 2.x,


Speed Adjust 1: Active Hz increase in the speed PC 3.x
Command setpoint
43906 Speed Droop Read/Write 0: Inactive Speed droop enable switch PC 2.x,
Enable 1: Active input status from Modbus PC 3.x
Switch
(Modbus)
43907 Voltage Read/Write 0: Inactive Voltage droop enable switch PC 2.x,
Droop Enable 1: Active input status from Modbus PC 3.x
Switch
(Modbus)

246 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43908 Genset CB Read/Write 0: Inactive Genset cb tripped from PC 3.x
Tripped 1: Active Modbus
Switch
(Modbus)
43909 Utility CB Read/Write 0: Inactive Utility cb tripped switch input PC 3.x
Tripped 1: Active from Modbus
Switch
(Modbus)
43910 Save Trims Read/Write 0: Do Nothing Save configuration PC 2.x,
1: Save Trims parameters or adjustments to PC 3.x
non-volatile memory. Perform
Save Trims after all
configurations have been
updated. Do not save trims
unless a change has
occurred.
43911 Aux101 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,
Output 3 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43912 Aux101 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,


Output 1 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43913 Aux101 0 Read/Write Multiplier: 1 Parameter to allow for the PC 2.x,


Output 8 Offset: 0 entry of the fault/event code PC 3.x
Fault/Event which will turn the output
Size (bits): 16 relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43915 Extended Read/Write 0: Disabled Use to enable the extended PC 3.x


Parallel 1: Enabled paralleling mode of PTC
Enable
43916 V/Hz Knee Read Only Multiplier: 0.1 The voltage will roll off PC 2.x,
Frequency Offset: 0 (decrease) proportionally to PC 3.x
50Hz the V/Hz setup, once the
Size (bits): 16 frequency drops below the
Sign: U set point in the V/Hz Knee
Unit: Hz Frequency. This allows the
Lower Limit: 0 generator set to recover
faster when the frequency
Upper Limit: 10 drops. This is for 50Hz
frequency.

A029X159 (Issue 14) 247


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43917 V/Hz Knee Read Only Multiplier: 0.1 The voltage will roll off PC 2.x,
Frequency Offset: 0 (decrease) proportionally to PC 3.x
60Hz the V/Hz setup, once the
Size (bits): 16 frequency drops below the
Sign: U set point in the V/Hz Knee
Unit: Hz Frequency. This allows the
Lower Limit: 0 generator set to recover
faster when the frequency
Upper Limit: 10 drops. This is for 60Hz
frequency.
43918 V/Hz Rolloff Read Only Multiplier: 0.1 The amount of voltage roll off PC 2.x,
Slope 50Hz Offset: 0 when the frequency is below PC 3.x
the knee frequency
Size (bits): 16
Sign: U
Unit: % / Hz
Lower Limit: 0
Upper Limit: 10

43919 V/Hz Rolloff Read Only Multiplier: 0.1 The amount of voltage roll off PC 2.x,
Slope 60Hz Offset: 0 when the frequency is below PC 3.x
the knee frequency
Size (bits): 16
Sign: U
Unit: % / Hz
Lower Limit: 0
Upper Limit: 10

43920 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit: % / Hz
Lower Limit: 0
Upper Limit: 10

43921 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43922 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

248 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43923 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43924 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43925 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43926 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43927 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43928 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 249


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43929 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43930 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43931 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43932 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43933 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43934 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

250 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43935 Genset Read/Write Multiplier: 1 Name for the generator set PC 2.x,
Source Name Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43952 Speed/Frequ Read/Write Multiplier: 0.1 Sets the delay time for PC 2.x,
ency Delay Offset: 0 generating the PC 3.x
Speed/Frequency mismatch
Size (bits): 136 fault
Sign: U
Unit: seconds
Lower Limit: 0.5
Upper Limit: 10

43953 Speed/Frequ Read/Write Multiplier: 0.1 Sets the threshold for PC 2.x,
ency Offset: 0 generating the PC 3.x
Threshold Speed/Frequency mismatch
Size (bits): 16 fault
Sign: U
Unit: Hz
Lower Limit: 0.5
Upper Limit: 20
43954 Sync Enable Read / Write 0: Inactive Modbus input for enabling the PC 3.x
(Modbus) 1: Active synchronizer

43955 Genset Idle Read Only 0: Disabled Enables or Disable idling of PC 2.x,
Enable 1: Enabled generator set with external PC 3.x
governor.
43956 Permissive Read Only Multiplier : 0.001 Frequency match error value PC 3.x
Frequency Offset: 0 used by permissive sync
Match Error check
Size (bits): 32
Sign: U
Unit: Hz
Lower Limit: NA
Upper Limit: NA
Default: NA
43957 Permissive Read Only Multiplier : 0.001 Frequency match error value PC 3.x
Frequency Offset: 0 used by permissive sync
Match Error check
Size (bits): 32
Sign: U
Unit: Hz
Lower Limit: NA
Upper Limit: NA
Default: NA
43958 Sync Enable Read Only 0: Inactive Indicates overall status of PC 3.x
Command 1: Active sync enable inputs

A029X159 (Issue 14) 251


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43959 Utility Read/Write Multiplier: 1 Sets threshold at which utility PC 3.x
Unloaded Offset: 0 source is considered as
Level unloaded.
Size (bits): 16
Sign: S
Unit: kW
Lower Limit: -32768
Upper Limit: 32762
43960 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43961 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43962 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43963 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43964 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43965 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

252 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43966 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43967 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43968 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43969 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43970 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43971 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43972 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 253


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43973 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43974 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43975 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43976 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

43977 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43978 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43979 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
1 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

254 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43980 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43981 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43982 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43983 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43984 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43985 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43986 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 255


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


43987 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43988 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43989 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43990 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

43991 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43992 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

256 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


43993 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43994 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43995 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43996 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43997 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43998 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43999 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
2 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 257


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


45999 Unrecognized Read Only 0: All Pairs Recognized Indicates whether or not all PC 2.x,
SPN/FMI 1: Pair Not Recognized pairs in current DM1 are PC 3.x
Status recognized
46000 Genset Read Only 0: L1-L2-L3 Generator set phase rotation PC 2.x,
Phase 1: L1-L3-L2 PC 3.x
Rotation
2: Not Available
46001 Utility Phase Read Only 0: L1-L2-L3 Utility phase rotation PC 3.x
Rotation 1: L1-L3-L2
2: Not Available
46002 Genset Bus Read Only 0: L1-L2-L3 Generator set bus phase PC 3.x
Phase 1: L1-L3-L2 rotation
Rotation
2: Not Available
46003 Base Speed Read Only Multiplier: 0.0625 Provides a point to monitor PC 2.x,
Offset: 0 the base speed PC 3.x
Size (bits): 32
Sign: U
Unit: RPM
Lower Limit:
Upper Limit:
46004 Base Speed Read Only Multiplier: 0.0625 Provides a point to monitor PC 2.x,
Offset: 0 the base speed PC 3.x
Size (bits): 32
Sign: U
Unit: RPM
Lower Limit:
Upper Limit:
46005 Final Speed Read Only Multiplier: 0.0625 Provides a point to monitor PC 2.x,
Reference Offset: 0 the final speed reference PC 3.x
Size (bits): 32
Sign: U
Unit: RPM
Lower Limit:
Upper Limit:
46006 Final Speed Read Only Multiplier: 0.0625 Provides a point to monitor PC 2.x,
Reference Offset: 0 the final speed reference PC 3.x
Size (bits): 32
Sign: U
Unit: RPM
Lower Limit:
Upper Limit:
46008 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
1 Offset: 0 Port 1 Temperature PC 3.x
Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -459
Upper Limit: 3155

258 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46009 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
2 Offset: 0 Port 2 Temperature PC 3.x
Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -459
Upper Limit: 3155
46010 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
3 Offset: 0 Port 3 Temperature PC 3.x
Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46011 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
4 Offset: 0 Port 4 Temperature PC 3.x
Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46012 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
5 Offset: 0 Port 5 Temperature PC 3.x
Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46013 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
6 Offset: 0 Port 6 Temperature PC 3.x
Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46014 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
7 Offset: 0 Port 7 Temperature PC 3.x
Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46015 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
8 Offset: 0 Port 8 Temperature PC 3.x
Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155

A029X159 (Issue 14) 259


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46016 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
9 Offset: 0 Port 9 Temperature PC 3.x
Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46017 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
10 Offset: 0 Port 10 Temperature PC 3.x
Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46018 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
11 Offset: 0 Port 11 Temperature PC 3.x
Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46019 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
12 Offset: 0 Port 12 Temperature PC 3.x
Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46020 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
13 Offset: 0 Port 13 Temperature PC 3.x
Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46021 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
14 Offset: 0 Port 14 Temperature PC 3.x
Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46022 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
15 Offset: 0 Port 15 Temperature PC 3.x
Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155

260 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46023 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
16 Offset: 0 Port 16 Temperature PC 3.x
Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46024 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
17 Offset: 0 Port 17 Temperature PC 3.x
Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46025 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
18 Offset: 0 Port 18 Temperature PC 3.x
Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46026 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
19 Offset: 0 Port 19 Temperature PC 3.x
Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46027 Exhaust Port Read Only Multiplier: 0.1 Monitor point for the Exhaust PC 2.x,
20 Offset: 0 Port 20 Temperature PC 3.x
Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: -460
Upper Limit: 3155
46028 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 1 PC 3.x
Cylinder 1 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46029 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 2 PC 3.x
Cylinder 2 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 261


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46030 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 3 PC 3.x
Cylinder 3 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46031 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 4 PC 3.x
Cylinder 4 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46032 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 5 PC 3.x
Cylinder 5 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46033 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 6 PC 3.x
Cylinder 6 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46034 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 7 PC 3.x
Cylinder 7 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46035 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 8 PC 3.x
Cylinder 8 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46036 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 9 PC 3.x
Cylinder 9 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:

262 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46037 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 10 PC 3.x
Cylinder 10 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46038 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 11 PC 3.x
Cylinder 11 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46039 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 12 PC 3.x
Cylinder 12 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46040 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 13 PC 3.x
Cylinder 13 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46041 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 14 PC 3.x
Cylinder 14 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46042 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 15 PC 3.x
Cylinder 15 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46043 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 16 PC 3.x
Cylinder 16 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 263


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46044 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 17 PC 3.x
Cylinder 17 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46045 Knock Level Read Only Multiplier: 1 Knock Level for cylinder 18 PC 3.x
Cylinder 18 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46046 Knock Level Read Only Multiplier : 1 Knock Level for cylinder 19 PC3.x
Cylinder 19 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
46047 Knock Level Read Only Multiplier : 1 Knock Level for cylinder 20 PC3.x
Cylinder 20 Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
46048 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 1 Offset: 0 cylinder 1
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46049 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 2 Offset: 0 cylinder 2
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

264 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46050 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 3 Offset: 0 cylinder 3
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46051 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 4 Offset: 0 cylinder 4
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46052 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 5 Offset: 0 cylinder 5
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46053 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 6 Offset: 0 cylinder 6
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46054 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 7 Offset: 0 cylinder 7
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46055 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cylr 8 Offset: 0 cylinder 8
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46056 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cylinder 9 Offset: 0 cylinder 9
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

A029X159 (Issue 14) 265


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46057 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cylinder 10 Offset: 0 cylinder 10
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46058 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 11 Offset: 0 cylinder 11
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46059 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 12 Offset: 0 cylinder 12
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46060 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 13 Offset: 0 cylinder 13
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46061 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 14 Offset: 0 cylinder 14
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46062 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 15 Offset: 0 cylinder 15
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46063 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 16 Offset: 0 cylinder 16
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

266 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46064 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 17 Offset: 0 cylinder 17
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46065 Knock Count Read Only Multiplier: 1 Knock count value for PC 3.x
Cyl 18 Offset: 0 cylinder 18
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46066 Knock Count Read Only Multiplier : 1 Knock count value for PC3.x
Cyl 19 Offset: 0 cylinder 19
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA
46067 Knock Count Read Only Multiplier : 1 Knock count value for PC3.x
Cyl 20 Offset: 0 cylinder 20
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA
46068 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 1 Offset: 0 cylinder 1
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit: 0
Upper Limit: 65530
Default: NA
46069 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 2 Offset: 0 cylinder 2
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 267


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46070 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 3 Offset: 0 cylinder 3
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46071 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 4 Offset: 0 cylinder 4
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46072 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 5 Offset: 0 cylinder 5
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46073 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 6 Offset: 0 cylinder 6
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46074 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 7 Offset: 0 cylinder 7
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46075 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 8 Offset: 0 cylinder 8
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46076 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 9 Offset: 0 cylinder 9
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:

268 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46077 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 10 Offset: 0 cylinder 10
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46078 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 11 Offset: 0 cylinder 11
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46079 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 12 Offset: 0 cylinder 12
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46080 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 13 Offset: 0 cylinder 13
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46081 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 14 Offset: 0 cylinder 14
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46082 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 15 Offset: 0 cylinder 15
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46083 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 16 Offset: 0 cylinder 16
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 269


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46084 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 17 Offset: 0 cylinder 17
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46085 Spark Timing Read Only Multiplier: 0.1 Spark timing degrees for PC 3.x
Cyl 18 Offset: 0 cylinder 18
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46086 Spark Timing Read Only Multiplier : 0.1 Spark timing degrees for PC 3.x
Cyl 19 Offset: 0 cylinder 19
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46087 Spark Timing Read Only Multiplier : 0.1 Spark timing degrees for PC 3.x
Cyl 20 Offset: 0 cylinder 20
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit: NA
Upper Limit: NA
Default: NA
46088 Internal Read Only Multiplier: 0.1 Temperature of the engine PC 3.x
SSM558 1 Offset: 0 electronic control unit
Temperature SSM558 1
Size (bits): 16
Sign: S
Unit: degF
Lower Limit:
Upper Limit:
46089 Internal Read Only Multiplier: 0.1 Temperature of the engine PC 3.x
SSM558 2 Offset: 0 electronic control unit
Temperature SSM558 2
Size (bits): 16
Sign: S
Unit: degF
Lower Limit:
Upper Limit

270 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46090 Internal Read Only Multiplier: 0.1 Temperature of the engine PC 3.x
MCM700 Offset: 0 electronic control unit
Temperature MCM700
Size (bits): 16
Sign: S
Unit: degF
Lower Limit:
Upper Limit
46091 Derate Read Only 0: NO Derate authorization request PC 3.x
Authorization 1: YES from customer.
2: Reserved
3: N/A
46092 Start System Read Only 0: Not Tripped Start system status monitor PC 3.x
Status 1: Tripped point.
2: Reserved
3: N/A
4: Network Failure
46093 Ventilator Fan Read Only 0: OFF Vent Fan status monitor PC 3.x
Status 1: ON point.
2: TRIPPED
3: N/A
46094 Louvres Read Only 0: Open Louvres Closed monitor point. PC 3.x
Status 1: Closed
2: Reserved
3: N/A
4: Network Failure
46095 Radiator Fan Read Only 0: OFF Radiator Fan status monitor PC 3.x
Status 1: ON point.
2: TRIPPED
3: N/A
46096 GIB Isolator Read Only 0: Close GIB Isolator Open monitor PC 3.x
Open 1: Open point.
(Aux101)
2: Reserved
3: N/A
46097 Alternator Read Only 0: OFF Alternator Heater status PC 3.x
Heater Status 1: ON monitor point.
2: TRIPPED
3: N/A
46099 Gearbox Oil Read Only 0: No Gearbox Oil Pressure monitor PC 3.x
Pressure 1: Yes point.
(Aux101)
2: Reserved
3: N/A
4: Network Failure
46100 Gearbox Oil Read Only 0: No Gearbox Oil Temperature PC 3.x
Temperature 1: Yes monitor point.
(Aux101)
2: Reserved
3: N/A
4: Network Failure

A029X159 (Issue 14) 271


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46101 Start Inhibit Read Only 0: Inactive Start Inhibit No1 monitor PC 3.x
No1 (Aux101) 1: Active point.
2: Reserved
3: N/A
46102 Start Inhibit Read Only 0: Inactive Start Inhibit No2 monitor PC 3.x
No2 (Aux101) 1: Active point.
2: Reserved
3: N/A
46103 Start Inhibit Read Only 0: Inactive Start Inhibit No3 monitor PC 3.x
No3 (Aux101) 1: Active point.
2: Reserved
3: N/A
46104 DC PSU Read Only 0: No Engine PSU Not Available PC 3.x
Unavailable 1: Yes monitor point.
(Aux101)
46105 Ventilator Fan Read Only 0: No Ventilator Fan Trip monitor PC 3.x
Trip (Aux101) 1: Yes point.

46106 Aux101-3 Read Only Multiplier: 0.01 Software version of the PC 3.x
Software Offset: 0 firmware for the Aux101-3
Version
Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit
46107 Aux101-4 Read Only Multiplier: 0.01 Software version of the PC 3.x
Software Offset: 0 firmware for the Aux101-4
Version
Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit
46108 Aux101-5 Read Only Multiplier: 0.01 Software version of the PC 3.x
Software Offset: 0 firmware for the Aux101-5
Version
Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit

272 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46109 Engine Read Only 0: Engine Stopped Indicate current state or mode PC 2.x
Operating 1: Pre-Start of operation by the engine PC 3.x
State
2: Starting
3: Warm-Up
4: Running
5: Cool-Down
6: Engine Stopping
7: Post-Run
8: Out Of Range
9: Out Of Range
10: Out Of Range
11: Out Of Range
12: Out Of Range
13: Out Of Range
14: Out Of Range
15: N/A
46110 Fuel Pump Read Only 0: Inactive Fuel pump state PC 3.x
Control 1: Active
Status
2: Reserved
3: Not Available
46112 Fuel Shutoff Read Only 0: Closed Fuel shutoff valve status PC 3.x
Vent Valve 1: Open
status
2: Reserved
3: Not Available
46113 Downstream Read Only 0: Open The result of the FSO driver PC 3.x
Valve 1: Closed output command logic for fuel
Command shutoff valve 1
Status 2: Reserved
3: N/A
46114 Upstream Read Only 0: Open The result of the FSO driver PC 3.x
Valve 1: Closed output command logic for fuel
Command shutoff valve 2.
Status 2: Reserved
3: N/A
46115 VPS Status Read Only 0: OFF Control setting for fuel shutoff PC 3.x
1: ON valve proving system test
2: Reserved
3: N/A
46116 Gas Supply Read Only Multiplier : 0.1 Gage Pressure of gas supply PC 3.x
Pressure Offset: 0 to fuel metering device
Size (bits): 16
Sign: U
Units: psi
Lower Limit: NA
Upper Limit: NA
Default: NA
46117 Engine Oil Read Only 0: OFF Engine Oil pre heater PC 3.x
PreHeater 1: ON command status
Ctrl Status
2: Reserved
3: N/A

A029X159 (Issue 14) 273


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46118 Engine Power Read Only 0: OFF Control setting for cutting PC 3.x
Conservation 1: ON power to various devices
Ctrl Status when the engine is not in use
2: Reserved
3: Not Available
46119 Engine Read Only 0: OFF Engine coolant PreHeater PC 3.x
Coolant 1: ON states
PreHeater
Ctrl Status 2: Reserved
3: N/A
46120 Engine Read Only 0: OFF Engine coolant circulating PC 3.x
Coolant 1: ON pump status
Pump Ctrl
Status 2: Reserved
3: N/A
46121 Engine Read Only 0: Inactive Active when the engine PC 3.x
Controlled 1: Active control request a controlled
Shutdown shutdown (shutdown with
Request 2: Reserved cooldown)
3: Not Available
46122 Emergency Read Only 0: Inactive Active when the engine PC 3.x
Shutdown 1: Active control request an emergency
Request shutdown (immediate
2: Reserved shutdown)
3: Not Available
46123 Engine Read Only Multiplier : 0.4 Derate request in percent PC 3.x
Derate Offset: 0 made by the engine control
Request
Size (bits): 8
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
46124 Coolant Read Only Multiplier: 0.1 Monitor point for the Coolant PC 2.x,
Pressure Offset: 0 Pressure. PC 3.x
Size (bits): 8
Sign: U
Unit: psi
Lower Limit: NA
Upper Limit: NA
46125 Coolant 2 Read Only Multiplier: 0.1 Monitor point for the Coolant PC 3.x
Pressure Offset: 0 2 Pressure.
Size (bits): 16
Sign: U
Unit: psi
Lower Limit: 0
Upper Limit: 145
46127 Coolant 2 Read Only Multiplier: 0.1 Monitor point for the Coolant PC 3.x
Temperature Offset: 0 2 Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit:
Upper Limit:

274 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46128 Compressor Read Only Multiplier: 0.1 Engine turbocharger PC 3.x
Bypass Offset: 0 compressor bypass actuator
Position position
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46129 Engine Oil Read Only Multiplier : 0.1 ”Engine oil pressure at the PC 3.x
Filter Outlet Offset: 0 outlet of the filter
Pressure Search ””17185”” (2 hits in 2
Size (bits): 16
files)”
Sign: U
Units: psi
Lower Limit: NA
Upper Limit: NA
Default: NA
46130 Oil Priming Read Only 0: OFF Status for the priming pump PC 3.x
Pump Control 1: ON (ON or OFF)
Status
2: Reserved
3: N/A
46131 Oil Priming Read Only 0: Low Status of the engine before PC 3.x
State 1: Optimum start (Pre-Lubed or Not)
2: Reserved
3: N/A
46132 Oil Pre- Read Only 0: Cold Status of the engine oil PC 3.x
Heated State 1: Heated before start (Pre-Heated or
Not)
2: Reserved
3: N/A
46133 Coolant Pre- Read Only 0: Cold Status of the engine coolant PC 3.x
Heated State 1: Heated before start (Pre-Heated or
Not)
2: Reserved
3: N/A
46134 Ventilation Read Only 0: Vented Engine Ventilation Status PC 3.x
Status 1: Not Vented (Vented or Not)
2: Ventilation Delay
3: Currently Venting
4: Reserved
5: Reserved
6: Not Able To Determine
7: Not Available
46135 Intake Read Only Multiplier: 0.1 Intake Manifold Pressure 1 PC 3.x
Manifold Offset: 0
Pressure 1
Size (bits): 16
Sign: U
Units: psi
Lower Limit: NA
Upper Limit: NA

A029X159 (Issue 14) 275


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46136 Compressor Read Only Multiplier: 0.1 Absolute Pressure at the PC 3.x
Outlet Offset: 0 outlet of the compressor.
Pressure
Size (bits): 16
Sign: U
Unit: kPa
Lower Limit: NA
Upper Limit: NA
46137 Turbocharger Read Only Multiplier : 0.1 Monitor point for the PC 3.x
1 Boost Offset: 0 Turbocharger 1 Boost
Pressure Pressure
Size (bits): 16
Sign: U
Units: psi
Lower Limit: NA
Upper Limit: NA
Default: NA
46138 Genset Avg Read Only Multiplier : 0.1 Average Genset AC PC 3.x
AC Offset: 0 frequency
Frequency
Size (bits): 16
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
46139 Fuel Valve 1 Read Only Multiplier: 0.1 Absolute Pressure of Gas on PC 3.x
Inlet Absolute Offset: 0 the inlet side of the first
Pressure system control valve
Size (bits): 16
Sign: U
Unit: psi
Lower Limit: NA
Upper Limit: NA
46140 Fuel Valve 1 Read Only Multiplier: 0.1 Absolute Pressure of Gas on PC 3.x
Outlet Offset: 0 the outlet side of the first
Absolute system control valve
Pressure Size (bits): 16
Sign: U
Unit: psi
Lower Limit: NA
Upper Limit: NA
46141 Fuel Valve 1 Read Only Multiplier: 0.1 PC 3.x
Position Offset: 0
Size (bits): 16
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA

276 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46142 Fuel Valve 2 Read Only Multiplier: 0.1 Absolute Pressure of Gas on PC 3.x
Inlet Absolute Offset: 0 the inlet side of the second
Pressure system control valve
Size (bits): 16
Sign: U
Unit: psi
Lower Limit: NA
Upper Limit: NA
46143 Fuel Valve 2 Read Only Multiplier: 0.1 Absolute Pressure of Gas on PC 3.x
Outlet Offset: 0 the outlet side of the second
Absolute system control valve
Pressure Size (bits): 16
Sign: U
Unit: psi
Lower Limit: NA
Upper Limit: NA
46144 Fuel Valve 2 Read Only Multiplier: 0.1 PC 3.x
Position Offset: 0
Size (bits): 16
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
46145 Gas Mass Read Only Multiplier: 0.1 Gas Mass Flow value of the PC 3.x
Flow Offset: 0 engine.
Size (bits): 16
Sign: U
Unit: Pounds per hour
Lower Limit:
Upper Limit:
46146 Gas Mass Read Only Multiplier: 0.1 Gas Mass Flow value of the PC 3.x
Flow Offset: 0 engine.
Size (bits): 32
Sign: U
Unit: Pounds per hour
Lower Limit:
Upper Limit:
46147 Throttle 1 Read Only Multiplier: 0.1 Position of the throttle 1. PC 3.x
Position Offset: 0
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46148 Throttle 2 Read Only Multiplier: 0.1 Position of the throttle 2. PC 3.x
Position Offset: 0
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 277


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46149 Raw Value Read Only Multiplier : 1 Raw Value for the DE RTD PC 3.x
DE RTD Offset: 0 Bearing from the Aux101
Bearing
Size (bits): 16
Sign: U
Units: Count
Lower Limit: NA
Upper Limit: NA
Default: NA
46150 Raw Value Read Only Multiplier : 1 Raw Value Alternator RTD L1 PC 3.x
Alternator Offset: 0 from Aux101 (10 bits raw
RTD L1 data)
Size (bits): 16
Sign: U
Units: Count
Lower Limit: NA
Upper Limit: NA
Default: NA
46151 Raw Value Read Only Multiplier : 1 Raw Value Alternator RTD L2 PC 3.x
Alternator Offset: 0 from Aux101 (10 bits raw
RTD L2 data)
Size (bits): 16
Sign: U
Units: Count
Lower Limit: NA
Upper Limit: NA
Default: NA
46152 Raw Value Read Only Multiplier : 1 Raw Value Alternator RTD L3 PC 3.x
Alternator Offset: 0 from Aux101 (10 bits raw
RTD L3 data)
Size (bits): 16
Sign: U
Units: Count
Lower Limit: NA
Upper Limit: NA
Default: NA
46153 Raw Value Read Only Multiplier : 1 Raw Value NDE RTD Bearing PC 3.x
NDE RTD Offset: 0 from Aux101 (10 bits raw
Bearing data)
Size (bits): 16
Sign: U
Units: Count
Lower Limit: NA
Upper Limit: NA
Default: NA
46155 MCM700 Read Only Multiplier: 0.1 Engine Control Module PC 3.x
Battery Offset: 0 Battery Voltage.
Voltage
Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA

278 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46157 CM700 Read Only Multiplier : 0.1 Engine Control Module PC 3.x
Sensor Offset: 0 CM700 Sensor Voltage A
Voltage A
Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: NA
Upper Limit: NA
Default: NA
46158 CM700 Read Only Multiplier : 0.1 Engine Control Module PC 3.x
Sensor Offset: 0 CM700 Sensor Voltage B
Voltage B
Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: NA
Upper Limit: NA
Default: NA
46159 CM700 Read Only Multiplier : 0.1 Engine Control Module PC 3.x
Sensor Offset: 0 CM700 Sensor Voltage C
Voltage C
Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: NA
Upper Limit: NA
Default: NA
46160 SSM558 1 Read Only Multiplier : 0.1 SSM558 1 Engine Control PC 3.x
Battery Offset: 0 Module Battery Voltage.
Voltage
Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: NA
Upper Limit: NA
Default: NA
46161 SSM558 1 Read Only Multiplier: 0.1 SSM558 1 Engine Control PC 3.x
Isolated Offset: 0 Module Isolated Battery
Battery Voltage.
Voltage Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA
46162 SSM558 2 Read Only Multiplier : 0.1 SSM558 2 Engine Control PC 3.x
Battery Offset: 0 Module Battery Voltage.
Voltage
Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA

A029X159 (Issue 14) 279


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46163 SSM558 2 Read Only Multiplier: 0.1 SSM558 2 Engine Control PC 3.x
Isolated Offset: 0 Module Isolated Battery
Battery Voltage.
Voltage Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA
46164 Intake Read Only Multiplier: 0.1 Intake Manifold Pressure 2 PC 3.x
Manifold Offset: 0
Pressure 2
Size (bits): 16
Sign: U
Unit: psi
Lower Limit:
Upper Limit:
46165 Intake Read only Multiplier : 0.1 Monitor point for the Intake PC 3.x
Manifold Offset: 0 Manifold Temperature 2
Temperature
2 Size (bits): 16
Sign: S
Units: degF
Lower Limit: -40
Upper Limit: 410
Default: NA
46166 Exhaust Back Read Only Multiplier: 0.1 Monitor point for exhaust PC 3.x
Pressure Offset: 0 back pressure value
Size (bits): 16
Sign: U
Unit: psi
Lower Limit: -40
Upper Limit: 410
46168 Air Filter Read only Multiplier : 0.1 Monitor point for air filter PC 3.x
Differential Offset: 0 differential pressure value
Pressure
Size (bits): 16
Sign: S
Unit: psi
Lower Limit: NA
Upper Limit: NA
Default: NA
46170 Gas Mass Read Only Multiplier: 0.1 Gas Mass Flow 2 value of the PC 3.x
Flow 2 Offset: 0 engine.
Size (bits): 16
Sign: U
Unit: Pounds per hour
Lower Limit:
Upper Limit:

280 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46171 Gas Mass Read Only Multiplier: 0.1 Gas Mass Flow 2 value of the PC 3.x
Flow 2 Offset: 0 engine.
Size (bits): 32
Sign: U
Unit: Pounds per hour
Lower Limit:
Upper Limit:
46180 E-Stops Read Only 0: Inactive PC 3.x
disengaged 1: Active
46176 Gearbox Read / Write 0: No Enables gearbox protection PC 3.x
Present 1: Yes
46182 Radiator Fan Read Only 0: Inactive Radiator fan control PC 3.x
control 1: Active command

46183 Ventilator Fan Read/Write 0: Limited Vent fan control mode, limited PC 3.x
mode 1: Continuous or continuous

46184 Louvre Read Only 0: Inactive Louvre control PC 3.x


Control 1: Active
46191 Ventilator Fan Read Only 0: Inactive Ventilator fan control PC 3.x
control 1: Active command

46192 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 1
1
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
46193 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 2
2
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46194 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 3
3
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA

A029X159 (Issue 14) 281


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46195 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 4
4
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46196 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 5
5
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46197 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 6
6
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46198 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 7
7
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46199 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 8
8
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46200 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 9
9
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA

282 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46201 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 10
10
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46202 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 11
11
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46203 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 12
12
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46204 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 13
13
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46205 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 14
14
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46206 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 15
15
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA

A029X159 (Issue 14) 283


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46207 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 16
16
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46208 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 17
17
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46209 Engine Spark Read Only Multiplier : 1 Spark Plug Voltage for PC 3.x
Plug Voltage Offset: 0 Cylinder 18
18
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA
46273 Alternator Read Only 0: No Alternator Heater monitor PC 3.x
Heater ON 1: Yes point.
(Aux101)
2: Reserved
3: N/A
4: Network Failure
46288 DE/NDE Read/Write 0: Drive End Gives reference point for PC 3.x
Cylinder 1: Non-Drive End engine cylinder numbering
Viewpoint
Reference 2: Reserved
3: N/A
46291 Radiator Fan Read Only 0: Not Tripped Radiator Fan Trip monitor PC 3.x
Trip (Aux 1: Tripped point.
101)
2: Reserved
3: N/A
46300 LBNG Genset Read/Write 0: Disable Switch to enable or disable PC 3.x
Enable 1: Enable the gas specific features and
parameters
46301 Aux101-3 Read/Write 0: Disable Enable the processing for PC 3.x
Enable 1: Enable Aux101-3 messages

46302 Aux101-4 Read/Write 0: Disable Enable the processing for PC 3.x


Enable 1: Enable Aux101-4 messages

46303 Aux101-5 Read/Write 0: Disable Enable the processing for PC 3.x


Enable 1: Enable Aux101-5 messages

46304 Aux101-6 Read/Write 0: Disable Enable the processing for PC 3.x


Enable 1: Enable Aux101-6 messages

284 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46308 Aux101-3 Read Only Multiplier: 1 Input Port configuration bye PC 3.x
Input Port Offset: 0 for the Aux101-3
Config
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255
46309 Aux101-4 Read Only Multiplier: 1 Input Port configuration bye PC 3.x
Input Port Offset: 0 for the Aux101-4
Config
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255
46310 Aux101-5 Read Only Multiplier: 1 Input Port configuration bye PC 3.x
Input Port Offset: 0 for the Aux101-5
Config
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255
46311 Aux101-3 DI Read Only Multiplier: 1 Digital Input Port PC 3.x
Active Offset: 0 configuration active High or
High/Low active low for the Aux101-3
Selection Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255
46312 Aux101-4 DI Read Only Multiplier: 1 Digital Input Port PC 3.x
Active Offset: 0 configuration active High or
High/Low active low for the Aux101-4
Selection Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255
46313 Aux101-5 DI Read Only Multiplier: 1 Digital Input Port PC 3.x
Active Offset: 0 configuration active High or
High/Low active low for the Aux101-5
Selection Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255
46314 Aux101-3 DI Read Only Multiplier: 1 Discrete Input configuration PC 3.x
Config Mask Offset: 0 bit mask for the Aux101-3
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255

A029X159 (Issue 14) 285


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46315 Aux101-4 DI Read Only Multiplier: 1 Discrete Input configuration PC 3.x
Config Mask Offset: 0 bit mask for the Aux101-4
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255
46316 Aux101-5 DI Read Only Multiplier: 1 Discrete Input configuration PC 3.x
Config Mask Offset: 0 bit mask for the Aux101-5
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255
46323 Vehicle Read/Write 0: Disabled A trim that enables the PC 3.x
Electrical 1: Enabled Vehicle Electrical Power 2
Power 2 message
PGN65165
Enable
46326 Gaseous Fuel Read/Write 0: Disabled A trim that enables the PC 3.x
Pressure 1: Enabled Gaseous Fuel Pressure
PGN65163 message
Enable
46327 Fuel Read/Write 0: Disabled A trim that enables the Fuel PC 3.x
Information 3 1: Enabled Information 3 - Gaseous
- Gaseous message
PGN64930
Enable
46328 Fuel Read/Write 0: Disabled A trim that enables the Fuel PC 3.x
Information 2 1: Enabled Information 2 - Gaseous
- Gaseous message
PGN65153
Enable
46332 Inlet/Exhaust Read/Write 0: Disabled A trim that enables the PC 3.x
Conditions 1: Enabled Inlet/Exhaust Conditions
PGN65270 message
Enable
46333 Knock Count Read/Write 0: Disabled A trim that enables Knock PC 3.x
1 PGN65336 1: Enabled Count 1 message
Enable
46334 Knock Count Read/Write 0: Disabled A trim that enables Knock PC 3.x
2 PGN65337 1: Enabled Count 2 message
Enable
46335 Knock Count Read/Write 0: Disabled A trim that enables Knock PC 3.x
3 PGN65338 1: Enabled Count 3 message
Enable
46336 Knock Count Read/Write 0: Disabled A trim that enables Knock PC 3.x
4 PGN65339 1: Enabled Count 4 message
Enable
46337 Knock Count Read/Write 0: Disabled A trim that enables Knock PC 3.x
5 PGN65340 1: Enabled Count 5 message
Enable

286 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46338 Ignition Read/Write 0: Disabled A trim that enables the PC 3.x
Timing 1 1: Enabled Ignition Timing 1 message
PGN65154
Enable
46339 Ignition Read/Write 0: Disabled A trim that enables the PC 3.x
Timing 2 1: Enabled Ignition Timing 2 message
PGN65155
Enable
46340 Ignition Read/Write 0: Disabled A trim that enables the PC 3.x
Timing 3 1: Enabled Ignition Timing 3 message
PGN65156
Enable
46341 Ignition Read/Write 0: Disabled A trim that enables the PC 3.x
Timing 4 1: Enabled Ignition Timing 4 message
PGN65157
Enable
46342 Ignition Read/Write 0: Disabled A trim that enables the PC 3.x
Timing 5 1: Enabled Ignition Timing 5 message
PGN65158
Enable
46344 Start-Enable Read/Write 0: Disable Remote Modbus Start-Enable PC 3.x
(Modbus 1: Enabled input.
Input)
46348 Target Speed Read Only Multiplier : 0.0625 The speed reference function PC 2.x,
Offset: 0 desired speed before ramping PC 3.x
Size (bits): 16
Sign: 32
Units: rpm
Lower Limit: NA
Upper Limit: NA
Default: NA
46349 Target Speed Read Only Multiplier : 0.0625 The speed reference function PC 2.x,
Offset: 0 desired speed before ramping PC 3.x
Size (bits): 16
Sign: 32
Units: rpm
Lower Limit: NA
Upper Limit: NA
Default: NA
46364 Modbus Read Only 0: Disable Modbus Register Read Only PC 2.x,
Register 1: Enable Enable For TB15 Modbus PC 3.x
Read Only Communication Port.
Enable
46365 Modbus Read Only 0: Disable Modbus Register Read Only PC 3.x
Register 1: Enable Enable For J14 Modbus
Read Only Communication Port.
Enable (J14)
46366 Modbus Stop Read/Write 0:01 Sets the Modbus number of PC 3.x
Bits (J14) 1:02 stop bits for this node Limited
to 1 bit if parity = Odd or
Even

A029X159 (Issue 14) 287


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46367 Modbus Bus Read Only Multiplier: 1 The number of Modbus PC 3.x
Message Offset: 0 messages with no response,
Count (J14) for J14 port only
Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit:
46368 Modbus CRC Read Only Multiplier: 1 The number of Modbus CRC PC 3.x
Error Count Offset: 0 errors, for J14 only.
(J14)
Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit:
46369 Modbus Read Only Multiplier: 1 Modbus exception count, for PC 3.x
Exception Offset: 0 J14 only.
Count (J14)
Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit:
46370 Modbus No Read Only Multiplier: 1 Modbus no response count, PC 3.x
Response Offset: 0 for J14 only.
Count (J14)
Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit:
46371 Modbus Read Only Multiplier: 1 The number of Modbus slave PC 3.x
Slave Offset: 0 messages, for J14 only.
Message
Count (J14) Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit:
46372 Modbus Node Read/Write Multiplier: 1 Sets the Modbus address for PC 3.x
Address (J14) Offset: 0 this node, for J14 only.
Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 247
46373 Modbus Baud Read/Write 1.6666667 Sets the baud rate for PC 3.x
Rate (J14) 3.375 Modbus communications, for
J14 only.
6.75
46374 Modbus Read/Write 0: Even Sets the Modbus parity for PC 3.x
Parity (J14) 1: Odd this node, for J14 only.
2: None

288 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46376 Modbus Baud Read/Write 0: 2400 Baud Sets the Modbus baud rate. PC 2.x,
Rate 1: 4800 Baud PC 3.x
2: 9600 Baud
3: 19200 Baud
4: 38400 Baud
46377 Modbus Read/Write 0: Even Sets the Modbus parity for PC 2.x,
Parity 1: Odd this node PC 3.x
2: None
46378 Modbus Node Read/Write Multiplier: 1 Sets the Modbus address for PC 2.x,
Address Offset: 0 this node PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 247
46379 Modbus Stop Read/Write 0:01 Sets the Modbus number of PC 2.x,
Bits 1:02 stop bits for this node Limited PC 3.x
to 1 bit if parity = Odd or
Even
46380 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46381 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46382 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46383 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 289


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46384 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46385 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46386 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46387 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46388 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46389 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46390 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

290 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46391 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46392 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46393 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46394 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46395 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46396 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46397 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 291


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46398 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46399 HMI113 Fault Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
3 Text Offset: 0 string to enter the PC 3.x
configurable fault text for this
Size (bits): 168 fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46600 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46601 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46602 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46603 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46604 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

292 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46605 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46606 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46607 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46608 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46609 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46610 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46611 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 293


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46612 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46613 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46614 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46615 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46616 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46617 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46618 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

294 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46619 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46620 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46621 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46622 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46623 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46624 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46625 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 295


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46626 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46627 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46628 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46629 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46630 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46631 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46632 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

296 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46633 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46634 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46635 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46636 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46637 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46638 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46639 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 297


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46640 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46641 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46642 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46643 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46644 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46645 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46646 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

298 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46647 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46648 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46649 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46650 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46651 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46652 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46653 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 299


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46654 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46655 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46656 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46657 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46658 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46659 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 1 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46660 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

300 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46661 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46662 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46663 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46664 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46665 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46666 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46667 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 301


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46668 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46669 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46670 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46671 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46672 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46673 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46674 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

302 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46675 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46676 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46677 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46678 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46679 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 2 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46800 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46801 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 303


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46802 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46803 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46804 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46805 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46806 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46807 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46808 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

304 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46809 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46810 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46811 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46812 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46813 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46814 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46815 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 305


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46816 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46817 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46818 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46819 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46820 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46821 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46822 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

306 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46823 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46824 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46825 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46826 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46827 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46828 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46829 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 307


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46830 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46831 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46832 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46833 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46834 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46835 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46836 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

308 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46837 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46838 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46839 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46840 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46841 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46842 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46843 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 309


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46844 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46845 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46846 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46847 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46848 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46849 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46850 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

310 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46851 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46852 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46853 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46854 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46855 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46856 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46857 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 311


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46858 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46859 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46860 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46861 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46862 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46863 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46864 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

312 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46865 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46866 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46867 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46868 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46869 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46870 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 313


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46871 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46872 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46873 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46874 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46875 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46876 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46877 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

314 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46878 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46879 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46880 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46881 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46882 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46883 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46884 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 315


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46885 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46886 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46887 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46888 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46889 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46890 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46891 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

316 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46892 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46893 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46894 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46895 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46896 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46897 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46898 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 317


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46899 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 3 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46900 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
Unit:
46901 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46902 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46903 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46904 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

318 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46905 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46906 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46907 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46908 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46909 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46910 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 319


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46911 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46912 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46913 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46914 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46915 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46916 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46917 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

320 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46918 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46919 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 4 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46920 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46921 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46922 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46923 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 321


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46924 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46925 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46926 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46927 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46928 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46929 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

322 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46930 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46931 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46932 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46933 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46934 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46935 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 323


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46936 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46937 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46938 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46939 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 5 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46940 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46941 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46942 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

324 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46943 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46944 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46945 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46946 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46947 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46948 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 325


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46949 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46950 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46951 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46952 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46953 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46954 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

326 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46955 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46956 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46957 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46958 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46959 Aux101 1 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 6 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46960 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 327


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46961 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46962 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,


Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46963 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46964 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46965 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46966 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46967 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

328 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46968 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46969 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46970 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46971 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46972 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46973 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46974 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 329


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46975 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46976 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46977 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46978 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46979 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 7 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46980 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46981 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

330 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46982 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46983 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46984 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46985 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46986 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46987 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46988 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

A029X159 (Issue 14) 331


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


46989 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46990 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46991 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46992 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46993 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46994 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46995 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

332 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


46996 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46997 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46998 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46999 Aux101 0 Read/Write Multiplier: 1 Twenty (20) character text PC 2.x,
Input 8 Fault Offset: 0 field to allow for the entry of PC 3.x
Text the displayed configurable
Size (bits): 168 fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
47002 GK1 (60Hz) Read Only Multiplier: 1 The governor 60Hz K1 gain PC 2.x,
Offset: 0 adjust. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47003 GK2 (60Hz) Read Only Multiplier: 1 The governor 60Hz integral PC 2.x,
Offset: 0 gain adjust. PC 3.x
Size (bits): 168
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47004 GK3 (60Hz) Read Only Multiplier: 1 The governor 60Hz K3 gain PC 2.x,
Offset: 0 adjust. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

A029X159 (Issue 14) 333


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


47005 Governor Read Only Multiplier: 1.52587890625E- The governor 60Hz damping PC 2.x,
Damping 05 adjust. PC 3.x
Effect (60Hz) Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0.6
Upper Limit: 0.95
47006 GK1 (50Hz) Read Only Multiplier: 1 The governor 50Hz K1 gain PC 2.x,
Offset: 0 adjust. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47007 GK2 (50Hz) Read Only Multiplier: 1 The governor 50Hz integral PC 2.x,
Offset: 0 gain adjust. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47008 GK3 (50Hz) Read Only Multiplier: 1 The governor 50Hz K3 gain PC 2.x,
Offset: 0 adjust. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47009 Governor Read Only Multiplier: The governor 50Hz damping PC 2.x,
Damping 1.52587890625E–05 adjust. PC 3.x
Effect (50Hz) Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0.6
Upper Limit: 0.95
47010 GK1(Idle) Read Only Multiplier: 1 This trim is used to adjust gk1 PC 2.x,
Offset: 0 in idle mode. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47011 GK2(Idle) Read Only Multiplier: 1 This trim is used to adjust gk2 PC 2.x,
Offset: 0 in idle mode. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

334 A029X159 (Issue 14)


10-2015 4. PowerCommand 2.x/3.x Modbus Register Map

Addr. Parameter Access Specifications Description Control


47014 Gain Read Only 0: Disable Either enables or disables PC 2.x,
Windowing 1: Enable Gain Windowing feature. PC 3.x
Enable
47015 GK1 Read Only Multiplier: 1 The governor 50Hz K1 low PC 2.x,
Low(50Hz) Offset: 0 gain adjust. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47016 GK1 Read Only Multiplier: 1 The governor 60Hz K1 low PC 2.x,
Low(60Hz) Offset: 0 gain adjust. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47017 GK1 Read Only Multiplier: 1 The governor 50Hz K1 high PC 2.x,
High(50Hz) Offset: 0 gain adjust. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47018 GK1 Read Only Multiplier: 1 The governor 60Hz K1 high PC 2.x,
High(60Hz) Offset: 0 gain adjust. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47019 Governor Read Only Multiplier: 1 The speed error higher limit. PC 2.x,
Speed Delta Offset: 0 PC 3.x
High
Size (bits): 16
Sign: U
Unit:
Lower Limit: 50
Upper Limit: 1000
47020 Governor Read Only Multiplier: 1 The speed error lower limit. PC 2.x,
Speed Delta Offset: 0 PC 3.x
Low
Size (bits): 16
Sign: U
Unit:
Lower Limit: 50
Upper Limit: 1000
47021 Intake Read Only 0: PGBU Either PGBU(Onan) or PC 2.x,
Manifold 1: EBU EBU(Cummins) sensor. PC 3.x
Temperature
Sensor Type

A029X159 (Issue 14) 335


4. PowerCommand 2.x/3.x Modbus Register Map 10-2015

Addr. Parameter Access Specifications Description Control


47022 Intake Read Only 0: Disable Intake Manifold Temperature PC 2.x,
Manifold 1: Enable Sensor available or not. PC 3.x
Temperature
Sensor
Enable
47023 Oil Read Only 0: PGBU Either PGBU(Onan) or PC 2.x,
Temperature 1: EBU EBU(Cummins) sensor. PC 3.x
Sensor Type
47024 Oil Read Only 0: Disable High Oil Temperature Sensor PC 2.x,
Temperature 1: Enable available or not. PC 3.x
Sensor
Enable
47025 AVR PWM Read Only Multiplier: 0.01 The AVR PWM software PC 2.x,
Command Offset: 0 command. Linear relationship PC 3.x
between counts and % duty
Size (bits): 16 cycle with 10000
Sign: U counts=100% duty cycle.
Unit: %
Lower Limit:
Upper Limit:
47026 Coolant Read Only 0: Disable Coolant Temperature 2 PC 3.x
Temperature 1: Enable Enable
2 Enable
47027 Start Inhibit Read Only Multiplier : 0.05 Delay progress until a fault is PC 3.x
Delay Offset: 0 declared for start inhibit
Progress
Size (bits): 16
Sign: U
Units: Seconds
Lower Limit: NA
Upper Limit: NA
Default: NA
47028 Genset Read Only 0: Close Indicates the Genset Voltage PC 3.x
Voltage 1: Open sensing MCB status.
Sensing MCB
status 2: Reserved
3: N/A
4: Network Failure
47029 Customer Read Only 0: Open Indicates the status of the PC 3.x
Gas Valve 1: Closed Customer Gas Valve position.
Status
2: Reserved
3: N/A
4: Network Failure
47030 Crankcase Read Only Multiplier : 0.01 Monitor point for the PC 2.x
Pressure Offset: 0 Crankcase Pressure with PC 3.x
Extended extended precision.
Size (bits): 16
Sign: S
Units: psi
Lower Limit: -35.67
Upper Limit: 38
Default: NA

336 A029X159 (Issue 14)


5 PowerCommand 2.x/3.x Modbus Fault
Status Bitmaps
NOTICE
Earlier versions of software may not support all of the Modbus registers in the following
table. If a particular register is not available in your installation, it is possible that the
Modbus connection is working but the controller software does not support that
particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

NOTICE
The Master device can read 1-40 contiguous registers, write 1-40 contiguous registers,
or read diagnostic counters.

Addr. Bit# Name Fault Event Name Response Control


Code
Fault Status Engine Magnetic Crankshaft PC 2.x,
40400 0 115 Shutdown
Bitmap 1 Speed/Position PC 3.x
Fault Status Intake Manifold 1 Pressure: Vtg PC 2.x,
40400 1 122 Warning
Bitmap 1 Above Normal PC 3.x
Fault Status Intake Manifold 1 Pressure: Vtg PC 2.x,
40400 2 123 Warning
Bitmap 1 Below Normal PC 3.x
Fault Status Intake Manifold 1 Pressure: PC 2.x,
40400 3 124 Warning
Bitmap 1 Moderately Severe PC 3.x
Fault Status Engine Oil Rifle Pressure 1: Vtg PC 2.x,
40400 4 135 Warning
Bitmap 1 Above Normal PC 3.x
Fault Status Engine Oil Rifle Pressure 1: Vtg PC 2.x,
40400 5 141 Warning
Bitmap 1 Below Normal PC 3.x
Fault Status Engine Oil Rifle Pressure - PC 2.x,
40400 6 143 Warning
Bitmap 1 Moderately Severe PC 3.x
Fault Status Engine Coolant Temp 1: Vtg Above PC 2.x,
40400 7 144 Warning
Bitmap 1 Normal PC 3.x
Fault Status Engine Coolant Temp 1: Vtg Below PC 2.x,
40400 8 145 Warning
Bitmap 1 Normal PC 3.x
Fault Status Engine Coolant Temp: Moderately PC 2.x,
40400 9 146 Derate
Bitmap 1 Above Normal PC 3.x
Fault Status Engine Coolant Temp: Severely PC 2.x,
40400 10 151 Shutdown
Bitmap 1 Above Normal PC 3.x
Fault Status Intake Manifold 1 Temp: Vtg Above PC 2.x,
40400 11 153 Warning
Bitmap 1 Normal PC 3.x

A029X159 (Issue 14) 337


5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 10-2015

Addr. Bit# Name Fault Event Name Response Control


Code
Fault Status Intake Manifold 1 Temp: Vtg Below PC 2.x,
40400 12 154 Warning
Bitmap 1 Normal PC 3.x
Fault Status Intake Manifold 1 Temp: Severely PC 2.x,
40400 13 155 Shutdown
Bitmap 1 Above Normal PC 3.x
Fault Status PC 2.x,
40400 14 187 Sensor Supply 2: Vtg Below Normal Warning
Bitmap 1 PC 3.x
Fault Status Coolant Level Sensor 1: Vtg Above PC 2.x,
40400 15 195 Warning
Bitmap 1 Normal PC 3.x
Fault Status Coolant Level Sensor 1: Vtg Below PC 2.x,
40401 0 196 Warning
Bitmap 2 Normal PC 3.x
Fault Status Coolant Level: Below Normal - PC 2.x,
40401 1 197 Warning
Bitmap 2 Moderately Severe PC 3.x
Fault Status Engine Oil Temp Sensor 1: Vtg PC 2.x,
40401 2 212 Warning
Bitmap 2 Above Normal PC 3.x
Fault Status Engine Oil Temp Sensor 1: Vtg PC 2.x,
40401 3 213 Warning
Bitmap 2 below Normal PC 3.x
Fault Status Engine Oil Temp: Above Normal - PC 2.x,
40401 4 214 Shutdown
Bitmap 2 Most severe PC 3.x
Fault Status Barometric Pressure: Vtg Above PC 2.x,
40401 5 221 Warning
Bitmap 2 Normal PC 3.x
Fault Status Barometric Pressure Sensor: Vtg PC 2.x,
40401 6 222 Warning
Bitmap 2 Below Normal PC 3.x
Fault Status Engine Oil Burn Valve Solenoid: Vtg PC 2.x,
40401 7 223 Warning
Bitmap 2 Below Normal PC 3.x
Fault Status Engine Oil Burn Valve Solenoid: Vtg PC 2.x,
40401 8 224 Warning
Bitmap 2 Above Normal PC 3.x
Fault Status PC 2.x,
40401 9 227 Sensor Supply 2: Vtg Above Normal Warning
Bitmap 2 PC 3.x
Fault Status Coolant Pressure: Below Normal- PC 2.x,
40401 10 228 Shutdown
Bitmap 2 Most Severe PC 3.x
Fault Status Coolant Pressure Sensor: Vtg Above PC 2.x,
40401 11 231 Warning
Bitmap 2 Normal PC 3.x
Fault Status Coolant Pressure Sensor: Vtg Below PC 2.x,
40401 12 232 Warning
Bitmap 2 Normal PC 3.x
Fault Status Engine Crankshaft Speed/Posn: PC 2.x,
40401 13 234 Shutdown
Bitmap 2 Above Normal PC 3.x
Fault Status Coolant Level: Below Normal-Most PC 2.x,
40401 14 235 Shutdown
Bitmap 2 Severe PC 3.x
Fault Status PC 2.x,
40401 15 238 Sensor Supply 3: Vtg Below Normal Warning
Bitmap 2 PC 3.x
Fault Status PC 2.x,
40402 0 239 Voltage Supply C High Error Warning
Bitmap 3 PC 3.x
Fault Status Radiator Fan Control Driver Low PC 2.x,
40402 1 245 Warning
Bitmap 3 Error PC 3.x

338 A029X159 (Issue 14)


10-2015 5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Addr. Bit# Name Fault Event Name Response Control


Code
Fault Status Engine Fuel Temp: Above Normal- PC 2.x,
40402 2 261 Warning
Bitmap 3 Moderately Severe PC 3.x
Fault Status Engine Fuel Temp Sensor 1: Vtg PC 2.x,
40402 3 263 Warning
Bitmap 3 Above Normal PC 3.x
Fault Status Engine Fuel Temp Sensor 1: Vtg PC 2.x,
40402 4 265 Warning
Bitmap 3 Below Normal PC 3.x
Fault Status Engine Fuel Temp: Above Normal- PC 2.x,
40402 5 266 Shutdown
Bitmap 3 Most severe PC 3.x
Fault Status Fuel Pump Pressurizing Assembly 1: PC 2.x,
40402 6 271 Warning
Bitmap 3 Vtg Below Normal PC 3.x
Fault Status Fuel Pump Pressurizing Assembly 1: PC 2.x,
40402 7 272 Warning
Bitmap 3 Vtg Above Normal PC 3.x
Fault Status APC_Diesel_CYL_PRS_IMBAL_Erro PC 2.x,
40402 8 281 Warning
Bitmap 3 r PC 3.x
Fault Status SAE J1939 Muxing PGN Timeout: PC 2.x,
40402 9 285 Warning
Bitmap 3 Abnormal Update Rate PC 3.x
Fault Status SAE J1939 Muxing Config: Out of PC 2.x,
40402 10 286 Warning
Bitmap 3 Calibration PC 3.x
Fault Status PC 2.x,
40402 13 295 Ambient_Air_Press_KeyOn_Error Warning
Bitmap 3 PC 3.x
Fault Status RTC PWR Intr: Data Erratic PC 2.x,
40402 14 319 Warning
Bitmap 3 Intermittent or Wrong PC 3.x
Fault Status Injector Solenoid Driver Cylinder 1: PC 2.x,
40402 15 322 Warning
Bitmap 3 UnderCurrent PC 3.x
Fault Status Injector Solenoid Driver Cylinder 5: PC 2.x,
40403 0 323 Warning
Bitmap 4 UnderCurrent PC 3.x
Fault Status Injector Solenoid Driver Cylinder 3: PC 2.x,
40403 1 324 Warning
Bitmap 4 UnderCurrent PC 3.x
Fault Status Injector Solenoid Driver Cylinder 6: PC 2.x,
40403 2 325 Warning
Bitmap 4 UnderCurrent PC 3.x
Fault Status Injector Solenoid Driver Cylinder 2: PC 2.x,
40403 3 331 Warning
Bitmap 4 UnderCurrent PC 3.x
Fault Status Injector Solenoid Driver Cylinder 4: PC 2.x,
40403 4 332 Warning
Bitmap 4 UnderCurrent PC 3.x
Fault Status Electronic Calibration Code: Out of PC 2.x,
40403 6 342 Shutdown
Bitmap 4 Calibration PC 3.x
Fault Status Eng Ctrl: internal h/w failure-Bad PC 2.x,
40403 7 343 Warning
Bitmap 4 Device/Component PC 3.x
Fault Status Injector Power Supply: Bad PC 2.x,
40403 8 351 Warning
Bitmap 4 Device/Component PC 3.x
Fault Status PC 2.x,
40403 9 352 Sensor Supply 1: Vtg Below Normal Warning
Bitmap 4 PC 3.x
Fault Status PC 2.x,
40403 10 359 Fail To Start Fault Shutdown
Bitmap 4 PC 3.x

A029X159 (Issue 14) 339


5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 10-2015

Addr. Bit# Name Fault Event Name Response Control


Code
Fault Status PC 2.x,
40403 11 386 Sensor Supply 1: Vtg Above Normal Warning
Bitmap 4 PC 3.x
Fault Status Eng Oil Rifle Pressure: Below PC 2.x,
40403 12 415 Shutdown
Bitmap 4 Normal-Most Severe PC 3.x
Fault Status Water in Fuel Indicator: Above PC 2.x,
40403 13 418 Warning
Bitmap 4 Normal-Least Severe PC 3.x
Fault Status Eng Oil Temp: Above Normal- PC 2.x,
40403 14 421 Warning
Bitmap 4 Moderately Severe PC 3.x
Fault Status PC 2.x,
40403 15 422 Coolant_Level_Reading_Incorrect Warning
Bitmap 4 PC 3.x
Fault Status PC 2.x,
40404 0 425 OIL_Temperature_In_Range_Error Warning
Bitmap 5 PC 3.x
Fault Status J1939 Datalink: Data PC 2.x,
40404 1 426 NONE
Bitmap 5 Erratic/Intermittent/Wrong PC 3.x
Fault Status PC 2.x,
40404 2 427 CAN Datalink Degraded Warning
Bitmap 5 PC 3.x
Fault Status PC 2.x,
40404 3 435 OIL_Pressure_Switch_Error Warning
Bitmap 5 PC 3.x
Fault Status PC 2.x,
40404 4 441 Low Battery Voltage Warning
Bitmap 5 PC 3.x
Fault Status PC 2.x,
40404 5 442 High Battery Voltage Warning
Bitmap 5 PC 3.x
Fault Status Injector Metering Rail 1 Pressure: PC 2.x,
40404 6 449 Shutdown
Bitmap 5 Above Normal PC 3.x
Fault Status Injector Metering Rail 1 Pressure: Vtg PC 2.x,
40404 7 451 Warning
Bitmap 5 Above Normal PC 3.x
Fault Status Injector Metering Rail 1 Pressure: Vtg PC 2.x,
40404 8 452 Warning
Bitmap 5 Below Normal PC 3.x
Fault Status Intake Manifold 1 Temp: Above PC 2.x,
40404 9 488 Derate
Bitmap 5 Normal-Moderate PC 3.x
Fault Status Fuel Delivery Pressure: Vtg Above PC 2.x,
40404 10 546 Warning
Bitmap 5 Normal PC 3.x
Fault Status Fuel Delivery Pressure: Vtg Below PC 2.x,
40404 11 547 Warning
Bitmap 5 Normal PC 3.x
Fault Status PC 2.x,
40404 12 553 APC_Diesel_High_PRS_Error Warning
Bitmap 5 PC 3.x
Fault Status PC 2.x,
40404 13 554 APC_DieselL_PRS_SIR_Error Warning
Bitmap 5 PC 3.x
Fault Status Injector Metering Rail 1 Pressure: PC 2.x,
40404 15 559 Warning
Bitmap 5 Below Normal PC 3.x
Fault Status Engine Shut Down Hot Condition PC 2.x,
40405 1 611 Warning
Bitmap 6 Exists PC 3.x
Fault Status PC 2.x,
40405 2 698 ECM Internal Temperature Low Error Warning
Bitmap 6 PC 3.x

340 A029X159 (Issue 14)


10-2015 5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Addr. Bit# Name Fault Event Name Response Control


Code
Fault Status PC 2.x,
40405 3 689 Eng Crankshaft Speed/Pos Warning Warning
Bitmap 6 PC 3.x
Fault Status Eng Speed: Cam/Crankshaft PC 2.x,
40405 4 731 Warning
Bitmap 6 Misalignment PC 3.x
Fault Status At Least One ACK: Most Severe PC 2.x,
40405 5 2661 Shutdown
Bitmap 6 Fault PC 3.x
Fault Status PC 2.x,
40405 6 781 CAN Datalink Failed Shutdown
Bitmap 6 PC 3.x
Fault Status PC 2.x,
40405 7 1117 Power Lost With Ignition On Warning
Bitmap 6 PC 3.x
Fault Status PC 2.x,
40405 8 1122 Rated to Idle Transition NONE
Bitmap 6 PC 3.x
Fault Status PC 2.x,
40405 9 1124 Delayed Shutdown Fault Warning
Bitmap 6 PC 3.x
Fault Status PC 2.x,
40405 10 1131 Battle Short Mode Active Warning
Bitmap 6 PC 3.x

40405 11 Fault Status 1132 Controlled Shutdown In Process Warning PC 3.x


Bitmap 6
Fault Status PC 2.x,
40405 13 1243 Engine Derate Derate
Bitmap 6 PC 3.x
Fault Status Shutdown PC 2.x,
40405 14 1244 Engine Normal Shutdown
Bitmap 6 w/Cooldown PC 3.x
Fault Status PC 2.x,
40405 15 1245 Engine Shutdown Shutdown
Bitmap 6 PC 3.x
Fault Status PC 2.x,
40406 0 1246 Unrecognized Engine Fault Warning
Bitmap 7 PC 3.x
Fault Status PC 2.x,
40406 1 1247 Engine Shutdown – Unannounced Shutdown
Bitmap 7 PC 3.x
Fault Status PC 2.x,
40406 2 1248 Engine Warning Warning
Bitmap 7 PC 3.x
Fault Status Ctrl Module ID Input State Warning PC 2.x,
40406 3 1256 Warning
Bitmap 7 Error PC 3.x
Fault Status Ctrl Module ID I/P State shutdown PC 2.x,
40406 4 1257 Shutdown
Bitmap 7 Error PC 3.x

40406 5 Fault Status 1322 kW Load Setpoint OOR High Warning PC 3.x
Bitmap 7

40406 6 Fault Status 1323 kW Load Setpoint OOR Low Warning PC 3.x
Bitmap 7

40406 7 Fault Status 1324 kVAR Load Setpoint OOR High Warning PC 3.x
Bitmap 7

40406 8 Fault Status 1325 kVAR Load Setpoint OOR Low Warning PC 3.x
Bitmap 7
Fault Status PC 2.x,
40406 9 1336 Cooldown Completed Fault Shutdown
Bitmap 7 PC 3.x

A029X159 (Issue 14) 341


5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 10-2015

Addr. Bit# Name Fault Event Name Response Control


Code
Fault Status Eng Oil Level Remote Reservoir: PC 2.x,
40406 10 1357 Warning
Bitmap 7 Below Normal PC 3.x
Fault Status Eng Oil Level Remote Reservoir: PC 2.x,
40406 11 219 Warning
Bitmap 7 Least Severe Level PC 3.x
Fault Status PC 2.x,
40406 12 233 HT Coolant Pressure Moderate Low Warning
Bitmap 7 PC 3.x
Fault Status PC 2.x,
40406 13 254 FSO NON Low Control Error Shutdown
Bitmap 7 PC 3.x
Fault Status PC 2.x,
40406 14 686 Turbo 1 Speed Incorrect Warning
Bitmap 7 PC 3.x
Fault Status PC 2.x,
40406 15 697 ECM Internal Temperature High Error Warning
Bitmap 7 PC 3.x
Fault Status PC 2.x,
40407 0 1376 Eng Camshaft Speed/Pos Warning Warning
Bitmap 8 PC 3.x

40407 1 Fault Status 3611 Custom Overcurrent Fault Warning PC 3.x


Bitmap 8

40407 2 Fault Status 3513 Negative Sequence Overcurrent Warning PC 3.x


Bitmap 8
Fault Status PC 2.x,
40407 3 1416 Fail to Shutdown Warning
Bitmap 8 PC 3.x
Fault Status PC 2.x,
40407 4 1417 Power Down Failure Warning
Bitmap 8 PC 3.x
Fault Status PC 2.x,
40407 5 1433 Local E-Stop Shutdown
Bitmap 8 PC 3.x
Fault Status PC 2.x,
40407 6 1434 Remote E-Stop Shutdown
Bitmap 8 PC 3.x
Fault Status PC 2.x,
40407 7 1435 Low Coolant Temperature Warning
Bitmap 8 PC 3.x
Fault Status PC 2.x,
40407 8 1438 Fail To Crank Fault Shutdown
Bitmap 8 PC 3.x
Fault Status PC 2.x,
40407 9 1439 Low Fuel in Day Tank Warning
Bitmap 8 PC 3.x
Fault Status PC 2.x,
40407 10 1441 Low Fuel Level Warning
Bitmap 8 PC 3.x
Fault Status PC 2.x,
40407 11 1442 Weak Battery Warning
Bitmap 8 PC 3.x
Fault Status PC 2.x,
40407 12 1443 Dead Battery Shutdown
Bitmap 8 PC 3.x
Fault Status PC 2.x,
40407 13 1444 Overload Warning
Bitmap 8 PC 3.x
Fault Status PC 2.x,
40407 14 1445 Short Circuit Shutdown
Bitmap 8 PC 3.x
Fault Status PC 2.x,
40407 15 1446 High AC Voltage Shutdown
Bitmap 8 PC 3.x

342 A029X159 (Issue 14)


10-2015 5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Addr. Bit# Name Fault Event Name Response Control


Code
Fault Status PC 2.x,
40408 0 1447 Low AC Voltage Shutdown
Bitmap 9 PC 3.x
Fault Status PC 2.x,
40408 1 1448 Underfrequency Shutdown
Bitmap 9 PC 3.x
Fault Status PC 2.x,
40408 2 1449 Overfrequency Warning
Bitmap 9 PC 3.x
Fault Status PC 2.x,
40408 3 1459 Reverse kW Shutdown
Bitmap 9 PC 3.x
Fault Status PC 2.x,
40408 4 1461 Loss of Field Shutdown
Bitmap 9 PC 3.x
Fault Status PC 2.x,
40408 5 1463 Not In Auto NONE
Bitmap 9 PC 3.x
Fault Status PC 2.x,
40408 6 1464 Load Dump Warning
Bitmap 9 PC 3.x
Fault Status PC 2.x,
40408 7 1465 Ready To Load NONE
Bitmap 9 PC 3.x
Fault Status PC 2.x,
40408 8 1469 Speed/Frequency Mismatch Fault Shutdown
Bitmap 9 PC 3.x
Fault Status PC 2.x,
40408 9 1471 High Current Warning Warning
Bitmap 9 PC 3.x
Fault Status PC 2.x,
40408 10 1472 Overcurrent Shutdown Shutdown
Bitmap 9 PC 3.x
Fault Status PC 2.x,
40408 11 1483 Common Alarm None
Bitmap 9 PC 3.x
Fault Status Injector Solenoid Driver Cylinder 7: PC 2.x,
40408 12 1548 Warning
Bitmap 9 UnderCurrent PC 3.x
Fault Status Injector Solenoid Driver Cylinder 8: PC 2.x,
40408 13 1549 Warning
Bitmap 9 UnderCurrent PC 3.x
Fault Status Injector Solenoid Driver Cylinder 10: PC 2.x,
40408 14 1551 Warning
Bitmap 9 UnderCurrent PC 3.x
Fault Status Injector Solenoid Driver Cylinder 11: PC 2.x,
40408 15 1552 Warning
Bitmap 9 UnderCurrent PC 3.x
Fault Status Injector Solenoid Driver Cylinder 12: PC 2.x,
40409 0 1553 Warning
Bitmap 10 UnderCurrent PC 3.x
Fault Status Injector Solenoid Driver Cylinder 13: PC 2.x,
40409 1 1554 Warning
Bitmap 10 UnderCurrent PC 3.x
Fault Status Injector Solenoid Driver Cylinder 14: PC 2.x,
40409 2 1555 Warning
Bitmap 10 UnderCurrent PC 3.x
Fault Status Injector Solenoid Driver Cylinder 15: PC 2.x,
40409 3 1556 Warning
Bitmap 10 UnderCurrent PC 3.x
Fault Status Injector Solenoid Driver Cylinder 16: PC 2.x,
40409 4 1557 Warning
Bitmap 10 UnderCurrent PC 3.x
Fault Status Injector Solenoid Driver Cylinder 9: PC 2.x,
40409 7 1622 Warning
Bitmap 10 UnderCurrent PC 3.x

A029X159 (Issue 14) 343


5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 10-2015

Addr. Bit# Name Fault Event Name Response Control


Code
Fault Status Real Time Clock Power Interrupt PC 2.x,
40409 8 1689 Warning
Bitmap 10 Fault PC 3.x
Fault Status Sensor_Supply_5_Voltage_High_Err PC 2.x,
40409 9 1695 Warning
Bitmap 10 or PC 3.x
Fault Status SENSOR_SUPPLY_5_VOLTAGE_L PC 2.x,
40409 10 1696 Warning
Bitmap 10 OW_ERROR PC 3.x
Fault Status Crankcase Pressure: Vtg Above PC 2.x,
40409 11 1843 Warning
Bitmap 10 Normal PC 3.x
Fault Status Crankcase Pressure: Vtg Below PC 2.x,
40409 12 1844 Warning
Bitmap 10 Normal PC 3.x
Fault Status Water in Fuel Indicator: Vtg Above PC 2.x,
40409 13 1845 Warning
Bitmap 10 Normal PC 3.x
Fault Status Water in Fuel Indicator: Vtg Below PC 2.x,
40409 14 1846 Warning
Bitmap 10 Normal PC 3.x
Fault Status Eng Coolant Temp - Shutdown Shutdown PC 2.x,
40409 15 1847
Bitmap 10 w/Cool w/Cooldown PC 3.x
Fault Status Water in Fuel Indicator: Above PC 2.x,
40410 0 1852 Warning
Bitmap 11 Normal-Moderate PC 3.x
Fault Status PC 2.x,
40410 1 1853 HMI113 Fault 1 NONE
Bitmap 11 PC 3.x
Fault Status PC 2.x,
40410 2 1854 HMI113 Fault 2 NONE
Bitmap 11 PC 3.x
Fault Status PC 2.x,
40410 3 1855 HMI113 Fault 3 NONE
Bitmap 11 PC 3.x
Fault Status PC 2.x,
40410 5 1891 Eng Oil Change Interval Warning
Bitmap 11 PC 3.x
Fault Status J39_EGR_Valve_Comm_Timeout_Er PC 2.x,
40410 6 1893 Warning
Bitmap 11 ror PC 3.x
Fault Status PC 2.x,
40410 7 1894 J39_VGT_Comm_Timeout_Error Warning
Bitmap 11 PC 3.x
Fault Status PC 2.x,
40410 8 1896 EGR_DL_Valve_Stuck_Error Warning
Bitmap 11 PC 3.x
Fault Status PC 2.x,
40410 9 1899 EGR_Delta_P_IR_Low_Error Warning
Bitmap 11 PC 3.x

40410 11 Fault Status 1912 Utility Loss Of Phase Warning PC 3.x


Bitmap 11

40410 12 Fault Status 1913 Genset Loss Of Phase Warning PC 3.x


Bitmap 11

40410 13 Fault Status 1914 Utility Phase Rotation Warning PC 3.x


Bitmap 11

40410 14 Fault Status 1915 Genset Phase Rotation Warning PC 3.x


Bitmap 11

40410 15 Fault Status 1916 Sync Check OK NONE PC 3.x


Bitmap 11

344 A029X159 (Issue 14)


10-2015 5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Addr. Bit# Name Fault Event Name Response Control


Code
Fault Status PC 2.x,
40411 0 1917 High Fuel Level Warning
Bitmap 12 PC 3.x
Fault Status PC 2.x,
40411 1 1918 Very Low Fuel Level Shutdown
Bitmap 12 PC 3.x
Fault Status PC 2.x,
40411 2 1933 EGR_DL_Voltage_High_Error Warning
Bitmap 12 PC 3.x
Fault Status PC 2.x,
40411 3 1934 EGR_DL_Voltage_Low_Error Warning
Bitmap 12 PC 3.x
Fault Status PC 2.x,
40411 4 1935 EGR_DL_Command_Source_Error Warning
Bitmap 12 PC 3.x
Fault Status PC 2.x,
40411 5 1942 Beyond_THD_AZ_Error Warning
Bitmap 12 PC 3.x
Fault Status PC 2.x,
40411 6 1943 CBR_Density_Detrat_Error_ID NONE
Bitmap 12 PC 3.x
Fault Status PC 2.x,
40411 7 1944 HMI113 Output Configuration Fault Warning
Bitmap 12 PC 3.x
Fault Status PC 2.x,
40411 8 1961 EGR_DL_EDU_TMPTR_High_Error Warning
Bitmap 12 PC 3.x
Fault Status Crankcase_Pressure_Least_Sev_Hig PC 2.x,
40411 9 1974 Warning
Bitmap 12 h PC 3.x
Fault Status Eng Crankshaft Speed/Posn: Above PC 2.x,
40411 10 1992 Shutdown
Bitmap 12 Normal PC 3.x

40411 11 Fault Status 1999 Maximum Parallel Time Warning PC 3.x


Bitmap 12
Fault Status PC 2.x,
40411 12 2185 Sensor Supply 4: Vtg Above Normal Warning
Bitmap 12 PC 3.x
Fault Status PC 2.x,
40411 13 2186 Sensor Supply 4: Vtg Below Normal Warning
Bitmap 12 PC 3.x
Fault Status Fuel Pump Delivery Pressure: Below PC 2.x,
40411 14 2215 Warning
Bitmap 12 Normal PC 3.x
Fault Status PC 2.x,
40411 15 2249 APC_Diesel_Low2_Prs_Error Warning
Bitmap 12 PC 3.x
Fault Status Fuel Pump Delivery Pressure: Above PC 2.x,
40412 0 2261 Warning
Bitmap 13 Normal PC 3.x
Fault Status PC 2.x,
40412 1 2262 Fuel Pump Delivery-Below Normal Warning
Bitmap 13 PC 3.x
Fault Status Electric Lift Pump for Eng Fuel: Vtg PC 2.x,
40412 2 2265 Warning
Bitmap 13 Above Normal PC 3.x
Fault Status Electric Lift Pump for Eng Fuel: Vtg PC 2.x,
40412 3 2266 Warning
Bitmap 13 Below Normal PC 3.x
Fault Status PC 2.x,
40412 4 2292 APC_Diesel_Flow_High_Error Warning
Bitmap 13 PC 3.x
Fault Status PC 2.x,
40412 5 2293 APC_Diesel_Flow_Low_Error Warning
Bitmap 13 PC 3.x

A029X159 (Issue 14) 345


5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 10-2015

Addr. Bit# Name Fault Event Name Response Control


Code
Fault Status Electronic Fuel Injection Control PC 2.x,
40412 6 2311 Warning
Bitmap 13 Valve PC 3.x

40412 7 Fault Status 2328 Utility Available NONE PC 3.x


Bitmap 13

40412 8 Fault Status 2331 Utility Undervoltage Warning PC 3.x


Bitmap 13

40412 9 Fault Status 2332 Utility Connected NONE PC 3.x


Bitmap 13

40412 10 Fault Status 2333 Genset Connected NONE PC 3.x


Bitmap 13
Fault Status Excitation/Loss of AC Voltage PC 2.x,
40412 11 2335 Shutdown
Bitmap 13 Sensing PC 3.x
Fault Status PC 2.x,
40412 13 2342 Too Long in Idle Warning
Bitmap 13 PC 3.x

40412 14 Fault Status 2358 Utility Overvoltage Warning PC 3.x


Bitmap 13
Fault Status PC 2.x,
40412 15 2377 Fan Control: Vtg Above Normal Warning
Bitmap 13 PC 3.x

40413 0 Fault Status 2396 Utility Breaker Fail To Close Warning PC 3.x
Bitmap 14

40413 1 Fault Status 2397 Utility Breaker Fail To Open Warning PC 3.x
Bitmap 14

40413 2 Fault Status 3226 Base Load NONE PC 3.x


Bitmap 14

40413 3 Fault Status 3227 Peak Shave NONE PC 3.x


Bitmap 14
Fault Status PC 2.x,
40413 4 2555 GHC_Low_Voltage_Error_1 Warning
Bitmap 14 PC 3.x
Fault Status PC 2.x,
40413 5 2556 GHC_High_Voltage_Error_1 Warning
Bitmap 14 PC 3.x
Fault Status PC 2.x,
40413 6 2678 Charging Alternator Failure Fault Warning
Bitmap 14 PC 3.x

40413 7 Fault Status 2965 Genset Available NONE PC 3.x


Bitmap 14
Fault Status PC 2.x,
40413 8 2971 Test/Exercise is Active Fault NONE
Bitmap 14 PC 3.x
Fault Status PC 2.x,
40413 9 2972 Field Overload Shutdown
Bitmap 14 PC 3.x
Fault Status PC 2.x,
40413 10 2973 Charge_Press_IR_Error Warning
Bitmap 14 PC 3.x
Fault Status PC 2.x,
40413 11 2943 Manual Switch Configuration Fault Warning
Bitmap 14 PC 3.x
Fault Status PC 2.x,
40413 12 2944 Auto Switch Configuration Fault Warning
Bitmap 14 PC 3.x

346 A029X159 (Issue 14)


10-2015 5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Addr. Bit# Name Fault Event Name Response Control


Code
Fault Status PC 2.x,
40413 13 2914 Genset AC Meter Failed Shutdown
Bitmap 14 PC 3.x

40413 14 Fault Status 2915 Genset Bus AC Meter Failed Warning PC 3.x
Bitmap 14

40413 15 Fault Status 2916 Utility AC Meter Failed Warning PC 3.x


Bitmap 14
Fault Status PC 2.x,
40414 0 2814 Genset CT Ratio Too Small Shutdown
Bitmap 15 PC 3.x
Fault Status PC 2.x,
40414 1 2815 Genset CT Ratio Too Large Warning
Bitmap 15 PC 3.x
Fault Status PC 2.x,
40414 2 2816 Genset PT Ratio Too Small Shutdown
Bitmap 15 PC 3.x
Fault Status PC 2.x,
40414 3 2817 Genset PT Ratio Too Large Warning
Bitmap 15 PC 3.x

40414 4 Fault Status 2818 Genset Bus PT Ratio Too Small Shutdown PC 3.x
Bitmap 15

40414 5 Fault Status 2819 Genset Bus PT Ratio Too Large Warning PC 3.x
Bitmap 15

40414 6 Fault Status 2821 Utility PT Ratio Too Small Shutdown PC 3.x
Bitmap 15

40414 7 Fault Status 2822 Utility PT Ratio Too Large Warning PC 3.x
Bitmap 15
Fault Status PC 2.x,
40414 8 2619 Aux101 0 Input 1 Fault Warning
Bitmap 15 PC 3.x
Fault Status PC 2.x,
40414 9 2621 Aux101 0 Input 2 Fault Warning
Bitmap 15 PC 3.x
Fault Status PC 2.x,
40414 10 2622 Aux101 0 Input 3 Fault Warning
Bitmap 15 PC 3.x
Fault Status PC 2.x,
40414 11 2623 Aux101 0 Input 4 Fault Warning
Bitmap 15 PC 3.x
Fault Status PC 2.x,
40414 12 2624 Aux101 0 Input 5 Fault Warning
Bitmap 15 PC 3.x
Fault Status PC 2.x,
40414 13 2625 Aux101 0 Input 6 Fault Warning
Bitmap 15 PC 3.x
Fault Status PC 2.x,
40414 14 2626 Aux101 0 Input 7 Fault Warning
Bitmap 15 PC 3.x
Fault Status PC 2.x,
40414 15 2627 Aux101 0 Input 8 Fault Warning
Bitmap 15 PC 3.x
Fault Status PC 2.x,
40415 0 2882 Aux101 1 Input 1 Fault Warning
Bitmap 16 PC 3.x
Fault Status PC 2.x,
40415 1 2883 Aux101 1 Input 2 Fault Warning
Bitmap 16 PC 3.x
Fault Status PC 2.x,
40415 2 2884 Aux101 1 Input 3 Fault Warning
Bitmap 16 PC 3.x

A029X159 (Issue 14) 347


5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 10-2015

Addr. Bit# Name Fault Event Name Response Control


Code
Fault Status PC 2.x,
40415 3 2885 Aux101 1 Input 4 Fault Warning
Bitmap 16 PC 3.x
Fault Status PC 2.x,
40415 4 2886 Aux101 1 Input 5 Fault Warning
Bitmap 16 PC 3.x
Fault Status PC 2.x,
40415 5 2887 Aux101 1 Input 6 Fault Warning
Bitmap 16 PC 3.x
Fault Status PC 2.x,
40415 6 2888 Aux101 1 Input 7 Fault Warning
Bitmap 16 PC 3.x
Fault Status PC 2.x,
40415 7 2889 Aux101 1 Input 8 Fault Warning
Bitmap 16 PC 3.x
Fault Status PC 2.x,
40415 8 2628 Aux102 0 Expansion Input 9 Fault Warning
Bitmap 16 PC 3.x
Fault Status PC 2.x,
40415 9 2629 Aux102 0 Expansion Input 10 Fault Warning
Bitmap 16 PC 3.x
Fault Status PC 2.x,
40415 10 2631 Aux102 0 Expansion Input 11 Fault Warning
Bitmap 16 PC 3.x
Fault Status PC 2.x,
40415 11 2632 Aux102 0 Expansion Input 12 Fault Warning
Bitmap 16 PC 3.x
Fault Status PC 2.x,
40415 12 2891 Aux102 1 Expansion Input 9 Fault Warning
Bitmap 16 PC 3.x
Fault Status PC 2.x,
40415 13 2892 Aux102 1 Expansion Input 10 Fault Warning
Bitmap 16 PC 3.x
Fault Status PC 2.x,
40415 14 2893 Aux102 1 Expansion Input 11 Fault Warning
Bitmap 16 PC 3.x
Fault Status PC 2.x,
40415 15 2894 Aux102 1 Expansion Input 12 Fault Warning
Bitmap 16 PC 3.x
Fault Status PC 2.x,
40416 0 2895 PCCnet Device Failed Warning Warning
Bitmap 17 PC 3.x
Fault Status PC 2.x,
40416 1 2896 PCCnet Device Failed Shutdown Shutdown
Bitmap 17 PC 3.x

40416 2 Fault Status 2917 Genset Bus Voltage OOR Warning Warning PC 3.x
Bitmap 17

40416 3 Fault Status 2918 Utility Voltage OOR Warning Warning PC 3.x
Bitmap 17

40416 4 Fault Status 2919 Utility Current OOR Warning Warning PC 3.x
Bitmap 17

40416 5 Fault Status 2921 Genset Bus Current OOR Warning Warning PC 3.x
Bitmap 17

40416 6 Fault Status 2922 Genset Neutral Current OOR Warning PC 3.x
Bitmap 17 Warning

40416 7 Fault Status 2923 Genset Bus kW OOR Warning Warning PC 3.x
Bitmap 17

40416 8 Fault Status 2924 Genset Bus kVAR OOR Warning Warning PC 3.x
Bitmap 17

348 A029X159 (Issue 14)


10-2015 5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Addr. Bit# Name Fault Event Name Response Control


Code

40416 9 Fault Status 2925 Genset Bus kVA OOR Warning Warning PC 3.x
Bitmap 17

40416 10 Fault Status 2926 Utility kW OOR Warning Warning PC 3.x


Bitmap 17

40416 11 Fault Status 2927 Utility kVAR OOR Warning Warning PC 3.x
Bitmap 17

40416 12 Fault Status 2928 Utility kVA OOR Warning Warning PC 3.x
Bitmap 17

40416 13 Fault Status 3599 Ground Current OOR Warning Warning PC 3.x
Bitmap 17
Fault Status PC 2.x,
40416 14 2931 AUX101 Device ID Fault Shutdown
Bitmap 17 PC 3.x

40416 15 Fault Status 2779 Utility Unloaded Event NONE PC 3.x


Bitmap 17
Fault Status PC 2.x,
40417 3 2932 AUX101 Oil Temp OOR Hi Warning
Bitmap 18 PC 3.x
Fault Status PC 2.x,
40417 4 2933 AUX101 Oil Temp OOR Low Warning
Bitmap 18 PC 3.x
Fault Status PC 2.x,
40417 5 2657 Exhaust Stack Temp 1 OOR High Warning
Bitmap 18 PC 3.x
Fault Status PC 2.x,
40417 6 2947 Exhaust Stack Temp 1 OOR Low Warning
Bitmap 18 PC 3.x
Fault Status PC 2.x,
40417 7 2949 High Exhaust Stack Temperature 1 Warning
Bitmap 18 PC 3.x
Fault Status PC 2.x,
40417 8 2653 Exhaust Stack Temp 2 OOR High Warning
Bitmap 18 PC 3.x
Fault Status PC 2.x,
40417 9 2946 Exhaust Stack Temp 2 OOR Low Warning
Bitmap 18 PC 3.x
Fault Status PC 2.x,
40417 10 2948 High Exhaust Stack Temperature 2 Warning
Bitmap 18 PC 3.x
Fault Status PC 2.x,
40417 11 2934 Ambient Temp OOR High Warning
Bitmap 18 PC 3.x
Fault Status PC 2.x,
40417 12 2935 Ambient Temp OOR Low Warning
Bitmap 18 PC 3.x
Fault Status PC 2.x,
40417 13 2936 Fuel Level OOR High Warning
Bitmap 18 PC 3.x
Fault Status PC 2.x,
40417 14 2937 Fuel Level OOR Low Warning
Bitmap 18 PC 3.x
Fault Status PC 2.x,
40417 15 2951 Alternator Temp 1 OOR High Warning
Bitmap 18 PC 3.x
Fault Status PC 2.x,
40418 0 2952 Alternator Temp 1 OOR Low Warning
Bitmap 19 PC 3.x
Fault Status PC 2.x,
40418 1 2953 High Alternator Temp 1 Warning
Bitmap 19 PC 3.x

A029X159 (Issue 14) 349


5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 10-2015

Addr. Bit# Name Fault Event Name Response Control


Code
Fault Status PC 2.x,
40418 2 2954 Alternator Temp 2 OOR High Warning
Bitmap 19 PC 3.x
Fault Status PC 2.x,
40418 3 2955 Alternator Temp 2 OOR Low Warning
Bitmap 19 PC 3.x
Fault Status PC 2.x,
40418 4 2956 High Alternator Temp 2 Warning
Bitmap 19 PC 3.x
Fault Status PC 2.x,
40418 5 2957 Alternator Temp 3 OOR High Warning
Bitmap 19 PC 3.x
Fault Status PC 2.x,
40418 6 2958 Alternator Temp 3 OOR Low Warning
Bitmap 19 PC 3.x
Fault Status PC 2.x,
40418 7 2959 High Alternator Temp 3 Warning
Bitmap 19 PC 3.x
Fault Status PC 2.x,
40418 8 2992 Intake Manifold Temp 1 OOR High Warning
Bitmap 19 PC 3.x
Fault Status PC 2.x,
40418 9 2978 Intake Manifold Temp 1 OOR Low Warning
Bitmap 19 PC 3.x
Fault Status PC 2.x,
40418 10 2981 Drive End Bearing Temp OOR High Warning
Bitmap 19 PC 3.x
Fault Status PC 2.x,
40418 11 2982 Drive End Bearing Temp OOR Low Warning
Bitmap 19 PC 3.x
Fault Status PC 2.x,
40418 12 2983 High Drive End Bearing Temperature Warning
Bitmap 19 PC 3.x
Fault Status Non-Drive End Bearing Temp OOR PC 2.x,
40418 13 2984 Warning
Bitmap 19 High PC 3.x
Fault Status Non-Drive End Bearing Temp OOR PC 2.x,
40418 14 2985 Warning
Bitmap 19 Low PC 3.x
Fault Status High Non-Drive End Bearing PC 2.x,
40418 15 2986 Warning
Bitmap 19 Temperature PC 3.x
Fault Status PC 2.x,
40419 0 2945 Rupture Basin Warning
Bitmap 20 PC 3.x
Fault Status PC 2.x,
40419 1 2979 High Alternator Temp Switch fault Warning
Bitmap 20 PC 3.x
Fault Status PC 2.x,
40419 2 2993 Battery Charger Failed Fault Warning
Bitmap 20 PC 3.x
Fault Status PC 2.x,
40419 3 2938 Earth/Ground Fault Warning
Bitmap 20 PC 3.x
Fault Status PC 2.x,
40419 4 2939 Modbus Failure Fault Warning
Bitmap 20 PC 3.x
Fault Status PC 2.x,
40419 5 2977 Low Coolant Level #2 Warning
Bitmap 20 PC 3.x
Fault Status PC 2.x,
40419 6 1978 Speed Bias OOR High Warning
Bitmap 20 PC 3.x
Fault Status PC 2.x,
40419 7 2541 Voltage Bias OOR Low Warning
Bitmap 20 PC 3.x

350 A029X159 (Issue 14)


10-2015 5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Addr. Bit# Name Fault Event Name Response Control


Code
Fault Status PC 2.x,
40419 8 2539 Voltage Bias OOR High Warning
Bitmap 20 PC 3.x
Fault Status PC 2.x,
40419 9 1573 Configurable Input #1 NONE
Bitmap 20 PC 3.x
Fault Status PC 2.x,
40419 10 1312 Configurable Input #2 NONE
Bitmap 20 PC 3.x
Fault Status PC 2.x,
40419 11 1317 Configurable Input #13 NONE
Bitmap 20 PC 3.x
Fault Status PC 2.x,
40419 12 1318 Configurable Input #14 NONE
Bitmap 20 PC 3.x
Fault Status PC 2.x,
40419 13 1979 Speed Bias OOR Low Warning
Bitmap 20 PC 3.x
Fault Status Both Engine Speed Signals Lost: PC 2.x,
40419 14 236 Shutdown
Bitmap 20 Most Severe Level PC 3.x

40419 15 Fault Status 3629 Less Severe Response-Warning Warning PC 3.x


Bitmap 20

40420 0 Fault Status 3631 Most Severe-Shutdown Shutdown PC 3.x


Bitmap 21

40427 1 Fault Status 4872 System Network Failure Warning PC 3.x


Bitmap 26

40427 2 Fault Status 4873 Genset Failed to Come Online Warning PC 3.x
Bitmap 26

40427 3 Fault Status 4874 Load Demand SW Version Warning PC 3.x


Bitmap 26 Incompatibility

40427 4 Fault Status 4875 Genset Ineligible for Load Demand None PC 3.x
Bitmap 26

40427 5 Fault Status 4876 Genset Lost on System Network Warning PC 3.x
Bitmap 26

40427 6 Fault Status 4877 System Settings Not Synchronized Warning PC 3.x
Bitmap 26

40427 7 Fault Status 4878 Check System Network Installation Warning PC 3.x
Bitmap 26

40427 8 Fault Status 4879 Load Demand Setup Error Warning PC 3.x
Bitmap 26

40427 9 Fault Status 4881 System Genset ID Conflict Warning PC 3.x


Bitmap 26

40427 10 Fault Status 4882 Genset Bus Overload Warning PC 3.x


Bitmap 26

40427 11 Fault Status 5145 Load Demand Genset Bus Failure Warning PC 3.x
Bitmap 26
Event Status PC 2.x,
40430 0 1540 Common Warning NONE
Bitmap 1 PC 3.x
Event Status PC 2.x,
40430 1 1541 Common Shutdown NONE
Bitmap 1 PC 3.x

40431 0 Fault Status Gas 121 EPS Main Channel Lost Error Warning PC 3.x
Bitmap 1

A029X159 (Issue 14) 351


5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 10-2015

Addr. Bit# Name Fault Event Name Response Control


Code

40431 1 Fault Status Gas 136 Oil Inlet Pressure High Error Warning PC 3.x
Bitmap 1

40431 2 Fault Status Gas 137 Oil Inlet Pressure Low Error Warning PC 3.x
Bitmap 1

40431 3 Fault Status Gas 142 Oil Overpressure Error Warning PC 3.x
Bitmap 1

40431 4 Fault Status Gas 156 Intake Manifold Temp 2 OORH Warning PC 3.x
Bitmap 1

40431 5 Fault Status Gas 157 Intake Manifold Temp 2 OORL Warning PC 3.x
Bitmap 1

40431 6 Fault Status Gas 158 Intake Manifold Temp 2 High Shutdown PC 3.x
Bitmap 1

40431 7 Fault Status Gas 159 Intake Manifold 3 Temp OORH Warning PC 3.x
Bitmap 1

40431 8 Fault Status Gas 161 Intake Manifold 3 Temp OORL Warning PC 3.x
Bitmap 1

40431 9 Fault Status Gas 162 Intake Manifold 3 Temp High Shutdown PC 3.x
Bitmap 1

40431 10 Fault Status Gas 163 Intake Manifold 4 Temp OORH Warning PC 3.x
Bitmap 1

40431 11 Fault Status Gas 164 Intake Manifold 4 Temp OORL Warning PC 3.x
Bitmap 1

40431 12 Fault Status Gas 165 Intake Manifold 4 Temp High Shutdown PC 3.x
Bitmap 1

40431 13 Fault Status Gas 175 Throttle_Driver_Feedback_High_Erro Shutdown PC 3.x


Bitmap 1 r w/Cooldown

40431 14 Fault Status Gas 176 Throttle_Driver_Feedback_Low_Error Shutdown PC 3.x


Bitmap 1 w/Cooldown

40431 15 Fault Status Gas 177 Throttle_Actuator_Error Shutdown PC 3.x


Bitmap 1 w/Cooldown

40432 2 Fault Status Gas 244 Red Stop Lamp Driver OORL Warning PC 3.x
Bitmap 2

40432 3 Fault Status Gas 246 Exhaust Gas Temp Sensor 1 OORH Warning PC 3.x
Bitmap 2

40432 4 Fault Status Gas 247 Exhaust Gas Temp Sensor 1 OORL Warning PC 3.x
Bitmap 2

40432 5 Fault Status Gas 248 Exhaust Gas Temp Sensor 1 High Warning PC 3.x
Bitmap 2

40432 6 Fault Status Gas 253 Oil Level Low Error Shutdown PC 3.x
Bitmap 2 w/Cooldown

40432 8 Fault Status Gas 277 Fuel Control Valve Out of Adj Warning PC 3.x
Bitmap 2

40432 9 Fault Status Gas 346 Powerdown Data Lost Error Warning PC 3.x
Bitmap 2

40432 10 Fault Status Gas 354 Manifold_Absolute_Pressure_1_High Warning PC 3.x


Bitmap 2 _Error

40432 11 Fault Status Gas 355 Manifold_Absolute_Pressure_1_Low Warning PC 3.x


Bitmap 2 _Error

352 A029X159 (Issue 14)


10-2015 5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Addr. Bit# Name Fault Event Name Response Control


Code

40432 12 Fault Status Gas 412 J1708 Link Cannot Transmit Error NONE PC 3.x
Bitmap 2

40432 13 Fault Status Gas 414 J1708 Link Not Fast Enough Error NONE PC 3.x
Bitmap 2

40432 14 Fault Status Gas 453 Gas_Mass_Flow_High_Error Warning PC 3.x


Bitmap 2

40432 15 Fault Status Gas 454 Gas_Mass_Flow_Low_Error Warning PC 3.x


Bitmap 2

40433 0 Fault Status Gas 458 Spark_Timing_B_Error Shutdown PC 3.x


Bitmap 3 w/Cooldown

40433 1 Fault Status Gas 459 Spark_Timing_A_Error Shutdown PC 3.x


Bitmap 3 w/Cooldown

40433 2 Fault Status Gas 461 Spark_Reference_B_Error Shutdown PC 3.x


Bitmap 3 w/Cooldown

40433 3 Fault Status Gas 462 Spark_Reference_A_Error Shutdown PC 3.x


Bitmap 3 w/Cooldown

40433 4 Fault Status Gas 477 Isolated Battery Voltage Low Error Warning PC 3.x
Bitmap 3

40433 5 Fault Status Gas 478 Isolated Battery Voltage High Error Warning PC 3.x
Bitmap 3

40433 6 Fault Status Gas 512 Throttle Pos 1 Feedback OOR High Warning PC 3.x
Bitmap 3

40433 7 Fault Status Gas 513 Throttle Pos 1 Feedback OOR Low Warning PC 3.x
Bitmap 3

40433 8 Fault Status Gas 557 Fuel Control Valve 2 OORH Shutdown PC 3.x
Bitmap 3 w/Cooldown

40433 9 Fault Status Gas 558 Fuel Control Valve 2 OORL Warning PC 3.x
Bitmap 3

40433 10 Fault Status Gas 561 Heavy_Knock_Error_1_(A1) Shutdown PC 3.x


Bitmap 3 w/Cooldown

40433 11 Fault Status Gas 562 Heavy_Knock_Error_2_(B1) Shutdown PC 3.x


Bitmap 3 w/Cooldown

40433 12 Fault Status Gas 563 Heavy_Knock_Error_3_(A2) Shutdown PC 3.x


Bitmap 3 w/Cooldown

40433 13 Fault Status Gas 564 Heavy_Knock_Error_4_(B2) Shutdown PC 3.x


Bitmap 3 w/Cooldown

40433 14 Fault Status Gas 565 Heavy_Knock_Error_5_(A3) Shutdown PC 3.x


Bitmap 3 w/Cooldown

40433 15 Fault Status Gas 566 Heavy_Knock_Error_6_(B3) Shutdown PC 3.x


Bitmap 3 w/Cooldown

40434 0 Fault Status Gas 567 Heavy_Knock_Error_7_(A4) Shutdown PC 3.x


Bitmap 4 w/Cooldown

40434 1 Fault Status Gas 568 Heavy_Knock_Error_8_(B4) Shutdown PC 3.x


Bitmap 4 w/Cooldown

40434 2 Fault Status Gas 569 Heavy_Knock_Error_9_(A5) Shutdown PC 3.x


Bitmap 4 w/Cooldown

40434 3 Fault Status Gas 571 Knock Cyl 1 (A1) OORL Warning PC 3.x
Bitmap 4

A029X159 (Issue 14) 353


5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 10-2015

Addr. Bit# Name Fault Event Name Response Control


Code

40434 4 Fault Status Gas 572 Knock Cyl 2 (B1) OORL Warning PC 3.x
Bitmap 4

40434 5 Fault Status Gas 573 Knock Cyl 3 (A2) OORL Warning PC 3.x
Bitmap 4

40434 6 Fault Status Gas 574 Knock Cyl 4 (B2) OORL Warning PC 3.x
Bitmap 4

40434 7 Fault Status Gas 575 Knock Cyl 5 (A3) OORL Warning PC 3.x
Bitmap 4

40434 8 Fault Status Gas 576 Knock Cyl 6 (B3) OORL Warning PC 3.x
Bitmap 4

40434 9 Fault Status Gas 577 Knock Cyl 7 (A4) OORL Warning PC 3.x
Bitmap 4

40434 10 Fault Status Gas 578 Knock Cyl 8 (B4) OORL Warning PC 3.x
Bitmap 4

40434 11 Fault Status Gas 579 Knock Cyl 9 (A5) OORL Warning PC 3.x
Bitmap 4

40434 12 Fault Status Gas 584 High Side DRV3 High Control Error Warning PC 3.x
Bitmap 4

40434 13 Fault Status Gas 585 High Side DRV3 Low Control Error Warning PC 3.x
Bitmap 4

40434 14 Fault Status Gas 591 Exhaust_Backpressure_High_Error Warning PC 3.x


Bitmap 4

40434 15 Fault Status Gas 592 Exhaust_Backpressure_Low_Error Warning PC 3.x


Bitmap 4

40435 0 Fault Status Gas 595 Turbo 1 Overspeed Warning Error Warning PC 3.x
Bitmap 5

40435 1 Fault Status Gas 618 Turbo 1 Inlet Pressure High Warning PC 3.x
Bitmap 5

40435 2 Fault Status Gas 619 Turbo 2 Inlet Press High Warning PC 3.x
Bitmap 5

40435 3 Fault Status Gas 641 Exhaust Temp 1 (A1) High Serious Shutdown PC 3.x
Bitmap 5 Error w/Cooldown

40435 4 Fault Status Gas 642 Exhaust Temp 3 (A2) High Serious Shutdown PC 3.x
Bitmap 5 Error w/Cooldown

40435 5 Fault Status Gas 643 Exhaust Temp 5 (A3) High Serious Shutdown PC 3.x
Bitmap 5 Error w/Cooldown

40435 6 Fault Status Gas 644 Exhaust Temp 7 (A4) High Serious Shutdown PC 3.x
Bitmap 5 Error w/Cooldown

40435 7 Fault Status Gas 645 Exhaust Temp 9 (A5) High Serious Shutdown PC 3.x
Bitmap 5 Error w/Cooldown

40435 8 Fault Status Gas 646 Exhaust Temp 11 (A6) High Serious Shutdown PC 3.x
Bitmap 5 Error w/Cooldown

40435 9 Fault Status Gas 647 Exhaust Temp 13 (A7) High Serious Shutdown PC 3.x
Bitmap 5 Error w/Cooldown

40435 10 Fault Status Gas 648 Exhaust Temp 15 (A8) High Serious Shutdown PC 3.x
Bitmap 5 Error w/Cooldown

40435 11 Fault Status Gas 651 Exhaust Temp 17 (A9) High Serious Shutdown PC 3.x
Bitmap 5 Error w/Cooldown

354 A029X159 (Issue 14)


10-2015 5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Addr. Bit# Name Fault Event Name Response Control


Code

40435 12 Fault Status Gas 652 Exhaust Temp 2 (B1) High Serious Shutdown PC 3.x
Bitmap 5 Error w/Cooldown

40435 13 Fault Status Gas 653 Exhaust Temp 4 (B2) High Serious Shutdown PC 3.x
Bitmap 5 Error w/Cooldown

40435 14 Fault Status Gas 654 Exhaust Temp 6 (B3) High Serious Shutdown PC 3.x
Bitmap 5 Error w/Cooldown

40435 15 Fault Status Gas 655 Exhaust Temp 8 (B4) High Serious Shutdown PC 3.x
Bitmap 5 Error w/Cooldown

40436 0 Fault Status Gas 656 Exhaust Temp 10 (B5) High Serious Shutdown PC 3.x
Bitmap 6 Error w/Cooldown

40436 1 Fault Status Gas 657 Exhaust Temp 12 (B6) High Serious Shutdown PC 3.x
Bitmap 6 Error w/Cooldown

40436 2 Fault Status Gas 658 Exhaust Temp 14 (B7) High Serious Shutdown PC 3.x
Bitmap 6 Error w/Cooldown

40436 3 Fault Status Gas 671 Exhaust Gas Temp Cyl 1 (A1) OORL Warning PC 3.x
Bitmap 6

40436 4 Fault Status Gas 672 Exhaust Gas Temp Cyl 3 (A2) OORL Warning PC 3.x
Bitmap 6

40436 5 Fault Status Gas 673 Exhaust Gas Temp Cyl 5 (A3) OORL Warning PC 3.x
Bitmap 6

40436 6 Fault Status Gas 674 Exhaust Gas Temp Cyl 7 (A4) OORL Warning PC 3.x
Bitmap 6

40436 7 Fault Status Gas 675 Exhaust Gas Temp Cyl 9 (A5) OORL Warning PC 3.x
Bitmap 6

40436 8 Fault Status Gas 676 Exhaust Gas Temp Cyl 11 (A6) Warning PC 3.x
Bitmap 6 OORL

40436 9 Fault Status Gas 677 Exhaust Gas Temp Cyl 13 (A7) Warning PC 3.x
Bitmap 6 OORL

40436 10 Fault Status Gas 678 Exhaust Gas Temp Cyl 15 (A8) Warning PC 3.x
Bitmap 6 OORL

40436 11 Fault Status Gas 683 Turbo 2 Speed Moderate High Warning PC 3.x
Bitmap 6

40436 12 Fault Status Gas 684 Turbo 2 Speed Moderate Low Warning PC 3.x
Bitmap 6

40436 13 Fault Status Gas 685 Turbo 2 Speed Incorrect Warning PC 3.x
Bitmap 6

40436 15 Fault Status Gas 687 Turbo 1 Speed Low Warning PC 3.x
Bitmap 6

40437 2 Fault Status Gas 721 Exhaust Gas Temp 2 (B1) OORL Warning PC 3.x
Bitmap 7

40437 3 Fault Status Gas 722 Exhaust Gas Temp 4 (B2) OORL Warning PC 3.x
Bitmap 7

40437 4 Fault Status Gas 723 Exhaust Gas Temp 6 (B3) OORL Warning PC 3.x
Bitmap 7

40437 5 Fault Status Gas 724 Exhaust Gas Temp 8 (B4) OORL Warning PC 3.x
Bitmap 7

40437 6 Fault Status Gas 725 Exhaust Gas Temp 10 (B5) OORL Warning PC 3.x
Bitmap 7

A029X159 (Issue 14) 355


5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 10-2015

Addr. Bit# Name Fault Event Name Response Control


Code

40437 7 Fault Status Gas 726 Exhaust Gas Temp 12 (B6) OORL Warning PC 3.x
Bitmap 7

40437 8 Fault Status Gas 727 Exhaust Gas Temp 14 (B7) OORL Warning PC 3.x
Bitmap 7

40437 9 Fault Status Gas 728 Exhaust Gas Temp 16 (B8) OORL Warning PC 3.x
Bitmap 7

40437 10 Fault Status Gas 736 Starter Air Pressure OORL Warning PC 3.x
Bitmap 7

40437 11 Fault Status Gas 737 Starter Air Pressure OORH Warning PC 3.x
Bitmap 7

40437 12 Fault Status Gas 738 Starter Air Press Underpressure Warning PC 3.x
Bitmap 7 Error

40437 13 Fault Status Gas 741 Air Filter Restriction Pressure High Warning PC 3.x
Bitmap 7 Error

40437 14 Fault Status Gas 742 Air Filter Restriction Pressure Low Warning PC 3.x
Bitmap 7 Error

40437 15 Fault Status Gas 751 Gas_Mass_Flow_In_Range_Error Warning PC 3.x


Bitmap 7

40438 0 Fault Status Gas 752 Exhaust_Gas_Oxygen_In_Range_Err Warning PC 3.x


Bitmap 8 or

40438 1 Fault Status Gas 783 Intake Manifold 1 Temp Abnormal Shutdown PC 3.x
Bitmap 8 w/Cooldown

40438 2 Fault Status Gas 1213 COP_Overboost_Error Shutdown PC 3.x


Bitmap 8 w/Cooldown

40438 3 Fault Status Gas 1274 Heavy_Knock_Error_10_(B5) Shutdown PC 3.x


Bitmap 8 w/Cooldown

40438 4 Fault Status Gas 1281 Heavy_Knock_Error_12_(B6) Shutdown PC 3.x


Bitmap 8 w/Cooldown

40438 5 Fault Status Gas 1285 Continuous_Light_Knock_Error_13_( Shutdown PC 3.x


Bitmap 8 A7) w/Cooldown

40438 6 Fault Status Gas 1286 Heavy_Knock_Error_13_(A7) Shutdown PC 3.x


Bitmap 8 w/Cooldown

40438 7 Fault Status Gas 1291 Heavy_Knock_Error_14_(B7) Shutdown PC 3.x


Bitmap 8 w/Cooldown

40438 8 Fault Status Gas 1295 Continuous_Light_Knock_Error_15_( Shutdown PC 3.x


Bitmap 8 A8) w/Cooldown

40438 9 Fault Status Gas 1296 Heavy_Knock_Error_15_(A8) Shutdown PC 3.x


Bitmap 8 w/Cooldown

40438 10 Fault Status Gas 1311 Heavy_Knock_Error_18_(B9) Shutdown PC 3.x


Bitmap 8 w/Cooldown

40438 11 Fault Status Gas 1362 Oil Filter Restriction Error Warning PC 3.x
Bitmap 8

40438 12 Fault Status Gas 1452 Genset Breaker Fail To Close Shutdown PC 3.x
Bitmap 8

40438 13 Fault Status Gas 1457 Fail To Synchronize Warning PC 3.x


Bitmap 8

40438 14 Fault Status Gas 1458 Sync Phase Rotation Mismatch Warning PC 3.x
Bitmap 8

356 A029X159 (Issue 14)


10-2015 5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Addr. Bit# Name Fault Event Name Response Control


Code

40438 15 Fault Status Gas 1474 ECM Software mismatch Shutdown PC 3.x
Bitmap 8 w/Cooldown

40439 0 Fault Status Gas 1521 Exhaust Gas Temp 3 (A2) OORH Warning PC 3.x
Bitmap 9

40439 1 Fault Status Gas 1522 Exhaust Gas Temp 5 (A3) OORH Warning PC 3.x
Bitmap 9

40439 2 Fault Status Gas 1523 Exhaust Gas Temp 7 (A4) OORH Warning PC 3.x
Bitmap 9

40439 3 Fault Status Gas 1524 Exhaust Gas Temp 9 (A5) OORH Warning PC 3.x
Bitmap 9

40439 4 Fault Status Gas 1525 Exhaust Gas Temp 11 (A6) OORH Warning PC 3.x
Bitmap 9

40439 5 Fault Status Gas 1526 Exhaust Gas Temp 13 (A7) OORH Warning PC 3.x
Bitmap 9

40439 6 Fault Status Gas 1527 Exhaust Gas Temp 15 (A8) OORH Warning PC 3.x
Bitmap 9

40439 7 Fault Status Gas 1528 Exhaust Gas Temp 17 (A9) OORH Warning PC 3.x
Bitmap 9

40439 8 Fault Status Gas 1529 Exhaust Gas Temp 2 (B1) OORH Warning PC 3.x
Bitmap 9

40439 9 Fault Status Gas 1531 Exhaust Gas Temp 6 (B3) OORH Warning PC 3.x
Bitmap 9

40439 10 Fault Status Gas 1532 Exhaust Gas Temp 8 (B4) OORH Warning PC 3.x
Bitmap 9

40439 11 Fault Status Gas 1533 Exhaust Gas Temp 10 (B5) OORH Warning PC 3.x
Bitmap 9

40439 12 Fault Status Gas 1534 Exhaust Gas Temp 12 (B6) OORH Warning PC 3.x
Bitmap 9

40439 13 Fault Status Gas 1535 Exhaust Gas Temp 14 (B7) OORH Warning PC 3.x
Bitmap 9

40439 14 Fault Status Gas 1536 Exhaust Gas Temp 16 (B8) OORH Warning PC 3.x
Bitmap 9

40439 15 Fault Status Gas 1537 Exhaust Gas Temp 18 (B9) OORH Warning PC 3.x
Bitmap 9

40440 0 Fault Status Gas 1545 EPS Backup Channel Lost Warning PC 3.x
Bitmap 10

40440 1 Fault Status Gas 1546 EPS Main Channel Lost Warning PC 3.x
Bitmap 10

40440 2 Fault Status Gas 1579 Continuous_Light_Knock_Error_12_( Shutdown PC 3.x


Bitmap 10 B6) w/Cooldown

40440 3 Fault Status Gas 1581 Continuous_Light_Knock_Error_14_( Shutdown PC 3.x


Bitmap 10 B7) w/Cooldown

40440 4 Fault Status Gas 1582 Continuous_Light_Knock_Error_16_( Shutdown PC 3.x


Bitmap 10 B8) w/Cooldown

40440 5 Fault Status Gas 1583 Heavy_Knock_Error_16_(B8) Shutdown PC 3.x


Bitmap 10 w/Cooldown

40440 6 Fault Status Gas 1587 Continuous_Light_Knock_Error_17_( Shutdown PC 3.x


Bitmap 10 A9) w/Cooldown

A029X159 (Issue 14) 357


5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 10-2015

Addr. Bit# Name Fault Event Name Response Control


Code

40440 7 Fault Status Gas 1588 Heavy_Knock_Error_17_(A9) Shutdown PC 3.x


Bitmap 10 w/Cooldown

40440 8 Fault Status Gas 1593 Continuous_Light_Knock_Error_18_( Shutdown PC 3.x


Bitmap 10 B9) w/Cooldown

40440 9 Fault Status Gas 1618 Exhaust Gas Temp, Cyl 1 (A1) Warning PC 3.x
Bitmap 10 OORH

40440 10 Fault Status Gas 1619 Exhaust Gas Temp, Cyl 4 (B2) Warning PC 3.x
Bitmap 10 OORH

40440 11 Fault Status Gas 1636 Intake Manif Press 2 OORH Warning PC 3.x
Bitmap 10

40440 12 Fault Status Gas 1637 Intake Manif Press 2 OORL Warning PC 3.x
Bitmap 10

40440 13 Fault Status Gas 1737 CAN_Throttle_Internal_Failure_Error Shutdown PC 3.x


Bitmap 10 w/Cooldown

40440 14 Fault Status Gas 1738 CAN_Throttle_Internal_Fault_Error Warning PC 3.x


Bitmap 10

40440 15 Fault Status Gas 1739 Engine Throttle Control Condition Warning PC 3.x
Bitmap 10 Exists

40441 0 Fault Status Gas 1741 CAN_Throttle_High_Temp_Warning_ Warning PC 3.x


Bitmap 11 Error

40441 1 Fault Status Gas 1742 CAN_Throttle_Temp_Limiting_Error Warning PC 3.x


Bitmap 11

40441 2 Fault Status Gas 1743 Throttle Ctrl 2 OOR High Shutdown PC 3.x
Bitmap 11 w/Cooldown

40441 3 Fault Status Gas 1744 Throttle Ctrl 2 OOR Low Shutdown PC 3.x
Bitmap 11 w/Cooldown

40441 4 Fault Status Gas 1745 Throttle Ctrl 2 Incorrect Shutdown PC 3.x
Bitmap 11 w/Cooldown

40441 5 Fault Status Gas 1746 Throttle Ctrl 2 Out of Adjustment Shutdown PC 3.x
Bitmap 11 w/Cooldown

40441 6 Fault Status Gas 1747 Throttle Ctrl 2 Bad Device Shutdown PC 3.x
Bitmap 11 w/Cooldown

40441 7 Fault Status Gas 1748 Throttle Ctrl 2 Root Unknown Warning PC 3.x
Bitmap 11

40441 8 Fault Status Gas 1749 Throttle Ctrl 2 Condition Exists Warning PC 3.x
Bitmap 11

40441 9 Fault Status Gas 1751 Throttle Ctrl 2 Warning High Warning PC 3.x
Bitmap 11

40441 10 Fault Status Gas 1752 Throttle Ctrl 2 Moderate High Warning PC 3.x
Bitmap 11

40441 11 Fault Status Gas 1753 Fuel Shutoff 2 OOR High Warning PC 3.x
Bitmap 11

40441 12 Fault Status Gas 1754 Fuel Tmp 2 OOR High Warning PC 3.x
Bitmap 11

40441 13 Fault Status Gas 1755 Fuel Tmp 2 OOR Low Warning PC 3.x
Bitmap 11

40441 14 Fault Status Gas 1756 Gas Flow 2 OOR High Warning PC 3.x
Bitmap 11

358 A029X159 (Issue 14)


10-2015 5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Addr. Bit# Name Fault Event Name Response Control


Code

40441 15 Fault Status Gas 1757 Gas Flow 2 OOR Low Warning PC 3.x
Bitmap 11

40442 0 Fault Status Gas 1758 Gas Flow 2 Incorrect Data Warning PC 3.x
Bitmap 12

40442 1 Fault Status Gas 1759 FCV 2 Pos Feedback Incorrect Shutdown PC 3.x
Bitmap 12 w/Cooldown

40442 2 Fault Status Gas 1761 FCV_Actuator_Error_1761 Shutdown PC 3.x


Bitmap 12 w/Cooldown

40442 3 Fault Status Gas 1984 Int Man 2 Tmp Moderate High Warning PC 3.x
Bitmap 12

40442 4 Fault Status Gas 1765 FCV 2 In Pr OOR High Warning PC 3.x
Bitmap 12

40442 5 Fault Status Gas 1766 FCV 2 In Pr OOR Low Warning PC 3.x
Bitmap 12

40442 6 Fault Status Gas 1767 FCV 2 Out Pr OOR High Warning PC 3.x
Bitmap 12

40442 7 Fault Status Gas 1768 FCV 2 Out Pr OOR Low Warning PC 3.x
Bitmap 12

40442 8 Fault Status Gas 1769 E_Shutd Indication OORH Warning PC 3.x
Bitmap 12

40442 9 Fault Status Gas 1771 E_Shutd Indication OORL Warning PC 3.x
Bitmap 12

40442 10 Fault Status Gas 1772 Eng Derate Request OORH Warning PC 3.x
Bitmap 12

40442 11 Fault Status Gas 1773 Eng Derate Request OORL Warning PC 3.x
Bitmap 12

40442 12 Fault Status Gas 1774 Oil Priming Pump OORH Warning PC 3.x
Bitmap 12

40442 13 Fault Status Gas 1775 Oil Priming Pump OORL Warning PC 3.x
Bitmap 12

40442 14 Fault Status Gas 3362 Power Conservation Control OORH Warning PC 3.x
Bitmap 12

40442 15 Fault Status Gas 3363 Power Conservation Control OORL Warning PC 3.x
Bitmap 12

40443 0 Fault Status Gas 1778 Engine_Heater_Control_Driver_High Warning PC 3.x


Bitmap 13 _Error

40443 1 Fault Status Gas 1779 Engine_Heater_Control_Driver_Low_ Warning PC 3.x


Bitmap 13 Error

40443 2 Fault Status Gas 1781 Shutd Request OOR High Warning PC 3.x
Bitmap 13

40443 3 Fault Status Gas 1782 Shutd Request OOR Low Warning PC 3.x
Bitmap 13

40443 4 Fault Status Gas 1783 Coolant_Pump_Control_Driver_High_ Warning PC 3.x


Bitmap 13 Error

40443 5 Fault Status Gas 1784 Coolant_Pump_Control_Driver_Low_ Warning PC 3.x


Bitmap 13 Error

40443 6 Fault Status Gas 1785 Oil_Priming_Pump_Manual_Override Warning PC 3.x


Bitmap 13 _Input_On

A029X159 (Issue 14) 359


5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 10-2015

Addr. Bit# Name Fault Event Name Response Control


Code

40443 7 Fault Status Gas 1786 Oil_Priming_Pump_Stuck_On_Error Warning PC 3.x


Bitmap 13

40443 8 Fault Status Gas 1787 Post_Lube_Oil_Priming_Error Warning PC 3.x


Bitmap 13

40443 9 Fault Status Gas 1788 Maintenance_Lube_Oil_Priming_Erro Warning PC 3.x


Bitmap 13 r

40443 10 Fault Status Gas 1789 Pre_Start_Lube_Oil_Priming_Error Shutdown PC 3.x


Bitmap 13 w/Cooldown

40443 11 Fault Status Gas 1791 Failure_To_Meet_Load_Speed_Error Shutdown PC 3.x


Bitmap 13 w/Cooldown

40443 12 Fault Status Gas 1792 Idle when CB Closed Warning PC 3.x
Bitmap 13

40443 13 Fault Status Gas 1793 Speed/Posit sensor out of Adj Warning PC 3.x
Bitmap 13

40443 14 Fault Status Gas 1794 Fire Detected Shutdown PC 3.x


Bitmap 13 w/Cooldown

40443 15 Fault Status Gas 1795 Compressor_Bypass_Position_High_ Warning PC 3.x


Bitmap 13 Error

40444 0 Fault Status Gas 1796 Compressor_Bypass_Position_Low_ Warning PC 3.x


Bitmap 14 Error

40444 1 Fault Status Gas 1797 Compressor Bypass ctrl OORH Warning PC 3.x
Bitmap 14

40444 2 Fault Status Gas 1798 Compressor Bypass ctrl OORL Warning PC 3.x
Bitmap 14

40444 3 Fault Status Gas 1799 CB_Position_Err_Status Warning PC 3.x


Bitmap 14

40444 4 Fault Status Gas 1811 HIGH_SIDE_DRV2_High_Control_Er Warning PC 3.x


Bitmap 14 ror (VPS)

40444 5 Fault Status Gas 1812 HIGH_SIDE_DRV2_Low_Control_Err Warning PC 3.x


Bitmap 14 or (VPS)

40444 6 Fault Status Gas 1813 Valve_Proving_System_Test_Failed_ Warning PC 3.x


Bitmap 14 Warning_Error

40444 7 Fault Status Gas 1814 Valve_Proving_System_Test_Failed_ Shutdown PC 3.x


Bitmap 14 Shutdown_Error w/Cooldown

40444 8 Fault Status Gas 1815 RLY14_High_Control_Error Warning PC 3.x


Bitmap 14

40444 9 Fault Status Gas 1816 Oil Pre-Heater Ctrl OOR Low Warning PC 3.x
Bitmap 14

40444 10 Fault Status Gas 1817 Oil_Pre-Heater_Tripped_Error Warning PC 3.x


Bitmap 14

40444 11 Fault Status Gas 1818 Oil_Pre-Heater_Not_Warming_Error Warning PC 3.x


Bitmap 14

40444 12 Fault Status Gas 1819 Common AC Aux CB tripped Warning PC 3.x
Bitmap 14

40444 13 Fault Status Gas 1821 Min_FSO_Speed_Error Shutdown PC 3.x


Bitmap 14 w/Cooldown

40444 14 Fault Status Gas 1822 LT Coolant Level Low Shutdown Shutdown PC 3.x
Bitmap 14 Error w/Cooldown

360 A029X159 (Issue 14)


10-2015 5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Addr. Bit# Name Fault Event Name Response Control


Code

40444 15 Fault Status Gas 1823 LT Coolant Level Low Warning Error Warning PC 3.x
Bitmap 14

40445 0 Fault Status Gas 1824 Idle_Rated_Trans_Oil_Temp_Low_Er Warning PC 3.x


Bitmap 15 ror

40445 1 Fault Status Gas 1825 Dirty_Oil_Level_Error Warning PC 3.x


Bitmap 15

40445 2 Fault Status Gas 1826 ECM Software incompatible Shutdown PC 3.x
Bitmap 15 w/Cooldown

40445 3 Fault Status Gas 1827 Fuel_Inlet_Pressure_High_Error Warning PC 3.x


Bitmap 15

40445 4 Fault Status Gas 1828 Fuel_Inlet_Pressure_Low_Error Warning PC 3.x


Bitmap 15

40445 5 Fault Status Gas 1829 Vent_Gas_Valve_Error Shutdown PC 3.x


Bitmap 15 w/Cooldown

40445 6 Fault Status Gas 1831 Upstream_FSO_Valve_Error Shutdown PC 3.x


Bitmap 15 w/Cooldown

40445 7 Fault Status Gas 1832 Downstream_FSO_Valve_Error Shutdown PC 3.x


Bitmap 15 w/Cooldown

40445 8 Fault Status Gas 1833 Engine_Heater_Trip_Error Warning PC 3.x


Bitmap 15

40445 9 Fault Status Gas 1834 Coolant_Pump_Trip_Error Warning PC 3.x


Bitmap 15

40445 10 Fault Status Gas 1835 Oil_Priming_Pump_Tripped_Error Warning PC 3.x


Bitmap 15

40445 11 Fault Status Gas 1836 LCP_(LT)_Low_Serious_Error Shutdown PC 3.x


Bitmap 15 w/Cooldown

40445 12 Fault Status Gas 1837 Permanent_FS_Cam_Sync_Lost_Err Shutdown PC 3.x


Bitmap 15 or w/Cooldown

40445 13 Fault Status Gas 1838 Partial_Engine_Overload_Shutdown_ Shutdown PC 3.x


Bitmap 15 Error w/Cooldown

40445 14 Fault Status Gas 1839 Fuel_Supply_Pressure_High_Error Warning PC 3.x


Bitmap 15

40445 15 Fault Status Gas 1841 Fuel_Supply_Pressure_Low_Error Warning PC 3.x


Bitmap 15

40446 0 Fault Status Gas 1842 Radiator_Fan_Trip_Error Warning PC 3.x


Bitmap 16

40446 1 Fault Status Gas 1858 Exhaust Aft Inlet O2 OOR High Warning PC 3.x
Bitmap 16

40446 2 Fault Status Gas 1859 Exhaust Aft Inlet O2 OOR Low Warning PC 3.x
Bitmap 16

40446 3 Fault Status Gas 1861 Exhaust Aft Inlet O2 Incorrect Warning PC 3.x
Bitmap 16

40446 4 Fault Status Gas 1862 Exhaust Aft Out O2 OOR High Warning PC 3.x
Bitmap 16

40446 5 Fault Status Gas 1863 Exhaust Aft Outlet O2 OOR Low Warning PC 3.x
Bitmap 16

40446 6 Fault Status Gas 1864 Exhaust Aft Outlet O2 Incorrect Warning PC 3.x
Bitmap 16

A029X159 (Issue 14) 361


5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 10-2015

Addr. Bit# Name Fault Event Name Response Control


Code

40446 7 Fault Status Gas 1985 Int Man 3 Tmp Moderate High Warning PC 3.x
Bitmap 16

40446 8 Fault Status Gas 1986 Int Man 4 Tmp Moderate High Warning PC 3.x
Bitmap 16

40446 9 Fault Status Gas 2111 Coolant_Inlet_Temperature_(LT)_Hig Warning PC 3.x


Bitmap 16 h_Error

40446 10 Fault Status Gas 2112 Coolant_Inlet_Temperature_(LT)_Lo Warning PC 3.x


Bitmap 16 w_Error

40446 11 Fault Status Gas 2113 CIT_(LT)_High_Warning_Error Warning PC 3.x


Bitmap 16

40446 12 Fault Status Gas 2114 CIT_(LT)_High_Serious_Error Shutdown PC 3.x


Bitmap 16 w/Cooldown

40446 13 Fault Status Gas 2115 LT_Coolant_Pressure_High_Error Warning PC 3.x


Bitmap 16

40446 14 Fault Status Gas 2116 LT_Coolant_Pressure_Low_Error Warning PC 3.x


Bitmap 16

40446 15 Fault Status Gas 2117 LCP_(LT)_Low_Warning_Error Warning PC 3.x


Bitmap 16

40447 0 Fault Status Gas 2121 Exhaust_Temp_1_(A1)_High_Warnin Warning PC 3.x


Bitmap 17 g_Error

40447 1 Fault Status Gas 2122 Exhaust_Temp_3_(A2)_High_Warnin Warning PC 3.x


Bitmap 17 g_Error

40447 2 Fault Status Gas 2123 Exhaust_Temp_5_(A3)_High_Warnin Warning PC 3.x


Bitmap 17 g_Error

40447 3 Fault Status Gas 2124 Exhaust_Temp_7_(A4)_High_Warnin Warning PC 3.x


Bitmap 17 g_Error

40447 4 Fault Status Gas 2125 Exhaust_Temp_9_(A5)_High_Warnin Warning PC 3.x


Bitmap 17 g_Error

40447 5 Fault Status Gas 2126 Exhaust_Temp_11_(A6)_High_Warni Warning PC 3.x


Bitmap 17 ng_Error

40447 6 Fault Status Gas 2127 Exhaust_Temp_13_(A7)_High_Warni Warning PC 3.x


Bitmap 17 ng_Error

40447 7 Fault Status Gas 2128 Exhaust_Temp_15_(A8)_High_Warni Warning PC 3.x


Bitmap 17 ng_Error

40447 8 Fault Status Gas 2129 Exhaust_Temp_17_(A9)_High_Warni Warning PC 3.x


Bitmap 17 ng_Error

40447 9 Fault Status Gas 2131 Exhaust_Temp_2_(B1)_High_Warnin Warning PC 3.x


Bitmap 17 g_Error

40447 10 Fault Status Gas 2132 Exhaust_Temp_4_(B2)_High_Warnin Warning PC 3.x


Bitmap 17 g_Error

40447 11 Fault Status Gas 2133 Exhaust_Temp_6_(B3)_High_Warnin Warning PC 3.x


Bitmap 17 g_Error

40447 12 Fault Status Gas 2134 Exhaust_Temp_8_(B4)_High_Warnin Warning PC 3.x


Bitmap 17 g_Error

40447 13 Fault Status Gas 2135 Exhaust_Temp_10_(B5)_High_Warni Warning PC 3.x


Bitmap 17 ng_Error

40447 14 Fault Status Gas 2136 Exhaust_Temp_12_(B6)_High_Warni Warning PC 3.x


Bitmap 17 ng_Error

362 A029X159 (Issue 14)


10-2015 5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Addr. Bit# Name Fault Event Name Response Control


Code

40447 15 Fault Status Gas 2137 Exhaust_Temp_14_(B7)_High_Warni Warning PC 3.x


Bitmap 17 ng_Error

40448 0 Fault Status Gas 2138 Exhaust_Temp_16_(B8)_High_Warni Warning PC 3.x


Bitmap 18 ng_Error

40448 1 Fault Status Gas 2139 Exhaust_Temp_18_(B9)_High_Warni Warning PC 3.x


Bitmap 18 ng_Error

40448 2 Fault Status Gas 2141 Start_Air_Pressure_High_Error Warning PC 3.x


Bitmap 18

40448 3 Fault Status Gas 2142 Start_Air_Pressure_Low_Error Warning PC 3.x


Bitmap 18

40448 4 Fault Status Gas 2143 SAP_Overpressure_Error Warning PC 3.x


Bitmap 18

40448 5 Fault Status Gas 2144 Exhaust Temp 16 (B8) High Serious Shutdown PC 3.x
Bitmap 18 Error w/Cooldown

40448 6 Fault Status Gas 2145 Exhaust Temp 18 (B9) High Serious Shutdown PC 3.x
Bitmap 18 Error w/Cooldown

40448 7 Fault Status Gas 2146 EGT 17 (A9) OOR Low Warning PC 3.x
Bitmap 18

40448 8 Fault Status Gas 2147 EGT 18 (B9) OOR Low Warning PC 3.x
Bitmap 18

40448 9 Fault Status Gas 2154 Oil_Filter_Outlet_Pressure_High_Err Warning PC 3.x


Bitmap 18 or

40448 10 Fault Status Gas 2155 Oil_Filter_Outlet_Pressure_Low_Erro Warning PC 3.x


Bitmap 18 r

40448 11 Fault Status Gas 2157 Int Man 2 Tmp Abnormal Rate Shutdown PC 3.x
Bitmap 18 w/Cooldown

40448 12 Fault Status Gas 2158 Int Man 3 Tmp Abnormal Rate Shutdown PC 3.x
Bitmap 18 w/Cooldown

40448 13 Fault Status Gas 2159 Int Man 4 Tmp Abnormal Rate Shutdown PC 3.x
Bitmap 18 w/Cooldown

40448 14 Fault Status Gas 2188 Exhaust O2 OOR High Warning PC 3.x
Bitmap 18

40448 15 Fault Status Gas 2191 ST_Throttle_Press_Err_Status Warning PC 3.x


Bitmap 18

40449 0 Fault Status Gas 2192 Exhaust O2 OOR Low Warning PC 3.x
Bitmap 19

40449 1 Fault Status Gas 2217 RAM_Image_Word_Error Warning PC 3.x


Bitmap 19

40449 2 Fault Status Gas 2219 Exhaust O2 Moderate High Warning PC 3.x
Bitmap 19

40449 3 Fault Status Gas 2221 Exhaust O2 Moderate Low Warning PC 3.x
Bitmap 19

40449 4 Fault Status Gas 2281 Knock 11 (A6) Moderate High Shutdown PC 3.x
Bitmap 19 w/Cooldown

40449 5 Fault Status Gas 2282 Knock 11 (A6) Critical High Shutdown PC 3.x
Bitmap 19 w/Cooldown

40449 6 Fault Status Gas 2298 Fuel Shutoff 2 OOR Low Warning PC 3.x
Bitmap 19

A029X159 (Issue 14) 363


5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 10-2015

Addr. Bit# Name Fault Event Name Response Control


Code

40449 7 Fault Status Gas 2315 Red Lamp OOR High Warning PC 3.x
Bitmap 19

40449 8 Fault Status Gas 2316 Amber Lamp OOR High Warning PC 3.x
Bitmap 19

40449 9 Fault Status Gas 2317 Amber Lamp OOR Low Warning PC 3.x
Bitmap 19

40449 10 Fault Status Gas 2427 Fuel_Outlet_Pressure_High_Error Warning PC 3.x


Bitmap 19

40449 11 Fault Status Gas 2428 Fuel_Outlet_Pressure_Low_Error Warning PC 3.x


Bitmap 19

40449 12 Fault Status Gas 2453 Total Real Power Circuit OORH Warning PC 3.x
Bitmap 19

40449 13 Fault Status Gas 2454 Total Real Power Circuit OORL Warning PC 3.x
Bitmap 19

40449 14 Fault Status Gas 2455 Speed_Bias_Low_Error Warning PC 3.x


Bitmap 19

40449 15 Fault Status Gas 2456 Speed_Bias_High_Error Warning PC 3.x


Bitmap 19

40450 0 Fault Status Gas 2457 Max_Total_Misfire_Error Shutdown PC 3.x


Bitmap 20 w/Cooldown

40450 1 Fault Status Gas 2458 Cylinder_2_(B1)_Total_Misfire_Error Warning PC 3.x


Bitmap 20

40450 2 Fault Status Gas 2459 Cylinder_4_(B2)_Total_Misfire_Error Warning PC 3.x


Bitmap 20

40450 3 Fault Status Gas 2461 Cylinder_6_(B3)_Total_Misfire_Error Warning PC 3.x


Bitmap 20

40450 4 Fault Status Gas 2462 Cylinder_8_(B4)_Total_Misfire_Error Warning PC 3.x


Bitmap 20

40450 5 Fault Status Gas 2463 Cylinder_10_(B5)_Total_Misfire_Erro Warning PC 3.x


Bitmap 20 r

40450 6 Fault Status Gas 2464 Cylinder_12_(B6)_Total_Misfire_Erro Warning PC 3.x


Bitmap 20 r

40450 7 Fault Status Gas 2465 Cylinder_14_(B7)_Total_Misfire_Erro Warning PC 3.x


Bitmap 20 r

40450 8 Fault Status Gas 2466 Cylinder_16_(B8)_Total_Misfire_Erro Warning PC 3.x


Bitmap 20 r

40450 9 Fault Status Gas 2467 Cylinder_18_(B9)_Total_Misfire_Erro Warning PC 3.x


Bitmap 20 r

40450 10 Fault Status Gas 2469 Cylinder_1_(A1)_Total_Misfire_Error Warning PC 3.x


Bitmap 20

40450 11 Fault Status Gas 2471 Cylinder_3_(A2)_Total_Misfire_Error Warning PC 3.x


Bitmap 20

40450 12 Fault Status Gas 2472 Cylinder_5_(A3)_Total_Misfire_Error Warning PC 3.x


Bitmap 20

40450 13 Fault Status Gas 2473 Cylinder_7_(A4)_Total_Misfire_Error Warning PC 3.x


Bitmap 20

40450 14 Fault Status Gas 2475 Cylinder_9_(A5)_Total_Misfire_Error Warning PC 3.x


Bitmap 20

364 A029X159 (Issue 14)


10-2015 5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Addr. Bit# Name Fault Event Name Response Control


Code

40450 15 Fault Status Gas 2476 Cylinder_11_(A6)_Total_Misfire_Erro Warning PC 3.x


Bitmap 20 r

40451 0 Fault Status Gas 2477 Cylinder_13_(A7)_Total_Misfire_Erro Warning PC 3.x


Bitmap 21 r

40451 1 Fault Status Gas 2478 Cylinder_15_(A8)_Total_Misfire_Erro Warning PC 3.x


Bitmap 21 r

40451 2 Fault Status Gas 2479 Cylinder_17_(A9)_Total_Misfire_Erro Warning PC 3.x


Bitmap 21 r

40451 3 Fault Status Gas 2482 Start_Before_Ready_Error Shutdown PC 3.x


Bitmap 21 w/Cooldown

40451 4 Fault Status Gas 2483 Continuous_Starter_Failure_Error Shutdown PC 3.x


Bitmap 21 w/Cooldown

40451 5 Fault Status Gas 2484 Exhaust Temperature 1 (A1) Shutdown PC 3.x
Bitmap 21 Abnormal Rate w/Cooldown

40451 6 Fault Status Gas 2485 Exhaust Temperature 3 (A2) Shutdown PC 3.x
Bitmap 21 Abnormal Rate w/Cooldown

40451 7 Fault Status Gas 2486 Exhaust Temperature 5 (A3) Shutdown PC 3.x
Bitmap 21 Abnormal Rate w/Cooldown

40451 8 Fault Status Gas 2487 Exhaust Temperature 7 (A4) Shutdown PC 3.x
Bitmap 21 Abnormal Rate w/Cooldown

40451 9 Fault Status Gas 2488 Exhaust Temperature 9 (A5) Shutdown PC 3.x
Bitmap 21 Abnormal Rate w/Cooldown

40451 10 Fault Status Gas 2489 Exhaust Temperature 11 (A6) Shutdown PC 3.x
Bitmap 21 Abnormal Rate w/Cooldown

40451 11 Fault Status Gas 2491 Exhaust Temperature 13 (A7) Shutdown PC 3.x
Bitmap 21 Abnormal Rate w/Cooldown

40451 12 Fault Status Gas 2492 Exhaust Temperature 15 (A8) Shutdown PC 3.x
Bitmap 21 Abnormal Rate w/Cooldown

40451 13 Fault Status Gas 2493 Exhaust Temperature 17 (A9) Shutdown PC 3.x
Bitmap 21 Abnormal Rate w/Cooldown

40451 14 Fault Status Gas 2494 Exhaust Temperature 2 (B1) Shutdown PC 3.x
Bitmap 21 Abnormal Rate w/Cooldown

40451 15 Fault Status Gas 2495 Exhaust Temperature 4 (B2) Shutdown PC 3.x
Bitmap 21 Abnormal Rate w/Cooldown

40452 0 Fault Status Gas 2496 Exhaust Temperature 6 (B3) Shutdown PC 3.x
Bitmap 22 Abnormal Rate w/Cooldown

40452 1 Fault Status Gas 2497 Exhaust Temperature 8 (B4) Shutdown PC 3.x
Bitmap 22 Abnormal Rate w/Cooldown

40452 2 Fault Status Gas 2498 Exhaust Temperature 10 (B5) Shutdown PC 3.x
Bitmap 22 Abnormal Rate w/Cooldown

40452 3 Fault Status Gas 2499 Exhaust Temperature 12 (B6) Shutdown PC 3.x
Bitmap 22 Abnormal Rate w/Cooldown

40452 4 Fault Status Gas 2511 Exhaust Temperature 14 (B7) Shutdown PC 3.x
Bitmap 22 Abnormal Rate w/Cooldown

40452 5 Fault Status Gas 2512 Exhaust Temperature 16 (B8) Shutdown PC 3.x
Bitmap 22 Abnormal Rate w/Cooldown

40452 6 Fault Status Gas 2513 Exhaust Temperature 18 (B9) Shutdown PC 3.x
Bitmap 22 Abnormal Rate w/Cooldown

A029X159 (Issue 14) 365


5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 10-2015

Addr. Bit# Name Fault Event Name Response Control


Code

40452 7 Fault Status Gas 2517 Compressor_Outlet_Pressure_High_ Warning PC 3.x


Bitmap 22 Error

40452 8 Fault Status Gas 2518 Compressor_Outlet_Pressure_Low_ Warning PC 3.x


Bitmap 22 Error

40452 9 Fault Status Gas 2521 Bank_Id_Error Shutdown PC 3.x


Bitmap 22 w/Cooldown

40452 10 Fault Status Gas 2522 Continuous_Light_Knock_Error_1_(A Shutdown PC 3.x


Bitmap 22 1) w/Cooldown

40452 11 Fault Status Gas 2523 Continuous_Light_Knock_Error_2_(B Shutdown PC 3.x


Bitmap 22 1) w/Cooldown

40452 12 Fault Status Gas 2524 Continuous_Light_Knock_Error_3_(A Shutdown PC 3.x


Bitmap 22 2) w/Cooldown

40452 13 Fault Status Gas 2525 Continuous_Light_Knock_Error_4_(B Shutdown PC 3.x


Bitmap 22 2) w/Cooldown

40452 14 Fault Status Gas 2526 Continuous_Light_Knock_Error_5_(A Shutdown PC 3.x


Bitmap 22 3) w/Cooldown

40452 15 Fault Status Gas 2527 Continuous_Light_Knock_Error_6_(B Shutdown PC 3.x


Bitmap 22 3) w/Cooldown

40453 0 Fault Status Gas 2528 Continuous_Light_Knock_Error_7_(A Shutdown PC 3.x


Bitmap 23 4) w/Cooldown

40453 1 Fault Status Gas 2529 Continuous_Light_Knock_Error_8_(B Shutdown PC 3.x


Bitmap 23 4) w/Cooldown

40453 2 Fault Status Gas 2531 Continuous_Light_Knock_Error_9_(A Shutdown PC 3.x


Bitmap 23 5) w/Cooldown

40453 3 Fault Status Gas 2532 Continuous_Light_Knock_Error_10_( Shutdown PC 3.x


Bitmap 23 B5) w/Cooldown

40453 4 Fault Status Gas 2544 ECM_Overtemp_Error Shutdown PC 3.x


Bitmap 23 w/Cooldown

40453 5 Fault Status Gas 2567 DG_Air_Compressor_Trip_Error Warning PC 3.x


Bitmap 23

40453 6 Fault Status Gas 2643 Throttle Pos 2 Feedback OOR High Warning PC 3.x
Bitmap 23

40453 7 Fault Status Gas 2644 Throttle Pos 2 Feedback OOR Low Warning PC 3.x
Bitmap 23

40453 9 Fault Status Gas 2724 Gas Supply Pr Moderate High Warning PC 3.x
Bitmap 23

40453 10 Fault Status Gas 2725 Gas Supply Pr Moderate Low Warning PC 3.x
Bitmap 23

40453 11 Fault Status Gas 2737 Exh Gas Tmp Critical High Shutdown PC 3.x
Bitmap 23 w/Cooldown

40453 12 Fault Status Gas 2766 Bank_A_CCD_Failed_Error Shutdown PC 3.x


Bitmap 23 w/Cooldown

40453 13 Fault Status Gas 2767 Bank_B_CCD_Failed_Error Shutdown PC 3.x


Bitmap 23 w/Cooldown

40453 14 Fault Status Gas 2768 CAN Parent Communication Incorrect Shutdown PC 3.x
Bitmap 23 w/Cooldown

40453 15 Fault Status Gas 2769 CAN Child Com Incorrect Shutdown PC 3.x
Bitmap 23 w/Cooldown

366 A029X159 (Issue 14)


10-2015 5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Addr. Bit# Name Fault Event Name Response Control


Code

40454 0 Fault Status Gas 2789 COT_Low_Error Warning PC 3.x


Bitmap 24

40454 1 Fault Status Gas 2793 COT_Low_Serious_Error Shutdown PC 3.x


Bitmap 24 w/Cooldown

40454 2 Fault Status Gas 2794 Ign Shutd Relay OOR High Warning PC 3.x
Bitmap 24

40454 3 Fault Status Gas 2795 Ign Shutd Relay OOR Low Warning PC 3.x
Bitmap 24

40454 4 Fault Status Gas 2796 Partial_Engine_Overload_Warning_E Warning PC 3.x


Bitmap 24 rror

40454 5 Fault Status Gas 2797 Inlet Gas Diff Pressure OOR High Warning PC 3.x
Bitmap 24

40454 6 Fault Status Gas 2798 Inlet Gas Diff Pressure OOR Low Warning PC 3.x
Bitmap 24

40454 7 Fault Status Gas 2799 IMOP_Compressor_Outlet_Presure_ Shutdown PC 3.x


Bitmap 24 Delta_Error w/Cooldown

40454 8 Fault Status Gas 2811 IMOP_Compressor_Outlet_Pressure Shutdown PC 3.x


Bitmap 24 _Maximum_Error w/Cooldown

40454 9 Fault Status Gas 2837 Exhaust_Temp_1_(A1)_Deviation_Er Warning PC 3.x


Bitmap 24 ror

40454 10 Fault Status Gas 2838 Exhaust_Temp_3_(A2)_Deviation_Er Warning PC 3.x


Bitmap 24 ror

40454 11 Fault Status Gas 2839 Exhaust_Temp_5_(A3)_Deviation_Er Warning PC 3.x


Bitmap 24 ror

40454 12 Fault Status Gas 2841 Exhaust_Temp_7_(A4)_Deviation_Er Warning PC 3.x


Bitmap 24 ror

40454 13 Fault Status Gas 2842 Exhaust_Temp_9_(A5)_Deviation_Er Warning PC 3.x


Bitmap 24 ror

40454 14 Fault Status Gas 2843 Exhaust_Temp_11_(A6)_Deviation_E Warning PC 3.x


Bitmap 24 rror

40454 15 Fault Status Gas 2844 Exhaust_Temp_13_(A7)_Deviation_E Warning PC 3.x


Bitmap 24 rror

40455 0 Fault Status Gas 2845 Exhaust_Temp_15_(A8)_Deviation_E Warning PC 3.x


Bitmap 25 rror

40455 1 Fault Status Gas 2846 Exhaust_Temp_17_(A9)_Deviation_E Warning PC 3.x


Bitmap 25 rror

40455 2 Fault Status Gas 2847 Exhaust_Temp_2_(B1)_Deviation_Er Warning PC 3.x


Bitmap 25 ror

40455 3 Fault Status Gas 2848 Exhaust_Temp_4_(B2)_Deviation_Er Warning PC 3.x


Bitmap 25 ror

40455 4 Fault Status Gas 2849 Exhaust_Temp_6_(B3)_Deviation_Er Warning PC 3.x


Bitmap 25 ror

40455 5 Fault Status Gas 2851 Exhaust_Temp_8_(B4)_Deviation_Er Warning PC 3.x


Bitmap 25 ror

40455 6 Fault Status Gas 2852 Exhaust_Temp_10_(B5)_Deviation_E Warning PC 3.x


Bitmap 25 rror

40455 7 Fault Status Gas 2853 Exhaust_Temp_12_(B6)_Deviation_E Warning PC 3.x


Bitmap 25 rror

A029X159 (Issue 14) 367


5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 10-2015

Addr. Bit# Name Fault Event Name Response Control


Code

40455 8 Fault Status Gas 2854 Exhaust_Temp_14_(B7)_Deviation_E Warning PC 3.x


Bitmap 25 rror

40455 9 Fault Status Gas 2855 Exhaust_Temp_16_(B8)_Deviation_E Warning PC 3.x


Bitmap 25 rror

40455 10 Fault Status Gas 2856 Exhaust_Temp_18_(B9)_Deviation_E Warning PC 3.x


Bitmap 25 rror

40455 11 Fault Status Gas 2857 Turbo_1_Overspeed_Critical_Error Shutdown PC 3.x


Bitmap 25 w/Cooldown

40455 12 Fault Status Gas 2858 Turbo_2_Overspeed_Critical_Error Shutdown PC 3.x


Bitmap 25 w/Cooldown

40455 13 Fault Status Gas 2859 Alt Heater Ctrl OOR High Warning PC 3.x
Bitmap 25

40455 14 Fault Status Gas 2861 Alt Heater Ctrl OOR Low Warning PC 3.x
Bitmap 25

40455 15 Fault Status Gas 2862 Gen Alternator 1st Start Cond Exists Warning PC 3.x
Bitmap 25

40456 0 Fault Status Gas 2863 Genset to Engine Com Incorrect Shutdown PC 3.x
Bitmap 26 w/Cooldown

40456 1 Fault Status Gas 2864 FSO_NON_High_Control_Error Shutdown PC 3.x


Bitmap 26 w/Cooldown

40456 2 Fault Status Gas 3364 Power Conservation Control Cond Warning PC 3.x
Bitmap 26 Exists

40456 3 Fault Status Gas 2866 FCV_Position_High_Error Warning PC 3.x


Bitmap 26

40456 4 Fault Status Gas 2867 FCV_Position_Low_Error Warning PC 3.x


Bitmap 26

40456 5 Fault Status Gas 2868 Engine_Heater_Over- Warning PC 3.x


Bitmap 26 Temperature_Alarm_Error

40456 6 Fault Status Gas 2869 HT Cool Temp Driver OOR High Warning PC 3.x
Bitmap 26

40456 7 Fault Status Gas 2871 HT Cool Temp Driver OOR Low Warning PC 3.x
Bitmap 26

40456 8 Fault Status Gas 2872 HT Cool Temp Driver Cond Exists Warning PC 3.x
Bitmap 26

40456 9 Fault Status Gas 2873 LT Cool Temp Driver OOR High Warning PC 3.x
Bitmap 26

40456 10 Fault Status Gas 2874 LT Cool Temp Driver OOR Low Warning PC 3.x
Bitmap 26

40456 11 Fault Status Gas 2875 LT Cool Temp Driver Cond Exists Warning PC 3.x
Bitmap 26

40456 12 Fault Status Gas 2876 Comp_Surge_Shutdown_Error Shutdown PC 3.x


Bitmap 26 w/Cooldown

40456 13 Fault Status Gas 2877 Comp_Surge_Derate_Error Warning PC 3.x


Bitmap 26

40456 14 Fault Status Gas 2994 MC68302_Error Warning PC 3.x


Bitmap 26

40456 15 Fault Status Gas 2995 Int Man Pressure 1 Critical High Shutdown PC 3.x
Bitmap 26 w/Cooldown

368 A029X159 (Issue 14)


10-2015 5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Addr. Bit# Name Fault Event Name Response Control


Code

40457 0 Fault Status Gas 2996 Int Man Pressure 1 Moderate High Warning PC 3.x
Bitmap 27

40457 1 Fault Status Gas 2997 Exhaust O2 Critical Low Shutdown PC 3.x
Bitmap 27 w/Cooldown

40457 2 Fault Status Gas 3111 Excessive_Mech_Vibration_1_(A1) Shutdown PC 3.x


Bitmap 27 w/Cooldown

40457 3 Fault Status Gas 3112 Excessive_Mech_Vibration_2_(B1) Shutdown PC 3.x


Bitmap 27 w/Cooldown

40457 4 Fault Status Gas 3113 Excessive_Mech_Vibration_3_(A2) Shutdown PC 3.x


Bitmap 27 w/Cooldown

40457 5 Fault Status Gas 3114 Excessive_Mech_Vibration_4_(B2) Shutdown PC 3.x


Bitmap 27 w/Cooldown

40457 6 Fault Status Gas 3115 Excessive_Mech_Vibration_5_(A3) Shutdown PC 3.x


Bitmap 27 w/Cooldown

40457 7 Fault Status Gas 3116 Excessive_Mech_Vibration_6_(B3) Shutdown PC 3.x


Bitmap 27 w/Cooldown

40457 8 Fault Status Gas 3117 Excessive_Mech_Vibration_7_(A4) Shutdown PC 3.x


Bitmap 27 w/Cooldown

40457 9 Fault Status Gas 3118 Excessive_Mech_Vibration_8_(B4) Shutdown PC 3.x


Bitmap 27 w/Cooldown

40457 10 Fault Status Gas 3119 Excessive_Mech_Vibration_9_(A5) Shutdown PC 3.x


Bitmap 27 w/Cooldown

40457 11 Fault Status Gas 3121 Excessive_Mech_Vibration_10_(B5) Shutdown PC 3.x


Bitmap 27 w/Cooldown

40457 12 Fault Status Gas 3122 Excessive_Mech_Vibration_11_(A6) Shutdown PC 3.x


Bitmap 27 w/Cooldown

40457 13 Fault Status Gas 3123 Excessive_Mech_Vibration_12_(B6) Shutdown PC 3.x


Bitmap 27 w/Cooldown

40457 14 Fault Status Gas 3124 Excessive_Mech_Vibration_13_(A7) Shutdown PC 3.x


Bitmap 27 w/Cooldown

40457 15 Fault Status Gas 3125 Excessive_Mech_Vibration_14_(B7) Shutdown PC 3.x


Bitmap 27 w/Cooldown

40458 0 Fault Status Gas 3126 Excessive_Mech_Vibration_15_(A8) Shutdown PC 3.x


Bitmap 28 w/Cooldown

40458 1 Fault Status Gas 3127 Excessive_Mech_Vibration_16_(B8) Shutdown PC 3.x


Bitmap 28 w/Cooldown

40458 2 Fault Status Gas 3128 Excessive_Mech_Vibration_17_(A9) Shutdown PC 3.x


Bitmap 28 w/Cooldown

40458 3 Fault Status Gas 3129 Excessive_Mech_Vibration_18_(B9) Shutdown PC 3.x


Bitmap 28 w/Cooldown

40458 4 Fault Status Gas 1275 Knock Cyl 10 (B5) OORL Warning PC 3.x
Bitmap 28

40458 5 Fault Status Gas 1277 Knock Cyl 11 (A6) OORL Warning PC 3.x
Bitmap 28

40458 6 Fault Status Gas 1282 Knock Cyl 12 (B6) OORL Warning PC 3.x
Bitmap 28

40458 7 Fault Status Gas 1287 Knock Cyl 13 (A7) OORL Warning PC 3.x
Bitmap 28

A029X159 (Issue 14) 369


5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 10-2015

Addr. Bit# Name Fault Event Name Response Control


Code

40458 8 Fault Status Gas 1292 Knock Cyl 14 (B7) OORL Warning PC 3.x
Bitmap 28

40458 9 Fault Status Gas 1297 Knock Cyl 15 (A8) OORL Warning PC 3.x
Bitmap 28

40458 10 Fault Status Gas 1584 Knock Cyl 16 (B8) OORL Warning PC 3.x
Bitmap 28

40458 11 Fault Status Gas 1589 Knock Cyl 17 (A9) OORL Warning PC 3.x
Bitmap 28

40458 12 Fault Status Gas 1338 Knock Cyl 18 (B9) OORL Warning PC 3.x
Bitmap 28

40459 0 Fault Status Gas 189 HT Coolant Temperature Root Cause Shutdown PC 3.x
Bitmap 29 Unknown w/Cooldown

40459 1 Fault Status Gas 229 HT Coolant Pressure Incorrect Warning PC 3.x
Bitmap 29

40459 2 Fault Status Gas 334 HT Coolant Temperature Incorrect Warning PC 3.x
Bitmap 29

40459 4 Fault Status Gas 831 Spark Plug 1 (A1) OORL Warning PC 3.x
Bitmap 29

40459 5 Fault Status Gas 832 Spark Plug 2 (B1) OORL Warning PC 3.x
Bitmap 29

40459 6 Fault Status Gas 833 Spark Plug 3 (A2) OORL Warning PC 3.x
Bitmap 29

40459 7 Fault Status Gas 834 Spark Plug 4 (B2) OORL Warning PC 3.x
Bitmap 29

40459 8 Fault Status Gas 835 Spark Plug 5 (A3) OORL Warning PC 3.x
Bitmap 29

40459 9 Fault Status Gas 836 Spark Plug 6 (B3) OORL Warning PC 3.x
Bitmap 29

40459 10 Fault Status Gas 837 Spark Plug 7 (A4) OORL Warning PC 3.x
Bitmap 29

40459 11 Fault Status Gas 838 Spark Plug 8 (B4) OORL Warning PC 3.x
Bitmap 29

40459 12 Fault Status Gas 839 Spark Plug 9 (A5) OORL Warning PC 3.x
Bitmap 29

40459 13 Fault Status Gas 841 Spark Plug 10 (B5) OORL Warning PC 3.x
Bitmap 29

40459 14 Fault Status Gas 842 Spark Plug 11 (A6) OORL Warning PC 3.x
Bitmap 29

40459 15 Fault Status Gas 843 Spark Plug 12 (B6) OORL Warning PC 3.x
Bitmap 29

40460 0 Fault Status Gas 844 Spark Plug 13 (A7) OORL Warning PC 3.x
Bitmap 30

40460 1 Fault Status Gas 845 Spark Plug 14 (B7) OORL Warning PC 3.x
Bitmap 30

40460 2 Fault Status Gas 846 Spark Plug 15 (A8) OORL Warning PC 3.x
Bitmap 30

40460 3 Fault Status Gas 847 Spark Plug 16 (B8) OORL Warning PC 3.x
Bitmap 30

370 A029X159 (Issue 14)


10-2015 5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Addr. Bit# Name Fault Event Name Response Control


Code

40460 4 Fault Status Gas 848 Spark Plug 17 (A9) OORL Warning PC 3.x
Bitmap 30

40460 5 Fault Status Gas 849 Spark Plug 18 (B9) OORL Warning PC 3.x
Bitmap 30

40460 7 Fault Status Gas 891 Spark Plug 1 (A1) Root Cause Warning PC 3.x
Bitmap 30 Unknown

40460 8 Fault Status Gas 892 Spark Plug 2 (B1) Root Cause Warning PC 3.x
Bitmap 30 Unknown

40460 9 Fault Status Gas 893 Spark Plug 3 (A2) Root Cause Warning PC 3.x
Bitmap 30 Unknown

40460 10 Fault Status Gas 894 Spark Plug 4 (B2) Root Cause Warning PC 3.x
Bitmap 30 Unknown

40460 11 Fault Status Gas 895 Spark Plug 5 (A3) Root Cause Warning PC 3.x
Bitmap 30 Unknown

40460 12 Fault Status Gas 896 Spark Plug 6 (B3) Root Cause Warning PC 3.x
Bitmap 30 Unknown

40460 13 Fault Status Gas 897 Spark Plug 7 (A4) Root Cause Warning PC 3.x
Bitmap 30 Unknown

40460 14 Fault Status Gas 898 Spark Plug 8 (B4) Root Cause Warning PC 3.x
Bitmap 30 Unknown

40460 15 Fault Status Gas 899 Spark Plug 9 (A5) Root Cause Warning PC 3.x
Bitmap 30 Unknown

40461 0 Fault Status Gas 911 Spark Plug 10 (B5) Root Cause Warning PC 3.x
Bitmap 31 Unknown

40461 1 Fault Status Gas 912 Spark Plug 11 (A6) Root Cause Warning PC 3.x
Bitmap 31 Unknown

40461 2 Fault Status Gas 913 Spark Plug 12 (B6) Root Cause Warning PC 3.x
Bitmap 31 Unknown

40461 3 Fault Status Gas 914 Spark Plug 13 (A7) Root Cause Warning PC 3.x
Bitmap 31 Unknown

40461 4 Fault Status Gas 915 Spark Plug 14 (B7) Root Cause Warning PC 3.x
Bitmap 31 Unknown

40461 5 Fault Status Gas 916 Spark Plug 15 (A8) Root Cause Warning PC 3.x
Bitmap 31 Unknown

40461 6 Fault Status Gas 917 Spark Plug 16 (B8) Root Cause Warning PC 3.x
Bitmap 31 Unknown

40461 7 Fault Status Gas 918 Spark Plug 17 (A9) Root Cause Warning PC 3.x
Bitmap 31 Unknown

40461 8 Fault Status Gas 919 Spark Plug 18 (B9) Root Cause Warning PC 3.x
Bitmap 31 Unknown

40461 10 Fault Status Gas 1276 Knock Cyl 10 (B5) OORH Warning PC 3.x
Bitmap 31

40461 11 Fault Status Gas 1278 Knock Cyl 11 (A6) OORH Warning PC 3.x
Bitmap 31

40461 12 Fault Status Gas 1279 Knock 12 (B6) High Warning Warning PC 3.x
Bitmap 31

40461 13 Fault Status Gas 1283 Knock Cyl 12 (B6) OORH Warning PC 3.x
Bitmap 31

A029X159 (Issue 14) 371


5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 10-2015

Addr. Bit# Name Fault Event Name Response Control


Code

40461 14 Fault Status Gas 1284 Knock 13 (A7) High Warning Warning PC 3.x
Bitmap 31

40461 15 Fault Status Gas 1288 Knock Cyl 13 (A7) OORH Warning PC 3.x
Bitmap 31

40462 0 Fault Status Gas 1289 Knock 14 (B7) High Warning Warning PC 3.x
Bitmap 32

40462 1 Fault Status Gas 1293 Knock Cyl 14 (B7) OORH Warning PC 3.x
Bitmap 32

40462 2 Fault Status Gas 1294 Knock 15 (A8) High Warning Warning PC 3.x
Bitmap 32

40462 3 Fault Status Gas 1298 Knock Cyl 15 (A8) OORH Warning PC 3.x
Bitmap 32

40462 4 Fault Status Gas 1299 Knock 16 (B8) High Warning Warning PC 3.x
Bitmap 32

40462 6 Fault Status Gas 1339 Knock Cyl 18 (B9) OORH Warning PC 3.x
Bitmap 32

40462 7 Fault Status Gas 1352 Knock 20 (B10) High Warning Warning PC 3.x
Bitmap 32

40462 8 Fault Status Gas 1353 Continuous_Light_Knock_Error_20_( Shutdown PC 3.x


Bitmap 32 B10) w/Cooldown

40462 9 Fault Status Gas 1354 Heavy_Knock_Error_20_(B10) Shutdown PC 3.x


Bitmap 32 w/Cooldown

40462 10 Fault Status Gas 1355 Knock Cyl 20 (B10) OORL Warning PC 3.x
Bitmap 32

40462 11 Fault Status Gas 1356 Knock Cyl 20 (B10) OORH Warning PC 3.x
Bitmap 32

40462 12 Fault Status Gas 1572 Continuous_Light_Knock_Error_19_( Shutdown PC 3.x


Bitmap 32 A10) w/Cooldown

40462 13 Fault Status Gas 1574 Heavy_Knock_Error_19_(A10) Shutdown PC 3.x


Bitmap 32 w/Cooldown

40462 14 Fault Status Gas 1575 Knock Cyl 19 (A10) OORL Warning PC 3.x
Bitmap 32

40462 15 Fault Status Gas 1576 Knock Cyl 19 (A10) OORH Warning PC 3.x
Bitmap 32

40463 0 Fault Status Gas 1585 Knock Cyl 16 (B8) OORH Warning PC 3.x
Bitmap 33

40463 1 Fault Status Gas 1586 Knock 17 (A9) High Warning Warning PC 3.x
Bitmap 33

40463 2 Fault Status Gas 1591 Knock Cyl 17 (A9) OORH Warning PC 3.x
Bitmap 33

40463 3 Fault Status Gas 1592 Knock 18 (B9) High Warning Warning PC 3.x
Bitmap 33

40463 4 Fault Status Gas 1594 Knock 19 (A10) High Warning Warning PC 3.x
Bitmap 33

40463 6 Fault Status Gas 2193 HT Coolant Level Moderate High Warning PC 3.x
Bitmap 33

40463 7 Fault Status Gas 2231 Knock Cyl 1 (A1) OORH Warning PC 3.x
Bitmap 33

372 A029X159 (Issue 14)


10-2015 5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Addr. Bit# Name Fault Event Name Response Control


Code

40463 8 Fault Status Gas 2232 Knock Cyl 2 (B1) OORH Warning PC 3.x
Bitmap 33

40463 9 Fault Status Gas 2233 Knock Cyl 3 (A2) OORH Warning PC 3.x
Bitmap 33

40463 10 Fault Status Gas 2234 Knock Cyl 4 (B2) OORH Warning PC 3.x
Bitmap 33

40463 11 Fault Status Gas 2235 Knock Cyl 5 (A3) OORH Warning PC 3.x
Bitmap 33

40463 12 Fault Status Gas 2236 Knock Cyl 6 (B3) OORH Warning PC 3.x
Bitmap 33

40463 13 Fault Status Gas 2237 Knock Cyl 7 (A4) OORH Warning PC 3.x
Bitmap 33

40463 14 Fault Status Gas 2238 Knock Cyl 8 (B4) OORH Warning PC 3.x
Bitmap 33

40463 15 Fault Status Gas 2239 Knock Cyl 9 (A5) OORH Warning PC 3.x
Bitmap 33

40464 0 Fault Status Gas 2279 Knock 11 (A6) High Warning Warning PC 3.x
Bitmap 34

40464 1 Fault Status Gas 2431 Knock 1 (A1) High Warning Warning PC 3.x
Bitmap 34

40464 2 Fault Status Gas 2432 Knock 2 (B1) High Warning Warning PC 3.x
Bitmap 34

40464 3 Fault Status Gas 2433 Knock 3 (A2) High Warning Warning PC 3.x
Bitmap 34

40464 4 Fault Status Gas 2434 Knock 4 (B2) High Warning Warning PC 3.x
Bitmap 34

40464 5 Fault Status Gas 2435 Knock 5 (A3) High Warning Warning PC 3.x
Bitmap 34

40464 6 Fault Status Gas 2436 Knock 6 (B3) High Warning Warning PC 3.x
Bitmap 34

40464 7 Fault Status Gas 2437 Knock 7 (A4) High Warning Warning PC 3.x
Bitmap 34

40464 8 Fault Status Gas 2438 Knock 8 (B4) High Warning Warning PC 3.x
Bitmap 34

40464 9 Fault Status Gas 2439 Knock 9 (A5) High Warning Warning PC 3.x
Bitmap 34

40464 10 Fault Status Gas 2441 Knock 10 (B5) High Warning Warning PC 3.x
Bitmap 34

40464 11 Fault Status Gas 2514 Exhaust Temperature 19 (A10) Shutdown PC 3.x
Bitmap 34 Abnormal Rate w/Cooldown

40464 12 Fault Status Gas 2515 Exhaust Temperature 20 (B10) Shutdown PC 3.x
Bitmap 34 Abnormal Rate w/Cooldown

40464 13 Fault Status Gas 2553 Engine Oil Level Low Warning Error Warning PC 3.x
Bitmap 34

40464 14 Fault Status Gas 2568 Gas Supply Pressure Critical High Shutdown PC 3.x
Bitmap 34 w/Cooldown

40464 15 Fault Status Gas 2569 Gas Supply Pressure Critical Low Shutdown PC 3.x
Bitmap 34 w/Cooldown

A029X159 (Issue 14) 373


5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 10-2015

Addr. Bit# Name Fault Event Name Response Control


Code

40465 0 Fault Status Gas 2586 Spark Plug 1 (A1) High Warning NONE PC 3.x
Bitmap 35

40465 1 Fault Status Gas 2587 Spark Plug 2 (B1) High Warning NONE PC 3.x
Bitmap 35

40465 2 Fault Status Gas 2588 Spark Plug 3 (A2) High Warning NONE PC 3.x
Bitmap 35

40465 3 Fault Status Gas 2589 Spark Plug 4 (B2) High Warning NONE PC 3.x
Bitmap 35

40465 4 Fault Status Gas 2591 Spark Plug 5 (A3) High Warning NONE PC 3.x
Bitmap 35

40465 5 Fault Status Gas 2592 Spark Plug 6 (B3) High Warning NONE PC 3.x
Bitmap 35

40465 6 Fault Status Gas 2593 Spark Plug 1 (A1) Low Warning NONE PC 3.x
Bitmap 35

40465 7 Fault Status Gas 2594 Spark Plug 2 (B1) Low Warning NONE PC 3.x
Bitmap 35

40465 8 Fault Status Gas 2595 Spark Plug 3 (A2) Low Warning NONE PC 3.x
Bitmap 35

40465 9 Fault Status Gas 2596 Spark Plug 4 (B2) Low Warning NONE PC 3.x
Bitmap 35

40465 10 Fault Status Gas 2597 Spark Plug 5 (A3) Low Warning NONE PC 3.x
Bitmap 35

40465 11 Fault Status Gas 2598 Spark Plug 6 (B3) Low Warning NONE PC 3.x
Bitmap 35

40465 12 Fault Status Gas 2646 HT Coolant Temperature Condition Warning PC 3.x
Bitmap 35 Exists

40466 0 Fault Status Gas 3262 Spark Plug 7 (A4) High Warning NONE PC 3.x
Bitmap 36

40466 1 Fault Status Gas 3263 Spark Plug 7 (A4) Low Warning NONE PC 3.x
Bitmap 36

40466 2 Fault Status Gas 3264 Spark Plug 8 (B4) High Warning NONE PC 3.x
Bitmap 36

40466 3 Fault Status Gas 3265 Spark Plug 8 (B4) Low Warning NONE PC 3.x
Bitmap 36

40466 4 Fault Status Gas 3266 Spark Plug 9 (A5) High Warning NONE PC 3.x
Bitmap 36

40466 5 Fault Status Gas 3267 Spark Plug 9 (A5) Low Warning NONE PC 3.x
Bitmap 36

40466 6 Fault Status Gas 3268 Spark Plug 10 (B5) High Warning NONE PC 3.x
Bitmap 36

40466 7 Fault Status Gas 3269 Spark Plug 10 (B5) Low Warning NONE PC 3.x
Bitmap 36

40466 8 Fault Status Gas 3271 Spark Plug 11 (A6) High Warning NONE PC 3.x
Bitmap 36

40466 9 Fault Status Gas 3272 Spark Plug 11 (A6) Low Warning NONE PC 3.x
Bitmap 36

40466 10 Fault Status Gas 3273 Spark Plug 12 (B6) High Warning NONE PC 3.x
Bitmap 36

374 A029X159 (Issue 14)


10-2015 5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Addr. Bit# Name Fault Event Name Response Control


Code

40466 11 Fault Status Gas 3274 Spark Plug 12 (B6) Low Warning NONE PC 3.x
Bitmap 36

40466 12 Fault Status Gas 3275 Spark Plug 13 (A7) High Warning NONE PC 3.x
Bitmap 36

40466 13 Fault Status Gas 3276 Spark Plug 13 (A7) Low Warning NONE PC 3.x
Bitmap 36

40466 14 Fault Status Gas 3277 Spark Plug 14 (B7) High Warning NONE PC 3.x
Bitmap 36

40466 15 Fault Status Gas 3278 Spark Plug 14 (B7) Low Warning NONE PC 3.x
Bitmap 36

40467 0 Fault Status Gas 3279 Spark Plug 15 (A8) High Warning NONE PC 3.x
Bitmap 37

40467 1 Fault Status Gas 3281 Spark Plug 15 (A8) Low Warning NONE PC 3.x
Bitmap 37

40467 2 Fault Status Gas 3282 Spark Plug 16 (B8) High Warning NONE PC 3.x
Bitmap 37

40467 3 Fault Status Gas 3283 Spark Plug 16 (B8) Low Warning NONE PC 3.x
Bitmap 37

40467 4 Fault Status Gas 3284 Spark Plug 17 (A9) High Warning NONE PC 3.x
Bitmap 37

40467 5 Fault Status Gas 3285 Spark Plug 17 (A9) Low Warning NONE PC 3.x
Bitmap 37

40467 6 Fault Status Gas 3286 Spark Plug 18 (B9) High Warning NONE PC 3.x
Bitmap 37

40467 7 Fault Status Gas 3287 Spark Plug 18 (B9) Low Warning NONE PC 3.x
Bitmap 37

40467 8 Fault Status Gas 3288 Exhaust Aft Outlet Oxygen Relay Warning PC 3.x
Bitmap 37 OORH

40467 9 Fault Status Gas 3289 Exhaust Aft Outlet Oxygen Relay Warning PC 3.x
Bitmap 37 OORL

40467 10 Fault Status Gas 3291 Exhaust Aft Inlet Oxygen Relay Warning PC 3.x
Bitmap 37 OORH

40467 11 Fault Status Gas 3292 Exhaust Aft Inlet Oxygen Relay Warning PC 3.x
Bitmap 37 OORL

40467 12 Fault Status Gas 3293 Exhaust Oxygen Relay OORH Warning PC 3.x
Bitmap 37

40467 13 Fault Status Gas 3294 Exhaust Oxygen Relay OORL Warning PC 3.x
Bitmap 37

40468 3 Fault Status Gas 3365 External Air Pressure Low Warning Warning PC 3.x
Bitmap 38 Error

40468 4 Fault Status Gas 3384 Manifold_Absolute_Pressure_2_High Warning PC 3.x


Bitmap 38 _Error

40468 5 Fault Status Gas 3391 Manifold_Absolute_Pressure_2_Low Warning PC 3.x


Bitmap 38 _Error

40468 6 Fault Status Gas 3392 Int Man Pressure 2 Critical High Shutdown PC 3.x
Bitmap 38 w/Cooldown

40468 7 Fault Status Gas 3393 Int Man Pressure 2 Moderate High Warning PC 3.x
Bitmap 38

A029X159 (Issue 14) 375


5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 10-2015

Addr. Bit# Name Fault Event Name Response Control


Code

40468 9 Fault Status Gas 3397 Low Gearbox Oil Pressure - Shutdown PC 3.x
Bitmap 38 Condition Exists

40468 10 Fault Status Gas 3398 High Gearbox Oil Temperature - Shutdown PC 3.x
Bitmap 38 Condition Exists w/Cooldown

40468 11 Fault Status Gas 3399 Differential Fault - Condition Exists Shutdown PC 3.x
Bitmap 38

40468 12 Fault Status Gas 3411 DC Power Supply Fault - Condition Warning PC 3.x
Bitmap 38 Exists

40468 13 Fault Status Gas 3412 GIB Isolator Open Fault - Condition Warning PC 3.x
Bitmap 38 Exists

40468 14 Fault Status Gas 3413 Radiator Fan Trip Fault - Condition Warning PC 3.x
Bitmap 38 Exists

40468 15 Fault Status Gas 3414 Ventilator Fan Trip Fault - Condition Warning PC 3.x
Bitmap 38 Exists

40469 0 Fault Status Gas 3415 Louvres Closed Fault - Condition Warning PC 3.x
Bitmap 39 Exists

40469 1 Fault Status Gas 3416 Start System Fault - Condition Exists Warning PC 3.x
Bitmap 39

40469 2 Fault Status Gas 3417 Alternator Heater Trip Fault - Warning PC 3.x
Bitmap 39 Condition Exists

40469 4 Fault Status Gas 9971 ECM Derate Fault NONE PC 3.x
Bitmap 39

40469 5 Fault Status Gas 3479 Start-Inhibit Shutdown Fault Shutdown PC 3.x
Bitmap 39

40469 6 Fault Status Gas 3481 Start-Inhibit Warning Fault Event Warning PC 3.x
Bitmap 39

40469 7 Fault Status Gas 3483 High Alternator Temperature 1 Shutdown PC 3.x
Bitmap 39 Shutdown Fault

40469 8 Fault Status Gas 3484 High Alternator Temperature 2 Shutdown PC 3.x
Bitmap 39 Shutdown Fault

40469 9 Fault Status Gas 3485 High Alternator Temperature 3 Shutdown PC 3.x
Bitmap 39 Shutdown Fault

40469 10 Fault Status Gas 3486 High Drive End Bearing Temperature Shutdown PC 3.x
Bitmap 39 Shutdown Fault

40469 11 Fault Status Gas 3487 High Non-Drive End Bearing Temp Shutdown PC 3.x
Bitmap 39 Shutdown Fault

40469 12 Fault Status Gas 3482 Off Load Running Fault Shutdown PC 3.x
Bitmap 39

40470 0 Fault Status Gas 3491 Oil Filter Restriction High Shutdown PC 3.x
Bitmap 40 w/Cooldown

40470 1 Fault Status Gas 2313 Fuel Control Valve Error Warning PC 3.x
Bitmap 40

40470 2 Fault Status Gas 3475 Engine Electronic Fuel Valve #2 Warning PC 3.x
Bitmap 40 OORH

40470 3 Fault Status Gas 3476 Engine Electronic Fuel Valve #2 Warning PC 3.x
Bitmap 40 OORL

40470 4 Fault Status Gas 2812 Throttle Control Actuator Error Shutdown PC 3.x
Bitmap 40 w/Cooldown

376 A029X159 (Issue 14)


10-2015 5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Addr. Bit# Name Fault Event Name Response Control


Code

40470 5 Fault Status Gas 3489 Compressor Bypass Actuator Error Warning PC 3.x
Bitmap 40

40470 6 Fault Status Gas 3458 Knock Engine Derate Warning PC 3.x
Bitmap 40

40470 8 Fault Status Gas 3499 Throttle Actuator 2- Special Shutdown PC 3.x
Bitmap 40 Instruction w/Cooldown

40470 9 Fault Status Gas 3511 Throttle Actuator 2- Shorted High Shutdown PC 3.x
Bitmap 40 w/Cooldown

40470 10 Fault Status Gas 3512 Throttle Actuator 2- Shorted Low Shutdown PC 3.x
Bitmap 40 w/Cooldown

40470 11 Fault Status Gas 2752 Throttle Actuator - Shorted High Shutdown PC 3.x
Bitmap 40 w/Cooldown

40470 12 Fault Status Gas 3514 Throttle Actuator - Shorted Low Shutdown PC 3.x
Bitmap 40 w/Cooldown

40470 13 Fault Status Gas 3515 Throttle Actuator - Special instruction Shutdown PC 3.x
Bitmap 40 w/Cooldown

40470 14 Fault Status Gas 3521 Throttle Actuator - Temperature low Warning PC 3.x
Bitmap 40

40470 15 Fault Status Gas 3522 Throttle Actuator 2- Temp low Warning PC 3.x
Bitmap 40

40474 10 Fault Status Gas 4686 Connector Cap Not Present Warning PC 3.x
Bitmap 40

A029X159 (Issue 14) 377


5. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps 10-2015

This page is intentionally blank.

378 A029X159 (Issue 14)


6 NFPA 110 and Extended Annunciation
Bitmap
TABLE 2. NFPA110 BITMAP

Bit Description
15 Common Alarm
14 Genset Supplying Load
13 Genset Running
12 Not in Auto
11 High Battery Voltage
10 Low Battery Voltage
9 Charger AC Failure
8 Fail to Start
7 Low Coolant Temperature
6 Pre–high Engine Temperature
5 High Engine Temperature
4 Pre–low Oil Pressure
3 Low Oil Pressure
2 Overspeed
1 Low Coolant Level
0 Low Fuel Level

See Chapter 3 Reg. 40016, Section 4.2 Reg. 40716, 40717, and Chapter 7

TABLE 3. EXTENDED ANNUNCIATION BITMAP

Bit Description
15 Check Genset
14 Ground Fault
13 High AC Voltage
12 Low AC Voltage
11 Under Frequency
10 Overload
9 Overcurrent
8 Short Circuit
7 Reverse KW
6 Reverse kVAR
5 Fail to Sync

A029X159 (Issue 14) 379


6. NFPA 110 and Extended Annunciation Bitmap 10-2015

Bit Description
4 Fail to Close
3 Load Demand
2 Genset Circuit Breaker Tripped
1 Utility Circuit Breaker Tripped
0 Emergency Stop

SeeChapter 3 Reg. 40017 and Chapter 7

TABLE 4. NFPA110 BITMAP

Bit Description
15 Source 1 Connected
14 Source 2 Connected
13 NA
12 Not in Auto
11 NA
10 NA
9 Charger AC Failure
8 NA
7 NA
6 NA
5 NA
4 NA
3 NA
2 NA
1 NA
0 NA

See Chapter 8

TABLE 5. EXTENDED ANNUNCIATION BITMAP

Bit Description
15 Source 1 Available
14 Source 2 Available
13 Source 1 Connected
12 Source 2 Connected
11 ATS Common Alarm
10 Not In Auto
9 Test / Exercise In Progress
8 Low Battery Voltage

380 A029X159 (Issue 14)


10-2015 6. NFPA 110 and Extended Annunciation Bitmap

Bit Description
7 Load Shed
6 Transfer Inhibit
5 Retransfer Inhibit
4 Fail To Close
3 Fail To Disconnect
2 Fail To Synchronize
1 Bypass to Source 1
0 Bypass to Source 2

See Chapter 8

A029X159 (Issue 14) 381


6. NFPA 110 and Extended Annunciation Bitmap 10-2015

This page is intentionally blank.

382 A029X159 (Issue 14)


7 DMC 1000 Modbus Parametric Data
NOTICE
Earlier versions of software may not support all of the Modbus registers in the following table. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

Addr System Name Access Specifications Description Function


Multiplier: Unit:
1.000000000000 Lower Limit: .000 Logical address
MB Logical Read/ Offset: 0
42001 Read Address Write Upper Limit: to be read via Communications
Size (bits): 16 65535.000 Modbus
Sign: U Default: 0
Multiplier: Unit:
1.000000000000 Logical data to
MB Logical Read Lower Limit:
42002 Read Data Offset: 0 be read via Communications
Only Upper Limit:
Size (bits): 32 Modbus
Default:
Sign: U
Multiplier: Unit:
1.000000000000 Hard coded
Read Lower Limit:
42009 Device Type Offset: 0 device type id = Communications
Only Upper Limit:
Size (bits): 16 52 (0x0034)
Default:
Sign: U
Multiplier: Unit:
0.000100000000
Software Read Lower Limit: Software version Controller
42010 Version Offset: 0
Only Upper Limit: number Information
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: The most
1.000000000000 recently
Current Fault Read Lower Limit: Fault and Event
42012 Status Offset: 0 occurring fault
Only Upper Limit: Info
Size (bits): 16 which is still
Default: active
Sign: U
Multiplier: Unit: Volts
1.000000000000
Genset L1N Read Lower Limit: Generator set
42018 Voltage Offset: 0 Voltage
Only Upper Limit: L1N voltage
Size (bits): 16
Default
Sign: U
Multiplier:
1.000000000000 Unit: Volts
Offset: 0 Lower Limit:
42019 Genset L2N Read Generator set Voltage
Voltage Only Size (bits): 16 Upper Limit: L2N voltage
Sign: U Default

A029X159 (Issue 14) 383


7. DMC 1000 Modbus Parametric Data 10-2015

Addr System Name Access Specifications Description Function


Multiplier: Unit: Volts
1.000000000000
Genset L3N Read Lower Limit: Generator set
42020 Voltage Offset: 0 Voltage
Only Upper Limit: L3N voltage
Size (bits): 16
Default
Sign: U
Multiplier: Unit: Volts
Genset LN 1.000000000000 Generator set
Read Lower Limit:
42021 Average Offset: 0 LN average Voltage
Only Upper Limit:
Voltage Size (bits): 16 voltage
Default
Sign: U
Multiplier: Unit: Volts
1.000000000000
Genset L1L2 Read Lower Limit: Generator set
42022 Voltage Offset: 0 Voltage
Only Upper Limit: L1L2 voltage
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: Volts
1.000000000000
Genset L2L3 Read Lower Limit: Generator set
42023 Voltage Offset: 0 Voltage
Only Upper Limit: L2L3 voltage
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: Volts
1.000000000000
Genset L3L1 Read Lower Limit: Generator set
42024 Voltage Offset: 0 Voltage
Only Upper Limit: L3L1 voltage
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: Volts
Genset LL 1.000000000000 Generator set
Read Lower Limit:
42025 Average Offset: 0 LL average Voltage
Only Upper Limit:
Voltage Size (bits): 16 voltage
Default:
Sign: U
Multiplier: Unit: Amps
1.000000000000
Genset L1 Read Lower Limit: Generator set
42026 Current Offset: 0 Current
Only Upper Limit: L1 current
Size (bits): 16
Default
Sign: U
Multiplier: Unit: Amps
1.000000000000
Genset L2 Read Lower Limit: Generator set
42027 Current Offset: 0 Current
Only Upper Limit: L2 current
Size (bits): 16
Default
Sign: U
Multiplier: Unit: Amps
1.000000000000
Genset L3 Read Lower Limit: Generator set
42028 Current Offset: 0 Current
Only Upper Limit: L3 current
Size (bits): 16
Default
Sign: U
Multiplier: Unit: Amps
Genset 1.000000000000
Read Lower Limit: Generator set
42029 Average Offset: 0 Current
Only Upper Limit: average current
Current Size (bits): 16
Default
Sign: U

384 A029X159 (Issue 14)


10-2015 7. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function


Multiplier: Unit: kW
1.000000000000
Read Lower Limit: Generator set
42030 Genset L1 kW Offset: 0 Current
Only Upper Limit: L1 kW
Size (bits): 16
Default:
Sign: S
Multiplier: Unit: kW
1.000000000000
Read Lower Limit: Generator set
42031 Genset L2 kW Offset: 0 Current
Only Upper Limit: L2 kW
Size (bits): 16
Default:
Sign: S
Multiplier: Unit: kW
1.000000000000
Read Lower Limit: Generator set
42032 Genset L3 kW Offset: 0 Power
Only Upper Limit: L3 kW
Size (bits): 16
Default:
Sign: S
Multiplier: Unit: kW
1.000000000000
Genset Total Read Lower Limit: Generator set
42033 kW Offset: 0 Power
Only Upper Limit: total kW
Size (bits): 16
Default:
Sign: S
Multiplier: Unit: kVAR
1.000000000000
Genset L1 Read Lower Limit: Generator set
42034 kVAR Offset: 0 Power
Only Upper Limit: L1 kVAR
Size (bits): 16
Default:
Sign: S
Multiplier: Unit: kVAR
1.000000000000
Genset L2 Read Lower Limit: Generator set
42035 kVAR Offset: 0 Power
Only Upper Limit: L2 kVAR
Size (bits): 16
Default:
Sign: S
Multiplier: Unit: kVAR
1.000000000000
Genset L3 Read Lower Limit: Generator set
42036 kVAR Offset: 0 Power
Only Upper Limit: L3 kVAR
Size (bits): 16
Default:
Sign: S
Multiplier: Unit: kVAR
1.000000000000
Genset Total Read Lower Limit: Generator set
42037 kVAR Offset: 0 Power
Only Upper Limit: total kVAR
Size (bits): 16
Default:
Sign: S
Multiplier: Unit:
0.010000000000 Generator set
Genset Total Read Lower Limit:
42038 Power Factor Offset: 0 total power Power
Only Upper Limit:
Size (bits): 8 factor
Default:
Sign: S
Multiplier: Unit: kVA
1.000000000000
Read Lower Limit: Generator set
42039 Genset L1 kVA Only Offset: 0 Power
Upper Limit: L1 kVA
Size (bits): 16
Default:
Sign: U

A029X159 (Issue 14) 385


7. DMC 1000 Modbus Parametric Data 10-2015

Addr System Name Access Specifications Description Function


Multiplier: Unit: kVA
1.000000000000
Read Lower Limit: Generator Set
42040 Genset L2 kVA Only Offset: 0 Power
Upper Limit: L2 kVA
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: kVA
1.000000000000
Read Lower Limit: Generator set
42041 Genset L3 kVA Only Offset: 0 Power
Upper Limit: L3 kVA
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: kVA
1.000000000000
Genset Total Read Lower Limit: kVA Generator set
42042 kVA Offset: 0 Power
Only Upper Limit: kVA total kVA
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: Hz
0.100000000000 Generator set
MB Genset Read Lower Limit: Hz line frequency
42043 Frequency Offset: 0 Communications
Only Upper Limit: Hz scaled by 10 =
Size (bits): 16 1Hz for Modbus
Default:
Sign: U
Multiplier: Unit: kWh
1.000000000000 Generator set
Genset Total Read Lower Limit: kWh total negative
42044 Negative kWh Offset: 0 Energy
Only Upper Limit: kWh kWh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier: Unit: kWh
.100000000000 Generator set
Genset Total Read Lower Limit: kWh total positive
42046 Positive kWh Offset: 0 Energy
Only Upper Limit: kWh kWh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier: Unit: kWh
1.000000000000 Generator set
Genset Total Read Lower Limit: kWh
42048 Net kWh Offset: 0 total net kWh Energy
Only Upper Limit: kWh
Size (bits): 32 accumulation
Default:
Sign: S
Multiplier: Unit: kVARh
1.000000000000 Generator set
Genset Total Read Lower Limit: kVARh total negative
42050 Negative Offset: 0 Energy
Only Upper Limit: kVARh kVARh
kVARh Size (bits): 32 accumulation
Default:
Sign: U
Multiplier: Unit: kVARh
1.000000000000 Generator set
Genset Total Read Lower Limit: kVARh total positive
42052 Positive kVARh Only Offset: 0 Energy
Upper Limit: kVARh kVARh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier: Unit: kVARh
1.000000000000 Generator set
Genset Total Read Lower Limit: kVARh
42054 Net kVARh Offset: 0 total net kVARh Energy
Only Upper Limit: kVARh
Size (bits): 32 accumulation
Default:
Sign: S

386 A029X159 (Issue 14)


10-2015 7. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function


Multiplier: Unit: kVAh
1.000000000000 Generator set
Genset Total Read Lower Limit: kVAh
40056 kVAh Offset: 0 total kVAh Energy
Only Upper Limit: kVAh
Size (bits): 32 accumulation
Default:
Sign: U
Calculated
Multiplier: Unit: Amps Amps which
Genset 1.000000000000 represent 100%
Read Lower Limit:
42058 Available Offset: 0 generator set Current
Only Upper Limit:
Current Size (bits): 16 bus current --
Default: used by
Sign: U
barograph
Generator set
Multiplier: Unit: % L1 current as
Genset L1 0.100000000000 percent of
Read Lower Limit:
42059 Current Offset: 0 generator set Current
Only Upper Limit:
Percent Size (bits): 16 total current
Default: capacity--used
Sign: U
by barograph
Generator set
Multiplier: Unit: % L2 current as
Genset L2 0.100000000000 percent of
Read Lower Limit:
42060 Current Offset: 0 generator set Current
Only Upper Limit:
Percent Size (bits): 16 total current
Default: capacity--used
Sign: U
by barograph
Generator set
Multiplier: Unit: % L3 current as
Genset L3 0.100000000000 percent of
Read Lower Limit:
42061 Current Offset: 0 generator set Current
Only Upper Limit:
Percent Size (bits): 16 total current
Default: capacity--used
Sign: U
by barograph
Multiplier: Generator set
0.100000000000 Unit: % total kW as
Lower Limit:
42062 Genset Total Read Offset: 0 percent of total Power
kW Percent Only Upper Limit: generator set
Size (bits): 16 capacity -- used
Sign: S Default:
by barograph
Generator set
Multiplier: Unit: % frequency as
Genset 0.100000000000 percent of
Read Lower Limit:
42063 Frequency Offset: 0 system Frequency
Only Upper Limit:
Percent Size (bits): 16 frequency --
Default: used by
Sign: U
barograph
Multiplier: Unit: %
0.100000000000
Genset L1L2 Read Lower Limit: Generator set
42064 Voltage% Offset: 0 Voltage
Only Upper Limit: L1L2 voltage%
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: %
0.100000000000
Genset L2L3 Read Lower Limit: Generator set
42065 Voltage% Offset: 0 Voltage
Only Upper Limit: L2L3 voltage%
Size (bits): 16
Default:
Sign: U

A029X159 (Issue 14) 387


7. DMC 1000 Modbus Parametric Data 10-2015

Addr System Name Access Specifications Description Function


Multiplier: Unit: %
0.100000000000
Genset L3L1 Read Lower Limit: Generator set
42066 Voltage% Offset: 0 Voltage
Only Upper Limit: L3L1 voltage%
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: Volts
1.000000000000
Utility L1N Read Lower Limit: Utility L1N
42118 Voltage Offset: 0 Voltage
Only Upper Limit: voltage
Size (bits): 16
Default: 0
Sign: U
Multiplier: Unit: Volts
1.000000000000
Utility L2N Read Lower Limit: Utility L2N
42119 Voltage Offset: 0 Voltage
Only Upper Limit: voltage
Size (bits): 16
Default: 0
Sign: U
Multiplier: Unit: Volts
1.000000000000
Utility L3N Read Lower Limit: Utility L3N
42120 Voltage Offset: 0 Voltage
Only Upper Limit: voltage
Size (bits): 16
Default: 0
Sign: U
Multiplier: Unit: Volts
Utility LN 1.000000000000
Read Lower Limit: Utility LN
42121 Average Offset: 0 Voltage
Only Upper Limit: average voltage
Voltage Size (bits): 16
Default: 0
Sign: U
Multiplier: Unit: Volts
1.000000000000
Utility L1L2 Read Lower Limit: Utility L1L2
42122 Voltage Offset: 0 Voltage
Only Upper Limit: voltage
Size (bits): 16
Default: 0
Sign: U
Multiplier: Unit: Volts
1.000000000000
Utility L2L3 Read Lower Limit: Utility L2L3
42123 Voltage Offset: 0 Voltage
Only Upper Limit: voltage
Size (bits): 16
Default: 0
Sign: U
Multiplier: Unit: Volts
1.000000000000
Utility L3L1 Read Lower Limit: Utility L3L1
42124 Voltage Offset: 0 Voltage
Only Upper Limit: voltage
Size (bits): 16
Default: 0
Sign: U
Multiplier: Unit: Volts
Utility LL 1.000000000000
Read Lower Limit: Utility LL
42125 Average Offset: 0 Voltage
Only Upper Limit: average voltage
Voltage Size (bits): 16
Default: 0
Sign: U
Multiplier: Unit: Amps
1.000000000000
Utility L1 Read Lower Limit:
42126 Current Offset: 0 Utility L1 current Current
Only Upper Limit:
Size (bits): 16
Default:
Sign: U

388 A029X159 (Issue 14)


10-2015 7. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function


Multiplier: Unit: Amps
1.000000000000
Utility L2 Read Lower Limit:
42127 Current Offset: 0 Utility L2 current Current
Only Upper Limit:
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: Amps
1.000000000000
Utility L3 Read Lower Limit:
42128 Current Offset: 0 Utility L3 current Current
Only Upper Limit:
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: Amps
1.000000000000
Utility Average Read Lower Limit: Utility average
42129 Current Offset: 0 Current
Only Upper Limit: current
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: kW
1.000000000000
Read Lower Limit:
42130 Utility L1 kW Offset: 0 Utility L1 kW Power
Only Upper Limit:
Size (bits): 16
Default:
Sign: S
Multiplier: Unit: kW
1.000000000000
Read Lower Limit:
42131 Utility L2 kW Offset: 0 Utility L2 kW Power
Only Upper Limit:
Size (bits): 16
Default
Sign: S
Multiplier: Unit: kW
1.000000000000
Read Lower Limit:
42132 Utility L3 kW Offset: 0 Utility L3 kW Power
Only Upper Limit:
Size (bits): 16
Default
Sign: S
Multiplier: Unit: kW
1.000000000000
Read Lower Limit:
42133 Utility Total kW Only Offset: 0 Utility total kW Power
Upper Limit:
Size (bits): 16
Default
Sign: S
Multiplier: Unit: kVAR
1.000000000000
Utility L1 Read Lower Limit:
42134 kVARt Offset: 0 Utility L1 kVAR Power
Only Upper Limit:
Size (bits): 16
Default
Sign: S
Multiplier: Unit: kVAR
1.000000000000
Read Lower Limit:
42135 Utility L2 kVAR Only Offset: 0 Utility L2 kVAR Power
Upper Limit:
Size (bits): 16
Default
Sign: S
Multiplier: Unit: kVAR
1.000000000000
Read Lower Limit:
42136 Utility L3 kVAR Only Offset: 0 Utility L3 kVAR Power
Upper Limit:
Size (bits): 16
Default:
Sign: S

A029X159 (Issue 14) 389


7. DMC 1000 Modbus Parametric Data 10-2015

Addr System Name Access Specifications Description Function


Multiplier: Unit: kVAR
1.000000000000
Utility Total Read Lower Limit:
42137 kVAR Offset: 0 Utility total kVAR Power
Only Upper Limit:
Size (bits): 16
Default:
Sign: S
Multiplier: Unit:
.010000000000
Utility Total Read Lower Limit: Utility total
42138 Power Factor Offset: 0 Power
Only Upper Limit: power factor
Size (bits): 8
Default:
Sign: S
Multiplier: Unit: kVA
1.000000000000
Read Lower Limit:
42139 Utility L1 kVA Offset: 0 Utility L1 kVA Power
Only Upper Limit:
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: kVA
1.000000000000
Read Lower Limit:
42140 Utility L2 kVA Offset: 0 Utility L2 kVA Power
Only Upper Limit:
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: kVA
1.000000000000
Read Lower Limit:
42141 Utility L3 kVA Offset: 0 Utility L3 kVA Power
Only Upper Limit:
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: kVA
1.000000000000
Utility Total Read Lower Limit:
42142 kVA Offset: 0 Utility total kVA Power
Only Upper Limit:
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: Hz
.100000000000 Utility line
MB Utility Read Lower Limit: frequency
42143 Frequency Offset: 0 Communications
Only Upper Limit: scaled by 10 =
Size (bits): 16 1Hz for Modbus
Default:
Sign: U
Multiplier: Unit: kWh
1.000000000000 Utility total
Utility Total Read Lower Limit:
42144 Negative kWh Offset: 0 negative kWh Energy
Only Upper Limit:
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier: Unit: kWh
1.000000000000 Utility total
Utility Total Read Lower Limit:
42146 Positive kWh Offset: 0 positive kWh Energy
Only Upper Limit:
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier: Unit: kWh
1.000000000000 Utility total net
Utility Total Net Read Lower Limit:
42148 kWh Offset: 0 kWh Energy
Only Upper Limit:
Size (bits): 32 accumulation
Default:
Sign: S

390 A029X159 (Issue 14)


10-2015 7. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function


Multiplier: Unit: kVARh
Utility Total 1.000000000000 Utility total
Read Lower Limit:
42150 Negative Offset: 0 negative kVARh Energy
Only Upper Limit:
kVARh Size (bits): 32 accumulation
Default:
Sign: U
Multiplier: Unit: kVARh
1.000000000000 Utility total
Utility Total Read Lower Limit:
42152 Positive kVARh Only Offset: 0 positive kVARh Energy
Upper Limit: accumulation
Size (bits): 32
Default:
Sign: U
Multiplier: Unit: kVARh
1.000000000000 Utility total net
Utility Total Net Read Lower Limit:
42154 kVARh Offset: 0 kVARh Energy
Only Upper Limit:
Size (bits): 32 accumulation
Default:
Sign: S
Multiplier: Unit: kVARh
1.000000000000
Utility Total Read Lower Limit: Utility total kVAh
42156 kVAh Offset: 0 Energy
Only Upper Limit: accumulation
Size (bits): 32
Default:
Sign: U
Multiplier: Unit: kW
1.000000000000 Sum of
System Total Read Lower Limit: generator set
42158 kW Offset: 0 Power
Only Upper Limit: bus and utility
Size (bits): 16 bus kW
Default:
Sign: S
Multiplier: Unit: kVAR
1.000000000000 Sum of
System Total Read Lower Limit: generator set
42159 kVAR Offset: 0 Power
Only Upper Limit: bus and utility
Size (bits): 16 bus kVAR
Default:
Sign: S
Multiplier: System total
0.010000000000 Unit: power factor
Lower Limit:
42160 System Total Read Offset: 0 (totalized value Power
Power Factor Only Upper Limit: of utility bus plus
Size (bits): 8 generator set
Sign: S Default:
bus)
Multiplier: Unit: kVA
1.000000000000 Sum of
System Total Read Lower Limit: generator set
42161 kVA Offset: 0 Power
Only Upper Limit: bus and utility
Size (bits): 16 bus kVA
Default:
Sign: U
Multiplier: Unit: %
Utility L1 .100000000000
Read Lower Limit:
42162 Current Offset: 0 barograph Current
Only Upper Limit:
Percent Size (bits): 16
Default:
Sign: U
Multiplier: Unit: %
Utility L2 .100000000000
Read Lower Limit:
42163 Current Offset: 0 barograph Current
Only Upper Limit:
Percent Size (bits): 16
Default:
Sign: U

A029X159 (Issue 14) 391


7. DMC 1000 Modbus Parametric Data 10-2015

Addr System Name Access Specifications Description Function


Multiplier:
.100000000000 Unit: %
Utility L3 Offset: 0 Lower Limit:
42164 Current Read barograph Current
Percent Only Size (bits): 16 Upper Limit:
Sign: U Default:

Multiplier:
.100000000000 Unit: % Utility total kW
Offset: 0 Lower Limit: as percent of
42165 Utility Total kW Read total utility Power
Percent Only Size (bits): 16 Upper Limit: capacity -- used
Sign: S Default: by barograph

Multiplier: Unit: % Utility frequency


.100000000000 Lower Limit: as percent of
Utility Read System
42166 Frequency Offset: 0 Upper Limit: Frequency
Only Frequency --
Percent Size (bits): 16 Default: used by
Sign: U barograph
Multiplier: Unit: %
.100000000000
Utility L1L2 Read Lower Limit: Utility L1L2
42167 Voltage% Offset: 0 Voltage
Only Upper Limit: voltage%
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: %
.100000000000
Utility L2L3 Read Lower Limit: Utility L2L3
42168 Voltage% Offset: 0 Voltage
Only Upper Limit: voltage%
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: %
.100000000000
Utility L3L1 Read Lower Limit: Utility L3L1
42169 Voltage% Offset: 0 Voltage
Only Upper Limit: voltage%
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: NA
1.000000000000 Number of
Total Number Read Lower Limit: generator sets System
42200 of Gensets Offset: 0
Only Upper Limit: with non-zero Information
Size (bits): 16 ratings entered
Default:
Sign: U
Multiplier: Unit: kW
1.000000000000 Sum of the
Total System Read Lower Limit: System
42201 Capacity Offset: 0 generator set
Only Upper Limit: Information
Size (bits): 16 kW ratings
Default:
Sign: S
Multiplier: Unit: kW Sum of the
1.000000000000 generator set
Total Online Read Lower Limit: System
42202 Capacity Offset: 0 kW ratings for
Only Upper Limit: Information
Size (bits): 16 generator sets
Default: which are online
Sign: S

392 A029X159 (Issue 14)


10-2015 7. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function


Multiplier: Unit: seconds
.100000000000 Countdown
Programmed Read Lower Limit: value of the
42203 Transition Offset: 0 PTC Timers
Only Upper Limit: programmed
Timer Size (bits): 16 transition timer
Default:
Sign: U
Multiplier: Unit: seconds
.100000000000 Countdown
Read Lower Limit:
42204 Transfer Timer Offset: 0 value of the PTC Timers
Only Upper Limit:
Size (bits): 16 transfer timer
Default: 0
Sign: U
Multiplier: Unit: seconds
.100000000000 Countdown
Retransfer Read Lower Limit:
42205 Timer Offset: 0 value of the PTC Timers
Only Upper Limit:
Size (bits): 16 retransfer timer
Default:
Sign: U
Multiplier: Unit: seconds
.100000000000 Countdown
Maximum Read Lower Limit: value of the
42206 Parallel Timer Offset: 0 PTC Timers
Only Upper Limit: maximum
Size (bits): 16 parallel timer
Default:
Sign: U
Multiplier: Unit: kW
1.000000000000 kW control
kW Load Read Lower Limit: reference value Master Load
42207 Reference Offset: 0
Only Upper Limit: for utility Control
Size (bits): 16 paralleling
Default:
Sign: S
Multiplier: Unit: seconds
Active .010000000000 Countdown
Read Lower Limit:
42212 Transition Offset: 0 timer value of PTC Timers
Only Upper Limit:
Timer Size (bits): 16 active timer
Default:
Sign: U
Multiplier: Unit:
1.000000000000 Indicates the
Hardware Read Lower Limit: hardware
42213 Version Offset: 0 Discrete Inputs
Only Upper Limit: version of the
Size (bits): 8 board
Default:
Sign: U
Multiplier: Unit: seconds
1.000000000000 Lower Limit: 0.000 Amount of time
Controller On Read Offset: 0 in seconds Controller
42214 Time Only Upper Limit: controller has Information
Size (bits): 32 4294967295.000 been powered
Sign: U Default: 0.000
Multiplier: Unit: kVAR
1.000000000000 kVAR control
kVAR Load Read Lower Limit: reference value Master Load
42220 Reference Offset: 0
Only Upper Limit: for extended Control
Size (bits): 16 paralleling
Default:
Sign: S
Multiplier: Unit: % Engineering
kVAR Load .010000000000
Setpoint Engr Read Lower Limit: units value for
42221 Units Display Offset: 0 the kVAR load Analog Inputs
Only Upper Limit:
Value Size (bits): 16 setpoint analog
Default input
Sign: S

A029X159 (Issue 14) 393


7. DMC 1000 Modbus Parametric Data 10-2015

Addr System Name Access Specifications Description Function


Multiplier: Unit: % Engineering
kW Load .010000000000
Setpoint Engr Read Lower Limit: units value for
42222 Units Display Offset: 0 the kW load Analog Inputs
Only Upper Limit:
Value Size (bits): 16 setpoint analog
Default: input
Sign: S
Multiplier: Power factor
.010000000000 Unit: setpoint analog
Lower Limit:
42223 Power Factor Read Offset: 0 input value Analog Inputs
Setpoint Only Upper Limit: (uses kVAR load
Size (bits): 8 setpoint analog
Sign: S Default:
input)
Multiplier: Unit: degrees
.010000000000 Utility to
Sync Phase Read Lower Limit: generator set L1
42226 Difference Offset: 0 Phase
Only Upper Limit: voltage phase
Size (bits): 16 angle
Default:
Sign: S
Multiplier: Unit:
1.000000000000
Current Add Read Lower Limit: Indicates the Load Add Shed
42250 Level Offset: 0
Only Upper Limit: next level to add Control
Size (bits): 8
Default:
Sign: U
Multiplier: Unit:
1.000000000000 Indicates the
Current Shed Read Lower Limit: Load Add Shed
42251 Level Offset: 0 next level to
Only Upper Limit: Control
Size (bits): 8 shed
Default
Sign: U
Multiplier: Unit: VDC Engineering
Battery Voltage Read .010000000000 units value for
Lower Limit:
42291 Engr Units Offset: 0 the battery Analog Inputs
Only Upper Limit:
Display Value Size (bits): 16 voltage analog
Default input
Sign: U
Multiplier:
kVAR Master Unit: VDC Voltage level
.010000000000 commanded to
Load Control Read Lower Limit:
42292 Output Only Offset: 0 kVAR Master Analog Outputs
Upper Limit: load control
Predictor Value Size (bits): 16
Default analog output
Sign: S
Multiplier: Unit: VDC Voltage level
kW Master .010000000000
Load Control Read Lower Limit: commanded to
42293 Output Offset: 0 kW Master load Analog Outputs
Only Upper Limit:
Predictor Value Size (bits): 16 control analog
Default output
Sign: S
Multiplier: Unit: VDC Voltage level
Master .010000000000
Frequency Read Lower Limit: commanded to
42294 Bias Output Offset: 0 Master Analog Outputs
Only Upper Limit:
Predictor Value Size (bits): 16 frequency bias
Default analog output
Sign: S
Multiplier: Unit: VDC Voltage level
Master Voltage Read .010000000000 commanded to
Lower Limit:
42295 Bias Output Offset: 0 Master voltage Analog Outputs
Only Upper Limit:
Predictor Value Size (bits): 16 bias analog
Default: output
Sign: S

394 A029X159 (Issue 14)


10-2015 7. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function


Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 01 kW Read/ Offset: 0 Sets gen1 kW System
42305 Rating Write Upper Limit: 32000.00 rating Information
Size (bits): 16 kW
Sign: S Default: 1000.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 02 kW Read/ Offset: 0 Sets gen2 kW System
42306 Rating Write Upper Limit: 32000.00 rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 03 kW Read/ Offset: 0 Sets gen3 kW System
42307 Rating Write Upper Limit: 32000.00 rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 04 kW Read/ Offset: 0 Sets gen4 kW System
42308 Rating Write Upper Limit: 32000.00 rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 05 kW Read/ Offset: 0 Sets gen5 kW System
42309 Rating Write Upper Limit: 32000.00 rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 06 kW Read/ Offset: 0 Sets gen6 kW System
42310 Rating Write Upper Limit: 32000.00 rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 07 kW Read/ Offset: 0 Sets gen7 kW System
42311 Rating Write Upper Limit: 32000.00 rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 08 kW Read/ Offset: 0 Sets gen8 kW System
42312 Rating Write Upper Limit: 32000.00 rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 09 kW Read/ Offset: 0 Sets gen9 kW System
42313 Rating Write Upper Limit: 32000.00 rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 10 kW Read/ Offset: 0 Sets gen10 kW System
42314 Rating Write Upper Limit: 32000.00 rating Information
Size (bits): 16 kW
Sign: S Default: 0.000

A029X159 (Issue 14) 395


7. DMC 1000 Modbus Parametric Data 10-2015

Addr System Name Access Specifications Description Function


Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 11 kW Read/ Offset: 0 Sets gen11 kW System
42315 Rating Write Upper Limit: 32000.00 rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 12 kW Read/ Offset: 0 Sets gen12 kW System
42316 Rating Write Upper Limit: 32000.00 rating Information
Size (bits): 16 kW
Sign: S Default: 0.000

Multiplier: Unit: seconds


0.100000000000 Lower Limit: 0.000 Sets the
Programmed seconds
42317 Transition Read/ Offset: 0 programmed PTC Timers
Delay (TDPT) Write Upper Limit: 60 transition time
Size (bits): 16 delay
seconds
Sign: U
Default: 3.000

Multiplier: Unit: seconds


0.100000000000 Lower Limit: 0.000
seconds
42318 Transfer Delay Read/ Offset: 0 Sets the transfer PTC Timers
(TDNE) Write Upper Limit: 120 time delay
Size (bits): 16
seconds
Sign: U
Default: 10.000

Multiplier: Unit: seconds


0.100000000000 Lower Limit: 0.000
seconds Sets the
42319 Retransfer Read/ Offset: 0 retransfer time PTC Timers
Delay (TDEN) Write Upper Limit: 1800 delay
Size (bits): 16
seconds
Sign: U
Default: 600.000

Multiplier: Unit seconds


Lower Limit: 0.000 Sets the
Maximum 0.000000000000 maximum
Read/ Offset: 0 seconds
42320 Parallel Time parallel time for PTC Timers
(TDMP) Write Upper Limit: 1800 soft load
Size (bits): 16
seconds transfers
Sign: U
Default: 20.000
Multiplier: Unit: % Sets %kW
.010000000000 Lower Limit: –5.000 % generator set
42321 Genset Bus Read/ Offset: 0 Upper Limit: 105.000
output level for Master Load
%kW Setpoint Write open loop base Control
Size (bits): 16 % load extended
Sign: S Default: 80.000 paralleling

Multiplier: Unit: Volts


1.000000000000 Lower Limit: 110.000
Genset Volts
42322 Nominal Read/ Offset: 0 Generator set AC Setup
Voltage Write Upper Limit: nominal voltage
Size (bits): 16
45000.000 Volts
Sign: U
Default: 480.000

Multiplier: Unit: Volts


1.000000000000 Lower Limit: 110.000
Volts
42323 Utility Nominal Read/ Offset: 0 Utility nominal AC Setup
Voltage Write Upper Limit: voltage
Size (bits): 16
45000.000 Volts
Sign: U
Default: 480.000

396 A029X159 (Issue 14)


10-2015 7. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function


Sets the center
Multiplier: Unit: Hz frequency for
0.100000000000 the generator
Genset Center Read/ Lower Limit: 45.000 Hz
42324 Frequency Offset: 0 set frequency PTC Sensors
Write Upper Limit: 65.000
Size (bits): 16 sensor
Default: 60.000 bandwidth
Sign: U
settings
Sets the center
Multiplier: Unit: Hz frequency for
0.100000000000 the utility
Utility Center Read/ Lower Limit: 45.000 Hz
42325 Frequency Offset: 0 frequency PTC Sensors
Write Upper Limit: 65.000 Hz
Size (bits): 16 sensor
Default: 60.000 bandwidth
Sign: U
settings
Multiplier: Unit: Hz
0.100000000000 Use to define
System Read/ Lower Limit: 45.000 Hz the system System
42327 Frequency Offset: 0
Write Upper Limit: 65.000 Hz nominal Information
Size (bits): 16 frequency
Default: 60.000
Sign: U
Multiplier: Unit: kW Sets the base
1.000000000000 Lower Limit: 0.000 kW load kW setpoint Master Load
Genset Bus Read/ Offset: 0
42330 kW Setpoint Write Upper Limit: in closed loop Control
Size (bits): 16 32767.000 kW extended
Sign: S Default: 0.000 paralleling

Multiplier: Unit: kVAR Sets the base


1.000000000000 Lower Limit: 0.000 load kVAR
kVAR
42331 Genset Bus Read/ Offset: 0 setpoint in Master Load
kVAR Setpoint Write Upper Limit: 32767 closed loop Control
Size (bits): 16 extended
kVAR
Sign: S paralleling
Default: 0.000
Multiplier: Unit: % Sets %kVAR
Genset Bus .010000000000 Lower Limit: –5.000 % generator set
42332 %kVAR Read/ Offset: 0 output level for Master Load
Write Upper Limit: 105.000 open loop base Control
Setpoint Size (bits): 16 % load extended
Sign: S Default: 0.000 paralleling
Multiplier: Sets the desired
.010000000000 Unit: generator set
Genset Bus Lower Limit: 0.700
42333 Power Factor Read/ Offset: 0 bus power factor Master Load
Setpoint Write Upper Limit: 1.000 in closed loop Control
Size (bits): 8 extended
Sign: S Default: 1.000
paralleling
Multiplier: Unit: kW
Genset 1.000000000000 Lower Limit: Setpoint for
Read/ Offset: 0 Master Load
42334 Unloaded Write -32768.000 kW generator set Control
Level Size (bits): 16 Upper Limit: 32767 kW unloaded level
Sign: S Default: 50.000
Multiplier: Unit: kW Sets the peak
1.000000000000 Lower Limit: - shave kW
42337 Utility Bus kW Read/ Offset: 0 32768.000 kW setpoint in Master Load
Setpoint Write closed loop Control
Size (bits): 16 Upper Limit: 32767 kW extended
Sign: S Default: 100.000 paralleling

A029X159 (Issue 14) 397


7. DMC 1000 Modbus Parametric Data 10-2015

Addr System Name Access Specifications Description Function


Unit: kW
Multiplier: Sets the utility
1.000000000000 Lower Limit:
Utility Bus kW kW constraint
42338 Constraint Read/ Offset: 0 –32768.000 kW level for base Master Load
Level Write Upper Limit: load extended Control
Size (bits): 16
32767.000 kW paralleling
Sign: S
Default: 100.000

Multiplier: Unit: kVAR Sets the peak


1.000000000000 Lower Limit: shave kVAR
32768.000 kVAR
42339 Utility Bus Read/ Offset: 0 setpoint in Master Load
kVAR Setpoint Write Upper Limit: closed loop Control
Size (bits): 16 extended
32767.000 kVAR
Sign: S paralleling
Default: 100.000
Multiplier: Unit: Sets the desired
Utility Bus .010000000000 utility bus power Master Load
Read/ Lower Limit: 0.700
42340 Power Factor Offset: 0 factor in closed Control
Write Upper Limit: 1.000
Setpoint Size (bits): 8 loop extended
Default: 1.000 paralleling
Sign: S

Multiplier: Unit: kW
1.000000000000 Lower Limit:
Utility –32768.000 kW Setpoint for
42341 Unloaded Read/ Offset: 0 utility unloaded Master Load
Level Write Upper Limit: level Control
Size (bits): 16
32767.000 kVAR
Sign: S
Default: 50.000

Multiplier: Unit: seconds


.100000000000 Lower Limit: 10.000 Sets ramp load
Extended seconds
42348 Parallel Ramp Read/ Offset: 0 time for Master Load
Load Time Write Upper Limit: 900.000 extended Control
Size (bits): 16 paralleling
seconds
Sign: U
Default: 60.000

Multiplier: Unit: seconds


.200000000000 Lower Limit: 10.000 Sets the fail to
Fail To seconds
42351 Synchronize Read/ Offset: 0 synchronize Master Sync
Time Write Upper Limit: 900.000 diagnostic time Control
Size (bits):16 delay
seconds
Sign: U
Default: 120.000
Multiplier: Unit: Hz Sets the
.00100000000 synchronizer slip Master Sync
Read/ Lower Limit: –3.000 Hz
42354 Slip Frequency Write Offset: 0 frequency (used Control
Upper Limit: 3.000 Hz when sync
Size (bits):16
Default: 0.100 method is slip)
Sign: S

Multiplier: Unit: seconds


.10000000000 Lower Limit: 0.000
seconds Sets the
42355 Start Time Read/ Offset: 0 generator sets PTC Operating
Delay (TDES) Write Upper Limit: 3600.000 start time delay Mode
Size (bits):16
seconds
Sign: U
Default: 0.000

Multiplier: Unit: seconds


.100000000000 Lower Limit: 0.000
seconds Sets the
42356 Stop Time Read/ Offset: 0 generator sets PTC Operating
Delay (TDEC) Write Upper Limit: 3600.000 stop time delay Mode
Size (bits):16
seconds
Sign: U
Default: 0.000

398 A029X159 (Issue 14)


10-2015 7. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function

Multiplier: Unit: seconds Indicates delay


1.000000000000 Lower Limit: 0.000 between add
Genset Bus seconds
42364 Load Add Read/ Offset: 0 levels when all Load Add Shed
Delay Write Upper Limit: 60.000 generator sets Control
Size (bits): 16 are online and
seconds
Sign: U no utility
Default: 1.000

Multiplier: Unit: seconds


1.000000000000 Lower Limit: 0.000 Indicates delay
Utility Bus seconds
42365 Load Add Read/ Offset: 0 between add Load Add Shed
Delay Write Upper Limit: 60.000 levels when on Control
Size (bits): 16 utility
seconds
Sign: U
Default: 1.000
Unit: seconds
Multiplier: Lower Limit: 1.000
.100000000000 seconds Indicates delay
Load Shed Read/ Offset: 0 between shed Load Add Shed
42366 Delay Write Upper Limit: 10.000 levels when on Control
Size (bits): 8 seconds generator sets
Sign: U Default: 1.000

Multiplier: Unit:
1.000000000000 Indicates which
Load 1 Add Read/ Lower Limit: 1.000 Load Add Shed
42373 Level Offset: 0 add level load 1
Write Upper Limit: 6.000 Control
Size (bits): 8 is assigned to
Default: 1.000
Sign: U
Multiplier: Unit:
1.000000000000 Indicates which
Load 2 Add Read/ Lower Limit: 1.000 Load Add Shed
42374 Level Offset: 0 add level load 2
Write Upper Limit: 6.000 Control
Size (bits): 8 is assigned to
Default: 2.000
Sign: U
Multiplier: Unit:
1.000000000000 Indicates which
Load 3 Add Read/ Lower Limit: 1.000 Load Add Shed
42375 Level Offset: 0 add level load 3
Write Upper Limit: 6.000 Control
Size (bits): 8 is assigned to
Default: 3.000
Sign: U
Multiplier: Unit:
1.000000000000 Indicates which
Load 4 Add Read/ Lower Limit: 1.000 Load Add Shed
42376 Level Offset: 0 add level load 4
Write Upper Limit: 6.000 Control
Size (bits): 8 is assigned to
Default: 4.000
Sign: U
Multiplier: Unit:
1.000000000000 Indicates which
Load 5 Add Read/ Lower Limit: 1.000 Load Add Shed
42377 Level Offset: 0 add level load 5
Write Upper Limit: 6.000 Control
Size (bits): 8 is assigned to
Default: 5.000
Sign: U
Multiplier: Unit:
1.000000000000 Indicates which
Load 6 Add Read/ Lower Limit: 1.000 Load Add Shed
42378 Level Offset: 0 add level load 6
Write Upper Limit: 6.000 Control
Size (bits): 8 is assigned to
Default: 6.000
Sign: U

A029X159 (Issue 14) 399


7. DMC 1000 Modbus Parametric Data 10-2015

Addr System Name Access Specifications Description Function


Multiplier: Unit:
1.000000000000 Indicates which
Load 1 Shed Read/ Lower Limit: 0.000 Load Add Shed
42379 Level Offset: 0 shed level load
Write Upper Limit: 5.000 Control
Size (bits): 8 1 is assigned to
Default: 0.000
Sign: U
Multiplier: Unit:
1.000000000000 Indicates which
Load 2 Shed Read/ Lower Limit: 0.000 Load Add Shed
42380 Level Offset: 0 shed level load
Write Upper Limit: 5.000 Control
Size (bits): 8 2 is assigned to
Default: 5.000
Sign: U
Multiplier: Unit:
1.000000000000 Indicates which
Load 3 Shed Read/ Lower Limit: 0.000 Load Add Shed
42381 Level Offset: 0 shed level load
Write Upper Limit: 5.000 Control
Size (bits): 8 3 is assigned to
Default: 4.000
Sign: U
Multiplier: Unit:
1.000000000000 Indicates which
Load 4 Shed Read/ Lower Limit: 0.000 Load Add Shed
42382 Level Offset: 0 shed level load
Write Upper Limit: 5.000 Control
Size (bits): 8 4 is assigned to
Default: 3.000
Sign: U
Multiplier: Unit:
1.000000000000 Indicates which
Load 5 Shed Read/ Lower Limit: 0.000 Load Add Shed
42383 Level Offset: 0 shed level load
Write Upper Limit: 5.000 Control
Size (bits): 8 5 is assigned to
Default: 2.000
Sign: U
Multiplier: Unit:
1.000000000000 Indicates which
Load 6 Shed Read/ Lower Limit: 0.000 Load Add Shed
42384 Level Offset: 0 shed level load
Write Upper Limit: 5.000 Control
Size (bits): 8 6 is assigned to
Default: 1.000
Sign: U
Multiplier: Unit: % Use to set the
Genset Bus 1.000000000000 Lower Limit: 80.000 % %kW threshold
Read/ Offset: 0 System
42386 %kW Overload Write Upper Limit: 140.000 for gen bus Information
Threshold Size (bits): 8 % overload
Sign: U Default: 105.000 condition

Multiplier: Unit: second


1.000000000000 Lower Limit: 0.000
Genset Bus second Sets the delay
42387 kW Overload Read/ Offset: 0 time for overload System
Delay Write Upper Limit: 120.000 based on kW Information
Size (bits): 8
second
Sign: U
Default: 60.000
Multiplier: Use to set the
Genset Bus .100000000000 Unit: Hz underfrequency
Lower Limit: 0.100 Hz
42388 Underfrequenc Read/ Offset: 0 offset threshold System
y Overload Write Upper Limit: 10.000 Hz for gen bus Information
Threshold Size (bits): 16 overload
Sign: U Default: 3.000
condition
Multiplier: Unit: second
Genset Bus 1.000000000000 Sets the delay
Underfrequenc Read/ Lower Limit: 0.000 Hz time for overload System
42389 y Overload Offset: 0
Write Upper Limit: 20.000 Hz based on Information
Delay Size (bits): 8 frequency
Default: 3.000
Sign: U

400 A029X159 (Issue 14)


10-2015 7. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function

Multiplier: Unit: minute


Lower Limit: 1.000 Sets the initial
1.000000000000 delay time
minute
42395 Load Demand Read/ Offset: 0 before load Load Demand
Initial Delay Write Upper Limit: 60.000 demand will Control
Size (bits): 8
minute operate
Sign: U
Default: 5.000
Multiplier: Sets the load
1.000000000000 Unit: % demand restart
Load Demand Lower Limit: 20 %
42396 Restart Read/ Offset: 0 threshold (make Load Demand
Percent Write Upper Limit: 100 % larger than Control
Size (bits): 8 shutdown
Sign: U Default: 80.000
percent)
Multiplier: Unit: Hours Sets run hours
Load Demand 1.000000000000 Lower Limit: 1.000 differential for
42397 Run Hours Read/ Offset: 0 Hours restarting a Load Demand
Differential Write generator set Control
Size (bits): 16 Upper Limit: 500 Hours stopped due to
Sign: S Default: 50.000 load demand

Multiplier: Unit: minute Sets the delay


1.000000000000 Lower Limit: 1.000 time between
Load Demand minute
42398 Shutdown Read/ Offset: 0 stopping Load Demand
Delay Write Upper Limit: 60.000 generator sets Control
Size (bits): 8 due to load
minute
Sign: U demand
Default: 5.000
Multiplier: Sets the load
1.000000000000 Unit: % demand
Load Demand Lower Limit: 20 %
42399 Shutdown Read/ Offset: 0 shutdown Load Demand
Percent Write Upper Limit: 100 % threshold (make Control
Size (bits): 8 smaller than
Sign: U Default: 60.000
restart percent)

Multiplier: Unit: seconds Sets how long to


1.000000000000 Lower Limit: 10.000 wait for a
seconds
42400 Genset Fail Read/ Offset: 0 generator set to Load Demand
Time Delay Write Upper Limit: 900.000 come online Control
Size (bits): 16 before declaring
seconds
Sign: U it failed
Default: 60.000

Multiplier: Unit: seconds


.020000000000 Lower Limit: 0.100
seconds Sets the utility
42401 Util CB Fail to Read/ Offset: 0 breaker fail to Breaker Control
Close Delay Write Upper Limit: 1.000 close time delay
Size (bits): 16
seconds
Sign: U
Default: 0.26

Multiplier: Unit: seconds


.200000000000 Lower Limit: 0.200
seconds Sets the utility
42402 Util CB Fail to Read/ Offset: 0 breaker fail to Breaker Control
Open Delay Write Upper Limit: 5.000 open time delay
Size (bits): 8
seconds
Sign: U
Default: 1

Multiplier: Unit: seconds


.020000000000 Lower Limit: 0.000 Sets the time to
Util CB seconds
42403 Recharge Read/ Offset: 0 allow for utility Breaker Control
Delay Write Upper Limit: 60 breaker
Size (bits): 16 recharge
seconds
Sign: U
Default: 10.000

A029X159 (Issue 14) 401


7. DMC 1000 Modbus Parametric Data 10-2015

Addr System Name Access Specifications Description Function

Multiplier: Unit: seconds


.020000000000 Lower Limit: 0.100 Sets the
seconds
42404 Gen CB Fail to Read/ Offset: 0 generator set Breaker Control
Close Delay Write Upper Limit: 1.000 breaker fail to
Size (bits): 16 close time delay
seconds
Sign: U
Default: 0.260

Multiplier: Unit: seconds


0.200000000000 Lower Limit: 0.200 Sets the
seconds
42405 Gen CB Fail to Read/ Offset: 0 generator set Breaker Control
Open Delay Write Upper Limit: 5.000 breaker fail to
Size (bits): 8 open time delay
seconds
Sign: U
Default: 1.000

Multiplier: Unit: seconds


Lower Limit: 0.000 Sets the time to
Gen CB .020000000000 allow for
Read/ Offset: 0 seconds
42406 Recharge generator set Breaker Control
Delay Write Upper Limit: 60.000 breaker
Size (bits): 16
seconds recharge
Sign: U
Default: 10.000

Multiplier: Unit: degrees Sets the


0.01000000000 Lower Limit: 0.100 permissive +/-
degrees
42407 Permissive Read/ 0Offset: 0 phase angle Master Sync
Phase Window Write Upper Limit: 20.000 window for the Control
Size (bits): 16 sync check
degrees
Sign: S function
Default: 10.000
Sets the
Multiplier: Unit: % permissive +/-
Permissive .100000000000 voltage
Read/ Lower Limit: 0.5000 % Master Sync
42408 Voltage Offset: 0 acceptance
Write Upper Limit: 10.000 % Control
Window Size (bits): 16 window for the
Default: 5.000 sync check
Sign: U
function

Multiplier: Unit: seconds Sets the


.020000000000 Lower Limit: 0.500 permissive
seconds
42409 Permissive Read/ Offset: 0 acceptance Master Sync
Window Time Write Upper Limit: 5.000 window dwell Control
Size (bits): 16 time for the sync
seconds
Sign: U check function
Default: 0.500
Multiplier: Sets the
.001000000000 Unit: Hz maximum
Permissive Lower Limit: 0.001 Hz
42410 Frequency Read/ Offset: 0 frequency Master Sync
Window Write Upper Limit: 1.000 Hz difference Control
Size (bits): 32 allowed for
Sign: U Default: 1.000
permissive close

Multiplier: Unit: degrees Sets a sync


0.010000000000 Lower Limit: –50.000 phase offset to
degrees
42412 Sync Phase Read/ Offset: 0 accommodate Master Sync
Offset Write Upper Limit: 50.000 sync across Control
Size (bits): 16 transformer with
degrees
Sign: S phase shift
Default: 0.000
Multiplier: Proportional
1.000000000000 Unit: gain for kW
Read/ Offset: 0 Lower Limit: 0.000 closed loop Master Load
42414 kW Kp
Write Upper Limit: 1000.000 control in Control
Size (bits): 16 extended
Sign: U Default: 60.000
paralleling

402 A029X159 (Issue 14)


10-2015 7. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function


Multiplier: Unit: Integral gain for
1.000000000000 kW closed loop
Read/ Lower Limit: 0.000 Master Load
42415 kW KI Offset: 0 control in
Write Upper Limit: 255.000 Control
Size (bits): 8 extended
Default: 60.000 paralleling
Sign: U
Multiplier: Proportional
1.000000000000 Unit: gain for kVAR
Read/ Offset: 0 Lower Limit: 0.000 closed loop Master Load
42416 kVAR Kp
Write Upper Limit: 1000.000 control in Control
Size (bits): 16 extended
Sign: U Default: 120.000
paralleling
Multiplier: Unit: Integral gain for
1.000000000000 kVAR closed
Read/ Lower Limit: 0.000 Master Load
42417 kVAR KI Offset: 0 loop control in
Write Upper Limit: 255.000 Control
Size (bits): 8 extended
Default: 50.000 paralleling
Sign: U
Multiplier: Unit:
1.000000000000 Selects which
Scheduler Read/ Lower Limit: 1.000 scheduler System
42418 Program Select Write Offset: 0
Upper Limit: 12.000 program to view Scheduler
Size (bits): 8 or edit
Default: 1.000
Sign: U

Multiplier: Unit: hour


1.000000000000 Lower Limit: 0.000 Use to adjust
Scheduler hour
42423 Program x Read/ Offset: 0 start hour for the System
Start Hour Write Upper Limit: 23.000 selected Scheduler
Size (bits): 8 program
hour
Sign: U
Default: 0.000

Multiplier: Unit: minute


1.000000000000 Lower Limit: 0.000 Use to adjust
Scheduler minute
42424 Program x Read/ Offset: 0 start minute for System
Start Minute Write Upper Limit: 59.000 the selected Scheduler
Size (bits): 8 program
minute
Sign: U
Default: 0.000

Multiplier: Unit: hour


1.000000000000 Lower Limit: 0.000 Use to adjust
Scheduler hour
42425 Program x Read/ Offset: 0 duration hours System
Duration Hours Write Size (bits): 8 Upper Limit: 23.000 for the selected Scheduler
hour program
Sign: U
Default: 0.000

Multiplier: Unit: minute


Scheduler 1.000000000000 Lower Limit: 0.000 Use to adjust
minute
42426 Program x Read / Offset: 0 duration minutes System
Duration Write Upper Limit: 59.000 for the selected Scheduler
Minutes Size (bits): 8 program
minute
Sign: U
Default: 0.000
Multiplier: Unit:
1.000000000000 Selects which
Scheduler Read/ Lower Limit: 1.000 scheduler System
42427 Exception Offset: 0
Write Upper Limit: 6.000 exception to Scheduler
Select Size (bits): 8 view or edit
Default: 1.000
Sign: U

A029X159 (Issue 14) 403


7. DMC 1000 Modbus Parametric Data 10-2015

Addr System Name Access Specifications Description Function

Multiplier: Unit: month


1.000000000000 Lower Limit: 1.000 Use to adjust
Scheduler month
42430 Exception x Read/ Offset: 0 the month of the System
Month Write Upper Limit: 12.000 selected Scheduler
Size (bits): 8 exception
month
Sign: U
Default: 1.000

Multiplier: Unit: date


1.000000000000 Lower Limit: 1.000 Use to adjust
Scheduler date
42431 Exception x Read/ Offset: 0 the date of the System
Date Write Upper Limit: 31.000 selected Scheduler
Size (bits): 8 exception
date
Sign: U
Default: 1.000

Multiplier: Unit: hour


1.000000000000 Lower Limit: 0.000 Use to adjust
Scheduler hour
42432 Exception x Read/ Offset: 0 the start hour of System
Hour Write Upper Limit: 23.000 the selected Scheduler
Size (bits):8 exception
hour
Sign: U
Default: 0.000

Multiplier: Unit: minute


1.000000000000 Lower Limit: 0.000 Use to adjust
Scheduler minute
42433 Exception x Read/ Offset: 0 the start minute System
Minute Write Upper Limit: 59.000 of the selected Scheduler
Size (bits): 8 exception
minute
Sign: U
Default: 0.000

Multiplier: Unit: days


Lower Limit: 0.000 Use to adjust
Scheduler 1.000000000000 the duration
Read/ Offset: 0 days System
42434 Exception x days of the
Duration Days Write Upper Limit: 44.000 selected Scheduler
Size (bits): 8
days exception
Sign: U
Default: 0.000
Multiplier: Unit: hour Use to adjust
Scheduler 1.000000000000 Lower Limit: 0.000 the duration
Read/ Offset: 0 hour System
42435 Exception x Write hours of the Scheduler
Duration Hours Size (bits): 8 Upper Limit: 23 hour selected
Sign: U Default: 0.000 exception

Multiplier: Unit: minute


Lower Limit: 0.000 Use to adjust
Scheduler 1.000000000000 the duration
minute
42436 Exception x Read/ Offset: 0 minutes of the System
Duration Write Upper Limit: 59.000 selected Scheduler
Minutes Size (bits): 8
minute exception
Sign: U
Default: 0.000

Multiplier: Unit: Volts


1.000000000000 Lower Limit: 110.000
Genset PT Volts Generator Set
42440 Primary Read/ Offset: 0 PT primary AC Setup
Voltage Write Upper Limit: voltage
Size (bits): 16
45000.000 Volts
Sign: U
Default: 480
Multiplier: Unit: Volts
Genset PT 1.000000000000 Lower Limit: 110.000 Generator set
Read/ Offset: 0
42441 Secondary Write Volts Upper Limit: 500 PT secondary AC Setup
Voltage Size (bits): 16 Volts voltage
Sign: U Default: 120

404 A029X159 (Issue 14)


10-2015 7. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function

Multiplier: Unit: Amp


1.000000000000 Lower Limit: 5.000
Genset CT Amp Generator set
42442 Primary Read/ Offset: 0 CT primary AC Setup
Current Write Upper Limit: current
Size (bits): 16
10000.000 Amp
Sign: U
Default: 100

Multiplier: Unit: Volts


1.000000000000 Lower Limit: 110.000
Utility PT Volts
42445 Primary Read/ Offset: 0 Utility PT AC Setup
Voltage Write Upper Limit: primary voltage
Size (bits): 16
45000.000 Volts
Sign: U
Default: 480

Multiplier: Unit: Volts


1.000000000000 Lower Limit: 110.000
Utility PT Volts Utility PT
42446 Secondary Read/ Offset: 0 secondary AC Setup
Voltage Write Upper Limit: 500.000 voltage
Size (bits): 16
Volts
Sign: U
Default: 120

Multiplier: Unit: Amps


1.000000000000 Lower Limit: 5.000
Utility CT Amps
42447 Primary Read/ Offset: 0 Utility primary AC Setup
Current Write Upper Limit: 10000.00 current
Size (bits): 16
Amps
Sign: U
Default: 100
Multiplier: Unit: kW Generator set
Load Add Shed 1.000000000000 Lower Limit: 0.000 kW kW capacity that
42449 Required Read/ Offset: 0 Upper Limit:
must be online Load Add Shed
Online Write to start timed Control
Capacity Size (bits): 16 32000.000 kW load add; 0
Sign: S Default: 0 disables this
Multiplier: Unit: kW Sets how much
Load Demand 1.000000000000 Lower Limit: 0.000 kW
Minimum Read/ capacity must Load Demand
42450 Online Offset: 0 Upper Limit: always be online Control
Write
Capacity Size (bits): 16 32767.000 kW regardless of
Sign: S Default: 0 what the load is

Multiplier: Unit: seconds Sets generator


0.100000000000 Lower Limit: 0.000 restart delay
seconds
42451 Load Demand Read/ Offset: 0 time to avoid Load Demand
Restart Delay Write Upper Limit: 25.000 nuisance Control
Size (bits): 8 restarts due to
seconds
Sign: U load transients
Default: 1

Multiplier: Unit: Amps


1.000000000000 Lower Limit: 1.000
Amps
42452 Utility Available Read/ Offset: 0 barograph AC Setup
Current Write Upper Limit:
Size (bits): 16
32000.000 Amps
Sign: U
Default: 1000
Multiplier: Unit: kW Use to set how
1.000000000000 Lower Limit: 1.000 kW kW = 100%
Total Utility Read/ Offset: 0
42453 Capacity Write Upper Limit: 32000.00 utility kW -- AC Setup
Size (bits): 16 kW Used by
Sign: S Default: 1000 barograph

A029X159 (Issue 14) 405


7. DMC 1000 Modbus Parametric Data 10-2015

Addr System Name Access Specifications Description Function

Multiplier: Unit: VDC


0.010000000000 Lower Limit: 28.000
24 V High VDC Sets 24V high
42455 Battery Voltage Read/ Offset: 0 battery voltage Battery Voltage
Threshold Write Upper Limit: 34.000 fault threshold Protection
Size (bits): 16
VDC
Sign: U
Default: 32

Multiplier: Unit: VDC


0.010000000000 Lower Limit: 22.000
24 V Low VDC Sets 24V low
42456 Battery Voltage Read/ Offset: 0 battery voltage Battery Voltage
Threshold Write Upper Limit: 26.000 fault threshold Protection
Size (bits): 16
VDC
Sign: U
Default: 24

Multiplier: Unit: VDC


0.010000000000 Lower Limit: 14.000
12 V High VDC Sets 12V high
42457 Battery Voltage Read/ Offset: 0 battery voltage Battery Voltage
Threshold Write Upper Limit: 17.000 fault threshold Protection
Size (bits): 16
VDC
Sign: U
Default: 16
Unit: VDC
Multiplier: Lower Limit: 11.000
12 V Low 0.010000000000 VDC Sets 12V low
Read/ Offset: 0 Battery Voltage
42458 Battery Voltage Write Upper Limit: 13.000 battery voltage Protection
Threshold Size (bits): 16 VDC fault threshold
Sign: U Default: 12

Multiplier: Unit: second


High Battery 1.000000000000
Read/ Lower Limit: 2 second Sets high Battery Voltage
42459 Voltage Set Offset: 0 battery voltage
Write Upper Limit: 60 second set time Protection
time Size (bits): 8
Default: 60
Sign: U
Multiplier: Unit: second
Low Battery 1.000000000000
Read/ Lower Limit: 2 second Sets low battery Battery Voltage
42460 Voltage Set Offset: 0
Write Upper Limit: 60 second voltage set time Protection
Time Size (bits): 8
Default: 60
Sign: U
Multiplier: Unit: kW Sets the online
Genset Online 1.000000000000 Lower Limit: 0.000 kW kW threshold at
42462 Capacity Read/ Offset: 0 Upper Limit:
which generator PTC Sensors
Sensor Write set bus is
Threshold Size (bits): 16 32000.000 kW available for
Sign: S Default: 0 loading
Multiplier: Unit:
1.000000000000 Bitmapped state
Fault Status Read Lower Limit: of utility and Fault and Event
42500 BitMap 1 Offset: 0
Only Upper Limit: other faults - 32 Info
Size (bits): 32 bits
Default:
Sign: U
Multiplier: Unit:
1.000000000000 Bitmapped state
Fault Status Read Lower Limit: of generator set Fault and Event
42502 BitMap 2 Offset: 0
Only Upper Limit: and other faults Info
Size (bits): 32 - 32 bits
Default:
Sign: U

406 A029X159 (Issue 14)


10-2015 7. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function


Multiplier: Unit:
1.000000000000 Bitmapped state Fault and Event
Event Status Read Lower Limit:
42504 BitMap 1 Offset: 0 of events - 32
Only Upper Limit: Info
Size (bits): 32 bits
Default:
Sign: U
Multiplier: Bitmapped word
1.000000000000 Unit: with status of
Genset Lower Limit:
42506 Metering Fault Read Offset: 0 generator set AC Interrupt
Status Only Upper Limit: AC metering out Service
Size (bits): 16 of range
Sign: U Default:
conditions
Multiplier: Unit: Bitmapped word
1.000000000000 with status of
Utility Metering Read Lower Limit: AC Interrupt
42507 Fault Status Offset: 0 utility AC
Only Upper Limit: Service
Size (bits): 16 metering out of
Default: range conditions
Sign: U

Multiplier: Unit: Hours


0.000277778 Lower Limit: 0.000
Hours
42704 Gen1 Online Read Offset: 0 Total online time System
Time Only Upper Limit: for Gen1 Information
Size (bits): 32
1193046.000 Hours
Sign: U
Default: 0

Multiplier: Unit: Hours


0.000277778 Lower Limit: 0.000
Hours
42706 Gen2 Online Read Offset: 0 Total online time System
Time Only Upper Limit: for Gen2 Information
Size (bits): 32
1193046.000 Hours
Sign: U
Default: 0

Multiplier: Unit: Hours


0.000277778 Lower Limit: 0.000
Hours
42708 Gen3 Online Read Offset: 0 Total online time System
Time Only Upper Limit: for Gen3 Information
Size (bits): 32
1193046.000 Hours
Sign: U
Default: 0

Multiplier: Unit: Hours


0.000277778 Lower Limit: 0.000
Hours
42710 Gen4 Online Read Offset: 0 Total online time System
Time Only Upper Limit: for Gen4 Information
Size (bits): 32
1193046.000 Hours
Sign: U
Default: 0
Multiplier: Indicates how
1.000000000000 Unit: many of the
Total Number Lower Limit:
42717 of Gensets Read Offset: 0 defined Gen1 System
Online Only Upper Limit: thru Gen4 Information
Size (bits): 8 generator sets
Sign: U Default:
are online
Multiplier: Difference
1.000000000000 Unit: kW between online
Total Spare Lower Limit:
42718 Online Read Offset: 0 capacity (4 System
Capacity Only Upper Limit: generator sets) Information
Size (bits): 16 and Genset Bus
Sign: S Default:
Total kW

A029X159 (Issue 14) 407


7. DMC 1000 Modbus Parametric Data 10-2015

Addr System Name Access Specifications Description Function


Multiplier: Indicates kW
1.000000000000 Unit: kW threshold for
Next Gen Lower Limit:
42719 Restart Read Offset: 0 gen bus at Load Demand
Threshold Only Upper Limit: which the next Control
Size (bits): 16 generator set
Sign: S Default:
will restart
Indicates kW
Multiplier: Unit: kW threshold for
Next Gen 1.000000000000 gen bus at
Read Lower Limit: Load Demand
42720 Shutdown Offset: 0 which the next
Only Upper Limit: Control
Threshold Size (bits): 16 generator set
Default: will load demand
Sign: S
stop
Multiplier: Calculated kW
1.000000000000 Unit: kW overload
Genset Bus Lower Limit:
42727 kW Overload Read Offset: 0 threshold based System
Threshold Only Upper Limit: on online Information
Size (bits): 16 capacity and %
Sign: S Default:
setting
Multiplier: Unit:
Modbus Bus 1.000000000000
Read Lower Limit: Modbus bus
42732 Message Offset: 0 Communications
Only Upper Limit: message count
Count Size (bits): 16
Default:
Sign: U
Multiplier: Unit:
1.000000000000
Modbus CRC Read Lower Limit: Modbus CRC
42733 Error Count Offset: 0 Communications
Only Upper Limit: error count
Size (bits): 16
Default:
Sign: U
Multiplier: Unit:
Modbus 1.000000000000
Read Lower Limit: Modbus
42734 Exception Offset: 0 Communications
Only Upper Limit: exception count
Count Size (bits): 16
Default:
Sign: U
Multiplier: Unit:
Modbus No 1.000000000000
Read Lower Limit: Modbus no
42735 Response Offset: 0 Communications
Only Upper Limit: response count
Count Size (bits): 16
Default:
Sign: U
Multiplier: Unit:
Modbus Slave 1.000000000000
Read Lower Limit: Modbus slave
42736 Message Offset: 0 Communications
Only Upper Limit: message count
Count Size (bits): 16
Default:
Sign: U
Multiplier: Unit: year
1.000000000000 Lower Limit: .000 year Use to set or
Read/ Offset: 0
42739 Clock Year Write Upper Limit: 99.000 read current Real Time Clock
Size (bits): 8 year year
Sign: U Default:

408 A029X159 (Issue 14)


10-2015 7. DMC 1000 Modbus Parametric Data

Addr System Name Access Specifications Description Function

Multiplier: Unit: month


1.000000000000 Lower Limit: 1.000
month Use to set or
42740 Clock Month Read/ Offset: 0 read current Real Time Clock
Write Upper Limit: 12.000 month
Size (bits): 8
month
Sign: U
Default:

Multiplier: Unit: date


1.000000000000 Lower Limit: 1.000
date Use to set or
42741 Clock Date Read/ Offset: 0 read current Real Time Clock
Write Upper Limit: 31.000 date
Size (bits): 8
date
Sign: U
Default:
Multiplier: Unit: hour
1.000000000000 Lower Limit: .000 hour Use to set or
Read/ Offset: 0
42742 Clock Hour Write Upper Limit: 23.000 read current Real Time Clock
Size (bits): 8 hour hour
Sign: U Default:

Multiplier: Unit: minute


1.000000000000 Lower Limit: .000
minute Use to set or
42743 Clock Minute Read/ Offset: 0 read current Real Time Clock
Write Upper Limit: 59.000 minute
Size (bits): 8
minute
Sign: U
Default:

Multiplier: Unit: seconds


1.000000000000 Lower Limit: .000
seconds Use to set or
42744 Clock Second Read/ Offset: 0 read current Real Time Clock
Write Upper Limit: 59.000 seconds
Size (bits): 8
seconds
Sign: U
Default:
Multiplier: Unit: seconds
0.100000000000 Countdown
Read Lower Limit: timer value for PTC Operating
42746 Start Timer Offset: 0
Only Upper Limit: generator set Mode
Size (bits): 16 start timer
Default:
Sign: U
Multiplier: Unit: seconds
.100000000000 Countdown
Read Lower Limit: timer value for PTC Operating
42747 Stop Timer Offset: 0
Only Upper Limit: generator set Mode
Size (bits): 16 stop timer
Default:
Sign: U
Multiplier: Unit: VDC
0.010000000000 Battery voltage
Low Battery Read Lower Limit: with respect to Battery Voltage
42748 Voltage Offset: 0
Only Upper Limit: the set low Protection
Threshold Size (bits): 16 battery threshold
Default:
Sign: U
Multiplier: Unit: VDC
0.010000000000 Battery voltage
High Battery Read Lower Limit: with respect to Battery Voltage
42749 Voltage Offset: 0
Only Upper Limit: set high battery Protection
Threshold Size (bits): 16 threshold
Default:
Sign: U

A029X159 (Issue 14) 409


7. DMC 1000 Modbus Parametric Data 10-2015

This page is intentionally blank.

410 A029X159 (Issue 14)


8 DMC 1000 Modbus Enumerated Data
NOTICE
Earlier versions of software may not support all of the Modbus registers in the following
table. If a particular register is not available in your installation, it is possible that the
Modbus connection is working but the controller software does not support that
particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

Addr. System Name Access Specifications Description Function


Save
configuration
parameters or
adjustments to
non-volatile
memory.
0: Do Nothing Perform Save
Save Read / Size (bits): 8 Controller
42004 Adjustments Write 1: Save Trims Trims after all Information
Number of Fields: 2 configurations
Default: Do Nothing
have been
updated. Do
not save trims
unless a
change has
occurred.
0: Time Delay Start
1: Time Delay Stop Indicates state
Genset Run Read Size (bits): 8 of the PTC Operating
42011 Sequence Only 2: Stop generator set Mode
State Number of Fields: 4
3: Run run sequence
Default:
0: Unavailable Energization
Size (bits): 8 1: Dead
42017 Genset Bus Read status of the PTC Sensors
Status Only Number of Fields: 3 2: Live generator set
Default: bus

0: Unavailable
Size (bits): 8 1: Dead Energization
42117 Utility Bus Read status of the PTC Sensors
Status Only Number of Fields: 3 2: Live utility bus
Default:
0: Not Available
Size (bits): 8 1: Not Unloaded Indicates utility
42208 Utility Unload Read unloaded Master Load
Status Only Number of Fields: 3 2: Unloaded status Control
Default:
0: Not Available Indicates
Size (bits): 8 1: Not Unloaded
42209 Genset Unload Read generator set Master Load
Status Only Number of Fields: 3 2: Unloaded unloaded Control
Default: status

A029X159 (Issue 14) 411


8. DMC 1000 Modbus Enumerated Data 10-2015

Addr. System Name Access Specifications Description Function


0: Not Available
1: TD Start
2: TD Stop
3: TD Programmed
Transition
4: TD Transfer
5: TD Retransfer
6: Synchronizing
7: Sync Check OK
Size (bits): 8 Indicates what
Read / 8: Inhibit state the System
42210 System State Number of Fields:
Write 9: Unassigned control is Information
18 currently in
10: Ramp Unload
11: Ramp Load
12: Manual
13: Utility Failure
14: Test
15: Standby
16: Factory Test
17: Extended Parallel
Default: Not Available
0: Manual
Size (bits): 8 1: Normal Indicates the
Number of Fields: 6 2: Normal Override current PTC
PTC Operating Read operating PTC Operating
42211 Mode Only 3: Test mode. Mode
4: Utility Fail Read/Write in
5: Extended Parallel Comp mode
Default:
Indicates
0: Not Available availability of
Genset Read Size (bits): 8 1: Available generator set
42216 Availability Only for loading as Availability
Status Number of Fields: 3 2: Unknown determined by
Default: generator set
sensors
Indicates
0: Not Available availability of
Utility Size (bits): 8 1: Available
42217 Availability Read utility for Availability
Status Only Number of Fields: 3 2: Unknown loading as
Default: determined by
utility sensors
Size (bits): 8
0: Open
Number of Fields: 3 Generator set
Gen CB Read 1: Closed
42218 Position Status Only breaker Breaker Control
2: Not Available position
Default:

Size (bits): 8
Number of Fields: 3 0: Open
1: Closed
42219 Util CB Read Utility breaker Breaker Control
Position Status Only 2: Not Available position
Default:

412 A029X159 (Issue 14)


10-2015 8. DMC 1000 Modbus Enumerated Data

Addr. System Name Access Specifications Description Function


0: Not Enabled
Indicates the
1: No Source connected
Connected state of the
Read Size (bits): 8 PTC State
42224 PTC State 2: Utility Connected power transfer
Only Number of Fields: 5 Machine
3: Genset Connected control
4: Paralleled Read/Write in
Comp.
Default:
Size (bits):8
Indicates
Number of Fields: 2 0: Not Allowed whether any
Sync Check Read Master Sync
42225 Close Allowed Only 1: Allowed sync check Control
Default: conditions for
have been met

Size (bits): 8
0: Synchronizer Off Indicates state
Number of Fields: 2
42227 Synchronizer Read 1: Synchronizer On of the Master Sync
Status Only synchronizer Control
Default:

Size (bits): 8 Faults have


Number of Fields: 2 0: Inactive occurred which
System Read prevent normal System
42228 Lockout Status Only 1: Active system Information
Default: operation;
reset faults
Size (bits): 8
0: Open
Number of Fields: 3 Indicates
Breaker 1 Read 1: Closed Load Add Shed
42229 Position Only position status Control
2: Not Available of breaker 1
Default: Not Available

0: Open
Size (bits): 8 Indicates
1: Closed
42230 Breaker 2 Read Number of Fields: 3 position status Load Add Shed
Position Only 2: Not Available of breaker 2 Control
Default: Not Available
0: Open
Size (bits): 8 1: Closed Indicates
42231 Breaker 3 Read position status Load Add Shed
Position Only Number of Fields: 3 2: Not Available of breaker 3 Control
Default: Not Available
Size (bits): 8 0: Open
Number of Fields: 3 1: Closed Indicates
Breaker 4 Read Load Add Shed
42232 Position Only 2: Not Available position status Control
Default: Not Available of breaker 4

0: Open
Size (bits): 8 1: Closed Indicates
42233 Breaker 5 Read position status Load Add Shed
Position Only Number of Fields: 3 2: Not Available of breaker 5 Control
Default: Not Available
0: Open
Size (bits): 8 1: Closed Indicates
42234 Breaker 6 Read position status Load Add Shed
Position Only Number of Fields: 3 2: Not Available of breaker 6 Control
Default: Not Available

A029X159 (Issue 14) 413


8. DMC 1000 Modbus Enumerated Data 10-2015

Addr. System Name Access Specifications Description Function


0: Not Available
Size (bits): 8 1: Normal Indicates trip
42235 Breaker 1 Trip Read status of Load Add Shed
Status Only Number of Fields: 3 2: Tripped breaker 1 Control
Default: Not Available
0: Not Available
Size (bits): 8 1: Normal Indicates trip
42236 Breaker 2 Trip Read status of Load Add Shed
Status Only Number of Fields: 3 2: Tripped breaker 2 Control
Default: Not Available
0: Not Available
Size (bits): 8 1: Normal Indicates trip
42237 Breaker 3 Trip Read status of Load Add Shed
Status Only Number of Fields: 3 2: Tripped breaker 3 Control
Default: Not Available
Size (bits): 8
0: Not Available
Number of Fields: 3 Indicates trip
Breaker 4 Trip Read 1: Normal Load Add Shed
42238 Status Only status of Control
2: Tripped breaker 4
Default: Not Available

0: Not Available
Size (bits): 8 1: Normal Indicates trip
42239 Breaker 5 Trip Read status of Load Add Shed
Status Only Number of Fields: 3 2: Tripped breaker 5 Control
Default: Not Available
0: Not Available
Size (bits): 8 1: Normal Indicates trip
42240 Breaker 6 Trip Read status of Load Add Shed
Status Only Number of Fields: 3 2: Tripped breaker 6 Control
Default: Not Available
0: Not Available
1: No Source
Connected Indicates
Read Size (bits): 8 Load Add Shed
42241 ATS 1 Position Only 2: Source 1 Connected position status
Number of Fields: 5 Control
3: Source 2 Connected of ATS 1
4: Paralleled
Default: Not Available
0: Not Available
1: No Source
Connected Indicates
Read Size (bits): 8 Load Add Shed
42242 ATS 2 Position Only 2: Source 1 Connected position status
Number of Fields: 5 Control
3: Source 2 Connected of ATS 3
4: Paralleled
Default: Not Available
0: Not Available
1: No Source
Connected Indicates
Read Size (bits): 8 Load Add Shed
42243 ATS 3 Position Only 2: Source 1 Connected position status
Number of Fields: 5 Control
3: Source 2 Connected of ATS 3
4: Paralleled
Default: Not Available

414 A029X159 (Issue 14)


10-2015 8. DMC 1000 Modbus Enumerated Data

Addr. System Name Access Specifications Description Function


0: Not Available
1: No Source
Connected Indicates
Read Size (bits):8 Load Add Shed
42244 ATS 4 Position Only 2: Source 1 Connected position status
Number of Fields: 5 Control
3: Source 2 Connected of ATS 4
4: Paralleled
Default: Not Available
0: Not Available
1: No Source
Connected Indicates
Read Size (bits): 8 Load Add Shed
42245 ATS 5 Position Only 2: Source 1 Connected position status
Number of Fields: 5 Control
3: Source 2 Connected of ATS 5
4: Paralleled
Default: Not Available
0: Not Available
1: No Source
Connected Indicates
Read Size (bits): 8 Load Add Shed
42246 ATS 6 Position Only 2: Source 1 Connected position status
Number of Fields: 5 Control
3: Source 2 Connected of ATS 6
4: Paralleled
Default: Not Available
0: Failed
PCCNet Size (bits): 8 1: Good Indicates
42248 Communication Read status of Communications
s Status Only Number of Fields: 3 2: Wait PCCNet
Default: Wait
Indicates the
Expansion 0: Disabled status of the
Size (bits): 8
42249 Board Read 1: Enabled SID to Communications
Communication Only Number of Fields: 2 expansion
s Default: Disabled board
connection
0: Do Nothing Indicates
Add Level 1 Read Size (bits): 8 Load Add Shed
42252 Command Only 1: Add Level status of add Control
Number of Fields: 2 level 1
Default: Do Nothing
0: Do Nothing Indicates
Add Level 2 Read Size (bits):8 Load Add Shed
42253 Command Only 1: Add Level status of add Control
Number of Fields: 2 level 2
Default: Do Nothing
0: Do Nothing Indicates
Add Level 3 Read Size (bits): 8 Load Add Shed
42254 Command Only 1: Add Level status of add Control
Number of Fields: 2 level 3
Default: Do Nothing
0: Do Nothing Indicates
Add Level 4 Read Size (bits): 8 Load Add Shed
42255 Command Only 1: Add Level status of add Control
Number of Fields: 2 level 4
Default: Do Nothing
0: Do Nothing Indicates
Add Level 5 Read Size (bits): 8 Load Add Shed
42256 Command Only 1: Add Level status of add Control
Number of Fields: 2 level 5
Default: Do Nothing
0: Do Nothing Indicates
Add Level 6 Read Size (bits): 8 Load Add Shed
42257 Command Only 1: Add Level status of add Control
Number of Fields: 2 level 6
Default: Do Nothing

A029X159 (Issue 14) 415


8. DMC 1000 Modbus Enumerated Data 10-2015

Addr. System Name Access Specifications Description Function


0: Do Nothing Indicates
Shed Level 1 Read / Size (bits): 8 Load Add Shed
42258 Command Write 1: Shed Level status of shed Control
Number of Fields: 2 level 1
Default: Do Nothing
0: Do Nothing Indicates
Shed Level 2 Read Size (bits): 8 Load Add Shed
42259 Command Only 1: Shed Level status of shed Control
Number of Fields: 2 level 2
Default: Do Nothing
0: Do Nothing Indicates
Shed Level 3 Read / Size (bits): 8 Load Add Shed
42260 Command Write 1: Shed Level status of shed Control
Number of Fields: 2 level 3
Default: Do Nothing
0: Do Nothing Indicates
Shed Level 4 Read Size (bits): 8 Load Add Shed
42261 Command Only 1: Shed Level status of shed Control
Number of Fields: 2 level 4
Default: Do Nothing
0: Do Nothing Indicates
Shed Level 5 Read Size (bits): 8 Load Add Shed
42262 Command Only 1: Shed Level status of shed Control
Number of Fields: 2 level 5
Default: Do Nothing

Manual add 0: Do Nothing Operator input


Read / Size (bits): 8 to add loads Load Add Shed
42263 Level 1 1: Add Level
Command Write Number of Fields: 2 assigned to Control
Default: Do Nothing level 1

Manual add 0: Do Nothing Operator input


Read / Size (bits): 8 to add loads Load Add Shed
42264 Level 2 1: Add Level
Command Write Number of Fields: 2 assigned to Control
Default: Do Nothing level 2

Manual add 0: Do Nothing Operator input


Read / Size (bits): 8 to add loads Load Add Shed
42265 Level 3 1: Add Level
Command Write Number of Fields: 2 assigned to Control
Default: Do Nothing level 3

Manual add 0: Do Nothing Operator input


Read / Size (bits): 8 to add loads Load Add Shed
42266 Level 4 1: Add Level
Command Write Number of Fields: 2 assigned to Control
Default: Do Nothing level 4

Manual add 0: Do Nothing Operator input


Read / Size (bits): 8 to add loads Load Add Shed
42267 Level 5 1: Add Level
Command Write Number of Fields: 2 assigned to Control
Default: Do Nothing level 5

Manual add 0: Do Nothing Operator input


Read / Size (bits): 8 to add loads Load Add Shed
42268 Level 6 1: Add Level
Command Write Number of Fields: 2 assigned to Control
Default: Do Nothing level 6

0: Do Nothing Operator input


Size (bits): 8
42269 Manual Shed Read / 1: Shed Level to shed loads Load Add Shed
Level 1 Write Number of Fields: 2 assigned to Control
Default: Do Nothing level 1

0: Do Nothing Operator input


Size (bits): 8
42270 Manual Shed Read / 1: Shed Level to shed loads Load Add Shed
Level 2 Write Number of Fields: 2 assigned to Control
Default: Do Nothing level 2

0: Do Nothing Operator input


Size (bits): 8
42271 Manual Shed Read / 1: Shed Level to shed loads Load Add Shed
Level 3 Write Number of Fields: 2 assigned to Control
Default: Do Nothing level 3

416 A029X159 (Issue 14)


10-2015 8. DMC 1000 Modbus Enumerated Data

Addr. System Name Access Specifications Description Function

0: Do Nothing Operator input


Size (bits): 8
42272 Manual Shed Read / 1: Shed Level to shed loads Load Add Shed
Level 4 Write Number of Fields:2 assigned to Control
Default: Do Nothing level 4

0: Do Nothing Operator input


Size (bits): 8
42273 Manual Shed Read / 1: Shed Level to shed loads Load Add Shed
Level 5 Write Number of Fields: 2 assigned to Control
Default: Do Nothing level 5

Restore Shed 0: Do Nothing Indicates if


Read / Size (bits): 8 shed level 1 Load Add Shed
42274 Level 1 1: Restore Level
Command Write Number of Fields: 2 has been Control
Default: Do Nothing restored

Restore Shed 0: Do Nothing Indicates if


Read / Size (bits): 8 shed level 2 Load Add Shed
42275 Level 2 1: Restore Level
Command Write Number of Fields: 2 has been Control
Default: Do Nothing restored

Restore Shed 0: Do Nothing Indicates if


Read / Size (bits): 8 shed level 3 Load Add Shed
42276 Level 3 1: Restore Level
Command Write Number of Fields: 2 has been Control
Default: Do Nothing restored

Restore Shed 0: Do Nothing Indicates if


Read / Size (bits): 8 shed level 4 Load Add Shed
42277 Level 4 1: Restore Level
Command Write Number of Fields: 2 has been Control
Default: Do Nothing restored

Restore Shed 0: Do Nothing Indicates if


Read / Size (bits): 8 shed level 5 Load Add Shed
42278 Level 5 1: Restore Level
Command Write Number of Fields: 2 has been Control
Default: Do Nothing restored
0: Do Nothing Indicates add
Add Load 1 Read Size (bits): 8 Load Add Shed
42279 Command Only 1: Add Load command for Control
Number of Fields: 2 load 1
Default: Do Nothing
0: Do Nothing Indicates add
Add Load 2 Read Size (bits): 8 Load Add Shed
42280 Command Only 1: Add Load command for Control
Number of Fields: 2 load 2
Default: Do Nothing
0: Do Nothing Indicates add
Add Load 3 Read Size (bits): 8 Load Add Shed
42281 Command Only 1: Add Load command for Control
Number of Fields: 2 load 3
Default: Do Nothing
0: Do Nothing Indicates add
Add Load 4 Read Size (bits): 8 Load Add Shed
42282 Command Only 1: Add Load command for Control
Number of Fields: 2 load 4
Default: Do Nothing
0: Do Nothing Indicates add
Add Load 5 Read Size (bits): 8 Load Add Shed
42283 Command Only 1: Add Load command for Control
Number of Fields: 2 load 5
Default: Do Nothing
0: Do Nothing Indicates add
Add Load 6 Read Size (bits): 8 Load Add Shed
42284 Command Only 1: Add Load command for Control
Number of Fields: 2 load 6
Default: Do Nothing
0: Do Nothing Indicates shed
Shed Load 1 Read Size (bits): 8 Load Add Shed
42285 Command Only 1: Shed Load command for Control
Number of Fields: 2 load 1
Default: Do Nothing

A029X159 (Issue 14) 417


8. DMC 1000 Modbus Enumerated Data 10-2015

Addr. System Name Access Specifications Description Function


0: Do Nothing Indicates shed
Shed Load 2 Read Size (bits): 8 Load Add Shed
42286 Command Only 1: Shed Load command for Control
Number of Fields: 2 load 2
Default: Do Nothing
0: Do Nothing Indicates shed
Shed Load 3 Read Size (bits): 8 Load Add Shed
42287 Command Only 1: Shed Load command for Control
Number of Fields: 2 load 3
Default: Do Nothing
0: Do Nothing Indicates shed
Shed Load 4 Read Size (bits): 8 Load Add Shed
42288 Command Only 1: Shed Load command for Control
Number of Fields: 2 load 4
Default: Do Nothing
0: Do Nothing Indicates shed
Shed Load 5 Read Size (bits): 8 Load Add Shed
42289 Command Only 1: Shed Load command for Control
Number of Fields: 2 load 5
Default: Do Nothing
0: Do Nothing Indicates shed
Shed Load 6 Read Size (bits): 8 Load Add Shed
42290 Command Only 1: Shed Load command for Control
Number of Fields: 2 load 6
Default: Do Nothing
0: Manual
1: Normal
Indicates the
PTC Genset 2: Normal Override current
Read Size (bits):8 PTC Operating
42296 Operating Only 3: Test operating Mode
Mode Number of Fields: 6 mode of the
4: Utility Fail
generator sets
5: Extended Parallel
Default:
0: Manual
1: Normal
Indicates the
PTC Transfer 2: Normal Override current
Read Size (bits):8 PTC Operating
42297 Pair Operating Only 3: Test operating Mode
Mode Number of Fields: 6 mode of the
4: Utility Fail
transfer pair
5: Extended Parallel
Default:
0: Open Transition Indicates the
1: Hard Closed transition type
PTC Operating Read Size (bits): 8 Transition currently PTC Operating
42298 Transition Type Only applicable to Mode
Number of Fields: 3 2: Soft Closed the PTC
Transition function
Default: operation
0: Master Synchronize
Only
1: Isolated Bus w/out
GM Main setting:
Sets system
Size (bits): 8 2: Isolated Bus w/GM
42300 System Read / topology; Application
Topology Write Number of Fields: 6 3: Common Bus control must be Configuration
4: Transfer Pair in manual to
set
5: Component Mode
Default: Master
Synchronize Only

418 A029X159 (Issue 14)


10-2015 8. DMC 1000 Modbus Enumerated Data

Addr. System Name Access Specifications Description Function


0: Open Transition
1: Hard Closed
Transition Sets the type
Read / Size (bits):8 of transition Application
42301 Transition Type Write 2: Soft Closed that will be Configuration
Number of Fields: 3
Transition used
Default: Open
Transition

0: Disabled Use to enable


Size (bits): 8
42302 Extended Read / 1: Enabled extended Application
Parallel Enable Write Number of Fields: 2 paralleling Configuration
Default: Disabled operation
Size (bits): 8
0: None
Number of Fields: 3
Load Demand Read / 1: Fixed Sequence Sets load Load Demand
42303 Type Write demand type Control
2: Run Hours
Default: None

0: Manual
Priority Control Read / Size (bits): 8 Sets priority
42304 Method Write 1: Automatic control method Priority Control
Number of Fields: 2
Default: Manual

0: Disabled Use to enable


Size (bits): 8
42326 Test With Load Read / 1: Enabled or disable load Application
Enable Write Number of Fields: 2 transfer during Configuration
Default: Disabled a test
selects where
Genset Bus 0: Internal the generator
Read / Size (bits):8 set kW setpoint Master Load
42328 kW Setpoint 1: Analog Input
Source Write Number of Fields: 2 will come from Control
Default: Internal for extended
paralleling
Selects where
the generator
Genset Bus 0: Internal set kVAR
Read / Size (bits):8 Master Load
42329 kVAR Setpoint Write 1: Analog Input setpoint will Control
Source Number of Fields: 2 come from
Default: Internal
extended
paralleling
Selects where
Utility Bus kW 0: Internal the utility kW
Read / Size (bits):8 setpoint will Master Load
42335 Setpoint 1: Analog Input
Source Write Number of Fields: 2 come from for Control
Default: Internal extended
paralleling
Selects where
Utility Bus 0: Internal the utility kVAR
Read / Size (bits):8 setpoint will Master Load
42336 kVAR Setpoint 1: Analog Input
Source Write Number of Fields: 2 come from Control
Default: Internal extended
paralleling

0: Inactive Use to
Size (bits):8
42342 Clear Fault Read / 1: Active completely Fault and Event
History Table Write Number of Fields: 2 clear the fault Info
Default: Inactive history table

A029X159 (Issue 14) 419


8. DMC 1000 Modbus Enumerated Data 10-2015

Addr. System Name Access Specifications Description Function


Use to
completely
Clear Size (bits):8 0: Inactive clear the
Read / Fault and Event
42343 Occurrence Write Number of Fields: 2 1: Active counts in faults Info
Table Default: Inactive and events
occurrence
tables
Use to
Genset Reset 0: Do Nothing permanently
Read / Size (bits):8 clear all
42344 All Energy 1: Clear Counters Energy
Meters Write Number of Fields: 2 generator set
Default: Do Nothing energy meter
values
Size (bits):8 Use to
0: Do Nothing permanently
Utility Reset All Read / Number of Fields: 2
42345 Energy Meters Write 1: Clear Counters clear all utility Energy
Default: Do Nothing energy meter
values
0: Genset % Level
(Open Loop)
1: Genset Bus kW Sets how and
(Closed Loop) where the kW
Extended will be
Paralleling kW Read / Size (bits):8 2: Genset Bus kW Master Load
42346 controlled for
Load Control Write Number of Fields: 4 w/Utility (open Loop) extended Control
Type 3: Utility Bus kW parallel
(Closed Loop) operation
Default: Genset Bus %
Level (Open Loop)
0: Genset Controllers
1: Genset Bus % Level
(Open Loop)
2: Genset Bus Power
Factor Sets how and
3: Genset Bus kVAR where the
Extended (Closed Loop)
Paralleling Read / Size (bits):8 kVAR will be Master Load
42347 kVAR Load Write 4: Genset Bus Power controlled for Control
Number of Fields: 7 extended
Control Type Factor (Closed Loop)
5: Utility Bus kVAR parallel
(Closed Loop) operation
6:Utility Bus Power
Factor(Closed Loop)
Default: Genset
Controllers

0: Disabled Enable if want


Size (bits):8
42349 Fail To Sync Read / 1: Enabled synchronizing Master Sync
Lockout Enable Write Number of Fields: 2 to stop if fail to Control
Default: Disabled sync occurs
Fail to Sync Use to enable
Open 0: Disabled or disable an
Read / Size (bits):16 PTC State
42350 Transition Write 1: Enabled open transition Machine
Retransfer Number of Fields: 2 retransfer upon
Default: Disabled
Enable a fail to sync

420 A029X159 (Issue 14)


10-2015 8. DMC 1000 Modbus Enumerated Data

Addr. System Name Access Specifications Description Function

Size (bits):8 In manual


0: Closed Requested mode, can be
Number of Fields: 3 used to
Gen CB Read / 1: No Command
42352 Manual Control Write semi–manually Breaker Control
2: Open Command control the
Default: No Command generator set
breaker
In manual
0: Closed Requested mode, can be
Size (bits):8 1: No Command
42353 Util CB Manual Read / used to Breaker Control
Control Write Number of Fields: 3 2: Open Command semi–manually
Default: No Command control the
utility breaker
0: Normal Use to invert
Synchronizer Read / Size (bits):8 Master Sync
42357 Polarity Write 1: Invert synchronizer Control
Number of Fields: 2 polarity
Default: Normal
0: Phase Match Sets the
Synchronize Read / Size (bits):8 Master Sync
42358 Method Write 1: Slip Frequency synchronizing Control
Number of Fields: 2 method
Default: Phase Match
Allows protocol
0: PCCNet CT the
Size (bits): 8
42359 Port Protocol Read / 1: MON PCCNet port to Communications
Selection Write Number of Fields: 2 be changed to
Default: PCCNet MON for
troubleshooting

System 0: Disabled Use to enable


Read / Size (bits): 8 or disable the System
42360 Scheduler 1: Enabled
Enable Write Number of Fields: 2 system Scheduler
Default: Disabled scheduler

0: Disabled Use to enable


Size (bits): 8
42361 Load Add Shed Read / 1: Enabled or disable the Load Add Shed
Enable Write Number of Fields: 2 load add shed Control
Default: Disabled feature

Open Use to enable


Transition 0: Disabled or disable the
Read / Size (bits): 8 shedding of Load Add Shed
42362 Retransfer 1: Enabled
Load Shed Write Number of Fields: 2 loads during Control
Default: Disabled open transition
Enable
retransfer
Indicates
Auto/Manual Size (bits): 8 0: Auto automatic or
Read / Load Add Shed
42363 Load Add Write Number of Fields: 2 1: Manual manual load Control
Restore Mode Default: Auto add restore
operation
Indicates type
0: None of load
Load 1 Device
Read / Size (bits): 8 1: Breaker connection to Load Add Shed
42367 Type
Write Number of Fields: 3 2: ATS load 1 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Size (bits): 8 1: Breaker
42368 Load 2 Device Read / connection to Load Add Shed
Type Write Number of Fields: 3 2: ATS load 2 add Control
Default: None shed control
and status I/O

A029X159 (Issue 14) 421


8. DMC 1000 Modbus Enumerated Data 10-2015

Addr. System Name Access Specifications Description Function


Indicates type
0: None of load
Size (bits): 8 1: Breaker
42369 Load 3 Device Read / connection to Load Add Shed
Type Write Number of Fields: 3 2: ATS load 3 add Control
Default: None shed control
and status I/O
Size (bits): 8 Indicates type
0: None of load
Number of Fields: 3
Load 4 Device Read / 1: Breaker connection to Load Add Shed
42370 Type Write load 4 add Control
2: ATS
Default: None shed control
and status I/O
Indicates type
Size (bits): 8 0: None of load
Number of Fields: 3 1: Breaker
42371 Load 5 Device Read / connection to Load Add Shed
Type Write 2: ATS load 5 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Size (bits):8 1: Breaker
42372 Load 6 Device Read / connected to Load Add Shed
Type Write Number of Fields: 3 2: ATS load 6 add Control
Default: None shed control
and status I/O
0: Both kW and Use to choose
Frequency method for
Genset Bus Size (bits):8 1: kW Only
42385 Overload Read / determining System
Method Write Number of Fields: 3 2: Frequency Only generator bus Information
Default: Both kW and overload
Frequency condition

0: Disabled Use to enable


Size (bits):8
42390 Load Demand Read / 1: Enabled or disable the Load Demand
Enable Write Number of Fields: 2 load demand Control
Default: Disabled feature
0: Gen1
1: Gen2 Sets GenA for Load Demand
Load Demand Read / Size (bits): 8
42391 GenA Write 2: Gen3 fixed sequence Control
Number of Fields: 4 load demand
3: Gen4
Default: Gen1
0: Gen1
1: Gen2 Sets GenB for Load Demand
Load Demand Read / Size (bits):8
42392 GenB Write 2: Gen3 fixed sequence Control
Number of Fields: 4 load demand
3: Gen4
Default: Gen2
0: Gen1
1: Gen2 Sets GenC for Load Demand
Load Demand Read / Size (bits):8
42393 GenC Write 2: Gen3 fixed sequence Control
Number of Fields: 4 load demand
3: Gen4
Default: Gen3
0: Gen1
Sets GenD
1: Gen2 (first to stop)
Load Demand Read / Size (bits):8 Load Demand
42394 GenD Write 2: Gen3 for fixed Control
Number of Fields: 4 sequence load
3: Gen4
demand
Default: Gen4

422 A029X159 (Issue 14)


10-2015 8. DMC 1000 Modbus Enumerated Data

Addr. System Name Access Specifications Description Function

0: L1–L2–L3 Defines what


Size (bits):8
42413 System Phase Read / 1:L1–L3–L2 the system System
Rotation Write Number of Fields: 2 phase rotation Information
Default: L1–L2–L3 sequence is

Scheduler 0: Disable Use to enable


Read / Size (bits):8 or disable the System
42419 Program x 1: Enable
Enable Write Number of Fields: 2 selected Scheduler
Default: Disable program
0: Once
1: Every Week
2: Every 2 Weeks
3: Every 3 Weeks
4: Every 4 Weeks
5: Every 5 Weeks
Scheduler Size (bits):8 6: First Week of Month Use to adjust
42420 Program x Read / 7: Second Week of repeat interval System
Number of Fields:
Repeat Interval Write 11 Month for the selected Scheduler
program
8: Third Week of
month
9: Forth Week of the
Month
10: Last Week of the
Month
Default: Once
0: No Load Use to adjust
Scheduler Size (bits): 8 1: With Load
42421 Program x Run Read / run mode for System
Mode Write Number of Fields: 3 2: Extended Parallel the selected Scheduler
Default: No Load program

0: Sunday
1: Monday
2: Tuesday Use to adjust
Scheduler Size (bits): 8 3: Wednesday start day of
42422 Program x Read / week for the System
Start Day Write Number of Fields: 7 4: Thursday selected Scheduler
5: Friday program
6: Saturday
Default: Sunday

Scheduler 0: Disable Use to enable


Read / Size (bits): 8 or disable the System
42428 Exception x 1: Enable
Enable Write Number of Fields: 2 selected Scheduler
Default: Disable exception
Use to adjust
Scheduler 0: Once Only the repeat
Read / Size (bits): 8 System
42429 Exception x Write 1: Every Year setting of the Scheduler
Repeat Number of Fields: 2 selected
Default: Once Only
exception

Daylight 0: Disabled Enables the


Read / Size (bits): 8 daylight
42437 Saving Time 1: Enabled Real Time Clock
Enable Write Number of Fields: 2 savings time
Default: Disabled feature

Load Demand Use to force a


0: Do Nothing refresh of the
Refresh Read / Size (bits): 8 Load Demand
42438 Sequence Write 1: Refresh Sequence active load Control
Number of Fields: 2 demand
Command Default: Do Nothing
sequence

A029X159 (Issue 14) 423


8. DMC 1000 Modbus Enumerated Data 10-2015

Addr. System Name Access Specifications Description Function

Genset 0: Wye Delta or Wye


Read / Size (bits):8
42439 Connection Write 1: Delta for generator AC Setup
Type Number of Fields: 2 set connection
Default: Wye

Genset CT 0: 1 Amp Generator set


Read / Size (bits): 8
42443 Secondary Write 1: 5 Amp CT secondary AC Setup
Current Number of Fields: 2 current
Default: 5 Amp

Utility 0: Wye Delta or Wye


Read / Size (bits): 8
42444 Connection Write 1: Delta for utility AC Setup
Type Number of Fields: 2 connection
Default: Wye

Utility CT 0: 1 Amp Utility CT


Read / Size (bits): 8
42448 Secondary Write 1: 5 Amp secondary AC Setup
Current Number of Fields: 2 current
Default: 5 Amp
0: 12V DC voltage
Nominal Read / Size (bits): 8 Battery Voltage
42454 Battery Voltage Write 1: 24V provided to the Protection
Number of Fields: 2 control
Default: 24V
Use to enable
Genset Online 0: Disable or disable the
Read / Size (bits): 8
42461 Capacity Write 1: Enable generator set PTC Sensors
Sensor Enable Number of Fields: 2 online capacity
Default: Disable
sensor
Indicates that
0: Inactive the generator
Gen Bus Base Read Size (bits):8 System
42472 Load Status Only 1: Active bus is on base Information
Number of Fields: 2 load extended
Default:
paralleling
Indicates that
0: Inactive the utility bus is System
Util Bus Peak Read Size (bits): 8
42473 Shave Status Only 1: Active on peak shave Information
Number of Fields: 2 extended
Default:
paralleling

Extended 0: Stop State of


Read / Size (bits): 8 extended
42600 Parallel Start 1: Start Discrete Inputs
Vol Write Number of Fields: 2 parallel start
Default: Stop volatile input

0: inactive State of
Size (bits): 8
42601 Synchronizer Read / 1: Active synchronizer Discrete Inputs
Enable Vol Write Number of Fields: 2 enable volatile
Default: inactive input
0: inactive State of utility
Utility Source Read / Size (bits): 8
42602 Failure Vol Write 1: Active source failure Discrete Inputs
Number of Fields: 2 volatile input
Default: inactive
0: No Inhibit State of
Transfer Inhibit Read / Size (bits):16
42603 Vol Write 1: Inhibit transfer inhibit Discrete Inputs
Number of Fields: 2 volatile input
Default: No Inhibit

0: No Inhibit State of
Size (bits):8
42604 Retransfer Read / 1: Inhibit retransfer Discrete Inputs
Inhibit Vol Write Number of Fields: 2 inhibit volatile
Default: No Inhibit input

0: No Inhibit State of
Size (bits): 8
42605 Gen CB Inhibit Read / 1: Inhibit generator CB Discrete Inputs
Vol Write Number of Fields: 2 inhibit volatile
Default: No Inhibit input

424 A029X159 (Issue 14)


10-2015 8. DMC 1000 Modbus Enumerated Data

Addr. System Name Access Specifications Description Function


0: No Inhibit State of utility
Util CB Inhibit Read / Size (bits): 8
42606 Vol Write 1: Inhibit CB inhibit Discrete Inputs
Number of Fields: 2 volatile input
Default: No Inhibit
0: Auto State of
Auto/Manual Read / Size (bits): 8
42607 Vol Write 1: Manual auto/manual Discrete Inputs
Number of Fields: 2 volatile input
Default: Auto
Size (bits): 8 0: Stop State of test
Read /
42608 Test Start Vol Write Number of Fields: 2 1: Start start volatile Discrete Inputs
Default: Stop input

0: Not Reset State of fault


Read / Size (bits): 8
42609 Fault Reset Vol Write 1: Reset reset volatile Discrete Inputs
Number of Fields: 2 input
Default: Not Reset
0: No Override State of
Read / Size (bits): 8
42610 Override Vol Write 1: Override override Discrete Inputs
Number of Fields: 2 volatile input
Default: No Override

Extended 0: Start State of


Read Size (bits): 8 extended
42611 Parallel Start 1: Stop Discrete Inputs
Sw Only Number of Fields: 2 parallel start
Default: input
0: Inactive State of
Synchronizer Read Size (bits): 8
42612 Enable Sw Only 1: Active synchronizer Discrete Inputs
Number of Fields: 2 enable input
Default:
0: Inactive State of utility
Utility Source Read Size (bits): 8
42613 Failure Sw Only 1: Active source failure Discrete Inputs
Number of Fields: 2 input
Default:
0: No Inhibit State of
Transfer Inhibit Read Size (bits): 8
42614 Sw Only 1: Inhibit transfer inhibit Discrete Inputs
Number of Fields: 2 input
Default:
0: No Inhibit State of
Retransfer Read Size (bits): 8
42615 Inhibit Sw Only 1: Inhibit retransfer Discrete Inputs
Number of Fields: 2 inhibit input
Default:
0: No Inhibit Sate of
Gen CB Inhibit Read Size (bits): 8
42616 Sw Only 1: Inhibit generator CB Discrete Inputs
Number of Fields: 2 inhibit input
Default:
0: No Inhibit
Util CB Inhibit Read Size (bits): 8 State of utility
42617 Sw Only 1: Inhibit CB inhibit input Discrete Inputs
Number of Fields: 2
Default:
0: Auto State of
Auto/Manual Read Size (bits): 8
42618 Sw Only 1: Manual auto/manual Discrete Inputs
Number of Fields: 2 input
Default:
0: Stop
Read Size (bits): 8 State of test
42619 Test Start Sw Only 1: Start start input Discrete Inputs
Number of Fields: 2
Default:
0: No Reset
Read Size (bits): 8 State of fault
42620 Fault Reset Sw Only 1: Reset reset input Discrete Inputs
Number of Fields: 2
Default:

A029X159 (Issue 14) 425


8. DMC 1000 Modbus Enumerated Data 10-2015

Addr. System Name Access Specifications Description Function


0: No Override
Read Size (bits): 8 State of
42621 Override Sw Only 1: Override override input Discrete Inputs
Number of Fields: 2
Default:
0: No Inhibit Indicates state
Read Size (bits): 8
42622 Master Inhibit Only 1: Inhibit of Master Priority Control
Number of Fields: 2 priority inhibit
Default:
0: Inactive State of
Gen CB Read Size (bits): 8
42623 Tripped Sw Only 1: Active generator CB Discrete Inputs
Number of Fields: 2 tripped input
Default:

0: Inactive State of
Size (bits): 8
42624 Gen CB Read / 1: Active generator CB Discrete Inputs
Tripped Vol Write Number of Fields: 2 tripped volatile
Default: Inactive input
0: Inactive State of utility
Util CB Tripped Read Size (bits): 8
42625 Sw Only 1: Active CB tripped Discrete Inputs
Number of Fields: 2 input
Default:
Size (bits): 8 0: Inactive State of utility
Util Cb Tripped Read /
42626 Vol Write Number of Fields: 4 1: Active CB tripped Discrete Inputs
Default: Inactive volatile input

0: L1–L2–L3
Genset Phase Read Size (bits): 8 Generator set
42627 Rotation Only 1: L1–L3–L2 phase rotation Phase
Number of Fields: 2
Default:
Size (bits): 8 0: L1–L2–L3
Utility Phase Read Utility phase
42628 Rotation Only Number of Fields: 2 1: L1–L3–L2 rotation Phase
Default:
Size (bits): 8 0: Breaker Open State of Gen1
Gen1 CB Read
42629 Position Sw Only Number of Fields: 2 1: Breaker Closed CB position Discrete Inputs
Default: input

0: Breaker Open State of Gen1


Gen1 CB Read / Size (bits): 8
42630 Position Vol Write 1: Breaker Closed CB position Discrete Inputs
Number of Fields: 2 volatile input
Default: Open
0: Breaker Open State of Gen2
Gen2 CB Read Size (bits): 8
42631 Position Sw Only 1: Breaker Closed CB position Discrete Inputs
Number of Fields: 2 input
Default:
0: Breaker Open State of Gen2
Gen2 CB Read / Size (bits): 8
42632 Position Vol Write 1: Breaker Closed CB position Discrete Inputs
Number of Fields: 2 volatile input
Default: Open
0: Breaker Open State of Gen3
Gen3 CB Read Size (bits):16
42633 Position Sw Only 1: Breaker Closed CB position Discrete Inputs
Number of Fields: 2 input
Default:
0: Breaker Open State of Gen3
Gen3 CB Read / Size (bits): 8
42634 Position Vol Write 1: Breaker Closed CB position Discrete Inputs
Number of Fields: 2 volatile input
Default: Open
0: Breaker Open State of Gen4
Gen4 CB Read Size (bits): 8
42635 Position Sw Only 1: Breaker Closed CB position Discrete Inputs
Number of Fields: 2 input
Default:

426 A029X159 (Issue 14)


10-2015 8. DMC 1000 Modbus Enumerated Data

Addr. System Name Access Specifications Description Function


0: Breaker Open State of Gen4
Gen4 CB Read / Size (bits): 8
42636 Position Vol Write 1: Breaker Closed CB position Discrete Inputs
Number of Fields: 2 volatile input
Default: Open
0: No Inhibit Use to
Network Read / Size (bits): 8
42637 Master Inhibit Write 1: Inhibit manually inhibit Priority Control
Number of Fields: 2 the module
Default: No Inhibit
0: Gen Does Not Exist
1: Offline For load
Gen1 Size (bits): 8 2: Waiting for Gen
42700 Availability Read demand use - Load Demand
State Only Number of Fields: 5 3: Online Indicates Control
4: Failed status of Gen1
Default:
0: Gen Does Not Exist
1: Offline For load
Gen2 Size (bits): 8 2: Waiting for Gen
42701 Availability Read demand use - Load Demand
State Only Number of Fields: 5 3: Online Indicates Control
4: Failed status of Gen2
Default:
0:Gen Does Not Exist
1: Offline For load
Gen3 Size (bits): 8 2: Waiting for Gen
42702 Availability Read demand use - Load Demand
State Only Number of Fields: 5 3: Online Indicates Control
4: Failed status of Gen3
Default:
0:Gen Does Not Exist
1: Offline For load
Gen4 Size (bits): 8
Read 2: Waiting for Gen demand use - Load Demand
42703 Availability Number of Fields: 5
State Only 3: Online Indicates Control
4: Failed status of Gen4
Default:
Size (bits): 8 0: Gen1
Indicates which
Number of Fields: 4 1: Gen2 generator set is Load Demand
Read
42712 GenA Only 2: Gen3 currently GenA Control
3: Gen4 for load
demand
Default:
Size (bits): 8 0: Gen1
Indicates which
Number of Fields: 4 1: Gen2 generator set is Load Demand
Read
42713 GenB Only 1: Gen3 currently GenB Control
1: Gen4 for load
demand
Default:
0: Gen1
Indicates which
1: Gen2 generator set is Load Demand
Read Size (bits): 8
42714 GenC Only 1: Gen3 currently GenC Control
Number of Fields: 4 for load
1: Gen4
demand
Default:

A029X159 (Issue 14) 427


8. DMC 1000 Modbus Enumerated Data 10-2015

Addr. System Name Access Specifications Description Function


0: Gen1 Indicates which
1: Gen2 generator set is
Read Size (bits): 8 currently GenD Load Demand
42715 GenD Only 1: Gen3 (first to stop) Control
Number of Fields: 4
1: Gen4 for load
Default: demand
Size (bits): 8
0: Off Indicates
Number of Fields: 3
Load Demand Read 1: Initial Delay Timing operating state Load Demand
42716 State Only of the load Control
2: Load Monitor
Default: demand control

0: Gen1
Indicates which
Size (bits): 8 1: Gen2 generator set is
Number of Fields: 5 2: Gen3
42721 Next Gen To Read next to be Load Demand
Restart Only 3: Gen4 restarted if load Control
4: None conditions are
met
Default:
0: Gen1
Size (bits): 8 Indicates which
1: Gen2 generator set is
Number of Fields: 5
2: Gen3
42722 Next Gen To Read next to be Load Demand
Shutdown Only 3: Gen4 stopped if load Control
4: None conditions are
met
Default:
Size (bits): 8
Number of Fields: 2 0: Run Status of the
Load Demand Read load demand
42723 Gen1 Driver Only 1: Load Demand Stop Gen1 driver Discrete Outputs
Status Default: output

Load Demand 0: Run Status of the


Read Size (bits): 8 load demand
42724 Gen2 Driver 1: Load Demand Stop Discrete Outputs
Status Only Number of Fields: 2 Gen2 driver
Default: output

Load Demand 0: Run Status of the


Read Size (bits): 8 load demand
42725 Gen3 Driver 1: Load Demand Stop Discrete Outputs
Status Only Number of Fields: 2 Gen3 driver
Default: output
Size (bits): 8
Number of Fields: 2 0: Run Status of the
Load Demand Read load demand
42726 Gen4 Driver Only 1: Load Demand Stop Gen4 driver Discrete Outputs
Status Default: output

Size (bits): 8 Indicates


Genset Bus 0: No Overload whether
Read Number of Fields: 2 System
42728 kW Overload Only 1: Overload generator bus Information
Status Default: is overloaded
based on kW
Size (bits): 8 Indicates
Genset Bus Number of Fields: 2 0: No Overload whether
Underfrequenc Read generator bus System
42729 y Overload Only 1: Overload is overloaded Information
Status Default: based on
frequency

428 A029X159 (Issue 14)


10-2015 8. DMC 1000 Modbus Enumerated Data

Addr. System Name Access Specifications Description Function


0: None
1: Program 1
2: Program 2
3: Program 3
4: Program 4
5: Program 5
6: Program 6
Size (bits): 8 7: Program 7
Number of Fields: 8: Program 8 Indicates the
19 9: Program 9 currently active
42730 Active Read scheduler System
Schedule Only 10: Program 10 program or Scheduler
11: Program 11 exception
12: Program 12
13: Exception 1
14: Exception 2
15: Exception 3
16: Exception 4
17: Exception 5
18: Exception 6
Default:
0: Off Indicates
1: No Load current run
Scheduler Run Read Size (bits): 8 command System
42731 Command Only 2: With Load coming from Scheduler
Number of Fields: 4
3: Extended Parallel the scheduler
Default: function
0: Do Nothing Clears all the
Modbus Clear Read / Size (bits): 8
42737 Counters Write 1: Clear Counters Modbus Communications
Number of Fields: 2 counters
Default: Do Nothing
Size (bits): 8
0: Normal
Number of Fields: 3 Use to set
Read / 1: Set Clock
42738 Clock Mode Write clock and save Real Time Clock
2: Save Clock setting
Default: Normal

0: Sunday
1: Monday
2: Tuesday
Size (bits): 8 3: Wednesday Indicates day
42745 Clock Day Read of week for Real Time Clock
Only Number of Fields: 7 4: Thursday current date
5: Friday
6: Saturday
Default:

A029X159 (Issue 14) 429


8. DMC 1000 Modbus Enumerated Data 10-2015

This page is intentionally blank.

430 A029X159 (Issue 14)


9 DMC 1000 Modbus Bitmap Data
NOTICE
Earlier versions of software may not support all of the Modbus registers in the following
table. If a particular register is not available in your installation, it is possible that the
Modbus connection is working but the controller software does not support that
particular register.

NOTICE
If an address or bit is not listed in this table, it is not implemented.

Addr. Bit# System Name Fault Code Event Name Response


42500 0 Fault Status 1455 Utility Main Warning
Bitmap 1 Breaker Position
Contact Warning
42500 1 Fault Status 2396 Utility Main Warning
Bitmap 1 Breaker Fail To
Close Warning
42500 2 Fault Status 2397 Utility Main Warning
Bitmap 1 Breaker Fail To
Open Warning
42500 3 Fault Status 1219 Utility Main Warning
Bitmap 1 Breaker Tripped
Warning
42500 4 Fault Status 1914 Utility Bus Phase Warning
Bitmap 1 Rotation Warning
42500 5 Fault Status 1912 Utility Bus Loss Warning
Bitmap 1 Of Phase
Warning
42500 6 Fault Status 2331 Utility Bus Warning
Bitmap 1 Undervoltage
Warning
42500 7 Fault Status 2358 Utility Bus Warning
Bitmap 1 Overvoltage
Warning
42500 8 Fault Status 1223 Utility Bus Warning
Bitmap 1 Frequency
Warning
42500 24 Fault Status 2648 Remote I/O Warning
Bitmap 1 Communication
Failure Warning
42500 25 Fault Status 1689 Real Time Clock Warning
Bitmap 1 Power Interrupt
Warning
42500 26 Fault Status 1335 AC Metering Out Warning
Bitmap 1 Of Range
Warning

A029X159 (Issue 14) 431


9. DMC 1000 Modbus Bitmap Data 10-2015

Addr. Bit# System Name Fault Code Event Name Response


42500 27 Fault Status 1999 Maximum Parallel Warning
Bitmap 1 Time Warning
42500 28 Fault Status 343 Hardware Failure Warning
Bitmap 1 Warning
42500 29 Fault Status 1456 Synchronizer Warning
Bitmap 1 Output Limit
Warning
42500 30 Fault Status 2416 Calibration Warning
Bitmap 1 Checksum
Warning
42500 31 Fault Status 353 EEPROM Write Warning
Bitmap 1 Error Warning
42502 0 Fault Status 1454 Genset Main Warning
Bitmap 2 Breaker Position
Contact Warning
42502 1 Fault Status 1452 Genset Main Warning
Bitmap 2 Breaker Fail To
Close Warning
42502 2 Fault Status 1453 Genset Main Warning
Bitmap 2 Breaker Tripped
Warning
42502 3 Fault Status 1328 Genset Bus Warning
Bitmap 2 Phase Rotation
Warning
42502 4 Fault Status 1915 Genset Bus Warning
Bitmap 2 Phase Rotation
Warning
42502 5 Fault Status 1913 Genset Bus Loss Warning
Bitmap 2 Of Phase
Warning
42502 6 Fault Status 1225 Genset Bus Warning
Bitmap 2 Undervoltage
Warning
42502 7 Fault Status 1224 Genset Bus Warning
Bitmap 2 Overvoltage
Warning
42502 8 Fault Status 1226 Genset Bus Warning
Bitmap 2 Frequency
Warning
42502 24 Fault Status 1541 Genset Failed To Warning
Bitmap 2 Come Online
Warning
42502 25 Fault Status 2647 Load Demand Warning
Bitmap 2 Setup Warning
42502 26 Fault Status 1444 Genset Bus Warning
Bitmap 2 Overload Warning
42502 27 Fault Status 1989 kW Load Control Warning
Bitmap 2 Output Limit
Warning
42502 28 Fault Status 1991 kVAR Load Warning
Bitmap 2 Control Output
Limit Warning

432 A029X159 (Issue 14)


10-2015 9. DMC 1000 Modbus Bitmap Data

Addr. Bit# System Name Fault Code Event Name Response


42502 29 Fault Status 1121 Fail To Warning
Bitmap 2 Disconnect
Warning
42502 30 Fault Status 1458 Synchronizer Warning
Bitmap 2 Phase Rotation
Mismatch
Warning
42502 31 Fault Status 1457 Fail To Warning
Bitmap 2 Synchronizer
Warning
42504 0 Event Status 1222 Not in Automatic Event
Bitmap 1 Event
42504 1 Event Status 1483 Common Warning Event
Bitmap 1 Event
42504 2 Event Status 2965 Genset Bus Event
Bitmap 1 Available Event
42504 3 Event Status 2328 Utility Bus Event
Bitmap 1 Available Event
42504 4 Event Status 2333 Genset Bus Event
Bitmap 1 Connected Event
42504 5 Event Status 2332 Utility Bus Event
Bitmap 1 Connected Event
42504 6 Event Status 2971 Test / Extended Event
Bitmap 1 Parallel Event
42504 7 Event Status 1916 Synchronized Event
Bitmap 1 Event
42504 8 Event Status 1534 Load Control Event
Bitmap 1 Output Event

A029X159 (Issue 14) 433


9. DMC 1000 Modbus Bitmap Data 10-2015

This page is intentionally blank.

434 A029X159 (Issue 14)


10 DMC 1500 Communication Server 1
10.1 Modbus Address: 2 (Slave)
NOTICE
If an address or bit is not listed in this table, it is not implemented.

NOTICE
The external device can read 1-40 contiguous registers, write 1-40 contiguous registers,
or read diagnostic counters.

Modbus Address Bit # Alarm Event


40001 0 (LSB) Utility Main Breaker Position Contact Warning
40001 1 Utility Main Breaker Fail To Close Warning
40001 2 Utility Main Breaker Fail To Open Warning
40001 3 Utility Main Breaker Tripped Warning
40001 4 Utility Bus Phase Rotation Warning
40001 5 Utility Bus Loss of Phase Warning
40001 6 Utility Bus Undervoltage Warning
40001 7 Utility Bus Overvoltage Warning
40001 8 Utility Bus Frequency Warning
40001 9 Remote IO Comm Failure Warning
40001 10 Real Time Clock Power Interrupt Warning
40001 11 AC Metering Out Of Range Warning
40001 12 Maximum Parallel Time Warning
40001 13 Not Implemented
40001 14 Synchronizer Output Limit Warning
40001 15 (MSB) Calibration Checksum Warning MCM 3320

Modbus Address Bit # Alarm Event


40002 0 (LSB) EEPROM Write Error Warning MCM 3320
40002 1 Genset Main Breaker Position Contact Warning
40002 2 Genset Main Breaker Fail to Close Warning
40002 3 Genset Main Breaker Fail to Open Warning
40002 4 Genset Main Breaker Tripped Warning
40002 5 Genset Bus Phase Rotation Warning

A029X159 (Issue 14) 435


10. DMC 1500 Communication Server 1 10-2015

Modbus Address Bit # Alarm Event


40002 6 Genset Bus Loss of Phase Warning
40002 7 Genset Bus Undervoltage Warning
40002 8 Genset Bus Overvoltage Warning
40002 9 Genset Bus Frequency Warning
40002 10 Low Battery Voltage Warning MCM 3320
40002 11 High Battery Voltage Warning MCM 3320
40002 12 Genset Failed to Come Online Warning
40002 13 Load Demand Setup Warning
40002 14 Genset Bus Over Load Limit Warning
40002 15 (MSB) kW Load Control Output Limit Warning

Modbus Address Bit # Alarm Event


40003 0 (LSB) kVAR Load Control Output Limit Warning
40003 1 Fail to Disconnect Warning
40003 2 Synchronizer Phase Rotation Mismatch Warning
40003 3 Fail to Synchronize Warning
40003 4 Normal Operation Lockout
40003 5 Common Warning MCM 3320
40003 6 Common Server 1 to Network ATS Comm Failure
40003 7 Common Server 1 to MCM3320 Comm Failure
40003 8 Common Server 1 Battery Warning
40003 9 Common Server 1 Comm Server 2 Comm Failure
40003 10 Not Implemented
40003 11 Not Implemented
40003 12 Not Implemented
40003 13 Not Implemented
40003 14 Not Implemented
40003 15 (MSB) Not Implemented

Modbus Address Bit # Alarm Event


40004 0 (LSB) Feeder Breaker 1 Trip
40004 1 Feeder Breaker 2 Trip
40004 2 Feeder Breaker 3 Trip
40004 3 Feeder Breaker 4 Trip
40004 4 Feeder Breaker 5 Trip
40004 5 Feeder Breaker 6 Trip
40004 6 Feeder Breaker 7 Trip

436 A029X159 (Issue 14)


10-2015 10. DMC 1500 Communication Server 1

Modbus Address Bit # Alarm Event


40004 7 Feeder Breaker 8 Trip
40004 8 Feeder Breaker 9 Trip
40004 9 Feeder Breaker 10 Trip
40004 10 Not Implemented
40004 11 Not Implemented
40004 12 Not Implemented
40004 13 Not Implemented
40004 14 Not Implemented
40004 15 (MSB) Not Implemented

NOTICE
40005 is not implemented.

Modbus Address Bit # Alarm Event


40006 0 (LSB) System in Auto-Opened Transition
40006 1 System in Auto-Hard Closed Transition
40006 2 System in Auto-Soft Closed Transition
40006 3 System Manual Mode Active
40006 4 System Automatic Mode Active
40006 5 Common Warning Event
40006 6 Genset Bus Available Event
40006 7 Utility Bus Available Event
40006 8 Genset Bus Connected Event
40006 9 Utility Bus Connected Event
40006 10 Synchronized Event
40006 11 Load Control Output Event
40006 12 Genset Source Unloaded Event
40006 13 Utility Source Unloaded Event
40006 14 Genset Bus Load Event
40006 15 (MSB) Utility Bus Peak Shave Event

Modbus Address Bit # Alarm Event


40007 0 (LSB) Extended Paralleling Enable
40007 1 Extended Paralleling Disable
40007 2 System in Extended Parallel
40007 3 System in Test with Load

A029X159 (Issue 14) 437


10. DMC 1500 Communication Server 1 10-2015

Modbus Address Bit # Alarm Event


40007 4 System in Test without Load
40007 5 System Test Off
40007 6 Load Demand Enable
40007 7 Load Demand Disable
40007 8 Extended Parallel Off
40007 9 Not Implemented
40007 10 Not Implemented
40007 11 Not Implemented
40007 12 Not Implemented
40007 13 Not Implemented
40007 14 Not Implemented
40007 15 (MSB) Not Implemented

10.2 Generator Set Bus Data


Generator Bus Data MB Address Data Type Multiplier Units
Generator Set L1N Volts 40009 16U 1 Volts
Generator Set L2N Volts 40010 16U 1 Volts
Generator Set L3N Volts 40011 16U 1 Volts
Generator Set LN Average Volt 40012 16U 1 Volts
Generator set L1L2 Volts 40013 16U 1 Volts
Generator Set L2L3 Volts 40014 16U 1 Volts
Generator Set L3L1 Volts 40015 16U 1 Volts
Generator Set LL Average Volts 40016 16U 1 Volts
Generator Set L1 Current 40017 16U 1 Amps
Generator Set L2 Current 40018 16U 1 Amps
Generator Set L3 Current 40019 16U 1 Amps
Generator Set Average Current 40020 16U 1 Amps
Generator Set L1 kW 40021 16S 1 kW
Generator Set L2 kW 40022 16S 1 kW
Generator Set L3 kW 40023 6S 1 kW
Generator Set Total kW 40024 16S 1 kW
Generator Set L1 kVAR 40025 16S 1 kVAR
Generator Set L2 kVAR 40026 16S 1 kVAR
Generator Set L3 kVAR 40027 16S 1 kVAR
Generator Set Total kVAR 40028 16S 1 kVAR
Generator Set Total Power Factor 40029 16S 0.01
Generator Set L1 kVA 40030 16U 1 kVA

438 A029X159 (Issue 14)


10-2015 10. DMC 1500 Communication Server 1

Generator Bus Data MB Address Data Type Multiplier Units


Generator Set L2 kVA 40031 16U 1 kVA
Generator Set L3 kVA 40032 16U 1 kVA
Generator Set Total kVA 40033 16U 1 kVA
MB Generator Set Frequency 40034 16U 0.1 Hz
Generator Set Total Negative kWh 40035 32U 1 kWh
40036
Generator Set Total Positive kWh 40037 32U 1 kWh
40038
Generator Set Total Net kWh 40039 32S 1 kWh
40040
Generator Set Total Negative kVARh 40041 32U 1 kVARh
40042
Generator Set Total Positive kVARh 40043 32U 1 kVARh
40044
Generator Set Total Net kVARh 40045 32S 1 kVARh
40046
Generator Set Total kVAh 40047 32U 1 kVAh
40048
Generator Set Available Current 40049 16U 1 Amps
Generator Set L1 Current Percent 40050 16U 0.1 %
Generator Set L2 Current Percent 40051 16U 0.1 %
Generator Set L3 Current Percent 40052 16U 0.1 %
Generator Set Total kW Percent 40053 16U 0.1 %
Generator Set Frequency Percent 40054 16S 0.1 %
Generator Set L1L2 Voltage Percent 40055 16U 0.1 %
Generator Set L2L3 Voltage Percent 40056 16U 0.1 %
Generator Set L3L1 Voltage Percent 40057 16U 0.1 %

10.3 Utility Bus Data


Utility Bus Data MB Address Data Type Multiplier Units
Utility L1N Voltage 40059 16U 1 Volts
Utility L2N Voltage 40060 16U 1 Volts
Utility L3N Voltage 40061 16U 1 Volts
Utility LN Average Voltage 40062 16U 1 Volts
Utility L1L2 Voltage 40063 16U 1 Volts
Utility L2L3 Voltage 40064 16U 1 Volts
Utility L3L1 Voltage 40065 16U 1 Volts

A029X159 (Issue 14) 439


10. DMC 1500 Communication Server 1 10-2015

Utility Bus Data MB Address Data Type Multiplier Units


Utility LL Average Voltage 40066 16U 1 Volts
Utility L1 Current 40067 16U 1 Amps
Utility L2 Current 40068 16U 1 Amps
Utility L3 Current 40069 16U 1 Amps
Utility Average Current 40070 16U 1 Amps
Utility L1 kW 40071 16S 1 kW
Utility L2 kW 40072 16S 1 kW
Utility L3 kW 40073 16S 1 kW
Utility Total kW 40074 16S 1 kW
Utility L1 kVAR 40075 16S 1 kVAR
Utility L2 kVAR 40076 16S 1 kVAR
Utility L3 kVAR 40077 16S 1 kVAR
Utility Total kVAR 40078 16S 1 kVAR
Utility Total Power Factor 40079 16S 0.01
Utility L1 kVA 40080 16U 1 kVA
Utility L2 kVA 40081 16U 1 kVA
Utility L3 kVA 40082 16U 1 kVA
Utility Total kVA 40083 16U 1 kVA
MB Utility Frequency 40084 16U 0.1 Hz
Utility Total Negative kWh 40085 32U 1 kWh
40086
Utility Total Positive kWh 40087 32U 1 kWh
40088
Utility Total Net kWh 40089 32S 1 kWh
40090
Utility Total Negative kVARh 40091 32U 1 kVARh
40092
Utility Total Positive kVARh 40093 32U 1 kVARh
40094
Utility Total Net kVARh 40095 32S 1 kVARh
40096
Utility Total kVAh 40097 32U 1 kVAh
40098
System Total kW 40099 16S 1 kW
System Total kVAR 40100 16S 0.01 kVAR
System Total Power Factor 40101 16S 1
System Total kVA 40102 16U 1 KVA

440 A029X159 (Issue 14)


10-2015 10. DMC 1500 Communication Server 1

10.4 ATS 1-5 DATA


ATS Raw Data ATS 1 ATS 2 ATS 3 ATS 4 ATS 5 Multiplier Units
Device Type 40257 40317 40377 40437 40497
Mode (See Table 7 on page 443) 40258 40318 40378 40438 40498
State (See Table 6 on page 442) 40259 40319 40379 40439 40499
Fault Code 40260 40320 40380 40440 40500
Fault Type (See Table 8 on page 40261 40321 40381 40441 40501
443)
Percent Amps 40262 40322 40382 40442 40502 0.5 %
Total kW 40263 40323 40383 40443 40503
NFPA 110 (See Table 2 on page 40264 40324 40384 40444 40504
379)
NFPA Extended(See Table 3 on 40265 40325 40385 40445 40505
page 379)
Frequency Load 40266 40326 40386 40446 40506 0.1 Hz
Total pf Load 40267 40327 40387 40447 40507 0.00005 pf
Total kVA Load 40268 40328 40388 40448 40508 kVA
Total kW Load 40269 40329 40389 40449 40509 kW
Total kVAR Load 40270 40330 40390 40450 40510 kVAR
Volts ab Load 40271 40331 40391 40451 40511 Volts
Volts bc Load 40272 40332 40392 40452 40512 Volts
Volts ca Load 40273 40333 40393 40453 40513 Volts
Volts a Load 40274 40334 40394 40454 40514 Volts
Volts b Load 40275 40335 40395 40455 40515 Volt
Volts c Load 40276 40336 40396 40456 40516 Volts
Amps a Load 40277 40337 40397 40457 40517 Amps
Amps b Load 40278 40338 40398 40458 40518 Amps
Amps c Load 40279 40339 40399 40459 40519 Amps
Percent Amps a Load 40280 40340 40400 40460 40520 0.5 %
Percent Amps b Load 40281 40341 40401 40461 40521 0.5 %
Percent Amps c Load 40282 40342 40402 40462 40522 0.5 %
Frequency SRC1 40283 40343 40403 40463 40523 0.1 Hz
Total pf SRC1 40284 40344 40404 40464 40524 0.00005 PF
Total kVA SRC1 40285 40345 40405 40465 40525
Total kW SRC1 40286 40346 40406 40466 40526
Total kVAR SRC1 40287 40347 40407 40467 40527
Volts ab SRC1 40288 40348 40408 40468 40528
Volts bc SRC1 40289 40349 40409 40469 40529
Volts ca SRC1 40290 40350 40410 40470 40530

A029X159 (Issue 14) 441


10. DMC 1500 Communication Server 1 10-2015

ATS Raw Data ATS 1 ATS 2 ATS 3 ATS 4 ATS 5 Multiplier Units
Volts a SRC1 40291 40351 40411 40471 40531
Volts b SRC1 40292 40352 40412 40472 40532 Volts
Volts c SRC1 40293 40353 40413 40473 40533
Amps a SCR1 40294 40354 40414 40474 40534 Amps
Amps b SCR1 40295 40355 40415 40475 40535
Amps c SRC1 40296 40356 40416 40476 40536
Percent Amps a SCR1 40297 40357 40417 40477 40537 0.5 %
Percent Amps b SCR1 40298 40358 40418 40478 40538 0.5 %
Percent Amps c SCR1 40299 40359 40419 40479 40539 0.5 %
Frequency SRC2 40300 40360 40420 40480 40540 0.1 Hz
Total pf SRC2 40301 40361 40421 40481 40541 0.00005 pf
Total kVA SRC2 40302 40362 40422 40482 40542 kVA
Total kW SRC2 40303 40363 40423 40483 40543 kW
Total kVAR SRC2 40304 40364 40424 40484 40544 kVAR
Volts ab SRC2 40305 40365 40425 40485 40545 Volts
Volts bc SRC2 40306 40366 40426 40486 40546 Volts
Volts ca SRC2 40307 40367 40427 40487 40547 Volts
Volts a SRC2 40308 40368 40428 40488 40548 Volts
Volts b SRC2 40309 40369 40429 40489 40549 Volts
Volts c SRC2 40310 40370 40430 40490 40550 Volts
Amps a SRC2 40311 40371 40431 40491 40551 Amps
Amps b SRC2 40312 40372 40432 40492 40552 Amps
Amps c SRC2 40313 40373 40433 40493 40553 Amps
Percent Amps a SRC2 40314 40374 40434 40494 40554 0.5 %
Percent Amps b SRC2 40315 40375 40435 40495 40555 0.5 %
Percent Amps c SRC2 40316 40376 40436 40496 40556 0.5 %

10.5 Word Data


Reference Tables ATS 1-5 and 6-10.

TABLE 6.

Digital State
0 Neutral
1 Source 1 Connected
2 Source 2 Connected
3 Source 1 and 2 Connected

442 A029X159 (Issue 14)


10-2015 10. DMC 1500 Communication Server 1

TABLE 7.

Digital Mode
0 Test
1 Utility / Genset
2 Utility / Utility
3 Genset / Genset

TABLE 8.

Digital Fault Type


0 No Faults
1 Warning

10.6 ATS 6-10 DATA


ATS Raw Data ATS 6 ATS 7 ATS 8 ATS 9 ATS 10 Multiplier Units
Device Type 40557 40617 40677 40737 40797
Mode (See Table 7 on page 443) 40558 40618 40678 40738 40798
State (See Table 6 on page 442) 40559 40619 40679 40739 40799
Fault Code 40560 40620 40680 40740 40800
Fault Type (See Table 8 on page 40561 40621 40681 40741 40801
443)
Percent Amps 40562 40622 40682 40742 40802 0.5 %
Total kW 40563 40623 40683 40743 40803
NFPA 110 (See Table 2 on page 40564 40624 40684 40744 40804
379)
NFPA Extended (See Table 3 on 40565 40625 40685 40745 40805
page 379)
Frequency Load 40566 40626 40686 40746 40806 0.1 Hz
Total pf Load 40567 40627 40687 40747 40807 0.00005 PF
Total kVA Load 40568 40628 40688 40748 40808 kVA
Total kW Load 40569 40629 40689 40749 40809 kW
Total kVAR Load 40570 40630 40690 40750 40810 kVAR
Volts ab Load 40571 40631 40691 40751 40811 Volts
Volts bc Load 40572 40632 40692 40752 40812 Volts
Volts ca Load 40573 40633 40693 40753 40813 Volts
Volts a Load 40574 40634 40694 40754 40814 Volts
Volts b Load 40575 40635 40695 40755 40815 Volts
Volts c Load 40576 40636 40696 40756 40816 Volts
Amps a Load 40577 40637 40697 40757 40817 Amps

A029X159 (Issue 14) 443


10. DMC 1500 Communication Server 1 10-2015

ATS Raw Data ATS 6 ATS 7 ATS 8 ATS 9 ATS 10 Multiplier Units
Amps b Load 40578 40638 40698 40758 40818 Amps
Amps c Load 40579 40639 40699 40759 40819 Amps
Percent Amps a Load 40580 40640 40700 40760 40820 0.5 %
Percent Amps b Load 40581 40641 40701 40761 40821 0.5 %
Percent Amps c Load 40582 40642 40702 40762 40822 0.5 %
Frequency SRC1 40583 40643 40703 40763 40823 0.1 Hz
Total pf SRC1 40584 40644 40704 40764 40824 0.00005 PF
Total kVA SRC1 40585 40645 40705 40765 40825 kVA
Total kW SRC1 40586 40646 40706 40766 40826 kW
Total kVAR SRC1 40587 40647 40707 40767 40827 kVAR
Volts bc SRC1 40588 40648 40708 40868 40828 Volts
Volts bc SRC1 40589 40649 40709 40869 40829 Volts
Volts ca SRC1 40590 40650 40710 40870 40830 Volts
Volts a SRC1 40591 40651 40711 40871 40831 Volts
Volts b SRC1 40592 40652 40712 40872 40832 Volts
Volts c SRC1 40593 40653 40713 40873 40833 Volts
Amps a SCR1 40594 40654 40714 40874 40834 Amps
Amps b SCR1 40595 40655 40715 40875 40835 Amps
Amps c SRC1 40596 40656 40716 40876 40836 Amps
Percent Amps a SCR1 40597 40657 40717 40777 40837 0.5 %
Percent Amps b SCR1 40598 40658 40718 40778 40838 0.5 %
Percent Amps c SCR1 40599 40659 40719 40779 40839 0.5 %
Frequency SRC2 40600 40660 40720 40780 40840 0.1 Hz
Total pf SRC2 40601 40661 40721 40781 40841 0.00005 pf
Total KVA SRC2 40602 40662 40722 40782 40842 kVA
Total kW SRC2 40603 40663 40723 40783 40843 kW
Total KVAR SRC2 40604 40664 40724 40784 40844 kVAR
Volts ab SRC2 40605 40665 40725 40785 40845 Volts
Volts bc SRC2 40606 40666 40726 40786 40846 Volts
Volts ca SRC2 40607 40667 40727 40787 40847 Volts
Volts a SRC2 40608 40668 40728 40788 40848 Volts
Volts b SRC2 40609 40669 40729 40789 40849 Volts
Volts c SRC2 40610 40670 40730 40790 40850 Volts
Amps a SRC2 40611 40671 40731 40791 40851 Amps
Amps b SRC2 40612 40672 40732 40792 40852 Amps
Amps c SRC2 40613 40673 40733 40793 40853 Amps
Percent Amps a SRC2 40614 40674 40734 40794 40854 0.5 %
Percent Amps b SRC2 40615 40675 40735 40795 40855 0.5 %

444 A029X159 (Issue 14)


10-2015 10. DMC 1500 Communication Server 1

ATS Raw Data ATS 6 ATS 7 ATS 8 ATS 9 ATS 10 Multiplier Units
Percent Amps c SRC2 40616 40676 40736 40796 40856 0.5 %

A029X159 (Issue 14) 445


10. DMC 1500 Communication Server 1 10-2015

This page is intentionally blank.

446 A029X159 (Issue 14)


11 DMC 1500 Communication Server 2
11.1 Modbus Address: 1 (Slave)
NOTICE
If an address or bit is not listed in this table, it is not implemented.

NOTICE
The external device can read 1-40 contiguous registers, write 1-40 contiguous registers,
or read diagnostic counters.

Modbus Address Bit # Alarm Event


40001 0 (LSB) Neutral Earthing 1 Fail to Open Warning
40001 1 Neutral Earthing 2 Fail to Open Warning
40001 2 Neutral Earthing 3 Fail to Open Warning
40001 3 Neutral Earthing 4 Fail to Open Warning
40001 4 Neutral Earthing 5 Fail to Open Warning
40001 5 Neutral Earthing 6 Fail to Open Warning
40001 6 Neutral Earthing 7 Fail to Open Warning
40001 7 Neutral Earthing 8 Fail to Open Warning
40001 8 Neutral Earthing 1 Fail to Closed Warning
40001 9 Neutral Earthing 2 Fail to Closed Warning
40001 10 Neutral Earthing 3 Fail to Closed Warning
40001 11 Neutral Earthing 4 Fail to Closed Warning
40001 12 Neutral Earthing 5 Fail to Closed Warning
40001 13 Neutral Earthing 6 Fail to Closed Warning
40001 14 Neutral Earthing 7 Fail to Closed Warning
40001 15 (MSB) Neutral Earthing 8 Fail to Closed Warning

Modbus Address Bit # Alarm Event


40002 0 (LSB) Neutral Earthing 1 Tripped Warning
40002 1 Neutral Earthing 2 Tripped Warning
40002 2 Neutral Earthing 3 Tripped Warning
40002 3 Neutral Earthing 4 Tripped Warning
40002 4 Neutral Earthing 5 Tripped Warning
40002 5 Neutral Earthing 6 Tripped Warning

A029X159 (Issue 14) 447


11. DMC 1500 Communication Server 2 10-2015

Modbus Address Bit # Alarm Event


40002 6 Neutral Earthing 7 Tripped Warning
40002 7 Neutral Earthing 8 Tripped Warning
40002 8 Undergrounded Bus Warning
40002 9 Undergrounded Bus Failure - System Shutdown
40002 10 Multiple NECs Connected
40002 11 Multiple System Grounds Connected
40002 12 Not Implemented
40002 13 Not Implemented
40002 14 Not Implemented
40002 15 (MSB) Not Implemented

Modbus Address Bit # Alarm Event


40003 0 (LSB) Station Battery Power Supply Fault
40003 1 UPS Fault
40003 2 On Station Battery Warning
40003 3 System Manual Mode Active
40003 4 Utility Failure
40003 5 Utility Out of Limits for Extended Parallel
40003 6 Common Server 2 Battery Warning
40003 7 System Emergency Stop
40003 8 Hardware Failure Warning MCM 3320
40003 9 Not Implemented
40003 10 Not Implemented
40003 11 Not Implemented
40003 12 Not Implemented
40003 13 Not Implemented
40003 14 Not Implemented
40003 15 (MSB) Not Implemented

Modbus Address Bit # Alarm Event


40004 0 (LSB) Illegal Genset Node Address Assignment
40004 1 Not Implemented
40004 2 Not Implemented
40004 3 Comm Server 2 to Comm Server 1 Comm Failure
40004 4 Manufacturing Test Mode Active
40004 5 Not Implemented
40004 6 Not Implemented

448 A029X159 (Issue 14)


10-2015 11. DMC 1500 Communication Server 2

Modbus Address Bit # Alarm Event


40004 7 Not Implemented
40004 8 Comm Server 2 to Genset 1 Comm Failure
40004 9 Comm Server 2 to Genset 2 Comm Failure
40004 10 Comm Server 2 to Genset 3 Comm Failure
40004 11 Comm Server 2 to Genset 4 Comm Failure
40004 12 Comm Server 2 to Genset 5 Comm Failure
40004 13 Comm Server 2 to Genset 6 Comm Failure
40004 14 Comm Server 2 to Genset 7 Comm Failure
40004 15 (MSB) Comm Server 2 to Genset 8 Comm Failure

NOTICE
40005 is unused.

Modbus Address Bit # Alarm Event


40006 0 (LSB) Gen 1 Breaker Closed
40006 1 Gen 2 Breaker Closed
40006 2 Gen 3 Breaker Closed
40006 3 Gen 4 Breaker Closed
40006 4 Gen 5 Breaker Closed
40006 5 Gen 6 Breaker Closed
40006 6 Gen 7 Breaker Closed
40006 7 Gen 8 Breaker Closed
40006 8 Gen 1 Breaker Open
40006 9 Gen 2 Breaker Open
40006 10 Gen 3 Breaker Open
40006 11 Gen 4 Breaker Open
40006 12 Gen 5 Breaker Open
40006 13 Gen 6 Breaker Open
40006 14 Gen 7 Breaker Open
40006 15 (MSB) Gen 8 Breaker Open

Modbus Address Bit # Alarm Event


40007 0 (LSB) Gen 1 Running
40007 1 Gen 2 Running
40007 2 Gen 3 Running
40007 3 Gen 4 Running

A029X159 (Issue 14) 449


11. DMC 1500 Communication Server 2 10-2015

Modbus Address Bit # Alarm Event


40007 4 Gen 5 Running
40007 5 Gen 6 Running
40007 6 Gen 7 Running
40007 7 Gen 8 Running
40007 8 Gen 1 Fault
40007 9 Gen 2 Fault
40007 10 Gen 3 Fault
40007 11 Gen 4 Fault
40007 12 Gen 5 Fault
40007 13 Gen 6 Fault
40007 14 Gen 7 Fault
40007 15 (MSB) Gen 8 Fault

Modbus Address Bit # Alarm Event


40008 0 (LSB) Gen 1 Shut Down in Load Demand
40008 1 Gen 2 Shut Down in Load Demand
40008 2 Gen 3 Shut Down in Load Demand
40008 3 Gen 4 Shut Down in Load Demand
40008 4 Gen 5 Shut Down in Load Demand
40008 5 Gen 6 Shut Down in Load Demand
40008 6 Gen 7 Shut Down in Load Demand
40008 7 Gen 8 Shut Down in Load Demand
40008 8 Gen Start Signal On MCM 3320
40008 9 Gen Start Signal Off MCM 3320
40008 10 Gen Main Breaker Closed
40008 11 Gen Main Breaker Opened
40008 12 Utility Main Breaker Closed
40008 13 Utility Main Breaker Opened
40008 14 Utility Failure
40008 15 (MSB) Return to Utility

Modbus Address Bit # Alarm Event


40009 0 (LSB) Remote Commands Enable
40009 1 Remote Commands Disable
40009 2 Remote Test On
40009 3 Remote Test Off
40009 4 Remote Extended Parallel On

450 A029X159 (Issue 14)


10-2015 11. DMC 1500 Communication Server 2

Modbus Address Bit # Alarm Event


40009 5 Remote Extended Parallel Off
40009 6 Remote Transfer Inhibit On
40009 7 Remote Transfer Inhibit Off
40009 8 Remote Retransfer Inhibit On
40009 9 Remote Retransfer Inhibit Off
40009 10 Auto Genset Start Inhibit in Manual Mode Enable
40009 11 Auto Genset Start Inhibit in Manual Mode Disable
40009 12 Not Implemented
40009 13 Not Implemented
40009 14 Not Implemented
40009 15 (MSB) Not Implemented

11.2 Generator Raw Data Gen 1-5


Generator Raw Data Gen 1 Gen 2 Gen 3 Gen 4 Gen 5 Multiplier Units
Device Type 40011 40066 40121 40176 40231
Control Switch (See Table 15 on 40012 40067 40122 40177 40232
page 454)
State (See Table 9 on page 453) 40013 40068 40123 40178 40233
Fault Code 40014 40069 40124 40179 40234
Fault Type (SeeTable 14 on page 40015 40070 40125 40180 40235
454)
Percent kW Standby 40016 40071 40126 40181 40236 0.5 %
Total kW 40017 40072 40127 40182 40237
NFPA 110 (See Table 4 on page 40018 40073 40128 40183 40238
380)
NFPA Extended (See Table 5 on 40019 40074 40129 40184 40239
page 380)
Frequency 40020 40075 40130 40185 40240 0.1 Hz
Total pf 40021 40076 40131 40186 40241 0.00005 pf
Total kVA 40022 40077 40132 40187 40242 kVA
Total kW 40023 40078 40133 40188 40243 kW
Total kVAR 40024 40079 40134 40189 40244 kVAR
Volts ab 40025 40080 40135 40190 40245 Volts
Volts bc 40026 40081 40136 40191 40246 Volts
Volts ca 40027 40082 40137 40192 40247 Volts
Volts a 40028 40083 40138 40193 40248 Volts
Volts b 40029 40084 40139 40194 40249 Volt
Volts c 40030 40085 40140 40195 40250 Volts
Amps a 40031 40086 40141 40196 40251 Amps

A029X159 (Issue 14) 451


11. DMC 1500 Communication Server 2 10-2015

Generator Raw Data Gen 1 Gen 2 Gen 3 Gen 4 Gen 5 Multiplier Units
Amps b 40032 40087 40142 40197 40252 Amps
Amps c 40033 40088 40143 40198 40253 Amps
Percent Amps a 40034 40089 40144 40199 40254 0.5 %
Percent Amps b 40035 40090 40145 40200 40255 0.5 %
Percent Amps c 40036 40091 40146 40201 40256 0.5 %
Battery Voltage 40037 40092 40147 40202 40257 0.1 Volts
Oil Pressure 40038 40093 40148 40203 40258 0.1 kPa
Oil Temp 40039 40094 40149 40204 40259 0.1 Deg K
Coolant Temp 40040 40095 40150 40205 40260 0.1 Deg K
Fuel Rate 40041 40096 40151 40206 40261 0.001 GPH
Engine RPM 40042 40097 40152 40207 40262 RPM
Engine Starts 40043 40098 40153 40208 40263 Starts
Engine Runtime High 40044 40099 40154 40209 40264
Engine Runtime Low 40045 40100 40155 40210 40265 0.1 Sec
Total kWH High 40046 40101 40156 40211 40266
Total kWH Low 40047 40102 40157 40212 40267 KWH
Total Fuel High 40048 40103 40158 40213 40268
Total Fuel Low 40049 40104 40159 40214 40269 0.01 GAL
Bus Frequency 40050 40105 40160 40215 40270 0.1 Hz
Bus Volts ab 40051 40106 40161 40216 40271 Volts
Bus Volts bc 40052 40107 40162 40217 40272 Volts
Bus Volts ca 40053 40108 40163 40218 40273 Volts
Bus Volts a 40054 40109 40164 40219 40274 Volts
Bus Volts b 40055 40110 40165 40220 40275 Volts
Bus Volts c 40056 40111 40166 40221 40276 Volts
Customer Faults 40057 40112 40167 40222 40277
Network Faults 40058 40113 40168 40223 40278
Customer Faults 40059 40114 40169 40224 40279
ES State (See Table 10 on page 40060 40115 40170 40225 40280
453)
Load Share State (See Table 11 on 40061 40116 40171 40226 40281
page 453)
Load Govern State kW (See Table 40062 40117 40172 40227 40282
15 on page 454)
Load Govern State kVAR (SeeTable 40063 40118 40173 40228 40283
13 on page 454)

11.3 Word Data


Reference the ATS 6-1 and 6-10 tables in Section 8.

452 A029X159 (Issue 14)


10-2015 11. DMC 1500 Communication Server 2

TABLE 9.

Digital State
0 Stopped
1 Start Pending
2 Warm-up at Idle
3 Running
4 Cooldown at Rated
5 Cooldown at idle

TABLE 10.

Digital ES State
0 Standby
1 Dead Bus Close
2 Synchronizing
3 Load Share
4 Load Govern

TABLE 11.

Digital Load Share State


0 Not in Load Share
1 Track Load
2 Ramp Load
3 Ramp Unload
4 Load Demand Shutdown

TABLE 12.

Digital Load Govern State kW


0 NA
1 Ramp Load
2 Track Target Load
3 Ramp Unload
4 Ramp Unload Done

A029X159 (Issue 14) 453


11. DMC 1500 Communication Server 2 10-2015

TABLE 13.

Digital Load Govern State kVAR


0 NA
1 Ramp Load
2 Track Target Load
3 Ramp Unload
4 Ramp Unload Done

TABLE 14.

Digital Fault Type


0 Normal
1 Warning
2 Derate
3 Shutdown with Cooldown
4 Shutdown

TABLE 15.

Digital Control Switch


0 Off
1 Manual
2 Automatic

11.4 Generator Raw Data Gen 6-8


Generator Raw Data Gen 6 Gen 7 Gen 8 Multiplier Units
Device Type 40286 40341 40396
Control Switch (See Table 15 on page 454) 40287 40342 40397
State (See Table 9 on page 453) 40288 40343 40398
Fault Code 40289 40344 40399
Fault Type (See Table 14 on page 454) 40290 40345 40400
Percent kW Standby 40291 40346 40401 0.5 %
Total kW 40292 40347 40402
NFPA 110 (See Table 4 on page 380) 40293 40348 40403
NFPA Extended (See Table 5 on page 380) 40294 40349 40404
Frequency 40295 40350 40405 0.1 Hz
Total pf 40296 40351 40406 0.00005 PF
Total kVA 40297 40352 40407 kVA

454 A029X159 (Issue 14)


10-2015 11. DMC 1500 Communication Server 2

Generator Raw Data Gen 6 Gen 7 Gen 8 Multiplier Units


Total kW 40298 40353 40408 kW
Total kVAR 40299 40354 40409 kVAR
Volts ab 40300 40355 40410 Volts
Volts bc 40301 40356 40411 Volts
Volts ca 40302 40357 40412 Volts
Volts a 40303 40358 40413 Volts
Volts b 40304 40359 40414 Volts
Volts c 40305 40360 40415 Volts
Amps a 40306 40361 40416 Amps
Amps b 40307 40362 40417 Amps
Amps c 40308 40363 40418 Amps
Percent Amps a 40309 40364 40419 0.5 %
Percent Amps b 40310 40365 40420 0.5 %
Percent Amps c 40311 40366 40421 0.5 %
Battery Voltage 40312 40367 40422 0.1 Volts
Oil Pressure 40313 40368 40423 0.1 kPa
Oil Temp 40314 40369 40424 0.1 Deg K
Coolant Temp 40315 40370 40425 0.1 Deg K
Fuel Rate 40316 40371 40426 0.001 GPH
Engine RPM 40317 40372 40427 RPM
Engine Starts 40318 40373 40428 Starts
Engine Runtime High 40319 40374 40429
Engine Runtime Low 40320 40375 40430 0.1 Sec
Total kWH High 40321 40376 40431
Total kWH Low 40322 40377 40432 KWH
Total Fuel High 40323 40378 40433
Total Fuel Low 40324 40379 40434 0.01 GAL
Bus Frequency 40325 40380 40435 0.1 Hz
Bus Volts ab 40326 40381 40436 Volts
Bus Volts bc 40327 40382 40437 Volts
Bus Volts ca 40328 40383 40438 Volts
Bus Volts a 40329 40384 40439 Volts
Bus Volts b 40330 40385 40440 Volts
Bus Volts c 40331 40386 40441 Volts
Customer Faults 40332 40387 40442
Network Faults 40333 40388 40443
Customer Faults 40334 40389 40444
ES State (See Table 10 on page 453) 40335 40390 40445

A029X159 (Issue 14) 455


11. DMC 1500 Communication Server 2 10-2015

Generator Raw Data Gen 6 Gen 7 Gen 8 Multiplier Units


Load Share State (See Table 11 on page 40336 40391 40446
453)
Load Govern State kW (See Table 12 on 40337 40392 40447
page 453)
Load Govern State kVAR (See Table 13 on 40338 40393 40448
page 454)

456 A029X159 (Issue 14)


12 MCM3320 Modbus Register Map
12.1 Modbus Communications
This section defines the Modbus communications interface. Serial communications use an RTU
(Remote Terminal Unit) two-wire RS485 multi-drop network configuration described in the
Modbus Protocol Reference Guide. The Cummins control is a Slave unit.

12.2 Reference Documents


1. “Modbus Over Serial Line Specification and Implementation Guide V1.02" describes the
lower levels of Modbus protocol.
2. “Modbus Application Protocol Specification V1.1b3" describes the application layer of the
Modbus protocol.

12.3 Serial Port Configuration


The port communications occur, by default, at a baud rate of 19200 using eight data bits, one
stop-bit with even parity, and are configurable via MON and PCCNet logically.

12.4 Device Addresses


The PLC is the Master device in the Modbus network. The Modbus node address is
configurable and is set to node 1 by default.

12.5 Power-Up Time


The MCM3320 is capable of supporting communication transactions within 10 seconds following
initial power-up.

12.6 Response Time


The controller responds within 100 ms of a request for information from the Master.

12.7 Data Formatting


The format for each register is defined in the Modbus register table.
All data parameters are transmitted as registers. All registers are two 8 bit bytes in length (16
bits per register). If a register requires more than 16 bits, then, the subsequent registers are also
used. Therefore, with a 32 bit register X and X+1, the X register contains the upper 16 bits of
data and the X+1 register contains the lower 16 bits. A register with 1 bit of data uses the least
significant bit of a 16 bit register.

A029X159 (Issue 14) 457


12. MCM3320 Modbus Register Map 10-2015

For all discrete data referenced a by bit number, the least significant bit for the register is
numbered as 0 inch and the most significant bit as 15 inch. For all fault statuses and event
statuses, a 1 inch indicates the fault or event is active and a 0 inch indicates inactive.

12.8 Modbus Activity LED


The Modbus activity LED is on when either the control is receiving a Modbus packet or sending
a Modbus packet. It is also on when a protocol timer is in timer mode. This precedes a protocol
switch on the SCI1 port. Otherwise, the LED is off.

12.9 Supported Functions


The controller is only capable of processing the following Modbus data and control function
queries from the Master:
• Read holding registers (Function Code 03)
• Preset single register (Function Code 06)
• Diagnostics (Function Code 08)
• Preset multiple registers (Function Code 16)
The control responds to any query containing a function code, other than codes 03, 06, 08 and
16, by sending an exception response with the exception code set to 01 (Illegal Function).
The control responds to any read of a single address that is not defined in this specification by
sending an exception response with the exception code set to 02 (Illegal Address).
The control responds to any read of a block of 2 or more addresses containing an address that
is not defined in this specification by returning data of 0xFFFF for that address.
The control responds to Preset Single Register and Preset Multiple Register functions when the
data is out of bounds by sending an exception response with the exception code set to 03
(Illegal Data Value).

12.10 Holding Register Function


The control provides the ability to read all read only and read/write registers in the Modbus
Registers Table via the Holding Register function. From 1 to 40 contiguous registers can be
read at a time. If an attempt is made to read a register that's not available, then an error is
returned and none of the data will be returned.

12.11 Preset Single/Preset Multiple Registers Function


The control provides the ability to write to (preset) Read/Write registers in the Modbus registers
table via both the preset single register (Function Code 06) and the preset multiple registers
(Function Code 16). A write to a single register can be performed by the Master using the
Modbus data and control function query preset single register (Function Code 06). For writes
requiring writes to 1 to 40 contiguous registers, the Master uses the Modbus data and control
function query called preset multiple registers (Function Code 16). If a write attempt is made
and any of the data is invalid or if an attempt is made to write to a register that's not available,
then an error is returned and none of the data will be written.

458 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

12.12 Diagnostic Counters


The following diagnostic counters is also available via the Modbus diagnostic function (Function
Code 08). The following parameters are updated and available via MON and Modbus logical
access. A single logical is also available to clear all counters.
• Bus Message Count - Total Modbus packets on bus
• CRC Errors Count - Total Modbus packets received with a bad CRC
• Exception Count - Total Modbus packets received where an exception was sent back
• No Response Count - Total Modbus packets received where no response sent back
• Slave Message Count - Total Modbus packets on bus addressed to this node

12.13 Register Maps


Addresses were assigned to maintain compatibility with the existing Modlon gateway where
applicable. The following conventions are followed:
• 40xxx - Genset control registers
• 41xxx - Transfer switch control register
• 42xxx - Master control registers (MCM3320)
• 4x0xx - General data registers (volts, current, etc.) primarily for genset bus
• 4x1xx - General data registers (volts, current, etc.) primarily for utility bus
• 4x2xx - Configuration and status registers - Block 1
• 4x3xx - Settings - Block 1
• 4x4xx - Settings - Block 2
• 4x5xx - Bitmap
• 4x6xx - Switch I/O
• 4x7xx - Configuration and status registers - Block 2

12.14 Application Layer


The application layer processes the packet. Four functions are supported: Read Hold Registers,
Set Single Register, Modbus Loopback, and Set Multiple Registers. If the request packet
specifies an unsupported function, then an illegal function response is returned. See the
"Modbus Application Protocol Specification" to see how the request and response packets are
formatted and how each function processes the data.

12.15 Read Hold Registers


Given a starting address and the quantity of registers desired, this function gets the data,
formats it if required, and writes it to the TX buffer. If any register in the range is not supported,
then an error is returned.

A029X159 (Issue 14) 459


12. MCM3320 Modbus Register Map 10-2015

12.16 Set Single Register


Given a register address and data, this function verifies that the data is within range; then if OK,
writes the data.

12.17 Modbus Loopback


This function performs Modbus diagnostic functionality. Some of the functionality defined here is
also available via MON and PCCNet logicals. See the "Diagnostic Counters" section of this
document for details. The Loopback function supports:
• 0x00 Return Query Data
• 0x01 Restart
• 0x04 Force Listen Only Mode
• 0x0A Clear Counter
• 0x0B Return Bus Message Count
• 0x0C Return Bus Communication Error Count (bad CRC)
• 0x0D Return Bus Exception Error Count
• 0x0E Return Slave Message Count
• 0x0F Return Slave No Response Count

12.18 Set Multiple Registers


Given a starting address, the quantity of registers, and two bytes of data for each register, this
function verifies that all the data is within range; then if OK, writes all data. If any register in the
range is not supported or any of the data is out of range then an error is returned and no data is
written. A 32-bit parameter is written using "Write Multiple Register" (Command Code 16) only.
Using "Write Single Register" (Command Code 06) returns an exception code 2 - Illegal
Address. If both registers are not in the same block, the control sends an exception code 2-
Illegal Address.

12.19 Modbus Register Table


NOTICE
Earlier versions of software may not support all of the Modbus registers in the following
table. If a particular register is not available in your installation, it is possible that the
Modbus connection is working but the controller software does not support that
particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

460 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Logical
MB logical Read / Offset: 0 address to be
42001 Read Address Write Upper Limit: read via Communications
Size (bits):16 65535.000 Modbus
Sign: U Default: 0
Multiplier: Unit: NA
1.000000000000 Logical data to
MB Logical Read Lower Limit:
42002 Read Data Offset: 0 be read via Communications
Only Upper Limit:
Size (bits): 32 Modbus
Default:
Sign: U
Save
configuration
parameters or
adjustments to
non-volatile
memory.
0: Do Nothing Perform Save
Save Read / Controller
42004 Adjustments Write 1: Save Trims Trims after all Information
Default: Do Nothing configurations
have been
updated. Do
not save trims
unless a
change has
occurred.
Multiplier: Unit: NA
1.000000000000 Hard coded
Read Lower Limit:
42009 Device Type Offset: 0 device type id= Communications
Only Upper Limit:
Size (bits):16 52 (0x0034)
Default:
Sign: U
Multiplier: Unit: NA
.000100000000
Software Read Lower Limit: Software Controller
42010 Version Offset: 0
Only Upper Limit: version number Information
Size (bits):16
Default:
Sign: U
0: Time Delay Start
1: Time Delay Stop Indicates state
Genset Run Read of the PTC Operating
42011 Sequence Only 2: Stop generator set Mode
State 3: Run run sequence
Default:
Multiplier: Unit: NA The most
1.000000000000 recently
Current Fault Read Lower Limit: Fault and Event
42012 Status Offset: 0 occurring fault
Only Upper Limit: Information
Size (bits):16 which is still
Default: active
Sign: U
0: Unavailable Energization
1: Dead
42017 Genset Bus Read status of PTC Sensors
Status Only 2: Live generator Set
Default: bus

Multiplier: Unit: Volts


1.000000000000
Genset L1N Read Lower Limit: Volts Generator set
42018 Voltage Offset: 0 Voltage
Only Upper Limit: Volts L1N voltage
Size (bits): 16
Default
Sign: U

A029X159 (Issue 14) 461


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


Multiplier: Unit: Volts
1.000000000000
Genset L2N Read Lower Limit: Volts Generator set
42019 Voltage Offset: 0 Voltage
Only Upper Limit: Volts L2N voltage
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: Volts
1.000000000000
Genset L3N Read Lower Limit: Volts Generator set
42020 Voltage Offset: 0 Voltage
Only Upper Limit: Volts L3N voltage
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: Volts
Genset LN 1.000000000000 Generator set
Read Lower Limit: Volts
42021 Average Offset: 0 LN average Voltage
Only Upper Limit: Volts
Voltage Size (bits): 16 voltage
Default:
Sign: U
Multiplier:
1.000000000000 Unit: Volts
Genset L1L2 Read Offset: 0 Lower Limit: Volts Generator set
42022 Voltage Only Upper Limit: Volts L1L2 voltage Voltage
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: Volts
1.000000000000
Genset L2L3 Read Lower Limit: Volts Generator set
42023 Voltage Offset: 0 Voltage
Only Upper Limit: Volts L2L3 voltage
Size (bits): 16
Default
Sign: U
Multiplier: Unit: Volts
1.000000000000
Genset L3L1 Read Lower Limit: Volts Generator set
42024 Voltage Offset: 0 Voltage
Only Upper Limit: Volts L3L1 voltage.
Size (bits): 16
Default
Sign: U
Multiplier: Unit: Volts
Genset LL 1.000000000000 Generator set
Read Lower Limit: Volts
42025 Average Offset: 0 LL Average Voltage
Only Upper Limit: Volts
Voltage Size (bits): 16 voltage
Default
Sign: U
Multiplier: Unit: Amps
1.000000000000
Genset L1 Read Lower Limit: Amps Generator set
42026 Current Offset: 0 Current
Only Upper Limit: Amps L1 current
Size (bits): 16
Default
Sign: U
Multiplier: Unit: Amps
1.000000000000
Genset L2 Read Lower Limit: Amps Generator set
42027 Current Offset: 0 Current
Only Upper Limit: Amps L2 current
Size (bits): 16
Default
Sign: U
Multiplier: Unit: Amps
1.000000000000
Genset L3 Read Lower Limit: Amps Generator set
42028 Current Offset: 0 Current
Only Upper Limit: Amps L3 current
Size (bits): 16
Default:
Sign: U

462 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier: Unit: Amps
Genset 1.000000000000 Generator set
Read Lower Limit: Amps
42029 Average Offset: 0 average Current
Only Upper Limit: Amps
Current Size (bits): 16 current
Default:
Sign: U
Multiplier: Unit: kW
1.000000000000
Read Lower Limit: kW Generator set
42030 Genset L1 kW Offset: 0 Power
Only Upper Limit: kW L1 kW
Size (bits): 16
Default:
Sign: S
Multiplier: Unit: kW
1.000000000000
Read Lower Limit: kW Generator set
42031 Genset L2 kW Offset: 0 Power
Only Upper Limit: kW L2 kW
Size (bits): 16
Default:
Sign: S
Multiplier: Unit: kW
1.000000000000
Read Lower Limit: kW Generator set
42032 Genset L3 kW Offset: 0 Power
Only Upper Limit: kW L3 kW
Size (bits): 16
Default:
Sign: S
Multiplier: Unit: kW
1.000000000000
Genset Total Read Lower Limit: kW Generator set
42033 kW Offset: 0 Power
Only Upper Limit: kW total kW
Size (bits): 16
Default:
Sign: S
Multiplier: Unit: kVAR
1.000000000000
Genset L1 Read Lower Limit: kVAR Generator set
42034 kVAR Offset: 0 Power
Only Upper Limit: kVAR L1 kVAR
Size (bits): 16
Default:
Sign: S
Multiplier: Unit: kVAR
1.000000000000
Genset L2 Read Lower Limit: kVAR Generator set
42035 kVAR Offset: 0 Power
Only Upper Limit: kVAR L2 kVAR
Size (bits): 16
Default:
Sign: S
Multiplier: Unit: kVAR
1.000000000000
Genset L3 Read Lower Limit: kVAR Generator set
42036 kVAR Offset: 0 Power
Only Upper Limit: kVAR L3 kVAR
Size (bits): 16
Default:
Sign: S
Multiplier: Unit: kVAR
1.000000000000
Genset Total Read Lower Limit: kVAR Generator set
42037 kVAR Offset: 0 Power
Only Upper Limit: kVAR total kVAR
Size (bits): 16
Default:
Sign: S
Multiplier: Unit: NA
1.000000000000
Genset Total Read Lower Limit: Generator set
42038 Power Factor Offset: 0
Only Upper Limit: L1 power factor Power
Size (bits): 16
Default:
Sign: S

A029X159 (Issue 14) 463


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


Multiplier: Unit: kVA
1.000000000000
Read Lower Limit: kVA Generator set
42039 Genset L1 kVA Only Offset: 0 Power
Upper Limit: kVA L1 kVA
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: kVA
1.000000000000
Read Lower Limit: kVA Generator set
42040 Genset L2 kVA Only Offset: 0 Power
Upper Limit: kVA L2 kVA
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: kVA
1.000000000000
Read Lower Limit: kVA Generator set
42041 Genset L3 kVA Only Offset: 0 Power
Upper Limit: kVA L3 kVA
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: kVA
1.000000000000
Genset Total Read Lower Limit: kVA Generator set
42042 kVA Offset: 0 Power
Only Upper Limit: kVA total kVA
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: Hz Generator set
.100000000000 line frequency
MB Genset Read Lower Limit: Hz
42043 Frequency Offset: 0 scaled by 10 = Communications
Only Upper Limit: Hz
Size (bits): 16 1Hz for
Default: Modbus
Sign: U
Multiplier: Unit: kWh
1.000000000000 Generator set
Genset Total Read Lower Limit: kWh total negative
42044 Negative kWh Offset: 0 Energy
Only Upper Limit: kWh kWh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier: Unit: kWh
1.000000000000 Generator set
Genset Total Read Lower Limit: kWh total positive
42046 Positive kWh Offset: 0 Energy
Only Upper Limit: kWh kWh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier: Unit: kWh
1.000000000000 Generator set
Genset Total Read Lower Limit: kWh
42048 Net kWh Offset: 0 total net kWh Energy
Only Upper Limit: kWh
Size (bits): 32 accumulation
Default:
Sign: S
Multiplier: Unit: kVARh
1.000000000000 Generator set
Genset Total Read Lower Limit: kVARh total negative
42050 Negative Offset: 0 Energy
Only Upper Limit: kVARh kVARh
kVARh Size (bits): 32 accumulation
Default:
Sign: U
Multiplier: Unit: kVARh
1.00000000000 Generator set
Genset Total Read Lower Limit: kVARh total positive
40052 Positive kVARh Only 0Offset: 0 Energy
Upper Limit: kVARh kVARh
Size (bits): 32 accumulation
Default:
Sign: U

464 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier: Unit: kVARh
1.000000000000 Generator set
Genset Total Read Lower Limit: kVARh total net
42054 Net kVARh Offset: 0 Energy
Only Upper Limit: kVARh kVARh
Size (bits): 32 accumulation
Default:
Sign: S
Multiplier: Unit: kVARh
1.000000000000 Generator set
Genset Total Read Lower Limit: kVARh
42056 kVAh Offset: 0 total kVAh Energy
Only Upper Limit: kVARh
Size (bits): 32 accumulation
Default:
Sign: U
Calculated
Multiplier: Unit: Amps amps which
Genset 1.000000000000 represent 100-
Read Lower Limit: Amps
42058 Available Offset: 0 % generator Current
Only Upper Limit: Amps
Current Size (bits): 16 set bus current
Default: - used by
Sign: U
bargraph
Generator set
Multiplier: Unit: % L1 current as
Genset L1 .100000000000 percent of
Read Lower Limit: %
42059 Current Offset: 0 generator Set Current
Only Upper Limit: %
Percent Size (bits): 16 total current
Default: capacity - used
Sign: S
by bargraph
Generator set
Multiplier: Unit: % L2 current as
Genset L2 .100000000000 percent of
Read Lower Limit: %
42060 Current Offset: 0 generator Set Current
Only Upper Limit: %
Percent Size (bits): 16 total current
Default: capacity - used
Sign: U
by bargraph
Generator set
Multiplier: Unit: % L3 current as
Genset L3 .100000000000 percent of
Read Lower Limit: %
42061 Current Offset: 0 generator Set Current
Only Upper Limit: %
Percent Size (bits): 16 total current
Default: capacity - used
Sign: U
by bargraph
Multiplier: Generator set
.100000000000 Unit: % kW as percent
Lower Limit: %
42062 Genset Total Read Offset: 0 of total Power
kW Percent Only Upper Limit: % generator set
Size (bits): 16 capacity - used
Sign: S Default:
by bargraph
Generator set
Multiplier: Unit: % frequency as
Genset .100000000000 percent of
Read Lower Limit: %
42063 Frequency Offset: 0 system Frequency
Only Upper Limit: %
Percent Size (bits): 16 frequency -
Default: used by
Sign: U
bargraph
Multiplier: Unit: %
.100000000000
Genset L1L2 Read Lower Limit: % Generator set
42064 Voltage% Offset: 0
Only Upper Limit: % L1L2 voltage% Voltage
Size (bits): 16
Default:
Sign: U

A029X159 (Issue 14) 465


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


Multiplier: Unit: %
.100000000000
Genset L2L3 Read Lower Limit: % Generator set
42065 Voltage% Offset: 0
Only Upper Limit: % L2L3 voltage % Voltage
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: %
.100000000000
Genset L3L1 Read Lower Limit: % Generator set
42066 Voltage% Offset: 0
Only Upper Limit: % L3L1 voltage% Voltage
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: kW
1.000000000000 Generator set
Genset Total Read Lower Limit: kW
42070 kW_32bit Offset: 0 total kW in 32 Power
Only Upper Limit: kW
Size (bits): 32 bit
Default:
Sign: S
Multiplier: Unit: kVAR
1.000000000000 Generator set
Genset Total Read Lower Limit: kVAR
42072 kVAR_32bit Offset: 0 total kVAR in Power
Only Upper Limit: kVAR
Size (bits): 32 32 bit
Default:
Sign: S
Multiplier: Unit: kVA
1.000000000000 Generator set
Genset Total Read Lower Limit: kVA
42074 kVA_32bit Offset: 0 total kVA in 32 Power
Only Upper Limit: kVA
Size (bits): 32 bit
Default:
Sign: U
0: Unavailable
1: Dead Energization
42117 Utility Bus Read status of the PTC Sensors
Status Only 2: Live utility bus
Default:
Multiplier: Unit: Volts
1.000000000000
Utility L1N Read Lower Limit: Volts Utility L1N
42118 Voltage Offset: 0 Voltage
Only Upper Limit: Volts voltage
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: Volts
1.000000000000
Utility L2N Read Lower Limit: Volts Utility L2N
42119 Voltage Offset: 0 Voltage
Only Upper Limit: Volts voltage
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: Volts
1.000000000000
Utility L3N Read Lower Limit: Volts Utility L3N
42120 Voltage Offset: 0 Voltage
Only Upper Limit: Volts voltage
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: Volts
Utility LN 1.000000000000 Utility LN
Read Lower Limit: Volts
42121 Average Offset: 0 average Voltage
Only Upper Limit: Volts
Voltage Size (bits): 16 voltage
Default:
Sign: U

466 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier: Unit: Volts
1.000000000000
Utility L1L2 Read Lower Limit: Volts Utility L1L2
42122 Voltage Offset: 0 Voltage
Only Upper Limit: Volts voltage
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: Volts
1.000000000000
Utility L2L3 Read Lower Limit: Volts Utility L2L3
42123 Voltage Offset: 0 Voltage
Only Upper Limit: Volts voltage
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: Volts
1.000000000000
Utility L3L1 Read Lower Limit: Volts Utility L3L1
42124 Voltage Offset: 0 Voltage
Only Upper Limit: Volts voltage
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: Volts
Utility LL 1.000000000000 Utility LL
Read Lower Limit: Volts
42125 Average Offset: 0 average Voltage
Only Upper Limit: Volts
Voltage Size (bits): 16 voltage
Default:
Sign: U
Multiplier: Unit: Amps
1.000000000000
Utility L1 Read Lower Limit: Amps Utility L1
42126 Current Offset: 0 Current
Only Upper Limit: Amps current
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: Amps
1.000000000000
Utility L2 Read Lower Limit: Amps Utility L2
42127 Current Offset: 0 Current
Only Upper Limit: Amps current
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: Amps
1.000000000000
Utility L3 Read Lower Limit: Amps Utility L3
42128 Current Offset: 0 Current
Only Upper Limit: Amps current
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: Amps
1.000000000000
Utility Average Read Lower Limit: Amps Utility average
42129 Current Offset: 0 Current
Only Upper Limit: Amps current
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: kW
1.000000000000
Read Lower Limit: kW
42130 Utility L1 kW Offset: 0 Utility L1 kW Power
Only Upper Limit: kW
Size (bits): 16
Default:
Sign: S
Multiplier: Unit: kW
1.000000000000
Read Lower Limit: kW
42131 Utility L2 kW Offset: 0 Utility L2 kW Power
Only Upper Limit: kW
Size (bits): 16
Default:
Sign: S

A029X159 (Issue 14) 467


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


Multiplier: Unit: kW
1.000000000000
Read Lower Limit: kW
42132 Utility L3 kW Offset: 0 Utility L3 kW Power
Only Upper Limit: kW
Size (bits): 16
Default:
Sign: S
Multiplier: Unit: kW
1.000000000000
Read Lower Limit: kW
42133 Utility Total kW Only Offset: 0 Utility total kW Power
Upper Limit: kW
Size (bits): 16
Default:
Sign: S
Multiplier: Unit: kVAR
1.000000000000
Read Lower Limit: kVAR
42134 Utility L1 kVAR Only Offset: 0 Utility L1 kVAR Power
Upper Limit: kVAR
Size (bits): 16
Default:
Sign: S
Multiplier: Unit: kVAR
1.000000000000
Read Lower Limit: kVAR
42135 Utility L2 kVAR Only Offset: 0 Utility L2 kVAR Power
Upper Limit: kVAR
Size (bits): 16
Default:
Sign: S
Multiplier: Unit: kVAR
1.000000000000
Read Lower Limit: kVAR
42136 Utility L3 kVAR Only Offset: 0 Utility L3 kVAR Power
Upper Limit: kVAR
Size (bits): 16
Default:
Sign: S
Multiplier: Unit: kVAR
1.000000000000
Utility Total Read Lower Limit: kVAR Utility total
42137 kVAR Offset: 0 Power
Only Upper Limit: kVAR kVAR
Size (bits): 16
Default:
Sign: S
Multiplier: Unit: NA
1.000000000000
Utility Total Read Lower Limit: Utility L1 power
42138 Power Factor Offset: 0 Power
Only Upper Limit: factor
Size (bits): 16
Default:
Sign: S
Multiplier: Unit: kVA
1.000000000000
Read Lower Limit: kVA
42139 Utility L1 kVA Offset: 0 Utility L1 kVA Power
Only Upper Limit: kVA
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: kVA
1.000000000000
Read Lower Limit: kVA
42140 Utility L2 kVA Offset: 0 Utility L2 kVA Power
Only Upper Limit: kVA
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: kVA
1.000000000000
Read Lower Limit: kVA
42141 Utility L3 kVA Offset: 0 Utility L3 kVA Power
Only Upper Limit: kVA
Size (bits): 16
Default:
Sign: U

468 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier: Unit: kVA
1.000000000000
Utility Total Read Lower Limit: kVA
42142 kVA Offset: 0 Utility total kVA Power
Only Upper Limit: kVA
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: Hz Utility line
1.000000000000 frequency
MB Utility Read Lower Limit: Hz
42143 Frequency Offset: 0 scaled by 10 = Communications
Only Upper Limit: Hz
Size (bits): 16 1Hz for
Default: Modbus
Sign: U
Multiplier: Unit: kWh
1.000000000000 Utility total
Utility Total Read Lower Limit: kWh
42144 Negative kWh Offset: 0 negative kWh Energy
Only Upper Limit: kWh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier: Unit: kWh
1.000000000000 Utility total
Utility Total Read Lower Limit: kWh
42146 Positive kWh Offset: 0 positive kWh Energy
Only Upper Limit: kWh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier: Unit: kWh
1.000000000000 Utility total net
Utility Total Net Read Lower Limit: kWh
42148 kWh Offset: 0 kWh Energy
Only Upper Limit: kWh
Size (bits): 32 accumulation
Default:
Sign: S
Multiplier: Unit: kVARh
1.000000000000 Utility total
Utility Total Read Lower Limit: kVARh negative
42150 Negative Offset: 0 Energy
Only Upper Limit: kVARh kVARh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier: Unit: kVARh
1.000000000000 Utility total
Utility Total Read Lower Limit: kVARh
42152 Positive kVARh Only Offset: 0 positive kVARh Energy
Upper Limit: kVARh accumulation
Size (bits): 32
Default:
Sign: U
Multiplier: Unit: kVARh
1.000000000000 Utility total net
Utility Total Net Read Lower Limit: kVARh
42154 kVARh Offset: 0 kVARh Energy
Only Upper Limit: kVARh
Size (bits): 32 accumulation
Default:
Sign: S
Multiplier: Unit: kVAh
1.000000000000 Utility total
Utility Total Read Lower Limit: kVAh
42156 kVAh Offset: 0 kVARh Energy
Only Upper Limit: kVAh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier: Unit: kW
1.000000000000 Sum of
System Total Read Lower Limit: kW generator set
42158 kW Offset: 0 Power
Only Upper Limit: kW bus and utility
Size (bits): 16 bus kW
Default:
Sign: S

A029X159 (Issue 14) 469


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


Multiplier: Unit: kVAR
1.000000000000 Sum of
System Total Read Lower Limit: kVAR generator set
42159 kVAR Offset: 0 Power
Only Upper Limit: kVAR bus and utility
Size (bits): 16 bus kVAR
Default:
Sign: S
Multiplier: System total
.010000000000 Unit: NA power factor
Lower Limit:
42160 System Total Read Offset: 0 (totalized value Power
Power Factor Only Upper Limit: of utility bus
Size (bits): 16 plus generator
Sign: S Default:
set bus)
Multiplier: Unit: kVA
1.000000000000 Sum of
System Total Read Lower Limit: kVA generator set
42161 kVA Offset: 0 Power
Only Upper Limit: kVA bus and utility
Size (bits): 16 bus kVA
Default:
Sign: U
Multiplier: Utility L1
.100000000000 Unit: % current as % of
Utility L1 Lower Limit: %
42162 Current Read Offset: 0 utility total Current
Percent Only Upper Limit: % current
Size (bits): 16 capacity - used
Sign: U Default:
by bargraph
Multiplier: Utility L2
.100000000000 Unit: % current as % of
Utility L2 Lower Limit: %
42163 Current Read Offset: 0 utility total Current
Percent Only Upper Limit: % current
Size (bits): 16 capacity - used
Sign: U Default:
by bargraph
Multiplier: Utility L3
.100000000000 Unit: % current as
Utility L3 Lower Limit: %
42164 Current Read Offset: 0 as % of utility Current
Percent Only Upper Limit: % total current
Size (bits): 16 capacity - used
Sign: U Default:
by bargraph
Multiplier: Unit: % Utility total kW
.100000000000 as percent of
Utility Total kW Read Lower Limit %
42165 Percent Offset: 0 total utility Power
Only Upper Limit: %
Size (bits): 16 capacity - used
Default: by bargraph
Sign: S
Utility
Multiplier: Unit: % frequency as
Utility .100000000000 percent of
Read Lower Limit: %
42166 Frequency Offset: 0 system Frequency
Only Upper Limit: %
Percent Size (bits): 16 frequency -
Default: used by
Sign: U
bargraph
Multiplier: Unit: %
.100000000000
Utility L1L2 Read Lower Limit: % Utility L1L2
42167 Voltage % Offset: 0 Voltage
Only Upper Limit: % voltage %
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: %
.100000000000
Utility L2L3 Read Lower Limit: % Utility L2L3
42168 Voltage % Offset: 0 Voltage
Only Upper Limit: % voltage %
Size (bits): 16
Default:
Sign: U

470 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier: Unit:%
.100000000000
Utility L3L1 Read Lower Limit: % Utility L3L1
42169 Voltage % Offset: 0 Voltage
Only Upper Limit: % voltage %
Size (bits): 16
Default:
Sign: U
Multiplier: Unit: kW
1.000000000000
Utility Total kW Read Lower Limit: kW
42170 _32 bit Offset: 0 Utility total kW Power
Only Upper Limit: kW
Size (bits): 32
Default:
Sign: S
Multiplier: Unit: kVAR
1.000000000000
Utility total Read Lower Limit: kVAR Utility total
42172 kVAR_32 bit Offset: 0 Power
Only Upper Limit: kVAR kVAR in 32 bit
Size (bits): 32
Default:
Sign: S
Multiplier: Unit: kVA
1.000000000000
Utility total Read Lower Limit: kVA Utility total kVA
42174 kVA_32 bit Offset: 0 Power
Only Upper Limit: kVA in 32 bit
Size (bits): 32
Default:
Sign: U
Multiplier: Unit: kW
1.000000000000 Sum of
System Total Read Lower Limit: kW generator bus
42176 kW_32 bit Offset: 0 Power
Only Upper Limit: kW and utility bus
Size (bits): 32 kW in 32 bit
Default:
Sign: S
Multiplier: Unit: kVAR
1.000000000000 Sum of
System Total Read Lower Limit: kVAR generator bus
42178 kVAR_32 bit Offset: 0 Power
Only Upper Limit: kVAR and utility bus
Size (bits): 32 kVAR in 32 bit
Default:
Sign: S
Multiplier: Unit: kVA
1.000000000000 Sum of
System Total Read Lower Limit: kVA generator set
42180 kVA_32 bit Offset: 0 Power
Only Upper Limit: kVA and utility bus
Size (bits): 32 kVA in 32 bit
Default:
Sign: U
Multiplier: Unit: NA
1.000000000000 Number of
Total Number Read Lower Limit: generator sets System
42200 of Gensets Offset: 0
Only Upper Limit: with non–zero Information
Size (bits): 16 rating entered
Default:
Sign: U
Multiplier: Unit: kW
1.000000000000 Sum of the
Total System Read Lower Limit: kW System
42201 Capacity Offset: 0 generator set
Only Upper Limit: kW Information
Size (bits): 16 kW ratings
Default:
Sign: U
Multiplier: Sum of the
1.000000000000 Unit: kW generator set
Lower Limit: kW
42202 Total Online Read Offset: 0 kW ratings for System
Capacity Only Upper Limit: kW generator sets Information
Size (bits): 16 which are
Sign: S Default:
Online

A029X159 (Issue 14) 471


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


Multiplier: Unit: seconds
.100000000000 Countdown
Programmed Read Lower Limit: seconds value of the
42203 Transition Offset: 0 PTC Timers
Only Upper Limit: seconds programmed
Timer Size (bits): 16 transition timer
Default:
Sign: U
Multiplier: Unit: seconds
.100000000000 Countdown
Read Lower Limit: seconds
42204 Transfer Timer Offset: 0 value of the PTC Timers
Only Upper Limit: seconds
Size (bits): 16 transfer timer
Default:
Sign: U
Multiplier: Unit: seconds
.100000000000 Countdown
Retransfer Read Lower Limit: seconds
42205 Timer Offset: 0 value of the PTC Timers
Only Upper Limit: seconds
Size (bits): 16 retransfer timer
Default:
Sign: U
Multiplier: Unit: seconds
.100000000000 Countdown
Maximum Read Lower Limit: seconds value of the
42206 Parallel Timer Offset: 0 PTC Timers
Only Upper Limit: seconds maximum
Size (bits): 16 parallel timer
Default:
Sign: U
Multiplier: Unit: kW
1.000000000000 kW Control
Read Lower Limit: kW reference value Master Load
42207 kW Reference Offset: 0
Only Upper Limit: kW for utility Control
Size (bits): 16 paralleling
Default:
Sign: S
0: Not Available
Utility 1: Not Unloaded Indicates utility
42208 Unloaded Read unloaded Master Load
Status Only 2: Unloaded status Control
Default:
0: Not Available Indicates
Genset 1: Not Unloaded
42209 Unloaded Read generator set Master Load
Status Only 2: Unloaded unloaded Control
Default: status

472 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Not Available
1: TD Start
2: TD Stop
3: TD Programmed Transition
4: TD Transfer
5: TD Retransfer
6: Synchronizing
7: Sync Check OK
8: Inhibit Indicates what
Read state the System
42210 System State Only 9: Unassigned control is Information
10: Ramp Upload currently IN
11. Ramp Load
12: Manual
13: Utility Failure
14: Test
15: Standby
16: Factory Test
17: Extended Parallel
Default: Not Available
0: Manual
1: Normal Indicates the
2: Normal Override Current PTC
PTC Operating Read Operating PTC Operating
42211 Mode Only 3: Test mode. Read/ Mode
4: Utility Fail Write on comp
5: Extended Parallel mode.
Default:
Multiplier: Unit: seconds
Active .100000000000 Countdown
Read Lower Limit: seconds
42212 Transition Offset: 0 timer value of PTC Timers
Only Upper Limit: seconds
Timer Size (bits): 16 active timer
Default:
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates the
Hardware Read Lower Limit: hardware
42213 Version Offset: 0 Discrete Inputs
Only Upper Limit: version of the
Size (bits): 16 board
Default:
Sign: U
Multiplier: Unit: seconds
1.000000000000 Lower Limit: .000 sec. Amount of time
Controller On Read Offset: 0 in seconds the Controller
42214 Time Only Upper Limit: controller has Information
Size (bits): 32 4294967295.000 sec been powered
Sign: U Default: 0
Indicates
0: Not Available availability of
Genset Read 1: Available generator set
42216 Availability Only for Loading, as PTC Availability
Status 2: Unknown determined by
Default: the generator
set sensors

A029X159 (Issue 14) 473


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


Indicates
0: Not Available availability of
Utility Read 1: Available utility for
42217 Availability Only loading as PTC Availability
Status 2: Unknown determined by
Default: the utility
sensors
0: Open
1: Closed Generator set
42218 Gen CB Read breaker Breaker Control
Position Status Only 2: Not Available position
Default:
0: Open
1: Closed
42219 Util CB Read Utility breaker Breaker Control
Position Status Only 2: Not Available position
Default:
Multiplier: Unit: kVAR
1.000000000000 kVAR control
kVAR Load Read Lower Limit: kVAR reference value Master Load
42220 Reference Offset: 0
Only Upper Limit: kVAR for extended Control
Size (bits): 16 paralleling
Default:
Sign: S
Multiplier: Unit: % Engineering
kVAR Load .010000000000
Setpoint Engr Read Lower Limit: % units value for
42221 Units Display Offset: 0 the kVAR load Analog Inputs
Only Upper Limit: %
Value Size (bits): 16 setpoint analog
Default: Input
Sign: U
Multiplier: Unit: % Engineering
kW Load .010000000000
Setpoint Engr Read Lower Limit: % units value for
42222 Units Display Offset: 0 the kW load Analog Inputs
Only Upper Limit: %
Value Size (bits): 16 setpoint analog
Default: input
Sign: S
Multiplier: Power factor
.010000000000 Unit: NA setpoint analog
Lower Limit:
42223 Power Factor Read Offset: 0 input value Analog Inputs
Setpoint Only Upper Limit: (uses kVAR
Size (bits): 16 load setpoint
Sign: S Default:
analog input)
0: Not Enabled
Indicates the
1: No Source Connected connected
Read 2: Utility Connected state of power PTC State
42224 PTC State
Only 3: Genset Connected transfer Machine
4: Paralleled control. read /
write in comp.
Default:
Indicates
0: Not Allowed whether any
Sync Check Read Master Sync
42225 Close Allowed Only 1: Allowed sync check Control
Default: conditions
have been met
Multiplier: Unit: degrees
.010000000000 Utility to
Sync Phase Read Lower Limit: degrees generator set
42226 Difference Offset: 0 Phase
Only Upper Limit: degrees L1 voltage
Size (bits): 16 phase angle
Default:
Sign: S

474 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Synchronizer Off Indicates state
Synchronizer Read Master Sync
42227 Status Only 1: Synchronizer On of the Control
Default: synchronizer

Faults have
0: Inactive occurred which
42228 System Read 1: Active prevent normal System
Lockout Status Only system Information
Default: operation;
reset faults
0: Open
1: Closed Indicates the
42229 Breaker 1 Read position status Load Add Shed
Position Only 2: Not Available of breaker 1 Control
Default: Not Available
0: Open
1: Closed Indicates the
42230 Breaker 2 Read position status Load Add Shed
Position Only 2: Not Available of breaker 2 Control
Default: Not Available
0: Open
1: Closed Indicates the
42231 Breaker 3 Read position status Load Add Shed
Position Only 2: Not Available of breaker 3 Control
Default: Not Available
0: Open
1: Closed Indicates the
42232 Breaker 4 Read position status Load Add Shed
Position Only 2: Not Available of breaker 4 Control
Default: Not Available
0: Open
1: Closed Indicates the
42233 Breaker 5 Read position status Load Add Shed
Position Only 2: Not Available of breaker 5 Control
Default: Not Available
0: Open
1: Closed Indicates the
42234 Breaker 6 Read position status Load Add Shed
Position Only 2: Not Available of breaker 6 Control
Default: Not Available
0: Not Available
1: Normal Indicates trip
42235 Breaker 1 Trip Read status of Load Add Shed
Status Only 2: Tripped breaker 1 Control
Default: Not Available
0: Not Available
1: Normal Indicates trip
42236 Breaker 2 Trip Read status of Load Add Shed
Status Only 2: Tripped breaker 2 Control
Default: Not Available
0: Not Available
1: Normal Indicates trip
42237 Breaker 3 Trip Read status of Load Add Shed
Status Only 2: Tripped breaker 3 Control
Default: Not Available
0: Not Available
1: Normal Indicates trip
42238 Breaker 4 Trip Read status of Load Add Shed
Status Only 2: Tripped breaker 4 Control
Default: Not Available

A029X159 (Issue 14) 475


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


0: Not Available
1: Normal Indicates trip
42239 Breaker 5 Trip Read status of Load Add Shed
Status Only 2: Tripped breaker 5 Control
Default: Not Available
0: Not Available
1: Normal Indicates trip
42240 Breaker 6 Trip Read status of Load Add Shed
Status Only 2: Tripped breaker 6 Control
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
42241 ATS 1 Position Read position status Load Add Shed
Only 3: Source 2 Connected of ATS 1 Control
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
42242 ATS 2 Position Read position status Load Add Shed
Only 3: Source 2 Connected of ATS 2 Control
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
42243 ATS 3 Position Read position status Load Add Shed
Only 3: Source 2 Connected of ATS 3 Control
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
42244 ATS 4 Position Read position status Load Add Shed
Only 3: Source 2 Connected of ATS 4 Control
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
42245 ATS 5 Position Read position status Load Add Shed
Only 3: Source 2 Connected of ATS 5 Control
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
42246 Position Read position status Load Add Shed
Only 3: Source 2 Connected of ATS 6 Control
4: Paralleled
Default: Not Available
0: Missing
1: Good Indicates
Read 2: Connecting status of SID1 Communications
42247 SID1 Status
Only 3: No EXP Board (AUX 101 / 102
4: Not Applicable module 1)
Default:

476 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Missing
1: Good Indicates
Read 2: Connecting status of SID0 Communications
42248 SID0 Status
Only 3: No EXP Board (AUX 101 / 102
4: Not Applicable module 0)
Default:

Expansion Indicates the


0: Disable status of SIDO
Board Read
42249 Communication Only 1: Enable to expansion Communications
s Default: Disable board
connection
Multiplier: Unit: NA
1.000000000000 Indicates the
Current Add Read Lower Limit: Load Add Shed
42250 Level Offset: 0 next level to
Only Upper Limit: Control
Size (bits): 16 add
Default:
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates the
Current Shed Read Lower Limit: Load Add Shed
42251 Level Offset: 0 next level to
Only Upper Limit: Control
Size (bits): 16 shed
Default:
Sign: U
0: Do Nothing Indicates
Add Level 1 Read Load Add Shed
42252 Command Only 1: Add Level status of add Control
Default: Do Nothing level 1

0: Do Nothing Indicates
Add Level 2 Read Load Add Shed
42253 Command Only 1: Add Level status of add Control
Default: Do Nothing level 2

0: Do Nothing Indicates
Add Level 3 Read Load Add Shed
42254 Command Only 1: Add Level status of add Control
Default: Do Nothing level 3

0: Do Nothing Indicates
Add Level 4 Read Load Add Shed
42255 Command Only 1: Add Level status of add Control
Default: Do Nothing level 4

0: Do Nothing Indicates
Add Level 5 Read Load Add Shed
42256 Command Only 1: Add Level status of add Control
Default: Do Nothing level 5

0: Do Nothing Indicates
Add Level 6 Read Load Add Shed
42257 Command Only 1: Add Level status of add Control
Default: Do Nothing level 6

0: Do Nothing Indicates
Shed Level 1 Read Load Add Shed
42258 Command Only 1: Add Level status of shed Control
Default: Do Nothing level 1

0: Do Nothing Indicates
Shed Level 2 Read Load Add Shed
42259 Command Only 1: Add Level status of shed Control
Default: Do Nothing level 2

0: Do Nothing Indicates
Shed Level 3 Read Load Add Shed
42260 Command Only 1: Add Level status of shed Control
Default: Do Nothing level 3

A029X159 (Issue 14) 477


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


0: Do Nothing Indicates
Shed Level 4 Read Load Add Shed
42261 Command Only 1: Add Level status of shed Control
Default: Do Nothing level 4

0: Do Nothing Indicates
Shed Level 5 Read Load Add Shed
42262 Command Only 1: Add Level status of shed Control
Default: Do Nothing level 5

Manual Add 0: Do Nothing


Read Operator input Load Add Shed
42263 Level 1 Only 1: Add Level to add level 1 Control
Command Default: Do Nothing

Manual Add 0: Do Nothing


Read Operator input Load Add Shed
42264 Level 2 Only 1: Add Level to add level 2 Control
Command Default: Do Nothing

Manual Add 0: Do Nothing


Read Operator input Load Add Shed
42265 Level 3 Only 1: Add Level to add level 3 Control
Command Default: Do Nothing

Manual Add 0: Do Nothing


Read Operator input Load Add Shed
42266 Level 4 Only 1: Add Level to add level 4 Control
Command Default: Do Nothing

Manual Add 0: Do Nothing


Read Operator input Load Add Shed
42267 Level 5 Only 1: Add Level to add level 5 Control
Command Default: Do Nothing

Manual Add 0: Do Nothing


Read Operator input Load Add Shed
42268 Level 6 Only 1: Add Level to add level 6 Control
Command Default: Do Nothing

Manual Shed 0: Do Nothing Operator input


42269 Level 1 Read 1: Add Level to shed loads Load Add Shed
Command Only assigned to Control
Default: Do Nothing level 1

Manual Shed 0: Do Nothing Operator input


42270 Level 2 Read 1: Add Level to shed loads Load Add Shed
Command Only assigned to Control
Default: Do Nothing level 2

Manual Shed 0: Do Nothing Operator input


42271 Level 3 Read 1: Add Level to shed loads Load Add Shed
Command Only assigned to Control
Default: Do Nothing level 3

Manual Shed 0: Do Nothing Operator input


42272 Level 4 Read 1: Add Level to shed loads Load Add Shed
Command Only assigned to Control
Default: Do Nothing level 4

Manual Shed 0: Do Nothing Operator Input


42273 Level 5 Read 1: Add Level to Shed Loads Load Add Shed
Command Only Assigned to Control
Default: Do Nothing Level 5

Restored Shed 0: Do Nothing Indicates if


42274 Level 1 Read 1: Add Level shed level 1 Load Add Shed
Command Only has been Control
Default: Do Nothing restored

478 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function

Restored Shed 0: Do Nothing Indicates if


42275 Level 2 Read 1: Add Level shed level 2 Load Add Shed
Command Only has been Control
Default: Do Nothing restored

Restored Shed 0: Do Nothing Indicates if


42276 Level 3 Read 1: Add Level shed level 3 Load Add Shed
Command Only has been Control
Default: Do Nothing restored

Restored Shed 0: Do Nothing Indicates if


42277 Level 4 Read 1: Add Level shed level 4 Load Add Shed
Command Only has been Control
Default: Do Nothing restored

Restored Shed 0: Do Nothing Indicates if


42278 Level 5 Read 1: Add Level shed level 5 Load Add Shed
Command Only has been Control
Default: Do Nothing restored
0: Do Nothing Indicates add
Add Load 1 Read Load Add Shed
42279 Command Only 1: Add Level command for Control
Default: Do Nothing load 1

0: Do Nothing Indicates add


Add Load 2 Read Load Add Shed
42280 Command Only 1: Add Level command for Control
Default: Do Nothing load 2

0: Do Nothing Indicates add


Add Load 3 Read Load Add Shed
42281 Command Only 1: Add Level command for Control
Default: Do Nothing load 3

0: Do Nothing Indicates add


Add Load 4 Read Load Add Shed
42282 Command Only 1: Add Level command for Control
Default: Do Nothing load 4.

0: Do Nothing Indicates add


Add Load 5 Read Load Add Shed
42283 Command Only 1: Add Level command for Control
Default: Do Nothing load 5

0: Do Nothing Indicates add


Add Load 6 Read Load Add Shed
42284 Command Only 1: Add Level command for Control
Default: Do Nothing load 6

0: Do Nothing Indicates shed


Shed Load 1 Read Load Add Shed
42285 Command Only 1: Add Level command for Control
Default: Do Nothing load 1

0: Do Nothing Indicates shed


Shed Load 2 Read Load Add Shed
42286 Command Only 1: Add Level command for Control
Default: Do Nothing load 2

0: Do Nothing Indicates shed


Shed Load 3 Read Load Add Shed
42287 Command Only 1: Add Level command for Control
Default: Do Nothing load 3

0: Do Nothing Indicates Shed Load Add Shed


Shed Load 4 Read
42288 Command Only 1: Add Level Command for Control
Default: Do Nothing Load 4

0: Do Nothing Indicates shed


Shed Load 5 Read Load Add Shed
42289 Command Only 1: Add Level command for Control
Default: Do Nothing load 5

A029X159 (Issue 14) 479


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


0: Do Nothing Indicates shed
Shed Load 6 Read Load Add Shed
42290 Command Only 1: Add Level command for Control
Default: Do Nothing load 6

Multiplier: Unit: VDC Engineering


Battery Voltage Read .010000000000 units value for
Lower Limit: VDC
42291 Engr Units Offset: 0 the battery Analog Inputs
Only Upper Limit: VDC
Display Value Size (bits): 16 voltage analog
Default Input
Sign: U
Multiplier: Unit: VDC Voltage level
kVAR Master .010000000000
Load Control Read Lower Limit: VDC commanded to
42292 Output Offset: 0 kVAR Master Analog Inputs
Only Upper Limit: VDC
Predictor Value Size (bits): 16 load control
Default analog output
Sign: S
Multiplier: Unit: VDC Voltage level
kW Master .010000000000
Load Control Read Lower Limit: VDC commanded to
42293 Output Offset: 0 kW Master Analog Inputs
Only Upper Limit: VDC
Predictor Value Size (bits): 16 load control
Default analog output
Sign: S
Multiplier: Unit: VDC Voltage level
Master .010000000000
Frequency Read Lower Limit: VDC commanded to
42294 Bias Output Offset: 0 Master Analog Inputs
Only Upper Limit: VDC
Predictor Value Size (bits): 16 frequency bias
Default analog output
Sign: S
Multiplier: Unit: VDC Voltage level
Master Voltage Read .010000000000 commanded to
Lower Limit: VDC
42295 Bias Output Offset: 0 Master voltage Analog Inputs
Only Upper Limit: VDC
Predictor Value Size (bits): 16 bias analog
Default output
Sign: S
0: Manual
1: Normal
Indicates the
PTC Genset 2: Normal Override current
Read PTC Genset
42296 Operating Only 3: Test operating Operating Mode
Mode 4: Utility Fail mode of the
generator set
5: Extended Parallel
Default
0: Manual
1: Normal
Indicates the
PTC Transfer 2: Normal Override current
Read PTC Genset
42297 Pair Operating Only 3: Test operating Operating Mode
Mode 4: Utility Fail mode of the
transfer pair
5: Extended Parallel
Default:
Indicates the
0: Open Transition transition type
PTC Operating Read 1: Hard Closed Transition currently PTC Genset
42298 Transition Type Only applicable to Operating Mode
2: Soft Closed Transition the PTC
Default: function
operation

480 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Indicates the
Expansion 0: Disabled status of the
42299 Board Read 1: Enabled SID1 to Communications
Communication Only expansion
s1 Default: Disabled board
connection
0: Master Synchronize Only
1: Isolated Bus w/ out GM Main setting:
2: Isolated Bus w/GM sets system
System Read/ topology; Application
42300 Topology Write 3: Common Bus control must be Configuration
4: Transfer Pair in manual to
5: Component Mode set
Default: Master Synchronize Only
0: Open Transition Sets the type
1: Hard Closed Transition
42301 Transition Type Read/ of transition Application
Write 2: Soft Closed Transition that will be Configuration
Default: Open Transition used

0: Disabled Use to enable


42302 Extended Read/ 1: Enabled extended Application
Parallel Enable Write paralleling Configuration
Default: Disabled operation
0: None
1: Fixed Sequence
42303 Load Demand Read/ Sets the load Load Demand
Type Write 2: Run Hours demand type Control
Default: None
0: Manual
Priority Control Read/ Set the priority
42304 Method Write 1: Automatic control method Priority Control
Default: Manual
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 01 kW Read/ Offset: 0 Sets generator System
42305 Rating Write Upper Limit: 1 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 1000
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 02 kW Read/ Offset: 0 Sets generator System
42306 Rating Write Upper Limit: 2 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 03 kW Read/ Offset: 0 Sets generator System
42307 Rating Write Upper Limit: 3 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 04 kW Read/ Offset: 0 Sets generator
42308 Rating Write Upper Limit: 4 kW rating PC 3.x
Size (bits): 16 32000.000 kW
Sign: S Default: 0

A029X159 (Issue 14) 481


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 05 kW Read/ Offset: 0 Sets generator System
42309 Rating Write Upper Limit: 5 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 06 kW Read/ Offset: 0 Sets generator System
42310 Rating Write Upper Limit: 6 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 07 kW Read/ Offset: 0 Sets generator System
42311 Rating Write Upper Limit: 7 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 08 kW Read/ Offset: 0 Sets generator System
42312 Rating Write Upper Limit: 8 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 09 kW Read/ Sets generator System
42313 Rating Write Offset: 0 Upper Limit: 9 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 10 kW Read/ Offset: 0 Sets generator System
42314 Rating Write Upper Limit: 10 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 11 kW Read/ Sets generator System
42315 Rating Write Offset: 0 Upper Limit: 11 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 12 kW Read/ Offset: 0 Sets generator System
42316 Rating Write Upper Limit: 12 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0

Multiplier: Unit: Seconds


.100000000000 Lower Limit: .000 Set the
Programmed Seconds
42317 Transition Read/ Offset: 0 programmed PTC Timers
Delay (TDPT) Write Upper Limit: 60.000 transition time
Size (bits): 16 delay
Seconds
Sign: U
Default: 3

482 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function

Multiplier: Unit: Seconds


.100000000000 Lower Limit: .000
Seconds Sets the
42318 Transfer Delay Read/ Offset: 0 transfer time PTC Timers
(TDNE) Write Upper Limit: 120.000 delay
Size (bits): 16
Seconds
Sign: U
Default: 10

Multiplier: Unit: Seconds


.100000000000 Lower Limit: .000
Seconds Sets the
42319 Retransfer Read/ Offset: 0 transfer time PTC Timers
Delay (TDEN) Write Upper Limit: 1800.000 delay
Size (bits): 16
Seconds
Sign: U
Default: 600

Multiplier: Unit: Seconds


Lower Limit: .000 Sets the
Maximum .100000000000 maximum
Read/ Offset: 0 Seconds
42320 Parallel Time parallel time for PTC Timers
(TDMP) Write Upper Limit: 1800.000 soft load
Size (bits): 16
Seconds transfers
Sign: U
Default: 20
Multiplier: Unit: %
.010000000000 Generator set
Genset Bus Read/ Lower Limit: -5.000% Master Load
42321 %kW Setpoint Offset: 0 nominal
Write Upper Limit: 105.000% voltage Control
Size (bits): 16
Default: 80
Sign: S

Multiplier: Unit: Volts


1.000000000000 Lower Limit: 100.000
Genset Volts Generator set
42322 Nominal Read/ Offset: 0 nominal AC Setup
Voltage Write Upper Limit: voltage
Size (bits): 16
45000.000 Volts
Sign: U
Default: 480

Multiplier: Unit: Volts


1.000000000000 Lower Limit: 100.000
Volts
42323 Utility Nominal Read/ Offset: 0 Utility nominal AC Setup
Voltage Write Upper Limit: voltage
Size (bits): 16
45000.000 Volts
Sign: U
Default: 480
Multiplier: Unit: Hz Sets the center
.100000000000 frequency
Genset Center Read/ Lower Limit: 45.000 Hz
42324 Frequency Offset: 0 sensor PTC Sensors
Write Upper Limit: 65.000 Hz
Size (bits): 16 bandwidth
Default: 60 settings
Sign: U
Multiplier: Unit: Hz Sets the center
.100000000000 frequency
Utility Center Read/ Lower Limit: 45.000 Hz
42325 Frequency Offset: 0 sensor PTC Sensors
Write Upper Limit: 65.000 Hz
Size (bits): 16 bandwidth
Default: 60 settings
Sign: U

0: Disable Use to enable


42326 test With Load Read/ 1: Enable or disable load Application
Enable Write transfer during Configuration
Default: Disable a Test

A029X159 (Issue 14) 483


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


Multiplier: Unit: Hz
.100000000000 Use to define
System Read/ Lower Limit: 45.000 Hz the system System
42327 Frequency Offset: 0
Write Upper Limit: 65.000 Hz nominal Information
Size (bits): 16 frequency
Default: 60
Sign: U
Selects where
Genset Bus 0: Internal the generator
42328 kW Setpoint Read/ 1: Analog Input set kW setpoint Master Load
Source Write will come from Control
Default Internal for extended
paralleling
Selects where
the generator
Genset Bus 0: Internal set kVAR
Read/ Master Load
42329 kVAR Setpoint Write 1: Analog Input setpoint will Control
Source Default Internal come from for
extended
paralleling
Multiplier: Unit: kW Set the base
1.000000000000 Lower Limit: .000 kW load kW
42330 Genset Bus Read/ Offset: 0 Upper Limit:
setpoint in Master Load
kW Setpoint Write closed loop Control
Size (bits): 16 32767.000 kW extended
Sign: S Default: 0 paralleling

Multiplier: Unit: kVAR Sets the base


1.000000000000 Lower Limit: .000 load kVAR
kVAR
42331 Genset Bus Read/ Offset: 0 setpoint in Master Load
kVAR Setpoint Write Upper Limit: closed loop Control
Size (bits): 16 extended
32767.000 kVAR
Sign: S paralleling
Default: 0
Multiplier: Sets % kVAR
.010000000000 Unit: % generator
Lower Limit: -5.000%
42332 Genset Bus % Read/ Offset: 0 output level for Master Load
kVAR Setpoint Write Upper Limit: 105.000% open loop base Control
Size (bits): 16 load extended
Sign: S Default: 0
paralleling
Sets the
Multiplier: Unit: NA desired
Genset Bus .010000000000 generator set
Read/ Lower Limit: .700 Master Load
42333 Power Factor Offset: 0 bus power
Write Upper Limit: 1.000 Control
Setpoint Size (bits): 16 factor in closed
Default: 1.00 loop extended
Sign: S
paralleling

Multiplier: Unit: kW
1.000000000000 Lower Limit: -
Genset 32768.000kW Setpoint for
42334 Unloaded Read/ Offset: 0 generator set Master Load
Level Write Upper Limit: unloaded level Control
Size (bits): 16
32767.000 kW
Sign: S
Default: 50
Selects where
Utility Bus kW 0: Internal the utility kW
42335 Setpoint Read/ 1: Analog Input setpoint will Master Load
Source Write come from for Control
Default: Internal extended
paralleling

484 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Selects where
Utility Bus 0: Internal the utility kVAR
42336 kVAR Setpoint Read/ 1: Analog Input setpoint will Master Load
Source Write come from for Control
Default: Internal extended
paralleling

Multiplier: Unit: kW Sets the peak


1.000000000000 Lower Limit: - Shave kW
32768.000kW
42337 Utility Bus kW Read/ Offset: 0 setpoint in Master Load
Setpoint Write Upper Limit: closed loop Control
Size (bits): 16 extended
32767.000 kW
Sign: S paralleling
Default: 100

Multiplier: Unit: kW
Lower Limit: - Sets the utility
Utility Bus kW 1.000000000000 kW constraint
Read/ Offset: 0 32768.000kW Master Load
42338 Constraint level for base
Level Write Upper Limit: load extended Control
Size (bits): 16
32767.000 kW paralleling
Sign: S
Default: 100

Multiplier: Unit: kW Sets the peak


1.000000000000 Lower Limit: - shave kVAR
32768.000 kVAR
42339 Utility Bus Read/ Offset: 0 setpoint in Master Load
kVAR Setpoint Write Upper Limit: closed loop Control
Size (bits): 16 extended
32767.000 kVAR
Sign: S paralleling
Default: 100
Multiplier: Sets the
.010000000000 Unit: NA desired utility
Utility Bus Lower Limit: .700
42340 Power Factor Read/ Offset: 0 bus power Master Load
Setpoint Write Upper Limit: 1.000 factor in loop Control
Size (bits): 16 extended
Sign: S Default: 1.00
paralleling

Multiplier: Unit: kW
1.000000000000 Lower Limit: -
Utility 32768.000kW Setpoint for
42341 Unloaded Read/ Offset: 0 utility unloaded Master Load
Level Write Upper Limit: level Control
Size (bits): 16
32767.000 kW
Sign: S
Default: 50

0: Inactive Use to
42342 Clear Fault Read/ 1: Active completely Fault and Event
History Table Write clear the fault Info
Default: Inactive history table
Use to
completely
Clear 0: Inactive clear the
42343 Occurrence Read/ 1: Active counters in Fault and Event
Tables Write faults and Info
Default: Inactive events
occurrence
tables
Use to
Genset Reset 0: Do Nothing permanently
42344 All Energy Read/ 1: Clear Counters clear all Energy
Meters Write generator set
Default: Do Nothing energy meter
values

A029X159 (Issue 14) 485


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


Use to
0: Do Nothing permanently
Utility Reset All Read/
42345 Energy Meters Write 1: Clear Counters clear all utility Energy
Default: Do Nothing energy meter
values
0: Genset Bus % Level (Open Loop) Sets how and
1: Genset Bus kW (Closed Loop) where the kW
Extended will be
42346 Paralleling kW Read/ 2: Genset Bus kW w/ Utility Constraint controlled for Master Load
Load Control Write (Closed Loop) extended Control
Type 3: Utility Bus kW (Closed Loop) parallel
Default: Genset Bus % Level (Open Loop) operation
0: Genset Controllers
1: Genset Bus % Level (Open Loop) Sets how and
2: Genset Bus Power Factor (Open Loop) where the
Extended kVAR will be
3: Genset Bus kVAR (Closed Loop)
42347 Paralleling Read/ controlled for Master Load
kVAR Load Write 4: Genset Bus Power Factor (Closed Loop) extended Control
Control Type 5: Utility Bus kVAR (Closed Loop) parallel
6: Utility Bus Power Factor (Closed Loop) operation
Default: Genset Controllers

Multiplier: Unit: seconds


.10000000000 Lower Limit: 10.000 Set ramp load
Extended seconds
42348 Parallel Ramp Read/ Offset: 0 time for Master Load
Load Time Write Upper Limit: 900.000 extended Control
Size (bits): 16 paralleling
seconds
Sign: U
Default:60

0:Disabled Enable if want


42349 Fail To Sync Read/ 1:Enabled synchronizing Master Sync
Lockout Enable Write to stop if fail to Control
Default: Disable sync occurs
Fail To Sync Use to enable
Open 0:Disabled or disable an
Read/ PTC State
42350 Transition Write 1:Enabled open transition Machine
Retransfer Default: Disable retransfer upon
Enable fail to sync

Multiplier: Unit: seconds


.200000000000 Lower Limit: 10.000 Set the fill to
Fail To seconds
42351 Synchronize Read/ Offset: 0 synchronize Master Sync
Time Write Upper Limit: 900.000 diagnostic time Control
Size (bits): 16 delay
seconds
Sign: U
Default:120
In manual
0: Closed Requested mode can be
Gen CB Read/ 1: No Command used to semi-
42352 Manual Control Write manually Breaker Control
2: Open Commanded control the
Default: No Command generator set
breaker
In Manual
0: Closed Requested Mode can be
1: No Command
42353 Util CB Manual Read/ used to Semi- Breaker Control
Control Write 2: Open Commanded Manually
Default: No Command Control the
Utility Breaker

486 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier: Sets the
.001000000000 Unit: seconds Synchronizer
Lower Limit: -3.000 Hz
42354 Slip Frequency Read/ Offset: 0 Slip Frequency Master Sync
Write Upper Limit: 3.000 Hz (used when Control
Size (bits): 16 Sync Method is
Sign: S Default:0.1
Slip)

Multiplier: Unit: seconds


.100000000000 Lower Limit: .000 Sets the
seconds
42355 Start Time Read/ Offset: 0 generator set PTC Operating
Delay (TDES) Write Upper Limit: 3600.000 Start Time Mode
Size (bits): 16 Delay
seconds
Sign: U
Default: 0

Multiplier: Unit: seconds


.100000000000 Lower Limit: .000 Sets the
seconds
42356 Stop Time Read/ Offset: 0 generator set PTC Operating
Delay (TDEC) Write Upper Limit: 3600.000 Stop Time Mode
Size (bits): 16 Delay
seconds
Sign: U
Default: 0
0: Normal Use to Invert
Synchronizer Read/ Master Sync
42357 Polarity Write 1: Invert Synchronizer Control
Default: Normal Polarity

0: Phase Match Sets the


Synchronize Read/ Master Sync
42358 Method Write 1: Slip Frequency synchronizing Control
Default: Phase Match method

Allows protocol
0: PCCNet of the PCCNet
42359 Port Protocol Read/ 1: MON port to be Communications
Selection Write changed to
Default: PCCNet MON for
troubleshooting

System 0: Disabled Use to enable


42360 Scheduler Read/ 1: Enabled or disable the System
Enable Write system Scheduler
Default: Disabled scheduler

0: Disabled Use the enable


42361 Load Add Shed Read/ 1: Enabled or disable the Load Add Shed
Enable Write load add shed Control
Default: Disabled feature

Open Use to enable


Transition 0: Disabled or disable the
42362 Retransfer Read/ 1: Enabled shedding of Load Add Shed
Load Shed Write loads during Control
Default: Disabled open transition
Enable
retransfer
Indicates
Auto/Manual 0: Auto automatic or
Read/ Load Add Shed
42363 Load Add Write 1: Manual manual load Control
Restore Mode Default: Auto add restore
operation

Multiplier: Unit: second Indicates delay


1.000000000000 Lower Limit: .000 between add
Genset Bus second
42364 Load Add Read/ Offset: 0 levels when all Load Add Shed
Delay Write Upper Limit: 60.000 generator sets Control
Size (bits): 16 are online and
second
Sign: U no utility
Default: 1

A029X159 (Issue 14) 487


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function

Multiplier: Unit: second


1.000000000000 Lower Limit: .000 Indicates delay
Utility Bus second
42365 Load Add Read/ Offset: 0 between add Load Add Shed
Delay Write Upper Limit: 60.000 levels when on Control
Size (bits): 16 utility
second
Sign: U
Default: 1

Multiplier: Unit: seconds


1.000000000000 Lower Limit: 1.000 Indicates delay
seconds
42366 Load Shed Read/ Offset: 0 between shed Load Add Shed
Delay Write Upper Limit: 10.000 levels when on Control
Size (bits): 16 generator sets
seconds
Sign: U
Default: 1
Indicates type
0: None of load
1: Breaker
42367 Load 1 Device Read/ connected to Load Add Shed
Type Write 2: ATS load 1 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
1: Breaker
42368 Load 2 Device Read/ connected to Load Add Shed
Type Write 2: ATS load 2 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
1: Breaker
42369 Load 3 Device Read/ connected to Load Add Shed
Type Write 2: ATS load 3 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
1: Breaker
42370 Load 4 Device Read/ connected to Load Add Shed
Type Write 2: ATS load 4 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
1: Breaker
42371 Load 5 Device Read/ connected to Load Add Shed
Type Write 2: ATS load 5 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
1: Breaker
42372 Load 6 Device Read/ connected to Load Add Shed
Type Write 2: ATS load 6 add Control
Default: None shed control
and status I/O
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 1 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42373 Level Offset: 0
Write Upper Limit: 18.000 1 is assigned Control
Size (bits): 16 to
Default: 1
Sign: U

488 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier: Unit: NA
1.000000000000 Indicates which
Load 2 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42374 Level Offset: 0
Write Upper Limit: 18.000 2 is assigned Control
Size (bits): 16 to
Default: 2
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 3 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42375 Level Offset: 0
Write Upper Limit: 18.000 3 is assigned Control
Size (bits): 16 to
Default: 3
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 4 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42376 Level Offset: 0
Write Upper Limit: 18.000 4 is assigned Control
Size (bits): 16 to
Default: 4
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 5 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42377 Level Offset: 0
Write Upper Limit: 18.000 5 is assigned Control
Size (bits): 16 to
Default: 5
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 6 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42378 Level Offset: 0
Write Upper Limit: 18.000 6 is assigned Control
Size (bits): 16 to
Default: 6
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 1 Shed Read/ Lower Limit: 1.000 shed level load Load Add Shed
42379 Level Offset: 0
Write Upper Limit: 17.000 1 is assigned Control
Size (bits): 16 to
Default: 1
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 2 Shed Read/ Lower Limit: 1.000 shed level load Load Add Shed
42380 Level Offset: 0
Write Upper Limit: 17.000 2 is assigned Control
Size (bits): 16 to
Default: 2
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 3 Shed Read/ Lower Limit: 1.000 shed level load Load Add Shed
42381 Level Offset: 0
Write Upper Limit: 17.000 3 is assigned Control
Size (bits): 16 to
Default: 3
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 4 Shed Read/ Lower Limit: 1.000 shed level load Load Add Shed
42382 Level Offset: 0
Write Upper Limit: 17.000 4 is assigned Control
Size (bits): 16 to
Default: 4
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 5 Shed Read/ Lower Limit: 1.000 shed level load Load Add Shed
42383 Level Offset: 0
Write Upper Limit: 17.000 5 is assigned Control
Size (bits): 16 to
Default: 5
Sign: U

A029X159 (Issue 14) 489


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


Multiplier: Unit: NA
1.000000000000 Indicates which
Load 6 Shed Read/ Lower Limit: 1.000 shed level load Load Add Shed
42384 Level Offset: 0
Write Upper Limit: 17.000 6 is assigned Control
Size (bits): 16 to
Default: 6
Sign: U
Use to choose
0: Both kW and Frequency method for
Genset Bus 1: kW Only
42385 Overload Read/ determining System
Method Write 2: Frequency Only generator bus Information
Default: Both kW and Frequency overload
condition
Multiplier: Use to set
1.000000000000 Unit: % the % kW
Genset Bus Lower Limit: 80.000%
42386 kW Overload Read/ Offset: 0 threshold for System
Delay Write Upper Limit: 140.000% generator bus Information
Size (bits): 16 overload
Sign: U Default: 105
condition

Multiplier: Unit: second


1.000000000000 Lower Limit: .000 Sets the delay
Genset Bus second
42387 kW Overload Read/ Offset: 0 time for System
Delay Write Upper Limit: 120.000 overload based Information
Size (bits): 16 on kW
second
Sign: U
Default: 60
Multiplier: Use to set the
Genset Bus 1.000000000000 Unit: Hz underfrequency
Lower Limit: .1000 Hz
42388 Underfrequenc Read/ Offset: 0 offset threshold System
y Overload Write Upper Limit: 10.000 Hz for generator Information
Threshold Size (bits): 16 bus overload
Sign: U Default: 3
condition

Multiplier: Unit: second


Genset Bus 1.000000000000 Lower Limit:.000 Sets the delay
second
42389 Underfrequenc Read/ Offset: 0 time for System
y Overload Write Upper Limit: 20.000 overload based Information
Delay Size (bits): 16 on frequency
second
Sign: U
Default: 3

0: Disable Use enable or


42390 Load Demand Read/ 1: Enable disable the Load Demand
Enable Write load demand Control
Default: Disable feature

490 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8 Sets GenA
Load Demand Read/ (never stop) for Load Demand
42391 GenA Write 8: Gen9 fixed sequence Control
9: Gen10 load demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen1
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8 Sets GenB
Load Demand Read/ (never stop) for Load Demand
42392 GenB Write 8: Gen9 fixed sequence Control
9: Gen10 load demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen2

A029X159 (Issue 14) 491


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8 Sets GenC
Load Demand Read/W (never stop) for Load Demand
42393 GenC rite 8: Gen9 fixed sequence Control
9: Gen10 load demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen3
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8 Sets GenD
Load Demand Read/W (never stop) for Load Demand
42394 GenD rite 8: Gen9 fixed sequence Control
9: Gen10 load demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen4

Multiplier: Unit: minute


Lower Limit: 1.000 Sets the Initial
1.000000000000 delay time
minute
42395 Load Demand Read/W Offset: 0 before load Load Demand
Initial Delay rite Upper Limit: 60.000 demand will Control
Size (bits): 16
minute operate
Sign: U
Default: 5
Multiplier: Unit: % Sets load
Load Demand 1.000000000000 demand restart Load Demand
Read/W Offset: 0 Lower Limit: 20.000%
42396 Restart rite threshold when Control
Percent Upper Limit: 100.000% method is
Size (bits): 16
Default: 80 %kW
Sign: U

Multiplier: Unit: Hours Sets run hours


1.000000000000 Lower Limit: 1.000 differential for
Load Demand Hours
42397 Run Hours Read/W Offset: 0 restart a Load Demand
Differential rite Upper Limit: 500.000 generator set Control
Size (bits): 16 stopped due to
Hours
Sign: U load demand
Default: 50

492 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function

Multiplier: Unit: minute Sets the delay


1.000000000000 Lower Limit: 1.000 time between
Load Demand minute
42398 Shutdown Read/W Offset: 0 stopping Load Demand
Delay rite Upper Limit: 60.000 generator sets Control
Size (bits): 16 due to load
minute
Sign: U demand
Default: 5
Multiplier: Unit: % Sets load
Load Demand 1.000000000000 Lower Limit: 20.000 % demand
42399 Shutdown Read/W Offset: 0 shutdown Load Demand
rite Upper Limit: 100.000 threshold when Control
Percent Size (bits): 16 % method is
Sign: U Default: 60 %kW
Unit: seconds Sets how long
Multiplier: to wait for a
1.000000000000 Lower Limit: 10.000
General Fail Read/W Offset: 0 seconds generator set Load Demand
42400 Time Delay rite to come online Control
Upper Limit: 900.000 before
Size (bits): 16 second
Sign: U declaring it
Default: 59 failed

Multiplier: Unit: seconds


.020000000000 Lower Limit: .100 Sets the utility
seconds
42401 Util CB Fail to Read/W Offset: 0 breaker fail to Breaker Control
Close Delay rite Upper Limit: 1.000 close time
Size (bits): 16 delay
seconds
Sign: U
Default: 0.26

Multiplier: Unit: seconds


.200000000000 Lower Limit: .200 Sets the utility
seconds
42402 Util CB Fail to Read/W Offset: 0 breaker fail to Breaker Control
Open Delay rite Upper Limit: 5.000 open time
Size (bits): 16 delay
seconds
Sign: U
Default: 1

Multiplier: Unit: seconds


.020000000000 Lower Limit: .000 Sets time to
Util CB seconds
42403 Recharge Read/W Offset: 0 allow for utility Breaker Control
Delay rite Upper Limit: 60.000 breaker
Size (bits): 16 recharge
seconds
Sign: U
Default: 10

Multiplier: Unit: seconds


Lower Limit: .100 Sets the
.020000000000 generator Set
seconds
42404 Gen CB Fail to Read/W Offset: 0 breaker fail to Breaker Control
Close Delay rite Upper Limit: 1.000 close time
Size (bits): 16
seconds delay
Sign: S
Default: 0.26

Multiplier: Unit: seconds


.200000000000 Lower Limit: .200 Sets generator
seconds
42405 Gen CB Fail to Read/W Offset: 0 set breaker fail Breaker Control
Open Delay rite Upper Limit: 5.000 to open time
Size (bits): 16 delay
seconds
Sign: U
Default: 1

Multiplier: Unit: seconds


Lower Limit: .000 Sets the time
Gen CB .020000000000 to allow for
Read/W Offset: 0 seconds
42406 Recharge generator set Breaker Control
Delay rite Upper Limit: 60.000 breaker
Size (bits): 16
second recharge
Sign: U
Default: 10

A029X159 (Issue 14) 493


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function

Multiplier: Unit: degrees Sets the


.010000000000 Lower Limit: .100 permissive +/-
degrees
42407 Permissive Read/W Offset: 0 phase angle Master Sync
Phase Window rite Upper Limit: 20.000 window for Control
Size (bits): 16 sync check
degrees
Sign: S function
Default: 10
Sets the
Multiplier: Unit: % permissive +/-
Permissive .100000000000 voltage
Read/W Offset: 0 Lower Limit: .500 % Master Sync
42408 Voltage rite acceptance Control
Window Upper Limit: 10.000 % window for
Size (bits): 16
Default: 5 sync check
Sign: U
function

Multiplier: Unit: seconds Sets the


.020000000000 Lower Limit: .500 permissive
seconds
42409 Permissive Read/W Offset: 0 acceptance Master Sync
Window Time rite Upper Limit: 5.000 window dwell Control
Size (bits): 16 time for sync
seconds
Sign: U check function
Default: 0.5
Multiplier: Sets maximum
.001000000000 Unit: Hz frequency
Permissive Lower Limit: .001 Hz
42410 Frequency Read/W Offset: 0 difference Master Sync
Window rite Upper Limit: 1.000 Hz allowed for Control
Size (bits): 32 permissive
Sign: U Default: 1
close

Multiplier: Unit: degrees Sets a sync


.010000000000 Lower Limit: -50.000 phase offset to
degrees
42412 Sync Phase Read/W Offset: 0 accommodate Master Sync
Offset rite Upper Limit: 50.000 sync across Control
Size (bits): 16 transformer
degrees
Sign: S with phase shift
Default: 0

0: L1-L2-L3 Defines what


42413 System Phase Read/W 1: L1-L3-L2 the system System
Rotation rite phase rotation Information
Default: L1-L2-L3 sequence is
Multiplier: Proportional
1.00000000000 Unit: NA gain for kW
Read/W Offset: 0 Lower Limit: .000 closed loop Master Load
42414 kW Kp
rite Upper Limit: 1000.000 control in Control
Size (bits): 16 extended
Sign: U Default: 60
paralleling
Multiplier: Unit: NA Integral gain
1.00000000000 for kW closed
Read/W Offset: 0 Lower Limit: .000 Master Load
42415 kW KI rite loop control in Control
Upper Limit: 255.000 extended
Size (bits): 16
Default: 60 paralleling
Sign: U
Multiplier: Proportional
.100000000000 Unit: NA gain for kVAR
Read/W Offset: 0 Lower Limit: .000 closed loop Master Load
42416 kVAR Kp
rite Upper Limit: 1000.000 control in Control
Size (bits): 16 extended
Sign: U Default: 120
paralleling

494 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier: Integral gain
1.00000000000 Unit: NA for kVAR
Read/W Offset: 0 Lower Limit: .000 closed loop Master Load
42417 kVAR K1
rite Upper Limit: 255.000 control in Control
Size (bits): 16 extended
Sign: U Default: 50
paralleling
Multiplier: Unit: NA
1.00000000000 Selects which
Scheduler Read/W Offset: 0 Lower Limit: 1.000 scheduler System
42418 Program Select rite program to Scheduler
Upper Limit: 12.000
Size (bits): 16 view or edit
Default: 1
Sign: U

Scheduler 0: Disable Use to enable


42419 Program Read/W 1: Enable or disable the System
Enable rite selected Scheduler
Default: Disable program
0: Once
1: Every Week
2: Every 2 Weeks
3: Every 3 Weeks
Scheduler 4: Every 4 Weeks use to adjust
42420 Program x Read/W 5: Every 5 Weeks repeat interval System
Repeats rite 6: First Week of the Month for the selected Scheduler
Interval 7: Second Week of the Month program
8: Third Week of the Month
9: Forth Week of the Month
10: Last Week of the Month
Default: Once
0: No Load Use to adjust
Scheduler 1: With Load
42421 Program x Run Read/W run mode for System
Mode rite 2: Extended Parallel the selected Scheduler
Default: No Load program

0: Sunday
1: Monday
2: Tuesday Use to adjust
Scheduler start day of
42422 Program x Read/W 3: Wednesday week for the System
Start Day rite 4: Thursday selected Scheduler
5: Friday program
6: Saturday
Default: Sunday
Multiplier: Unit: hour
1.00000000000 Lower Limit: .000 hour Use to adjust
Scheduler Read/W Offset: 0 start hour for System
42423 Program x rite Upper Limit: 23.000 the selected Scheduler
Start Hour Size (bits): 16 hour program
Sign: U Default: 0

Multiplier: Unit: minute


1.00000000000 Lower Limit: .000 Use to adjust
Scheduler minute
42424 Program x Read/W Offset: 0 start minute for System
Start Minute rite Upper Limit: 59.000 the selected Scheduler
Size (bits): 16 program
minute
Sign: U
Default: 0

A029X159 (Issue 14) 495


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


Multiplier: Unit: hour
1.00000000000 Lower Limit: .000 hour Use to adjust
Scheduler Read/W Offset: 0 duration hours System
42425 Program x rite Upper Limit: 23.000 for the selected Scheduler
Duration Hours Size (bits): 16 hour program
Sign: U Default: 0

Multiplier: Unit: minute


Scheduler 1.000000000000 Lower Limit: .000 Use to adjust
minute
42426 Program x Read/W Offset: 0 duration minute System
Duration rite Upper Limit: 59.000 for the selected Scheduler
Minutes Size (bits): 16 program
minute
Sign: U
Default: 0
Multiplier: Unit: NA
1.000000000000 Selects which
Scheduler Read/W Offset: 0 Lower Limit: 1.000 scheduler System
42427 Exception rite exception to Scheduler
Select Upper Limit: 6.000
Size (bits): 16 view or edit
Default: 1
Sign: U

Scheduler 0: Disable Use to enable


42428 Exception x Read/W 1: Enable or disable the System
Enable rite selected Scheduler
Default: Disable exception
Use to adjust
Scheduler 0: Once Only the repeat
Read/W System
42429 Exception x rite 1: Every Year setting of the Scheduler
Repeat Default: Only Once selected
exception

Multiplier: Unit: month


1.000000000000 Lower Limit: 1.000 Use to adjust
Scheduler month
42430 Exception x Read/W Offset: 0 the month of System
Month rite Upper Limit: 12.000 the selected Scheduler
Size (bits): 16 exception
month
Sign: U
Default: 1

Multiplier: Unit: date


1.000000000000 Lower Limit: 1.000 Use to adjust
Scheduler date
42431 Exception x Read/W Offset: 0 the start date System
Date rite Upper Limit: 31.000 of the selected Scheduler
Size (bits): 16 exception
date
Sign: U
Default: 1
Multiplier: Unit: hour
1.000000000000 Lower Limit: .000 hour Use to adjust
Scheduler Read/W Offset: 0 the start hour System
42432 Exception x rite Upper Limit: 23.000 of the selected Scheduler
Hour Size (bits): 16 hour exception
Sign: U Default: 0

Multiplier: Unit: minute


Scheduler 1.000000000000 Lower Limit: .000 Use to adjust
minute
42433 Exception x Read/W Offset: 0 the start minute System
Duration rite Upper Limit: 59.000 of the selected Scheduler
Minute Size (bits): 16 exception
minute
Sign: U
Default: 0
Multiplier: Unit: days Use to adjust
Scheduler 1.000000000000 Lower Limit: .000 days the duration
Read/W Offset: 0 System
42434 Exception x rite Upper Limit: 44.000 days of the Scheduler
Duration Days Size (bits): 16 days selected
Sign: U Default: 0 exception

496 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier: Unit: hour Use to adjust
Scheduler 1.000000000000 Lower Limit: .000 hour the duration
Read/W Offset: 0 System
42435 Exception x rite Upper Limit: 23.000 hours of the Scheduler
Duration Hours Size (bits): 16 hour selected
Sign: U Default: 0 exception

Multiplier: Unit: minute


Lower Limit: .000: Use to adjust
Scheduler 1.000000000000 the duration
minute
42436 Exception x Read/W Offset: 0 minutes of the System
Duration rite Upper Limit: 59.000: selected Scheduler
Minutes Size (bits): 16
minute exception
Sign: U
Default: 0

Daylight 0: Disable Enables the


42437 Saving Time Read/W 1: Enable daylight Real Time Clock
Enable rite savings time
Default: Disable feature

Load Demand Use to force a


0: Do Nothing refresh of the
Refresh Read/W Load Demand
42438 Sequence rite 1: Refresh Sequence active load Control
Command Default: Do Nothing demand
sequence

Genset 0: Wye Delta or wye


Read/W
42439 Connection rite 1: Delta for generator AC Setup
Type Default: Wye set connection

Multiplier: Unit: Volts


1.000000000000 Lower Limit: 100.000
Genset PT Volts Generator set
42440 Primary Read/W Offset: 0 PT primary AC Setup
Voltage rite Upper Limit: voltage
Size(bits): 16
45000.000 Volts
Sign: U
Default: 480

Multiplier: Unit: Volts


1.000000000000 Lower Limit: 100.000
Genset PT Volts Generator set
42441 Secondary Read/W Offset: 0 PT secondary AC Setup
Voltage rite Upper Limit: 500.000 voltage
Size(bits): 16
Volts
Sign: U
Default: 120

Multiplier: Unit: Amps


1.000000000000 Lower Limit: 5.000
Genset CT Amps Generator set
42442 Primary Read/W Offset: 0 CT primary AC Setup
Current rite Upper Limit: current
Size(bits): 16
25000.000 Volts
Sign: U
Default: 100

Genset CT 0: 1 Amp Generator set


Read/W
42443 Secondary rite 1: 5 Amp CT secondary AC Setup
Current Default: 5 Amp current

Utility 0: Wye Delta or wye


Read/W
42444 Connection rite 1: Delta for utility AC Setup
Type Default: Wye connection

Multiplier: Unit: Volts


1.000000000000 Lower Limit: 100.000
Utility PT Volts
42445 Primary Read/W Offset: 0 Utility PT AC Setup
Voltage rite Upper Limit: primary voltage
Size(bits): 16
45000.000 Volts
Sign: U
Default: 480

A029X159 (Issue 14) 497


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function

Multiplier: Unit: Volts


1.000000000000 Lower Limit: 100.000
Utility PT Volts Utility PT
42446 Secondary Read/W Offset: 0 secondary AC Setup
Voltage rite Upper Limit: 500.000 voltage
Size(bits): 16
Volts
Sign: U
Default: 120

Multiplier: Unit: Amps


1.000000000000 Lower Limit: 5.000
Utility CT Amps
42447 Primary Read/W Offset: 0 Utility CT AC Setup
Current rite Upper Limit: primary current
Size(bits): 16
25000.000 Amps
Sign: U
Default: 100

Utility CT 0: 1 Amp Utility CT


Read/W
42448 Secondary rite 1: 5 Amp secondary AC Setup
Current Default: 5 Amp current

Generator set
Multiplier: Unit: kW kW capacity
Load Add Shed 1.000000000000 Lower Limit: .000 kW
Required Read/W Offset: 0 that must be Load Add Shed
42449 Online rite Upper Limit: online to start Control
Capacity Size(bits): 16 32767.000 kW timed load
Sign: S Default: 0 add : 0
disables this
Sets how much
Multiplier: Unit: kW capacity must
Load Demand 1.000000000000 Lower Limit: .000 kW
Minimum Read/W Offset: 0 always be Load Demand
42450 Online rite Upper Limit: online Control
Capacity Size(bits): 16 32767.000 kW regardless of
Sign: S Default: 0 what the load
is

Multiplier: Unit: second Sets generator


.100000000000 Lower Limit: .000 restart delay
second
42451 Load Demand Read/W Offset: 0 time to avoid Load Demand
Restart Delay rite Upper Limit: 25.000 nuisance Control
Size(bits): 16 restarts due to
second
Sign: U load transients
Default: 1

Multiplier: Unit: Amps


Lower Limit: 1.000 Use to set how
1.000000000000 many amps =
Amps
42452 Utility Available Read/W Offset: 0 100% utility kW AC Setup
Current rite Upper Limit: - used by
Size(bits): 16
32000.000 Amps bargraph
Sign: U
Default: 1000
Multiplier: Unit: kW Use to set hoe
1.000000000000 Lower Limit: 1.000 kW many kW =
Total Utility Read/W Offset: 0
42453 Capacity rite Upper Limit: 100% utility kW AC Setup
Size(bits): 16 32000.000 kW - used by
Sign: S Default: 1000 bargraph

0: 12V DC voltage
Nominal Read/W Battery Voltage
42454 Battery Voltage rite 1: 24V provided to the Protection
Default: 24V control

498 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function

Multiplier: Unit: VDC


.0100000000000 Lower Limit: 28.000
24V High VDC Sets 24V high
42455 Battery Voltage Read/W Offset: 0 battery voltage Battery Voltage
Threshold rite Upper Limit: 34.000 fault threshold Protection
Size(bits): 16
VDC
Sign: U
Default: 32

Multiplier: Unit: VDC


.0100000000000 Lower Limit: 22.000
24V Low VDC Sets 24V low
42456 Battery Voltage Read/W Offset: 0 battery voltage Battery Voltage
Threshold rite Upper Limit: 26.000 fault threshold Protection
Size(bits): 16
VDC
Sign: U
Default: 24

Multiplier: Unit: VDC


.0100000000 Lower Limit: 14.000
12V High VDC Sets 12V high
42457 Battery Voltage Read/W Offset: 0 battery voltage Battery Voltage
Threshold rite Upper Limit: 17.000 fault threshold Protection
Size(bits): 16
VDC
Sign: U
Default: 16

Multiplier: Unit: VDC


.010000000000 Lower Limit: 11.000
12 V Low VDC Sets 12V low
42458 Battery Voltage Read/W Offset: 0 battery voltage Battery Voltage
Threshold rite Upper Limit: 13.000 fault threshold Protection
Size(bits): 16
VDC
Sign: U
Default: 12

Multiplier: Unit: second


1.000000000000 Lower Limit: 2.000
High Battery second Sets high
42459 Voltage Set Read/W Offset: 0 battery voltage Battery Voltage
Time rite Upper Limit: 60.000 set time Protection
Size(bits): 16
second
Sign: U
Default: 60

Multiplier: Unit: second


1.000000000000 Lower Limit: 2.000
Low Battery second Sets low
42460 Voltage Set Read/W Offset: 0 battery voltage Battery Voltage
Time rite Upper Limit: 60.000 set time Protection
Size(bits): 16
second
Sign: U
Default: 60
Used to enable
Genset Online 0: Disable or disable the
Read/W
42461 Capacity rite 1: Enable generator set PTC Sensors
Sensor Enable Default: Disable online capacity
sensor
Multiplier: Unit: kW Sets the online
Genset Online 1.000000000000 Lower Limit: .000 kW kW threshold
42462 Capacity Read/W Offset: 0
Upper Limit:
at which PTC Sensors
Sensor rite generator set
Threshold Size(bits): 16 32000.000 kW bus is available
Sign: S Default: 0 for loading
Use to enable
Nominal 0: Disable or disable the
Read/W Battery Voltage
42463 Battery Voltage rite 1: Enable nominal battery Protection
Check Enable Default: Disable voltage
monitoring

A029X159 (Issue 14) 499


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/W Offset: 0 code tied to
42464 Output1 Code rite Upper Limit: configurable Discrete Outputs
Size(bits): 16 65535.000 output 1
Sign: U Default: 1483
Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/W Offset: 0 code tied to
42465 Output2 Code rite Upper Limit: configurable Discrete Outputs
Size(bits): 16 65535.000 output 2
Sign: U Default: 1457
Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/W Offset: 0 code tied to
42466 Output3 Code rite Upper Limit: configurable Discrete Outputs
Size(bits): 16 65535.000 output 3
Sign: U Default: 2965
Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/W Offset: 0 code tied to
42467 Output4 Code rite Upper Limit: configurable Discrete Outputs
Size(bits): 16 65535.000 output 4
Sign: U Default: 2328
Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/W Offset: 0 code tied to
42468 Output5 Code rite Upper Limit: configurable Discrete Outputs
Size(bits): 16 65535.000 output 5
Sign: U Default: 1121
Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/W code tied to
42469 Output6 Code rite Offset: 0 Upper Limit: configurable Discrete Outputs
Size(bits): 16 65535.000 output 6
Sign: U Default: 1916
Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/W Offset: 0 code tied to
42470 Output7 Code rite Upper Limit: configurable Discrete Outputs
Size(bits): 16 65535.000 output 7
Sign: U Default: 0
Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/W Offset: 0 code tied to
42471 Output8 Code rite Upper Limit: configurable Discrete Outputs
Size(bits): 16 65535.000 output 8
Sign: U Default: 343
0: None Indicates that
Gen Bus Base Read/W 1: Breaker the generator System
42472 Load Status rite bus is on base Information
2: ATS load extended
Default: None paralleling
0: None Indicates that
Util Bus Peak Read/W 1: Breaker the utility bus is System
42473 Shave Status rite on peak shave Information
2: ATS extended
Default: None paralleling

500 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Indicates type
0: None of load
42474 Load 7 Device Read/W 1: Breaker connected to Load Add Shed
Type rite 2: ATS load 7 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
42475 Load 8 Device Read/W 1: Breaker connected to Load Add Shed
Type rite 2: ATS load 8 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
42476 Load 9 Device Read/W 1: Breaker connected to Load Add Shed
Type rite 2: ATS load 9 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
42477 Load 10 Read/W 1: Breaker connected to Load Add Shed
Device Type rite 2: ATS load 10 add Control
Default: None shed control
and status I/O
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 7 Add Read/W Offset: 0 Lower Limit: .000 add level load Load Add Shed
42478 Level rite 7 is assigned Control
Upper Limit: 17.000
Size (bits): 16 to
Default: 7
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 8 Add Read/W Offset: 0 Lower Limit: 1.000 add level load Load Add Shed
42479 Level rite 8 is assigned control
Upper Limit: 18.000
Size (bits): 16 to
Default: 8
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 9 Add Read/W Offset: 0 Lower Limit: 1.000 add level load Load Add Shed
42480 Level rite 9 is assigned control
Upper Limit: 18.000
Size (bits): 16 to
Default: 9
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 10 Add Read/W Offset: 0 Lower Limit: 1.000 add level load Load Add Shed
42481 Level rite 10 is assigned control
Upper Limit: 18.000
Size (bits): 16 to
Default: 10
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 7 Shed Read/W Offset: 0 Lower Limit: .000 shed level load Load Add Shed
42482 Level rite 7 is assigned control
Upper Limit: 17.000
Size (bits): 16 to
Default: 6
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 8 Shed Read/W Offset: 0 Lower Limit: .000 shed level load Load Add Shed
42483 Level rite 8 is assigned control
Upper Limit: 17.000
Size (bits): 16 to
Default: 7
Sign: U

A029X159 (Issue 14) 501


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


Multiplier: Unit: NA
1.000000000000 Indicates which
Load 9 Shed Read/ Lower Limit: .000 shed level load Load Add Shed
42484 Level Offset: 0
Write Upper Limit: 17.000 9 is assigned control
Size (bits): 16 to
Default: 8
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 10 Shed Read/ Lower Limit: .000 shed level load Load Add Shed
42485 Level Offset: 0
Write Upper Limit: 17.000 10 is assigned control
Size (bits): 16 to
Default: 9
Sign: U
Selects
whether to
Load Demand 0: %kW shutdown /
Read/ Load Add Shed
42486 Threshold Write 1: kW restart control
Method Default: %kW generator sets
based on %kW
or absolute kW
Multiplier: Unit: kW Sets minimum
Load Demand 1.000000000000 Lower Limit: .000 kW kW reserve
42487 Restart kW Read/ Offset: 0 capacity when Load Add Shed
Write Upper Limit: threshold control
Threshold Size (bits): 16 32000.000 kW method is
Sign: S Default: 500 absolute kW
Multiplier: Unit: kW Sets maximum
Load Demand 1.000000000000 Lower Limit: .000 kW kW reserve
42488 Shutdown kW Read/ Offset: 0 capacity when Load Add Shed
Write Upper Limit: threshold control
Threshold Size (bits): 16 32000.000 kW method is
Sign: S Default: 1000 absolute kW
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8 Sets GenE for Load Demand
Load Demand Read/
42489 GenE Write 8: Gen9 fixed sequence Control
9: Gen10 load demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen5

502 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8 Sets GenF for Load Demand
Load Demand Read/
42490 GenF Write 8: Gen9 fixed sequence Control
9: Gen10 load demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen6
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8 Sets GenG for Load Demand
Load Demand Read/
42491 GenG Write 8: Gen9 fixed sequence Control
9: Gen10 load demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen7
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8 Sets GenH for Load Demand
Load Demand Read/
42492 GenH Write 8: Gen9 fixed sequence Control
9: Gen10 load demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen8

A029X159 (Issue 14) 503


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


Sets how long
Multiplier: Unit: second to wait for
.200000000000 Lower Limit: 2.000 generator set
Virtual Gen second
42494 Main Fail to Read/ Offset: 0 paralleling Breaker Control
Open Delay Write Upper Limit: 30.000 circuit breakers
Size (bits): 16 to open when
second
Sign: U no generator
Default: 5
main
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 13 kW Read/ Offset: 0 Sets generator System
42495 Rating Write Upper Limit: 13 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 14kW Read/ Offset: 0 Sets generator System
42496 Rating Write Upper Limit: 14 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 15kW Read/ Offset: 0 Sets generator System
42497 Rating Write Upper Limit: 15 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 16kW Read/ Offset: 0 Sets generator System
42498 Rating Write Upper Limit: 16 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: NA
1.000000000000 Bitmapped
Fault Status Read Lower Limit: state of utility Fault and Event
42500 BitMap 1 Offset: 0
Only Upper Limit: and other faults Info
Size (bits): 32 - 32 bits
Default: 0
Sign: U
Multiplier: Unit: NA Bitmapped
1.000000000000 state of
Fault Status Read Lower Limit: Fault and Event
42502 BitMap 2 Offset: 0 generator set
Only Upper Limit: Info
Size (bits): 32 and other faults
Default: 0 - 32 bits
Sign: U
Multiplier: Unit: NA
1.000000000000 Bitmapped
Event Status Read Lower Limit: Fault and Event
42504 BitMap 1 Offset: 0 state of events
Only Upper Limit: Info
Size (bits): 32 - 32 bits
Default: 0
Sign: U
Bit mapped
Multiplier: Unit: NA word with
Genset 1.000000000000 status of
Read Lower Limit: AC Interrupt
42506 Metering Fault Offset: 0 generator set
Only Upper Limit: Service
Status Size (bits): 16 AC metering
Default: 0 out of range
Sign: U
conditions

504 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier: Bit mapped
1.000000000000 Unit: NA word with
Lower Limit:
42507 Utility Metering Read Offset: 0 status of utility AC Interrupt
Fault Status Only Upper Limit: AC metering Service
Size (bits): 16 out of range
Sign: U Default: 0
conditions

Extended 0: Stop State of


42600 Parallel Start Read / 1: Start extended Discrete Inputs
Vol Write parallel start
Default: Stop volatile input

0: Inactive State of
42601 Synchronizer Read / 1: Active synchronizer Discrete Inputs
Enable Vol Write enable volatile
Default: Inactive input
0: Inactive State of utility
Utility Source Read /
42602 Fail Vol Write 1: Active source failure Discrete Inputs
Default: Inactive volatile input

0: No Inhibit State of
Transfer Inhibit Read /
42603 Vol Write 1: Inhibit transfer inhibit Discrete Inputs
Default: No Inhibit volatile input

0: No Inhibit State of
42604 Retransfer Read / 1: Inhibit retransfer Discrete Inputs
Inhibit Vol Write inhibit volatile
Default: No Inhibit input

0: No Inhibit State of
42605 Gen CB Inhibit Read / 1: Inhibit generator CB Discrete Inputs
Vol Write inhibit volatile
Default: No Inhibit input
0: No Inhibit State of utility
Utility CB Read /
42606 Inhibit Vol Write 1: Inhibit CB inhibit Discrete Inputs
Default: No Inhibit volatile input

0: Auto State of
Auto/Manual Read/
42607 Vol Write 1: Manual auto/manual Discrete Inputs
Default: Auto volatile input

0: Stop state of test


Read/
42608 Test Start Vol Write 1: Start start volatile Discrete Inputs
Default: Stop input

0: No Reset state of fault


Read/
42609 Fault Reset Vol Write 1: Reset reset volatile Discrete Inputs
Default: No Reset input

0: No Override State of
Read/
42610 Override Vol Write 1: Override override Discrete Inputs
Default: No Override volatile input

Extended 0: Stop State of


42611 Parallel Start Read 1: Start extended Discrete Inputs
Sw Only parallel start
Default: input
0: Inactive State of
Synchronizer Read
42612 Enable Sw Only 1: Active synchronizer Discrete Inputs
Default: enable input

A029X159 (Issue 14) 505


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


0: Inactive State of utility
Utility Source Read
42613 Failure Sw Only 1: Active source failure Discrete Inputs
Default: input

0: No Inhibit Status of
Transfer Inhibit Read
42614 Sw Only 1: Inhibit transfer inhibit Discrete Inputs
Default: input

0: No Inhibit Status of
Retransfer Read
42615 Inhibit Sw Only 1: Inhibit retransfer Discrete Inputs
Default: inhibit input

0: No Inhibit State of
Gen CB Inhibit Read
42616 Sw Only 1: Inhibit generator CB Discrete Inputs
Default: inhibit input

0: No Inhibit
Utility CB Read State of utility
42617 Inhibit Sw Only 1: Inhibit CB inhibit input Discrete Inputs
Default:
0: Auto
Auto/Manual Read State of auto /
42618 Sw Only 1: Manual manual input Discrete Inputs
Default:
0: Stop
Read State of test
42619 Test Start Sw Only 1: Start start input Discrete Inputs
Default:
0: No Reset
Read State of fault
42620 Fault Reset Sw Only 1: Reset reset input Discrete Inputs
Default:
0: No Override
Read State of
42621 Override Sw Only 1: Override override input Discrete Inputs
Default:
0: No Inhibit Indicates state
Read
42622 Master Inhibit Only 1: Inhibit of Master Priority Control
Default: priority inhibit

0: Inactive State of
Genset CB Read
42623 Tripped Sw Only 1: Active generator CB Discrete Inputs
Default: tripped input

0: Inactive State of
42624 Genset CB Read/ 1: Active generator CB Discrete Inputs
Tripped Vol Write tripped volatile
Default: Inactive input
0: Inactive State of Utility
Utility CB Read
42625 Tripped Sw Only 1: Active CB tripped Discrete Inputs
Default: input

0: Inactive State of Utility


Util CB Tripped Read/
42626 Vol Write 1: Active CB tripped Discrete Inputs
Default: Inactive volatile input

0: L1-L2-L3
Genset Phase Read Generator set
42627 Rotation Only 1: L1-L3-L2 phase rotation Phase
Default:

506 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: L1-L2-L3
Utility Phase Read Utility phase
42628 Rotation Only 1: L1-L3-L2 rotation Phase
Default:
0: Breaker Open State of Gen1
Gen1 CB Read
42929 Position Sw Only 1: Breaker Closed CB position Discrete Inputs
Default: Open input

0: Breaker Open State of Gen1


Gen1 CB Read/
42630 Position Vol Write 1: Breaker Closed CB volatile Discrete Inputs
Default: Open input

0: Breaker Open State of Gen2


Gen2 CB Read
42631 Position Sw Only 1: Breaker Closed CB position Discrete Inputs
Default: input

0: Breaker Open State of Gen2


Gen2 CB Read/
42632 Position Vol Write 1: Breaker Closed CB volatile Discrete Inputs
Default: Open input

0: Breaker Open State of Gen3


Gen3 CB Read
42633 Position Sw Only 1: Breaker Closed CB position Discrete Inputs
Default: input

0: Breaker Open State of Gen3


Gen3 CB Read/
42634 Position Vol Write 1: Breaker Closed CB volatile Discrete Inputs
Default: Open input

0: Breaker Open State of Gen4


Gen4 CB Read
42635 Position Sw Only 1: Breaker Closed CB position Discrete Inputs
Default: input

0: Breaker Open State of Gen4


Gen4 CB Read/
42636 Position Vol Write 1: Breaker Closed CB volatile Discrete Inputs
Default: Open input

0: No Inhibit Use to
Network Read/
42637 Master Inhibit Write 1: Inhibit manually inhibit Priority Control
Default: No Inhibit the module

0: Breaker Open State of Gen5


Gen5 CB Read
42638 Position Sw Only 1: Breaker Closed CB position Discrete Inputs
Default: input

0: Breaker Open State of Gen5


Gen5 CB Read/
42639 Position Vol Write 1: Breaker Closed CB position Discrete Inputs
Default: Open volatile input

0: Breaker Open State of Gen6


Gen6 CB Read
42640 Position Sw Only 1: Breaker Closed CB position Discrete Inputs
Default: input

0: Breaker Open State of Gen6


Gen6 CB Read/
42641 Position Vol Write 1: Breaker Closed CB position Discrete Inputs
Default: Open volatile input

0: Breaker Open State of Gen7


Gen7 CB Read
42642 Position Sw Only 1: Breaker Closed CB position Discrete Inputs
Default: input

A029X159 (Issue 14) 507


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


0: Breaker Open State of Gen7
Gen7 CB Read/
42643 Position Vol Write 1: Breaker Closed CB position Discrete Inputs
Default: Open volatile input

0: Breaker Open State of Gen8


Gen8 CB Read
42644 Position Sw Only 1: Breaker Closed CB position Discrete Inputs
Default: input

0: Breaker Open State of Gen8


Gen8 CB Read/
42645 Position Vol Write 1: Breaker Closed CB position Discrete Inputs
Default: Open volatile input

0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
42646 ATS 7 Position Read position status Load Add Shed
Only 3: Source 2 Connected of ATS 7 Control
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
42647 ATS 8 Position Read position status Load Add Shed
Only 3: Source 2 Connected of ATS 8 Control
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
42648 ATS 9 Position Read position status Load Add Shed
Only 3: Source 2 Connected of ATS 9 Control
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
42649 ATS 10 Read position status Load Add Shed
Position Only 3: Source 2 Connected of ATS 10 Control
4: Paralleled
Default: Not Available
0: Open
1: Closed Indicates
42650 Breaker 7 Read position status Load Add Shed
Position Only 2: Not Available of breaker 7 Control
Default: Not Available
0: Open
1: Closed Indicates
42651 Breaker 8 Read position status Load Add Shed
Position Only 2: Not Available of breaker 8 Control
Default: Not Available
0: Open
1: Closed Indicates
42652 Breaker 9 Read position status Load Add Shed
Position Only 2: Not Available of breaker 9 Control
Default: Not Available
0: Open
1: Closed Indicates
42653 Breaker 10 Read position status Load Add Shed
Position Only 2: Not Available of breaker 10 Control
Default: Not Available

508 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Not Available
1: Normal Indicates trip
42654 Breaker 7 Trip Read status of Load Add Shed
Status Only 2: Tripped breaker 7 Control
Default: Not Available
0: Not Available
1: Normal Indicates trip
42655 Breaker 8 Trip Read status of Load Add Shed
Status Only 2: Tripped breaker 8 Control
Default: Not Available
0: Not Available
1: Normal Indicates trip
42656 Breaker 9 Trip Read status of Load Add Shed
Status Only 2: Tripped breaker 9 Control
Default: Not Available
0: Not Available
1: Normal Indicates trip
42657 Breaker 10 trip Read status of Load Add Shed
Status Only 2: Tripped breaker 10 Control
Default: Not Available
0: Breaker Open State of Gen9
Gen9 CB Read
42658 Position Sw Only 1: Breaker Closed CB position Discrete Inputs
Default: input

0: Breaker Open State of Gen9


Gen9 CB Read/
42659 Position Vol Write 1: Breaker Closed CB position Discrete Inputs
Default: Open volatile input

0: Breaker Open State of Gen10


Gen10 CB Read
42660 Position Sw Only 1: Breaker Closed CB position Discrete Inputs
Default: input

0: Breaker Open State of Gen10


Gen10 CB Read/
42661 Position Vol Write 1: Breaker Closed CB position Discrete Inputs
Default: Open volatile input

0: Breaker Open State of Gen11


Gen11 CB Read
42662 Position Sw Only 1: Breaker Closed CB position Discrete Inputs
Default: input

0: Breaker Open State of Gen11


Gen11 CB Read/
42663 Position Vol Write 1: Breaker Closed CB position Discrete Inputs
Default: Open volatile input

0: Breaker Open State of Gen12


Gen12 CB Read
42664 Position Sw Only 1: Breaker Closed CB position Discrete Inputs
Default: input

0: Breaker Open State of Gen12


Gen12 CB Read/
42665 Position Vol Write 1: Breaker Closed CB position Discrete Inputs
Default: Open volatile input

0: Breaker Open State of Gen13


Gen13 CB Read
42666 Position Sw Only 1: Breaker Closed CB position Discrete Inputs
Default: input

0: Breaker Open State of Gen13


Gen13 CB Read/
42667 Position Vol Write 1: Breaker Closed CB position Discrete Inputs
Default: Open volatile input

A029X159 (Issue 14) 509


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


0: Breaker Open State of Gen
Gen14 CB Read
42668 Position Sw Only 1: Breaker Closed 14 CB position Discrete Inputs
Default: input

0: Breaker Open State of Gen


Gen14 CB Read/
42669 Position Vol Write 1: Breaker Closed 14 CB position Discrete Inputs
Default: Open volatile input

0: Breaker Open State of Gen


Gen15 CB Read
42670 Position Sw Only 1: Breaker Closed 15 CB position Discrete Inputs
Default: input

0: Breaker Open State of Gen


Gen15 CB Read/
42671 Position Vol Write 1: Breaker Closed 15 CB position Discrete Inputs
Default: Open volatile input

0: Breaker Open State of Gen


Gen16 CB Read
42672 Position Sw Only 1: Breaker Closed 16 CB position Discrete Inputs
Default: input

0: Breaker Open State of Gen


Gen16 CB Read/
42673 Position Vol Write 1: Breaker Closed 16 CB position Discrete Inputs
Default: Open volatile input

0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
42674 ATS 11 Read position status Load Add Shed
Position Only 3: Source 2 Connected of ATS 11 Control
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
42675 ATS 12 Read position status Load Add Shed
Position Only 3: Source 2 Connected of ATS 12 Control
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
42676 ATS 13 Read position status Load Add Shed
Position Only 3: Source 2 Connected of ATS 13 Control
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
42677 ATS 14 Read position status Load Add Shed
Position Only 3: Source 2 Connected of ATS 14 Control
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
42678 ATS 15 Read position status Load Add Shed
Position Only 3: Source 2 Connected of ATS 15 Control
4: Paralleled
Default: Not Available

510 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
42679 ATS 16 Read position status Load Add Shed
Position Only 3: Source 2 Connected of ATS 16 Control
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
42680 ATS 17 Read position status Load Add Shed
Position Only 3: Source 2 Connected of ATS 17 Control
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
42681 ATS 18 Read position status Load Add Shed
Position Only 3: Source 2 Connected of ATS 18 Control
4: Paralleled
Default: Not Available
0: Open
1: Closed Indicates
42682 Breaker 11 Read position status Load Add Shed
Position Only 2: Not Available of breaker 11 Control
Default: Not Available
0: Open
1: Closed Indicates
42683 Breaker 12 Read position status Load Add Shed
Position Only 2: Not Available of breaker 12 Control
Default: Not Available
0: Open
1: Closed Indicates
42684 Breaker 13 Read position status Load Add Shed
Position Only 2: Not Available of breaker 13 Control
Default: Not Available
0: Open
1: Closed Indicates
42685 Breaker 14 Read position status Load Add Shed
Position Only 2: Not Available of breaker 14 Control
Default: Not Available
0: Open
1: Closed Indicates
42686 Breaker 15 Read position status Load Add Shed
Position Only 2: Not Available of breaker 15 Control
Default: Not Available
0: Open
1: Closed Indicates
42687 Breaker 16 Read position status Load Add Shed
Position Only 2: Not Available of breaker 16 Control
Default: Not Available
0: Open
1: Closed Indicates
42688 Breaker 17 Read position status Load Add Shed
Position Only 2: Not Available of breaker 17 Control
Default: Not Available

A029X159 (Issue 14) 511


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


0: Open
1: Closed Indicates
42689 Breaker 18 Read position status Load Add Shed
Position Only 2: Not Available of breaker 18 Control
Default: Not Available
0: Not Available
1: Normal Indicates trip
42690 Breaker 11 Trip Read status of Load Add Shed
Status Only 2: Tripped breaker 11 Control
Default: Not Available
0: Not Available
1: Normal Indicates trip
42691 Breaker 12 Trip Read status of Load Add Shed
Status Only 2: Tripped breaker 12 Control
Default: Not Available
0: Not Available
1: Normal Indicates trip
42692 Breaker 13 Trip Read status of Load Add Shed
Status Only 2: Tripped breaker 13 Control
Default: Not Available
0: Not Available
1: Normal Indicates trip
42693 Breaker 14 Trip Read status of Load Add Shed
Status Only 2: Tripped breaker 14 Control
Default: Not Available
0: Not Available
1: Normal Indicates trip
42694 Breaker 15 Trip Read status of Load Add Shed
Status Only 2: Tripped breaker 15 Control
Default: Not Available
0: Not Available
1: Normal Indicates trip
42695 Breaker 16 Trip Read status of Load Add Shed
Status Only 2: Tripped breaker 16 Control
Default: Not Available
0: Not Available
1: Normal Indicates trip
42696 Breaker 17 Trip Read status of Load Add Shed
Status Only 2: Tripped breaker 17 Control
Default: Not Available
0: Not Available
1: Normal Indicates trip
42697 Breaker 18 Trip Read status of Load Add Shed
Status Only 2: Tripped breaker 18 Control
Default: Not Available
0: Disabled Indicates the
1: Enabled
42698 Load Add Shed Read overall state of Load Add Shed
Enable Status Only 2: Paused the load add Control
Default: shed function

0: No Connection Indicates
Read 1: Connected overall state of
42699 PCCNet Status Only the PCCNet Communications
2: Connecting communication
Default: s bus

512 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Gen Does Not Exist
1: Offline For load
Gen1 2: Waiting For Gen
42700 Availability Read demand use - Load Demand
State Only 3: Online indicates status Control
4: Failed of Gen1
Default:
0: Gen Does Not Exist 1: Offline
2: Waiting For Gen For load
Gen2 Read demand use - Load Demand
42701 Availability Only 3: Online indicates status Control
State 4: Failed of Gen2
Default:
0: Gen Does Not Exist 1: Offline For load
Gen3 2: Waiting For Gen
42702 Availability Read demand use - Load Demand
State Only 3: Online 4: Failed indicates status Control
Default: of Gen3

0: Gen Does Not Exist 1: Offline


2: Waiting For Gen For load
Gen4 Read demand use - Load Demand
42703 Availability Only 3: Online indicates status Control
State 4: Failed of Gen4
Default:
Multiplier: Unit: Hours
.000277777780 Lower Limit:.000 Hours
Gen1 Online Read Offset: 0 Total online System
42704 Time Only Upper Limit: time for Gen1 Information
Size (bits): 32 1193046.000 Hours
Sign: U Default: 0
Unit: Hours Lower
Multiplier: Limit: .000 Hours
Gen2 Online Read .000277777780 Total online System
42706 Time Upper Limit:
Only Offset: 0 time for Gen2 Information
1193046.000 Hours
Size (bits): 32
Default: 0

Multiplier: Unit: Hours Lower


.000277777780 Limit: .000 Hours
Gen3 Online Read Total online System
42708 Time Only Offset: 0 Upper Limit: time for Gen3 Information
1193046.000 Hours
Size (bits): 32
Default: 0

Multiplier: Unit: Hours Lower


.000277777780 Limit: .000 Hours
Gen4 Online Read Total online System
42710 Time Only Offset: 0 Upper Limit: time for Gen4 Information
1193046.000 Hours
Size (bits): 32
Default: 0

A029X159 (Issue 14) 513


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Read currently GenA Load Demand
42712 GenA Only 8: Gen9 (never stops) Control
9: Gen10 for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
Indicates which
7: Gen8 generator set is Load Demand
Read
42713 GenB Only 8: Gen9 currently GenB Control
9: Gen10 for load
demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
Indicates which
7: Gen8 generator set is Load Demand
Read
42714 GenC Only 8: Gen9 currently GenC Control
9: Gen10 for load
demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

514 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
Indicates which
7: Gen8 generator sets Load Demand
Read
42715 GenD Only 8: Gen9 is currently Control
9: Gen10 GenD for load
demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Off Indicates
1: Initial Delay Timing
42716 Load Demand Read operating state Load Demand
State Only 2: Load Monitor of the load Control
Default demand control

Indicates how
Multiplier: Unit: NA many of the
Total Number 1.000000000000 generator sets
Read Lower Limit: System
42717 of Gensets Offset: 0 are online
Only Upper Limit: Information
Online Size (bits): 16 which are
Default: sensed by CB
Sign: U
position
Multiplier: Difference
1.000000000000 Unit: kW between
Total Spare Lower Limit: kW
42718 Online Read Offset: 0 sensed online System
Capacity Only Upper Limit: kW capacity and Information
Size (bits): 16 generator set
Sign: S Default:
bus total kW
Multiplier: Indicates kW
1.000000000000 Unit: kW threshold for
Next Gen Lower Limit: kW
42719 Shutdown Read Offset: 0 generator bus Load Demand
Threshold Only Upper Limit: kW at which next Control
Size (bits): 16 generator set
Sign: S Default:
will restart
Indicates kW
Multiplier: Unit: kW threshold for
Next Gen 1.000000000000 generator bus
Read Lower Limit: kW Load Demand
42720 Shutdown Offset: 0 at which the
Only Upper Limit: kW Control
Threshold Size (bits): 16 next generator
Default: set will load
Sign: S
demand stop

A029X159 (Issue 14) 515


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Next Gen Read next to be Load Demand
42721 Restart Only 8: Gen9 restarted if load Control
9: Gen10 conditions are
10: Gen11 met
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Next Gen Read next to be Load Demand
42722 Shutdown Only 8: Gen9 stopped if load Control
9: Gen10 conditions are
10: Gen11 met
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

Load Demand 0: Run Status of the


42723 Gen1 Driver Read 1: Load Demand Stop load demand Discrete Outputs
Status Only Gen1 driver
Default: output

Load Demand 0: Run Status of the


42724 Gen2 Driver Read 1: Load Demand Stop load demand Discrete Outputs
Status Only Gen2 driver
Default: output

Load Demand 0: Run Status of the


42725 Gen3 Driver Read 1: Load Demand Stop load demand Discrete Outputs
Status Only Gen3 driver
Default: output

Load Demand 0: Run Status of the


42726 Gen4 Driver Read 1: Load Demand Stop load demand Discrete Outputs
Status Only Gen4 driver
Default: output

516 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier: Calculated kW
1.000000000000 Unit: kW overload
Genset Bus Lower Limit: kW
42727 kW Overload Read Offset: 0 threshold System
Status Only Upper Limit: kW based on Information
Size (bits): 16 online capacity
Sign: S Default:
and % setting
Indicates
Genset Bus 0: No Overload whether
Read System
42728 kW Overload Only 1: Overload generator bus Information
Status Default: is overloaded
based on kW
Indicates
Genset Bus 0: No Overload whether
42729 Underfrequenc Read 1: Overload generator bus System
y Overload Only is overloaded Information
Status Default: based on
frequency
0: None
1: Program 1
2: Program 2
3: Program 3
4: Program 4
5: Program 5
6: Program 6
7: Program 7
8: Program 8 Indicates the
9: Program 9 currently active
42730 Active Read scheduler System
Schedule Only 10: Program 10 program or Scheduler
11: Program 11 exception
12: Program 12
13: Exception 1
14: Exception 2
15: Exception 3
16: Exception 4
17: Exception 5
18: Exception 6
Default:
0: Off Indicates
1: No Load current run
Scheduler Run Read command System
42731 Command Only 2: With Load coming from Scheduler
3: Extended Parallel scheduler
Default: function
Multiplier: Unit: NA
Modbus Bus 1.000000000000
Read Lower Limit: Modbus
42732 Message Offset: 0
Only Upper Limit: message count Communications
Count Size (bits): 16
Default:
Sign: U
Multiplier: Unit: NA
1.000000000000
Modbus CRC Read Lower Limit: Modbus CRC
42733 Error Count Offset: 0 Communications
Only Upper Limit: error count
Size (bits): 16
Default:
Sign: U

A029X159 (Issue 14) 517


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


Multiplier: Unit: NA
Modbus 1.000000000000 Modbus
Read Lower Limit:
42734 Exception Offset: 0 exception Communications
Only Upper Limit:
Count Size (bits): 16 count
Default:
Sign: U
Multiplier: Unit: NA
Modbus No 1.000000000000
Read Lower Limit: Modbus no
42735 Response Offset: 0
Only Upper Limit: response count Communications
Count Size (bits): 16
Default:
Sign: U
Multiplier: Unit: NA
Modbus Slave 1.000000000000
Read Lower Limit: Modbus slave
42736 Message Offset: 0
Only Upper Limit: message count Communications
Count Size (bits): 16
Default:
Sign: U
0: Do Nothing Clears all
Modbus Clear Read/
42737 Counters Write 1: Clear Counters Modbus Communications
Default: Do Nothing counters

0: Normal
1: Set Clock Use to set
42738 Clock Mode Read/ clock and save Real Time Clock
Write 2: Save Clock setting
Default: Normal

Multiplier: Unit: year


1.000000000000 Lower Limit: .000 year
Use to set or
42739 Clock Year Read/ Offset: 0 Upper Limit: 99.000 read current Real Time Clock
Write year year
Size (bits): 16
Sign: U Default: Read from
RTC chip
Unit: month
Multiplier: Lower Limit: 1.000
1.000000000000 month Use to set or
Read/ Offset: 0
42740 Clock Month Write Upper Limit: 12.000 read current Real Time Clock
Size (bits): 16 month month
Sign: U Default: Read from
RTC chip
Unit: date
Multiplier: Lower Limit: 1.000
1.000000000000 date Use to set or
Read/ Offset: 0
42741 Clock Date Write Upper Limit: 31.000 read current Real Time Clock
Size (bits): 16 date date
Sign: U Default: Read from
RTC chip
Unit: hour
Multiplier: Lower Limit: 1.000
1.000000000000 hour Use to set or
Read/ Offset: 0
42742 Clock Hour Write Upper Limit: 23.000 read current Real Time Clock
Size (bits): 16 hour hour
Sign: U Default: Read from
RTC chip

518 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Unit: minute
Multiplier: Lower Limit: 1.000
1.000000000000 minute Use to set or
Read/ Offset: 0
42743 Clock Minute Write Upper Limit: 59.000 read current Real Time Clock
Size (bits): 16 minute minute
Sign: U Default: Read from
RTC chip
Unit: second
Multiplier: Lower Limit: .000
1.000000000000 second Use to set or
Read/ Offset: 0
42744 Clock Second Write Upper Limit: 59.000 read current Real Time Clock
Size (bits): 16 second second
Sign: U Default: Read from
RTC chip
0: Sunday
1: Monday
2: Tuesday
3: Wednesday Indicates day
42745 Clock Day Read of the week for Real Time Clock
Only 4: Thursday current date
5: Friday
6: Saturday
Default:
Multiplier: Unit: seconds
.100000000000 Countdown
Read Lower Limit: seconds timer value for PTC Operating
42746 Start Timer Offset: 0
Only Upper Limit: seconds generator set Mode
Size (bits): 16 start timer
Default:
Sign: U
Multiplier: Unit: seconds
.100000000000 Countdown
Read Lower Limit: seconds timer value for PTC Operating
42747 Stop Timer Offset: 0
Only Upper Limit: seconds generator set Mode
Size (bits): 16 stop timer
Default:
Sign: U
Multiplier: Unit: VDC
.010000000000 Battery voltage
Low Battery Read Lower Limit: VDC with respect to Battery Voltage
42748 Voltage Offset: 0
Only Upper Limit: VDC set low battery Protection
Threshold Size (bits): 16 threshold
Default:
Sign: U
Multiplier: Unit: VDC
.010000000000 Battery voltage
High Battery Read Lower Limit: VDC with respect to Battery Voltage
42749 Voltage Offset: 0
Only Upper Limit: VDC set high battery Protection
Threshold Size (bits): 16 threshold
Default:
Sign: U
0: Gen Does Not Exist
1: Offline For load
Gen5 2: Waiting for Gen
42750 Availability Read demand use - Load Demand
State Only 3: Online indicates status Control
4: Failed of Gen5
Default:

A029X159 (Issue 14) 519


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


0: Gen Does Not Exist
1: Offline For load
Gen6 2: Waiting for Gen
42751 Availability Read demand use - Load Demand
State Only 3: Online indicates status Control
4: Failed of Gen6
Default:
0: Gen Does Not Exist
1: Offline For load
Gen7 2: Waiting for Gen
42752 Availability Read demand use - Load Demand
State Only 3: Online indicates status Control
4: Failed of Gen7
Default:
0: Gen Does Not Exist
1: Offline For load
Gen8 2: Waiting for Gen
42753 Availability Read demand use - Load Demand
State Only 3: Online indicates status Control
4: Failed of Gen8
Default:

Load Demand 0: Run Status of the


42754 Gen5 Driver Read 1: Load Demand Stop load demand Discrete Outputs
Status Only Gen5 driver
Default: output

Load Demand 0: Run Status of the


42755 Gen6 Driver Read 1: Load Demand Stop load demand Discrete Outputs
Status Only Gen6 driver
Default: output

Load Demand 0: Run Status of the


42756 Gen7 Driver Read 1: Load Demand Stop load demand Discrete Outputs
Status Only Gen7 driver
Default: output

Load Demand 0: Run Status of the


42757 Gen8 Driver Read 1: Load Demand Stop load demand Discrete Outputs
Status Only Gen8 driver
Default: output
0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
Indicates which
7: Gen 8 generator set is Load Demand
Read
42758 GenE Only 8: Gen 9 currently GenE Control
9: Gen 10 for load
demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default:

520 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
Indicates which
7: Gen 8 generator set is Load Demand
Read
42759 GenF Only 8: Gen 9 currently GenF Control
9: Gen 10 for load
demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default:
0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
Indicates which
7: Gen 8 generator set is Load Demand
Read
42760 GenG Only 8: Gen 9 currently GenG Control
9: Gen 10 for load
demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default:
0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
Indicates which
7: Gen 8 generator set is Load Demand
Read
42761 GenH Only 8: Gen 9 currently GenH Control
9: Gen 10 for load
demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default:

A029X159 (Issue 14) 521


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


0: Do Nothing Indicates
Add Level 7 Read Load Add Shed
42762 Command Only 1: Add Level status of add Control
Default: Do Nothing level 7

0: Do Nothing Indicates
Add Level 8 Read Load Add Shed
42763 Command Only 1: Add Level status of add Control
Default: Do Nothing level 8

0: Do Nothing Indicates
Add Level 9 Read Load Add Shed
42764 Command Only 1: Add Level status of add Control
Default: Do Nothing level 9

0: Do Nothing Indicates
Add Level 10 Read Load Add Shed
42765 Command Only 1: Add Level status of add Control
Default: Do Nothing level 10

0: Do Nothing Indicates add


Add Load 7 Read Load Add Shed
42766 Command Only 1: Add Level command for Control
Default: Do Nothing load 7

0: Do Nothing Indicates add


Add Load 8 Read Load Add Shed
42767 Command Only 1: Add Level command for Control
Default: Do Nothing load 8

0: Do Nothing Indicates add


Add Load 9 Read Load Add Shed
42768 Command Only 1: Add Level command for Control
Default: Do Nothing load 9

0: Do Nothing Indicates add


Add Load 10 Read Load Add Shed
42769 Command Only 1: Add Level command for Control
Default: Do Nothing load 10

0: Do Nothing Indicates
Shed Level 6 Read Load Add Shed
42770 Command Only 1: Shed Level status of shed Control
Default: Do Nothing level 6

0: Do Nothing Indicates
Shed Level 7 Read Load Add Shed
42771 Command Only 1: Shed Level status of shed Control
Default: Do Nothing level 7

0: Do Nothing Indicates
Shed Level 8 Read Load Add Shed
42772 Command Only 1: Shed Level status of shed Control
Default: Do Nothing level 8

0: Do Nothing Indicates
Shed Level 9 Read Load Add Shed
42773 Command Only 1: Shed Level status of shed Control
Default: Do Nothing level 9

0: Do Nothing Indicates shed


Shed Load 7 Read Load Add Shed
42774 Command Only 1: Shed Load command for Control
Default: Do Nothing load 7

0: Do Nothing Indicates shed


Shed Load 8 Read Load Add Shed
42775 Command Only 1: Shed Load command for Control
Default: Do Nothing load 8

0: Do Nothing Indicates shed


Shed Load 9 Read Load Add Shed
42776 Command Only 1: Shed Load command for Control
Default: Do Nothing load 9

522 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Do Nothing Indicates shed
Shed Load 10 Read Load Add Shed
42777 Command Only 1: Shed Load command for Control
Default: Do Nothing load 10

Restore Shed 0: Do Nothing Indicates if


42778 Level 6 Read 1: Restore Level shed level 6 Load Add Shed
Command Only has been Control
Default: Do Nothing restored

Restore Shed 0: Do Nothing Indicates if


42779 Level 7 Read/ 1: Restore Level shed level 7 Load Add Shed
Command Write has been Control
Default: Do Nothing restored

Restore Shed 0: Do Nothing Indicates if


42780 Level 8 Read/ 1: Restore Level shed level 8 Load Add Shed
Command Write has been Control
Default: Do Nothing restored

Restore Shed 0: Do Nothing Indicates if


42781 Level 9 Read/ 1: Restore Level shed level 9 Load Add Shed
Command Write has been Control
Default: Do Nothing restored

Multiplier: Unit: hours


.000277777780 Lower Limit: .000
hours
42782 Gen5 Online Read Offset: 0 Total online System
Time Only Upper Limit: time for Gen5 Information
Size (bits): 32
1193046.000 hours
Sign: U
Default: 0

Multiplier: Unit: hours


.000277777780 Lower Limit: .000
hours
42784 Gen6 Online Read Offset: 0 Total online System
Time Only Upper Limit: time for Gen6 Information
Size (bits): 32
1193046.000 hours
Sign: U
Default: 0

Multiplier: Unit: hours


.000277777780 Lower Limit: .000
hours
42786 Gen7 Online Read Offset: 0 Total online System
Time Only Upper Limit: time for Gen7 Information
Size (bits): 32
1193046.000 hours
Sign: U
Default: 0

Multiplier: Unit: hours


.000277777780 Lower Limit: .000
hours
42788 Gen8 Online Read Offset: 0 Total online System
Time Only Upper Limit: time for Gen8 Information
Size (bits): 32
1193046.000 hours
Sign: U
Default: 0

Manual Add 0: Do Nothing Operator input


42790 Level 7 Read/ 1: Add Level to add loads Load Add Shed
Command Write assigned to Control
Default: Do Nothing level 7

Manual Add 0: Do Nothing Operator input


42791 Level 8 Read/ 1: Add Level to add loads Load Add Shed
Command Write assigned to Control
Default: Do Nothing level 8

A029X159 (Issue 14) 523


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function

Manual Add 0: Do Nothing Operator input


42792 Level 9 Read/ 1: Add Level to add loads Load Add Shed
Command Write assigned to Control
Default: Do Nothing level 9

Manual Add 0: Do Nothing Operator input


42793 Level 10 Read/ 1: Add Level to add loads Load Add Shed
Command Write assigned to Control
Default: Do Nothing level 10

Manual Shed 0: Do Nothing Operator input


42794 Level 6 Read/ 1: Shed Level to shed loads Load Add Shed
Command Write assigned to Control
Default: Do Nothing level 6

Manual Shed 0: Do Nothing Operator input


42795 Level 7 Read/ 1: Shed Level to shed loads Load Add Shed
Command Write assigned to Control
Default: Do Nothing level 7

Manual Shed 0: Do Nothing Operator input


42796 Level 8 Read/ 1: Shed Level to shed loads Load Add Shed
Command Write assigned to Control
Default: Do Nothing level 8

Manual Shed 0: Do Nothing Operator input


42797 Level 9 Read/ 1: Shed Level to shed loads Load Add Shed
Command Write assigned to Control
Default: Do Nothing level 9
0: Gen Does Not Exist
1: Offline For load
Gen9 2: Waiting For Gen
42798 Availability Read demand use - Load Demand
State Only 3: Online indicates status Control
4: Failed of Gen9
Default:
0: Gen Does Not Exist
1: Offline For load
Gen10 2: Waiting For Gen
42799 Availability Read demand use - Load Demand
State Only 3: Online indicates status Control
4: Failed of Gen10
Default:
0: Gen Does Not Exist
1: Offline For load
Gen11 2: Waiting For Gen
42800 Availability Read demand use - Load Demand
State Only 3: Online indicates status Control
4: Failed of Gen11
Default:
0: Gen Does Not Exist
1: Offline For load
Gen12 2: Waiting For Gen
42801 Availability Read demand use - Load Demand
State Only 3: Online indicates status Control
4: Failed of Gen12
Default:

524 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Gen Does Not Exist
1: Offline For load
Gen13 2: Waiting For Gen
42802 Availability Read demand use - Load Demand
State Only 3: Online indicates status Control
4: Failed of Gen13
Default:
0: Gen Does Not Exist
1: Offline For load
Gen14 2: Waiting for Gen
42803 Availability Read demand use - Load Demand
State Only 3: Online indicates status Control
4: Failed of Gen14
Default:
0: Gen Does Not Exist
1: Offline For load
Gen15 2: Waiting for Gen
42804 Availability Read demand use - Load Demand
State Only 3: Online indicates status Control
4: Failed of Gen15
Default:
0: Gen Does Not Exist
1: Offline For load
Gen16 2: Waiting for Gen
42805 Availability Read demand use - Load Demand
State Only 3: Online indicates status Control
4: Failed of Gen16
Default:

Load Demand 0: Run Status of load


Read
42806 Gen9 Driver Only 1: Load Demand Stop demand Gen9 Discrete Outputs
Status Default: driver output

Load Demand 0: Run Status of load


Read
42807 Gen10 Driver Only 1: Load Demand Stop demand Gen10 Discrete Outputs
Status Default: driver output

Load Demand 0: Run Status of load


Read
42808 Gen11 Driver Only 1: Load Demand Stop demand Gen11 Discrete Outputs
Status Default: driver output

Load Demand 0: Run Status of load


Read
42809 Gen12 Driver Only 1: Load Demand Stop demand Gen12 Discrete Outputs
Status Default: driver output

Load Demand 0: Run Status of load


Read
42810 Gen13 Driver Only 1: Load Demand Stop demand Gen13 Discrete Outputs
Status Default: driver output

Load Demand 0: Run Status of load


Read
42811 Gen14 Driver Only 1: Load Demand Stop demand Gen14 Discrete Outputs
Status Default: driver output

Load Demand 0: Run Status of load


Read
42812 Gen15 Driver Only 1: Load Demand Stop demand Gen15 Discrete Outputs
Status Default: driver output

Load Demand 0: Run Status of load


Read
42813 Gen16 Driver Only 1: Load Demand Stop demand Gen16 Discrete Outputs
Status Default: driver output

A029X159 (Issue 14) 525


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
Indicates which
7: Gen8 generator set is Load Demand
Read
42814 GenI Only 8: Gen9 currently GenI Control
9: Gen10 for load
demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
Indicates which
7: Gen8 generator set is Load Demand
Read
42815 GenJ Only 8: Gen9 currently GenJ Control
9: Gen10 for load
demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
Indicates which
7: Gen8 generator set is Load Demand
Read
42816 GenK Only 8: Gen9 currently GenK Control
9: Gen10 for load
demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

526 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
Indicates which
7: Gen8 generator set is Load Demand
Read
42817 GenL Only 8: Gen9 currently GenL Control
9: Gen10 for load
demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
Indicates which
7: Gen8 generator set is Load Demand
Read
42818 GenM Only 8: Gen9 currently GenM Control
9: Gen10 for load
demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
Indicates which
7: Gen8 generator set is Load Demand
Read
42819 GenN Only 8: Gen9 currently GenN Control
9: Gen10 for load
demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

A029X159 (Issue 14) 527


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
Indicates which
7: Gen8 generator set is Load Demand
Read
42820 GenO Only 8: Gen9 currently GenO Control
9: Gen10 for load
demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
Indicates which
7: Gen8 generator set is Load Demand
Read
42821 GenP Only 8: Gen9 currently GenP Control
9: Gen10 for load
demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Do Nothing Indicates
Add Level 11 Read Load Add Shed
42822 Command Only 1: Add Level status of add Control
Default: Do Nothing level 11

0: Do Nothing Indicates
Add Level 12 Read Load Add Shed
42823 Command Only 1: Add Level status of add Control
Default: Do Nothing level 12

0: Do Nothing Indicates
Add Level 13 Read Load Add Shed
42824 Command Only 1: Add Level status of add Control
Default: Do Nothing level 13

0: Do Nothing Indicates
Add Level 14 Read Load Add Shed
42825 Command Only 1: Add Level status of add Control
Default: Do Nothing level 14

0: Do Nothing Indicates
Add Level 15 Read Load Add Shed
42826 Command Only 1: Add Level status of add Control
Default: Do Nothing level 15

528 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Do Nothing Indicates
Add Level 16 Read Load Add Shed
42827 Command Only 1: Add Level status of add Control
Default: Do Nothing level 16

0: Do Nothing Indicates
Add Level 17 Read Load Add Shed
42828 Command Only 1: Add Level status of add Control
Default: Do Nothing level 17

0: Do Nothing Indicates
Add Level 18 Read Load Add Shed
42829 Command Only 1: Add Level status of add Control
Default: Do Nothing level 18

0: Do Nothing Indicates add


Add Load 11 Read Load Add Shed
42830 Command Only 1: Add Load command for Control
Default: Do Nothing load 11

0: Do Nothing Indicates add


Add Load 12 Read Load Add Shed
42831 Command Only 1: Add Load command for Control
Default: Do Nothing load 12

0: Do Nothing Indicates add


Add Load 13 Read Load Add Shed
42832 Command Only 1: Add Load command for Control
Default: Do Nothing load 13

0: Do Nothing Indicates add


Add Load 14 Read Load Add Shed
42833 Command Only 1: Add Load command for Control
Default: Do Nothing load 14

0: Do Nothing Indicates add


Add Load 15 Read Load Add Shed
42834 Command Only 1: Add Load command for Control
Default: Do Nothing load 15

0: Do Nothing Indicates add


Add Load 16 Read Load Add Shed
42835 Command Only 1: Add Load command for Control
Default: Do Nothing load 16

0: Do Nothing Indicates add


Add Load 17 Read Load Add Shed
42836 Command Only 1: Add Load command for Control
Default: Do Nothing load 17

0: Do Nothing Indicates add


Add Load 18 Read Load Add Shed
42837 Command Only 1: Add Load command for Control
Default: Do Nothing load 18

0: Do Nothing Indicates
Shed Level 10 Read Load Add Shed
42838 Command Only 1: Shed Level status of shed Control
Default: Do Nothing level 10

0: Do Nothing Indicates
Shed Level 11 Read Load Add Shed
42839 Command Only 1: Shed Level status of shed Control
Default: Do Nothing level 11

0: Do Nothing Indicates
Shed Level 12 Read Load Add Shed
42840 Command Only 1: Shed Level status of shed Control
Default: Do Nothing level 12

0: Do Nothing Indicates
Shed Level 13 Read Load Add Shed
42841 Command Only 1: Shed Level status of shed Control
Default: Do Nothing level 13

A029X159 (Issue 14) 529


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


0: Do Nothing Indicates
Shed Level 14 Read Load Add Shed
42842 Command Only 1: Shed Level status of shed Control
Default: Do Nothing level 14

0: Do Nothing Indicates
Shed Level 15 Read Load Add Shed
42843 Command Only 1: Shed Level status of shed Control
Default: Do Nothing level 15

0: Do Nothing Indicates
Shed Level 16 Read Load Add Shed
42844 Command Only 1: Shed Level status of shed Control
Default: Do Nothing level 16

0: Do Nothing Indicates
Shed Level 17 Read Load Add Shed
42845 Command Only 1: Shed Level status of shed Control
Default: Do Nothing level 17

0: Do Nothing Indicates shed


Shed Load 11 Read Load Add Shed
42846 Command Only 1: Shed Load command for Control
Default: Do Nothing load 11

0: Do Nothing Indicates shed


Shed Load 12 Read Load Add Shed
42847 Command Only 1: Shed Load command for Control
Default: Do Nothing load 12

0: Do Nothing Indicates shed


Shed Load 13 Read Load Add Shed
42848 Command Only 1: Shed Load command for Control
Default: Do Nothing load 13

0: Do Nothing Indicates shed


Shed Load 14 Read Load Add Shed
42849 Command Only 1: Shed Load command for Control
Default: Do Nothing load 14

0: Do Nothing Indicates shed


Shed Load 15 Read Load Add Shed
42850 Command Only 1: Shed Load command for Control
Default: Do Nothing load 15

0: Do Nothing Indicates shed


Shed Load 16 Read Load Add Shed
42851 Command Only 1: Shed Load command for Control
Default: Do Nothing load 16

0: Do Nothing Indicates shed


Shed Load 17 Read/ Load Add Shed
42852 Command Write 1: Shed Load command for Control
Default: Do Nothing load 17

0: Do Nothing Indicates shed


Shed Load 18 Read/ Load Add Shed
42853 Command Write 1: Shed Load command for Control
Default: Do Nothing load 18

Restore Shed 0: Do Nothing Indicates if


42854 Level 10 Read/ 1: Restore Level shed level 10 Load Add Shed
Command Write has been Control
Default: Do Nothing restored

Restore Shed 0: Do Nothing Indicates if


42855 Level 11 Read/ 1: Restore Level shed level 11 Load Add Shed
Command Write has been Control
Default: Do Nothing restored

530 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function

Restore Shed 0: Do Nothing Indicates if


42856 Level 12 Read/ 1: Restore Level shed level 12 Load Add Shed
Command Write has been Control
Default: Do Nothing restored

Restore Shed 0: Do Nothing Indicates if


42857 Level 13 Read/ 1: Restore Level shed level 13 Load Add Shed
Command Write has been Control
Default: Do Nothing restored

Restore Shed 0: Do Nothing Indicates if


42858 Level 14 Read/ 1: Restore Level shed level 14 Load Add Shed
Command Write has been Control
Default: Do Nothing restored

Restore Shed 0: Do Nothing Indicates if


42859 Level 15 Read/ 1: Restore Level shed level 15 Load Add Shed
Command Write has been Control
Default: Do Nothing restored

Restore Shed 0: Do Nothing Indicates if


42860 Level 16 Read/ 1: Restore Level shed level 16 Load Add Shed
Command Write has been Control
Default: Do Nothing restored

Restore Shed 0: Do Nothing Indicates if


42861 Level 17 Read/ 1: Restore Level shed level 17 Load Add Shed
Command Write has been Control
Default: Do Nothing restored

Multiplier: Unit: Hours


.000277777780 Lower Limit: .000
Hours
42862 Gen9 Online Read Offset: 0 Total online System
Time Only Upper Limit: time for Gen9 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0

Multiplier: Unit: Hours


.000277777780 Lower Limit: .000
Hours
42864 Gen10 Online Read Offset: 0 Total online System
Time Only Upper Limit: time for Gen10 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0

Multiplier: Unit: Hours


.000277777780 Lower Limit: .000
Hours
42866 Gen11 Online Read Offset: 0 Total online System
Time Only Upper Limit: time for Gen11 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0

Multiplier: Unit: Hours


.000277777780 Lower Limit: .000
Hours
42868 Gen12 Online Read Offset: 0 Total online System
Time Only Upper Limit: time for Gen12 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0

Multiplier: Unit: Hours


.000277777780 Lower Limit: .000
Hours
42870 Gen13 Online Read Offset: 0 Total online System
Time Only Upper Limit: time for Gen13 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0

A029X159 (Issue 14) 531


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function

Multiplier: Unit: Hours


.000277777780 Lower Limit: .000
Hours
42872 Gen14 Online Read Offset: 0 Total online System
Time Only Upper Limit: time for Gen14 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0

Multiplier: Unit: Hours


.000277777780 Lower Limit: .000
Hours
42874 Gen15 Online Read Offset: 0 Total online System
Time Only Upper Limit: time for Gen15 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0

Multiplier: Unit: Hours


.000277777780 Lower Limit: .000
Hours
42876 Gen16 Online Read Offset: 0 Total online System
Time Only Upper Limit: time for Gen16 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0

Manual Add 0: Do Nothing Operator input


42878 Level 11 Read/ 1: Add Level to add loads Load Add Shed
Command Write assigned to Control
Default: Do Nothing level 11

Manual Add 0: Do Nothing Operator input


42879 Level 12 Read/ 1: Add Level to add loads Load Add Shed
Command Write assigned to Control
Default: Do Nothing level 12

Manual Add 0: Do Nothing Operator input


42880 Level 13 Read/ 1: Add Level to add loads Load Add Shed
Command Write assigned to Control
Default: Do Nothing level 13

Manual Add 0: Do Nothing Operator input


42881 Level 14 Read/ 1: Add Level to add loads Load Add Shed
Command Write assigned to Control
Default: Do Nothing level 14

Manual Add 0: Do Nothing Operator input


42882 Level 15 Read/ 1: Add Level to add loads Load Add Shed
Command Write assigned to Control
Default: Do Nothing level 15

Manual Add 0: Do Nothing Operator input


42883 Level 16 Read/ 1: Add Level to add loads Load Add Shed
Command Write assigned to Control
Default: Do Nothing level 16

Manual Add 0: Do Nothing Operator input


42884 Level 17 Read/ 1: Add Level to add loads Load Add Shed
Command Write assigned to Control
Default: Do Nothing level 17

Manual Add 0: Do Nothing Operator input


42885 Level 18 Read/ 1: Add Level to add loads Load Add Shed
Command Write assigned to Control
Default: Do Nothing level 18

Manual Shed 0: Do Nothing Operator input


42886 Level 10 Read/ 1: Shed Level to shed loads Load Add Shed
Command Write assigned to Control
Default: Do Nothing level 10

532 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function

Manual Shed 0: Do Nothing Operator input


42887 Level 11 Read/ 1: Shed Level to shed loads Load Add Shed
Command Write assigned to Control
Default: Do Nothing level 11

Manual Shed 0: Do Nothing Operator input


42888 Level 12 Read/ 1: Shed Level to shed loads Load Add Shed
Command Write assigned to Control
Default: Do Nothing level 12

Manual Shed 0: Do Nothing Operator input


42889 Level 13 Read/ 1: Shed Level to shed loads Load Add Shed
Command Write assigned to Control
Default: Do Nothing level 13

Manual Shed 0: Do Nothing Operator input


42890 Level 14 Read/ 1: Shed Level to shed loads Load Add Shed
Command Write assigned to Control
Default: Do Nothing level 14

Manual Shed 0: Do Nothing Operator input


42891 Level 15 Read/ 1: Shed Level to shed loads Load Add Shed
Command Write assigned to Control
Default: Do Nothing level 15

Manual Shed 0: Do Nothing Operator input


42892 Level 16 Read/ 1: Shed Level to shed loads Load Add Shed
Command Write assigned to Control
Default: Do Nothing level 16

Manual Shed 0: Do Nothing Operator input


42893 Level 17 Read/ 1: Shed Level to shed loads Load Add Shed
Command Write assigned to Control
Default: Do Nothing level 17
Indicates type
0: None of load
1: Breaker
42894 Load 11 Read/ connected to Load Add Shed
Device Type Write 2: ATS load 11 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
1: Breaker
42895 Load 12 Read/ connected to Load Add Shed
Device Type Write 2: ATS load 12 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
1: Breaker
42896 Load 13 Read/ connected to Load Add Shed
Device Type Write 2: ATS load 13 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
1: Breaker
42897 Load 14 Read/ connected to Load Add Shed
Device Type Write 2: ATS load 14 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
1: Breaker
42898 Load 15 Read/ connected to Load Add Shed
Device Type Write 2: ATS load 15 add Control
Default: None shed control
and status I/O

A029X159 (Issue 14) 533


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


Indicates type
0: None of load
1: Breaker
42899 Load 16 Read/ connected to Load Add Shed
Device Type Write 2: ATS load 16 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
1: Breaker
42900 Load 17 Read/ connected to Load Add Shed
Device Type Write 2: ATS load 17 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
1: Breaker
42901 Load 18 Read/ connected to Load Add Shed
Device Type Write 2: ATS load 18 add Control
Default: None shed control
and status I/O
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 11 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42902 Level Offset: 0
Write Upper Limit: 18.000 11 is assigned Control
Size (bits): 0 to
Default: 11
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 12 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42903 Level Offset: 0
Write Upper Limit: 18.000 12 is assigned Control
Size (bits): 0 to
Default: 12
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 13 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42904 Level Offset: 0
Write Upper Limit: 18.000 13 is assigned Control
Size (bits): 0 to
Default: 13
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 14 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42905 Level Offset: 0
Write Upper Limit: 18.000 14 is assigned Control
Size (bits): 0 to
Default: 14
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 15 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42906 Level Offset: 0
Write Upper Limit: 18.000 15 is assigned Control
Size (bits): 0 to
Default: 15
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 16 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42907 Level Offset: 0
Write Upper Limit: 18.000 16 is assigned Control
Size (bits): 0 to
Default: 16
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 17 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42908 Level Offset: 0
Write Upper Limit: 18.000 17 is assigned Control
Size (bits): 0 to
Default: 17
Sign: U

534 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier: Unit: NA
1.000000000000 Indicates which
Load 18 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42909 Level Offset: 0
Write Upper Limit: 18.000 18 is assigned Control
Size (bits): 0 to
Default: 18
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 11 Shed Read/ Lower Limit: .000 shed level load Load Add Shed
42910 Level Offset: 0
Write Upper Limit: 17.000 11 is assigned Control
Size (bits): 0 to
Default: 10
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 12 Shed Read Lower Limit: .000 shed level load Load Add Shed
42911 Level Offset: 0
/Write Upper Limit: 17.000 12 is assigned Control
Size (bits): 0 to
Default: 11
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 13 Shed Read Lower Limit: .000 shed level load Load Add Shed
42912 Level Offset: 0
/Write Upper Limit: 17.000 13 is assigned Control
Size (bits): 16 to
Default: 12
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 14 Shed Read Lower Limit: .000 shed level load Load Add Shed
42913 Level Offset: 0
/Write Upper Limit: 17.000 14 is assigned Control
Size (bits): 16 to
Default: 13
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 15 Shed Read Lower Limit: .000 shed level load Load Add Shed
42914 Level Offset: 0
/Write Upper Limit: 17.000 15 is assigned Control
Size (bits): 16 to
Default: 14
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 16 Shed Read Lower Limit: .000 shed level load Load Add Shed
42915 Level Offset: 0
/Write Upper Limit: 17.000 16 is assigned Control
Size (bits): 16 to
Default: 15
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 17 Shed Read Lower Limit: .000 shed level load Load Add Shed
42916 Level Offset: 0
/Write Upper Limit: 17.000 17 is assigned Control
Size (bits): 16 to
Default: 16
Sign: U
Multiplier: Unit: NA
1.000000000000 Indicates which
Load 18 Shed Read Lower Limit: .000 shed level load Load Add Shed
42917 Level Offset: 0
/Write Upper Limit: 17.000 18 is assigned Control
Size (bits): 16 to
Default: 17
Sign: U

A029X159 (Issue 14) 535


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8 Sets GenI for
Load Demand Read Load Demand
42918 GenI /Write 8: Gen 9 fixed sequence Shed Control
9: Gen 10 load demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen9
0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8 Sets GenJ for Load Demand
Load Demand Read
42919 GenJ /Write 8: Gen 9 fixed sequence Shed Control
9: Gen 10 load demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen10
0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8 Sets GenK for Load Demand
Load Demand Read
42920 GenK /Write 8: Gen 9 fixed sequence Shed Control
9: Gen 10 load demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen11

536 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8 Sets GenL for Load Demand
Load Demand Read
42921 GenL /Write 8: Gen 9 fixed sequence Shed Control
9: Gen 10 load demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen12
0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8 Sets GenM for Load Demand
Load Demand Read
42922 GenM /Write 8: Gen 9 fixed sequence Control
9: Gen 10 load demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen13
0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8 Sets GenN for Load Demand
Load Demand Read
42923 GenN /Write 8: Gen 9 fixed sequence Control
9: Gen 10 load demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen14

A029X159 (Issue 14) 537


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8 Sets GenO for Load Demand
Load Demand Read
42924 GenO /Write 8: Gen 9 fixed sequence Control
9: Gen 10 load demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen15
0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8 Sets GenP for Load Demand
Load Demand Read
42925 GenP /Write 8: Gen 9 fixed sequence Control
9: Gen 10 load demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen16
0: Missing
1: Good Indicates
Read 2: Connecting status of SID2
42926 SID2 Status Communications
Only 3: No Exp Board (aux101/102
4: Not Applicable module 2)
Default:
0: Missing
1: Good Indicates
Read 2: Connecting status of SID3
42927 SID3 Status Communications
Only 3: No Exp Board (aux101/102
4: Not Applicable module 3)
Default:
Indicates the
Expansion 0: Disabled status of the
1: Enabled
42928 Board Read SID2 to Communications
Communication Only 2: Connecting expansion
s2 Default: Disabled board
connection

538 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Indicates the
Expansion 0: Disabled status of the
1: Enabled
42929 Board Read SID3 to Communications
Communication Only 2: Connecting expansion
s3 Default: Disabled board
connection

0: After Transfer Delay PTC - point in


42930 Utility Breaker Read 1: Upon Utility Failure time at which PTC Connected
Opening Point /Write system opens
Default: After Transfer Delay utility breaker
PTC - sets
0: Utility Disconnect point at which
Commit To 1: Genset Start
42931 Transfer Read system PTC Operating
Method /Write 2: No Commit commits to Mode
Default: Utility Disconnect transfer to
generator set
PTC - indicates
0: Not Committed if system is
Commit To Read PTC Operating
42932 Transfer State Only 1: Committed committed to Mode
Default: transferring to
generator set
Multiplier: Unit: kW
1.000000000000 Sum of the
Total System Read Lower Limit: kW generator set System
42933 Capacity 32bit Offset: 0
Only Upper Limit: kW kW ratings in Information
Size (bits): 32 32bit
Default:
Sign: S
Sum of the
Multiplier: Unit: kW generator set
1.000000000000 kW ratings in
Total Online Read Lower Limit: kW System
42935 Capacity 32bit Offset: 0 32bit for
Only Upper Limit: kW Information
Size (bits): 32 generator sets
Default: which are
Sign: S
online
Multiplier: Unit: kW kW control
kW Load 1.000000000000 reference value Master Load
Read Lower Limit: kW
42937 Reference Offset: 0 in 32bit for
Only Upper Limit: kW Control
32bit Size (bits): 3 extended
Default: paralleling
2Sign: S
Multiplier: Unit: kVAR kVAR control
kVAR Load 1.000000000000 reference value Master Load
Read Lower Limit: kVAR
42939 Reference Offset: 0 in 32bit for
Only Upper Limit: kVAR Control
32bit Size (bits): 32 extended
Default: paralleling
Sign: S
Unit: kW
Sets the base
Multiplier: Lower Limit: .000 kW load kW
Genset Bus
42943 kW Setpoint Read 1.000000000000Off Upper Limit: setpoint in Master Load
32bit /Write set: 0Size (bits): 2147483647.000 32bit in closed Control
32Sign: S kW loop extended
paralleling
Default: 0

A029X159 (Issue 14) 539


12. MCM3320 Modbus Register Map 10-2015

Addr. System Name Access Specifications Description Function


Unit: kVAR
Multiplier: Lower Limit: .000 Sets the base
1.000000000000 kVAR load kVAR
Genset Bus Read setpoint in Master Load
42945 kVAR Setpoint Offset: 0 Upper Limit:
/Write 32bit in closed Control
32bit Size (bits): 32 2147483647.000 loop extended
Sign: S kVAR paralleling
Default: 0

Multiplier: Unit: kW
1.000000000000 Lower Limit: - Setpoint for
Genset 2147483648.000 kW
42947 Unloaded Read Offset: 0 generator set Master Load
Level 32bit /Write Upper Limit: unloaded level Control
Size (bits): 32 in 32bit
2147483647.000 kW
Sign: S
Default:50

Multiplier: Unit: kW Sets the peak


1.000000000000 Lower Limit: - shave kW
2147483648.000 kW
42949 Utility Bus kW Read Offset: 0 setpoint in Master Load
Setpoint 32bit /Write Upper Limit: 32bit in closed Control
Size (bits): 32 loop extended
2147483647.000 kW
Sign: S paralleling
Default: 100

Multiplier: Unit: kW sets the utility


1.000000000000 Lower Limit: - kW constraint
Utility Bus kW 2147483648.000 kW
42951 Constraint Read / Offset: 0 level in 32bit Master Load
Level 32bit write Upper Limit: for base load Control
Size (bits): 32 extended
2147483647.000 kW
Sign: S paralleling
Default: 100
Unit: kVAR
Multiplier: Lower Limit: - Sets the peak
1.000000000000 2147483648.000 shave kVAR
Utility Bus kVAR
42953 kVAR Setpoint Read / Offset: 0 setpoint in Master Load
32bit write Upper Limit: 32bit in closed Control
Size (bits): 32 loop extended
2147483647.000
Sign: S kVAR paralleling
Default: 100

Multiplier: Unit: kW
1.000000000000 Lower Limit: -
Utility 2147483648.000 kW Setpoint for
42955 Unloaded Read / Offset: 0 utility unload Master Load
Level 32bit write Upper Limit: level in 32bit Control
Size (bits): 32
2147483647.000 kW
Sign: S
Default: 50
Multiplier: Unit: kW generator set
Load Add Shed 1.000000000000 Lower Limit: .000 kW kW capacity
42957 Required Read / Offset: 0 Upper Limit:
that must be Load Demand
Online write online to start Control
Capacity 32bit Size (bits): 32 2147483647.000 kW timed load add;
Sign: S Default: 0 0 disables this
Sets how much
Multiplier: Unit: kW capacity must
Load Demand 1.000000000000 Lower Limit: .000 kW
Minimum Read / always be Load Demand
42959 Online Offset: 0 Upper Limit: online
write Control
Capacity 32bit Size (bits): 32 2147483647.000 kW regardless of
Sign: S Default: 0 what the load
is

540 A029X159 (Issue 14)


10-2015 12. MCM3320 Modbus Register Map

Addr. System Name Access Specifications Description Function


Multiplier: Unit: kW Use to set how
1.000000000000 Lower Limit: 1.000 kW many kW
42961 Total Utility Read / Offset: 0 Upper Limit:
(32bit) =100% AC Setup
Capacity 32bit write utility kW --
Size (bits): 32 2147483647.000 kW used by
Sign: S Default: 1000 bargraph
Multiplier: Unit: kW Set the online
Genset Online 1.000000000000 Lower Limit: .000 kW kW threshold
Capacity Read / 32bit at which
42963 Sensor write Offset: 0 Upper Limit: generator set PTC Sensors
Threshold 32bit Size (bits): 32 2147483647.000 kW but is available
Sign: S Default: 0 for loading
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW Set minimum
Load Demand Read kW reserve Load Demand
42965 Restart kW Offset: 0 Upper Limit:
/Write capacity when Control
Threshold 32bit Size (bits): 32 2147483647.000 kW kW in 32bit
Sign: S Default: 500
Sets maximum
Multiplier: Unit: kW kW reserve
Load Demand Read / 1.000000000000 Lower Limit: .000 kW capacity when Load Demand
42967 Shutdown kW write Offset: 0 Upper Limit: threshold Control
Threshold 32bit Size (bits): 32 2147483647.000 kw method is
Sign: S Default: 1000 absolute kW in
32bit
Difference
Multiplier: Unit: kW between
Total Spare 1.000000000000 sensed online System
Read Lower Limit: kW
42971 Online Offset: 0 capacity and
Only Upper Limit: kW Information
Capacity 32bit Size (bits): 32 generator Set
Default: bus total kW in
Sign: S
32bit
Multiplier: Shows 32 bit
1.000000000000 Unit: kW kW threshold
Next Gen Lower Limit: kW
42973 Restart Read Offset: 0 for generator Load Demand
Threshold 32bit Only Size (bits): 32 Upper Limit: kW bus at which Control
Default: next generator
Sign: S set will restart
Shows 32 bit
Multiplier: kW threshold
1.000000000000 Unit: kW for generator
Next Gen Lower Limit: kW
42975 Shutdown Read Offset: 0 bus at which Load Demand
Threshold 32bit Only Size (bits): 32 Upper Limit: kW next generator Control
Default: set load
Sign: S demand stops
in
Multiplier: Calculated kW
1.000000000000 Unit: kW overload
Genset Bus Lower Limit: kW
42977 kW Overload Read Offset: 0 threshold in System
Threshold 32bit Only Size(bits): 32 Upper Limit: kW 32bit based on Information
Default: online capacity
Sign: S and % setting

A029X159 (Issue 14) 541


12. MCM3320 Modbus Register Map 10-2015

This page is intentionally blank.

542 A029X159 (Issue 14)


13 MCM3320 Modbus Fault Status
Bitmaps
NOTICE
Earlier versions of software may not support all of the Modbus registers in the following
table. If a particular register is not available in your installation, it is possible that the
Modbus connection is working but the controller software does not support that
particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

Addr. Bit# System Name Fault Event Name Response


Code

42500 0 Fault Status Bitmap 1 1455 Utility Main Breaker Position Contact Warning
Warning
42500 1 Fault Status Bitmap 1 2396 Utility Main Breaker Fail To Close Warning Warning
42500 2 Fault Status Bitmap 1 2397 Utility Main Breaker Fail To Open Warning Warning
42500 3 Fault Status Bitmap 1 1219 Utility Main Breaker Tripped Warning Warning
42500 4 Fault Status Bitmap 1 1914 Utility Bus Phase Rotation Warning Warning
42500 5 Fault Status Bitmap 1 1912 Utility Bus Loss Of Phase Warning Warning
42500 6 Fault Status Bitmap 1 2331 Utility Bus Undervoltage Warning Warning
42500 7 Fault Status Bitmap 1 2358 Utility Bus Overvoltage Warning Warning
42500 8 Fault Status Bitmap 1 1223 Utility Bus Frequency Warning Warning
42500 21 Fault Status Bitmap 1 4137 Advanced Grid Protection Warning Warning
42500 22 Fault Status Bitmap 1 3924 Utility Reverse kW Warning Warning
42500 23 Fault Status Bitmap 1 2939 Modbus Communication Failure Warning Warning
42500 24 Fault Status Bitmap 1 2648 Remote IO Communication Failure Warning Warning
42500 25 Fault Status Bitmap 1 1689 Real Time Clock Power Interrupt Warning Warning
42500 26 Fault Status Bitmap 1 1335 AC Metering Out Of Range Warning Warning
42500 27 Fault Status Bitmap 1 1999 Maximum Parallel Time Warning Warning
42500 28 Fault Status Bitmap 1 343 Hardware Failure Warning Warning
42500 29 Fault Status Bitmap 1 1456 Synchronizer Output Limit Warning Warning
42500 30 Fault Status Bitmap 1 2416 Calibration Checksum Warning Warning
42500 31 Fault Status Bitmap 1 353 EEPROM Write Error Warning Warning

42502 0 Fault Status Bitmap 2 1454 Genset Main Breaker Position Contact Warning
Warning
42502 1 Fault Status Bitmap 2 1452 Genset Main Breaker Fail To Close Warning Warning

A029X159 (Issue 14) 543


13. MCM3320 Modbus Fault Status Bitmaps 10-2015

Addr. Bit# System Name Fault Event Name Response


Code
42502 2 Fault Status Bitmap 2 1453 Genset Main Breaker Fail To Open Warning
42502 3 Fault Status Bitmap 2 1328 Genset Main Breaker Tripped Warning Warning
42502 4 Fault Status Bitmap 2 1915 Genset Bus Phase Rotation Warning Warning
42502 5 Fault Status Bitmap 2 1913 Genset Bus Loss Of Phase Warning Warning
42502 6 Fault Status Bitmap 2 1225 Genset Bus Undervoltage Warning Warning
42502 7 Fault Status Bitmap 2 1224 Genset Bus Overvoltage Warning Warning
42502 8 Fault Status Bitmap 2 1226 Genset Bus Frequency Warning Warning
42502 22 Fault Status Bitmap 2 441 Low Battery Voltage Warning Warning
42502 23 Fault Status Bitmap 2 442 High Battery Voltage Warning Warning
42502 24 Fault Status Bitmap 2 1541 Genset Failed To Come Online Warning Warning
42502 25 Fault Status Bitmap 2 2647 Load Demand Setup Warning Warning
42502 26 Fault Status Bitmap 2 1444 Genset Bus Overload Warning Warning
42502 27 Fault Status Bitmap 2 1989 kW Load Control Output Limit Warning Warning
42502 28 Fault Status Bitmap 2 1991 kVAR Load Control Output Limit Warning Warning
42502 29 Fault Status Bitmap 2 1121 Failure To Disconnect Warning Warning

42502 30 Fault Status Bitmap 2 1458 Synchronizer Phase Rotation Mismatch Warning
Warning
42502 31 Fault Status Bitmap 2 1457 Fail To Synchronize Warning Warning
42504 0 Fault Status Bitmap 1 1222 Not In Automatic Event Event
42504 1 Fault Status Bitmap 1 1483 Common Warning Event Event
42504 2 Fault Status Bitmap 1 2965 Genset Bus Available Event Event
42504 3 Fault Status Bitmap 1 2328 Utility Bus Available Event Event
42504 4 Fault Status Bitmap 1 2333 Genset Bus Connected Event Event
42504 5 Fault Status Bitmap 1 2332 Utility Bus Connected Event Event
42504 6 Fault Status Bitmap 1 2971 Test / Extended Parallel Event Event
42504 7 Fault Status Bitmap 1 1916 Synchronized Event Event
42504 8 Fault Status Bitmap 1 1534 Load Control Output Event Event
42504 9 Fault Status Bitmap 1 2781 Genset Source Unloaded Event Event
42504 10 Event Status Bitmap 1 2779 Utility Source Unloaded Event Event
42504 11 Event Status Bitmap 1 3226 Genset Bus Base Load Event Event
42504 12 Event Status Bitmap 1 3227 Utility Bus Peak Shave Event Event

544 A029X159 (Issue 14)


14 MCM3320 Modbus Address 42506,
42507
NOTICE
Earlier versions of software may not support all of the Modbus registers in the following
table. If a particular register is not available in your installation, it is possible that the
Modbus connection is working but the controller software does not support that
particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

Metering Fault Status Bitmaps


Bit (LSB = 0) Parameter Metering Fault Status Bitmaps
0 ZXA Timeout Zero Crossing cannot be detected on L1 voltage signal
1 ZXB Timeout Zero Crossing cannot be detected on L2 voltage signal
2 ZXC Timeout Zero Crossing cannot be detected on L3 voltage signal
Voltage scaling error due to incompatible combination of
3 (See Note 1) Voltage Out of Range settings for Nominal Voltage, PT Primary Voltage, and PT
Secondary Voltage

4 (See Note 1) Current Out of Range Current Input is saturated; actual current cannot be
determined

5 Frequency Out of Frequency input is out of range; valid range 24-80 Hz


Range

6 Loss Phase Out of One or more zero crossings of voltage cannot be


Range detected; loss phase cannot be determined
Synchronizer phase difference cannot be measured due
Sync Phase Out of to any of the following: genset frequency out of range,
7 Range utility frequency out of range, genset L1 voltage zero
crossing not detected, or utility L1 voltage zero crossing
not detected

8 (See Note 1) kW Out of Range kW is out of range; valid range is - 2147483648 to


+2147483647 kW

9 (See Note 1) kVAR Out of Range kVAR is out of range; valid range is - 2147483648 to
+2147483647 kVAR
10 (See Note 1) kVA Out of Range kVA is out of range; valid range is 0 to 4294867295 kVA

11 (See Note 1) Power Factor Out of Power factor is out of range due to either kW > kVA or
Range kVA = 0; should not normally occur

12 AC Metering Failure Main processor is unable to communicate with metering


processor
13 Not Implemented
14 Not Implemented

A029X159 (Issue 14) 545


14. MCM3320 Modbus Address 42506, 42507 10-2015

Metering Fault Status Bitmaps


Bit (LSB = 0) Parameter Metering Fault Status Bitmaps
15 Not Implemented
NOTE:
1. If any of bits are active (1), the "AC Metering Out of Range Warning" fault
will be active.
2. If Bit 12 is active (1), the "Hardware Failure Warning" fault will be active.
3. Some bits do not generate warning faults because they are a normal occurrence (e.g. if a source is dead).

546 A029X159 (Issue 14)


15 PC500/550 Modbus TCP Register Map
NOTICE
Earlier versions of software may not support all of the Modbus registers in the following
table. If a particular register is not available in your installation, it is possible that the
Modbus connection is working but the controller software does not support that
particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

PC500/550 (PC5xx)

Parameter Modbus Sign Units Comments


Register
Device Type in Configuration 40001 U ENUM 64= PC500/PC550
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40002 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40003 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40004 U ENUM
2=Not Communicating
Communications Error Counter 40005 U
Last Successful Communication
40006 U Bitfield See Note 5
(Year, Month)
Last Successful Communication
40007 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication
40008 U Bitfield See Note 5
(Seconds, Milliseconds)
PC500/550 (Device 1)

Parameter Modbus Sign Units Comments


Register
Device Type in Configuration 40011 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40012 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40013 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40014 U ENUM
2=Not Communicating
Communications Error Counter 40015 U
Last Successful Communication
40016 U Bitfield See Note 5
(Year, Month)

A029X159 (Issue 14) 547


15. PC500/550 Modbus TCP Register Map 10-2015

Last Successful Communication


40017 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication
40018 U Bitfield See Note 5
(Seconds, Milliseconds)
PC500/550 (Device 2)

Parameter Modbus Sign Units Comments


Register
Device Type in Configuration 40021 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40022 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40023 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40024 U ENUM
2=Not Communicating
Communications Error Counter 40025 U
Last Successful Communication
40026 U Bitfield See Note 5
(Year, Month)
Last Successful Communication
40027 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40028 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 3)

Parameter Modbus Sign Units Comments


Register
Device Type in Configuration 40031 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40032 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40033 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40034 U ENUM
2=Not Communicating
Communications Error Counter 40035 U
Last Successful Communication
40036 U Bitfield See Note 5
(Year, Month)
Last Successful Communication
40037 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication
40038 U Bitfield See Note 5
(Seconds, Milliseconds)
PC500/550 (Device 4)

Parameter Modbus Sign Units Comments


Register
Device Type in Configuration 40041 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40042 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40043 U Configurable from User Interface

548 A029X159 (Issue 14)


10-2015 15. PC500/550 Modbus TCP Register Map

0=Communicating,
Modbus Communication Status 40044 U ENUM
2=Not Communicating
Communications Error Counter 40045 U
Last Successful Communication
40046 U Bitfield See Note 5
(Year, Month)
Last Successful Communication
40047 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication
40048 U Bitfield See Note 5
(Seconds, Milliseconds)
PC500/550 (Device 5)

Parameter Modbus Sign Units Comments


Register
Device Type in Configuration 40051 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40052 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40053 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40054 U ENUM
2=Not Communicating
Communications Error Counter 40055 U
Last Successful Communication See Note 5
40056 U Bitfield
(Year, Month)
Last Successful Communication See Note 5
40057 U Bitfield
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40058 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 6)

Parameter Modbus Sign Units Comments


Register
Device Type in Configuration 40061 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40062 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40063 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40064 U ENUM
2=Not Communicating
Communications Error Counter 40065 U
Last Successful Communication See Note 5
40066 U Bitfield
(Year, Month)
Last Successful Communication See Note 5
40067 U Bitfield
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40068 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 7)

A029X159 (Issue 14) 549


15. PC500/550 Modbus TCP Register Map 10-2015

Parameter Modbus Sign Units Comments


Register
Device Type in Configuration 40071 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40072 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40073 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40074 U ENUM
2=Not Communicating
Communications Error Counter 40075 U
Last Successful Communication See Note 5
40076 U Bitfield
(Year, Month)
Last Successful Communication See Note 5
40077 U Bitfield
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40078 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 8)

Parameter Modbus Sign Units Comments


Register
Device Type in Configuration 40081 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40082 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40083 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40084 U ENUM
2=Not Communicating
Communications Error Counter 40085 U
Last Successful Communication See Note 5
40086 U Bitfield
(Year, Month)
Last Successful Communication See Note 5
40087 U Bitfield
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40088 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 9)

Parameter Modbus Sign Units Comments


Register
Device Type in Configuration 40091 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40092 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40093 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40094 U ENUM
2=Not Communicating
Communications Error Counter 40095 U
Last Successful Communication See Note 5
40096 U Bitfield
(Year, Month)

550 A029X159 (Issue 14)


10-2015 15. PC500/550 Modbus TCP Register Map

Last Successful Communication See Note 5


40097 U Bitfield
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40098 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 10)

Parameter Modbus Sign Units Comments


Register
Device Type in Configuration 40101 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40102 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40103 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40104 U ENUM
2=Not Communicating
Communications Error Counter 40105 U
Last Successful Communication See Note 5
40106 U Bitfield
(Year, Month)
Last Successful Communication See Note 5
40107 U Bitfield
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40108 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 11)

Parameter Modbus Sign Units Comments


Register
Device Type in Configuration 40111 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40112 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40113 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40114 U ENUM
2=Not Communicating
Communications Error Counter 40115 U
Last Successful Communication See Note 5
40116 U Bitfield
(Year, Month)
Last Successful Communication See Note 5
40117 U Bitfield
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40118 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 12)

Parameter Modbus Sign Units Comments


Register
Device Type in Configuration 40121 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40122 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40123 U Configurable from User Interface

A029X159 (Issue 14) 551


15. PC500/550 Modbus TCP Register Map 10-2015

0=Communicating,
Modbus Communication Status 40124 U ENUM
2=Not Communicating
Communications Error Counter 40125 U
Last Successful Communication See Note 5
40126 U Bitfield
(Year, Month)
Last Successful Communication See Note 5
40127 U Bitfield
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40128 U Bitfield
(Seconds, Milliseconds)
NOTES:
1. Modbus TCP can be enabled/disabled in the PC500/550 User Interface (Setup > Modbus Settings).
2. Default Modbus TCP port is 502 and is configurable in the PC500/550 User Interface (Setup > Modbus Settings).
No more than 2 Modbus TCP sessions can be established at a time.
3. PC5xx provides READ ONLY access over Modbus TCP.
4. PC500/550 registers return details about all configured devices in PC5xx (Generator Set, ATS, AUX101/102) and
can be accessed using Modbus TCP Unit ID 255 (default for PC500/550).
5. In PC500/550 registers, Devices 1 through 12 are numbered in the same order as they are arranged in the
Interface Device Configuration grid. To access details of these devices over Modbus TCP, the user must use the
Modbus TCP Unit ID (returned by register 4xxx3) in the query.
6. Bitmap registers indicating Last Successful Communication (4xxx6, 4xxx7, 4xxx8) are formatted as below:

7. Site IOs (sensors) and AUX101/102 data cannot be accessed over Modbus TCP.

Generator Set
Modbus Scale Sign Units Description Comments
Register
40001 1 U ENUM Switch Position 0=Off, 1=AUTO, 2=Manual
0=Stopped, 1=Pending, 2=Warm
Up, 3=Running, 4=Cool Down
40002 1 U ENUM Control State (rated),
5=Cool Down (idle)
40003 1 U Fault Code
0=Normal, 1=Warning,
2=Derate,
40004 1 U ENUM Fault Type
3=Shutdown w/Cooldown,
4=Shutdown
40005 1 U Bitfield NFPA110 See Table 2 on page 379
40006 1 U Bitfield NFPA Extended See Table 3 on page 379
40007 1 U Volts L1N Voltage
40008 1 U Volts L2N Voltage
40009 1 U Volts L3N Voltage

552 A029X159 (Issue 14)


10-2015 15. PC500/550 Modbus TCP Register Map

Generator Set
Modbus Scale Sign Units Description Comments
Register
40010 1 U Volts L1L2 Voltage
40011 1 U Volts L2L3 Voltage
40012 1 U Volts L3L1 Voltage
40013 1 U Amps L1 Current
40014 1 U Amps L2 Current
40015 1 U Amps L3 Current
40016 1 S kVA Total kVA
40017 0.01 U Hz Frequency
40018 0.1 U % PercentAmps APhase
40019 0.1 U % PercentAmps BPhase
40020 0.1 U % PercentAmps CPhase
40021 1 S kW Total kW
40022 0.01 S Total Power Factor
40023 0.01 S Volts Battery Voltage
40024 0.1 S psi Oil Pressure
40025 0.1 S _F Oil Temperature
40026 0.1 S _F Coolant Temperature
40027 1 U GPH Fuel Rate
40028 0.1 U Gallons Fuel Level
40029 1 U RPM Average Engine Speed
40030 1 U Engine Starts
40031 0.1 U Hours Engine Runtime

ATS
Modbus Scale Sign Units Description Comments
Register
0=Test 1=Utility/Genset,
40001 1 U ENUM Mode 2=Utility/Utility,
3=Genset/Genset
0=None,
1=EngineStartASource2,
2=EngineStartBSource1,
3=NormaltoEmergency (TDNE),
4=EmergencytoNormal (TDEN),
40002 1 U ENUM Active Transfer Timer 5=EngineCooldownA (TDECa),
6=EngineCooldownB (TDECb),
7=ProgramTransition (TDPT),
8=Transfer Pend./Elevator
(TDEL),
255=Unknown

A029X159 (Issue 14) 553


15. PC500/550 Modbus TCP Register Map 10-2015

ATS
Modbus Scale Sign Units Description Comments
Register
40003 1 U Fault Code
40004 1 U ENUM Fault Type 0=No Faults, 1=Warning
40005 1 U Bitfield NFPA110 See Table 4 on page 380
40006 1 U Bitfield NFPA Extended See Table 5 on page 380
40007 1 U Volts L1N Voltage (Load)
40008 1 U Volts L2N Voltage (Load)
40009 1 U Volts L3N Voltage (Load)
40010 1 U Volts L1L2 Voltage (Load)
40011 1 U Volts L2L3 Voltage (Load)
40012 1 U Volts L3L1 Voltage (Load)
40013 1 U Amps L1 Current (Load)
40014 1 U Amps L2 Current (Load)
40015 1 U Amps L3 Current (Load)
40016 1 S kW Total kW (Load)
40017 0.01 S Total Power Factor (Load)
40018 1 S kVAR Total kVAR (Load)
40019 1 S kVA Total kVA (Load)
40020 0.01 U Hz Frequency (Load)
40021 0.1 U % PercentAmps APhase (Load)
40022 0.1 U % PercentAmps BPhase (Load)
40023 0.1 U % PercentAmps CPhase (Load)
40024 1 U Volts L1N Voltage Source1
40025 1 U Volts L2N Voltage Source1
40026 1 U Volts L3N Voltage Source1
40027 1 U Volts L1L2 Voltage Source1
40028 1 U Volts L2L3 Voltage Source1
40029 1 U Volts L3L1 Voltage Source1
40037 0.01 U Hz Frequency Source1
40041 1 U Volts L1N Voltage Source2
40042 1 U Volts L2N Voltage Source2
40043 1 U Volts L3N Voltage Source2
40044 1 U Volts L1L2 Voltage Source2
40045 1 U Volts L2L3 Voltage Source2
40046 1 U Volts L3L1 Voltage Source2
40054 0.01 U Hz Frequency Source2

554 A029X159 (Issue 14)


16 AUX101/102 Modbus Register Map
NOTICE
Earlier versions of software may not support all of the Modbus registers in the following
table. If a particular register is not available in your installation, it is possible that the
Modbus connection is working but the controller software does not support that
particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

Addr. System Access Specifications Comments


Name

Default: Modbus Changing the address causes no


43044 Modbus Read As supported by Address 13 communication with the annunciator
Device ID Only Modbus protocol until the Modbus Master also
Type: Trim changes its sending address.
0: 2400 Baud
1: 4800 Baud
Changing the baud rate causes no
2: 9600 Baud Default: 3
43045 Modbus Read communication with the annunciator
Baud Rate Only 3: 19200 Baud Type: Trim until the Modbus Master also
changes its baud rate.
4: 38400 Baud
5: 57600 Baud
0: Even Changing the parity causes no
Modbus Read Default: 2 communication with the annunciator
43046 Parity Only 1: Odd until the Modbus Master also
Type: Trim
2: None changes its parity.

1 Changing the stop bits causes no


Default: 1
43047 Modbus Read communication with the annunciator
Stop Bits Only 2 Type: Trim until the Modbus Master also
changes its stop bits.
Changes the communication
Read 0: RS485 Default: 0 protocol between RS485 and
43048 Protocol Modbus.
Only Type: Trim
1: Modbus
Default: NA
43049 Software Read Sends AUX101 current firmware
Version Only Type: Trim version.
Default: 59
43050 Device Read AUX101 Device Type
Type Only Type: Trim
0: Not Available Default: 0
43051 AUX 102 Read Indicates if AUX102 expansion
Available Only 1: Available Type: Trim board is available.

A029X159 (Issue 14) 555


16. AUX101/102 Modbus Register Map 10-2015

Addr. System Access Specifications Comments


Name
0: Do Nothing Save configuration parameters or
adjustments to non-volatile
Do Nothing
43052 Save Trims Read/ memory. Perform Save Trims after
Write 1: Save Trims Type: Trim all configurations have been
updated. Do not save trims unless
a change has occurred.
Relay 1
Relay 2 Parameters to allow the Relay to be
turned on/off. The lower 8 bits are
Relay 3 used to store out relay values.
Relay 1 is stored in bit 0 and Relay
Relay 4 Read/ 0: Inactive 8 is stored in bit 7. The upper 8 bits
42001 Default: 0
Relay 5 Write 1: Active are 0. In the event of a power cycle
or reboot, all the output values are
Relay 6 reset to 0. This register is used as
heartbit for AUX101 and indicates a
Relay 7 secure communication.
Relay 8
Relay 9
Relay 10
Relay 11
Relay 12 Read/ 0: Inactive Parameters to allow the Relay to be
42009 Default: 0
Relay 13 Write 1: Active turned on/off.

Relay 14
Relay 15
Relay 16

42017 Input 1 Read Default: NA Register that contains the value of


Only Input 1.

42018 Input 2 Read Default: NA Register that contains the value of


Only Input 2.

42019 Input 3 Read Default: NA Register that contains the value of


Only Input 3.

42020 Input 4 Read Default: NA Register that contains the value of


Only Input 4.

42021 Input 5 Read Default: NA Register that contains the value of


Only Input 5.

42022 Input 6 Read Default: NA Register that contains the value of


Only Input 6.

42023 Input 7 Read Default: NA Register that contains the value of


Only Input 7.

42024 Input 8 Read Default: NA Register that contains the value of


Only Input 8.

556 A029X159 (Issue 14)


10-2015 16. AUX101/102 Modbus Register Map

Addr. System Access Specifications Comments


Name

Input 9 Bit 0 of this register is used for


Input 9 when AUX102 is available.

Input 10 Bit 1 of this register is used for


Read Input 10 when AUX102 is available.
42025 Default: NA
Only Bit 2 of this register is used for
Input 11
Input 11 when AUX102 is available.

Input 12 Bit 3 of this register is used for


Input 12 when AUX102 is available.
Current Read/ Default: NA
42029 Source 1 Write mA = CS/10 Set for Analog Input 3.
Settings Type: Trim

Current Read/ Default: NA


42030 Source 2 Write mA = CS/10 Set for Analog Input 4.
Settings Type: Trim

Current Read/ Default: NA


42031 Source 3 Write mA = CS/10 Set for Analog Input 5.
Settings Type: Trim

Current Read/ Default: NA


42032 Source 4 Write mA = CS/10 Set for Analog Input 6.
Settings Type: Trim

0: Sender
Input 1 Read/ Default: NA
42033 Settings Write 1: Switch - Active Low Register to configure Input 1.
Type: Trim
2: Switch - Active High
0: Sender
Input 2 Read/ Default: NA
42034 Settings Write 1: Switch - Active Low Register to configure Input 2.
Type: Trim
2: Switch - Active High
0: Sender
Input 3 Read/ Default: NA
42035 Settings Write 1: Switch - Active Low Register to configure Input 3.
Type: Trim
2: Switch - Active High
0: Sender
Input 4 Read/ Default: NA
42036 Settings Write 1: Switch - Active Low Register to configure Input 4.
Type: Trim
2: Switch - Active High
0: Sender
Input 5 Read/ Default: NA
42037 Settings Write 1: Switch - Active Low Register to configure Input 5.
Type: Trim
2: Switch - Active High
0: Sender
Input 6 Read/ Default: NA
42038 Settings Write 1: Switch - Active Low Register to configure Input 6.
Type: Trim
2: Switch - Active High
0: Sender
Input 7 Read/ Default: NA
42039 Settings Write 1: Switch - Active Low Register to configure Input 7.
Type: Trim
2: Switch - Active High

A029X159 (Issue 14) 557


16. AUX101/102 Modbus Register Map 10-2015

Addr. System Access Specifications Comments


Name
0: Sender
Input 8 Read/ Default: NA
42040 Settings Write 1: Switch - Active Low Register to configure Input 8.
Type: Trim
2: Switch - Active High

558 A029X159 (Issue 14)


power.cummins.com
Copyright © 2015 Cummins Power Generation Inc. All rights reserved.
Cummins Power Generation, the "C" logo, and Cummins are registered
trademarks of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our
energy working for you.” are trademarks of Cummins Power Generation.
Other company, product, or service names may be trademarks or service
marks of others. Specifications are subject to change without notice.