You are on page 1of 11

Commissioning Service Department

Commissioning Standard Test Formats


Description: FUNCTIONAL TEST – FEEDER Record No.:
Bay no.: Drawing ref.: Sheet: 1 of 11
Contractor: Contract no.: Substation No :

As Per the Schematic drawings the contents in this Test format can be modified

Note: The following should be done before starting the activity


1. Approved commissioning copy schematic drawing shall be pre-checked.
2. All secondary injection and all components tests shall be completed and witnessed.all test results
must be available and signed.
3. Auxiliaries, timers, contactors, pulse units, annunciators, MCB’s … etc.
4. All final settings shall be applied and signed

1. GENERAL DATA AND INFORMATION:

Panel designation
Manufacture

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: FUNCTIONAL TEST – FEEDER Record No.:
Bay no.: Drawing ref.: Sheet: 2 of 11
Contractor: Contract no.: Substation No :

2. MECHANICAL CHECK AND VISUAL INSPECT As per TCS–P-105 Rev - 1, Item no 4.1

Item Description Checked


1 Check tightness of all connections Yes N/A
2 Inspect for physical damage / defects Yes N/A
3 Panel condition, cleanliness, organization, labeling, readiness for service, panel doors, Yes N/A
handles...etc
4 CT shorting checked Yes N/A
5 Indications checked Yes N/A
6 Contact resistance of tripping and alarm checked Yes N/A
7 Check the ferrules as per specification Yes N/A
8 Confirm that each panel has been properly secured to the floor in its final service location. Yes N/A
9 Confirm that panels are constructed and wired as per SEC relevant specification. Yes N/A
10 Panel earthing checked Yes N/A
11 Check case cover and gasket for proper seal against dust. Yes N/A
12 Check all installed equipment nameplate information for compliance to approved drawings Yes N/A
and equipment /material lists.
13 For all internal and external panel wiring, confirm that all screw terminations are tight and that Yes N/A
crimp connectors are firmly secured to the wire and to the termination point. Ensure that no
part of the wire is bent at the termination point. Check Ferrules.
14 Check that panel equipment is mounted securely and protected against mal operation due to Yes N/A
vibration, shock, etc
Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: FUNCTIONAL TEST – FEEDER Record No.:
Bay no.: Drawing ref.: Sheet: 3 of 11
Contractor: Contract no.: Substation No :

15 Use of ring type terminals for wire termination for current circuit wires. Yes N/A
3. GENERAL FUNCTIONAL CHECK As per TCS–P-105 Rev - 1, Item no 5.1

Item Description Checked


1. Check Output Of 127v Ac Outlet Yes N/A
2. Check Output Of 220v Ac Outlet Yes N/A
3. Check Function Of Illumination Lamp Yes N/A
4. Check Function Of Door Switch Yes N/A
5. Check Function Of Heater Yes N/A

4. D.C. LOOP:

Measuring
S no X ---- : ---- , --- X ---- : ---- , --- X ---- : ---- , -- X ---- : ---- , ---
points in MCB
1
2
3
4
5
6
7

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: FUNCTIONAL TEST – FEEDER Record No.:
Bay no.: Drawing ref.: Sheet: 4 of 11
Contractor: Contract no.: Substation No :

Relay panel ----------- Control panel -- Fault Recorder IT Send CB operation FMK -
Protection
Trip CBF IT Ind /flag Close Remarks
operated CH Alarms CH Event 85 S/R Trip T.B
relay start send Relay Block
87 C cable 87 C FR ----
86 50 / 62 85 Main prtn Check close
diff prtn CH -- FMP optd --------
PW BF S/R 86 PW optd CH ---- TC 1 --------- X--:--,- LK
optd
51 /51N BK 51 / 51 N FR ---- O/C +
86 50 / 62 85 Bk up prtn Check close
up O/C + CH - E/F prtn
BU BF S/R 86 BU optd CH ---- ------- TC 2 --------- X--:--,- LK
E/F prtn optd
85 S/R FR ----
IT Rcv 50 / 62 IT RCV IT Rcv 85
------ ------ CH - TC 1
85S/R BF optd CH ---- S/R ------- --------- X--:--,- -----------
-------- &TC2
86
50 / 62 BF 50 / 62 85 50/62 BF CBF prtn FR ---- CBF prtn Check close
RTR CH -- ------- TC 1
prtn BF S/R optd optd -------- X--:--,- LK
86 B 86 RTR CH ---- &TC2
------ Switch
----------
86B B/B 50 / 62 85 ------- (in/out)
86 B --------- TC 1
prtn trip BF S/R - ------ --------- --------- -------- X--:--,--- “out”
&TC2
86B Position
86 Switch
86 RTR ------
86B B/B RTR 50 / 62 85 ------- (in/out)“in
--------- TC 1
prtn trip BF S/R - --------- --------- -------- X--:--,- ”
86 B 86 B ----- &TC2
Position

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: FUNCTIONAL TEST – FEEDER Record No.:
Bay no.: Drawing ref.: Sheet: 5 of 11
Contractor: Contract no.: Substation No :

Relay panel Control panel FMK


Function as
Event ------ ------- ---- Remark
expected
IND / Flag relay Channel Alarms TB
Main protection
74 R1
Breaking path of supervision faulty
X ----: ----.--
circuit R1 CH ---- Inter Trip Send / ( ) Yes
R1 DC supply fail
Rcv Faulty
Breaking path of supervision 74 R2 Back up prot
X ----: ----.--
circuit R2 R2 DC supply fail CH ---- Faulty ( ) Yes
Breaking path of supervision 74 IT Inter trip DC supply
X ----: ----.--
circuit IT IT DC supply fail CH ---- failed ( ) Yes
Breaking path of supervision 74 BF CBF protection
X ----: ----.--
circuit CBF CBF DC supply fail CH ---- faulty ( ) Yes
Breaking path of supervision 74 TC1
CH ---- Trip circuit -1 faulty X ----: ----.--
circuit TC 1 Trip ckt -1 faulty ( ) Yes
Breaking path of supervision 74 TC2
CH ---- Trip circuit -2 faulty X ----: ----.--
circuit TC 2 Trip ckt -1 faulty ( ) Yes
74 TRS
Relay Reset supply TRS CH ---- Control supply failed X ----: ----.-- ( ) Yes
Trip ckt – 2 faulty
74 IC at ------ CH ---- Control supply failed X ----: ----.-- ( ) Yes
Relay Indication supply IC
Indication supply CH ---- Control supply failed X ----: ----.-- ( ) Yes

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: FUNCTIONAL TEST – FEEDER Record No.:
Bay no.: Drawing ref.: Sheet: 6 of 11
Contractor: Contract no.: Substation No :

Relay panel ------ Control panel ------- FMK ---- Function as


Event Remarks
IND / FLAG relay Channel Alarms TB expected
CH ---- Optical line system failed
Optical cable system Main protection faulty Remove fiber
87 C /85 S/R X ----: ----.--- ( ) Yes
failed CH ---- Inter trip send/Rcv faulty optic cable
Main protection faulty
Main protection faulty
74 R1 CH ---- Inter trip send/Rcv faulty X ----: ----.--- MCB off ( ) Yes
Back up protection
51 / 51N faulty 74 R2 CH ---- X ----: ----.--- MCB off ( ) Yes
Faulty
IT send relay DC off 74 IT CH ---- Inter trip dc supply faulty X ----: ----.--- MCB off ( ) Yes
CBF protection faulty 74 BF CH ---- Cbf protection faulty X ----: ----.--- MCB off ( ) Yes
Synchro check relay Closing LCC supply Synchro check relay
CH ---- X ----: ----.--- -------------- ( ) Yes
faulty off Faulty
Switch off DC supply Main protection faulty ( ) Yes
R1 DC supply fail CH ---- -------------- --------------
fail MCB R1 Inter trip send/Rcv faulty ( ) Yes
Switch off DC supply Back up protection
R2 DC supply fail CH ---- ------------- -------------- ( ) Yes
fail MCB R2 Faulty
Switch off IT DC supply
IT DC supply fail CH ---- Inter trip dc supply faulty ------------- -------------- ( ) Yes
fail MCB
CBF DC supply MCB off
CBF DC supply fail CH ---- Cbf protection faulty ------------- -------------- ( ) Yes
in BBCH panel

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: FUNCTIONAL TEST – FEEDER Record No.:
Bay no.: Drawing ref.: Sheet: 7 of 11
Contractor: Contract no.: Substation No :

5. OPERATIONAL CHECK:
Local / Remote Switch in local position, no operation from CR & ECC for all equipments is O.K ( ) or Not O.K ( )
From control Remarks
LCC D----- From ----+
panel (k----) Device operated Command Flickering Operation as
FMK----- Indications
Local/ Remote CR/ ECC operation expected
Remote CR Disconnector ----06 Close
Remote ECC Disconnector ----06 Close
Remote CR Disconnector ---- 06 Open
Remote ECC Disconnector ----06 Open
Remote CR Disconnector ---- 04 Close
Remote ECC Disconnector ---- 04 Close
Remote CR Disconnector -----04 Open
Remote ECC Disconnector -----04 Open
Remote CR Line Disconnector----03 Close
Remote ECC Line Disconnector ---03 Close
Remote CR Line Disconnector ---03 Open
Remote ECC Line Disconnector ---03 Open
Remote CR Line earth switch -----01 Close -
Remote CR Line earth switch ---- 01 Open -
Remote CR Circuit breaker ----- 05 (Test & service position) Close -
Remote ECC Circuit Breaker ----05 (service position) Close -
Remote CR Circuit Breaker -----05 (test & service position) Open -
Remote ECC Circuit Breaker -------05 (service position) Open -

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: FUNCTIONAL TEST – FEEDER Record No.:
Bay no.: Drawing ref.: Sheet: 8 of 11
Contractor: Contract no.: Substation No :

Remarks
LCC D --- Device operated Command
Semaphore indications Operation as expected
Operate from LCC Earth Switch -----01X Close
Operate from LCC Earth Switch -----01X Open
Operate from LCC Earth Switch ------01Y Close
Operate from LCC Earth Switch ------01Y Open
Operate from LCC Earth Switch -------01Z Close
Operate from LCC Earth Switch -------01Z Open
Operate from LCC VT isolator ----------93 Close
Operate from LCC VT isolator ----------93 Open

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: FUNCTIONAL TEST – FEEDER Record No.:
Bay no.: Drawing ref.: Sheet: 9 of 11
Contractor: Contract no.: Substation No :

6. CIRCUIT BREAKER CLOSE BLOCK CHECK


Control panel
Synchronism check Circuit Breaker Close Blocking Protection Operation of circuit
(K---)
CB breaker
By syn. Main Back-up CBF Bus bar Remarks
position By Manual
CR/ECC Relay protn protn. protn. protn
switch To Expected
------ ------ --------- -------- --------
CR Test - - - - - - Close Close
CR Test - - - - - - Open Open
CR Service On Close N/o N/o N/o N/o Close Close
CR Service Off Close N/o N/o N/o N/o Close Not close
CR Service On Open N/o N/o N/o N/o Close Not close
CR Service On Close O N/o N/o N/o Close Not close
CR Service On Close N/o O N/o N/o Close Not close
CR Service On Close N/o N/o O N/o Close Not close
CR Service On Close N/o N/o N/o O Close Not close
ECC Test - - - - - - Close Not close
ECC Test - - - - - - Open Not open
ECC Service Off Close N/o N/o N/o N/o Close Close
ECC Service Off Open N/o N/o N/o N/o Close Not close
ECC Service Off Close O N/o N/o N/o Close Not close
ECC Service Off Close N/o O N/o N/o Close Not close
ECC Service Off Close N/o N/o O N/o Close Not close
ECC Service Off Close N/o N/o N/o O Close Not close
Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: FUNCTIONAL TEST – FEEDER Record No.:
Bay no.: Drawing ref.: Sheet: 10 of 11
Contractor: Contract no.: Substation No :

Note: N/o - not operated O – operated

7. CIRCUIT BREAKER TRIP CIRCUIT (TC-1) CHECK:

Circuit breaker Main protn Busbar protn. Inter-trip received Operation Remarks
position ----------- -------------- --------------- Expected Operated
Test/service Trip
Test/service Trip
Test/service Trip

8. CIRCUIT BREAKER TRIP CIRCUIT(T C-2) CHECK:

Circuit Bk / up Operation Remarks


Bus bar protn. Inter-trip received
breaker protn.
--------------- -------------- Expected Operated
position ----------
Test/service Trip
Test/service Trip
Test/service Trip

Note: N/o - not operated O – operated

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: FUNCTIONAL TEST – FEEDER Record No.:
Bay no.: Drawing ref.: Sheet: 11 of 11
Contractor: Contract no.: Substation No :

9. ANNUNCIATION ALARM CHECK

FMK------
Alarm Event K----- control panel(ann1) Indication Remarks
panel(TB)

Note: *Checked by Multi-meter

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date: