TECHNICAL SPECIFICATION A5LCY-I(F)_(i)-0003

Supercedes:
A5LCY-I(F)_(i)-0002

Model Name
Models : Indoor Outdoor
A5WMY10LR A5LCY10FR
Heatpump
A5WMY15LR A5LCY15FR
TECHNICAL SPECIFICATION A5LCY-I(F)_(i)-0003

Content Page

Nomenclature ---------------------------------------- 1
- Product Line-up 2
Application Information ---------------------------------------- 3
- Operating Range 3
- Refrigeration Circuit 4
Sound Data ---------------------------------------- 5
- Sound Pressure Level 5
Engineering and Physical
---------------------------------------- 6
Data
Outline and Dimension ---------------------------------------- 8
Wiring Diagrams ---------------------------------------- 10
Error Code ---------------------------------------- 11
Part List ---------------------------------------- 19

Installation and maintenance are to be performed only by qualified personnel who


Note: are familiar with local codes and regulation, and experienced with this type of
equipment
Caution : Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them

Moving machinery and electrical power hazard may cause severe personnel injury or
Warning :
death. Disconnect and lock off power before servicing equipment

“Acson” is a registered trademark of Acson International. All rights reserved.


© 2011 Acson International. All rights reserved throughout the world.
Bulletin illustrations cover the general appearance of Acson International products at the time of publication.
We reserve the right to change design and construction specification at any time without notice
TECHNICAL SPECIFICATION A5LCY-I(F)_(i)-0003

Nomenclature
Indoor

A 5 WM Y 10 L R – A C B D D
Product Specification
Brand Variation
A: Acson D: Fourth Issue

Refrigerant Grille
“ ”: R22 D: Grille D
4: R407C
5: R410A
Type of Air Filter
B: Bio Filter
Product Type
WM: Wall Mounted
Market Region
C: Export with CE Marking
Inverter System Type
Y: Y Series Electrical Characteristics
A : 50Hz / 1Ph / 220-240V
Size F : 50Hz / 3Ph / 380-415V
10 : 10,000 Btu/h
15 : 15,000 Btu/h
Model
Product series “ ”: Cooling Only
L: L Series R: Heat Pump

Outdoor

A 5 LC Y 10 F R – A C D O A
Product Specification
Brand Variation
A: Acson A: First Issue

Refrigerant Specifications Variation


“ ”: R22 O: Standard Unit
4: R407C
5: R410A
Compressor
D: Daikin
Product Type
LC: Single Split Condensing Unit
Market Region
C: Export with CE Marking
Inverter System Type
Y: Y Series Electrical Characteristics
A : 50Hz / 1Ph / 220-240V
Size F : 50Hz / 3Ph / 380-415V
10 : 10,000 Btu/h
15 : 15,000 Btu/h
Model
Product series “ ”: Cooling Only
F: F Series R: Heat Pump

1
HEAT
PUMP HEAT
PUMP

2
A5LCY

15FR
10FR
15LR
10LR
A5WMY
Indoor Unit

Outdoor Unit
Nomenclature

ACDOA
ACDOA
A5LCY-F Series
Product Line Up

A5WMY-L Series

X
X
2P257375-1 Nomenclature
PCB

ACBDD
ACBDD
Cap Tube

X
X
Refrigerant APGS02
Control Handset

X
X
EXV

Gold Coated

X
X
W_2_03A

X
X
Blue Coated FIN PCB
Bare Fin

X
X
Overload Relay
Saranet Filter
HP Safety Devices
Air
X
X
Bio Filter
Purification
LP

Classification
TECHNICAL SPECIFICATION

Nano Technology
Classification

X
X

DC Inverter Swing Air Filtration

X
X
Compressor
Compressor
X
X

DC Inverter Scroll CE
Marking
Compressor

X
X
CE
Marking
X
X

Auto Restart
A5LCY-I(F)_(i)-0003

Others

Others
TECHNICAL SPECIFICATION A5LCY-I(F)_(i)-0003

Application Information
Operating Range

Ensure the operating temperature is in allowable range.

Heatpump

3
TECHNICAL SPECIFICATION A5LCY-I(F)_(i)-0003

Refrigerant Circuit Diagram

Model: A5WMY10LR – A5LCY10FR A5WMY15LR – A5LCY15FR

70014113878

4
TECHNICAL SPECIFICATION A5LCY-I(F)_(i)-0003

Sound Data
Sound Pressure Level

Model Speed 1/1 Octave A-Weighted Sound Pressure (dBA), ref 20µPa Overall Noise
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA) Criteria
A5WMY10LR Turbo 43 39 37 37 33 26 13 41 36
High 42 38 37 36 32 24 12 40 35
Medium 37 33 32 30 25 17 13 34 29
Low 32 29 28 24 19 14 13 29 22
Quiet 21 22 20 15 10 7 8 21 -
A5WMY15LR Turbo 41 39 38 38 36 29 15 42 37
High 40 38 38 37 34 27 14 41 36
Medium 36 32 32 30 26 18 11 34 29
Low 33 29 29 25 21 15 11 30 23
Quiet 24 22 21 17 11 7 7 22 -
010102000WMY-L
SOUND PRESSURE LEVEL ARE TESTED ACCORDING TO JIS C 9612 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE UNIT.

5
TECHNICAL SPECIFICATION A5LCY-I(F)_(i)-0003

Engineering and Physical Data


INDOOR UNIT A5WMY10LR A5WMY15LR
MODEL
OUTDOOR UNIT A5LCY10FR A5LCY15FR
Btu/h 8700 (4400~10200) 11000 (4400~13000)
NOMINAL COOLING CAPACITY
W 2550 (1300~3000) 3230 (1300~3800)
Btu/h 9700 (4400~13600) 11900 (4400~16400)
NOMINAL HEATING CAPACITY
W 2840 (1300~4000) 3500 (1300~4800)
NOMINAL TOTAL INPUT POWER (COOLING) W 730 (290 ~ 1030) 970 (290 ~ 1360)
NOMINAL TOTAL INPUT POWER (HEATING) W 700 (270 ~ 1280) 930 (310 ~ 1520)
NOMINAL RUNNING CURRENT (COOLING) A 4.06 (1.68 ~ 4.99) 4.68 (1.68 ~ 6.39)
NOMINAL RUNNING CURRENT (HEATING) A 3.86 (2.16 ~ 6.05) 5.12 (1.80~ 7.11)
EER W/W 3.49 3.33
COP W/W 4.06 3.76
REFRIGERANT CONTROL (EXPANSION DEVICE) EXV
REFRIGERANT CHARGE kg 0.74 1.00
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50
REFRIGERANT TYPE R410A
AIR DISCHARGE AIR SWING LOUVER
CONTROL
OPERATION WIRELESS HANDSET
TURBO l/s / CFM 178 / 378 185 / 392
HIGH l/s / CFM 163 / 345 169 / 358
AIR FLOW MEDIUM l/s / CFM 128 / 272 133 / 282
LOW l/s / CFM 101 / 215 109 / 232
QUIET l/s / CFM 86 / 182 86 / 182
SOUND PRESSURE LEVEL (H/M/L) dBA 40/34/29 41/34/30
UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 288 X 800 X 206
PACKING DIMENSION HEIGHT X WIDTH X DEPTH mm 350 x 894 x 280
UNIT WEIGHT kg 9
CONDENSATE DRAIN SIZE mm 19
INDOOR UNIT

TYPE Cross Flow


FAN
DRIVE Direct
TYPE 1-phase SCR
INDEX OF PROTECTION (IP) 44
INSULATION GRADE E
FAN MOTOR RATED INPUT POWER W 34 42
RATED RUNNING CURRENT A 0.19 0.21
MOTOR OUTPUT W 18
POLES 4
MATERIAL Copper Inner Groove
TUBE
DIAMETER mm 7.00
COIL MATERIAL Aluminium
FIN FACE AREA m2 0.18
ROW 2
TYPE Saranet
AIR QUALITY FILTER
QUANTITY pc 2
CASING COLOUR White

6
TECHNICAL SPECIFICATION A5LCY-I(F)_(i)-0003

INDOOR UNIT A5WMY10LR A5WMY15LR


MODEL
OUTDOOR UNIT A5LCY10FR A5LCY15FR
AIR FLOW l/s / CFM 940 810
SOUND PRESSURE LEVEL dBA 48
UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 550 X 658 X 289
PACKING DIMENSION HEIGHT X WIDTH X DEPTH mm 580 X 775 X 355
UNIT WEIGHT kg 26 28
TYPE Flare Valve
PIPE
LIQUID mm 6.35
CONNECTION SIZE
GAS mm 9.52
TYPE Propeller
FAN
DRIVE Direct
TYPE DC Brushless Motor
INDEX OF PROTECTION (IP) 23
INSULATION GRADE E
OUTDOOR UNIT

FAN MOTOR RATED INPUT POWER W 32 35


RATED RUNNING CURRENT A 0.26 0.28
MOTOR OUTPUT W 23
POLES 8
TYPE Hermetic Swing
OIL TYPE Daphne FVC50K (Ether Oil)
OIL AMOUNT cm3 375
RATED INPUT POWER (COOLING) W 661 893
COMPRESSOR
RATED INPUT POWER (HEATING) W 631 853
RATED RUNNING CURRENT (COOLING) A 3.61 4.19
RATED RUNNING CURRENT (HEATING) A 3.41 4.63
LOCKED ROTOR AMP. A - -
MATERIAL Copper Inner Groove
TUBE
DIAMETER mm 7.00
COIL MATERIAL Aluminium
FIN FACE AREA m2 0.33 0.32
ROW 1 2
CASING COLOUR Light Grey
DRAWING NUMBER 020452103F10 000452103F15

ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO 13253 (DUCTED UNIT).
COOLING HEATING
INDOOR: 27°C DB / 19°C WB INDOOR: 20°C DB
OUTDOOR: 35°C DB / 24°C WB OUTDOOR: 7°C DB / 6°C WB

7
TECHNICAL SPECIFICATION A5LCY-I(F)_(i)-0003

Outline and Dimension

Outdoor Unit

Model: A5LCY10/15FR

70014113877

Note: Dimension in mm

8
TECHNICAL SPECIFICATION A5LCY-I(F)_(i)-0003

Indoor Unit

Model: A5WMY10/15LR

Note: Dimension in mm

9
TECHNICAL SPECIFICATION A5LCY-I(F)_(i)-0003

Wiring Diagram
Outdoor Unit Indoor Unit

Model: A5LCY10/15FR Model: A5WMY10/15LR

70034113879

10
TECHNICAL SPECIFICATION A5LCY-I(F)_(i)-0003

Error Code

Indicator Lights
IR Signal Receiver

When an infrared remote control operating signal has been transmitted, the signal
receiver on the indoor unit will respond as below to confirm acceptance of the signal
transmission.

ON to OFF 1 Long Beep


OFF to ON 2 Short Beep
Pump down/ Cool force on
Others 1 Short Beep

Heat Pump Unit

The table shows the LED indicator lights for the air conditioner unit under normal
operation and fault conditions.
The LED indicator lights are located at the side of the air conditioner unit. The heat
pump units are equipped with an “auto” mode sensor whereby it will provide
reasonable room temperature by switching automatically to either “cool” or “heat”
mode according to the temperature set by the user.

11
TECHNICAL SPECIFICATION A5LCY-I(F)_(i)-0003

LED Indicator Lights: Normal Operation and Fault Conditions for


Heat Pump Unit

SLEEP COOL/HEAT TIMER Operation / Faulty Indication


(RED) (GREEN/RED) (YELLOW)

Green

Green Green Cooling mode


Green

Green
Red Heating mode
Red

Red

Green
Red Auto mode in heating operation

TIMER

(YELLO Auto mode in cooling operation


Green
W)

Time Off (when unit is on)


COOL/H
EAT

(GREEN/
RED) Time On (when unit is off)
SLEEP

(RED)
Sleep mode on
ON

Blinki
Green Fan mode on
ng
Green

Green Green Dry Mode on


Green

Green
Defrost operation
Red Red

Red

Green Green Error indication

TIMER

(YELLO
ON Blinking
W)

12
Brand
A:
Acson
TECHNICAL SPECIFICATION A5LCY-I(F)_(i)-0003

Error Code Diagnosis by Wireless Handset APGS02

Diagnosis Step
1. Hold down TIMER CANCEL button for 5 seconds, a “ ” indication flashes
on the temperature display section.
2. Press TIMER CANCEL repeatedly until indoor buzzer produces a long beep.
This indicates the error code, refers to Error Codes table and is displayed on
the temperature display section.
3. A short beep or two consecutive beeps indicate non-corresponding error
codes.
4. To cancel the error code display, hold down TIMER CANCEL button for 5
seconds. Alternatively, the code display will cancel itself if the button is not
pressed for 1 minute.

Error
Error Description Action
Codes
0 Normal No action.
1. Check sensor connection.
2. Check stop valve.
U0 Insufficient gas 3. Check for gas leak.
4. Check the EXV.
5. Check H8.
1. Check the supply voltage.
2. Check the outdoor fan by rotating with hand.
U2 DC voltage out of range
3. Restart the system.
4. Check power supply waveform.
1. Check the indoor unit - outdoor unit connection wires.
2. Check the voltage of the signal terminal.
U4 Communication error
3. Check the indoor fan by rotating with hand.
4. Check the power supply waveform.

13
TECHNICAL SPECIFICATION A5LCY-I(F)_(i)-0003

Error
Error Description Action
Codes
1. Restart the system.
Signal transmission
U7 error (on outdoor 2. Replace outdoor PCB.
unit PCB)
3. Long term monitor on external factor.
1. Check the indoor and outdoor unit model name.
UA Installation error
2. Check the part code on the indoor and outdoor PCB.
Communication 1. Check the wiring and piping between indoor and outdoor units.
Error (indoor and
UF 2. Check refrigerant level.
outdoor) piping and
wiring 3. Check refrigerant line on blockage.
1. Check which indoor having error A5.
Anti-freeze function
UH 2. Check the supply voltage.
in other room
3. Check the indoor and outdoor model name.
1. Check connector connection.
A1 Indoor PCB error
2. Replace indoor PCB.
1. Check for short circuit.
2. Check connection on drain pump.
A3 Water pump error 3. Restart the system.
4. Check the drain water level.
5. Check float switch connection.
1. Check the air passage.
2. Check the intake air filter.
3. Check dust accumulation on indoor coil.
4. Check wiring and piping.
A5 Antifreeze
5. Check the EXV.
6. Check indoor coil sensor resistance value.
7. Check refrigerant level.
8. Check room sensor resistance value.
1. Check the indoor fan by rotating with hand.
2. Replace indoor fan motor if not rotating smoothly.
Indoor fan motor 3. Check fan motor voltage.
A6
abnormal 4. Replace indoor PCB if not at the rated voltage.
5. Check fan capacitor's conductivity (AC Motor).
6. Replace fan capacitor if there's conductivity.

14
TECHNICAL SPECIFICATION A5LCY-I(F)_(i)-0003

Error
Error Description Action
Codes
Indoor heat exchanger
C4
thermistor short/ open 1. Check the connector connection.
Indoor room thermistor short/ 2. Check the sensor resistance value.
C9
open
1. Restart the system.
2. Replace outdoor PCB.
E1 Outdoor PCB error
3. Check to see that the unit is grounded.
4. Check power supply waveform.
1. Check installation conditions.
2. Check stop valve.
3. Check HPS connection.
E3 High pressure protection
4. Check pressure level by pressure gauge.
5. Wait for 10 minutes then restart the system.
6. Check if H3 is displayed.
1. Check stop valve.
2. Check low pressure sensor connection.
3. Check low side pressure and voltage.
E4 Low pressure protection
4. Check outdoor coil sensor connection.
5. Check sensor resistance value.
6. Check refrigerant level.
1. Check connection on discharge pipe sensor.
2. Check discharge pipe sensor resistance value.
E5 Compressor motor lock/overload
3. Check the EXV.
4. Check the refrigerant line on blockage or shortage.
1. Check with inverter checker.
E6 Compressor lock/start-up error
2. Check the EXV.
1. Check the fan motor connection.
E7 Outdoor DC fan motor lock
2. Check if foreign matters exist around or in the fan.
1. Measure the input current.
2. Check the main circuit electrolytic capacitor.
E8 AC input over current 3. Check with inverter checker.
4. Check discharge pressure.
5. Check the installation condition.
1. Restart the system.
2. Check the EXV connection.
E9 EXV error
3. Check EXV coil resistance.
4. Check sensors resistance value.

15
TECHNICAL SPECIFICATION A5LCY-I(F)_(i)-0003

Error Error
Action
Codes Description
1. Check 4WV coil connection.
2. Check the continuity of the 4WV coil and harness.
3. Check the 4WV switching output.
EA 4-way valve error
4. Check sensor connection.
5. Check sensor resistance value.
6. Check the refrigerant line on blockage or shortage.
1. Check the discharge pipe sensor.
Discharge pipe
F3 2. Check the EXV.
overheat
3. Check the refrigerant line on blockage or shortage.
1. Check the installation space.
Heat exchanger 2. Check the outdoor fan.
F6
overheat 3. Check the EXV.
4. Check the coil sensor.
1. Check the reactor connection.
Compressor 2. Check the compressor connection.
H0 sensor system
abnormality 3. Measure the resistance value between the reactor terminals.
4. Measure the resistance value between the compressor terminals.
High pressure 1. Check pressure sensor connection.
H3
switch error 2. Check HPS continuity.
1. Check for short circuit.
Position sensor 2. Check the electrolytic capacitor voltage.
H6
abnormality 3. Check compressor harness wire.
4. Check with inverter checker.
1. Restart the system.
2. Check capacitor voltage.
AC current
H8 3. Measure the rectifier input voltage.
sensor error
4. Check compressor harness wire.
5. Check with inverter checker.
Outdoor air 1. Check the sensor connection.
H9 thermistor short /
open 2. Check the sensor resistance value.

Pressure sensor 1. Check pressure sensor connection.


J1
error 2. Check pressure and voltage level.

16
TECHNICAL SPECIFICATION A5LCY-I(F)_(i)-0003

Error
Error Description Action
Codes
1. Check the sensor connection.
Compressor discharge
J3 pipe thermistor short 2. Check the sensor resistance value.
/open / misplaced
3. Check indoor coil sensor resistance value.
Suction pipe thermistor
J5 Same as H9.
short/ open
Outdoor heat
J6 Same as H9.
exchanger
Subcooling heat
J7 exchanger thermistor Same as H9.
short/ open
Liquid pipe thermistor
J8 Same as H9.
short/ open
Gas pipe thermistor
J9 Same as H9.
abnormality
Communication Error 1. Check fan motor connection.
LC (control PCB and
inverter PCB) 2. Check if LED blinking normally at outdoor PCB.
1. Check the range of power supply.
2. Check connection between compressor and PCB.
L1 Outdoor PCB error
3. Check fan motor resistance.
4. Check the power supply waveform.
1. Restart the system.
2. Check sensor resistance value.
Electrical box
L3 3. Check heat sink temperature and conditions.
temperature rise
4. Check outdoor fan.
5. Check the installation condition.
1. Restart the system.
2. Check the silicon grease condition on heat sink.
3. Check sensor resistance value.
L4 Heat sink overheat
4. Check heat sink temperature and conditions.
5. Check outdoor fan.
6. Check the installation condition.

17
TECHNICAL SPECIFICATION A5LCY-I(F)_(i)-0003

Error
Error Description Action
Codes
1. Check stop valve.
2. Check with inverter checker.
3. Check the power transistor.
L5 IPM error / IGBT error 4. Check the supply voltage.
5. Check the compressor phase.
6. Check the discharge pressure.
7. Check the installation condition.
L8 Electrical thermal switch Contact dealers for assistance.
1. Check installation conditions.
2. Check stop valve.
L9 Stall prevention 3. Check difference between high and low pressure side.
4. Check continuity on the power transistor.
5. Check the output voltage.
1. Check LED on outdoor PCB.
Open phase or voltage
P1 2. Check open phase of power supply voltage.
unbalance
3. Check voltage balance between phases.
Heat sink thermistor short /
P4 Same as H9.
open
PJ Capacity setting error 1. Check the connection between capacitor and Outdoor PCB.

18
TECHNICAL SPECIFICATION A5LCY-I(F)_(i)-0003

Exploded View and Part List

Outdoor Unit

Model: A5LCY10/15FR

19
TECHNICAL SPECIFICATION A5LCY-I(F)_(i)-0003

70024113404

No. Part Description No. Part Description


1 ASSY., BASE PAN 17 THERMISTOR HOLDER
2 COMPRESSOR, 1YC23AEXD 18 ASSY., RIGHT PANEL
DAIKIN
3 GROMMET,COMPRESSOR 19 PANEL, LEFT (PLASTIC)
4P180906-1 DAIKIN
4 ASSY., OUTDOOR COIL 20 COMP. JACKET, TOP
5 BRACKET, VALVE 21 ASSY., SOUND INSULATION
(OUTER SLEEVE)
6 ASSY., 4WV 22 SOUND, INSULATION (INNER
SLEEVE 1)
7 VALVE,ASSY,3 WAY,3/8",HANG 23 SOUND, INSULATION (INNER
JI SLEEVE 2)
8 ASSY., TUBE DISCHARGE 24 ASSY., CONTROL BOX
9 ASSY., EXV WITH SERVICE 25 ASSY., FRONT PANEL
VALVE
10 VALVE,ASSY,2 WAY,1/4",HANG 26 GRILLE, DISCHARGE
JI
11 SOLENOID COIL,QA(Q)12-OYL- 27 ASSY., VALVE COVER
08-RK(E)SANHUA
12 ASSY., PARTITION 28 PLATE, SHIELD
13 BRACKET, MOTOR 29 ASSY., TOP PANEL
14 ASSY., EPS COIL TOP 30 ASSY., COMPRESSOR WIRE
15 MOTOR, DC BRUSHLESS 31 ASSY., SOLENOID COIL
16 FAN, BLADE

20
TECHNICAL SPECIFICATION A5LCY-I(F)_(i)-0003

Indoor Unit

Model: A5WMY10/15LR

70024113858

21
TECHNICAL SPECIFICATION A5LCY-I(F)_(i)-0003

No. Part Description No. Part Description


1 ASSY., FRONT GRILLE ACSON - 12 ASSY., INSTALLATION PLATE
INVERTER
2 ASSY., PANEL (ACSON - 13 RIGHT SIDE PANEL
INVERTER)
3 ASSY., 14 DRIP PROOF COVER
DISC.GRILLE.HOR.BLADE
4 BOTTOM FRAME ASSY 15 CLIP, COIL SENSOR
5 ASST., CONTROL BOX 16 ASSY., COIL
6 ASSY., SERVICE COVER 17 ASSY., DRAIN HOSE
7 ASSY., PIPING FIXTURE 18 FAN BEARING VIBRATION
ABSORBER SET
8 MOTOR 19 AIR FILTER
9 MOTOR MOUNTING PLATE (1) 20 HANDSET, WIRELESS APGS02
ACSON
10 MOTOR MOUNTING PLATE (2) 21 ASSY., PCB (WITH LAMP COVER)
11 BLOWER, CROSS FLOW

22
TECHNICAL SPECIFICATION A5LCY-I(F)_(i)-0003

Product manufactured in an ISO certified facility.


This document contains the most current information as of this orienting.
For the most up to date product information, please go to www.acson-international.com

23