You are on page 1of 5

Power and Energy Capacity Requirements of

Storages Providing Frequency Control Reserves


Theodor Borsche, Andreas Ulbig, Michael Koller, Göran Andersson
Power Systems Laboratory, ETH Zürich
{borsche, ulbig, andersson}@eeh.ee.ethz.ch, michael.koller 1@alumni.ethz.ch

Abstract—Due to their fast response time and high ramp then continue by defining the method used for analysing the
rates, storage systems are capable of providing frequency control required energy capacity in Section IV and by giving results
reserves. However, the limit in energy capacity poses difficulties in Section V.
as frequency control signals are not unbiased. We describe a
scheme to recharge or discharge the storage without impeding
the quality of the provided service, and formulate an analyzing II. R EGULATORY BACKGROUND
method to investigate the resulting size of the storage.
We show that even small storage sizes are sufficient to provide Traditionally, ancillary services are being supplied by power
continuous and reliable primary and secondary frequency control plants (§ 4.4, 4.5 in [5]) and regulation of frequency control
reserves to the grid.
reserves focuses on issues related to power plant operation.
I. I NTRODUCTION However, when using storage systems to provide ancillary
services, new questions arise. In this paper, primary and
With the introduction of intermittent energy sources and secondary control reserves are investigated. Their task is to
the advent of electric vehicles, much focus is given to stor- balance any power mismatch and resulting frequency deviation
age technologies. Currently, only pumped hydro storage is and unscheduled exchanges in the system, but not to sustain
used on a major scale, however pumped hydro is strongly longer periods of energy mismatch. Payments for these fast
dependent on geographical features. Other technologies, such ancillary service are based on power provision and not on
as batteries [1], flywheels and electrothermal energy storage energy delivery, while costs for storage systems arise mainly
(ETES, [2]) are independent of location and have rapid de- from energy capacity. For an economical operation of a storage
ployment times. While costs for such systems are constantly within frequency control, it is essential to maximize the of-
decreasing, they are not yet able to compete with pumped fered control reserves per storage capacity. Tertiary frequency
hydro storage. control is neglected, as the aim of tertiary control is to provide
One possible business case for storage is provision of energy to the system – something which is hard for a storage
ancillary services, for example frequency control [3], [4]. device with limited energy capacity.
Batteries have also an added benefit of being able to react
very fast to frequency deviations. It is well known, that a faster A. Primary frequency control reserves
response reduces overall frequency deviation and consequently
reduces stress on the power system. It would therefore be in Primary control in ENTSO-E describes the first tier of
the interest of the TSO to include fast reacting storage systems frequency control. Participating units are responding in a
in the primary frequency control scheme. In the course of this proportional manner to deviations from nominal frequency,
paper we will discuss primary and secondary frequency control stabilizing the frequency after a mismatch in production and
in Europe, which is equivalent to spinning reserves and load consumption. Full activation is at 200 mHz and after a maxi-
frequency control (LFC) or area generation control (AGC) in mum of 30 s. There also is a dead band of no activation for
other networks. deviations less than 10 mHz [6]. The tendering period is one
Ancillary services are not guaranteed to be zero-mean, week, and in the ENTSO-E network currently 3000 MW of
and losses are inherent to any storage system. This leads primary reserves are contracted. There are some conflicting
to violations of the storage capacity constraints and thus to statements about the energy capacity of a unit participating
an inability to provide the promised service to the grid. We in primary control. In the following we will discuss the main
propose to enable storage systems to participate in ancillary aspects.
services by adjusting the operating point to allow for an a) Power-to-Energy ratio: The Swiss TSO requires in
appropriate charging or discharging that keeps the state of its contracts, that the units must have an availability of 100 %
charge within acceptable levels. The adjustment of the working [7], which would mean basically infinite energy capacity . On
point has to be considerably slower than the associated service. the other hand, the ENTSO-E operating handbook specifies,
The paper starts by giving an overview over the relevant that a unit has to be able to sustain at least 15 minutes of full
regulation in Section II, before the proposed recharge strategy activation [6], and has to be able to do so again after frequency
based on slow changes in setpoint is outlined in Section III. We has been restored.

978-1-4799-1303-9/13/$31.00 ©2013 IEEE


150 0.6
P
η2 = 1 AS
2 0.4 P
η = 0.90 ext
100 P
Energy capacity

η2 = 0.81 0.2 WP
[MWh/MW]

η2 = 0.64

P/PAS
50 0

−0.2
0
−0.4

−0.6
−50
Jan FebMar Apr May Jun Jul Aug Sep Oct NovDec 0 15 30 45 60 75 90 105 120
time time [min]

Fig. 1: SoC evolution after following primary control for one Fig. 2: Typical behaviour of storage system with setpoint
year adjustment. The response to the primary control signal is
clearly visible, the working point changes comparably slow

b) Operating point: German TSO’s explicitly allow the


co-use of a plant for primary control and other services such incident, which is usually the failure of the largest generator
as load-following and secondary control (§3.2.9 in [8]). One in the interconnected network. In such a case primary control
might now be tempted to claim that the plant was following would need to provide control power for up to 15 minutes
a load with opposite behavior as the primary control signal. until secondary control takes over. A storage participating in
Thus the two control actions would cancel out and the plant primary reserves would need to have a storage capacity of
could produce a flat output. Obviously, this is a misuse of 30 min in order to be able to provide 15 min in either up or
the regulation. While no detailed specifications for adjusting down direction. However, prolonged periods with no change of
the operating point of a unit taking part in primary control are sign and covering an energy content bigger than the reference
provided, framework agreements for secondary control provide incident are observed in historic time series. Such signals lead
rules on this. Usually, there are two options. Either a change to a continued charging or discharging of the storage system,
of working point at each full fifteen minutes, or with a five eventually violating the capacity constraints.
minute notice to the TSO (cf. [9], §3.2.3). While a statistical analysis proofs the near-normal distribu-
B. Secondary frequency control reserves tion of frequency deviations, there is a small bias of 1.5 %,
which leads to the substantial cumulative energy shown in
The amount of secondary control reserves and minimum
Figure 1. While energy capacity is a design parameter of many
requirements are set by ENTSO-E, but the implementation
storage technologies, it is associated with high costs. In the
is organized and regulated by each control area indepen-
case of Li-ion batteries, it is even the dominating cost factor.
dently. This leads to varying definitions even within Europe.
Increasing storage capacity to accommodate biased signals is
As Switzerland utilizes mainly fast hydro power plants, the
therefore not an economically viable option.
requirements for response time and ramp rates are far stricter
In [3], it was proposed to use the dead band of primary
than in Germany, which relies heavily on rather slow thermal
control for adjusting the state of charge. Furthermore, using
power plants. There are attempts to align regulation to make
resistors for down control (reduced production/ increased con-
trading in secondary control reserves between control zones
sumption) was investigated. However, former adds only some
possible. Table I gives an overview over secondary control in
flexibility without actually solving the cause for imbalances,
Germany and Switzerland.
latter is only a unidirectional solution that wastes substantial
TABLE I: Comparison of regulatory framework for secondary amounts of energy.
control reserves in Switzerland and Germany Instead, by adjusting the setpoint of the storage system,
the SoC can be kept within defined capacity bounds. We
Germany Switzerland propose using an average over the previous usage to force
Full activation < 5 min 1 < 140 s the control signal to be zero-mean. A typical 2-hour period
PN 2 PN of primary control with averaging and delay time of both 15
Ramp 2% · 0.5 % ·
min s minutes is shown in Figure 2. Assuming that the control signal
1 Step-response, including ramp is bounded, this leads to a bounded SoC. Furthermore, with
2 PN : nominal power
bounded input the averaging period defines a maximum ramp
rate which can be chosen to be slow enough as not to interfere
III. A NCILLARY SERVICES WITH LIMITED CAPACITY with the offered service. Additionally, a delay can be added
STORAGE to give next tier ancillary services enough time to relieve the
While primary and secondary control reserves are usually current tier service. This leads to new questions:
assumed to be utilized with no bias, this is not at all guar- a) Setpoint adjustment: There are several options to
anteed. Ancillary services are designed to clear a reference contract the energy needed for adjusting the setpoint: 1)
Storage parameters
- efficiency The evolution of the SoC is modelled by
- self-discharge
SoC(k + 1) = SoC(k)+

(ηPext (k) − Pξ )ΔT if Pext (k) ≥ 0 (1)
Historic time series
E / PAS ratio +
of ancillary Storage System
Simulation P / PAS ratio ( η1 Pext (k) − Pξ )ΔT if Pext (k) < 0
sercvice signal

Where ΔT is the time difference between k and k + 1,


operating point adjustment Pext is the external power flowing into the storage and Pξ
- delay describes the self-discharge and may depend on the SoC,
- ramp rates
ambient temperature and other factors. Usually, Pξ > 0,
Fig. 3: Analysis method: historic times series and parameters meaning a loss of charge, but it may also be negative, e. g.
of the storage and setpoint adjustment are the inputs natural inflows in a pumped hydro storage. η is the one-way
efficiency including all losses in the system, e. g. converter
losses and battery losses. Generally, η can be different for
intraday markets, 2) bilateral agreements, 3) pooling with a charging and discharging and can depend on P , SoC, ambient
power plant or 4) consumption of balancing energy. Intraday and internal temperature or basically any other parameter.
markets and bilateral agreements are cheaper than balancing As the analysis would be very device dependent and quite
energy, but suffer from a longer time until delivery and may be involved without adding much value to our statement, we
fixed to 15 minute or hourly intervals, hence time granularity assume constant efficiency at all operating points. The loss
may not be sufficiently fine. Balancing energy is expensive but can be computed as
immediately available. To still provide the desired service to 
the grid, setpoint adjustments have to be made with a slower (1 − η)Pext (k) if Pext (k) ≥ 0
Ploss (k) = Pξ (k) + (2)
time scale and ramp rate than the service provided by the unit (1 − η1 )Pext (k) if Pext (k) < 0
(cf. Section II).
The adjustment of the working point has to 1) cancel out
b) System stability: System stability is paramount and any imbalance in the ancillary service signal, 2) adjust for
may not be impeded in any way. This is guaranteed, as long losses in the storage system. We define PWP as the working
as 1) the energy content of the storage is capable of clearing point of the storage, and PAS as the power requested by the
the reference incident as defined in the respective ancillary ancillary service signal. At time k, we can compute the offset,
service regulation, 2) the amount of the next tier ancillary which will be applied after a delay of d time steps
service is increased in such a way as to cancel out the setpoint k
adjustment. Also, the power capacity of the storage device j=k−a (−PAS (j) + Ploss (j))
must be able to provide the full ancillary service power at any PWP (k + d) = (3)
a
time. This means, the power capacity has to be at least the Here, a is a parameter defining over what time period the
sum of offered reserves and maximum set point adjustment. average should be taken.
c) Cost: The operating expenses will increase, as the Finally, the actual setpoint for power to be consumed by the
energy associated with adjusting the energy setpoint has to be battery can be computed as the sum of the ancillary service
paid. Further investigation in economical optimal control have signal and the current working point
to made, which may also take into account the capital expense
for power and energy capacity, as well as the degradation of Pext (k) = PAS (k) + PWP (k) (4)
the storage system, e.g. battery wear due to utilization pattern
The resulting power to energy ratio is computed as the
[10].
difference between minimum and maximum state of charge
IV. A NALYSIS METHOD reached for a certain parameter set and time series. This can
be either expressed as power that can be offered per energy
As described in the previous section, we aim at overcoming MW
capacity with unit [ MW h ], or as the reciprocal thereof yielding
the limited energy capacity of a storage system by adjusting storage capacity expressed in time that the offered PAS can
the operating point in such a way that a true zero-mean be stored. We will mainly use latter notation. The required
signal is achieved. SoC evolution also depends on some power capacity is computed as P = PAS + max(|PWP |). We
storage system specific parameters, such as efficiency and will usually normalize this value with respect to PAS .
self-discharge, and on the parameters of the operating point
adjustment, mainly delay and averaging period. An analysis V. R ESULTS
method was devised which provides both the power capacity To test the algorithm, different scenarios were investigated.
and energy capacity needed to provide some ancillary service. As input a step signal, as well as historic time series provided
As input, historic time series or artificial test signals can be by the Swiss TSO swissgrid were used. In all simulations,
used and a parameter scan over the storage system and setpoint an ideal storage with η = 1 is compared to a lithium-ion
adjustment parameters can be performed. Figure 3 shows the battery system (η = 0.95), standard battery (η = 0.9) and
basic setup. ETES (η = 0.8). Note that these efficiencies translate to a
0.2
1
0

Energy capacity
[MWh/MW]
−0.2
0.5
PAS

−0.4 reference
2
−0.6 η =1
η2 = 0.90
0
−0.8 η2 = 0.81 60
2
−1 η = 0.64 60
45
0 15 30 45 60 15 15
5 15
time Averaging period Delay
[min] [min]
Fig. 4: Power production of storage system after negative step (a)
response
2
0
1.8

Power capacity
η2 = 1

[MW/MW]
2
η = 0.90 1.6
−7.5
η2 = 0.81
2 1.4
η = 0.64
[min]
SoC

−15 1.2

1
−22.5 60 60
45
15 5 15
15
Averaging period Delay
−30 [min] [min]
0 15 30 45 60
time (b)
Fig. 5: SoC evolution of storage system after negative step Fig. 6: Required energy (a) and power (b) capacity per offered
response MW of primary control as a function of the averaging period
and delay. η 2 = 0.90

round-trip efficiency η 2 of 1, 0.9, 0.81 and 0.64, respectively.


TABLE II: Required power capacity and energy capacity per
Furthermore, we neglect self-discharge as this is minimal
offered unit of primary control reserve
compared to other losses and can be easily accounted for by
a constant slow charging. a: 5 min, d: 5 min a: 15 min, d: 15 min a: 60 min, d: 60 min
η2
P/PAS E/PAS P/PAS E/PAS P/PAS E/PAS
A. Step response [h] [h] [h]
Figures 4 and 5 show the step response for a controller with 1 1.6733 0.1507 1.6161 0.3752 1.5272 0.9170
both 15 minute averaging period and 15 minute delay, and 0.90 1.6685 0.1511 1.6114 0.3809 1.5043 0.9054
0.81 1.6631 0.1514 1.6063 0.3868 1.4808 0.8939
systems with varying efficency. Specifically, Figure 4 shows 0.64 1.7466 0.1518 1.5942 0.3990 1.4311 0.8711
the power consumed by the storage system. As defined by
the delay, the storage provides fifteen minutes of full power
before bringing back the power output gradually to zero.
The overshoot is due to adjustments for the internal losses. a comparably small influence, while the delay strongly affects
The same can be observed in the SoC, which continuously the required capacity. Further results are displayed in Table II.
decreases until it is limited by the controller to 22.5 min · PAS In Section II it was argued that a power-to-energy ratio
of 2 or in other words a storage capacity of 30 minutes
B. Primary control time series is a minimum requirement for primary control, guaranteeing
For the delay we assume 1, 5, 15, 45 or 60 minutes, where 1 system stability in face of the reference incident. If a delay and
and 5 minutes would be energy supply from balancing energy, averaging period of 15 minutes is chosen, that capacity would
5 and 15 could be bilateral agreements or pooling with a power also be sufficient for the investigated historic time-series.
plant, and 45 or 60 minutes may be the delay of intraday Interesting enough, perfect efficiency would increase the re-
markets. The averaging period is chosen from 5, 15 or 60 quired energy capacity for certain cases. Generally, efficiency
minutes, correlating again to balancing, pooling or trading. has only a weak effect on the capacity.
As expected, in Figure 6a we see an increase in the required The maximum power required decreases somewhat with
size of storage with both an increase in delay and averaging increased averaging period, and increases slightly with delay
period. The increase is not linear, the difference between a time assuming there are losses in the system (cf. Figure 6b).
45 minute and 1 hour delay for example is quite small. It can For an ideal storage behaviour is similar, just that there is no
further be observed, that the length of the averaging period has dependency on the delay. These results are as expected.
4
It would be quite expensive to provide this kind of storage
Energy capacity with lithium ion batteries. Other technologies such as the
[MWh/MW] 3 ETES, which have far lower round-trip efficiency but at the
2 same time lower cost per kW h of storage capacity, might be
1
more favorable for secondary control.
0 VI. C ONCLUSION
60
45 In this paper, we have shown a way to use storage systems
30 105
15 45 60 for the provision of ancillary services by adjusting the setpoint.
15 30
Averaging period Delay Furthermore, we introduced a way to analyse the required
[min] [min] storage size given historic time-series and parameters of the
(a) storage system itself.
We argued, why adjusting the setpoint would be acceptable
2 to the TSO and would still guarantee system stability, while
1.8 at the same time limiting the required energy capacity of
Power capacity

the storage. While regulation has to be clarified on the issue


[MW/MW]

1.6
of setpoint adjustment, we assume a storage capacity of
1.4 30 min for primary control and 2 h for secondary control to be
1.2 reasonable. With falling prices for storage systems this might
become an economically viable option in the future.
1
60 Future work may look at ways to improve the basic algo-
45 105
30 60 rithm presented here. Especially taking into account varying
15 15 30 45
Averaging period Delay prices for balancing energy or intraday trades at different times
[min] [min]
of the day may further improve the business case.
(b)
ACKNOWLEDGMENT
Fig. 7: Required energy (a) and power (b) capacity per offered
MW of secondary control as a function of the averaging period The authors would like to thank Marc Moeckli and Bruno
and delay. η 2 = 0.90 Völlmin at EKZ for access to the Zurich 1 MW BESS,
Marc Scherer at swissgrid for insights on ancillary services
and Philipp Fortenbacher and Olivier Megél for the fruitful
TABLE III: Required power capacity and energy capacity per discussions about battery technology and applications.
offered unit of secondary control reserve
R EFERENCES
a: 15 min, d: 15 min a: 30 min, d: 45 min a: 1 h, d: 105 min
η2 [1] K. Divya and J. Østergaard, “Battery energy storage technology for
P/PAS E/PAS P/PAS E/PAS P/PAS E/PAS power systems – an overview,” Electric Power Systems Research, vol. 79,
[h] [h] [h] no. 4, pp. 511–520, 2009.
[2] M. Mercangöz, J. Hemrle, L. Kaufmann, A. Z’Graggen, and C. Ohler,
1 2 0.7472 2 1.9510 2 3.8179
“Electrothermal energy storage with transcritical CO2 cycles,” Energy,
0.90 2.0311 0.7508 2.0285 1.9748 1.9973 3.8124
vol. 45, no. 1, pp. 407–415, 2012, the 24th International Conference on
0.81 2.0766 0.7545 2.0619 1.9999 2.0103 3.8002
Efficiency, Cost, Optimization, Simulation and Environmental Impact of
0.64 2.1806 0.7672 2.1755 2.0525 2.0627 3.7561
Energy, ECOS 2011.
[3] A. Oudalov, D. Chartouni, and C. Ohler, “Optimizing a battery energy
storage system for primary frequency control,” Power Systems, IEEE
Transactions on, vol. 22, no. 3, pp. 1259 –1266, aug. 2007.
C. Secondary control time series [4] P. Mercier, R. Cherkaoui, and A. Oudalov, “Optimizing a battery energy
storage system for frequency control application in an isolated power
The results for secondary control reserves are similar. We system,” Power Systems, IEEE Transactions on, vol. 24, no. 3, pp. 1469–
used slower operating point adjustments, which represent 1477, Aug. 2009.
[5] swissgrid, “Transmission code 2008,” VSE, Aug 2008. [Online].
energy compensation by tertiary control or power markets. Available: www.swissgrid.ch
For delay and averaging period we scanned parameter sets [6] ENTSO-E, Operation Handbook, 2009, ch. Policy 1: Load-Frequency
of 15, 30, 45 and 60 minutes. Additionally, we added a run Control and Performance.
[7] swissgrid ag, “Rahmenvertrag zur Lieferung von Primärregelleistung,”
with delay of 105 minutes which represents the worst case November 2009, version 2.0. [Online]. Available: www.swissgrid.ch
intraday market delay. Secondary control reserves call for a [8] VDN, Transmission Code 2003, 2003, ch. Anhang D1: Unterlagen
higher power to energy ratio compared to primary reserves zur Präqualifikation für die Erbringung von Primärregelleistung für die
ÜNB. [Online]. Available: www.regelleistung.net
(cf. Table III). Efficiency has only minor influence on this, [9] FNN, Transmission Code 2007. VDE, Nov 2007, ch. Anhang
while the averaging period somewhat and the delay strongly D2 Teil 1: Unterlagen zur Präqualifikation von Anbietern zur
affect the minimum storage size. As can be read from Figure Erbringung von Sekundärregelleistung für die ÜNB. [Online]. Available:
www.regelleistung.net
7a, values range between 0.75 and 4 for fast and slow set point [10] M. Koller, T. Borsche, A. Ulbig, and G. Andersson, “Defining a
adjustment. The storage also has to provide twice the power degradation cost function for optimal control of a battery energy storage
capacity of the offered reserve power (cf. Figure 7b). system,” submitted to PowerTech 2013.

You might also like