Professional Documents
Culture Documents
Abstract—Due to their fast response time and high ramp then continue by defining the method used for analysing the
rates, storage systems are capable of providing frequency control required energy capacity in Section IV and by giving results
reserves. However, the limit in energy capacity poses difficulties in Section V.
as frequency control signals are not unbiased. We describe a
scheme to recharge or discharge the storage without impeding
the quality of the provided service, and formulate an analyzing II. R EGULATORY BACKGROUND
method to investigate the resulting size of the storage.
We show that even small storage sizes are sufficient to provide Traditionally, ancillary services are being supplied by power
continuous and reliable primary and secondary frequency control plants (§ 4.4, 4.5 in [5]) and regulation of frequency control
reserves to the grid.
reserves focuses on issues related to power plant operation.
I. I NTRODUCTION However, when using storage systems to provide ancillary
services, new questions arise. In this paper, primary and
With the introduction of intermittent energy sources and secondary control reserves are investigated. Their task is to
the advent of electric vehicles, much focus is given to stor- balance any power mismatch and resulting frequency deviation
age technologies. Currently, only pumped hydro storage is and unscheduled exchanges in the system, but not to sustain
used on a major scale, however pumped hydro is strongly longer periods of energy mismatch. Payments for these fast
dependent on geographical features. Other technologies, such ancillary service are based on power provision and not on
as batteries [1], flywheels and electrothermal energy storage energy delivery, while costs for storage systems arise mainly
(ETES, [2]) are independent of location and have rapid de- from energy capacity. For an economical operation of a storage
ployment times. While costs for such systems are constantly within frequency control, it is essential to maximize the of-
decreasing, they are not yet able to compete with pumped fered control reserves per storage capacity. Tertiary frequency
hydro storage. control is neglected, as the aim of tertiary control is to provide
One possible business case for storage is provision of energy to the system – something which is hard for a storage
ancillary services, for example frequency control [3], [4]. device with limited energy capacity.
Batteries have also an added benefit of being able to react
very fast to frequency deviations. It is well known, that a faster A. Primary frequency control reserves
response reduces overall frequency deviation and consequently
reduces stress on the power system. It would therefore be in Primary control in ENTSO-E describes the first tier of
the interest of the TSO to include fast reacting storage systems frequency control. Participating units are responding in a
in the primary frequency control scheme. In the course of this proportional manner to deviations from nominal frequency,
paper we will discuss primary and secondary frequency control stabilizing the frequency after a mismatch in production and
in Europe, which is equivalent to spinning reserves and load consumption. Full activation is at 200 mHz and after a maxi-
frequency control (LFC) or area generation control (AGC) in mum of 30 s. There also is a dead band of no activation for
other networks. deviations less than 10 mHz [6]. The tendering period is one
Ancillary services are not guaranteed to be zero-mean, week, and in the ENTSO-E network currently 3000 MW of
and losses are inherent to any storage system. This leads primary reserves are contracted. There are some conflicting
to violations of the storage capacity constraints and thus to statements about the energy capacity of a unit participating
an inability to provide the promised service to the grid. We in primary control. In the following we will discuss the main
propose to enable storage systems to participate in ancillary aspects.
services by adjusting the operating point to allow for an a) Power-to-Energy ratio: The Swiss TSO requires in
appropriate charging or discharging that keeps the state of its contracts, that the units must have an availability of 100 %
charge within acceptable levels. The adjustment of the working [7], which would mean basically infinite energy capacity . On
point has to be considerably slower than the associated service. the other hand, the ENTSO-E operating handbook specifies,
The paper starts by giving an overview over the relevant that a unit has to be able to sustain at least 15 minutes of full
regulation in Section II, before the proposed recharge strategy activation [6], and has to be able to do so again after frequency
based on slow changes in setpoint is outlined in Section III. We has been restored.
η2 = 0.81 0.2 WP
[MWh/MW]
η2 = 0.64
P/PAS
50 0
−0.2
0
−0.4
−0.6
−50
Jan FebMar Apr May Jun Jul Aug Sep Oct NovDec 0 15 30 45 60 75 90 105 120
time time [min]
Fig. 1: SoC evolution after following primary control for one Fig. 2: Typical behaviour of storage system with setpoint
year adjustment. The response to the primary control signal is
clearly visible, the working point changes comparably slow
Energy capacity
[MWh/MW]
−0.2
0.5
PAS
−0.4 reference
2
−0.6 η =1
η2 = 0.90
0
−0.8 η2 = 0.81 60
2
−1 η = 0.64 60
45
0 15 30 45 60 15 15
5 15
time Averaging period Delay
[min] [min]
Fig. 4: Power production of storage system after negative step (a)
response
2
0
1.8
Power capacity
η2 = 1
[MW/MW]
2
η = 0.90 1.6
−7.5
η2 = 0.81
2 1.4
η = 0.64
[min]
SoC
−15 1.2
1
−22.5 60 60
45
15 5 15
15
Averaging period Delay
−30 [min] [min]
0 15 30 45 60
time (b)
Fig. 5: SoC evolution of storage system after negative step Fig. 6: Required energy (a) and power (b) capacity per offered
response MW of primary control as a function of the averaging period
and delay. η 2 = 0.90
1.6
of setpoint adjustment, we assume a storage capacity of
1.4 30 min for primary control and 2 h for secondary control to be
1.2 reasonable. With falling prices for storage systems this might
become an economically viable option in the future.
1
60 Future work may look at ways to improve the basic algo-
45 105
30 60 rithm presented here. Especially taking into account varying
15 15 30 45
Averaging period Delay prices for balancing energy or intraday trades at different times
[min] [min]
of the day may further improve the business case.
(b)
ACKNOWLEDGMENT
Fig. 7: Required energy (a) and power (b) capacity per offered
MW of secondary control as a function of the averaging period The authors would like to thank Marc Moeckli and Bruno
and delay. η 2 = 0.90 Völlmin at EKZ for access to the Zurich 1 MW BESS,
Marc Scherer at swissgrid for insights on ancillary services
and Philipp Fortenbacher and Olivier Megél for the fruitful
TABLE III: Required power capacity and energy capacity per discussions about battery technology and applications.
offered unit of secondary control reserve
R EFERENCES
a: 15 min, d: 15 min a: 30 min, d: 45 min a: 1 h, d: 105 min
η2 [1] K. Divya and J. Østergaard, “Battery energy storage technology for
P/PAS E/PAS P/PAS E/PAS P/PAS E/PAS power systems – an overview,” Electric Power Systems Research, vol. 79,
[h] [h] [h] no. 4, pp. 511–520, 2009.
[2] M. Mercangöz, J. Hemrle, L. Kaufmann, A. Z’Graggen, and C. Ohler,
1 2 0.7472 2 1.9510 2 3.8179
“Electrothermal energy storage with transcritical CO2 cycles,” Energy,
0.90 2.0311 0.7508 2.0285 1.9748 1.9973 3.8124
vol. 45, no. 1, pp. 407–415, 2012, the 24th International Conference on
0.81 2.0766 0.7545 2.0619 1.9999 2.0103 3.8002
Efficiency, Cost, Optimization, Simulation and Environmental Impact of
0.64 2.1806 0.7672 2.1755 2.0525 2.0627 3.7561
Energy, ECOS 2011.
[3] A. Oudalov, D. Chartouni, and C. Ohler, “Optimizing a battery energy
storage system for primary frequency control,” Power Systems, IEEE
Transactions on, vol. 22, no. 3, pp. 1259 –1266, aug. 2007.
C. Secondary control time series [4] P. Mercier, R. Cherkaoui, and A. Oudalov, “Optimizing a battery energy
storage system for frequency control application in an isolated power
The results for secondary control reserves are similar. We system,” Power Systems, IEEE Transactions on, vol. 24, no. 3, pp. 1469–
used slower operating point adjustments, which represent 1477, Aug. 2009.
[5] swissgrid, “Transmission code 2008,” VSE, Aug 2008. [Online].
energy compensation by tertiary control or power markets. Available: www.swissgrid.ch
For delay and averaging period we scanned parameter sets [6] ENTSO-E, Operation Handbook, 2009, ch. Policy 1: Load-Frequency
of 15, 30, 45 and 60 minutes. Additionally, we added a run Control and Performance.
[7] swissgrid ag, “Rahmenvertrag zur Lieferung von Primärregelleistung,”
with delay of 105 minutes which represents the worst case November 2009, version 2.0. [Online]. Available: www.swissgrid.ch
intraday market delay. Secondary control reserves call for a [8] VDN, Transmission Code 2003, 2003, ch. Anhang D1: Unterlagen
higher power to energy ratio compared to primary reserves zur Präqualifikation für die Erbringung von Primärregelleistung für die
ÜNB. [Online]. Available: www.regelleistung.net
(cf. Table III). Efficiency has only minor influence on this, [9] FNN, Transmission Code 2007. VDE, Nov 2007, ch. Anhang
while the averaging period somewhat and the delay strongly D2 Teil 1: Unterlagen zur Präqualifikation von Anbietern zur
affect the minimum storage size. As can be read from Figure Erbringung von Sekundärregelleistung für die ÜNB. [Online]. Available:
www.regelleistung.net
7a, values range between 0.75 and 4 for fast and slow set point [10] M. Koller, T. Borsche, A. Ulbig, and G. Andersson, “Defining a
adjustment. The storage also has to provide twice the power degradation cost function for optimal control of a battery energy storage
capacity of the offered reserve power (cf. Figure 7b). system,” submitted to PowerTech 2013.