Abstract: The paper deals with the problem of coordination particular case: series reclosers installed in overhead line.
of reclosers installed in series in overhead line. Existing This goal shall be achieved with the aid of autocoordination
practice is based upon set of rules that require human algorithm that shall allow automatic calculation of the
interference. This may lead to errors and incorrect operation protection settings on the basis of line parameters and
of protection. We have developed a set of algorithms that selected grading margins.
allow determining settings of protection elements providing
Table 1
protection against short circuit and sensitive earth faults.
Percentage of utilities using
Network parameters and grading margins serve as input data Advanced relay function
advanced function
for the mentioned algorithms. The algorithms have been
Distance protection 4%
tested with the aid of network computer models. The tests
Directional protection 2%
proved applicability of the algorithms for field application.
Negative sequence protection 8%
Moreover in many cases customers do not employ even has been designed in order to support autocoordination
minor fraction of the capabilities offered by microprocessor algorithm. This characteristics (named TEL A - "TEL
relays [2]. Table 1 summarises results of survey [2] with Automatic") is supported by the new generation of Tavrida
regard to applicability of advanced protection practice for Electric recloser controls (RC02). It delivers minimum
distribution overhead lines. possible tripping times if TCC's for downstream devices as
The same survey indicates that only limited number of well as time and current grades are known. Fig. 1 illustrates
utilities takes into considerations all important considerations typical example of plotting TEL A characteristic.
10
fJ· current range shall be coordinated in order to avoid nuisance
tripping of the upstream devices
tripping times of all reclosers within the entire applicable
current range shall preserve wire from burning at the point of
their installations
As a result of application of the mentioned limitations
optimum time-current characteristics shall be automatically
01
calculated.
In general case there are two possible outputs resulted
from the mentioned procedure:
10 100 solution does not exist, i.e, at least one of the mentioned
limitations cannot be satisfied for any combination of
Fig. I Example of plottingTEL A characteristic
reclosers settings
over Tee of downstream device.
solution exists, i.e, for a certain range of Tee satisfies
all mentioned criteria.
3. Task formalisation
In the latter case among available solutions the one
The following input parameters are taking into account having the highest pickup currents and the lowest tripping
while calculating the shape of the TELA time-current curve: times is selected.
the structure of the feeder: the lengths of lines sections,
the points of branching, fuses and reclosers locations,
4. Software implementation
physical and geometric parameters of the lines The protection settings automatic calculating algorithms
the data on the load connection points and on the load are included in the new version of the Tavrida Electric user
power software
maximum clearing and minimum melting time-current TELUS 3.0. User is provided with the special
characteristics of the applied fuses visual-style editor, which allows him drawing feeder
maximum phase-to-phase and phase-toground fault schematic (Fig. 2) and specify the protection settings
resistance, which must be treated by the protection as a fault calculating criteria. The time-current characteristics of the
peak load coefficient slow, fast and sensitive elements of the overcurrent and the
cold load coefficient earth-fault protections are then automatically calculated
maximum arcing time limiting duration of fault almost immediately (Fig. 3 - Fig. 6).
clearance (even sacrificing coordination with the downstream The user is allowed to correct the value of any setting of
fuse) any recloser. However, the automatic checking takes place to
grade margins for current and time between neighboring verify that the new value still corresponds to the recloser-to-
reclosers as well as between reclosers and downstream fuses. recloser coordination conditions, line wires thermal stability
The following limitations are applied for calculation of criteria, minimal fault current and maximum load current
protection settings: conditions. The correspondent neighbour reclosers' settings
all reclosers shall provide protection against faults are automatically changed to meet the coordination criteria.
located at all sections located immediately below next All changes can be visually watched on the time-current
downstream reclosers(s) (if any) diagram windows (Fig. 3 - Fig. 6).
all reclosers shall be insensitive to maximum possible Designed protection settings are downloaded into
load current at the point of installation recloser simulation model, that implements then exactly the
all slow curves of all reclosers shall allow clearance of same software code as a real recloser. Afterward correctness
the downstream fuses (if fuse clearance time at particular of settings can be tested with the aid of feeder simulation
current does not exceed maximum arcing time) model. In order to do this fault model shall be added to
all fast curves of all reclosers shall provide maximum the system. Visually it looks as lighting sign (refer to Fig. 2).
2
CICED2008 Technical Session 3 Protection, Control, Communication and Automation of Distribution Network
1, -
'0 10
0 .1 0 .1
, o~-------:=,"-----=---~
l ID mil I.- IO~---.&..-----:::;:------=---~
l ID
Fig. 3 - Set of slow phase current TCC's for Fig. 5 - Set of slow earth fault TCC 's for
reclosers 1-4 calculated with the aid of reclosers 1-4 calculated with the aid of
autocoordination algorithm for feeder pictured in autocoordination algorithm for feeder pictured in
Fig. 2. Fig. 2.
t.s
to
D.l
10 -m 1[)Jl 1,-
Fig. 4 - Set of fast phase currents TeC's for reclosers 1-4 Fig. 6 - Set of fast earth fault TCC's for
calculated with the aid of autocoordination reclosers 1-4 calculated with the aid of
algorithm for feeder pictured in Fig. 2. autocoordination algorithm for feeder pictured in Fig. 2.
3
CICED2008 Technical Session 3 Protection, Control, Communication and Automation of Distribution Network
------------1"
microprocessor relay. Further tests of the real software code
(restoration of supply after second reclosure) . (including designed settings) with the aid of feeder model
r allow ensuring correctness of settings .
I. A , ete
120 On the basis of the above we conclude that this algorithm
presents extremely useful tool for protection engineers that may
1== = = ::::; Closed
change dramatically existing setting design practice .
80
I
60
References
I
40 [1] Oddbjorn Gjerde, Bjorn I. Langdal , Gerd Kjolle, Yngve
Aabo, "Utilisation of numerical protection and control
for a better handling of reliability of supply and
o 01:200
-02:400 03:600 04:800
Open
t. s
maintenance", Proceedings of the 18th International
R3 (la) - R3 (State) -
Conference and Exhibition on Electricity Distribution -
Fig.8 Position of main contacts and phase A CIRED , Turin, June 2005.
current seen by R3 during clearance of non- [2] IEEE PSRC Report "Distribution line protection
sustained downstream earth fault. practises - Industry survey results" , December 2002.