PowerCube 1000 Hybrid Power Solution

ICC330-H7-C1 Datasheet

Introduction

ICC330-H7-C1 is an outdoor cabinet system used for


solar/diesel/grid hybrid scenario, it integrates a HEX cooling
system. The system configures DCDU-450AN1, maximum 450 A
system capacity, supports 9 rectifiers, the equipment cabin
reserves 19-inch rack space for other equipments, occupies
small footprint, easy installation and deployment.

Features

 Small size, easy deployment


 Compact design for installation of equipment
 High rectifier efficiency up to 98%
 Rectifier modules are hot-swappable to simplify operation
 Intelligent battery management function helps to prolong
battery lifespan
 Easy installation & maintenance by front door design

Scenarios

 Outdoor ICC330-H7-C1

 Solar/diesel/grid hybrid system


Specifications
Product Type ICC330-H7-C1
Dimension (W × D × H) 650 mm × 820 mm × 1600 mm (including base and protruding part)
Base (W × D × H) 650 mm × 650 mm × 100 mm
Weight 115 kg (without rectifier modules and battery)
Installation Mode Ground installation
Cabling Mode From the bottom
System Maintenance Mode From the front
Cabinet Material Hull, inside frame, & base: steel
Cabinet color Light grey: RAL 7035
Grounding Bar 7 × M6, 1 × M8
Cable Entry Detail Cable entry from base of cabinet, 45 mm diameter holes, 3 left & 3 right
EMC EN 300386 Class A
Inner Rack & Space 20 U, 19-inch rack (according to the actual configuration of ATO pre-installation)
Equipment
Protection Level IP55 (EN 60529)
Cabin
Cooling Mode HEX: 150W/K
Inner Rack & Space NA
Battery Type NA
Battery Cabin
Protection Level NA
Cooling Mode NA
Power Model DCDU-450AN1
200-240/346-415 Vac, three-phase, 50/60 Hz or
AC Input 200 Vac to 240 Vac dual-wire, 50/60 Hz or
Input 200 Vac to 240 Vac single-phase, 50/60 Hz
DC1 Input -42 Vdc to -58 Vdc, Max. 300 A
Voltage -42 Vdc to -58 Vdc (typical: -48 Vdc )
Output
Capacity Max. 450 A
AC Output & Socket 1 × 10 A/16 A MCB, 1 × 10 A (maintenance socket, optional)
Power System
Battery Branch 2 × 250 A Fuse
LLVD Branch 2 × 80 A MCB, 2 ×63A MCB (LLVD1)
BLVD Branch 1 × 63 A MCB, 4 × 32 A MCB, 2 × 16 A MCB (LLVD2)
AC Input According to the ACDU or ATS
SPD
DC Output 10/20 kA (8/20 μs)
Signal Input & Output 6 DI, 2 AI, 1 SMOKE, 1 TEM_HUM, 1 WATER, 8 DO etc. (according to actual configuration)
Noise ≤ 65 dB(A) @ 1.5 m, satisfy the GR487 standard (under the condition of 45ºC)

Optional Lighting LED


Accessories Sensor Smoke, water, door switch, temperature & humidity etc.
Operating Temperature -20 ºC to +45 ºC + solar radiation

Environment Storage Temperature -40 ºC to +70 ºC


Operating Relative Humidity 5% to 95% (no condensation)
Altitude 0 to 4000 m (1 ºC per 200 m temperature derating from 2000 to 4000 m)

Remark:
 DCDU: Direct Current Distribution Unit  SPD: Surge Protective Device

 DC1 Input: 3rd part DC input, such as: solar energy input, reused existing -48V DC power input etc.

Copyright © Huawei Technologies Co., Ltd. 2016. All rights reserved. HUAWEI TECHNOLOGIES CO., LTD.
No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Technologies Co., Ltd. Huawei Industrial Base
General Disclaimer Bantian Longgang
The information in this document may contain predictive statements including, without limitation, statements regarding the future financial and operating Shenzhen 518129, P.R. China
results, future product portfolio, new technology, etc. There are a number of factors that could cause actual results and developments to differ materially
from those expressed or implied in the predictive statements. Therefore, such information is provided for reference purpose only and constitutes neither an Tel: +86-755-28780808
offer nor an acceptance. Huawei may change the information at any time without notice.