ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
CONTENTS PAGE
1 SCOPE 2
2 TECHNICAL REQUIREMENTS TO BE SPECIFIED BY THE ENGINEER 2
3 DEFINITIONS 2
4 REQUIREMENTS 3
4.1 WELDING CONSUMABLES 3
4.2 CERTIFICATION 3
4.3 MATERIALS 3
4.4 MATERIALS SUBSTITUTION 3
4.5 CORROSION PROTECTION 4
4.6 DRAWINGS 4
4.7 CONSTRUCTION 4
4.8 WELDING 5
4.9 SPAN OF GRATING 5
4.10 TOLERANCES 6
4.11 PANEL SIZE 6
4.12 FLOORING PATTERN 8
4.13 FIXING OF FLOOR GRATING PANELS 9
4.14 LANDING OF FLOORING 12
4.15 BANDING 13
4.16 KICK PLATES 15
4.17 STAIR TREAD 16
4.18 FLOORING PANELS 17
4.19 CLOSING OF EXISTING REDOUNDED EQUIPMENT OPENINGS 24
4.20 HANDRAILING 25
5 QUALITY ASSURANCE PROVISIONS 37
5.1 QUALITY MANAGEMENT 37
5.2 QUALITY PLAN 37
5.3 TEST FACILITIES 37
5.4 INSPECTION 37
6 TEST AND INSPECTION METHODS 37
7 MARKING AND IDENTIFICATION 37
7.1 GENERAL 37
7.2 STAMP IDENTIFICATION 37
7.3 MARKING 38
APPENDIX A: RELATED DOCUMENTS 39
APPENDIX B: RECORD OF AMENDMENTS 39
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
1 SCOPE
This specification details the Anglo Coal South Africa requirements for the design,
fabrication, installation and maintenance of open grid grating for floors, stairways and
handrailing. It is not intended for mobile machinery.
3 DEFINITIONS
For the purpose of this specification the following definitions shall apply:
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
4 REQUIREMENTS
4.1 WELDING CONSUMABLES
4.2 CERTIFICATION
4.3 MATERIALS
All materials shall comply with the following specifications, whichever is applicable:
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
Corrosion protection shall be by hot dip galvanising to SANS 121/ISO 1461. For
particularly corrosive environments it is recommended that the flooring panels be hot dip
galvanised to SANS 121/ISO 1461 followed by dipping in black bitumen in accordance
with the requirements of SANS 1137.
Should any shaping of the panel be carried out after the application of the corrosion
protection, the appropriate area shall be made good by wire brushing and hand painting
two coats of Zinc Chromate Type 1, complying with SANS 679. If the panel also had a
coat of bitumen before shaping, the two coats of Zinc Chromate Type 1 shall be followed
by one coat of bitumen.
4.6 DRAWINGS
4.7 CONSTRUCTION
4.7.1 Load–bearing bar or bearer bar is the load carrying member running between supports.
4.7.2 Transverse bar is the member at right angles to load bearing bars to provide lateral
restraint.
4.7.3 Maximum pitch of bars (unless otherwise specified on the approved drawings), shall
be:
Load-bearing bars - 50 mm
Transverse bars - 50 mm
30 and 40mm
Grating shall not support any form of equipment (e.g. pipe bracket, lifting slings etc.)
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
Where the surrounding panels have deeper bearer – bars the new panel shall have the
same depth.
Where the surrounding panels have bearer – bars with a depth of less than 30mm
sufficient panels shall be replaced to blend smoothly into 30 mm deep bearer – bars.
By this it is intended that all panels up to a natural break in the floor, where a change in
panel depth will not be noticed, must be replaced.
Welding design shall comply with the requirements of SANS 0162 and welding practice
shall comply with the requirements of BS 5135.
Every third bearer bar shall be welded on one side only to the banding, kick plate or side
plate using a 3mm continuous fillet weld equal in length to the depth of the bar.
Every third transverse bar shall be welded all round to the banding or kick plate using a
3mm continuous fillet weld. All other intermediate transverse bars shall be tack welded to
the top of banding/kick plates.
The span shall be based on the manufacturer of the grating’s recommendations, usually
contained in a table in their catalogues. The minimum imposed floor loads listed below
shall be used to decide which table to use (refer to Anglo American Specification 114001
Design Criteria for Steel Structures 4.6.2)
Where machinery or parts there of maybe placed during maintenance or change outs the
flooring shall be designed to resist a minimum concentrated load of 10kN.
Note: if these spans are not listed in the catalogue the suppliers must be consulted.
Grating shall not exceed the manufacture recommended maximum safe span for bearer
bars.
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
4.10 TOLERANCES
4.10.1 Maximum camber: (positive or negative) of any panel shall not exceed 10mm or 1/200 of
the span, whichever is the lesser.
4.10.2 Maximum clearance: between adjacent grating panels after erection shall not exceed
10,0mm.
4.10.3 The length and width of any panel: shall be within the tolerance of +0,0mm
and -5,0mm.
4.10.4 The out of squareness: measured diagonally across the corners of any panel shall not
exceed 5,0mm.
4.10.5 Longitudinal bow: parallel to the bearer bars of any panel shall not exceed 1/200 of the
span or 5mm whichever is the lesser before fastening panel to supporting steelwork.
4.10.6 Transverse bow: perpendicular to the bearer bars shall not exceed 5 mm before fastening
to supporting steelwork.
4.10.7 Bearer bars: shall have a thickness tolerance of +0,4mm to -0,1mm and a height tolerance
of +1,2mm to -0,0mm.
4.10.8 Width of stairtreads: shall be within the tolerance of ±5,0mm.
4.10.9 Lengths of stairtreads: shall be within the tolerance of +0,0mm, -3,0mm.
4.10.10 Landing of flooring: on supporting steelwork shall be not less than 50mm. In the case of
panels landing on channels, a seating/ledge angle may be necessary.
4.11 PANEL SIZE
Panels shall be made to the size of the opening that they are to fit in with the following
tolerances:
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
Main and transverse bars of adjacent panels shall be in line with each other.
Panels shall be securely fastened to the supporting steelwork at each corner or as close
as possible to each corner by the system described below.
The HILTI threaded stud, in conjunction with the saddle clamp, washer and nylock nuts
must be utilised. Special care must be taken not to over tighten the nuts. Should
excessive torque be applied, the stud will be pulled out of the support steel.
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
The length of a panel is defined as the spanning length of the bearer bars. Panels will be
securely fastened along the width of the panel and thus along the landing steelwork where
the bearer bars rest upon at intervals not greater than 1000mm.
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
Landing of flooring on supporting steelwork shall be not less than 50mm. In the case of
panels landing on channels, a seating/ledge angle may be necessary.
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
4.15 BANDING
All grating panels shall be provided with banding bars around the perimeter of the panel
except when
Every fourth bearer bar shall be welded on one side only to the banding, kick plate or side
plate using a 3mm continuous fillet weld equal in length to the depth of the bar.
Every fourth transverse bar shall be welded all round to the banding or kick plate using a
3mm continuous fillet weld. All other intermediate transverse bars shall be tack welded to
the top of banding/kick plates.
Care should be taken during detailing so that panel sizes are multiples of the grating
aperture dimensions. This is to ensure that the aperture at the panel perimeter, where
fixture must be done, is adequate for the securing system.
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
A flat bar 130mm x 8mm should be welded to the end or side of a floor panel as
appropriate. Note that 6mm thick kick plates are also acceptable but cutting will be
required given that it is a non standard flat section.
Kick plates shall be provided at all open edges of flooring including stair landing and
equipment openings. Kick plates are essential to prevent tools or other items from
dropping off platforms or walkways and causing injury.
Kick plate shall have a minimum height of 100mm above the flooring.
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
Note: Above detail shows K/FLT not less than 100mm above floor level.
A rectangular pattern bar grating with an abrasive nosing and side plates shall be
provided.
All stair treads shall be bolted to stair stringers using a minimum of 4 - M12 bolts with
self-locking nuts.
Nosing shall be a special non – slip edging, welded to the front edge of the stair tread.
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
Side plates shall have a minimum thickness of 4.5mm and shall be welded to the ends,
the stair tread and drilled for bolting to stringer.
Flooring panels shall be formed from approved open grid grating by cutting stock sheets
to the correct size and providing cut-outs, banding and kick plates as required. Before
forming, the panel’s accurate dimensions of the required size, cut–outs and supporting
steelwork must be determined and a drawing of the panel. These drawings must be filed
for future reference.
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
Where openings have been left in concrete floors due to equipment having been removed
and not replaced the following shall apply:
Handrail the area. This is the preferred method as it eliminates steps in flooring and
tripping hazards. This method shall be used wherever possible.
If removable covers are required use method as shown below.
This method shall only be used on openings smaller than 1500mm square.
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
4.20 HANDRAILING
Handrailing should preferably, and always in the case of stairs, be continuous, and should
have no obstruction on, above or near to it that might obstruct a hand moving along it. The
recommended clearance between a handrail and any wall or other obstruction behind or
below it is 65mm.
Handrailing to platforms, walkways, landings and unguarded edges of raised floors shall
not be less than 1100mm high above finished floor level. Handrailing to stairs shall have a
height of not less than 1100mm measured vertically from the top of the stanchion base
plate to the upper surface of the handrail. Refer to figure Typical Angular Handrailing
(Sheet 10 of 10).
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
The requirements of SANS ISO9001 shall apply. All optional requirements in SABS
ISO9001 shall be compulsory requirements for material supplied against this specification.
Contractors shall compile and submit a quality plan which shall be approved prior to
commencement of manufacture. The quality plan shall list all major works, specifications,
tests, methods of test, equipment to be used and acceptance/rejection criteria.
The Contractor shall provide test samples, qualified labour and approved testing
equipment for tests. If facilities are not available at Contractor's premises the Contractor
shall arrange for tests to be conducted by approved test authorities. The costs of all tests
shall be borne by the Contractor.
5.4 INSPECTION
The QAR shall have access at all reasonable times to those parts of the manufacturing
facilities engaged in the manufacture of articles to this specification. The QAR is
authorised to witness any stage of manufacture, tests and to inspect documentation. The
QAR is authorised to reject any items not complying with the requirements of this
specification. In the event of a dispute arising regarding the interpretation of test results
the decision of the Engineer shall be final.
The Contractor shall prepare marking drawings and supply one sepia print to the Engineer
for approval.
Each element shall be hard stamped in accordance with the requirements of the drawing.
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
7.3 MARKING
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.
ACSA SPECIFICATION 114012
ISSUE 2
DESIGN, FABRICATION, INSTALLATION AND
MAINTENANCE OF OPEN GRID GRATING FOR
FLOORS, STAIRWAYS AND HANDRAILING COPYRIGHT
Unless otherwise specified the latest issue of the following documents shall be deemed to form
part of this specification:
For information or comments on this document please contact M&T Risk & Assurance
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the information contained
therein, irrespective of the cause and quantum thereof.