The modular fieldbus system for automation
Bus Terminal
469
Bus Terminal
472 System overview 514 Bus Terminal Controllers 539 Safety terminals
474 Product overview
484 System description 516 Lightbus BC2000 539 TwinSAFE terminals KLx904
488 Features 516 PROFIBUS BC31x0, BX3100
494 Technical data 517 Interbus BC4000
517 CANopen BC5150, BX5100
518 DeviceNet BC5250, BX5200 606 System terminals
519 Modbus BC7300
Bus Terminal
519 RS232 / RS485 BC8xx0, BX8000 606 System terminals KL9xxx, KS9xxx
521 Ethernet TCP / IP BC9xx0, BX9000 617 Special terminals KLxxxx, KSxxxx
471
498 Bus Couplers 524 Bus Terminals digital I/O 620 Accessories
500 EtherCAT BK11x0, BK1250 526 Digital input KL1xxx, KS1xxx, 620 Connectors and cables
501 Lightbus BK2xx0 KM1xxx 623 Assembly aids
502 PROFIBUS BK3xx0, LC3100 540 Digital output KL2xxx, KS2xxx, 624 Marking material
504 Interbus BK4xx0 KM2xxx 625 Demokits
505 CANopen BK51xx, LC5100 626 Accessories radio technology
506 DeviceNet BK52x0, LC5200
508 ControlNet BK7000
508 CC-Link BK7150 564 Bus Terminals analog I/O
509 Modbus BK73x0 731 Software
509 Fipio BK7420 564 Analog input KL3xxx, KS3xxx,
510 SERCOS interface BK75x0 KM37xx 732 Configuration software KS2000
510 RS232 / RS485 BK8x00 582 Analog output KL4xxx, KS4xxx, 820 Programming system TwinCAT
511 Ethernet TCP / IP BK9xx0 KM4602
512 PROFINET BK9xx3
513 EtherNet / IP BK9x05
513 USB BK9500
590 Bus Terminals
special functions
Function fieldbus slave fieldbus slave fieldbus slave fieldbus slave fieldbus slave fieldbus slave, fieldbus slave, Building
with integrated with integrated Automation
IEC 61131-3 IEC 61131-3 Room
472 PLC PLC Controller
Power supply 1,750 mA 500 mA 1,750 mA 1,000 mA 500 mA 1,750 mA 1,000 mA 350 mA
Fieldbus plug (design plug (design plug (design plug (design direct to the plug (design plug (design 2 x RJ 45
connection depends on depends on depends on depends on spring-loaded depends on depends on (switched)
the fieldbus) the fieldbus) the fieldbus) the fieldbus) terminals the fieldbus) the fieldbus)
Supported all only digital all all only digital all all all
Bus Terminals I/Os (except I/Os (except
KL15xx, KL15xx,
KL25xx, KL25xx,
KL2692, KL2692,
KL27x1) KL27x1)
Maximum 64 64 64 (255 with 64 (255 with 64 64 64 (255 with 64
number of terminal bus terminal bus terminal bus
Bus Terminals extension) extension) extension)
Electrical between between between between PROFIBUS: yes, between between between
isolation fieldbus / fieldbus / fieldbus / fieldbus / CANopen and fieldbus / fieldbus / fieldbus /
power power power power DeviceNet: no power power power
contacts / contacts / contacts / contacts / contacts / contacts / contacts /
supply voltage supply voltage supply voltage supply voltage supply voltage supply voltage supply voltage
BECKHOFF New Automation Technology We reserve the right to make technical changes.
Embedded PC
Bus Terminal
fieldbus slave, fieldbus slave, Embedded PC, Embedded PC, Embedded PC, Embedded PC, Embedded PC,
with integrated with integrated fieldbus slave, with integrated with integrated with integrated with integrated
IEC 61131-3 PLC IEC 61131-3 PLC with integrated IEC 61131-3 PLC, IEC 61131-3 PLC, IEC 61131-3 PLC, IEC 61131-3 PLC,
IEC 61131-3 PLC Motion Control, Motion Control, Motion Control, Motion Control, 473
visualisation visualisation visualisation visualisation
128 kbyte 256 kbyte 64 Mbyte DDR2 64…128 Mbyte 256 Mbyte DDR 512 Mbyte DDR2 256 Mbyte…
SDRAM 1 Gbyte DDR
plug (design plug (design plug (design – optional, plug optional, plug optional, plug
depends on depends on depends on (design depends (design depends (design depends
the fieldbus) the fieldbus) the fieldbus) on the fieldbus) on the fieldbus) on the fieldbus)
64 (255 with 64 (255 with 64 (255 with 64 (255 with 64 (255 with 64 (255 with 64 (255 with
terminal bus terminal bus terminal bus terminal bus terminal bus terminal bus terminal bus
extension) extension) extension) extension) extension) extension) extension)
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Product overview Bus Couplers
BK3010 502
Bus Terminal
1.5 Mbaud
BK3100 502 BK3110 502 BK3120 503 BK3150 503 LC3100 503 BC3100 516 BC3150 516
12 Mbaud 12 Mbaud 12 Mbaud 12 Mbaud 12 Mbaud 12 Mbaud 12 Mbaud
BK5110 505 BK5120 505 BK5150 505 LC5100 506 BC5150 517
BK5151 506
BK5200 506 BK5210 507 BK5220 507 BK5250 507 LC5200 507 BC5250 518
BK7000 508
BK7150 508
BK9500 513
BECKHOFF New Automation Technology We reserve the right to make technical changes.
Embedded PC
Program memory Program memory CX80xx CX9xxx CX1010 CX50xx CX1020, CX1030
128 kbyte 256 kbyte
CX8010 190 optional (2)
Bus Terminal
BX3100 517
12 Mbaud
475
BX5200 518
BX8000 520 optional (2) optional (2) optional (2) optional (2)
(2) (2) (2)
BX8000 520 optional optional optional optional (2)
BC9020 521 BX9000 523 CX8090 191 CX9000 194 CX1010 202 CX5010 208 CX1020 212
BC9120 522 CX9010 196 CX5020 208 CX1030 214
2-channel switch
CX8093 191 optional (3) optional (3) optional (2) optional (3)
CX8095 191 optional (3) optional (3) optional (2) optional (3)
(1)
via modular fieldbus interface, (2) via system interface, (3) via software library
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Product overview Bus Terminals
24 V DC KL1002 | KS1002 529 KL1012 | KS1012 529 KL1104 | KS1104 528 KL1114 | KS1114 528
filter 3.0 ms filter 0.2 ms filter 3.0 ms filter 0.2 ms
sensor supply
KL1302 | KS1302 529 KL1312 | KS1312 529 KL1304 | KS1304 528 KL1314 | KS1314 528
filter 3.0 ms, type 2 filter 0.2 ms, type 2 filter 3.0 ms, type 2 filter 0.2 ms, type 2
KL1402 | KS1402 529 KL1412 | KS1412 529 KL1404 | KS1404 527 KL1414 | KS1414 527
filter 3.0 ms, type 3 filter 0.2 ms, type 3 filter 3.0 ms, 4 x 2-wire connection filter 0.2 ms, 4 x 2-wire connection
4 x 2-wire connection
KLxxxx: Standard Bus Terminals, KSxxxx: Bus Terminals with pluggable wiring level
EN 61131-2 specification: www.beckhoff.com/EN61131-2
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KM1xxx
Bus Terminal
KL1872 529 KM1004 534
filter 0.2 ms, flat-ribbon cable, type 3 filter 3.0 ms, 32-channel
KM1018 534
filter 0.2 ms, 64-channel
KL1819 527
filter 0.2 ms, type 3
KL1859 527
8 inputs, 8 outputs, filter 3.0 ms, type 3, IMAX = 0.5 A
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Product overview Bus Terminals
KL2212 | KS2212 543 KL2442 542 KL2404 | KS2404 541 KL2424 | KS2424 541
Bus Terminal
IMAX = 0.5 A, diagnostic, 2 x 4 A/1 x 8 A IMAX = 0.5 A, 4 x 2-wire IMAX = 2.0 A, 4 x 2-wire
KL2904 563
TwinSAFE, 4 safe outputs
478
24 V AC/DC KL2784 | KS2784 547 KL2794 | KS2794 547
IMAX = 2.0 A, solid state relay IMAX = 2.0 A, solid state relay
no power contacts
DC motor KL2532 | KS2532 561 KL2552 | KS2552 561 KL2284 | KS2284 561
output stage 24 V DC, 1 A 50 V DC, 5 A IMAX = 2.0 A, reverse switching
KLxxxx: Standard Bus Terminals, KSxxxx: Bus Terminals with pluggable wiring level
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KM2xxx
KL2408 | KS2408 540 KL2872 543 KL2872-0010, IMAX = 0.5 A, 546 KM2002 544
IMAX = 0.5 A IMAX = 0.5 A, flat-ribbon cable flat-ribbon cable, negative switching IMAX = 0.5 A, 16-channel
Bus Terminal
8 inputs, 8 outputs, filter 3.0 ms, IMAX = 0.5 A, 64-channel
KM2604 550
relay, 16 A, 4-channel
KM2614 550
relay, 16 A, 4-channel, manual operation
KM2774 553
triac outputs for 4 blind motors
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Product overview Bus Terminals
0...10 V KL3061 | KS3061 566 KL3062 | KS3062 566 KL3162 | KS3162 567 KL3064 | KS3064 566
single-ended, 12 bit single-ended, 12 bit 16 bit, 0.05 % single-ended, 12 bit
Bus Terminal
± 10 V KL3001 | KS3001 564 KL3002 | KS3002 564 KL3102 | KS3102 565 KL3404 | KS3404 565 KL3408 | KS3408 565
differential input, 12 bit differential input, 12 bit differential input, 16 bit single-ended, 12 bit single-ended, 12 bit
480
KL3132 | KS3132 565
16 bit, 0.05 %
0...20 mA KL3011 | KS3011 568 KL3041 | KS3041 569 KL3012 | KS3012 568 KL3112 | KS3112 569 KL3044 | KS3044 568 KL3448 | KS3448 569
differential input, 12 bit with sensor supply, 12 bit differential input, 12 bit differential input, 16 bit single-ended, 12 bit single-ended, 12 bit
4...20 mA KL3021 | KS3021 570 KL3051 | KS3051 571 KL3022 | KS3022 570 KL3122 | KS3122 571 KL3054 | KS3054 570 KL3458 | KS3458 571
differential input, 12 bit with sensor supply, 12 bit differential input, 12 bit differential input, 16 bit single-ended, 12 bit single-ended, 12 bit
Resistance KL3201 | KS3201 572 KL3202 | KS3202 573 KL3222 572 KL3204 | KS3204 573 KL3208-0010 573
thermometer PT100…1000, Ni100, PT100…1000, Ni100, PT100, 4-wire connection, PT100…1000, Ni100, PT1000, Ni1000, PTC
self-calibration
measuring, -100…+100 hPa measuring, up to 340 hPa 7,500 hPa -1,000…+1,000 hPa
KLxxxx: Standard Bus Terminals, KSxxxx: Bus Terminals with pluggable wiring level
BECKHOFF New Automation Technology We reserve the right to make technical changes.
Analog output: KL4xxx | KS4xxx KM4xxx
Signal
1-channel 2-channel 4-channel 8-channel 2-channel
0...10 V KL4001 | KS4001 584 KL4002 | KS4002 584 KL4004 | KS4004 584 KM4602 585
12 bit, potential-free output 12 bit 12 bit, no power contacts 12-bit manual/automatic
operation
Bus Terminal
± 10 V KL4031 | KS4031 582 KL4032 | KS4032 582 KL4034 | KS4034 583
12 bit, potential-free output 12 bit 12 bit, no power contacts
481
KL4434 | KS4434 583 KL4438 | KS4438 583
12 bit 12 bit
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Product overview Bus Terminals
Special functions: KL | KS5xxx, KL | KS6xxx Power terminals: KL8xxx Safety terminals: KLx904
Signal Signal Signal
Position KL5001 | KS5001 590 KL5051 | KS5051 590 400 V AC 3~ KL8001 604 24 V DC KL1904 539
measurement SSI encoder interface bidirectional SSI switching capacity 5.5 kW, TwinSAFE,
KL5101 | KS5101 592 KL5111 | KS5111 593 connection mechanism for input terminal,
incremental encoder incremental encoder Siemens contactors (Sirius IEC 61508 SIL 3 and
Communi- KL6001 | KS6001 594 KL6031 | KS6031 594 for Schneider TeSys U 4-channel digital
KL6781 602
M-Bus master terminal
KLxxxx: Standard Bus Terminals, KSxxxx: Bus Terminals with pluggable wiring level
BECKHOFF New Automation Technology We reserve the right to make technical changes.
System terminals: KL9xxx | KS9xxx
Signal System Signal Potential supply Power supply and
accessories
System KL9010, bus end terminal 610 24 V DC KL9100 | KS9100 606 KL9400 | KS9400 612
KL9020 610 input 24 V DC,
Bus Terminal
adapter terminal for power terminal KL8xxx KL9200 607 KL9508 | KS9508 613
KL9070 | KS9070, shield terminal 607 with fuse input 24 V DC,
surge filter terminal for field supply 120...230 V AC KL9150 | KS9150 606
for analog terminals KL9160 | KS9160 606
KL9550 | KS9550 615 diagnostic
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Potential feeder terminals enable
to set up different potential groups.
Bus Coupler:
the link between
Bus Terminals
and fieldbus
Bus Terminals in
1-, 2-, 4-, 8- and
16-channel modularity
with combinations
of any desired types
of signal
fieldbus devices with fixed input/output con- market, connection systems. It is no longer necessary
figurations and design often make it neces- – SERCOS interface, the bus from to wire the field devices between the first
sary to use an entire group of devices with the drives engineering field, terminal connection in the control cabinet
484 similar functions. This costly method of signal – RS232/RS485, the network for or in the terminal box and the controller.
acquisition gives rise to high material, instal- the most economical solution, This significantly reduces the costs involved
lation, planning and documentation costs as – Ethernet TCP/IP, the network bus, in controller design and saves space, mate-
well as high costs for subsequent modifica- – Ethernet/IP, Industrial Ethernet solution rial, work, and money.
tion or expansion. Inventory management from ODVA, The field devices can be wired using the
and service staff are put under unnecessary – PROFINET, Industrial Ethernet solution Beckhoff Bus Terminal system on site where
strain. from PNO, the signals occur. Installation and wiring of
– USB, the fast interface for the the Beckhoff Bus Terminal is thus simple like
Flexible and stable laboratory. that of a standard terminal block. The Bus
The Beckhoff Bus Terminal is an open and With the master terminals, fieldbus function- Terminal can be connected to the controller
fieldbus-neutral I/O system consisting of elec- alities are also available in form of a standard by connecting a Bus Coupler via the fieldbus
tronic terminal blocks. The head of an elec- Bus Terminal. This is particularly advanta- as required.
tronic terminal block is the Bus Coupler with geous for bus systems that are integrated The Beckhoff Bus Terminals have been
the interface to the fieldbus. Bus Couplers are as subsystems into a higher-level system. tried and tested in a wide range of sectors
available for the following bus systems: It means that only one system is required for worldwide, from machine construction to
– EtherCAT, the high-speed Ethernet the subsystem and for the higher-level bus building management. Beckhoff Bus Termi-
fieldbus, interface. Master terminals are available for nal technology makes design, construction,
– Lightbus, the fast fibre optic fieldbus, the following bus systems: wiring, commissioning and maintenance of
– PROFIBUS DP/FMS, conforms to – AS-Interface, the sensor/actuator bus equipment and machines very cost-effective.
the European standard EN 50170, for the lower control level,
– Interbus, which has been on – EIB, LON, DALI, MP-Bus, M-Bus, i.e. Design
the market since 1987, the communication standards in building The robust housing, secure contacts and the
– CANopen, multi-masters in automation. solidly built electronics are prominent fea-
the actuator/sensor area, tures of our components. A station consists
– DeviceNet, the device bus Automation standard of one Bus Coupler and up to 64 electronic
with CAN technology, The Beckhoff Bus Terminal ensures that terminal blocks. With the K-bus extension it
– ControlNet, the standardised fieldbus, control cabinets and terminal boxes are con- is possible to operate up to 255 Bus Termi-
– Modbus, the open fieldbus, structed more economically. Using the 4-wire nals on one Bus Coupler.
BECKHOFF New Automation Technology We reserve the right to make technical changes.
Operation of up to 64 Bus Terminals
on one Bus Coupler (255 with K-bus Bus end
extension KL9020 and KL9050) terminal
The electronic terminal blocks are clipped serial interfaces in accordance with RS232, machinery equipped with Beckhoff Bus
onto the Bus Coupler. They connect by RS485 or 20 mA TTY. Terminals offer significant competitive
simply latching together. This means that The fine granularity of the Bus Termi- advantages.
Bus Terminal
each electronic terminal block can be nals enables bit-precise composition of the
exchanged separately and can be mounted required I/O channels. The digital Bus Termi- Project engineering and
on a standard mounting rail. In addition to nals are available as 2-, 4-, 8- or 16-channel parameterisation
horizontal type mounting, all other mounting terminals. In the 16-channel variant, digital If the TwinCAT automation software 485
types are permitted in the majority of the input and output signals are arranged in an from Beckhoff is used, the I/O stations
cases. ultra-compact way within a standard Bus Ter- can be integrated and parameterised
The Beckhoff Bus Terminal with its out- minal housing across a width of only 12 mm. conveniently via the TwinCAT System
side contour adjusts perfectly to the measure- The standard analog signals of -10…+10 V, Manager. As a “configuration centre”,
ments of terminal boxes. The clear front panel 0…+10 V, 0…20 mA and 4…20 mA are all the System Manager links the PLC pro-
of the terminal with light-emitting diodes for available as 1-, 2-, 4- and 8-channel variants grams and the connected I/O channels.
status display, plug-in contact labelling and within a standard housing. The system is thus
detachable labelling fields guarantee clarity. highly modular and can be projected cost-
The 3-wire system supplemented by a protec- effectively with an accuracy down to a single
tive conductor terminal makes it possible to channel.
wire sensors/actuators directly. The KMxxxx terminal modules with
plug-in wiring combine 16, 32 or 64 digital
Free mix of signals I/Os within a very small space and with high
The Beckhoff I/O system supports about packing density.
400 Bus Terminals and is thus probably the
most comprehensive system on the market. Economical and small
The components enable users to operate For the user, Beckhoff Bus Terminals offer
mixed signal configurations without restric- independence from the particular fieldbus
tion at each station. This means that a single and terminal block design. Digital and analog
non-central input/output node can map all signals can be mixed without restriction,
the necessary signals. starting with one or two signals per terminal.
Appropriate Bus Terminals are avail- They replace manufacturer-specific designs
able for any digital or analog automation and all the intermediate terminal positions.
signal type, for currents and voltages with The Bus Terminal ensures transparency and
standardised signal levels and for PT100 flexibility. Distributors and terminal boxes
and thermocouple signals. Intelligent devices become smaller, more economical, and
can be connected via Bus Terminals with in some cases can be omitted. Plants and
We reserve the right to make technical changes. BECKHOFF New Automation Technology
KLxxxx | The standard KL type The Bus Terminals with 16 terminal KSxxxx | The KS series Bus Terminals feature a pluggable
Bus Terminals include electronics points offers a very high packing connection level enabling the complete wiring to be removed
and connection level in a single housing. density in 12 mm. as a plug connector from the top of the housing for servicing.
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KMxxxx | The KM type terminal modules
feature pluggable wiring, combining
16, 32 or 64 digital I/Os in a very small
area with high packing density.
Bus Terminal
tral and can therefore be oper- types such as digital I/Os. Interface standards
ated with any Beckhoff Bus Cou- The very compact digital KM1xxx within the Bus Terminal 487
pler or Bus Terminal Controller. and KM2xxx input/output ter- In addition to plug-in wiring,
Like the standard Bus Terminals, minal modules have 16, 32 or sensor-specific plug connectors
the KM modules are integrated 64 channels. Each I/O connec- such as D-sub, RJ 45 or BNC sim-
in the I/O system and connected tor has eight inputs or outputs. plify the application of the Bus
with the internal terminal bus LEDs integrated in the connector Terminal system. Sensors and
(K-bus). Bus Terminals and ter- indicate the signal state for each actuators with pre-assembled
minal modules can be combined channel directly at the wire. connectors can be connected
without restriction. Depending on the connection directly and quickly with the Bus
More sensor and actuator func- Like for the Bus Terminals, type, the terminal modules are Terminal system.
tionality makes machines and no tools are required for the available with 1- or 3-pin plug Relay or power modules are
systems more and more power- wiring. Spring-loaded terminals connector and enable connection also available, which are either
ful. The Bus Terminal reliably are used, however with con- with 1, 2 or 3 wires. equipped with standard relays
meets increased requirements nectors (cable cross section or with integrated electronics to
for I/O signals through its modu- 0.5…1.5 mm²). Customer-specific connect wattages up to 16 A.
larity and compact design. The The terminal modules com- signal mix
existing Bus Terminal system is bine 16, 32 or 64 digital inputs In addition to the standard I/O
complemented by the compact or outputs on a very small area. types, the terminal modules
version of the KMxxxx terminal This compact and slimline design are also available as customer-
module with increased pack- enables very high packing densi- specific types, e.g. for use in
ing density. In many areas of ties, leading to smaller control production machines with
application, cost benefits can be cabinets and terminal boxes. identical I/O combinations.
realised through lower overall The combination terminal mod-
installed size and application- Digital l/O modules ules consolidate typical automa-
specific signal mix. with up to 64 channels tion signal combinations. This
The terminal modules are The KM modules are used, for enables smaller physical size
fully system-compatible. Like the example, in applications with and quantity of parts with sig-
Bus Terminals, they are bus-neu- high demand for standard signal nificant cost savings.
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Bus Terminal features
Assembly on 35 mm DIN
mounting rail with no
accessories
Ethernet TCP/IP
BECKHOFF New Automation Technology We reserve the right to make technical changes.
Screwless connection:
using the reliable spring-
loaded technique with
vertical cable inlet
Bus Terminal
strip; release slide does not
require a tool.
489
DALI
The 4-wire terminating
system (signal, 24 V DC,
MP-Bus 0 V, PE) reduces assembly
costs.
EIB LON
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Beckhoff Bus Terminals:
The complete automation kit
490
BECKHOFF New Automation Technology We reserve the right to make technical changes.
3-phase power Integrated safety:
measurement capability the TwinSAFE Bus Bus end terminal
enables all relevant Terminals enable
electrical data of the the connection of all
supply network to be common safety sensors
measured. and actuators.
Bus Terminal
The terminal bus extension
enables the connection of up to
255 Bus Terminals (instead of 64)
to a single station.
491
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Via the K-bus extension, the Bus Coupler The coupler terminal Operation of Bus end
“Economy plus” enables the connection KL9050 starts a further up to 64 Bus terminal
of up to 255 Bus Terminals. remote bus terminal block. Terminals KL9010
Operation of
up to 64 Bus
Terminals K-bus extension via
screened Industrial Ethernet
cable with two RJ 45 plugs
(distance up to 5 m)
Bus Coupler, any number of terminals The extension is transparent for the fieldbus a coupler terminal KL9050. This coupling
between 1 and 64, and a bus end terminal. and higher-level systems. works at up to 31 stations.
The “Economy plus” and “Compact” series The system of Bus Coupler and Bus The maximum distance between two
492 support all Bus Terminals of the Beckhoff Terminal can be extended by replacing the Bus Terminal blocks is 5 m and allows a
system. It is also possible to operate up to end terminal KL9010 with the extension total extension of 155 m. The system uses
255 Bus Terminals on this Bus Coupler series KL9020. The KL9020 makes available the screened Industrial Ethernet cables with two
with the K-bus extension. K-bus signals in a RJ 45 socket for trans- RJ 45 plugs for the transmission. The cable
The Bus Terminal extension allows Bus mission onwards via a screened Industrial is supplied ready-made in different lengths
Terminals to be located in up to 31 blocks Ethernet cable. or can be made-to-measure for applications
in the control cabinet or in the application. The coupler terminal KL9050 starts a fur- with conventional Ethernet tools.
With a distance of up to 5 m between the ther remote Bus Terminal block and provides Data transfer is based on the interfer-
Bus Terminal blocks, the Bus Terminal system the logical connection to the Bus Coupler ence-free and RS485 industry standard in
can be used over a wider area and helps save via the Ethernet cable. 24 V DC, electrically a double-screened cable.
costs. isolated, for the field level can be input at
The Bus Coupler recognises the terminals this coupler terminal. The internal K-bus
to which it is connected, and performs the shares the same potential as the K-bus of
assignment of the inputs and outputs to the the coupler. The KL9050 can be used via
Operation with up to 64 Bus Terminals to one Operation with up to 255 Bus Terminals to one Bus Coupler with terminal bus extension
Bus Coupler with KL9010 bus end terminal end terminal KL9020 and coupler terminal KL9050
BECKHOFF New Automation Technology We reserve the right to make technical changes.
The TwinSAFE Bus Terminals Certification: all TwinSAFE devices The KL6904 TwinSAFE Logic Bus Terminal enables communication with
enable the connection of all are subjected to a prototype up to 15 TwinSAFE devices. The Bus Terminal features certified safety
common safety sensors and test according to IEC 61508 and blocks for functions such as emergency stop, safety door monitoring,
actuators. DIN EN ISO 13849-1:2008 PLe. etc. In addition, the TwinSAFE Logic Bus Terminal has four safe digital
24 V DC outputs.
The KL2904 Safety Bus Terminal is a digital output terminal with four chan- The KL1904 digital input terminal for sensors with potential-free contacts
nels. The terminal switches 24 V DC actuators with up to 0.5 A total current. for 24 V DC: the Safety Bus Terminal has 4 fail-safe inputs.
Bus Terminal
TwinSAFE from Beckhoff provides a con- – KL2904 | 4-channel digital output
sistent hardware and software technology – KL6904 | TwinSAFE Logic Bus Terminal
for achieving integrated and simplified with 4 digital outputs
handling, ranging from safe input and 493
output terminals and safe miniature For further information on TwinSAFE and
controllers for the Bus Terminal system the TwinSAFE products see page 856
and the AX5000 Servo Drives to the PC-
based Safety PLC.
K1 K3 K1 K2
K2 K4 K3 K4
PROFIBUS
Open control technology for safety integration: the TwinSAFE protocol enables transfer of safety-relevant
data via any medium.
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Bus Coupler Housing
43 mm
94 mm
46 mm
100 mm
100 mm
100 mm
100 mm
15 mm
18 mm
47 mm 42 mm 81 mm 21 mm
49 mm 44 mm
BKxxxx, BCxxxx BKxx50, BCxx50 BXxxxx LCxxxx
requires, automatically implement a continued connection, carrying the potential of the power circuit to the next Bus Terminal. The supply voltage
that is connected to the Bus Coupler spring-loaded terminals is 24 V DC. If a different voltage is required for the power contacts, the appropriate
power feed terminal must be inserted after the Bus Coupler.
494
BECKHOFF New Automation Technology We reserve the right to make technical changes.
Bus Terminal Housing
46 mm
46 mm
46 mm
46 mm
46 mm
100 mm
100 mm
100 mm
100 mm
100 mm
18 mm
18 mm
18 mm
18 mm
18 mm
12 mm 24 mm 12 mm 12 mm 12 mm
Bus Terminal
and can have a variety of voltages. Care should be taken to ensure that a change in voltage always starts with a power feed terminal.
Mechanical data KLxxxx KL5101 KL5102 KSxxxx KLx80x, KLx81x, KL1862, 495
KLx889 KLx872
Design form compact terminal compact terminal compact terminal terminal housing compact terminal compact terminal
housing with housing with housing with with pluggable housing with housing with
signal LED signal LED signal LED wiring level signal LED signal LED
Material polycarbonate
Dimensions (W x H x D) 12 mm x 100 mm 24 mm x 100 mm 24 mm x 100 mm 12/24 mm x 12 mm x 100 mm 12 mm x 100 mm
x 68 mm x 68 mm x 68 mm 100 mm x 71 mm x 68 mm x 68 mm
Installation on 35 mm DIN rail, conforming to EN 50022 with lock
Side by side mounting by double slot and key connection
means of
Marking standard terminal standard terminal standard terminal standard terminal – standard terminal
block marking block marking block marking block marking block marking
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
We reserve the right to make technical changes. BECKHOFF New Automation Technology
KM Housing
46 mm
46 mm
100 mm
100 mm
18 mm
18 mm
24 mm 51 mm 73 mm 35 mm
26.5 mm 71 mm 75 mm 55 mm
KM10x2, KM10x4, KM20x4
KM20x2
spring-loaded terminals are used and no tools are required for the wiring.
496
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KM Housing
46 mm
100 mm
18 mm
121 mm 35 mm
123 mm 55 mm
KM10x8, KM20x8
Bus Terminal
497
Connection KMx0x8
Wiring spring-loaded technique
Connection cross-section 0.08…1.5 mm², stranded wire, solid wire
Stripping length 8 mm
Power contacts none
Nominal voltage depends on Bus Terminal type, max. 60 V DC
We reserve the right to make technical changes. BECKHOFF New Automation Technology
BKxxxx | Bus Couplers
Power LEDs
Bus Terminal
498
K-bus
Fieldbus connection
Power contacts
Address selector
Configuration
interface Input for power contacts
BECKHOFF New Automation Technology We reserve the right to make technical changes.
Standard | BKxx00 Economy | BKxx10 Economy plus | BKxx20 Compact | BKxx50 Low Cost | LCxx00
The Bus Couplers link the modularly expand- In addition to digital signal types, the +60 °C The Bus Terminal system has stood
able electronic terminal blocks with the “Economy plus” Bus Couplers also support -25 °C
the test of time in machine or build-
respective fieldbus systems. The Bus Coupler all other types. Up to 255 Bus Terminals can ing automation applications where a
performs all the monitoring and control tasks be connected via the K-bus extension. temperature range of 0 to 55 °C is sufficient.
that are necessary for operation of the con- The “Compact” Bus Couplers have a For requirements beyond that, the operating
nected Bus Terminals. particularly compact housing and also enable temperature range of selected standard Bus
The specific settings of analog and connection of up to 255 Bus Terminals via the Terminals and Couplers has been extended
multifunctional Bus Terminals are adapted to terminal bus extension. to -25 to +60 °C. The storage temperature of
the application via the KS2000 configuration The “Low Cost” Bus Couplers are these ET components (Extended Temperature
Bus Terminal
software. characterised by small dimensions and cost- Range) has also been adapted and is now
In the standard Bus Couplers a unit con- effective connection technology and enable -40 to +85 °C. The exact definition of the
sists of a Bus Coupler, any number of up to connection of up to 64 digital input/output operating conditions in temperature ranges
64 terminals and a bus end terminal. terminals. outside 0 to 55 °C, installation requirements 499
The “Economy” versions enable particu- that possibly deviate from the standard and,
larly cost-effective configuration of peripheral if applicable, deviating technical data can be
interfacing connections with up to 64 digital found in the documentation. Bus Couplers
input/output terminals. that have been qualified for the extended
temperature range are identified accordingly.
www. beckhoff.com/Bus-Coupler
We reserve the right to make technical changes. BECKHOFF New Automation Technology
EtherCAT BK1xxx
Max. number of bytes 1,024 byte input and 1,024 byte output
fieldbus
Current supply K-bus 1,750 mA 2,000 mA 500 mA
+60 °C
-25 °C
Bus Terminal
500
The BK1120 Bus Coupler connects The BK1150 Bus Coupler connects The BK1250 is a “Bus Coupler in
EtherCAT, the real-time Ethernet EtherCAT to the modular extendable terminal housing” for mixed applica-
system, with the modular, exten- Bus Terminals (K-bus). A unit consists tion of EtherCAT Terminals (ELxxxx)
dable electronic terminal blocks. of a Bus Coupler, any number of ter- and standard Bus Terminals (KLxxxx) in
A unit consists of a Bus Coupler, minals from 1 to 64 (with K-bus exten- a bus station. Up to 64 Bus Terminals
any number (between 1 and 64) sion: 255) and a bus end terminal. (with K-bus extension up to 255) can
of terminals (255 with K-bus exten- The “Compact” Bus Coupler offers be connected to a BK1250.
sion) and one end terminal. a cost-optimised alternative to the
BK1120 EtherCAT Bus Coupler.
BECKHOFF New Automation Technology We reserve the right to make technical changes.
BK20xx Lightbus
Max. number of bytes 512 byte input and 512 byte output 32 byte input and 32 byte output 512 byte input and 512 byte output
fieldbus
Current supply K-bus 1,750 mA 500 mA 1,750 mA
Bus Terminal
501
The BK2000 Bus Coupler connects The BK2010 „Economy“ variant per- With the K-bus extension technology,
the Lightbus system to the electronic mits particularly economical creation the “Economy plus” Bus Coupler
terminal blocks, which can be expanded of peripheral interfacing connections. BK2020 allows the connection of up to
in modular fashion. One unit consists Up to 64 digital input/output terminals 255 spatially distributed Bus Terminals
of one Bus Coupler, any number of up can be connected. to one Bus Coupler. The “Economy
to 64 terminals and one end terminal. plus” series supports all Beckhoff sys-
– distance between stations: tem Bus Terminals. It can process in its
– distance between stations: 45 m for APF fibre, full configuration 1,020 digital signals
45 m for APF fibre, 300 m HCS fibre and a maximum of 128 analog input
300 m HCS fibre and output channels per slave.
Bus interface 2 x standard fibre optic connector Z1000 2 x standard fibre optic connector Z1000 2 x standard fibre optic connector Z1000
(plastic fibre), Z1010 (HCS fibre) (plastic fibre), Z1010 (HCS fibre) (plastic fibre), Z1010 (HCS fibre)
Data transfer rates 2.5 Mbaud 2.5 Mbaud 2.5 Mbaud
Weight approx. 150 g approx. 130 g approx. 150 g
Operating temperature 0…+55 °C 0…+55 °C 0…+55 °C
Approvals CE, UL, Ex CE, UL, Ex CE, UL, Ex
Further information www.beckhoff.com/BK2000 www.beckhoff.com/BK2010 www.beckhoff.com/BK2020
Accessories
Cordsets and connectors see page 620 see page 620 see page 620
PC Fieldbus Cards FC200x 715 FC200x 715 FC200x 715
We reserve the right to make technical changes. BECKHOFF New Automation Technology
PROFIBUS BK3010, BK31xx
PROFIBUS Bus Coupler PROFIBUS DP/FMS Bus Coupler PROFIBUS Bus Coupler
for up to 64 digital Bus Terminals, for up to 64 Bus Terminals, for up to 64 digital Bus Terminals,
1.5 Mbaud 12 Mbaud 12 Mbaud
Max. number of bytes 64 byte input and 64 byte input and 64 byte output 64 byte input and
fieldbus 64 byte output (DP and FMS mode), 128 byte input 64 byte output
and 128 byte output (only DP mode)
Current supply K-bus 500 mA 1,750 mA 500 mA
Bus Terminal
502
The BK3010 „Economy“ variant per- The BK3100 Bus Coupler connects the The BK3110 „Economy“ variant per-
mits particularly economical creation PROFIBUS system to the electronic mits particularly economical creation
of peripheral interfacing connections. terminal blocks, which can be extended of peripheral interfacing connections.
Up to 64 digital input/output terminals in modular fashion. One unit consists of Up to 64 digital input/output terminals
can be connected. the Bus Coupler, any number of up to can be connected.
64 terminals and one end terminal.
Bus interface 1 x D-sub 9-pin socket 1 x D-sub 9-pin socket 1 x D-sub 9-pin socket
with shielding with shielding with shielding
BECKHOFF New Automation Technology We reserve the right to make technical changes.
BK3xxx, LC3100 PROFIBUS
PROFIBUS “Economy plus” PROFIBUS “Compact” PROFIBUS Bus Coupler PROFIBUS “Economy plus” PROFIBUS “Low Cost”
Bus Coupler for up to 64 Bus Bus Coupler for up to 64 Bus with fibre optic connection Bus Coupler for up to 64 Bus Bus Coupler for up to
Terminals (255 with K-bus Terminals (255 with K-bus for up to 64 Bus Terminals, Terminals (255 with K-bus 64 digital Bus Terminals,
extension), 12 Mbaud extension), 12 Mbaud 1.5 Mbaud extension), 12 Mbaud 12 Mbaud
+60 °C +60 °C
-25 °C -25 °C
Bus Terminal
503
The “Economy plus“ version The “Compact” Bus Coupler The particular feature of The particular feature for The LC3100 “Low Cost”
extends the existing PROFIBUS BK3150 for PROFIBUS the BK3500 Bus Coupler is the BK3520 Bus Coupler is Bus Coupler is marked by
Bus Coupler series BK3xx0. extends the Beckhoff its fibre optic connection. its fibre optic connection a smaller design and a
The K-bus extension technology Bus Terminal system by a The fibre optics mean that and its high transmission more economical connec-
allows the connection of up to cost-optimised version in a the transmission is particu- rate of up to 12 Mbaud. tion method.
255 spatially distributed Bus compact housing. larly safe from interference
Terminals to one Bus Coupler. and has absolute electrical – distance between
isolation. stations: up to 40 m
– distance between
stations: up to 25 m
1 x D-sub 9-pin socket 1 x D-sub 9-pin socket 2 x HP-Simplex sockets 4 x HP-Simplex sockets connection via
with shielding with shielding (HP-Simplex plugs included) (HP-Simplex plugs ZS1031- Bus Terminal
3500 included)
automatic detection automatic detection automatic detection automatic detection up to 12 Mbaud
up to 12 Mbaud up to 12 Mbaud up to max. 1.5 Mbaud up to 12 Mbaud
approx. 170 g approx. 100 g approx. 170 g approx. 170 g approx. 100 g
-25…+60 °C -25…+60 °C 0…+55 °C 0…+55 °C 0…+55 °C
CE, UL, Ex, GL CE, UL, Ex CE, UL, Ex CE, UL, Ex CE, UL, Ex
www.beckhoff.com/BK3120 www.beckhoff.com/BK3150 www.beckhoff.com/BK3500 www.beckhoff.com/BK3520 www.beckhoff.com/LC3100
see page 620 see page 620 see page 620 see page 620 see page 620
FC310x 716 FC310x 716 FC310x 716 FC310x 716 FC310x 716
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Interbus BK40xx
Interbus Bus Coupler Interbus Bus Coupler Interbus “Economy plus” Bus Coupler
for up to 64 Bus Terminals for up to 64 digital Bus Terminals for up to 64 Bus Terminals
(255 with K-bus extension)
Max. number of bytes 64 byte input and 64 byte output 8 byte input and 8 bytes output 64 byte input and 64 byte output
fieldbus
Current supply K-bus 1,750 mA 500 mA 1,750 mA
Bus Terminal
504
The BK4000 Bus Coupler connects the The BK4010 „Economy“ variant per- With the K-bus extension technology,
Interbus bus system to the electronic mits particularly economical creation the “Economy plus” Bus Coupler
terminal blocks, which can be extended of peripheral interfacing connections. BK4020 allows the connection of up to
in modular fashion. One unit consists Up to 64 digital input/output terminals 255 spatially distributed Bus Terminals
of one Bus Coupler, any number of up can be connected. to one Bus Coupler. The “Economy
to 64 terminals and one end terminal. plus” coupler supports all Beckhoff
system Bus Terminals and can process
512 bit digital inputs and outputs per
slave.
Bus interface 2 x D-sub plug, 9-pin, plug and socket 2 x D-sub plug, 9-pin, plug and socket 2 x D-sub plug, 9-pin, plug and socket
with screening and vibration lock with screening and vibration lock with screening and vibration lock
Data transfer rates 500 kbaud 500 kbaud 500 kbaud
Weight approx. 170 g approx. 150 g approx. 170 g
Operating temperature 0…+55 °C 0…+55 °C 0…+55 °C
Approvals CE, UL, Ex CE, UL, Ex CE, UL, Ex
Further information www.beckhoff.com/BK4000 www.beckhoff.com/BK4010 www.beckhoff.com/BK4020
Accessories
Cordsets and connectors see page 620 see page 620 see page 620
PC Fieldbus Cards – – –
BECKHOFF New Automation Technology We reserve the right to make technical changes.
BK4500, BK51xx Interbus, CANopen
Interbus Bus Coupler CANopen Bus Coupler CANopen “Economy plus” CANopen “Compact”
with fibre optic connection for up to 64 digital Bus Coupler for up to Bus Coupler for up to
for up to 64 Bus Terminals Bus Terminals 64 Bus Terminals 64 Bus Terminals
(255 with K-bus extension) (255 with K-bus extension)
+60 °C
-25 °C
Bus Terminal
505
The particular feature for the The BK5110 “Economy” variant With the K-bus extension technol- The “Compact” Bus Coupler
BK4500 Bus Coupler is its fibre optic permits particularly economical ogy, the “Economy plus” Bus Cou- BK5150 for CANopen extends the
connection. Its functions correspond creation of peripheral interfacing pler BK5120 allows the connection Beckhoff Bus Terminal system by a
to those of the BK4000 Bus Coupler connections. Up to 64 digital input/ of up to 255 spatially distributed cost-optimised version in a compact
in relation to the Bus Terminals and output terminals can be connected. Bus Terminals to one Bus Coupler. housing. Up to 64 Bus Terminals are
the fieldbus properties. The fibre The Bus Coupler works on the supported; with the terminal bus
optics mean that the transmission CAN protocol basis as defined in extension, up to 255 Bus Terminals
is particularly safe from interference, ISO 11898. can be connected. The CANopen
and has absolute electrical isolation. Bus Coupler offers automatic baud
rate detection up to 1 Mbaud and
two address selection switches for
address assignment.
2 x 2 FSMA plugs 1 x open style connector, 5-pin, 1 x open style connector, 5-pin, open style connector, 5-pin
included included
500 kbaud up to 1 Mbaud up to 1 Mbaud automatic detection up to 1 Mbaud
approx. 170 g approx. 130 g approx. 150 g approx. 100 g
0…+55 °C 0…+55 °C -25…+60 °C 0…+55 °C
CE, UL, Ex CE, UL, Ex, GL CE, UL, Ex, GL CE, UL, Ex
www.beckhoff.com/BK4500 www.beckhoff.com/BK5110 www.beckhoff.com/BK5120 www.beckhoff.com/BK5150
see page 620 see page 620 see page 620 see page 620
– FC510x 718 FC510x 718 FC510x 718
We reserve the right to make technical changes. BECKHOFF New Automation Technology
CANopen, DeviceNet BK5xxx, LC5100
CANopen “Compact” Bus Coupler CANopen “Low Cost” Bus Coupler DeviceNet Bus Coupler
for up to 64 Bus Terminals for up to 64 digital Bus Terminals for up to 64 Bus Terminals
(255 with K-bus extension) (255 with K-bus extension)
Max. number of bytes 16 Tx/Rx PDOs 5 Tx/Rx PDOs 512 byte input and 512 byte output
fieldbus
Current supply K-bus 1,000 mA 500 mA 1,750 mA
Bus Terminal
506
In contrast to the BK5150, the BK5151 The LC5100 “Low Cost” Bus Coupler is The BK5200 Bus Coupler connects the
has a 9-pin D-sub connector as a bus marked by a smaller design and a more DeviceNet bus system to the electronic
interface. economical connection method. All the terminal blocks, which can be extended
bit-oriented terminals can be connected in modular fashion. One unit consists of
to the LC5100. All the digital input and one Bus Coupler, any number of up to
output terminals are supported with 64 terminals and one end terminal.
the exception of the KL15xx, KL25x2,
KL2692 and KL27x1 terminals. All the
system terminals, with and without
diagnostics, can also be connected.
Bus interface D-sub 9-pin socket connection via Bus Terminal 1 x open pluggable connector, 5-pin,
included
Data transfer rates automatic detection up to 1 Mbaud up to 1 Mbaud automatic detection up to 500 kbaud
Weight approx. 100 g approx. 100 g approx. 150 g
Operating temperature 0…+55 °C 0…+55 °C 0…+55 °C
Approvals CE, UL, Ex CE, UL, Ex CE, UL, Ex
Further information www.beckhoff.com/BK5151 www.beckhoff.com/LC5100 www.beckhoff.com/BK5200
Accessories
Cordsets and connectors see page 620 see page 620 see page 620
PC Fieldbus Cards FC510x 718 FC510x 718 FC520x 720
BECKHOFF New Automation Technology We reserve the right to make technical changes.
BK52xx, LC5200 DeviceNet
DeviceNet Bus Coupler DeviceNet “Economy plus” Bus DeviceNet “Compact” Bus Coupler DeviceNet “Low Cost” Bus Coupler
for up to 64 digital Bus Terminals Coupler for up to 64 Bus Terminals for up to 64 Bus Terminals for up to 64 digital Bus Terminals
(255 with K-bus extension) (255 with K-bus extension) (255 with K-bus extension)
32 byte input and 32 byte output 512 byte input and 512 byte output 32 byte input and 32 byte output
Bus Terminal
507
The BK5210 “Economy” variant With the K-bus extension technology, The “Compact” Bus Coupler BK5250 The LC5200 “Low Cost” Bus Coupler
permits particularly economical the “Economy plus” Bus Coupler for DeviceNet extends the Beckhoff is marked by a smaller design and a
creation of peripheral interfacing BK5220 allows the connection of Bus Terminal system by a cost- more economical connection meth-
connections. Up to 64 digital input/ up to 255 spatially distributed Bus optimised version in a compact od. All the bit-oriented terminals can
output terminals can be connected. Terminals to one Bus Coupler. The housing. The DeviceNet Bus Coupler be connected to the LC5200. All the
“Economy plus” series supports all offers automatic baud rate detection digital input and output terminals
Beckhoff system Bus Terminals and it up to 500 kbaud and two address are supported with the exception
can process in its full configuration selection switches for address as- of the KL15xx, KL25x2, KL2692 and
1,020 digital signals and a maximum signment. A 5-pin connector for the KL27x1 terminals. All the system ter-
of 256 analog input and output fieldbus connection is included in the minals, with and without diagnostics,
channels per slave. scope of supply. can also be connected.
1 x open pluggable connector, 5-pin, 1 x open pluggable connector, 5-pin, open style connector, 5-pin connection via Bus Terminal
included included
automatic detection up to 500 kbaud automatic detection up to 500 kbaud automatic detection up to 500 kbaud automatic detection up to 500 kbaud
approx. 130 g approx. 130 g approx. 100 g approx. 100 g
0…+55 °C 0…+55 °C 0…+55 °C 0…+55 °C
CE, UL, Ex, GL CE, UL, Ex, GL CE, UL, Ex CE, UL, Ex
www.beckhoff.com/BK5210 www.beckhoff.com/BK5220 www.beckhoff.com/BK5250 www.beckhoff.com/LC5200
see page 620 see page 620 see page 620 see page 620
FC520x 720 FC520x 720 FC520x 720 FC520x 720
We reserve the right to make technical changes. BECKHOFF New Automation Technology
ControlNet, CC-Link BK7000, BK7150
Max. number of bytes 512 byte input and 512 byte output 32 byte input and 32 byte output
fieldbus
Current supply K-bus 1,750 mA 1,000 mA
Bus Terminal
508
The Bus Coupler BK7000 connects the ControlNet bus The “Compact” Bus Coupler BK7150 connects the
system with the electronic terminal blocks, which can be CC-Link system to the electronic terminal blocks, which
extended in modular fashion. One unit consists of one can be extended in modular fashion.
Bus Coupler, any number from 1 to 64 terminals and one The BK7150 Bus Coupler supports the operation of
end terminal. all Bus Terminals. As far as the user is concerned, handling
The BK7000 Bus Coupler supports the operation of all of the analog inputs/outputs is not different to other series.
Bus Terminals. As far as the user is concerned, handling of The information is available in the process image of the
the analog inputs/outputs is not different to other series. controller for processing in the form of a byte array.
The information is available in the process image of the
controller for processing in the form of a byte array.
Bus interface 2 x BNC female connector + NAP 1 x open style connector, 5-pin, included
Data transfer rates 5 Mbaud 156 kbaud…10 Mbaud
Weight approx. 170 g approx. 100 g
Operating temperature 0…+55 °C 0…+55 °C
Approvals CE, UL, Ex CE, Ex
Further information www.beckhoff.com/BK7000 www.beckhoff.com/BK7150
Accessories
Cordsets and connectors see page 620 see page 620
PC Fieldbus Cards – –
BECKHOFF New Automation Technology We reserve the right to make technical changes.
BK73xx, BK7420 Modbus, Fipio
Modbus Bus Coupler Modbus “Compact” Bus Coupler Fipio “Economy plus” Bus Coupler
for up to 64 Bus Terminals for up to 64 Bus Terminals for up to 64 Bus Terminals
(255 with K-bus extension) (255 with K-bus extension)
512 byte input and 512 byte output 64 byte input and 64 byte output
Bus Terminal
509
The BK7300 Bus Coupler connects the Modbus The “Compact” BK7350 Bus Coupler is a cost- The BK7420 Bus Coupler links the Fipio bus
bus system to the modular, extendable electronic optimised version with compact housing. With system to the modular, extendable electronic
terminal blocks. One unit consists of one Bus the K-bus extension, up to 255 Bus Terminals terminal blocks. One unit consists of a Bus Coupler,
Coupler, any number from 1 to 64 terminals and can be connected. any number of Bus Terminals between 1 and 64,
one end terminal. and up to 255 terminals with the K-bus extension.
The Bus Coupler automatically recognises the
connected terminals and activates the relevant
transfer profile.
D-sub 9-pin, RS485 D-sub 9-pin, RS485 1 x D-sub 9-pin socket with shielding
150 baud…38,400 baud 150 baud…38,400 baud automatic detection up to max. 1 Mbaud
approx. 170 g approx. 100 g approx. 170 g
0…+55 °C 0…+55 °C 0…+55 °C
CE, UL, Ex, GL CE, UL, Ex CE, Ex
www.beckhoff.com/BK7300 www.beckhoff.com/BK7350 www.beckhoff.com/BK7420
We reserve the right to make technical changes. BECKHOFF New Automation Technology
SERCOS, RS485 BK75xx, BK8000
SERCOS Bus Coupler SERCOS “Economy plus” Bus Coupler RS485 Bus Coupler
for up to 64 Bus Terminals for up to 64 Bus Terminals for up to 64 Bus Terminals
(255 with K-bus extension)
Max. number of bytes 32 byte input/32 byte output for the cy- 254 word I/O for the cyclic interface 512 byte input and 512 byte output
fieldbus clic interface (depending on the master) (depending on the master)
Current supply K-bus 1,750 mA 1,750 mA 1,750 mA
Bus Terminal
510
The Bus Coupler BK7500 connects the Compared with the Bus Coupler The Bus Coupler BK8000 uses the
SERCOS bus system with the electronic BK7500, the BK7520 allows, with physics of the RS485 specification for
terminal blocks, which can be extended the K-bus extension technology, the data transmission. Application of the
in modular fashion. One unit consists connection of up to 255 Bus Terminals Bus Coupler with a serial interface is
of one Bus Coupler, any number from to one Bus Coupler. The Bus Coupler suited to those cases in which the use
1 to 64 terminals and one end terminal. recognises the connected terminals of a fieldbus system can be omitted.
and automatically generates the affilia- The RS485 interface can be used by any
– distance between stations: tions of the inputs/outputs to the bytes automation device to gain access to the
40 m plastic fibre optic of the process image. Bus Coupler. Data exchange is made via
an open, documented protocol.
– distance between stations:
40 m plastic fibre optic
Bus interface F-SMA standard, IEC 872-2 F-SMA standard, IEC 872-2 RS485 D-sub
Data transfer rates 2/4 Mbaud, adjustable by means 2/4/8/16 Mbaud, adjustable by means 9.6 kbaud, 19.2 kbaud, 38.4 kbaud
of configuration switch of configuration switch
Weight approx. 170 g approx. 170 g approx. 170 g
Operating temperature 0…+55 °C 0…+55 °C 0…+55 °C
Approvals CE, UL, Ex CE, UL, Ex CE, UL, Ex, GL
Further information www.beckhoff.com/BK7500 www.beckhoff.com/BK7520 www.beckhoff.com/BK8000
Accessories
Cordsets and connectors see page 620 see page 620 see page 620
PC Fieldbus Cards FC750x 721 FC750x 721 –
Communication software – – KS8000 733
BECKHOFF New Automation Technology We reserve the right to make technical changes.
BK8100, BK9xxx RS232, Ethernet
RS232 Bus Coupler Ethernet TCP/IP Bus Coupler Ethernet TCP/IP “Compact” Ethernet TCP/IP Bus Coupler
for up to 64 Bus Terminals for up to 64 Bus Terminals Bus Coupler for up to for up to 64 Bus Terminals
64 Bus Terminals (with integrated 2-channel switch)
(255 with K-bus extension)
+60 °C
-25 °C
Bus Terminal
511
The Bus Coupler BK8100 uses The BK9000 Bus Coupler connects The “Compact” BK9050 Bus Coupler The BK9100 Bus Coupler connects
the physics of the RS232C (V.24) Ethernet with the modular, extend- is a cost-optimised version with Ethernet with the modular, extend-
specification for data transmission. able electronic terminal blocks. compact housing. With the K-bus able electronic terminal blocks.
Application of the Bus Coupler with One unit consists of one Bus Coupler, extension, up to 255 Bus Terminals One unit consists of one Bus Coupler,
a serial interface is suited to those any number from 1 to 64 terminals can be connected. any number from 1 to 64 terminals
cases in which the use of a fieldbus and one end terminal. and one end terminal.
system can be omitted. The RS232 – distance between stations:
interface can be used by any auto- – distance between stations: 100 m between hub/switch and – distance between stations:
mation device (e.g. a PC with RS232 100 m between hub/switch and Bus Coupler 100 m between hub/switch and
interface) to gain access to the Bus Coupler Bus Coupler or between Bus
Bus Coupler. Coupler and Bus Coupler
see page 620 see page 620 see page 620 see page 620
– FC90xx 722 FC90xx 722 FC90xx 722
KS8000 733 – – –
We reserve the right to make technical changes. BECKHOFF New Automation Technology
PROFINET BK9053, BK9103
Max. number of bytes 512 byte input and 512 byte output
fieldbus
Current supply K-bus 1,750 mA 1,750 mA
Bus Terminal
512
The BK9053 Bus Coupler connects PROFINET with the The BK9103 Bus Coupler connects PROFINET IO with the
modular, extendable electronic terminal blocks. One unit modular, extendable electronic terminal blocks. One unit
consists of one Bus Coupler, any number from 1 to 64 termi- consists of one Bus Coupler, any number from 1 to 64 termi-
nals (255 with K-bus extension) and one end terminal. nals (255 with K-bus extension) and one end terminal.
– distance between stations: 100 m between – distance between stations: 100 m between
hub/switch and Bus Coupler or between Bus Coupler hub/switch and Bus Coupler or between Bus Coupler
and Bus Coupler and Bus Coupler
BECKHOFF New Automation Technology We reserve the right to make technical changes.
BK9xxx EtherNet/IP, USB
EtherNet/IP “Compact” Bus Coupler EtherNet/IP Bus Coupler USB Bus Coupler
for up to 64 Bus Terminals for up to 64 Bus Terminals for up to 64 Bus Terminals
(255 with K-bus extension) (255 with K-bus extension)
512 byte input and 512 byte output 512 byte input and 512 byte output
Bus Terminal
513
The “Compact” BK9055 Bus Coupler is a cost- The BK9105 Bus Coupler connects EtherNet/IP The Bus Coupler BK9500 connects the Universal
optimised version with compact housing. With with the modular, extendable electronic terminal Serial Bus (USB) system with the electronic
the K-bus extension, up to 255 Bus Terminals can blocks. One unit consists of one Bus Coupler, any terminal blocks, which can be extended in modular
be connected. number from 1 to 64 terminals (255 with K-bus fashion. One unit consists of one Bus Coupler,
extension) and one end terminal. any number from 1 to 64 terminals and one end
– distance between stations: 100 m between terminal.
hub/switch and Bus Coupler – distance between stations: 100 m between
hub/switch and Bus Coupler or between – distance between stations: 30 m,
Bus Coupler and Bus Coupler 5 m from BK9500 to BK9500
We reserve the right to make technical changes. BECKHOFF New Automation Technology
BCxxxx, BXxxxx | Bus Terminal Controllers
Power LEDs
Bus Terminal
Fieldbus connection
514
K-bus
Power contacts
Address selector
Configuration
interface Input for power contacts
BECKHOFF New Automation Technology We reserve the right to make technical changes.
BCxxxx | Bus Terminal BXxxxx | Bus Terminal
Controllers Controllers
The Bus Terminal Controllers of the BC The BCxx00 Bus Terminal Controllers form +60 °C The Bus Terminal system has stood
and BX series are small controllers with a unit consisting of the controller, any -25 °C
the test of time in machine or build-
a high degree of flexibility. The I/O system number (up to 64) of terminals and a bus ing automation applications where a
consisting of modularly expandable elec- end terminal. In contrast to the BCxx50, temperature range of 0 to 55 °C is sufficient.
tronic terminal blocks, interfaces for all BCxx20 and BXxx00 series, a terminal bus For requirements beyond that, the operating
market-relevant fieldbus systems and the extension cannot be used. temperature range of selected standard Bus
integrated IEC 61131-3 PLC enables the The “Compact” BCxx50 and BCxx20 Terminals and Couplers has been extended
Bus Terminal Controllers to be used as Bus Terminal Controllers are fitted in cost- to -25 to +60 °C. The storage temperature of
stand-alone control systems or as intelli- optimised, compact housings and support these ET components (Extended Temperature
Bus Terminal
gent fieldbus slaves. The Bus Terminal the K-bus extension (up to 255 Bus Termi- Range) has also been adapted and is now
Controller is programmed using the nals). -40 to +85 °C. The exact definition of the
TwinCAT programming system according The devices of the BX family have operating conditions in temperature ranges
to IEC 61131-3. The configuration or field- two serial interfaces. The device itself outside 0 to 55 °C, installation requirements 515
bus interface of the controller is used for comprises an illuminated LC display with that possibly deviate from the standard and,
loading the PLC program. 2 lines of 16 characters each, a joystick if applicable, deviating technical data can be
The main distinguishing features switch and a real-time clock. Further found in the documentation. Bus Terminal
between the BX series and the BC series peripheral devices, e.g. displays, can be Controllers that have been qualified for the
are the larger memory capacity and a connected via the integrated Beckhoff extended temperature range are identified
larger number of expandable interfaces. Smart System Bus (SSB). accordingly.
www. beckhoff.com/Bus-Terminal-Controller
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Lightbus, PROFIBUS BC2000, BC31xx
Lightbus Bus Terminal Controller PROFIBUS Bus Terminal Controller PROFIBUS “Compact“ Bus Terminal
for up to 64 Bus Terminals for up to 64 Bus Terminals, 12 Mbaud Controller for up to 64 Bus Terminals
(255 with K-bus extension), 12 Mbaud
Max. number of bytes 512 byte input and 512 byte output 128 byte input and 128 byte output
fieldbus
Current supply K-bus 1,750 mA 1,750 mA 1,000 mA
+60 °C
-25 °C
Bus Terminal
516
The Bus Terminal Controller BC2000 The Bus Terminal Controller BC3100 is The “Compact” BC3150 Bus Terminal
is a Bus Coupler with integrated PLC a Bus Coupler with integrated PLC Controller is housed in a cost-optimised
functionality and has a fieldbus inter- functionality and has a fieldbus inter- and compact housing. Unlike the
face for the Lightbus. The BC2000 is an face for PROFIBUS. It is an intelligent BC3100, the BC3150 supports up
intelligent slave and can be used as a slave and can be used as distributed to 255 Bus Terminals via the K-bus
non-central intelligence in the Lightbus intelligence in the PROFIBUS system. extension.
system.
Bus interface 2 x standard fibre optic connector 1 x D-sub socket, 9-pin 1 x D-sub socket, 9-pin
Z1000 (plastic fibre), Z1010 (HCS fibre)
Data transfer rates 2.5 Mbaud automatic detection up to 12 Mbaud automatic detection up to 12 Mbaud
Program memory 32/96 kbytes 32/96 kbytes 48 kbytes
Data memory 32/64 kbytes 32/64 kbytes 32 kbytes
Remanent data 512 bytes 512 bytes 2 kbytes
Online change – – yes
Weight approx. 170 g approx. 170 g approx. 100 g
Operating temperature 0…+55 °C 0…+55 °C -25…+60 °C
Approvals CE, UL, Ex CE, UL, Ex, GL CE, UL, Ex
Further information www.beckhoff.com/BC2000 www.beckhoff.com/BC3100 www.beckhoff.com/BC3150
Accessories
Cordsets and connectors see page 620 see page 620 see page 620
PC Fieldbus Cards FC200x 715 FC310x 716 FC310x 716
TwinCAT PLC see page 820 see page 820 see page 820
BECKHOFF New Automation Technology We reserve the right to make technical changes.
BX3100, BCxxxx Interbus, CANopen
PROFIBUS Bus Terminal Controller Interbus Bus Terminal Controller CANopen “Compact” Bus Terminal
for up to 64 Bus Terminals for up to 64 Bus Terminals Controller for up to 64 Bus Terminals
(255 with K-bus extension), 12 Mbaud (255 with K-bus extension)
244 byte input and 244 byte output 64 byte input and 64 byte output 16 Tx/Rx PDOs
+60 °C
-25 °C
Bus Terminal
517
The BX3100 Bus Terminal Controller has The Bus Terminal Controller BC4000 is a The “Compact” BC5150 Bus Terminal Controller
a PROFIBUS slave interface with automatic Bus Coupler with integrated PLC functionality for CANopen extends the Beckhoff small controller
baud rate detection up to 12 Mbaud and and has a fieldbus interface for the Interbus. series by a cost-optimised version in a compact
an address selection switch for address The BC4000 is an intelligent slave and can be housing.
assignment. used as a decentralised intelligence in the
Interbus system.
1 x D-sub socket, 9-pin 2 x D-sub plug, 9-pin, plug and socket open style connector, 5-pin
with screening and vibration lock
automatic detection up to 12 Mbaud 500 kbaud automatic detection up to 1 Mbaud
256 kbytes 32/96 kbytes 48 kbytes
256 kbytes 32/64 kbytes 32 kbytes
2 kbytes 508 bytes 2 kbytes
yes – yes
approx. 250 g approx. 170 g approx. 100 g
0…+55 °C 0…+55 °C -25…+60 °C
CE, UL CE, UL, Ex CE, UL, Ex
www.beckhoff.com/BX3100 www.beckhoff.com/BC4000 www.beckhoff.com/BC5150
We reserve the right to make technical changes. BECKHOFF New Automation Technology
CANopen, DeviceNet BX5xxx, BC5250
CANopen Bus Terminal Controller DeviceNet “Compact” Bus Terminal DeviceNet Bus Terminal Controller
for up to 64 Bus Terminals Controller for up to 64 Bus Terminals for up to 64 Bus Terminals
(255 with K-bus extension) (255 with K-bus extension) (255 with K-bus extension)
Number of Bus Terminals 64 (255 with K-bus extension) 64 (255 with K-bus extension)
Max. number of bytes 32 Tx/Rx PDOs 512 byte input and 512 byte output
fieldbus
Current supply K-bus 1,450 mA 1,000 mA 1,450 mA
Bus Terminal
518
The BX5100 Bus Terminal Controller The “Compact” BC5250 Bus Terminal The BX5200 Bus Terminal Controller
has a CANopen slave interface. It has Controller with DeviceNet interface has a DeviceNet slave interface. It has
automatic baud rate detection up to extends the Beckhoff small control- automatic baud rate detection up
1 Mbaud and an address selection ler series by a cost-optimised version to 500 kbaud and an address selection
switch for address assignment. in a compact housing. The DeviceNet switch for address assignment. Up to
Controller offers automatic baud rate 512 byte of input and 512 byte of
detection up to 500 kbaud and two output can be exchanged with the
address selection switches for address controller.
assignment.
Bus interface open style connector, 5-pin open style connector, 5-pin open style connector, 5-pin
Data transfer rates automatic detection up to 1 Mbaud automatic detection up to 500 kbaud automatic detection up to 500 kbaud
BECKHOFF New Automation Technology We reserve the right to make technical changes.
BC7300, BC80xx Modbus, RS485
Modbus RS485 Bus Terminal Controller RS485 Bus Terminal Controller RS485 “Compact“ Bus Terminal
for up to 64 Bus Terminals for up to 64 Bus Terminals Controller for up to 64 Bus Terminals
(255 with K-bus extension)
512 byte input and 512 byte output 512 byte input and 512 byte output
Bus Terminal
519
The Bus Terminal Controller BC7300 is The Bus Terminal Controller BC8000 is a Bus The “Compact” Bus Terminal Controller BC8050
a Bus Coupler with integrated PLC function- Coupler with integrated PLC functionality and with serial RS485 interface extends the Beckhoff
ality and has a fieldbus interface for Modbus. has an RS485 interface. The programmable inter- small controller series by a cost-optimised version
The BC7300 is an intelligent slave and can face is suitable for the connection of serial de- in a compact housing. An open serial protocol –
be used as a non-central intelligence in the vices. The protocol can be freely programmed. like in the BK8x00 Bus Couplers – and the Modbus
Modbus system. The serial interface then functions as a master. RTU/ASCII protocol are implemented. The address
and the protocol are selected via the two rotary
selection switches.
We reserve the right to make technical changes. BECKHOFF New Automation Technology
RS232/RS485 BC81xx, BX8000
RS232 Bus Terminal Controller RS232 “Compact“ Bus Terminal RS232/RS485 Bus Terminal
for up to 64 Bus Terminals Controller for up to 64 Bus Terminals Controller for up to 64 Bus Terminals
(255 with K-bus extension) (255 with K-bus extension)
Max. number of bytes 512 byte input and 512 byte output
fieldbus
Current supply K-bus 1,750 mA 1,000 mA 1,450 mA
Bus Terminal
520
The BC8100 Bus Terminal Controller The “Compact” Bus Terminal Controller The BX8000 Bus Terminal Controller is
is a Bus Coupler with integrated PLC BC8150 with serial RS232 interface a stand-alone PLC. One unit consists of
functionality and has a RS232 interface, extends the Beckhoff small controller the BX8000 Bus Terminal Controller with
with which peer-to-peer connection is series by a cost-optimised version in a up to 64 Bus Terminals and a bus end
possible. The programmable interface compact housing. An open serial pro- terminal. With the terminal bus extension
is suitable for the connection of serial tocol – like in the BK8x00 Bus Couplers system, the connection of up to 255 Bus
devices. The protocol can be freely – and the Modbus RTU/ASCII protocol Terminals is possible. The controller is
programmed. are implemented. programmed via the COM1 interface.
Bus interface RS232 D-sub RS232 D-sub open style connector, 5-pin
Data transfer rates 1.2 kbaud…57.6 kbaud 1.2 kbaud…38.4 kbaud 300 baud…115 kbaud
BECKHOFF New Automation Technology We reserve the right to make technical changes.
BC90xx Ethernet
Ethernet Bus Terminal Controller Ethernet “Compact“ Bus Terminal Ethernet TCP/IP “Economy plus” Bus Terminal
for up to 64 Bus Terminals Controller for up to 64 Bus Terminals Controller for up to 64 Bus Terminals
(255 with K-bus extension) (255 with K-bus extension)
Bus Terminal
521
The Bus Terminal Controller BC9000 is a Bus The “Compact” BC9050 Bus Terminal Controller The BC9020 “Economy plus” Bus Terminal
Coupler with integrated PLC functionality and has with Ethernet interface extends the Beckhoff small Controller is a Bus Coupler with integrated
a fieldbus interface for Ethernet. It is an intelligent controller series by a cost-optimised version in a PLC functionality and has a fieldbus interface
slave that can be used as a non-central intelli- compact housing. for Ethernet. It is an intelligent slave and can
gence in the Ethernet system. One unit consists of be used as decentralised intelligence in the
the Bus Terminal Controller, any number of termi- Ethernet system.
nals between 1 and 64, and a bus end terminal.
1 x RJ 45 1 x RJ 45 1 x RJ 45
10/100 Mbaud, automatic recognition 10/100 Mbaud, automatic recognition 10/100 Mbaud, automatic recognition
of the transmission rate of the transmission rate of the transmission rate
64/96 kbytes 48 kbytes 128 kbytes
64/128 kbytes 32 kbytes 128 kbytes
4,080 bytes 2 kbytes 2 kbytes
– yes yes
approx. 170 g approx. 100 g approx. 170 g
0…+55 °C 0…+55 °C 0…+55 °C
CE, UL, Ex, GL CE, UL, Ex CE, UL, Ex, GL
www.beckhoff.com/BC9000 www.beckhoff.com/BC9050 www.beckhoff.com/BC9020
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Ethernet BC9120, BC9100
Ethernet TCP/IP “Economy plus” Bus Terminal Ethernet TCP/IP Bus Terminal Controller
Controller for up to 64 Bus Terminals (255 with for up to 64 Bus Terminals
K-bus extension, with integrated 2-channel switch) (with integrated 2-channel switch)
Max. number of bytes 512 byte input and 512 byte output
fieldbus
Current supply K-bus 1,750 mA 1,750 mA
+60 °C
-25 °C
Bus Terminal
522
In contrast to the BC9020, the BC9120 has The Bus Terminal Controller BC9100 is a
an additional RJ 45 port. Both Ethernet ports Bus Coupler with integrated PLC functional-
operate as 2-channel switches. ity and has a fieldbus interface for Ethernet.
The BC9100 is an intelligent slave and can
be used as a non-central intelligence in the
Ethernet system.
BECKHOFF New Automation Technology We reserve the right to make technical changes.
BX9000, BC9191 Ethernet
BX9000 BC9191
1,450 mA 200 mA
Digital inputs:
3 x 24 V DC
Analog inputs:
3 x 0…10 V;
1 x PT/Ni1000;
1 x resistance mea-
surement for set value
specification
Bus Terminal
Digital outputs:
1 x 230 V AC, 10 A, relay;
3 x 230 V AC, 1 A, relay;
2 x 230 V AC, 1 A, triac 523
Analog outputs:
2 x 0…10 V
The BX9000 Bus Terminal Controller has an Ethernet The BC9191 Ethernet Room Controller with integrated PLC functionality covers the
slave/master interface. The controller has automatic standard inputs and outputs for room control. In addition, the BC9191 can be extended
baud rate detection up to 100 Mbaud. The address can with Bus Terminals. A parameterisable PLC program for room control is included in the
optionally be entered via DHCP, BootP, ARP or with scope of supply.
the joystick switch.
RJ 45 2 x RJ 45 (switched)
10/100 Mbaud, automatic recognition 10/100 Mbaud, automatic recognition
of the transmission rate of the transmission rate
256 kbytes 48 kbytes
256 kbytes 32 kbytes
2 kbytes 2 kbytes
yes yes
approx. 250 g approx. 440 g
0…+55 °C 0…+55 °C
CE, UL CE
www.beckhoff.com/BX9000 www.beckhoff.com/BC9191
We reserve the right to make technical changes. BECKHOFF New Automation Technology
KLxxxx | Bus Terminals
BECKHOFF New Automation Technology We reserve the right to make technical changes.
2-channel terminals 4-channel terminals 8-channel terminals 16-channel terminals
The 2-channel terminals Along with four channels The 8-channel terminals have one The HD (High Density) housing allows
provide additional power the 4-channel terminals have channel per connection point due to 16 channels to be accommodated
(+24 V DC), ground (0 V DC) another four connection points a high packing density. The power on a unit that is only 12 mm wide.
and in many cases also PE for available. These can provide contact of the terminal will be used The power contact of the terminal
each channel. Connection is 24 V DC or ground. Connec- as the common reference potential. will be used as the common reference
carried out with 3- or 4-wire tion is carried out with 2-wire Connection is carried out with 1-wire potential. Connection is carried out
connection. connection. connection. with 1-wire connection.
The Bus Terminals offer the possibility various supply voltages. 1-, 2-, 3- and 4-wire +60 °C The Bus Terminal system has stood
Bus Terminal
to directly connect many different signals. connections allow the use of Bus Terminals in -25 °C
the test of time in machine or build-
No signal converter or additional evalua- almost all applications without further wiring ing automation applications where
tion device is needed. The direct connection work. a temperature range of 0 to +55 °C is suf-
reduces the costs and simplifies the control The KL3xxx and KL4xxx Bus Terminal ficient. For requirements beyond that, the 525
technology. Each Bus Terminal separates the product family processes analog signals. operating temperature range of selected
internal electronics from the connection level The most commonly used are 0…10 V, ±10 V, standard Bus Terminals and couplers was
and thus simplifies the creation of voltage 0…20 mA and 4…20 mA. Also many other extended to -25 to +60 °C. The storage tem-
groups with different voltages. In addition, industry-standard voltage and current signals perature of these ET components (Extended
interfering voltages on the signal connector are supported and pre-processed. Temperature Range) has also been adapted
lose their adverse effects. In the KL5xxx and KL6xxx Bus Terminal and is now -40 to +85 °C. The exact defini-
The KL1xxx, KL2xxx Bus Terminal product product families other complex signals, such tion of the operating conditions in tempera-
family is designed for the processing of dig- as position values and digital interfaces, are ture ranges outside 0 to +55 °C, installation
ital or binary signals. There are “High” and supported. Some Bus Terminals act as field- requirements that possibly deviate from the
“Low” states. In the positive switching logic bus masters for subordinate bus systems. standard and, if applicable, deviating techni-
the High state corresponds to the level of the The Bus Terminal station thus becomes a uni- cal data can be found in the documenta-
supply voltage, the Low state corresponds to versal gateway between different systems. tion. Bus Terminals which are suited to the
ground level. For negative switching logic it is The KL9xxx system terminals round off extended temperature range are marked
the other way around. The Bus Terminal prod- the application of Bus Terminals with power accordingly.
uct family supports both types of logic for feed and power supply units.
www. beckhoff.com/BusTerminal
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Digital Input KL1408, KL1418
2 6
3 7
526
4 8
Type 3
VIN /V
30
25 Nominal voltage 24 V DC (-15 %/+20 %)
20 ON
Current consumption typ. 2 mA + load
15
10 power contacts
5 Current consumpt. K-bus typ. 5 mA
0 OFF Operating temperature -25…+60 °C
−3 I IN /mA
0 5 10 15 Approvals CE, UL, Ex, GL
Signal voltage “0”: -3…5 V DC Characteristics of the 3 input types Weight approx. 55 g
Signal voltage “1”: 11…30 V DC according to EN 61131-2 (24 V DC) Further information www.beckhoff.com/KL1408
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL18xx, KL14xx Digital Input
16-channel digital 8-channel digital input + 8-channel digital 4-channel digital 4-channel digital
input terminal, 8-channel digital output, input terminal, input terminal, input terminal,
24 V DC, 1-wire, 24 V DC, 1-wire, 24 V DC, 2-wire, 24 V DC, 2-wire, 24 V DC, 2-wire,
type 1/3 type 1/3 type 1/3 type 1/3 type 2
EN 61131-2, type 2
typ. 3.0 ms typ. 3.0 ms typ. 3.0 ms typ. 3.0 ms typ. 0.2 ms typ. 0.2 ms
16 8 inputs + 8 outputs 8 4 4
Type 2
1 5 1 5
1 9 1 9 1 9
2 10 2 10 2 10
Bus Terminal
3 11 3 11 3 11 2 6 2 6
4 12 4 12 4 12
5 13 5 13 5 13 3 7 3 7
6 14 6 14 6 14
527
7 15 7 15 7 15
4 8 4 8
Type 2
8 16 8 16 8 16
The HD (High Density) The KL1859 digital Bus Terminal The KL1808 HD (High The KL1404 and KL1414 The KL1434 digital input
Bus Terminals with higher combines eight digital inputs Density) Bus Terminal has digital input terminals are terminal is suitable for
packing density contain and eight digital outputs in one eight inputs and eight suitable for the connection the connection of four
16 terminal points housed device. 24 V connections, which of four 2-wire sensors. 2-wire sensors of type 2
in a 12 mm terminal block. are suitable for the connec- (EN 61131-2).
– number of outputs: 8 tion of 2-wire sensors.
– max. output current: 0.5 A
(per channel)
– load type: ohmic, inductive,
lamp load
– reverse voltage protection:
yes
24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %)
typ. 4 mA + load typ. 15 mA + load typ. 2 mA + load typ. 1 mA + load only load
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Digital Input KL1xxx
Specification EN 61131-2, type 1/3 EN 61131-2, type 2 EN 61131-2, type 1 EN 61131-2, type 1/3
Input filter typ. 3.0 ms typ. 0.2 ms typ. 3.0 ms typ. 0.2 ms typ. 3.0 ms typ. 3.0 ms typ. 0.2 ms
Number of inputs 4 4 2 4
+60 °C
-25 °C
Type 2
1 5 1 5 1 5
1 9
Bus Terminal
2 10
2 6 2 6 2 6 3 11
4 12
3 7 3 7 3 7 5 13
528
6 14
7 15
4 8 4 8 4 8
Type 2
8 16
The KL1104 and KL1114 The KL1304 and KL1314 The KL1212 digital input The KL1804 and KL1814
digital input terminals have digital input terminals have terminal contains two HD Bus Terminals contain
four inputs and also provide four inputs and also provide inputs, which are suitable four inputs, 24 V and ground
24 V DC and ground per 24 V DC and ground per for the connection of 3-wire connections, which are suit-
channel. channel. The terminals are sensors. The terminal offers able for the application of
especially suitable for sen- a short-circuit-proof sensor 3-wire sensors.
sors which require a high supply voltage with inte-
quiescent current. grated diagnostic. A short-
circuit or an open lead in
the sensor supply is detected
and the terminal status is
relayed to the controller via
the K-bus.
Nominal voltage 24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %)
Current consumption only load only load only load typ. 1 mA + load
power contacts
Current consumpt. K-bus typ. 5 mA typ. 3 mA typ. 8 mA typ. 10 mA
Operating temperature -25…+60 °C 0…+55 °C 0…+55 °C 0…+55 °C
Approvals CE, UL, Ex, GL CE, UL, Ex CE, UL, Ex, GL CE, Ex
Weight approx. 55 g approx. 50 g approx. 55 g approx. 60 g
Further information www.beckhoff.com/KL1104 www.beckhoff.com/KL1304 www.beckhoff.com/KL1212 www.beckhoff.com/KL1804
Special terminals
Distinguishing features
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL1xxx Digital Input
typ. 3.0 ms typ. 0.2 ms typ. 3.0 ms typ. 0.2 ms typ. 3.0 ms typ. 0.2 ms typ. 3.0 ms typ. 0.2 ms
2 2 2 16
+60 °C
-25 °C
1 5 1 5 1 5
Bus Terminal
2 6 2 6 2 6
3 7 3 7 3 7
529
+ –
4 8 4 8 4 8 1 2
The KL1002 and KL1012 digital input The current/voltage characteristics The KL1302 and KL1312 digital input A 20-pin plug connector with
terminals have two inputs, which are have been optimised for 4-wire sen- terminals have two inputs, which are 2.54 mm contact spacing enables
suitable for the connection of 4-wire sors. The input current in low state suitable for the connection of 4-wire the secure connection of plug con-
sensors. is increased to a minimum value of sensors. The terminals are especially nectors using insulation displace-
1.5 mA and therefore supports the suitable for sensors which require a ment contact, as is usual for ribbon
majority of commercially available high quiescent current. cables and special round cables.
4-wire sensors. A typical value for The required 24 V DC voltage supply
the energy-saving high current is must be input by the ribbon cable
2.2 mA. or the terminal points.
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Digital Input KL1xxx
Input filter typ. 3.0 ms typ. 0.2 ms typ. 3.0 ms typ. 3.0 ms typ. 0.2 ms typ. 3.0 ms
Number of inputs 8 16 4 16
1 5 1 5
1 9
2 10
Bus Terminal
2 6 3 11 2 6
4 12
3 7 5 13 3 7
530 6 14
7 15 + –
4 8 4 8 1 2
8 16
The negative switching The HD (High Density) Negative switching sensors A 20-pin plug connector
KL1488 and KL1498 digital Bus Terminals with higher can be connected to the with 2.54 mm contact spac-
input terminals are suitable packing density contain KL1184 and KL1194 digital ing enables the secure con-
for the connection of eight 16 terminal points housed input terminals. nection of plug connectors
sensors by 1-wire technology. in a 12 mm terminal block. using insulation displace-
ment contact, as is usual for
ribbon cables and special
round cables. The required
24 V DC voltage supply must
be input by the ribbon cable
or the terminal points.
Nominal voltage 24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %)
Current consumption typ. 2 mA + load typ. 4 mA + load only load typ. 4 mA from the 24 V
power contacts supply (no power contacts)
Current consumpt. K-bus typ. 5 mA typ. 20 mA typ. 8 mA typ. 3 mA
Operating temperature 0…+55 °C 0…+55 °C 0…+55 °C 0…+55 °C
Approvals CE, UL, Ex CE, Ex CE, UL, Ex CE
Weight approx. 55 g approx. 55 g approx. 55 g approx. 50 g
Further information www.beckhoff.com/KL1488 www.beckhoff.com/KL1889 www.beckhoff.com/KL1184 www.beckhoff.com/KL1862
Special terminals KL1862
Distinguishing features positive switching 529
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL11xx, KL1052 Digital Input
Number of inputs 4 2
1 5 1 5
Bus Terminal
2 6 2 6
3 7 3 7
531
4 8 4 8
Positive or negative switching sensors can be connected Positive or negative switching sensors can be connected
to the KL1154 and KL1164 digital input terminals. to the KL1052 digital input terminal.
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Digital Input KL1124, KL1032
1 5 1 5
Bus Terminal
2 6 2 6
+5 V +48 V
3 7 3 7
0V 0V
532
4 8 4 8
PE
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL17xx Digital Input
2-wire
2 2 2 2
1 5 1 5 1 5 1 5
Bus Terminal
2 6 2 6 2 6 2 6
60 V DC 120 V 120 V/
230 V
3 7 3 7 3 7 3 7
0V 0V 0V
533
4 8 4 8 4 8 4 8
PE PE PE
The KL1712-0060 digital input The KL1712 digital input terminal The KL1702 digital input terminal The KL1722 digital input terminal
terminal is suitable for the reading is suitable for the acquisition of is suitable for the acquisition of does not have a power contact,
of 60 V DC logic signals. direct and alternating voltage logic logic signals in the alternating volt- so that individual potential groups
signals. age range from 120…230 V AC. can be built up. The voltage between
input 1 and input 2 must not exceed
230 V AC.
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Digital Input KM10xx
Input filter typ. typ. typ. 3.0 ms typ. 0.2 ms typ. 3.0 ms typ. 0.2 ms
3.0 ms 0.2 ms
Number of inputs 16 (2 x 8) 32 (4 x 8) 64 (8 x 8)
Bus Terminal
534
Like the standard Bus Terminals, the terminal modules are integrated in the I/O system. Plug connectors with spring
connections enable plug-in wiring and are optionally available with 1 or 3 pins. LEDs integrated in the plug indicate
the signal state for each channel directly at the wire.
Ordering information:
KM10xx-0000 without plugs
-0001 1-pin plug (without status LED)
-0002 1-pin plug (with status LED)
-0004 3-pin plug (with status LED)
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KM1644 Digital Input
Bus Terminal
– KM4602: 2-channel analog output
terminal, 0…10 V, manual/automatic
operation
The digital KM1644 input terminal is used for manual 535
input directly in the process data. The four switches supply
their status to the control system as digital bit information.
The four LEDs indicate the four output bits from the process
data and cannot be activated directly via the switches.
Nominal voltage –
Current consumption – (no power contacts)
power contacts
Current consumpt. K-bus typ. 5 mA
Switch settings ON, OFF, PUSH
Special features manual/emergency operation
Operating temperature 0…+55 °C
Approvals CE
Weight approx. 65 g
Further information www.beckhoff.com/KM1644
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Digital Input KL1232
1 5
2 6
Bus Terminal
3 7
4 8
536
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL13xx Digital Input
2-wire
3.0 ms 30 ms 3.0 ms
2 2 2
1 5 1 5 1 5
+5 V +8.2 V
2 6 4.7 k 2 6 2 6 10 k
υ
υ
4.7 k 1k
Bus Terminal
3 7 3 7 3 7
+ + +
- - -
4 8 4 8 4 8
Alarm Equivalent circuit PTC Equivalent circuit Namur Equivalent circuit
sensor alarm sensor sensor PTC sensor sensor Namur sensor 537
The digital KL1362 input terminal analyses the The digital KL1382 input terminal analyses the The digital input terminal KL1352 analyses the
input signals of break-in sensors with the aid of a input signal of thermistor sensors with the aid input signal from Namur sensors in accordance
current loop. It enables safe monitoring of alarm of a current loop and a voltage of less than 5 V. with EN 50277 (previously DIN 19234). One bit
contacts with fixed resistance ratio. In the process It is a monitoring device for the thermal machine indicates the sensor’s signal state in the process
image, the state of the sensor is indicated by one protection of PTC sensors, suitable for the direct image. A further bit reports short circuits or line
bit each. A further bit reports short circuits or line monitoring of motors, bearings and equipment. interruptions.
interruptions. In the process image, the state of the sensor is
indicated by one bit each. A further bit reports – switching hysteresis: 0.2 mA
– line interruption: < 0.1 mA short circuits or line interruptions. – short circuit current: < 8.2 mA
– short circuit: > 3 mA – short circuit detection: > 6.5 mA
– cable resistance: ≤ 200 Ω – sensor voltage: ≤ 5 V
– diagnostics: open-circuit: > 8 kΩ
short-circuit: < 25 Ω
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Digital Input KL1501, KL1512
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL1904 Digital Input
Number of inputs 4
1 5
2 6
Bus Terminal
3 7
4 8
539
Protocol TwinSAFE/FSoE
Nominal voltage 24 V DC (-15 %/+20 %)
Current consumption –
power contacts
Current consumpt. K-bus 48 mA
Response time typ. 4 ms (read input/write to K-bus)
Fault response time ≤ watchdog time (parameterisable)
Permiss. degree 2
of contamination
Climate class EN60721-3-3 3K3
Installation position horizontal
Special features 4 safe inputs
Operating temperature 0…+55 °C
Approvals CE, UL, Ex, TÜV Süd
Weight approx. 50 g
Protection class IP 20
Further information www.beckhoff.com/KL1904
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Digital Output KL2408, KL2809
2 6 3 11
5 13
ing diode prevents this voltage peak. How- 3 7
8 16
applications. For example, a valve remains
open for many milliseconds. The Bus Termi-
nals represent a compromise between pre- The KL2408 digital output The KL2809 HD (High
terminal has 8 outputs, each Density) Bus Terminal has
vention of overvoltage and rapid switch-off.
one is assigned a terminal 16 digital outputs and is
They suppress the induction voltage to about point. This way, a high pack- suitable for applications in
24 V DC and realise switch-off times which ing density can be achieved which a very high packing
approximately correspond to the switch-on for actuators with common density is required.
time of the coil. ground potential.
In the case of short-circuit, the output
circuit limits the current and prevents the
activation of the upstream circuit-breaker.
The Bus Terminal maintains this current until
important self-heating and finally switches
off. After the circuit has cooled, it switches
back on. The output signal is driven in time Nominal voltage 24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %)
until the output of the controller is switched Current consumption typ. 60 mA + load typ. 35 mA + load
off or the short-circuit is rectified. The clock power contacts
frequency depends on the ambient tempera- Current consumpt. K-bus typ. 18 mA typ. 35 mA
ture and the load of the other terminal chan- Breaking energy < 150 mJ/channel < 150 mJ/channel
nels. The overload protection of the output is Reverse voltage protection yes yes
also realised by thermal switch-off. The total Short circuit current <2A <2A
current specified should be observed. If a Operating temperature -25…+60 °C 0…+55 °C
total current is not given, it is not limited. Approvals CE, UL, Ex, GL CE, Ex
Weight approx. 70 g approx. 70 g
Further information www.beckhoff.com/KL2408 www.beckhoff.com/KL2809
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL2xxx, KL1859 Digital Output
+60 °C
-25 °C
1 5
1 9 1 9
2 10 2 10
Bus Terminal
3 11 2 6 3 11
4 12 4 12
5 13 3 7 5 13
6 14 6 14
541
7 15 7 15
4 8
8 16 8 16
The KL1859 digital Bus Terminal combines The KL2404 and KL2424 digital input terminals The KL2808 High Density Bus Terminal contains
eight digital inputs and eight digital outputs are suitable for the connection of four 2-wire eight outputs and eight ground connection points
in one device. actuators. for the connection of 2-wire actuators and thus
allows a very high packing density.
– number of inputs: 8
– input filter: 3.0 ms
– type 1/3
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Digital Output KL2xxx
Max. output current 0.5 A (short-circuit-proof) 0.5 A (short-circuit-proof) 4.0 A (short-circuit-proof) 0.5 A (short-circuit-proof)
per channel per channel per channel, 8 A for parallel per channel
connection
Number of outputs 4 4 2 2
+60 °C +60 °C
-25 °C -25 °C
8A
1 5 1 5 1 5 1 5
Bus Terminal
2 6 2 6 2 6 2 6
3 7 3 7 3 7 3 7
542
4 8 4 8 4 8 4 8
The KL2114 digital output The KL2134 digital output The KL2442 is suitable for the The KL2032 digital output
terminal connects the con- terminal connects the con- connection of actuators with terminal connects the con-
trol signals to the actuators trol signals to the actuators high current requirement of trol signals to the actuators
in an electrically isolated in an electrically isolated 4 A. For parallel switched out- in an electrically isolated
manner. manner. puts, even 8 A is possible. manner.
Nominal voltage 24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %)
Current consumption typ. 30 mA + load typ. 30 mA + load typ. 30 mA + load typ. 20 mA + load
power contacts
Current consumpt. K-bus typ. 9 mA typ. 9 mA typ. 9 mA typ. 5 mA
Breaking energy < 150 mJ/channel < 150 mJ/channel no data < 150 mJ/channel
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL2xxx Digital Output
0.5 A (short- 2.0 A (short- 0.5 A (short-circuit-proof) 0.5 A (short-circuit-proof) 0.5 A (short-circuit-proof)
circuit-proof) circuit-proof) per channel per channel per channel
per channel per channel
2 2 16 16
1 5 1 5
Bus Terminal
2 6 2 6 +48 V
3 7 3 7
543
+ –
4 8 4 8 1 2
The digital output terminals Diagnostic possibilities: The KL2872 allows the connection The digital output terminal KM2042
KL2012 and KL2022 connect – short-circuit to 24 V of 16 actuators by direct ribbon allows direct connection of actuators
the control signals to the actuators – short-circuit to 0 V cable via a 20-pin contact strip by D-sub connection, which is com-
in an electrically isolated manner. – undervoltage with a 2.54 mm contact spacing. mon in e.g. valve terminals. Plug X2
The required 24 V DC voltage supply included in the scope of supply.
must be input by the ribbon cable
or the terminal points.
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Digital Output KM200x
544
Like the standard Bus Terminals, the terminal modules are integrated in the I/O system. Plug connectors with spring
connections enable plug-in wiring and are optionally available with 1 or 3 pins. LEDs integrated in the plug indicate
the signal state for each channel directly at the wire.
Ordering information:
KM200x -0000 without plugs
-0001 1-pin plug (without status LED)
-0002 1-pin plug (with status LED)
-0004 3-pin plug (with status LED)
Nominal voltage 24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %)
Current consumption – (no power contacts) – (no power contacts) – (no power contacts)
power contacts
Current consumpt. K-bus typ. 5 mA typ. 5 mA typ. 5 mA
Breaking energy < 150 mJ/channel < 150 mJ/channel < 150 mJ/channel
Reverse voltage protection yes yes yes
Short circuit current <2A <2A <2A
Operating temperature 0…+55 °C 0…+55 °C 0…+55 °C
Approvals CE CE CE
Weight approx. 90 g with 1-pin approx. 90 g with 1-pin connector, approx. 310 g with 1-pin connector,
connector, approx. 110 g approx. 110 g with 3-pin connector approx. 390 g with 3-pin connector
with 3-pin connector
Further information www.beckhoff.com/ www.beckhoff.com/KM2004 www.beckhoff.com/KM2008
KM2002
Special terminals KM2002-000x KM2004-000x KM2008-000x
Distinguishing features different connectors different connectors different connectors
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL2124 Digital Output
1 5
Bus Terminal
2 6
+5 V
3 7
545
4 8
Nominal voltage 5 V DC
Current consumption typ. 16 mA + load
power contacts
Current consumpt. K-bus typ. 14 mA
Breaking energy –
Reverse voltage protection yes
Short circuit current –
Operating temperature 0…+55 °C
Approvals CE, UL, Ex
Weight approx. 70 g
Further information www.beckhoff.com/KL2124
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Digital Output KL2xxx
Max. output current 0.5 A (short-circuit-proof) 0.5 A (short-circuit-proof) 0.5 A (short-circuit-proof) 0.5 A (short-circuit-proof)
per channel per channel per channel per channel
Number of outputs 8 16 4 16
1 5 1 5
1 9
2 10
Bus Terminal
2 6 3 11 2 6
4 12
3 7 5 13 3 7
546 6 14
7 15 + –
4 8 4 8 1 2
8 16
The KL2488 digital output The KL2889 HD (High Den- The KL2184 digital output A 20-pin plug connector
terminal is suitable for the sity) Bus Terminal offers terminal offers four outputs with 2.54 mm contact
connection of eight negative terminal points for 16 nega- and additionally provides spacing enables the secure
switching actuators using tive switching actuators 24 V DC and ground (0 V) connection of plug con-
1-wire connection technol- using 1-wire connection for each channel. nectors using insulation
ogy. technology and thus a very displacement contact, as
high packing density. is usual for ribbon cables
and special round cables.
The required 24 V DC volt-
age supply must be input
by the ribbon cable or the
terminal points 1 and 2.
Nominal voltage 24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %)
Current consumption typ. 60 mA + load typ. 35 mA + load typ. 30 mA + load typ. 60 mA from the supply
power contacts (no power contacts)
Current consumpt. K-bus typ. 18 mA typ. 45 mA typ. 9 mA typ. 5 mA
Breaking energy < 100 mJ/channel < 100 mJ/channel < 100 mJ/channel < 100 mJ/channel
Reverse voltage protection yes yes yes yes
Short circuit current <7A <7A <7A <7A
Operating temperature 0…+55 °C 0…+55 °C 0…+55 °C 0…+55 °C
Approvals CE, Ex CE, Ex CE, UL, Ex CE, Ex
Weight approx. 70 g approx. 70 g approx. 70 g approx. 55 g
Further information www.beckhoff.com/KL2488 www.beckhoff.com/KL2889 www.beckhoff.com/KL2184 www.beckhoff.com/KL2872
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL2784, KL2794 Digital Output
Bus Terminal
2 6 2 6
3 7 3 7
547
4 8 4 8
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Digital Output KL2612, KL2641
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL26xx Digital Output
5A 2A
2 x make contacts for power contact 2 x make contacts 2 x change-over 1 x make contacts for power contact
+60 °C +60 °C
-25 °C -25 °C
1 5 1 5 1 5 1 5
2 6 2 6 2 6 2 6
…230 V AC …400 V AC
Bus Terminal
3 7 3 7 3 7 3 7
4 8 4 8 4 8 4 8
549
The KL2602 output terminal has The KL2622 Bus Terminal has The KL2652 output terminal has two The KL2631 output terminal has a
two relays each of which has a potential-free contacts; the power relays each with a changeover con- relay with a single contact, which is
single contact. The relay contact contacts are not looped through. tact, which can be used universally connected with the power contacts
is connected to the power contacts, for the switching of mains voltage (usable up to 400 V AC) and can be
which are suitable for use at up consumers of 230 V AC or 300 V DC. used universally for the switching of
to 230 V AC, and can be generally The KL2652 Bus Terminal is equipped mains voltage consumers. In order to
used for switching devices requiring with potential-free contacts. use high voltages of up to 400 V AC,
mains power. the KL2631 must be supplied via the
KL9190 power feed terminal.
230 V AC/30 V DC 230 V AC/30 V DC 230 V AC (max. switching voltage 400 V AC/300 V DC
250 V AC/300 V DC)
only load – – (no power contacts) only load
typ. 80 mA typ. 85 mA typ. 90 mA typ. 80 mA
5 A AC/DC (ohmic)/2 A AC/DC 5 A AC/DC (ohmic)/2 A AC/DC max. 3 A AC/3 A DC at 30 V DC switch. capacity DC: 300 V = 0.15 A;
(inductive) (inductive) 24 V = 5 A; non-linear; AC:1,500 VA
2 x 107 2 x 107 5 x 106 1 x 107
3 x 105 (5 A/30 V DC) 3 x 105 (5 A/30 V DC) 1 x 106 (1 A/250 V AC) 1.3 x 105 (2 A/250 V AC)
max. 5 A starting current (4 x 58 W) max. 5 A starting current (4 x 58 W) max. 6 A starting current no data
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Digital Output KM2604, KM2614
550
The KM2604 terminal module combines four pluggable The KM2614 terminal module combines four pluggable
power relays in one fieldbus module. The high switching power relays in one fieldbus module. The high switching
capacity of 16 A at 230 V AC enables direct mains connection capacity of 16 A at 230 V AC enables direct mains connection
of consumers with high current consumption. The relays are of consumers with high current consumption. The relays are
positioned at the top and can therefore be exchanged easily. positioned at the top and can therefore be exchanged easily.
Each relay can be manually switched to the ON status. A seal
indicates the initial manual operation.
Nominal voltage 230 V AC (max. switching voltage 250 V AC/30 V DC) 230 V AC (max. switching voltage 250 V AC/30 V DC)
Current consumption – (no power contacts) – (no power contacts)
power contacts
Current consumpt. K-bus typ. 15 mA typ. 15 mA
Switching current 16 A AC/12 A DC at 30 V DC 16 A AC/12 A DC at 30 V DC
Operat. cycles mech. (min.) 5 x 106 5 x 106
Operat. cycles electr. (min.) 1 x 106 (1 A/250 V AC) 1 x 106 (1 A/250 V AC)
Lamp test, max. 25 A starting current max. 25 A starting current
electronic ballast
Minimum permitted load 5 mA (10 V DC) 5 mA (10 V DC)
Special features – automatic/manual operation at the relay
Operating temperature 0…+55 °C 0…+55 °C
Approvals CE CE
Weight approx. 250 g approx. 250 g
Further information www.beckhoff.com/KM2604 www.beckhoff.com/KM2614
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KM2642, KM2652 Digital Output
KM2642 KM2652
6A
2 x change-over 2 x change-over
Bus Terminal
551
The digital KM2642 output terminal has two independent relay change-over The digital KM2652 output terminal has two independent relay change-over
contacts, which can be used for switching mains current consumers. For each contacts, which can be used for switching mains current consumers. For each
channel a switch enables selection between automatic, manual on, manual channel a switch enables selection between automatic, manual on, manual
off. In automatic mode the logical state of an output bit switches the relay. off. In automatic mode the logical state of an output bit switches the relay.
For manual mode a 24 V supply is required for the Bus Coupler. The output For manual mode a 24 V supply is required for the Bus Coupler. The state of
state can be read by the controller. the output and the switch can be read by the controller.
230 V AC (max. switching voltage 250 V AC) 230 V AC (max. switching voltage 250 V AC)
– (no power contacts) – (no power contacts)
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Digital Output KL27xx
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL27xx Digital Output
1.5 A per channel 3 A steady load 0.3 A steady load 1.5 A steady load
on each channel on each channel
4 x 3 make contacts 1 make contact 2 x make contacts
1 5 1 5
2 6 2 6
Bus Terminal
3 7 3 7
4 8 4 8
553
Mixed module 24 V DC/230 V AC for the direct control The KL2701 output terminal uses The KL2702 output terminal uses
of blinds applications an electronic load relay to switch a an electronic load relay to switch a
mains voltage of up to 230 V AC/DC. mains voltage of up to 230 V AC/DC.
The switching element is a high- The switching element is a high-
power MOSFET which is connected power MOSFET which is connected
to the power contact potential. As to the power contact potential. As
a semiconductor switch, it is not a semiconductor switch, it is not
subject to wear. subject to wear.
80…230 V AC 0…230 V AC/DC 0…230 V AC/DC
– (no power contacts) only leakage and load current only leakage and load current
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Digital Output KL2692
1 5
Bus Terminal
2 6
3 7
554
4 8
Nominal voltage 30 V DC
Current consumption –
power contacts
Current consumpt. K-bus approx. 165 mA
Switching times parameterisable
Ohmic switching current 5 A AC/DC
Inductive switching 2 A AC/DC
current
Operat. cycles mech. (min.) 2 x 107
Operat. cycles electr. (min.) 1 x 105 (5 A/30 V DC)
Minimum permitted load 10 mA at 5 V DC
Operating temperature 0…+55 °C
Approvals CE, UL
Weight approx. 60 g
Further information www.beckhoff.com/KL2692
Special terminals KL2692-1001
Distinguishing features 2 digital inputs, 2 potential-free relays,
end terminal variant
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL2521 Digital Output
Bus Terminal
2 6 2 6
3 7 3 7
555
4 8 4 8
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Digital Output KL25xx
Technical data KL2502 | KS2502 KL2512 | KS2512 KL2535 | KS2535 KL2545 | KS2545
Max. output current 0.1 A (1 A driver compo- 1.5 A per channel 2 x 1 A (short-circuit-proof, 2 x 3.5 A (short-circuit-proof,
nent) per channel thermal overload-proof for thermal overload-proof for both
both channels together) channels together)
Number of outputs 2 2 2 2
Enc
1 5 1 5 1 5 1 5 1’ 5’
A1 A2 A1 A2
2 6 2 6 2 6 2 6 2’ 6’
B1 B2 B1 B2
Bus Terminal
3 7 3 7 3 7 3 7 3’ 7’
4 8 4 8 4 8 4 8 4’ 8’
556
The KL2502 digital output The negative switching The KL2535 digital out- The KL2545 digital output termi-
terminal modulates the KL2512 output terminal put terminal controls an nal controls an output current via
pulse width of a binary enables direct connection output current via pulse pulse width control of the supply
signal, and outputs it elec- of different ohmic loads. width control of the supply voltage. It is electrically isolated
trically isolated from the The output signal is a voltage. It is electrically from the K-bus. The current value
K-bus. The mark/space pulse-width modulated isolated from the K-bus. (0 to 3.5 A) is specified by the
ratio is prescribed by a voltage. The typical load of The current value (0 to automation device via a 16-bit
16-bit value from the an LED group or an incan- 1 A) is specified by the value.
automation unit. descent lamp is connected automation device via
between the positive side a 16-bit value.
of the supply voltage and
the output of the KL2512.
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL2751, KL2761 Digital Output
Bus Terminal
2 6
230 V AC
3 7
N
557
4 8
PE
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Digital Output KL2531, KL2541
dynamic movement, this problem in areas of runat its resonance frequency. Under certain eration causes the feedback of energy, which
higher speeds of rotation can be solved. circumstances the motor may even stop. leads to voltage peaks at the power supply
The KL2531 and KL2541 stepper motor Resonances in the lower frequency range unit. A KL9570 buffer capacitor terminal
558 terminals are designed for direct connection essentially result from the mechanical protects from the effects of overvoltage, in
of medium capacity stepper motors. A high motor parameters. Apart from their impact that it absorbs some of the energy. If the volt-
frequency clocked PWM output stage regu- on smooth running, such resonances can age exceeds the capacity of the terminal, it
lates the currents through the motor coils. lead to significant loss of torque, or even gets rid of the excess energy via an external
The stepper motor terminals are synchronised loss of step of the motor, and are therefore resistance.
with the motor by parameterising. Unipolar particularly undesirable. Due to their sine/
as well as bipolar stepper motors can be cosine current profile, KL2531 and KL2541 AS1xxx | Stepper motors see page 796
driven. stepper motor terminals are able to prevent
A1 A2 A1 A2 A1 A2
B1 B2 B1 B2 B1 B2
M M M
Connection of a unipolar stepper motor Connection of a bipolar AS10x0 Connection of a bipolar AS10x0
stepper motor, serial stepper motor, parallel
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL2531, KL2541 Digital Output
Enc
1 5 1 5 1’ 5’
B1
B2
Bus Terminal
2 6 2 6 2’ 6’
A1 A2
3 7 3 7 3’ 7’
559
4 8 4 8 4’ 8’
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Digital Output KL25xx, KL2284
Terminal can perform positioning travels it absorbs some of the energy. If the voltage
independently without the use of NC. exceeds a threshold, the terminal dissipates
Nothing further is required apart from the excess energy via an external resistance.
560 a DC motor and a terminal. For applications with start/stop or
2. High-end positioning by means of (counter-)clockwise functions without loop
integration in TwinCAT NC: in conjunc- control, the KL2284 output terminal is suf-
tion with the DC motor output stage, ficient. It switches loads in selectable polar-
the DC motor is used with TwinCAT ity. This means that DC motors can be used
for the application without further in both directions of rotation. A polarity is
changes – analogous to a servo-axis. switched with two output bits per channel.
Control of a DC motor with travel distance control Control of a DC motor with encoder feedback
Actual value
Position control E speed E
in the terminal
KL2552 KL2552
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL25xx, KL2284 Digital Output
Enc
1 5 1 5 1’ 5’ 1 5
M
M
A1 A2
M
Bus Terminal
2 6 2 6 2’ 6’ 2 6
M
B1 B2
3 7 3 7 3’ 7’ 3 7
M
561
4 8 4 8 4’ 8’ 4 8
M
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Digital Output KL2791
2 6
230 V 1~
embedded device. The controller specifies the
set value for the motor speed in the form of a
16-bit word; the speed is regulated internally N 3 7
Motor load
pattern, so that the motor consumes less
power and the speed falls significantly. This
method is well suited to motors with fixed
loads, such as pumps and fans, in order to
achieve a control range for the flow rate from
10 to 100 %.
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL2904 Digital Output
Number of outputs 4
1 5
Bus Terminal
2 6
3 7
563
4 8
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Analog Input KL3001, KL3002
1 5 1 5
power contact.
564 The input circuit of the terminals differs
between single-ended and differential inputs. 3 7 3 7
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL340x, KL31xx Analog Input
4 8 2 2
Bus Terminal
1 5 1 5 1 5 1 5
2 6 2 6 2 6 2 6
+24 V
565
3 7 3 7 3 7 3 7
0V
4 8 4 8 4 8 4 8
The KL3404 analog input termi- The KL3408 analog input terminal The KL3102 analog input terminal The KL3132 analog input terminal is
nal has four inputs, which are combines eight inputs in one hous- combines two differential inputs optimised for highly accurate control
implemented in 2-wire technique. ing. The use of single conductor with a common internal ground processes due to its low measuring
The common reference ground of connection technology enables the potential in one housing. error of ±0.05 % (in relation to
the inputs is the internal ground. connection of multi-channel sensor the full scale value). The differential
technology with minimum space re- inputs have a common, internal
quirements. The reference ground for ground potential.
all inputs is the 0 V power contact.
< ±0.3 % (relative < ±0.3 % (relative < ±0.3 % (relative < ±0.05 % (relative
to full scale value) to full scale value) to full scale value) to full scale value)
– – – (no power contacts) –
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Analog Input KL306x, KL3464
Technical data KL3061 | KS3061 KL3062 | KS3062 KL3064 | KS3064 KL3464 | KS3464
Resolution 12 bits
Conversion time ~ 1 ms ~ 2 ms ~ 4 ms ~ 2 ms
Number of inputs 1 2 4 4
+60 °C +60 °C
-25 °C -25 °C
1 5 1 5 1 5 1 5
Bus Terminal
2 6 2 6 2 6 2 6
3 7 3 7 3 7 3 7
566
4 8 4 8 4 8 4 8
The KL3061 analog input The KL3062 analog input The KL3064 analog input The KL3464 analog input
terminal is characterised terminal combines two terminal contains four terminal combines four
by its fine granularity and single-ended inputs with a single-ended inputs with a single-ended inputs with a
electrical isolation. common internal ground common internal ground common internal ground
potential in one housing. potential. potential in one housing.
Measuring error < ±0.3 % (relative < ±0.3 % (relative < ±0.3 % (relative < ±0.3 % (relative
to full scale value) to full scale value) to full scale value) to full scale value)
Current consumption – (no power contacts) – (no power contacts) – (no power contacts) –
power contacts
Current consumpt. K-bus typ. 60 mA typ. 60 mA typ. 85 mA typ. 100 mA
Internal resistance > 130 kΩ > 130 kΩ > 130 kΩ > 130 kΩ
Common-mode voltage UCM – – – –
Special features – – – –
Operating temperature 0…+55 °C 0…+55 °C -25…+60 °C -25…+60 °C
Approvals CE, UL, Ex CE, UL, Ex CE, UL, Ex, GL CE, UL, Ex, GL
Weight approx. 60 g approx. 60 g approx. 80 g approx. 75 g
Further information www.beckhoff.com/KL3061 www.beckhoff.com/KL3062 www.beckhoff.com/KL3064 www.beckhoff.com/KL3464
Special terminals KL3062-00xx KL3064-00xx
Distinguishing features special terminals see 617 special terminals see 617
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL3468, KL31xx Analog Input
8-channel analog 2-channel analog 2-channel analog 2-channel analog 2-channel analog
input terminal, input terminal, input terminal, input terminal, input terminal,
0…10 V, 12 bits, 0…10 V, 16 bits, 0…2 V, 16 bits, 0…500 mV, 16 bits, -2…+2 V, 16 bits,
single-ended differential input differential input differential input differential input
16 bits
~ 4 ms 140 ms, configurable 140 ms, configurable 140 ms, configurable 140 ms, configurable
8 2 2 2 2
1 5 1 5 1 5 1 5 1 5
Bus Terminal
2 6 2 6 2 6 2 6 2 6
+24 V
3 7 3 7 3 7 3 7 3 7
0V
567
4 8 4 8 4 8 4 8 4 8
The KL3468 analog input ter- The KL3162 analog input The KL3172 analog input The KL3172-0500 analog The KL3182 analog input
minal combines eight inputs terminal is optimised for terminal is optimised for input terminal is optimised terminal is optimised for
in one housing. The use of highly accurate control highly accurate control for highly accurate control highly accurate control
single conductor connection processes due to its low processes due to its low processes due to its low processes due to its low
technology enables the con- measuring error of ±0.05 % measuring error of ±0.05 % measuring error of ±0.05 % measuring error of ±0.05 %
nection of multi-channel sen- (in relation to the full scale (in relation to the full scale (in relation to the full scale (in relation to the full scale
sor technology with minimum value). The differential inputs value). The differential inputs value). The differential inputs value). The differential inputs
space requirements. The refer- have a common, internal have a common, internal have a common, internal have a common, internal
ence ground for all inputs is ground potential. ground potential. ground potential. ground potential.
the 0 V power contact.
< ±0.3 % (relative < ±0.05 % (relative < ±0.05 % (relative < ±0.05 % (relative < ±0.05 % (relative
to full scale value) to full scale value) to full scale value) to full scale value) to full scale value)
– – – – –
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Analog Input KL30xx, KL3444
Technical data KL3011 | KS3011 KL3012 | KS3012 KL3044 | KS3044 KL3444 | KS3444
Resolution 12 bits
+60 °C
-25 °C
1 5 1 5 1 5 1 5
2 6 2 6 2 6 2 6
Bus Terminal
3 7 3 7 3 7 3 7
568 4 8 4 8 4 8 4 8
The KL3011 analog input The KL3012 analog input The KL3044 analog input The KL3444 analog input
terminal is characterised by terminal combines two terminal has four inputs, terminal has four inputs,
its electrical isolation. The differential inputs with a which are implemented in which are implemented in
input channels of the Bus common internal ground 2-wire technique. The com- 2-wire technique. The com-
Terminal have differential in- potential in one housing. mon reference ground of the mon reference ground of the
puts and possess a common, inputs is the internal ground. inputs is the internal ground.
internal ground potential.
Measuring error < ±0.3 % (relative < ±0.3 % (relative < ±0.3 % (relative < ±0.3 % (relative
to full scale value) to full scale value) to full scale value) to full scale value)
Current consum. pow.cont. – (no power contacts) – (no power contacts) – (no power contacts) –
Current consumpt. K-bus typ. 60 mA typ. 60 mA typ. 65 mA typ. 85 mA
Internal resistance 80 Ω + 0.7 V 80 Ω + 0.7 V 80 Ω + 0.7 V < 85 Ω
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL3xxx Analog Input
8-channel analog 1-channel analog 2-channel analog 2-channel analog 2-channel analog
input terminal, input terminal, input terminal, input terminal, input terminal,
0…20 mA, 12 bits, 0…20 mA, 12 bits, 0…20 mA, 12 bits, 0…20 mA, 15/16 bits, 0…20 mA, 16 bits,
single-ended with sensor supply with sensor supply differential input differential input
KL3448 | KS3448 KL3041 | KS3041 KL3042 | KS3042 KL3112 | KS3112 KL3142 | KS3142
15 bits, 16 bits
configurable to 16 bits
single-ended single-ended single-ended differential input differential input
~ 4 ms ~ 1 ms ~ 2 ms 140 ms, configurable to 2 ms 140 ms, configurable
8 1 2 2 2
+60 °C
-25 °C
1 5 1 5 1 5 1 5 1 5
2 6 2 6 2 6 2 6 2 6
Bus Terminal
3 7 3 7 3 7 3 7 3 7
4 8 4 8 4 8 4 8 4 8 569
The KL3448 analog input ter- The job of the KL3041 and KL3042 analog input terminals The KL3112 analog input The KL3142 analog input
minal combines eight inputs is to supply power to measuring transducers located in the terminal combines two terminal is optimised for
in one housing. The use of field and to transmit analog measurement signals with elec- differential inputs with a highly accurate control
single conductor connection trical isolation to the automation device. The voltage for the common internal ground processes due to its low
technology enables the con- sensors is supplied to the terminals via the power contacts. potential in one housing. measuring error of ±0.05%
nection of multi-channel sen- The power contacts can optionally be supplied with operating (in relation to the full scale
sor technology with minimum voltage in the standard way or via a supply terminal (KL9560) value). The differential inputs
space requirements. The refer- with electrical isolation. The 0 V power contact is the refer- have a common, internal
ence ground for all inputs is ence potential for the inputs. ground potential.
the 0 V power contact.
< ±0.3 % (relative < ±0.3 % (relative < ±0.3 % (relative < ±0.3 % (relative < ±0.05 % (relative
to full scale value) to full scale value) to full scale value) to full scale value) to full scale value)
– only load only load – (no power contacts) –
typ. 105 mA typ. 65 mA typ. 65 mA typ. 60 mA typ. 85 mA
< 85 Ω 80 Ω + 0.7 V 80 Ω + 0.7 V 50 Ω typ. shunt, 100 Ω typ. shunt
load: 60 Ω + diode voltage
– – – 35 V max. ±10 V max.
30 V DC 35 V max. 35 V max. 35 V DC 35 V DC
high packing density with sensor supply with sensor supply – increased measuring accuracy
0…+55 °C 0…+55 °C -25…+60 °C 0…+55 °C 0…+55 °C
CE, UL, Ex, GL CE, UL, Ex, GL CE, UL, Ex, GL CE, UL, Ex CE, UL, Ex
approx. 75 g approx. 70 g approx. 70 g approx. 70 g approx. 70 g
www.beckhoff.com/KL3448 www.beckhoff.com/KL3041 www.beckhoff.com/KL3042 www.beckhoff.com/KL3112 www.beckhoff.com/KL3142
KL3042-00xx KL3112-0050
special terminals see 617 Siemens S7 format
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Analog Input KL30xx, KL3454
Technical data KL3021 | KS3021 KL3022 | KS3022 KL3054 | KS3054 KL3454 | KS3454
Resolution 12 bits
+60 °C +60 °C
-25 °C -25 °C
1 5 1 5 1 5 1 5
2 6 2 6 2 6 2 6
Bus Terminal
3 7 3 7 3 7 3 7
570 4 8 4 8 4 8 4 8
The KL3021 analog input The KL3022 analog input The KL3054 analog input In the KL3454 Bus Terminal,
terminal is characterised terminal combines two terminal has four inputs, the four inputs are 2-wire
by its fine granularity and differential inputs with a which are implemented in versions and have a com-
electrical isolation. The input common internal ground 2-wire technique. The com- mon ground potential.
channels of the Bus Terminal potential in one housing. mon reference ground of the The 24 V power contact is
have differential inputs and inputs is the internal ground. connected to the terminal in
possess a common, internal order to enable the connec-
ground potential. tion of 2-wire sensors.
Measuring error < ±0.3 % (relative < ±0.3 % (relative < ±0.3 % (relative < ±0.3 % (relative
to full scale value) to full scale value) to full scale value) to full scale value)
Current consum. pow.cont. – (no power contacts) – (no power contacts) – (no power contacts) only load
Current consumpt. K-bus typ. 60 mA typ. 60 mA typ. 75 mA typ. 85 mA
Internal resistance 80 Ω + 0.7 V 80 Ω + 0.7 V 80 Ω + 0.7 V < 85 Ω
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL3xxx Analog Input
8-channel analog 1-channel analog 2-channel analog 2-channel analog 2-channel analog
input terminal, input terminal, input terminal, input terminal, input terminal,
4…20 mA, 12 bits, 4…20 mA, 12 bits, 4…20 mA, 12 bits, 4…20 mA, 15/16 bits, 4…20 mA, 16 bits,
single-ended with sensor supply with sensor supply differential input differential input
KL3458 | KS3458 KL3051 | KS3051 KL3052 | KS3052 KL3122 | KS3122 KL3152 | KS3152
15 bits, 16 bits
configurable to 16 bits
single-ended single-ended single-ended differential input differential input
~ 4 ms ~ 1 ms ~ 2 ms 140 ms, configurable to 2 ms 140 ms, configurable
8 1 2 2 2
+60 °C
-25 °C
1 5 1 5 1 5 1 5 1 5
2 6 2 6 2 6 2 6 2 6
Bus Terminal
3 7 3 7 3 7 3 7 3 7
4 8 4 8 4 8 4 8 4 8 571
The KL3458 analog input ter- The job of the KL3051 and KL3052 analog input terminals The KL3122 analog input The KL3152 analog input
minal combines eight inputs is to supply power to measuring transducers located in the terminal combines two terminal is optimised for
in one housing. The use of field and to transmit analog measurement signals with elec- differential inputs with a highly accurate control
single conductor connection trical isolation to the automation device. The voltage for the common internal ground processes due to its low
technology enables the con- sensors is supplied to the terminals via the power contacts. potential in one housing. measuring error of ±0.05 %
nection of multi-channel sen- The power contacts can optionally be supplied with operating (in relation to the full scale
sor technology with minimum voltage in the standard way or via a power feed terminal value). The differential inputs
space requirements. The refer- (KL9xxx) with electrical isolation. The 0 V power contact is have a common, internal
ence ground for all inputs is the reference potential for the inputs. ground potential.
the 0 V power contact.
< ±0.3 % (relative < ±0.3 % (relative < ±0.3 % (relative < ±0.3 % (relative < ±0.05 % (relative
to full scale value) to full scale value) to full scale value) to full scale value) to full scale value)
– only load only load – (no power contacts) –
typ. 105 mA typ. 65 mA typ. 65 mA typ. 60 mA typ. 85 mA
< 85 Ω 80 Ω + 0.7 V 80 Ω + 0.7 V 50 Ω typ. shunt, 100 Ω typ. shunt
load: 60 Ω + diode voltage
– – – 35 V max. ±10 V max.
30 V DC 35 V max. 35 V max. 35 V DC 35 V DC
high packing density with sensor supply with sensor supply – increased measuring accuracy
0…+55 °C 0…+55 °C -25…+60 °C 0…+55 °C 0…+55 °C
CE, UL, Ex, GL CE, UL, Ex, GL CE, UL, Ex, GL CE, UL, Ex CE, UL, Ex
approx. 75 g approx. 70 g approx. 70 g approx. 70 g approx. 70 g
www.beckhoff.com/KL3458 www.beckhoff.com/KL3051 www.beckhoff.com/KL3052 www.beckhoff.com/KL3122 www.beckhoff.com/KL3152
KL3052-00xx KL3122-0050
special terminals see 617 Siemens S7 format
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Analog Input KL3222, KL3201
-RL
572 4 8 4 8
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL32xx Analog Input
PT1000, Ni1000
+60 °C +60 °C
-25 °C -25 °C
+R +R +R +R1 -R1 +R
1 5 1 5 1 5
1 9 υ
+R2 -R2
2 10
υ +R3 -R3 +R
RL RL -R
2 6 2 6 3 11 2 6
+24 V υ
υ υ
+R4 -R4
Bus Terminal
4 12
+R5 -R5 +R
-R -R +R 5 13
3 7 3 7 3 7
0V
υ
+R6 -R6
6 14
+R7 -R7
-R 7 15 +R
4 8 4 8
+R8 -R8
4 8
υ
573
8 16
The Bus Terminal’s standard settings The Bus Terminal’s standard settings The Bus Terminal’s standard settings The Bus Terminal’s standard settings
are: resolution 0.1 °C in the tem- are: resolution 0.1 °C in the tem- are: resolution 0.25 °C in the tem- are: resolution 0.1 °C in the tem-
perature range of PT100 sensors perature range of PT100 sensors. perature range of Ni1000 sensors. perature range of Ni1000 sensors.
in 3-wire connection. The inputs have a common, internal
ground potential.
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Analog Input KL3311
1 5
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL3312, KL3314 Analog Input
KL3312 KL3314
2-wire 2-wire
~ 250 ms ~ 250 ms
2 4
+TC +TC
Bus Terminal
1 5 1 5
–TC –TC
2 6 2 6
575
+TC
3 7 3 7
–TC
4 8 4 8
The KL3312 analog input terminal allows two thermocouples to be connected The KL3314 analog input terminal allows four thermocouples to be connected
directly. The circuit of the Bus Terminal can operate thermocouples using directly. The circuit of the Bus Terminals can operate thermocouples using
2-wire technique. Linearisation over the full temperature range is realised 2-wire technique. Linearisation over the full temperature range is realised
with the aid of a microprocessor. Compensation for the cold junction is made with the aid of a microprocessor. Compensation for the cold junction is made
through an internal temperature measurement at the terminals. The KL3312 through an internal temperature measurement at the terminals. The KL3314
can also be used for mV measurement. can also be used for mV measurement.
< ±0.5 % (relative to full scale value) < ±0.5 % (relative to full scale value)
in the range defined in each case for the sensor in the range defined in each case for the sensor
(default setting: type K; -100…+1,370 °C); (default setting: type K; -100…+1,370 °C);
mV measurement: ±30 mV…±120 mV mV measurement: ±30 mV…±120 mV
– (no power contacts) – (no power contacts)
typ. 65 mA typ. 75 mA
– –
0…+55 °C 0…+55 °C
CE, UL, Ex CE, UL, Ex
approx. 70 g approx. 75 g
www.beckhoff.com/KL3312 www.beckhoff.com/KL3314
KL3312-xxxx
special terminals see page 617
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Analog Input KL3351, KL3356
+UV +UV
+UREF +UREF
1 5 1 5
-UD -UD
+UD +UD
2 6 2 6
+Uv
Bus Terminal
-UREF -UREF
-UV -UV
3 7 3 7
–Uv
576 4 8 4 8
The KL3351 analog input terminal permits direct connection The KL3356 analog input terminal permits direct connec-
of a resistor bridge. The bridge voltage, UD, and the supply tion of a resistor bridge. Its improved input circuit makes
voltage, UREF, to the bridge are digitised with 16 bit resolution, the KL3356 significantly more accurate than the KL3351.
and are transmitted along an electrically isolated channel to The ratio between the bridge voltage UD and the supply volt-
the supervising automation system. The input channels are age UREF is determined in the input circuit. In order to achieve
available in the form of two 16 bit values for further process- good long-term stability, the complete circuit is re-calibrated
ing. The resulting measurement can be calculated from the at least every three minutes. This procedure can be syn-
formula: measurement = UD/UREF. Precise acquisition of the chronised by the control in order to prevent the calibration
supply voltage along with the bridge voltage compensates leading to a delay in the production process.
for long-term and temperature drift.
Measuring error < ±0.1 % (relative to full scale value) < ±0.01 % (relative to full scale value)
Current consumption – (no power contacts) only load
power contacts
Current consumpt. K-bus typ. 65 mA typ. 85 mA
Internal resistance > 200 kΩ (UREF), > 1 MΩ (UD) > 200 kΩ (UREF), > 1 MΩ (UD)
Power supply UV 5 V DC, max. 20 mA via power contacts
Filter 50 Hz, configurable 50 Hz, configurable
Special features with internal bridge supply increased measuring accuracy, self-calibration
Operating temperature 0…+55 °C 0…+55 °C
Approvals CE, UL, Ex CE, UL, Ex
Weight approx. 70 g approx. 75 g
Further information www.beckhoff.com/KL3351 www.beckhoff.com/KL3356
Special terminals KL3351-0001
Distinguishing features with faster measurement time approx. 10 ms
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL3361, KL3362 Analog Input
+UV
1 5 1 5
-UB
+UB
2 6 2 6
Bus Terminal
-UV
3 7 3 7
4 8 4 8 577
The KL3361 and KL3362 analog input terminals make it possible to perform non-central preliminary processing of analog
values. The input values are digitised with a 14-bit resolution and written into an internal memory. An efficient processor can
pre-process the values. Limit values, maximum and minimum values will be determined or monitored. The Bus Terminals can
also carry out envelope curve monitoring. A trigger starts cyclical processes. The result or all the measured values are trans-
ported to the higher-level automation unit.
Measuring error < ±1 % (relative to full scale value) < ±0.5 % (relative to full scale value)
Current consumption – (no power contacts) – (no power contacts)
power contacts
Current consumption typ. 120 mA with external DMS power supply, typ. 140 mA typ. 120 mA
K-bus with internal DMS power supply from terminal (4 x 350 Ω)
Internal resistance > 1 MΩ (UB) > 500 kΩ
Supply voltage 5 V DC, max. 20 mA –
Power supply via the K-bus via the K-bus
Internal memory 32 kbytes 32 kbytes
Special features high-speed strain gauge analysis (for all fieldbuses) high-speed analog analysis
Operating temperature 0…+55 °C 0…+55 °C
Approvals CE, UL, Ex CE, UL, Ex
Weight approx. 55 g approx. 55 g
Further information www.beckhoff.com/KL3361 www.beckhoff.com/KL3362
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Analog Input KL3403
1 5 L1
500 k
40 m
2 6
500 k L2
40 m
578
3 7
L3
500 k
40 m
4 8
Measuring error 0.5 % relative to full scale value (U, I), 1 % calculated value
Current consumption – (no power contacts)
power contacts
Current consumpt. K-bus typ. 115 mA
Measuring procedure true RMS with 64,000 samples/s
Measured values current, voltage, effective power, energy, cos φ,
peak values U, I and P, frequency
Measuring current max. 1 A, via measuring max. 5 A (AC/DC), via meas-
transformers x A/1 A uring transformers x A/5 A
Electrical isolation 1,500 V (terminal/K-bus)
Special features energy meter, power measurement, True RMS
Operating temperature 0…+55 °C
Approvals CE, UL
Weight approx. 75 g
Further information www.beckhoff.com/KL3403
Special terminals KL3403-0020 KL3403-0022
Distinguishing features current path designed for current path and voltage
20 mA, optimised for elec- input designed for 20 mA
tronic current transformer
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL3681 Analog Input
Bus Terminal
1 5
digital multimeter.
12.5 M
In measuring applications in particular, 2 6
0.2
by LEDs.
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Analog Input KM3701
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KM3702, KM3712 Analog Input
KM3702 KM3712
2 2
Bus Terminal
581
The KM3702 pressure measuring terminal enables direct measurement of The KM3712 pressure measuring terminal enables direct measurement of
two pressure values at the hose connections. The pressure is determined as two negative pressure values at the hose connections. The pressure is deter-
a pressure difference to the ambiance of the KM3702 and is available in the mined as a pressure difference to the ambiance of the KM3712 and is avail-
fieldbus as a 16 bit value. The status LEDs indicate proper function or errors able in the fieldbus as a 16 bit value. The status LEDs indicate proper function
such as over-range. or errors such as over-range.
typ. 15 mA typ. 15 mA
10,000 hPa (10 bar) 5,000 hPa (5 bar)
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Analog Output KL4031, KL4032
2 6 2 6
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL4xxx Analog Output
4-channel analog 4-channel analog 8-channel analog 2-channel analog input, 2-channel analog
output terminal, output terminal, output terminal, 2-channel analog output output terminal,
-10…+10 V, 12 bits -10…+10 V, 12 bits -10…+10 V, 12 bits terminal, -10…+10 V, 12 bits -10…+10 V, 16 bits
KL4034 | KS4034 KL4434 | KS4434 KL4438 | KS4438 KL4494 | KS4494 KL4132 | KS4132
16 bits
1 5 1 5 1 5 1 5 1 5
Bus Terminal
2 6 2 6 2 6 2 6 2 6
3 7 3 7 3 7 3 7 3 7
583
4 8 4 8 4 8 4 8 4 8
The KL4034 analog output The KL4434 analog output The KL4438 analog output The KL4494 analog output The KL4132 analog output
terminal generates signals in terminal generates signals in terminal generates signals in terminal combines two terminal generates signals in
the range from -10 to +10 V. the range from -10 to +10 V. the range from -10 to +10 V. analog inputs and two ana- the range from -10 to +10 V.
It combines four output It combines four output It combines eight output log outputs. The input and It combines two output
channels, which have a com- channels, which have a com- channels in one housing and output channels of the Bus channels, which have a com-
mon ground potential in one mon ground potential in one is thus particularly suited Terminal have a common mon ground potential in one
housing. housing. for space-saving use in the ground potential. housing.
control cabinet. The 0 V
power contact serves as the – input internal resist-
common ground potential. ance: > 130 kΩ
< ±0.1 % (relative < ±0.1 % (relative < ±0.2 % (relative < ±0.3 % (relative < ±0.1 % (relative
to end value) to end value) to end value) to end value) to end value)
– (no power contacts) only load only load only load – (no power contacts)
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Analog Output KL400x
Resolution 12 bits
Number of outputs 1 2 4
+60 °C
-25 °C
Bus Terminal
1 5 1 5 1 5
2 6 2 6 2 6
584
3 7 3 7 3 7
4 8 4 8 4 8
The KL4001 analog output terminal The KL4002 analog output terminal The KL4004 analog output terminal
generates signals in the range from generates signals in the range from generates signals in the range from
0 to +10 V. It combines two output 0 to +10 V. It combines two output 0 to +10 V. It combines four output
channels, which have a common channels, which have a common channels, which have a common
ground potential in one housing. ground potential in one housing. ground potential in one housing.
Output error < ±0.1 % (relative to end value) < ±0.1 % (relative to end value) < ±0.1 % (relative to end value)
Current consumption – (no power contacts) – (no power contacts) – (no power contacts)
power contacts
Current consumpt. K-bus typ. 75 mA typ. 75 mA typ. 85 mA
Load > 5 kΩ (short-circuit-proof) > 5 kΩ (short-circuit-proof) > 5 kΩ (short-circuit-proof)
Special features potential-free output – –
Operating temperature 0…+55 °C -25…+60 °C 0…+55 °C
Approvals CE, UL, Ex CE, UL, Ex CE, UL, Ex
Weight approx. 85 g approx. 85 g approx. 85 g
Further information www.beckhoff.com/KL4001 www.beckhoff.com/KL4002 www.beckhoff.com/KL4004
Special terminals KL4002-00xx KL4004-0050
Distinguishing features special terminals see page 617 Siemens S7 format
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL4404, KL4408 Analog Output
~ 4 ms ~ 8 ms ~ 1.5 ms
4 8 2
Bus Terminal
1 5 1 5
2 6 2 6
585
3 7 3 7
4 8 4 8
The KL4404 analog output terminal The KL4408 analog output terminal The analog KM4602 output terminal has two potential-free analog
generates signals in the range from generates signals in the range from 0…10 V outputs. Both are connected internally to common ground.
0 to +10 V. It combines four output 0 to +10 V. It combines eight output For each channel a switch enables selection of automatic or manual
channels, which have a common channels in one housing and is thus mode. In automatic mode, an analog value is issued depending on the
ground potential in one housing. particularly suited to space-saving use process data. With the manual switch settings, the value set via the
in the control cabinet. The 0 V power potentiometer is applied to the output. For manual mode a 24 V supply
contact serves as the common ground is required for the Bus Coupler. The switch state can be read by the
potential. controller.
< ±0.1 % (relative to end value) < ±0.2 % (relative to end value) < ±0.1 % (relative to end value)
only load only load – (no power contacts)
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Analog Output KL4011, KL4012
Resolution 12 bits
Number of outputs 1 2
+60 °C
-25 °C
Bus Terminal
1 5 1 5
2 6 2 6
586
3 7 3 7
4 8 4 8
The KL4011 analog output terminal generates The KL4012 analog output terminal generates signals in
analog output signals in the range from 0 to 20 mA. the range from 0 to 20 mA. It combines two output channels,
which have a common ground potential with the 24 V DC
supply, in one housing. The output stages are powered by
the 24 V DC supply.
Output error < ±0.1 % (relative to end value) < ±0.1 % (relative to end value)
Current consumption typ. 30 mA + load typ. 50 mA + load
power contacts
Current consumpt. K-bus typ. 60 mA typ. 60 mA
Load < 500 Ω < 500 Ω
Power supply 24 V DC via power contacts (alternative 15 V DC 24 V DC via power contacts (alternative 15 V DC
with power supply terminal KL9515) with power supply terminal KL9515)
Special features – –
Operating temperature 0…+55 °C -25…+60 °C
Approvals CE, UL, Ex, GL CE, UL, Ex, GL
Weight approx. 80 g approx. 80 g
Further information www.beckhoff.com/KL4011 www.beckhoff.com/KL4012
Special terminals KL4012-00xx
Distinguishing features special terminals see page 617
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL441x, KL4112 Analog Output
~ 4 ms ~ 8 ms ~ 3.5 ms
4 8 2
Bus Terminal
1 5 1 5 1 5
2 6 2 6 2 6
587
3 7 3 7 3 7
4 8 4 8 4 8
The KL4414 analog output terminal generates The KL4418 analog output terminal generates The KL4112 analog output terminal generates
signals in the range from 0 to 20 mA. It combines signals in the range from 0 to 20 mA. It combines signals in the range from 0 to 20 mA. It combines
four channels, which have a common ground eight output channels in one housing and is thus two output channels, which have a common
potential in one housing. The output stages are particularly suited to space-saving use in the ground potential with the 24 V DC supply, in one
powered by the 24 V DC supply. control cabinet. The 0 V power contact serves as housing. The output stages are powered by the
the common ground potential. 24 V DC supply.
< ±0.1 % (relative to end value) < ±0.2 % (relative to end value) < ±0.1 % (relative to end value)
typ. 60 mA + load typ. 60 mA + load typ. 50 mA + load
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Analog Output KL4021, KL4022
Resolution 12 bits
Number of outputs 1 2
+60 °C
-25 °C
Bus Terminal
1 5 1 5
2 6 2 6
588
3 7 3 7
4 8 4 8
The KL4021 analog output terminal generates The KL4022 analog output terminal generates signals in
analog output signals in the range from 4 to 20 mA. the range from 4 to 20 mA. It combines two output channels,
which have a common ground potential with the 24 V DC
supply, in one housing. The output stages are powered by
the 24 V DC supply.
Output error < ±0.1 % (relative to end value) < ±0.1 % (relative to end value)
Current consumption typ. 30 mA + load typ. 50 mA + load
power contacts
Current consumpt. K-bus typ. 60 mA typ. 60 mA
Load < 500 Ω < 500 Ω
Power supply 24 V DC via power contacts (alternative 15 V DC 24 V DC via power contacts (alternative 15 V DC
with power supply terminal KL9515) with power supply terminal KL9515)
Special features – –
Operating temperature 0…+55 °C -25…+60 °C
Approvals CE, UL, Ex, GL CE, UL, Ex, GL
Weight approx. 80 g approx. 80 g
Further information www.beckhoff.com/KL4021 www.beckhoff.com/KL4022
Special terminals KL4022-00xx
Distinguishing features special terminals see page 617
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL4424, KL4428 Analog Output
single-ended single-ended
~ 4 ms ~ 8 ms
4 8
Bus Terminal
1 5 1 5
2 6 2 6
589
3 7 3 7
4 8 4 8
The KL4424 analog output terminal generates signals in the range from The KL4428 analog output terminal generates signals in the range from
4 to 20 mA. It combines four channels, which have a common ground poten- 4 to 20 mA. It combines eight output channels in one housing and is thus
tial in one housing. The output stages are powered by the 24 V DC supply. particularly suited to space-saving use in the control cabinet. The 0 V
power contact serves as the common ground potential.
< ±0.1 % (relative to end value) < ±0.2 % (relative to end value)
typ. 60 mA + load typ. 60 mA + load
typ. 20 mA typ. 20 mA
< 350 Ω (short-circuit-proof) < 150 Ω (short-circuit-proof)
24 V DC via power contacts (alternative 15 V DC 24 V DC via power contacts (alternative 15 V DC
with power supply terminal KL9515) with power supply terminal KL9515)
– increased packing density
0…+55 °C 0…+55 °C
CE, UL, Ex, GL CE, UL, Ex, GL
approx. 75 g approx. 75 g
www.beckhoff.com/KL4424 www.beckhoff.com/KL4428
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Position measurement KL5001, KL5051
2 6 2 6
+24 V +5 V
power contacts.
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL5121 Position measurement
Bus Terminal
3 7 3’ 7’
4 8 4’ 8’
591
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Position measurement KL5101
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL5111, KL515x Position measurement
1-channel incremental encoder interface, 1-channel incremental encoder interface, 2-channel incremental encoder interface,
16 bits, single-ended, 24 V DC 32 bits, single-ended, 24 V DC 32 bits, single-ended, 24 V DC
+60 °C
-25 °C
1 5 1 5 1 5
2 6 2 6 2 6
Bus Terminal
3 7 3 7 3 7
4 8 4 8 4 8
593
The KL5111 Bus Terminal is an interface for the The KL5151 Bus Terminal is an interface with 24 V The KL5152 Bus Terminal is an interface with
direct connection of 24 V incremental encoders. inputs for the direct connection of incremental en- 24 V inputs for the direct connection of incremen-
A 16 bit counter with a quadrature decoder and coders. A 32 bit counter with a quadrature decoder tal encoders. Two 32 bit counters with quadrature
a 16 bit latch for the zero pulse can be read, set and a 32 bit latch for the zero pulse can be read, decoders can be read or set.
or enabled. The state of the counter is transmitted set or enabled. The KL5151 inputs can optionally
quickly and securely to the PC, PLC or CNC over be used as single or two-counter inputs.
the fieldbus. Interval measurement with a resolu-
tion of 200 ns is possible.
24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %)
– – –
typ. 40 mA typ. 40 mA typ. 40 mA
24 V DC 24 V DC 24 V DC
– – –
16 bits, binary 32 bits, binary 32 bits, binary
1 million increments/s (with 4-fold evaluation) 400,000 increments/s (with 4-fold evaluation) 400,000 increments/s (with 4-fold evaluation)
4-fold evaluation 4-fold evaluation 4-fold evaluation
16 bits 32 bits –
read, set, enable read, set, enable read
– – –
0…+55 °C -25…+60 °C 0…+55 °C
CE, UL, Ex CE, UL, Ex CE, UL, Ex
approx. 60 g approx. 50 g approx. 50 g
www.beckhoff.com/KL5111 www.beckhoff.com/KL5151 www.beckhoff.com/KL5152
KL5111-00xx KL5151-0021
for special terminals see page 617 incremental encoder 1 x 32 bits A, B,
capture input and 1 driver output 24 V, 0.5 A
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Communication KL6001, KL6031
3 7 3 7
594 4 8 4 8
Data buffer 128 bytes receive buffer, 1024 bytes receive buffer,
16 bytes transmit buffer 128 bytes transmit buffer
Current consumption – (no power contacts) – (no power contacts)
power contacts
Current consumpt. K-bus typ. 55 mA typ. 55 mA
Cable length max. 15 m max. 15 m
Line impedance – –
Special features high interference immunity, high interference immunity,
electrically isolated signals electrically isolated signals
Operating temperature 0…+55 °C -25…+60 °C
Approvals CE, UL, Ex CE, UL, Ex
Weight approx. 80 g approx. 80 g
Further information www.beckhoff.com/KL6001 www.beckhoff.com/KL6031
Special terminals KL6001-0020
Distinguishing features standard format 5 bytes
of user data
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL60xx Communication
Serial interface RS422/RS485, Serial interface RS422/RS485, Serial interface TTY, Data exchange terminal
up to 19,200 baud up to 115.2 kbaud 20 mA current loop with serial interface
1,200…19,200 baud; 4,800…115,200 baud; 1,200…19,200 baud; 62,500 baud, 32 bits bidirectional
default: 9,600 baud, 8 data bits, default: 9,600 baud, 8 data bits, default: 9,600 baud, 8 data bits, data exchange between two KL6051
no parity and one stop bit no parity and one stop bit no parity and one stop bit
TxD and RxD, full/half duplex TxD and RxD, full/half duplex 2 (1/1), TxD and RxD, full duplex TxD and RxD, full duplex
+60 °C
-25 °C
1 5 1 5 1 5 1 5
2 6 2 6 2 6 2 6
Bus Terminal
3 7 3 7 3 7 3 7
4 8 4 8 4 8 4 8 595
The KL6021 and KL6041 serial interfaces allow devices with an RS422 or The KL6011 serial interface allows Under the terminal’s default set-
RS485 interface to be connected. The active communication channel operates devices with a 20 mA current inter- ting, 32 inputs and 32 outputs are
independently of the higher-level bus system in full or half duplex mode at face to be connected. The interface transferred between the fieldbus
up to 19,200 baud (KL6021) or 115.2 kbaud (KL6041). The transmission of operates passively. The current inter- systems. The time to exchange the
differential signals conforms to RS422 and guarantees high immunity to face (TTY) guarantees high immunity data is about 5 ms for 32 bits of I/O.
interference through electrically isolated signals. to interference through electrically The exchange of data with the Bus
isolated signals with injected current. Coupler is indicated by the run LED.
The TxD and RxD LEDs indicate the
state of the signal transmission.
128 bytes receive buffer, 1024 bytes receive buffer, 128 bytes receive buffer, 32 bit bidirectional
16 bytes transmit buffer 128 bytes transmit buffer 16 bytes transmit buffer
– (no power contacts) – (no power contacts) – (no power contacts) – (no power contacts)
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Communication KL6201, KL6211
Communication | AS-Interface
The AS-Interface master terminal is an AS-Interface AS-Interface
extended master according to the M3 master terminal master terminal
profile and enables the direct connection with power contacts
of AS-Interface slaves. The AS-compliant
interface supports digital and analog slaves
with the versions 2.0 and 2.1, safety slaves Technical data KL6201 | KS6201 KL6211 | KS6211
and slaves with Combined Transaction
Type 1 (profile S-7.3 and 7.4). Process data Technology AS-Interface
exchange, parameterisation and the diagno-
sis are fieldbus-independent. Together with Cycle time max. 5 ms (31 devices)
the various Bus Couplers, the KL6201 or the
KL6211 represents a universal AS-Interface/ Number of channels 1 1
fieldbus gateway. Together with the BK3120,
the PROFIBUS DP V1 services can be used
for communication with the KL6201 or the
KL6211. Unlike the KL6201 AS-Interface
master terminal, the KL6211 features power
contacts. This enables direct connection
1 5 1 5
Mode Mode Mode Mode
to the AS-Interface supply via the KL9520
AS-Interface potential feed terminal or the 2 6 2 6
ASi+
KL9528 power supply terminal.
Bus Terminal
596
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KM6551 Communication
Bus Terminal
Option 1 | Data exchange peer-to-peer
597
send output data
Master Slave
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Communication KL658x
Technology EnOcean
Number of channels 1 – –
1 7 8
KL6583 … KL6583 KL6583
A
B
1 5
+24 V
2 6
+24 V
Bus Terminal
0V
3 7
0V
max. 500 m
598 4 8
The bidirectional EnOcean technol- The KL6583 EnOcean module enables The KL6583-0100 EnOcean module
ogy receives signals from battery-less EnOcean data to be transmitted and enables EnOcean data to be trans-
sensors or transmits data to actuators. received. An antenna is integrated in mitted and received. An antenna is
With a radio signal range of 30 m, the the device. The KL6583 module is sup- integrated in the device. The KL6583-
wiring of buildings can be simplified plied with 24 V and offers a bus con- 0100 module is supplied with 24 V and
significantly. The KL6581 EnOcean mas- nection to the KL6581 EnOcean master offers a bus connection to the KL6581
ter terminal is the link between up to terminal. The KL6583 is addressed via EnOcean master terminal. The KL6583-
eight KL6583 EnOcean transmitter and an address selection switch. Up to eight 0100 is addressed via an address selec-
receiver modules and the application. KL6583 modules can be connected to tion switch. Up to eight KL6583-0100
a KL6581. modules can be connected to a KL6581.
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL602x Communication
Technology EnOcean
Number of channels 1 –
KL6023
1 5
2
+RxD
2 6
-RxD 6
Bus Terminal
GND
3 7
+5 V
4 8 599
max. 300 m
The KL6021-0023 serial interface enables connection The KL6023 Wireless Adapter receives signals from battery-
of a KL6023 wireless adapter. It processes the RS485 less sensors with EnOcean technology. These signals are con-
signals of the wireless adapter. verted by the Wireless Adapter to a RS485 signal and directly
processed further by the KL6021-0023 serial Bus Terminal.
The system does not limit the number of transmitters per
receiver unit. In practice, between 25 and 100 transmitters
per receiver are used.
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Communication KL6224, KL6301
EIB
IO-Link EIB
master terminal Bus Terminal
IO
1 5
1 9 Set Set
2 10
IO
2 6
+EIB
3 11
Bus Terminal
4 12
IO
5 13 -EIB
3 7
6 14
IO
7 15 Shield
600 4 8
8 16
The IO-Link terminal enables connection of up to four IO-Link The KL6301 EIB Bus Terminal is integrated in an EIB net-
devices. A point-to-point connection is used between the work and can receive/transmit data from/to other EIB devices.
terminal and the device. The terminal is parameterised via The Bus Terminal is commissioned or configured via TwinCAT
the master. 2-wire and 3-wire connections are supported. function blocks. Several KL6301 can be used with a single
Additional 24 V and 0 V connection points can be realised Bus Coupler or a Bus Terminal Controller. Up to 256 group
via the KL918x potential distributor terminal. addresses can be received; sending is only limited by the
application.
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL6401, KL6771 Communication
LON
LON MP-Bus
Bus Terminal master terminal
LON MP-Bus
1 1
5
1 5 1 5
Service Service
2
2 6 2 6
MP-Bus
Bus Terminal
slave
1
3 7 3 7
4 8 4 8 601
The KL6401 LON Bus Terminal enables direct connection of LON devices. The MP-Bus master terminal enables direct connection of MP-Bus slave
Several KL6401 can be used with a single Bus Coupler or a Bus Terminal devices. Up to sixteen field devices, eight drives and eight sensors can be
Controller. The KL6401 supports 62 SNVTs. All SNVT types can be configured connected to the KL6771. The Bus Terminal is configured and commissioned
as input or output variable via the KS2000 software. The KS2000 software via TwinCAT function blocks. Several KL6771 terminals can be connected to
generates an XIF file that is integrated in an LON tool. the same Bus Coupler or Bus Terminal Controller.
typ. 55 mA typ. 55 mA
FTT-10, LPT MP-Bus
CSMA polling
15 devices; TwinCAT library available 8 drives/sensors; TwinCAT library available
0…+55 °C 0…+55 °C
CE, Ex CE, UL, Ex
approx. 85 g approx. 85 g
www.beckhoff.com/KL6401 www.beckhoff.com/KL6771
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Communication KL6781, KL6811
M-Bus DALI
M-Bus DALI/DSI
master terminal master and power supply terminal
+DALI -DALI
1 5 1 5
2 6 2 6
+24 V +24 V
M-Bus
Bus Terminal
device
3 7 3 7
0V 0V
+DALI -DALI
602 4 8 4 8
The KL6781 M-Bus master terminal enables the direct con- The KL6811 enables the connection of up to 64 DALI slaves.
nection of M-Bus devices. The M-Bus (Meter Bus) is a field- The KS2000 software enables simple configuration via a PC
bus for the acquisition of consumption data from electricity, that is directly coupled with the Bus Coupler via an RS232
water, gas or energy meters. The KL6781 does not contain interface or via the fieldbus. The integrated power supply
the M-Bus protocol; instead, it converts the data present unit generates an electrically isolated 24 V DC output voltage.
on the terminal bus into M-Bus compliant physics. 24 byte No further components are required for the operation of the
data are available on the K-bus for this. In conjunction with DALI slaves. The KL6811 operates fieldbus-independent.
the TwinCAT M-Bus library, it is possible to work without
an external M-Bus gateway, i.e. the M-Bus devices can be
connected directly to the KL6781. With a total cable length
of 300 m, up to 40 M-Bus devices (each with a current
consumption of 1.5 mA) can be connected.
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL6904 Communication
Communication | TwinSAFE
TwinSAFE enables networks with up to TwinSAFE Logic Bus Terminal,
1,024 TwinSAFE devices. The KL6904 Bus 4 safe inputs
Terminal features certified safety function
blocks, which are configured according to
the application to be realised. Functions
such as emergency stop, safety door moni- Technical data KL6904
toring etc. can thus easily be selected and
linked. All blocks can be freely connected Technology TwinSAFE Logic
among each other and are complemented
by operators such as AND, OR, etc. The Safety standard IEC 61508 SIL 3 and DIN EN ISO 13849-1:2008 PLe
necessary functions are configured using
the TwinCAT System Manager and loaded Number of outputs 4
into the terminal via the fieldbus.
Protocol TwinSAFE/FSoE
For further information on TwinSAFE
and the TwinSAFE products
see page 856
1 5
2 6
Bus Terminal
3 7
4 8 603
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Power Terminals KL8001
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL8601, KL8610 Power Terminals
Bus Terminal
plane can thus be realised within the control
cabinet.
We reserve the right to make technical changes. BECKHOFF New Automation Technology
System Terminals KL91xx
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL9xxx System Terminals
+60 °C +60 °C
-25 °C -25 °C
1 5
2 6
Bus Terminal
3 7
4 8
607
We reserve the right to make technical changes. BECKHOFF New Automation Technology
System Terminals KL9180, KL9185
608
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL91xx System Terminals
Potential distribution Potential distribution Potential distribution Potential distribution Potential distribution
terminal, 8 x 24 V terminal, 8 x 0 V terminal, 8 x 24 V, 8 x 0 V terminal, 16 x 24 V terminal, 16 x 0 V
+60 °C +60 °C
-25 °C -25 °C
+24 V 1 5
+24 V 0V 1 5
0V +24 V 0V +24 V +24 V 0V 0V
1 9 1 9 1 9
Bus Terminal
+24 V 0V +24 V +24 V 0V 0V
+24 V +24 V 0V 0V 7 15 7 15 7 15
4 8 4 8
+24 V 0V +24 V +24 V 0V 0V
8 16 8 16 8 16
609
≤ 60 V DC ≤ 60 V DC ≤ 60 V DC ≤ 60 V DC ≤ 60 V DC
≤ 10 A ≤ 10 A ≤ 10 A ≤ 10 A ≤ 10 A
– – – – –
– – – – –
– – – – –
– – – – –
– – – – –
– – – – –
We reserve the right to make technical changes. BECKHOFF New Automation Technology
System Terminals KL90xx
+60 °C
-25 °C
Bus Terminal
610 The KL9060 Bus Terminal The KL9020 forms a prop- The KL9050 coupler terminal
enables a connection to the erly working unit together replaces the Bus Coupler
KL8001. For further informa- with at least one KL9050. on a Bus Terminal block.
tion see page 604 No further parameterisation The second RJ 45 socket
or configuration work is allows the system to be
necessary. extended further. The whole
system can be extended by
31 stations.
Nominal voltage – 24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %)
Current load – ≤ 10 A ≤ 10 A ≤ 10 A
Power LED – – – green
Defect LED – – – –
PE contact – yes – yes
Current consumption – – typ. 70 mA typ. 70 mA + (total K-bus
K-bus current)/4, max. 200 mA
Distance between – – max. 5 m between max. 5 m between
stations KL9020 and KL9050 KL9050 and KL9050
Starting current – – – 2.5 x continuous current
Current supply K-bus – – – up to 400 mA
Electrical isolation – 500 V (power contact/ 500 V (power contact/ 500 V (power contact/
supply voltage/K-bus) supply voltage/K-bus) supply voltage/fieldbus)
Special features end terminal for connection to KL8001 via end terminal coupler terminal
bus communication 20-pin flat ribbon plug for K-bus extension for K-bus extension
(max. 64 Bus Terminals)
Operating temperature -25…+60 °C 0…+55 °C 0…+55 °C 0…+55 °C
Approvals CE, UL, Ex, GL CE CE, UL, Ex, GL CE, Ex, GL
Weight approx. 50 g approx. 65 g approx. 45 g approx. 75 g
Further information www.beckhoff.com/KL9010 www.beckhoff.com/KL9060 www.beckhoff.com/KL9020 www.beckhoff.com/KL9050
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL93xx System Terminals
1 5 1 5 1 5
2 6 2 6 2 6
Bus Terminal
3 7 3 7 3 7
4 8 4 8 4 8
611
We reserve the right to make technical changes. BECKHOFF New Automation Technology
System Terminals KL9400, KL9505
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL95xx System Terminals
Power supply terminal, Power supply terminal, Power supply terminal, Power supply terminal, Power supply terminal,
8 V DC 10 V DC 12 V DC 15 V DC 24 V DC, electrical isolation
KL9508 | KS9508 KL9510 | KS9510 KL9512 | KS9512 KL9515 | KS9515 KL9560 | KS9560
power supply terminal, power supply terminal, power supply terminal, power supply terminal, power supply terminal,
8 V DC, with diagnostics 10 V DC, with diagnostics 12 V DC, with diagnostics 15 V DC, with diagnostics 24 V DC
2 6 2 6 2 6 2 6 2 6
3 7 3 7 3 7 3 7 3 7
Bus Terminal
4 8 4 8 4 8 4 8 4 8
The KL9508 generates 8 V The KL9510 generates 10 V The KL9512 generates 12 V The KL9515 generates 15 V The KL9560 generates 613
from the fed-in 24 V without from the fed-in 24 V without from the fed-in 24 V without from the fed-in 24 V without potential-free 24 V
electrical isolation. electrical isolation. electrical isolation. electrical isolation. from the fed-in 24 V
with electrical isolation.
24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %) 24 V DC (-15 %/+20 %)
8 V DC ±1 % 10 V DC ±1 % 12 V DC ±1 % 15 V DC ±1 % 24 V DC (-15 %/+5 %)
0.5 A 0.5 A 0.5 A 0.5 A ≤ 0.1 A
yes yes yes yes yes,
automatic restart
< 5 mV < 5 mV < 5 mV < 5 mV no data
– – – – –
– – – – 1,500 V AC
constant load
input/output voltage
stabilised analog voltage stabilised analog voltage stabilised analog voltage stabilised analog voltage analog voltage with
electrical isolation
0…+55 °C 0…+55 °C 0…+55 °C 0…+55 °C 0…+55 °C
CE, UL, Ex CE, UL, Ex CE, UL, Ex CE, UL, Ex CE, UL, Ex, GL
approx. 65 g approx. 65 g approx. 65 g approx. 65 g approx. 65 g
www.beckhoff.com/KL9508 www.beckhoff.com/KL9510 www.beckhoff.com/KL9512 www.beckhoff.com/KL9515 www.beckhoff.com/KL9560
We reserve the right to make technical changes. BECKHOFF New Automation Technology
System Terminals KL9520, KL9528
BECKHOFF New Automation Technology We reserve the right to make technical changes.
KL9540, KL9550 System Terminals
+60 °C +60 °C
-25 °C -25 °C
1 5 1 5 1’ 5’ 1 5
U U
+24 V
2 6 2 6 2’ 6’ 2 6
0V
3 7 3 7 3’ 7’ 3 7
Bus Terminal
4 8 4 8 4’ 8’ 4 8
The KL9540 system terminal contains an overvoltage filter for the 24 V field supply, the KL9550 for the 24 V field and system 615
supply. The filter protects the Bus Terminals from line-bound surge voltages that can occur due to high-energy disturbances
such as switching overvoltages at inductive consumers or lightning strikes at the supply lines. The Bus Terminals KL9540 or
KL9550 protect the Bus Terminal station from damage in particularly harsh environments. The use of such overvoltage filters
is stipulated by the ship classification organisations in shipbuilding and on/offshore applications in which GL certification is
required.
The KL9540-0010 is intended in particular for the protection of analog terminals; the standard variant KL9540 for digital
terminals. The terminal does not transfer process data to the higher-level control system.
We reserve the right to make technical changes. BECKHOFF New Automation Technology
System Terminals KL9570
10
2 6
3 7
Bus Terminal
4 8
Nominal voltage 50 V
Capacity 500 µF
Ripple current 10 A in continuous operation
Internal resistance < 10 mΩ
Surge voltage protection > 56 V
Recommended 10 Ω, typ. 10 W
ballast resistor
Overvoltage ±2 V
control range
Ballast resistor load-dependent, 2-point control
clock rate
Electrical isolation 1,500 V (terminal/K-bus)
Operating temperature 0…+55 °C
Approvals CE, Ex
Weight approx. 65 g
Further information www.beckhoff.com/KL9570
BECKHOFF New Automation Technology We reserve the right to make technical changes.
Special Terminals
Ordering information
Bus Coupler
BK8100-0060 watchdog special setting 60 s
BK8100-1001 watchdog special setting 10 s
Digital input
KL1052-0010 96 V DC positive and negative switching, not in accordance with the EN 61131-2 specifications:
I high = 3 mA, I low = 0.5 mA
KL1232-0001 plus-switching, positive edge-triggered input, 10 ms pulse extension, input filter 0.2 ms
KL1232-0002 plus-switching, positive edge-triggered input, 20 ms pulse extension, input filter 0.2 ms
KL1232-0010 plus-switching, positive edge-triggered input, 100 ms pulse extension, input filter 3.0 ms
KL1232-0100 plus-switching, negative edge-triggered input, 100 ms pulse extension, input filter 0.2 ms
KL1232-0110 plus-switching, negative edge-triggered input, 100 ms pulse extension, input filter 3.0 ms
KL1232-1000 negative switching, positive edge-triggered input, 100 ms pulse extension, input filter 0.2 ms
KL1232-1001 5 V, negative switching, negative edge-triggered input, 20 ms pulse extension, input filter 0.2 ms
KL1232-1010 negative switching, positive edge-triggered input, 100 ms pulse extension, input filter 3.0 ms
KL1232-1100 negative switching, negative edge-triggered input, 100 ms pulse extension, input filter 0.2 ms
KL1232-1110 negative switching, negative edge-triggered input, 100 ms pulse extension, input filter 3.0 ms
Bus Terminal
KL1232-2000 plus switching, positive edge-triggered input, 200 ms pulse extension, input filter 0.2 ms
KL1501-0010 gate-counter with auto-reset and setting A0
KL1501-0011 up/down counter with 5 V inputs, 24 V DC outputs
KL1702-0010 230 V AC input circuit with type 2 characteristics 617
KL1712-0010 24 V AC/DC input circuit
Digital output
KL2502-0012 time-delayed setting of the outputs
KL2502-3020 5 V output, 30 kHz limit frequency
KL2521-0010 with additional outputs (230 V AC/DC, 100 mA) instead of the additional inputs of the default variant
KL2521-0024 for 24 V signal level
KL2541-0006 stepper motor terminal 50 V DC, 5 A, 5 V encoder supply
KL2692-1001 2 digital inputs, 2 potential-free relays, end terminal variant
KL2702-0020 2-channel solid state load relay up to 230 V AC/DC, 1.5 A
KL2722-0010 without reciprocal locking of the channels, total current 1 A
KL2732-0010 without reciprocal locking of the channels, total current 1 A
KL2751-0011 dimmer terminal without power contacts
KL2751-1200 dimmer terminal for 120 V AC
KL2761-0011 1-channel universal dimmer terminal, 230 V AC, 600 VA (W), 50 Hz, without power contacts
KL2791-0011 1-channel AC motor speed controller, 230 V AC, 200 VA, max. 0.9 A, without power contacts
KL2791-1200 1-channel AC motor speed controller, 120 V AC, 100 VA
Analog input
KL3002-0010 Siemens S5 format
KL3002-0011 fast µP, scan time approx. 0.5 ms
KL3002-0050 Siemens S7 format
KL3012-0011 altered range: 0…21.5 mA, maximum value corresponds to 21.5 mA instead of 20 mA
KL3012-0012 fast µP, scan time approx. 0.5 ms
KL3012-0050 Siemens S7 format
KL3022-0010 Siemens S5 format
KL3022-0011 fast µP, scan time approx. 0.5 ms
KL3022-0050 Siemens S7 format
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Special Terminals
BECKHOFF New Automation Technology We reserve the right to make technical changes.
Special Terminals
KL3312-0022 type S
KL3312-0023 type S in Siemens S5 format
KL3312-0024 type T
KL3312-0025 type T in Siemens S5 format
KL3312-0026 type U
KL3312-0027 type U in Siemens S5 format
KL3312-0028 0…120 mV measurement
KL3312-0029 type K in Siemens S5 format
KL3312-0040 expanded temperature range for type S and L type S: -50…+1,700 °C (as supplied type L: -100…+900 °C)
KL3312-0110 type J, Fahrenheit scaling
KL3312-2000 setting of reference junction temperature via process image, unit 1/256° C in a 16 bit word
KL3312-2100 external reference point temperature specification via process image is possible,
the unit is 1/256 °C in 16-bit format, fast conversion time 65 ms
KL3351-0001 1-channel resistor bridge terminal (strain gauge), with faster measurement time approx. 10 ms
KL3403-0010 3-phase power measurement terminal, current path designed for 5 A transducer (1 % measuring accuracy I)
KL3403-0020 3-phase power measurement terminal, current path designed for 20 mA, optimised for electronic current transformer
KL3403-0022 3-phase power measurement terminal, current path and voltage input designed for 20 mA
KL3403-0333 3-phase power measurement terminal, 500 V AC, 333 mV AC
KM3701-0340 differential pressure up to 340 hPa
Analog output
KL4002-0010 Siemens S5 format
KL4002-0011 fast µP, scan time approx. 0.15 ms
KL4002-0050 Siemens S7 format
KL4004-0050 Siemens S7 format
KL4012-0010 Siemens S5 format
Bus Terminal
KL4012-0011 altered range: 0…21.5 mA, maximum value corresponds to 21.5 mA instead of 20 mA
KL4012-0050 Siemens S7 format
KL4022-0010 Siemens S5 format
KL4022-0050 Siemens S7 format 619
KL4032-0010 Siemens S5 format
KL4032-0011 fast µP, scan time approx. 0.15 ms
KL4032-0050 Siemens S7 format
KL4034-0010 Siemens S5 format
KL4112-0010 Siemens S5 format
KL4112-0050 Siemens S7 format
KL4132-0010 Siemens S5 format
KL4132-0050 Siemens S7 format
Special functions
KL5111-0010 A, B, C signals: 5 V inputs
KL5111-0011 special function: latch input sets counter to zero
KL5111-0012 latches on both edges, A, B, C inputs 24 V
KL5111-0013 latches on both edges, A, B, C inputs 5 V
KL5111-0015 frequency measurement over a selectable time window; 24 V inputs
KL5111-0016 frequency measurement over a selectable time window; 5 V inputs
KL5111-0020 12 V input circuit
KL5151-0021 incremental encoder 1 x 32 bits A, B, capture input and 1 driver output 24 V, 0.5 A
KL5151-0050 incremental encoder 2 x 32 bits A, B-track
KL6001-0020 standard format 5 bytes of user data
KL6011-0020 standard format 5 bytes of user data
KL6021-0020 standard format 5 bytes of user data (rest default)
KL6021-0021 standard format 5 bytes of user data (7 bits, even, 1 stop bit, 9,600 baud)
KL6201-0010 preset to 22 bytes K-bus interface (2 K-bus cycles 31 AS-Interface slaves)
KL6201-0011 preset to 38 bytes K-bus interface (4 K-bus cycles 62 AS-Interface slaves)
KL6904-0001 TwinSAFE Logic Bus Terminal, preconfigured ex factory to 15 TwinSAFE connections
System terminals
KL9210-0020 with 2 A fuse (slow-blow) and modified label
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Accessories
PROFIBUS Description
ZB3100 9-pin D-sub connector for PROFIBUS (12 Mbaud) with switchable termination resistor
ZB3101 9-pin D-sub connector for PROFIBUS (12 Mbaud) with programming interface
ZB3102 9-pin D-sub connector for PROFIBUS (12 Mbaud) with programming interface (housing invers)
ZS1031-3000 9-pin D-sub connector for PROFIBUS (12 Mbaud) with integrated termination resistor
ZS1031-3500 fibre optic connector for Bus Coupler BK3500 and BK3520
Interbus Description
Z1003 FSMA plug with knurled nut for 1,000 µm plastic fibre
ZB4100 9-pin D-sub socket for incoming remote bus
ZB4101 9-pin D-sub plug for outgoing remote bus
Bus Terminal
CANopen/DeviceNet Description
ZS1051-3000 9-pin D-sub connector for CANopen with integrated termination resistor
ZS1052-3000 5-pin open style connector for CANopen/DeviceNet with integrated termination resistor
620 ZS1052-5150 CAN diagnostic interface
A B
BECKHOFF New Automation Technology We reserve the right to make technical changes.
Accessories
Bus Terminal
Ordering information Description
ZK1010-8080-3003 ribbon cable (3 cm) for connecting two KL8001 (included in the scope of supply)
ZK1010-8080-3005 ribbon cable (5 cm) for connecting two KL8001, if a reversing contactor connection is used 621
ZK1010-8080-3010 ribbon cable (10 cm) for connecting the KL9060 with the KL8001 (included in the scope of supply for KL9060)
ZS1010-1610 end plug for KL8001 (included in the scope of supply for KL9060)
ZK1090-0101-1002 extension cable with two plugs, double screened, red, 20 cm, cable for TeSys module KL8601/KL8610
ZK1090-0101-1005 extension cable with two plugs attached, double screened, red, 50 cm, cable for TeSys module KL8601/KL8610
ZK1090-0101-1010 extension cable with two plugs attached, double screened, red, 100 cm
ZK1090-0101-1020 extension cable with two plugs attached, double screened, red, 200 cm
ZK1090-0101-1030 extension cable with two plugs attached, double screened, red, 300 cm
ZK1090-0101-1050 extension cable with two plugs attached, double screened, red, 500 cm
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Accessories
Cables
Lightbus Description
Z1100 plastic fibre optic, single core, 1,000 µm, 2.2 mm
Z1101 plastic fibre optic, single core, 1,000 µm with protective PU cladding and Kevlar strain relief, drag chain suitable
Z1111 HCS fibre optic, single core, 200 µm with protective PU cladding and Kevlar strain relief
PROFIBUS Description
ZB3200 PROFIBUS cable 12 Mbaud 1 x 2 x 0.64 mm²
Z1100 plastic fibre optic, single core, 1,000 µm, 2.2 mm
Z1101 plastic fibre optic, single core, 1,000 µm with protective PU cladding and Kevlar strain relief, drag chain suitable
Interbus Description
ZB4200 Interbus remote bus cable, certified 3 x 2 x 0.22 mm²
Z1120 Interbus plastic fibre optic, 2-core, 1,000 µm
Z1121 Interbus plastic fibre optic, 2-core, 1,000 µm with protective PU cladding
CANopen Description
ZB5100 CAN cable, 4-core, fixed laying 2 x 2 x 0.25 mm²
DeviceNet Description
ZB5200 DeviceNet cable, 4-core with screen, fixed laying 2 x 2/22 AWG
Ethernet/EtherCAT Description
ZB9010 Industrial Ethernet/EtherCAT cable, fixed installation, CAT 5e, 4 wires
Bus Terminal
ZB9020 Industrial Ethernet/EtherCAT cable, drag chain suitable, CAT 5e, 4 wires
622
Patch cables
Ethernet/EtherCAT Description
ZK1090-9191-0001 Industrial Ethernet/EtherCAT patch cable, 0.17 m
ZK1090-9191-0002 Industrial Ethernet/EtherCAT patch cable, 0.26 m
ZK1090-9191-0005 Industrial Ethernet/EtherCAT patch cable, 0.5 m
ZK1090-9191-0010 Industrial Ethernet/EtherCAT patch cable, 1.0 m
ZK1090-9191-0020 Industrial Ethernet/EtherCAT patch cable, 2.0 m
ZK1090-9191-0030 Industrial Ethernet/EtherCAT patch cable, 3.0 m
ZK1090-9191-0050 Industrial Ethernet/EtherCAT patch cable, 5.0 m
ZK1090-9191-0100 Industrial Ethernet/EtherCAT patch cable, 10.0 m
ZK1090-9191-0150 Industrial Ethernet/EtherCAT patch cable, 15.0 m
ZK1090-9191-0200 Industrial Ethernet/EtherCAT patch cable, 20.0 m
ZK1090-9191-0250 Industrial Ethernet/EtherCAT patch cable, 25.0 m
ZK1090-9191-0300 Industrial Ethernet/EtherCAT patch cable, 30.0 m
ZK1090-9191-0350 Industrial Ethernet/EtherCAT patch cable, 35.0 m
ZK1090-9191-0400 Industrial Ethernet/EtherCAT patch cable, 40.0 m
ZK1090-9191-0450 Industrial Ethernet/EtherCAT patch cable, 45.0 m
ZK1090-9191-0500 Industrial Ethernet/EtherCAT patch cable, 50.0 m
Fur further information see page 416
BECKHOFF New Automation Technology We reserve the right to make technical changes.
Accessories
Relays
Ordering information Description
ZB2601 relay, 230 V AC, 16 A, coil 24 V, spare part KM2604
ZB2602 relay, manual operation, 230 V AC, 16 A, coil 24 V, spare part KM2614
Bus Terminal
Assembly aids 623
If desired, the housings can be supplied fully fitted with Bus Couplers, Bus Terminals, flanges and PG threaded fittings.
Further sizes are available on request.
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Accessories
Marking material
The KLxxxx Bus Terminals can be individually labelled with standard contact signs. Signs with markings for the supply voltages are supplied
together with the BKxxxx Bus Couplers, but can be changed if required. The marking material is not included in the Bus Terminal delivery.
BZ5100 push-in strips for labels, A4 sheet, 160 pieces, pre-punched, packing unit = 10
624
Slide-in label cover, transparent
The slide-in label covers BZ3200 enable clear labelling of the individual channels or text-based functional description of the EtherCAT Terminals.
The labels are inserted in the designated slots. For connecting the individual channels the label cover can be tilted upwards.
A B C C
BECKHOFF New Automation Technology We reserve the right to make technical changes.
Accessories
Demokits
The Demokits offer a convenient (BCxxxx). A Bus Coupler serves Each Demokit consists of: If required for the respective
and fast introduction to fieldbus as a physical interface between – BKxxxx Bus Coupler or BCxxxx Demokit, the following addi-
communication with TwinCAT. the selected fieldbus and the I/O Bus Terminal Controller tional components are included:
Currently more than 10 field- terminals. It is therefore not pro- – 2 digital input terminals – programming cable
buses are covered, including grammable. In these Demokits 24 V DC (if a BCxxxx Bus Terminal
Lightbus, RS232, PROFIBUS, the connected terminals receive – 2 digital output terminals Controller is used)
Ethernet, and EtherCAT. The aim their data from a higher-level 24 V DC – TwinCAT PLC licence
of the Demokits is to familiarise PC. In contrast, the Bus Terminal – Beckhoff product folder – end terminal
the user with the basic TwinCAT Controllers are programmed – Beckhoff TwinCAT CD – fieldbus cable
automation procedures. Program from a PC via the selected – “TwinCAT Quickstart” (e.g. PROFIBUS or
creation and interfacing of the fieldbus or a programming documentation SERCOS cable)
program with the hardware is cable based on IEC 61131. – documentation describing – fieldbus interface card for
explained in detail, based on After programming, the Bus the Bus Coupler or Bus the PC (e.g. PROFIBUS PCI
examples. For many fieldbuses Terminal Controllers autono- Terminal Controller used master card or SERCOS PCI
the Demokits are available both mously manage the connected – a 25 cm section of 35 mm master card)
with Bus Couplers (BKxxxx) I/O terminals without involve- mounting rail for fitting the
and Bus Terminal Controllers ment from the PC. terminal system
Ordering information Demokits with Bus Coupler and TwinCAT PLC licence
TC9910-B110 EtherCAT, EK1100, EtherCAT Terminals
TC9910-B111 EtherCAT, EK1100, EtherCAT Terminals (without PLC licence)
TC9910-B112 EtherCAT, EK1100, EtherCAT Terminals (without PLC licence) (1 instead of 2 digital input terminals)
Bus Terminal
TC9910-B200 Lightbus, BK2020
TC9910-B310 PROFIBUS, BK3150
TC9910-B400 Interbus, BK4020
TC9910-B510 CANopen, BK5120 625
TC9910-B520 DeviceNet, BK5220
TC9910-B750 SERCOS, BK7520
TC9910-B800 RS485, BK8000
TC9910-B810 RS232, BK8100
TC9910-B900 Ethernet TCP/IP, BK9100
TC9910-B903 PROFINET, BK9103
TC9910-B905 EtherNet/IP, BK9105
Ordering information Demokits with Bus Terminal Controller and TwinCAT PLC licence
TC9910-C200 Lightbus, BC2000
TC9910-C310 PROFIBUS, BC3150
TC9910-C400 Interbus, BC4000
TC9910-C730 Modbus, BC7300
TC9910-C800 RS485, BC8000
TC9910-C810 RS232, BC8100
TC9910-C815 RS232, BC8150
TC9910-C900 Ethernet TCP/IP, BC9100
We reserve the right to make technical changes. BECKHOFF New Automation Technology
Accessories
BECKHOFF New Automation Technology We reserve the right to make technical changes.
Accessories
Bus Terminal
Elevation base diameter: 12 mm
Operating temperature -40…+80 °C
Mounting direct connection, with angle joint
Matching cables not applicable, direct connection 627
Antenna cables
Ordering information Description
ZK6000-0102-0020 coaxial cable, 50 Ω impedance, with attached connectors (SMA plug and reverse SMA socket), black, 200 cm
ZK6000-0102-0040 coaxial cable, 50 Ω impedance, with attached connectors (SMA plug and reverse SMA socket), black, 400 cm
We reserve the right to make technical changes. BECKHOFF New Automation Technology