DROOP 10V
2400 Hz 5K
PICK-UP BATTERY
IDLE OUTPUT
ACTUATOR
- + AUX 3000 Hz 10 K
A B C D E F G H J K L M N P
GROUND TO CASE GROUND TO CASE 3500 Hz 25 K
(One End Only) (One End Only)
3700 Hz 50 K
OPTIONAL ACTUATOR
CABLE SHIELDING TO
MEET CE DIRECTIVE Conversion Formulas
* (HertzMAG PICKUP x 60sec)
(RPM x #Teeth) RPM =
ACTUATOR
HertzMAG PICKUP = #Teeth
60sec
4
MAGNETIC
PICK-UP TERMINAL “M” IDLE SWITCH (OPTIONAL)
_ + S1
FUSE PICK-UP BATTERY DROOP 10V
BATTERY 15A MAX IDLE OUTPUT
ACTUATOR
- + AUX
* SEE SPECIFIC ACTUATOR PUBLICATION FOR PROPER
WIRING OF ACTUATOR BASED ON BATTERY VOLTAGE
A B C D E F G H J K L M N P
3
GROUND TO CASE GROUND TO CASE
TERMINALS G & J - TRIM POT. WIRING
PICK-UP BATTERY DROOP 10V
IDLE OUTPUT
OPTIONAL ACTUATOR
ACTUATOR
- + AUX CABLE SHIELDING TO
MEET CE DIRECTIVE
A B C D E F G H J K L M N P
GROUND TO CASE GROUND TO CASE *
ACTUATOR
DROOP DROOP
*
IMPORTANT::
CW Speed Adjustment Is a
25 Turn Potentiometer
* Select proper potentiometer
value from Table 1
ESD5500 Series Controller Wiring 4.28.2017 PIB1119 A
1 © 2017 Copyright All Rights Reserved
IDLE SPEED SETTING AUXILIARY / ACCESSORY INPUT - TERMINAL “N”
Place the optional external selector switch in the IDLE position. The idle speed set
point is increased by the clockwise rotation of the IDLE adjustment control. When
the engine is at idle speed, the speed control unit applies droop to the governor
system to insure stable operation.
A B C D E F G H J K L M N P
GROUND TO CASE GROUND TO CASE
(One End Only) (One End Only)
OPTIONAL ACTUATOR
CABLE SHIELDING TO
MEET CE DIRECTIVE
*
ACTUATOR
MAGNETIC
PICK-UP
CLOSE FOR DROOP
7 TERMINAL “P” ACCESSORY 10V OUTPUT
The +10 volt regulated supply, Terminal P, can be utilized to provide power to
_ + S1 GAC governor system accessories. Up to 20 mA of current can be drawn from
FUSE
BATTERY 15A MAX this supply. Ground reference is Terminal G.
* SEE SPECIFIC ACTUATOR PUBLICATION FOR PROPER
WIRING OF ACTUATOR BASED ON BATTERY VOLTAGE
A short circuit on this terminal can damage the speed control
Droop is typically used for the paralleling of engine driven generators. When in CAUTION
unit. Do not connect ‘N’ and ‘P’ directly to each other.
droop operation, the engine speed will decrease as engine load increases. The
percentage of droop is based on the actuator current change from no engine
load to full load.
(mm)
Dimensions in
Place the optional external selector switch in the DROOP position. DROOP is
increased by clockwise rotation of the DROOP adjustment control.
After the droop level has been adjusted, the rated engine speed setting may
need to be reset. Check the engines speed and adjust that speed setting ac-
cordingly.
When an accessory is connected to Terminal N, the speed will decrease and the
speed adjustment must be reset.
If the auto synchronizer is used alone, not in conjunction with a load sharing module,
a 3 ohm resistor should be connected between Terminals N and P. This is required
to match the voltage levels between the speed control unit and the synchronizer.