Professional Documents
Culture Documents
Failure To TriD: The most undesirable function Low ratio ct saturation for high currents will
which may result due to a saturated ct is a failure of cause the relay time current characteristic to be slower
a protective device to trip when the secondary current than published values or to fail to operate. In
is either very low or extremely distorted. For example, addition, the saturated ct output is rich in odd order
fault current at the medium voltage switchgear may be harmonics which can be detrimental to the mechanical and
higher than 20,000A. A ct with a 50/5A ratio for a electrical operation of the connected relays.
small load off the switchgear will most likely saturate Saturation will cause very dissimilar outputs from cts
to the point where it cannot be expected to deliver connected to a current differential relay. This problem
current sufficient to trip an instantaneous overcurrent will be severely aggravated for transformer differential
relay. In such conditions, backup relays may operate to applications because of the usual need for applying low
isolate the fault after extended time delay, resulting ratio and high ratio cts.
in de-energizing the entire bus. This may ultimately
result in tripping a generating station or similar large THE PRACTICAL APPROACH TO APPLYING LOW RATIO CTS
faci 1 i ty .
The knowledg! that low ratio current transformers,
with their low C" rating, could easily go into
Failure To Block TriDDinq of Overdutied Devices: saturation has been long understood. This knowledge has
Overdutied fault interrupting equipment (starter, load dictated a number of basic philosophies in applying
switch, or circuit switcher) is sometimes applied where these cts and the corresponding relay types. One basic
the tripping is blocked by high speed fault sensing rule-of-thumb has applied in the application of cts,
relays if the fault current exceeds the equipment namely: The kneepoint voltage o f the ct as defined by
interrupting capability. Saturation of a ct could the ct excitation curve should not be less than twice
prevent proper blocking by the fault sensing relay and the voltage required to drive the maximum secondary
permit interruption attempt of fault current in excess symmetrical current through the combined burden o f the
of the equipment rating. Application of such a blocking relay, connecting wiring, and ct. See Figure 1. This
scheme must include careful evaluation of the ct requirement frequently results in application of the
characteristic so that the desired blocking will be higher ratio cts to provide a "C" rating sufficient for
dependabl e. the connected burden.
155
POWER SYSTEM CONSTRAINTS THAT MAY REOUIRE
HIGH-SPEED TRIPPING
is (rmr sym) x 2 , T
n 2 Several factors may prompt the choice o f high-
w CT Application Ruleoi-Thumb speed clearing of faults. Stability of rotating
m
c
machinery, thermal storage to equipment such as
transformers, buswork, and safety ground grids,
$ coordination of serial current sensing protective
devices, etc., all require the accurate measurement of
P magnitude and duration of current. This requirement is
=Yc especially true during conditions such as faults,
ij
w
X transformer energization, motor starting in-rush, etc.
--
T Re1 ay
CB
Load
1
E: Ft
{
FIG. 4 CT Saturation Could Result in Loss of so01
c10 s VB = 1ov
Coordination Between the Relay and the Fuse
CT 1001s 1001s
ClO C20
10015 IWlS
CfO
U 0
FIG. 5 Use of Time Delay May Permit Use of FIG. 6 Comparison o f the primary current that can
Overcurrent Relay For Device 87 Even with be carried by cts using series secondaries
Mismatched CTs versus a single ct to yield comparable
accuracy.
C T PERFORMANCE IMPROVEMENT (a) Single ct
AND CORRECTIVE ALTERNATIVES (b) Two identical cts with series
secondaries and same voltage
capability and ratio as a single ct
There are some improvements and some corrective (c) Two identical cts with series
alternatives that can be made to the overall accuracy of secondaries and same voltage
a l o w ratio ct scheme. These improvements are mentioned capability and ratio as a single ct
here because manufacturers sometimes will provide the ct but with twice the ratio
connections as described below to meet a customer's (d) Two identical cts with series
accuracy requirement, The corrective alternatives secondaries and twice the voltage
discussed provide a more complete solution but may be capability and ratio of a single ct
expensive and/or physically difficult to implement.
CT Performance ImDrovement Considerations
Series Connection: Use two identical toroidal cts
with series secondary windings to approximately double
the ct voltage capability as compared to the use of a Parallel Connection: Similar improvements to ct
single ct of the same ratio and voltage capability. voltage capabilities can be achieved as illustrated in
Each ct only has to develop one half the excitation Figure 7 by using two identical toroidal cts with
voltage for a given fault current that a single ct must parallel secondary windings. Twice the ratio of a
develop. Therefore, with the series connection, the single ct is required when paralleling two secondary
fault current that can be transformed accurately will be windings so that the current to the relay load will be
about twice the fault current accurately transformable the same as that developed by a single ct. There is an
with a single ct. If the series connection utilized cts advantage to using this two ct connection as long as the
with twice the ratio but the same voltage capability as higher ratio cts have a higher voltage capability than
the single ratio ct, the fault current that can be the single ct. If the higher ratio cts have twice the
accurately transformed will be approximately four times voltage capability of a single ct, the fault current
that of the single ratio ct. Also, if the series that can be accurately transformed is approximately
connection utilized cts with twice the ratio and twice twice that of the single ct as shown in Figure 7b.
the voltage capability of the single ratio ct, the fault Also, if the two ct connection uses cts with four times
current that can be accurately transformed will be the ratio and twice the voltage capability of the single
approximately eight times that of a single ratio ct. ct, the fault current that could be transformed
Figure 6 illustrates these ct voltage capability accurately would be approximately four times that of a
enhancements. single ct as illustrated in Figure 7c.
157
I the rated voltage capability, the burden cannot exceed
about 0.01 ohms. A realistic burden in the range of
0.5-0.75 ohms will cause severe saturation of the ct.
{/,1s-A
20A, 'o_A., 4.16Kv 3SOMVA Swltchwu Bu8
so1s 1001s
c10 a
o
1001s
Sole-CTs for Motor
QO Protection
Single ct
I Two identical cts
rJ I I-800A
with
secondaries
parallel
and
twice the ratio and
2001s
vol tage capabi 1 i ty
of the single ct. A viable solution to the problem caused by using
CZO
low ratio cts with high fault currents requires two sets
Two identical cts of cts as illustrated in Figure 9. Presuming ground
wi t h para1 le1
secondaries and
2001s four times the
C20
ratio but only
twice the voltage
capabi 1 i ty of a
single ct
STAllON SERVICE
PERFORMANCE CHARACTERISTIC EVALUATION CONSIDERATIONS
TRANSFORMER
The choice of .atechniaue to evaluate overcurrent
performance characteristics of a ct and the associated
relay combination is strongly influenced by the
magnitude of the current, the ct relaying accuracy
rating, and its secondary burden. These three factors
directly influence the volt ampere requirements of the
test current source.
Depending on the power and economic resources
available, there are several evaluation techniques that
can be used. In descending order of volt ampere
requirements (and cost) these are:
350 MVA 4.16kV
(a) Full Scale Tests
(b) Lower Power Secondary Shunt Connected Tests
FIG. 10 Simplified Single Line of Higher Speed (c) Analog Model ing
Backup Phase Overcurrent Re1 ay Scheme for (d) Digital Computer Simulation Methods
4.16kV Switchgear
It is required that the tests evaluate the effects
Another possible consideration for existing of magnetic remanence in the ct core. There are several
switchgear installations is to replace the low ratio cts ways a ct can become magnetized leaving remanent in the
on a feeder with higher ratio cts selected for the core. One common cause is polarity testing using a
maximum fault and burden. Refer to Figure 11 which battery. Remanence can affect the ct performance later
illustrates such an arrangement. The instantaneous if the initial direction of the primary fault current
relays will utilize the main cts but the overcurrent drives the core flux in the same polarity as its
re1 ays and metering must use step-up auxi 1 iary cts remanent magnetization. It may become saturated and
connected to the high ratio cts to regain sensitivity. provide a distorted current to the relay. Therefore,
When the secondary burden on the step-up auxiliary ct is the test facility must have a means to demagnetize the
reflected to its primary winding this burden is equal to ct before test as well as to produce a known amount of
remanent flux in the core to evaluate the effects.
4.l6 kV 350 HVA BUS Full Scale Tests
Volt AmDere Reauirements: The performance of a
1-30 CIM? current transformer and any associated protective re1 ays
under conditions of extreme overcurrent is best
evaluated by full scale high current tests. These tests
are usually performed at a high power testing laboratory
such as used for testing power circuit breakers for
interrupting capacity. A properly designed full scale
test can provide the most accurate results because, to
a large degree, it eliminates distortion of the primary
current waveform by the non-linear behavior of the ct.
Eliminating distortion is accomplished in full scale
testing by insuring that the test source impedance is
lault current linear and is very much larger than the primary linear
is limited impedance of the unsaturated ct, including the reflected
L-1 secondary and burden impedances. This imp1 ies also that
the source must develop enough voltage to drive the
required primary current through its source impedance.
Figure 12 shows a schematic diagram illustrating the
test circuit requirements.
The dual requirements, high voltage and high
FIG. 11 Auxiliary CT Used with High Ratio Main CT current, for the source define its volt-ampere rating.
to Provide Sensitive Overload Protection and This volt-ampere rating can be quite large, even for
Metering testing small low ratio cts.
159
C I rcui t the test circuit must have the capability o f producing
Breaker a control 1 ab1 e dc component.
r PIT--?
Small Reactor
Smal=ac tor/
Contactor The current amplifier is the limiting factor in
this scheme. It must develop sufficient output power to
CT drive the actual desired instantaneous secondary current-
LOW r through the actual relay burden. A1 though suitable
Voltage AC Relay amplifiers have been developed and can be obtained, they
are very costly and require an equally large power
Source source for operation. For example, to perform the test
on the 50/5 ct shown in Figure 13 the amplifier would
need to deliver a peak current o f about 1250 amperes
through an impedance of .05 ohm. This i s an
Shunt Shunt instantaneous power of 78 kilowatts.
Therefore, the switch closes when the area Equation (IO) can be expressed in multiples of a
represents the total flux change of 28 . The switch
remains closed for the remainder of the hglf cycle until rated current by letting V , = M V , , and V = M V , where
the current goes to zero and reverses. V , , is the peak secondary voltage when rited Surrent is
applied to the transformer. With these substitutions,
The assumption that no magnetizing current flows equation (10) becomes:
when the switch is open is justified because the ratio ( V I / V 1 1 ) = N = (2Ms(M - MS/2) I 0.5
current is very high in comparison to the magnetizing (11)
163
Equation (11) is plotted in Figure 21 along with The secondary current remains zero until the
the resulting voltage waveforms at various multiples of primary current. reverses. At this point the area
rated current. decreases and there is again a rate.of change of flux
and ratio current then switches from magnetizing current
As shown in Figure 21, an input of (M /2) produces to secondary current. Figure 23 shows the saturated
a sine wave output with a volt-time area Jqual to that secondary current and the flux without the primary
of the transformer core. When the input is M , the current superimposed to emphasize the form o f secondary
output exists for 90 degrees of the sine wave a%d the current and it‘s relation to the flux.
last linear peak occurs. When the input exceeds M , the L
volt-time area occurs in less than 90 degrees at?d the
peak output volts follows the parabola described by
equation (IO).
A simple BASXCA PC program listed below provides
a convenient demonstration of the volt-time concept of
ct saturation for a resistive burden. The program
assumes that the magnetizing leg is’a volt-time switch
and that at saturation all ratio current switches to
magnetizing current as indicated in Figure 21.
The user enters the number of cycles to be
plotted, a fault current, fault closing angle, and the FIG. 23 Graph of Figure 22 with Primary I Omitted
impedance angle of the primary fault circuit. The
current is entered in per unit of ct rating. The user
then enters the symnetrical current at which saturation This example is not as severe a case as can occur
occurs in per unit of ct rating. The residual flux may with low ratio and extremely high fault current, but was.
also be entered in per unit of the saturation flux. A shown to clearly illustrate the form of current produced
scale factor for the plot is then entered to complete by ct saturation. In more typical cases, the secondary
the input data. current becomes no more then a high current pulse each
half cycle. Such cases can be studied using the program
For example, assume that 20 per unit current flows given in Appendix A.
in a ct which will saturate with 5 per unit current and
that current was last interrupted with maximum negative
residual flux. To study this case, enter the following CONCLUSIONS
data:
No. of cycles------------------------?:4 This paper offers solutions to the basic hazard of
per unit current---------------------?:20 failure to trip when using low ratio cts on systems with
Closing angle------------------------?:go high fault levels such as exist in power plants and
Circuit impedance angle--------------?:85 industrial plants in metal-clad switchgear. The
Per unit to saturate-----------------?:5 conflict between large ct core size requirements and
Per unit residual flux---- -- - ------ --?: - 5 switchgear space 1 imitations reduces the relaying
P1 ot vertical scale factor--- -- ---- -- ?:lo accuracy at these installations to less than what is
required for adequate protect_ion at high fault current
The program then produces a plot, as shown in levels.
Figure 22, of the primary current, core flux and the
secondary current all plotted to the same scale. To do The selection of cts based solely on load and
this the program determines the area of the per unit overload currents can result in inadeauate relay
voltage at which saturation occurs. Since a resistive protection for the facility.
burden is assumed, the perunit current and the voltage
drop across it are numerically equal. The volt-time The following i s offered to guide the application
area is plotted as the flux which accumulates until it engineer in minimizing this problem.
equals the volt-time area determined by the symmetrical
current at which saturation occurs. At this point the 1. For new relay installations, apply high ratio cts
flux becomes fixed and the secondary current goes to near the bus connection for energizing instantaneous
zero since there is no longer a rate of change of flux. relays. Use low ratio cts for metering and overcurrent
Here all ratio current switches t o magnetizing Current protection downstream from and as near to the high ratio
which flows in a zero ohm magnetizing impedance. cts as feasible. The performance of selected ct and
relay settings should be confirmed for the maximum
asymmetric fault current by means of ct performance
application guides or calculation .
A conservative 1 imiting condition would be for
this maximum fault current not to exceed 20 times the
selected ct current rating with the total secondary
external burden not greater than the ct’s standard
burden rating.
2. For existing installations where it is not
feasible to install an additional set of high ratio cts,
the following changes will improve the present
performance.
a. When the present cts are marginal, replace them
with cts selected for maximum fault current and
burden. Supply the instantaneous relays from
FIG. 22 Graph of CT Performance for Example Input these cts and the metering and overcurrent relays
164
-
165